Академический Документы
Профессиональный Документы
Культура Документы
Contents
1.
2.
3.
PRODUCT ......................................................................................................................................................... 4
1.1. MODELS LIST....................................................................................................................................... 4
1.2. NOMENCLATURE ................................................................................................................................ 5
1.3. FUNCTION............................................................................................................................................. 5
1.4. PRODUCT DATA .................................................................................................................................. 6
1.4.1. Product Data at Rated Condition ............................................................................................ 6
1.4.2. Operation Range ..................................................................................................................... 17
1.4.3. Electrical Data.......................................................................................................................... 18
1.5. PIPING DIAGRAM .............................................................................................................................. 19
1.5.1. Cooling Only ............................................................................................................................ 19
1.5.2. Heat Pump ............................................................................................................................... 20
CONTROL........................................................................................................................................................ 21
2.1. OPERATION FLOWCHART.............................................................................................................. 21
2.1.1. Cooling/Dry Operation............................................................................................................ 21
2.1.2. Heating Operation ................................................................................................................... 22
2.2. MAIN LOGIC........................................................................................................................................ 23
2.2.1. Cooling...................................................................................................................................... 23
2.2.2. Dry Mode .................................................................................................................................. 25
2.2.3. Heating Mode .......................................................................................................................... 26
2.2.4. Defrosting ................................................................................................................................. 28
2.2.5. Fan Mode ................................................................................................................................. 30
2.3. WIRELESS REMOTE CONTROLLER ............................................................................................ 30
2.3.1. Operation View ........................................................................................................................ 30
2.3.2. Display View............................................................................................................................. 32
2.4. WIRED REMOTE CONTROLLER ................................................................................................... 33
2.4.1. Operation View ........................................................................................................................ 33
2.4.2. Display View............................................................................................................................. 34
2.4.3. Dimension ................................................................................................................................ 35
2.4.4. Installation ................................................................................................................................ 35
2.5. CENTRALIZED CONTROLLER ....................................................................................................... 36
2.5.1. Centralized Controller-not with week timer ......................................................................... 36
2.5.2. Centralized Controller-week timer ........................................................................................ 38
2.5.3. Field Setting ............................................................................................................................. 41
2.5.4. Control Wiring Design............................................................................................................. 42
INSTALLATION ............................................................................................................................................... 44
3.1. INDOOR UNIT INSTALLATION ........................................................................................................ 46
3.1.1. Installation Site ........................................................................................................................ 46
3.1.2. Dimension Data ....................................................................................................................... 46
3.1.3. Installation Clearance Data.................................................................................................... 48
3.1.4. Drain Piping Work ................................................................................................................... 48
3.2. OUTDOOR UNIT INSTALLATION.................................................................................................... 49
4.
1. PRODUCT
1.1. MODELS LIST
Capacity
Class
Model Name
kW/Ton
Cooling
Heating
CFGR20/B-G
20/5.69
23/6.54
CFG20/B-G
20/5.69
CFGR25/B-G
25/7.11
28/7.96
CFG25/B-G
25/7.11
CFGR30/B-G
30/8.53
33/9.38
CFG30/B-G
30/8.53
CFGR40/B-G
40/11.37
43/12.23
Appearance
Ref.
Outdoor
Indoor
R22
Duct Type
R22
CFG40/B-G
40/11.37
CFGR50/
B(2)-G
50/14.22
53/15.07
CFG50/B(2)-G
50/14.22
/
R22
CFGR60/
B(2)-G
60/17.06
64/18.20
CFG60/B(2)-G
60/17.06
CFGR55/B-G
55/15.64
60/17.06
CFG55/B-G
55/15.64
/
R22
CFGR65/B-G
65/18.48
70/19.90
CFG65/B-G
65/18.48
1.2. NOMENCLATURE
CFG
Supplementation code
Control method
Frequency conversion system
Static pressure type
Cooling capacity
Product type
CARDIFF Air-duct air supply
Meaning of standard model before/
Meaning
CFG
Unit type
Cooling capacity
Static pressure
type
Frequency
Control
conversion
method
system
Fixed
Routine
frequency-omitte -omitted
d
Frequency
Remote
conversion-P
monitoringY
Heat pump
High static
auxiliary electric
pressure-H
heat type-R
Auxiliary hot water
The outdoor unit is
not expressed.
plate and pipe
type-W
Meaning of supplementation code after /
Meaning Design No. Refrigerant
Production
Power type
method
R22-omitted
Self-control-omitte 3N~ 380v-G
Expression Arranged
method
based on A, R407-N
d
(The unit to be
B, C
exported must be
expressed)
R410a-Na
Others to be
applied for when
they are used
1.3. FUNCTION
Function
Serenity
Description
Special structure design makes the extremely low noise during the running of the unit.
Efficient National energy-saving certificate has been gained and the energy-saving level has
Energy-saving reached the peak in this field.
Max. length of connecting pipe between the indoor unit and the outdoor unit can be 70m
Agile
and its drop can be 30m. External static pressure of the indoor unit can be customized
Application
according to the requirement of the customer.
Indoor
Unit
Models
20
Nominal Capacity
At Rated ESP
Heating
Power Supply
Unit
20
25
30
Btu/h
68243
85304
102360
kW
20
25
30
Btu/h
78479
95540
112601
kW
23
28
33
V/Ph/Hz
Cooling
Power Consumption
kW
Heating
Cooling
Running Current
Heating
380/3/50
8.5
10.2
12.1
6.8
8.7
11.1
15.8
18.9
21.8
13.5
16.8
18.3
Refrigerant Type
R22
Refrigerant Charge
kg
Power Supply
V/Ph/Hz
12
380/3/50
Type
2354
2825
3237
m /h
4000
4800
5500
Input Power
1.1
1.1
1.5
Running Current
2.8
3.0
3.6
in.wg
0.36
0.36
0.52
Pa
90
90
130
Air flow
Fan
30
CFGR/B-G(O)
Outdoor
Cooling
25
Rated ESP
Fan Motor Protection
Sound Pressure Level
Indoor Unit
(H/M/L/SL)
dB(A)
Overload protection
54
54
57
Material
Diameter
mm
Material
No.of Rows/FPI
3/16
3/16
5/16
Sqm
0.59
0.66
0.66
Tube
Coil
Fin
Coil Area
Dimensions
(Outline/Package)
9.52
Aluminum
Height
Width
9.52
500/673
mm
1500/1840
Depth
1000/1200
Weight(Net/Gross)
kg
130/180
150/200
170/220
Condensate Drainage(O.D)
mm
25.4
Air Filter
CFGR/B-G(I)
Indoor
Unit
Models
20
25
CFGR/B-G(O)
Outdoor
Unit
Power Supply
20
25
V/Ph/Hz
Compressor
Scroll
A
L.R.A
12.5
15.8
17.6
95
110
110
Vibration Isolator
Rubber
Protection Device
Fan Type/Drive
Fan Speed
Fan
rpm
660
730
Blade Material
Outdoor Unit
Diameter
mm
750
(Outline/Package)
Aluminum
1/16
2/15
2/15
Coil Area
Sqm
2.2
2.1
2.4
dB(A)
61
66
67
Height
Width
990/1162
mm
880/980
Depth
Weight(Net/Gross)
Pipe sizes
750
No.of Rows/FPI
Dimension
750
Material
Fin
730
Plastic
Tube Material
Coil
30
380/3/50
Compressor Type
Nominal Current
30
Suction
Liquid
1772/1950
kg
Inch
200/250
230/260
1-1/8"
5/8"
250/280
CFG/B-G(I)
Indoor
Unit
Models
20
Nominal Capacity
At Rated ESP
Heating
Power Supply
Unit
20
25
30
Btu/h
68243
85304
102360
kW
20
25
30
Btu/h
kW
V/Ph/Hz
Cooling
Power Consumption
kW
Heating
Cooling
Running Current
Heating
380/3/50
8.5
10.2
12.1
15.8
18.9
21.8
Refrigerant Type
R22
Refrigerant Charge
kg
Power Supply
V/Ph/Hz
12
380/3/50
Type
2354
2825
3237
m /h
4000
4800
5500
Input Power
1.1
1.1
1.5
Running Current
2.8
3.0
3.6
in.wg
0.36
0.36
0.52
Pa
90
90
130
Air flow
Fan
30
CFG/B-G(O)
Outdoor
Cooling
25
Rated ESP
Fan Motor Protection
Sound Pressure Level
Indoor Unit
(H/M/L/SL)
dB(A)
Overload protection
54
54
57
Material
Diameter
mm
Material
No.of Rows/FPI
3/16
3/16
5/16
Sqm
0.59
0.66
0.66
Tube
Coil
Fin
Coil Area
Dimensions
(Outline/Package)
9.52
Aluminum
Height
Width
9.52
500/673
mm
1500/1840
Depth
1000/1200
Weight(Net/Gross)
kg
130/180
150/200
170/220
Condensate Drainage(O.D)
mm
25.4
Air Filter
CFG/B-G(I)
Indoor
Unit
Models
20
25
CFG/B-G(O)
Outdoor
Unit
Power Supply
20
25
V/Ph/Hz
Compressor
Scroll
A
L.R.A
12.5
15.8
17.6
95
110
110
Vibration Isolator
Rubber
Protection Device
Fan Type/Drive
Fan Speed
Fan
rpm
660
730
Blade Material
Outdoor Unit
Diameter
mm
750
(Outline/Package)
Aluminum
1/16
2/15
2/15
Coil Area
Sqm
2.2
2.1
2.4
dB(A)
61
66
67
Height
Width
990/1162
mm
880/980
Depth
Weight(Net/Gross)
Pipe sizes
750
No.of Rows/FPI
Dimension
750
Material
Fin
730
Plastic
Tube Material
Coil
30
380/3/50
Compressor Type
Nominal Current
30
Suction
Liquid
1772/1950
kg
Inch
200/250
230/260
1-1/8"
5/8"
250/280
CFGR/B-G(I)
Indoor
Unit
Models
40
Nominal Capacity
At Rated ESP
Heating
Power Supply
Unit
40
55
65
Btu/h
136490
187669
221790
kW
40
55
65
Btu/h
146722
204730
238851
kW
43
60
70
V/Ph/Hz
Cooling
Power Consumption
kW
Heating
Cooling
Running Current
Heating
380/3/50
17
21.5
27.5
14
19.5
22.8
31.9
40.4
51.6
27.3
38
44.3
Refrigerant Type
R22
Refrigerant Charge
kg
Power Supply
13.2
V/Ph/Hz
17
19
380/3/50
Type
4120
5297
6474
m /h
7000
9000
11000
Input Power
kW
2.2
3.0
3.3
Running Current
4.5
8.4
in.wg
0.52
0.64
0.64
Pa
130
160
160
Air flow
Fan
65
CFGR/B-G(O)
Outdoor
Cooling
55
Rated ESP
Fan Motor Protection
Sound Pressure Level
Indoor Unit
(H/M/L/SL)
dB(A)
Overload protection
58
60
62
Material
Diameter
mm
Material
No.of Rows/FPI
4/16
4/16
4/16
Sqm
0.81
0.96
1.22
650/835
700/885
850/1040
1700/1890
1900/2090
1900/2090
1100/1460
1100/1460
1100/1460
200/250
230/280
250/300
Tube
Coil
Fin
Coil Area
Dimensions
(Outline/Package)
Height
Width
mm
Depth
9.52
9.52
Aluminum
Weight(Net/Gross)
kg
Condensate Drainage(O.D)
mm
25.4
Air Filter
CFGR/B-G(I)
Indoor
Unit
Models
40
Power Supply
40
V/Ph/Hz
Compressor
29.6
37.9
168
225
272
Rubber
Protection Device
Fan Type/Drive
730
Blade Material
Outdoor Unit
Diameter
mm
(Outline/Package)
730
750
750
No.of Rows/FPI
Dimension
750
Material
Fin
730
Plastic
Tube Material
2/15
2/15
2/15
Coil Area
Sqm
2.8
4.2
4.8
dB(A)
69
70
71
Height
Width
mm
Depth
Weight(Net/Gross)
Pipe sizes
25.6
Vibration Isolator
Fan Speed
Coil
65
Scroll
L.R.A
Fan
55
380/3/50
Compressor Type
Nominal Current
65
CFGR/B-G(O)
Outdoor
Unit
55
Suction
Liquid
kg
Inch
1772/1890
1760
1290/1460
1980
880
920
200/250
550/580
550/580
1-3/8"
1-5/8"
5/8"
7/8"
CFG/B-G(I)
Indoor
Unit
Models
40
Nominal Capacity
At Rated ESP
Heating
Power Supply
Unit
40
55
65
Btu/h
136490
187669
221790
kW
40
55
65
Btu/h
kW
V/Ph/Hz
Cooling
Power Consumption
kW
Heating
Cooling
Running Current
Heating
380/3/50
17
21.5
27.5
31.9
40.4
51.6
Refrigerant Type
R22
Refrigerant Charge
kg
Power Supply
13.2
V/Ph/Hz
17
19
380/3/50
Type
4120
5297
6474
m /h
7000
9000
11000
Input Power
kW
2.2
3.0
3.3
Running Current
4.5
8.4
in.wg
0.52
0.64
0.64
Pa
130
160
160
Air flow
Fan
65
CFG/B-G(O)
Outdoor
Cooling
55
Rated ESP
Fan Motor Protection
Sound Pressure Level
Indoor Unit
(H/M/L/SL)
dB(A)
Overload protection
58
60
62
Material
Diameter
mm
Material
No.of Rows/FPI
4/16
4/16
4/16
Sqm
0.81
0.96
1.22
650/835
700/885
850/1040
1700/1890
1900/2090
1900/2090
1100/1460
1100/1460
1100/1460
200/250
230/280
250/300
Tube
Coil
Fin
Coil Area
Dimensions
(Outline/Package)
Height
Width
mm
Depth
9.52
9.52
Aluminum
Weight(Net/Gross)
kg
Condensate Drainage(O.D)
mm
25.4
Air Filter
CFGR/B-G(I)
Indoor
Unit
Models
40
Power Supply
40
V/Ph/Hz
Compressor
29.6
37.9
168
225
272
Rubber
Protection Device
Fan Type/Drive
730
Blade Material
Outdoor Unit
Diameter
mm
(Outline/Package)
730
750
750
No.of Rows/FPI
Dimension
750
Material
Fin
730
Plastic
Tube Material
2/15
2/15
2/15
Coil Area
Sqm
2.8
4.2
4.8
dB(A)
69
70
71
Height
Width
mm
Depth
Weight(Net/Gross)
Pipe sizes
25.6
Vibration Isolator
Fan Speed
Coil
65
Scroll
L.R.A
Fan
55
380/3/50
Compressor Type
Nominal Current
65
CFGR/B-G(O)
Outdoor
Unit
55
Suction
Liquid
kg
Inch
1772/1890
1760
1290/1460
1980
880
920
200/250
550/580
550/580
1-3/8"
1-5/8"
5/8"
7/8"
CFGR/B-G(I)
Indoor
Unit
Models
50
60
CFGR/B-G(O)
Outdoor
Cooling
Nominal Capacity
At Rated ESP
Heating
Power Supply
Unit
50
60
Btu/h
170610
204730
kW
50
60
Btu/h
180844
218378
kW
53
64
V/Ph/Hz
Cooling
Power Consumption
kW
Heating
Cooling
Running Current
Heating
380/3/50
20.7
24.5
17.7
20.5
38.9
46
34.5
39.9
Refrigerant Type
R22
Refrigerant Charge
kg
Power Supply
28.0
V/Ph/Hz
380/3/50
Type
5297
6474
m /h
9000
11000
Input Power
3.3
3.3
Running Current
8.4
in.wg
0.64
0.64
Pa
160
160
Air flow
Fan
212.0
Rated ESP
Fan Motor Protection
Sound Pressure Level
Indoor Unit
(H/M/L/SL)
dB(A)
Overload protection
60
62
Material
Diameter
mm
Material
No.of Rows/FPI
4/16
4/16
Sqm
0.96
1.22
700/885
850/1040
1900/2090
1900/2090
1100/1460
1100/1460
230/280
250/300
Tube
Coil
Fin
Coil Area
Dimensions
(Outline/Package)
Height
Width
mm
Depth
9.52
Aluminum
Weight(Net/Gross)
kg
Condensate Drainage(O.D)
mm
24.5
Air Filter
CFGR/B-G(I)
Indoor
Unit
Models
50
CFGR/B-G(O)
Outdoor
Unit
Power Supply
50
V/Ph/Hz
Compressor
Scroll
A
L.R.A
217.6
2110
2110
Rubber
Protection Device
Fan Type/Drive
730
Blade Material
Outdoor Unit
Diameter
mm
750
No.of Rows/FPI
2/15
2/15
Coil Area
Sqm
22.1
22.4
dB(A)
70
71
Dimension
Height
(Outline/Packag
Width
e)
Depth
Weight(Net/Gross)
Pipe sizes
750
Material
Fin
730
Plastic
Tube Material
Coil
215.8
Vibration Isolator
Fan Speed
Fan
60
380/3/50
Compressor Type
Nominal Current
60
Suction
Liquid
1772/1950
mm
990/1162
880/980
kg
Inch
200/250
21-1/8"
25/8"
CFG/B-G(I)
Indoor
Unit
Models
50
60
CFG/B-G(O)
Outdoor
Cooling
Nominal Capacity
At Rated ESP
Heating
Power Supply
Unit
50
60
Btu/h
170610
204730
kW
50
60
Btu/h
kW
V/Ph/Hz
Cooling
Power Consumption
kW
Heating
Cooling
Running Current
Heating
380/3/50
20.7
24.5
38.9
46
Refrigerant Type
R22
Refrigerant Charge
kg
Power Supply
28.0
V/Ph/Hz
380/3/50
Type
5297
6474
m /h
9000
11000
Input Power
3.3
3.3
Running Current
8.4
in.wg
0.64
0.64
Pa
160
160
Air flow
Fan
212.0
Rated ESP
Fan Motor Protection
Sound Pressure Level
Indoor Unit
(H/M/L/SL)
dB(A)
Overload protection
60
62
Material
Diameter
mm
Material
No.of Rows/FPI
4/16
4/16
Sqm
0.96
1.22
700/885
850/1040
1900/2090
1900/2090
1100/1460
1100/1460
230/280
250/300
Tube
Coil
Fin
Coil Area
Dimensions
(Outline/Package)
Height
Width
mm
Depth
9.52
Aluminum
Weight(Net/Gross)
kg
Condensate Drainage(O.D)
mm
24.5
Air Filter
CFG/B-G(I)
Indoor
Unit
Models
50
60
CFG/B-G(O)
Outdoor
Unit
Power Supply
50
60
V/Ph/Hz
380/3/50
Compressor Type
Scroll
Nominal Current
Compressor
L.R.A
217.6
2110
2110
Vibration Isolator
Rubber
Protection Device
Fan Type/Drive
Fan Speed
Fan
rpm
730
730
Blade Material
Plastic
Outdoor Unit
Diameter
mm
Tube Material
Coil
215.8
750
750
Material
Fin
Aluminum
No.of Rows/FPI
2/15
2/15
Coil Area
Sqm
22.1
22.4
dB(A)
70
71
Dimension
Height
(Outline/Packag
Width
e)
Depth
1772/1950
mm
880/980
Weight(Net/Gross)
kg
Suction
Pipe sizes
990/1162
200/250
21-1/8"
Inch
Liquid
25/8"
Heating
Outdoor
DB27(80.6)
DB35(95)
WB19(66.2)
WB/(/)
DB20(68)
DB7(44.6)
WB/(/)
WB6(42.8)
Piping Length
32/23
43/26
Min. Cooling
21/15
21/15
Max. Heating
27/-
24/18
Min. Heating
20/-
-5/-6
Fan Motor
Max. Fuse
Min.
Breaker Size
Disconnect Size
(Indoor/Outdoor) (Indoor/Outoor)
Model
Power
Supply
Qty.
RLA
LRA
Condenser
Fan Motors
Supply
Blower
Motor
Amperes
Amperes
VPhHz
Each
Each
FLA Each
FLA Each
CFGR20/B-G
380,3,50
16.4
95
1.5
2.89A
38.4/6.5
22/3.62
CFG20/B-G
380,3,50
16.4
95
1.5
2.89
38.4/6.5
22/3.62
CFGR25/B-G
380,3,50
19.2
110
2.5
2.89
45.7/6.5
26.5/3.62
CFG25/B-G
380,3,50
19.2
110
2.5
2.89
45.7/6.5
26.5/3.62
CFGR30/B-G
380,3,50
22.1
110
2.5
3.7
52.22/8.33
30.13/4.63
CFG30/B-G
380,3,50
22.1
110
2.5
3.7
52.22/8.33
30.13/4.63
CFGR40/B-G
380,3,50
26.9
168
2.5
5.16
63.02/11.61
36.13/6.45
CFG40/B-G
380,3,50
26.9
168
2.5
5.16
63.02/11.61
36.13/6.45
CFGR50/B(2)-G
380,3,50
219.2 2110
2x2.5
6.78
91.4/15.26
53/8.48
CFG50/B(2)-G
380,3,50
219.2 2110
2x2.5
6.78
91.4/15.26
53/8.48
CFGR60/B(2)-G
380,3,50
222.1 2110
2x2.5
6.78
104.45/15.26
60.25/8.48
CFG60/B(2)-G
380,3,50
222.1 2110
2x2.5
6.78
104.45/15.26
60.25/8.48
CFGR55/B-G
380,3,50
34
225
2x2.5
6.78
81.5/15.26
47.5/8.48
CFG55/B-G
380,3,50
34
225
2x2.5
6.78
81.5/15.26
47.5/8.48
CFGR65/B-G
380,3,50
41.4
272
2x2.5
6.78
98.15/15.26
56.75/8.48
CFG65/B-G
380,3,50
41.4
272
2x2.5
6.78
98.15/15.26
56.75/8.48
Notes
RLARated load amperes
LRALocked rotor amperes
FLAFull load current
2. CONTROL
2.1. OPERATION FLOWCHART
2.1.1. Cooling/Dry Operation
CONTROL
CONTROL
CONTROL
Cooling Mode
ON
Manually OFF
ON
Compressor
OFF
OFF
ON
Outer Fan
OFF
Inner Fan
OFF
way Valve
OFF
OFF
ON
OFF
Time
When Tamb Tset 1,cooling mode will be entered. In that case, compressor, outer
fan and inner fan will run; Outer fan will firstly run for 15s and then, the compressor will
start running.
When Tamb Tset1,The unit will be in cooling Off status. Compressor and outer fan
will stop running but inner fan will run. The compressor will firstly stop running and 15s
later, the outer fan will stop.
When Tamb=Tset, compressor and outer fan keep the previous running status while the
indoor fan is running.
CONTROL
Cooling Mode
ON
Manually OFF
ON
Compresspor
OFF
Outer Fan
OFF
Compressor
OFF
Outer Fan
OFF
OFF
ON
OFF
ON
ON
Inner Fan
OFF
way
Valve
OFF
way
Valve
OFF
OFF
ON
OFF
Time
When the unit is on, if TambTset+ 1, the unit will run at cooling mode and inner fan runs
at setting speed. Outer fan firstly runs for 15s and then compressor A starts. When
compressor A runs for 15s, outer fan B will start running and 15s later, compressor B
starts.
During the running of the unit, every 6min, the unit will execute specific operation on the
below condition:
When Tamb Tset-1, compressor A will be Off and 15s later, outer fan A will be Off;
Inspection will be executed after 6 min. If the TambTser- 1, compressor B will be Off and
15s later, out fan B will be Off.
When TambTset+ 1, outer fan firstly runs for 15s and then compressor A will be On;
Inspection will be executed after 6min. If Tamb Tset+ 1, Outer fan B will firstly start
running and 15s later, compressor B will be On.
CONTROL
Compressor
OFF
Outer Fan
OFF
Manually
OFF
OFF
ON
Inner Fan
OFF
way
Valve
OFF
OFF
ON
OFF
Time
When Tamb Tset2, cooling mode will be entered. In that case, compressor, outer
fan and inner fan will run. Outer fan will firstly run and 15s later, compressor will start.
When Tset2TambTset2, compressor and outer fan will run for 6min, and then
stop for 4min, which will be circularly executed, while the inner fan is running.
When Tamb Tset-2 , compressor and outer fan will stop running. In that case,
compressor will firstly stop and 15s later, outer fan will stop.
CONTROL
Manually OFF
ON
Compressor
OFF
OFF
ON
Outer Fan
OFF
Inner Fan
OFF
Auxiliary
Heater
OFF
way
Valve
OFF
OFF
ON
OFF
ON running in specific
OFF
condition
ON
OFF
Time
When Tamb- TcomTset-1, heating mode will be entered. In that case, reversal valve,
outer fan and compressor will be energized to run while inner fan will run at cold-blast air
proof mode. At that time, outer fan will firstly run. 1s later, compressor will run and 20s
later after that, 4-way valve will run.
When Tamb-TcomTset, compressor, reversal valve and outer fan keep previous status
while inner fan is running.
When Tamb-TcomTset1, Compressor and outer fan stop running, reversal valve is
still energized and inner fan runs at blowing surplus heat mode (in that case, inner fan has
to keep running to avoid heat accumulation inside air duct.). At that time, compressor
stops firstly and 15s later, outer fan stops running.
CONTROL
Heating Mode
ON
M anually OFF
ON
Outer Fan
O FF
Compressor
O FF
OFF
ON
OFF
ON
way
Valve
O FF
Outer Fan
O FF
OFF
ON
OFF
ON
Com pressor
O FF
OFF
ON
way
Valve
O FF
Inner Fan
O FF
Auxiliary
Heater
O FF
O FF
ON
OFF
ON
Running in
specific condition
OFF
Time
Cold-blast Air Proof
When the unit is turned on: if Tamb-TcomTset-1, Inner fan will run at setting speed
and cold-blast air proof mode. Outer fan will firstly run and 1s later, compressor A will
run and 20s later after that, 4-way valve will run; 15s later after startup of 4-way valve,
outer fan B will run, and 1s after that, compressor B will start. 20s later after startup of
compressor B, 4-way valve will run.
During the running of the unit, every 6min, the unit will execute specific operation on the
below condition:
When Tset-1Tamb-TcomTset+1, compressor, reversal valve and outer fan keep the
previous running status while inner fan runs at setting speed.
When Tamb-TcomTset+1,compressor A will be OFF. 15s later, outer fan A will be OFF
while reversal valve will still be energized; Inspection will be executed after 6min, if
Tamb-TcomTset+1, compressor B will be OFF.15s later, outer fan B will be OFF while
reversal valve will be still energized and inner fan will run at setting speed and blowing
surplus heat(In that case, inner fan has to keep running to avoid heat accumulation inside
air duct.
When Tamb-TcomTset-1, outer fan will firstly run and 1s later, compressor A will run;
Inspection will be executed 6min later, if Tamb-TcomTset-1, outer fan B will run and
1s later, compressor B will run.
CONTROL
2.2.4. Defrosting
2.2.4.1. Single System
Defrosting Mode
Enter
Exit
ON
Compressor
ON
Outer Fan
ON
OFF
ON running at
ON
OFF
Inner Fan
setting speed
ON
Auxiliary
Heater
ON
way
Valve
ON
ON
OFF
Time
Cold-blast Air Proof
Conditions of Defrosting ON
After accumulated heating time reaches 44min, if detect that Tcon. 5 for 1min,
defrosting will start. At that time, reversal valve, outer fan and auxiliary electric heater will
stop running, compressor will compulsive run, and inner fan will run at cold-blast air proof
mode ( inner fan is not ON when defrosting. When defrosting has finished and Teva.35
or Time45s, inner fan start running.
Conditions of Defrosting OFF
When defrosting has been executed for 10min, or Tcon. 10 exists for 1s,
defrosting will finished, and reversal valve and outer fan will run.
When defrosting is finished, 4-way valve will be switch firstly. Reversal valve and outer fan
will run at the same time.
Conditions of Defrosting ON
After accumulated heating time of any system (such as system A) reaches 44min,if detect
that its Tcon. 5 exist for 1min, in that case:
1Detect defrosting temp. sensor of other system(such as system B). When it defrosting
temp. sensor 10 , system A will enter defrosting and system B will be in
CONTROL
standby( compressor stops and 4-way valve is energized).If system B has been in standby,
it will continue. After defrosting has been finished, the system which finishes the defrosting
will turn to heating ( 4-way valve reverses) and then, The standby system will enter
heating.
Note: The standby time do no have to wait for 6min.
2If detect that the other defrosting temp. sensor is less than 10
a.If the compressor is running at that time, both two systems will enter defrosting. The
system which finishes defrosting firstly will be in standby. After two systems have
finished defrosting, they will enter heating respectively.
b. If it is in standby, and the time of being standby 3min, the two systems will enter
defrosting at the same time. The system which is firstly finished defrosting will be in
standby. After two systems have finished the defrosting, they will enter heating
respectively.
c. If it is in standby but the time of standby 3min, the system A will firstly enter
defrosting.
(a) During defrosting of system A, if standby time of it (system B) 3min, the
system B will enter defrosting. The system which firstly finishes defrosting will
be in standby. After two systems have finished defrosting, they will enter heating
respectively.
(b)When system A has finished defrosting, if standby time of it( system B)3min,
system A will exit from defrosting. When the system B has stopped for 3min, it
will enter heating.
3When system enters defrosting mode, low pressure protection of related system will
be shielded.
4During defrosting and 3min later after defrosting is finished, inspection for temp.
sensor error of indoor evaporator of related system will be shielded.
5During defrosting, if there are other protections, they will be normally executed (but
super high temp. of indoor running of the two systems will be shielded). If the error can be
restored, after restoring the error and the compressor has stopped for 3min, it will run for
6min and then reenter defrosting.
Conditions of Defrosting OFF
(1) If only one system enters defrosting,
and this system has been in defrosting mode for 10min or Tcon. 10 exists for
1s, the defrosting of this system will be finished. This system will exit from defrosting.
(2) If both the two systems have entered defrosting,
and each system has been in defrosting mode for 10min or corresponding Tcon
10 exists for 1s, the system will finished defrosting respectively. The system which
finishes defrosting firstly will be in standby and until the other system has been finished
defrosting, they will
NoteDuring this course, there is 3min delay of compressor protection.
CONTROL
SWING
FAN
AUTO FAN
OPER
AUTO
AIR
SWING
MODE
NO.
Name
ON/OFF button
Mode button
ON/OFF
Function description
Press the button to start or close unit
Press the button to select the mode, including
cooling, heating, fan or auto mode.
Increase/Decrease button
LCD Screen
Swing button
SWING
FAN
Auto Fan
OPER
CONTROL
SWING
FAN
AUTO FAN
OPER
AUTO
AUTO
AIR
AIR
HR
HR
SLEEP
AIR
LIGHT
HUMID
MODE
ON/OFF
NO.
Name
Swing button
Increase/Decrease button
Mode button
MODE
SAVE
ON/OFF
Function description
Press this button to set swing function
Press this button to increase/decrease the setup temp
Press the button to select the mode, including
cooling, heating , fan or auto mode.
ON/OFF button
LCD Screen
Sleep button
Time on
Time off
CONTROL
SWING
FAN
AUTO FAN
OPER
AUTO
AIR
No.
Display
Fan Speed
HR
Function description
auto fan speed
middle fan speed
Auto Running
Run Mode
Dry Running
Cool Running
Fan Running
Setup temp
Swing function
Sleep mode
Sleep mode is on
Time value
OPER
Swing is on
The controller is on
CONTROL
SLEEP
TIMER
ON/OFF
NO.
Name
Function description
Press the button to select the mode,
MODE button
cooling , heating , fan or auto mode.
Increasing button
Decreasing button
Sleep button
Timer button
On/off button
Remote window
LCD display
Note:
1) MEMORY function setup: When the unit is turned off, press MODE button for 10
seconds, to switch ON/OFF of the unit after powered off.
2) Lock function: Press and at the same time for 5 seconds, the set temp. will
display EE and shield, all buttons will sound; and repress theand at the same
time for 5 seconds, the lock function will be released.(for details, please read
corresponding parts of manual).
CONTROL
MODE
SLEEP
TIMER
ON/OFF
NO.
Name
Function description
Timer value
Timer on/off
nothing displays.
4
6
7
temp
: cool mode,
: dry mode,
Frost display
Sleep display
10
Swing display
11
Error display
CONTROL
2.4.3. Dimension
2.4.4. Installation
First select an installation position. According to the size of the communication line of
the wire controller, leave a recess or an embedded wire hole to bury the
communication line.
If the communication line between the wire controller (858520) and the indoor unit
is surface-mounted, use 1# PVC pipe and make matching recess in the wall (refer to
Figure 6); If concealed installation is adopted, 1# PVC pipe can be used (Refer to
Figure 7).
Caution:
During the installation of the bottom plate of the wire controller, pay attention to the
direction of the bottom plate. The plates side with two notches must be at the lower
position, and otherwise the panel of the wire controller cannot be correctly installed.
CONTROL
PVC pipe
Name
Wall Surface
Screw M4X10
Caution:
The communication distance between the main board and the wire controller can be
as far as 20m (The standard distance is 8m).
The wire controller shall not be installed in a place where there is water drop or large
amount of water vapor.
CONTROL
NO.
Name
Function description
ON button
OFF button
LCD display
LED
LED indication
CONTROL
2.5.1.4. Dimensions
CONTROL
NO.
Name
ENTER button
Increasing button
Function description
Press the button to let setting validate.
Press and selected the unit or a certain day in one week or specific
value. Press can set week part of time.
Decreasing button
Press
CANCEL/DELET
button
certain day
SINGLLE/GROU
button
GROUP displayed
TIMER/TIME
button
On/off button
LCD display
CONTROL
NO.
Name
Function description
Timer displays
Display time
on control displays
10
11
12
13
display
Note:
Please read corresponding manual of weekly timer controller to be familiar with it.
CONTROL
2.5.2.4. Dimensions
Example 1: Code 0111means S/N 8. Rods 1,2,3 are dialed to the opposite side of ON
and rod 4 is dialed to the position ON.
Example 2: Code 1010means S/N 11. Rods 2 and 4 are dialed to the opposite side of
Position
S/N
Position
S/N
Position
S/N
Position
S/N
0000
0100
1000
1100
13
0001
0101
1001
10
1101
14
0010
0110
1010
11
1110
15
0011
0111
1011
12
1111
16
CONTROL
Unit S/N:1
0000
Unit S/N:2
0001
Unit S/N:3
0010
Unit S/N:4
0011
Unit S/N:5
0100
Unit S/N:6
0101
Unit S/N:7
0110
Unit S/N:8
0111
Unit S/N:9
1000
Unit S/N:10
1001
Unit S/N:11
1010
Unit S/N:12
1011
Unit S/N:13
1100
Unit S/N:14
1101
Unit S/N:15
1110
Unit S/N:16
1111
LCD
LCD
16 Units in Max
LC
Power supply
Twisted-wire with crystal joint
CONTROL
0000
0010
0001
0011
13
1000
1010
1001
10
1011
14
0100
0110
0101
11
0111
15
1100
1110
1101
12
1111
16
CONTROL
3. INSTALLATION
Caution for Installation
Before installation, please make sure that the selection of installation site, specification of
power supply, the application range( distance of piping, drop height between the indoor
and the outdoor and voltage of power supply) and insllation space are correct and
suitable.
There are
warnings and
serious injury which may be caused by improper installation are belong to the
warning group. However, even the items in
sometimes. Therefore, both of them are very important contents which have be to strictly
complied with.
After finishing installation, try to run it and make sure that the unit is in good conditon.
Then, introduce operation and maintenance methods to users according to operation
instruction. Besides, this cautions and operation instructions should be given to users and
suggest them keeping them well.
Warning
1Installation shall be executed by distributors of the unit or professional shop. Dont
install it by yourself or improper installation may cause leak, electric shock and
fire,etc.
2Installation has to strictly comply with installation manual. Improper installation will
cause leakage, electric shock and fire, etc.
3If install big air conditoner system in small room,the measures which prevent the l
eakage of refrigerants from exceeding limit concentration must be adopted and
should be disscused with the distributor. If proper measures are not adopted and
there is leakage of refrigerants , peoples suffocation may be caused..
4Please install it in the place which can fully withstand the weight of the unit or the
CONTROL
cable shall be applied when wiring. Please fix the joints of fixed
termination to avoid that the outside force imposed on the cable affects the
connection of the joints.Improper connection and fixation will cause generation of
heat, fire,etc.
8Wiring shall be kept correctly and dont convex. Please protect it with maintenance
board. Improper installation will cause generation of heat, fire, etc.
9When installing and removing the air conditioner, Dont interfuse air except for
indicated refrigerants. If there is air in cooling circulation system, abnormal high
pressure will be caused that will resulte in cracking and peoples injury.
Packaged parts or indicated parts shall be applied when installation. If not, water leakage,
electric shock, fire and refrigerants leakage,etc.will be resulted in.
Note:
1 Earthing must be executed. Dont connect earth line with gas pipe, water
pipe,lightning arrester or earth line of telephone. Improper earthing may cause
electric shock.
As air-conditioning unit is of Class 1 electrical appliance, reliable grounding
measures must be taken for it.
The double color (yellow and green) cable inside the unit is specially used for
grounding, so it shall not be used for other purposes nor can it be cut. Do not tighten
with tapping screws; otherwise it might cause risk of electric shock.
Installation of earth resistance should be in accordance with the national standards
CONTROL
GB17790.
The user power supply shall have reliable grounding terminal. It is prohibited to
connect the grounding wire to the following items:
Water Supply Pipe Gas Pipe Sewage Pipe Other positions that are considered
to be unreliable by professionals.
2Creepage breaker must be installed in specific sites. If not, electric shock will be
resulted in.
3Dont install it in the place which may has the leakage of flammable gas. In the
event that the leaked gas is accumulated around the unit, fire may be caused.
unitmm
Model
FG20/B-G
FGR20/B-G
FG25/B-G
FGR25/B-G
FG30/B-G
FGR30/B-G
1560
CONTROL
910
1194
1194
292
342
e
c
a
unitmm
Model
FG40/B-G
FGR40/B-G
FG50/B(2)-G FGR50/B(2)-G
FG55/B-G
FGR55/B-G
FG60/B(2)-G FGR60/B(2)-G
FG65/B-G
FGR65/G-G
1780
1040
990
295
1450
555
1980
1040
1120
1650
347
600
1980
104
1120
1650
347
755
CONTROL
Suspender
>560
>1,000
Hook
Air supply
Flat
washer
Spring
washer
Nut
installation of suspender
>1000
Air return
For easy drainage of the condensation water, It should be installed with a downward
gradient. To avoid the condensation, the connection pipe joint should be insulated with
thermal insulation material. A water seal should be employed as shown above and the
height of the water seal could be determined by the pressure of the drain hose.
Drain hose is in negative pressure state: A = BP/10+20 (mm)
Drain hose is in positive pressure state: A30mmBP/10+20 (mm)
Note: P is the absolute pressure of the drain hose position, Pa
CONTROL
Dont connect any air leading duct to the outdoor unit, at neither the air inlet nor the air
outlet. The outdoor unit will drop condensate while running at heat mode. If the temp is
minus, it will form ice. Dont let the rain proof interfere the ventilation of outdoor unit.
1772
840
880
A
B2
8442
C2
Unit: mm
Model
FG20/B-G(O) FGR20/B-G(O)
FG25/B-G(O) FG25/B-G(O)
FG30/B-G(O) FG30/B-G(O)
990
787
337
CONTROL
FG40/B-G(O) FGR40/B-G(O)
1290
1160
850
A
D2
F2
E2
Unit: mm
Model
1980
840
920
1400
460
880
1760
FG55/B-G(O)
FGR55/B-G(O)
>1000
>1200
>1000
>1000
>3000
>300
CONTROL
>300
>300
90 Number of bends
Length of connecting pipes
30M
12
70M
The pipe meld type could be employed for the connection of the pipes between the
indoor and outdoor units.
The pipe joint should be tightly connected when a pipe joint is employed between two
pipes. It is better to use only one connecting pipe if the distance is not far.
The pipes should not be shriveled when the pipes are connecting. The bend diameter
should be longer than 200 millimeter. The connecting pipes should not be extended
or curved frequently and the curving process should not be larger than 3 times in the
same bending position.
CONTROL
External
Maximum
Maximum
Diameter
Length
Difference in
of Connection
Height between
Additional
Max. Qty of
Charge of
Gas
Liquid
Pipe
Pipe
Pipe
Outdoor and
(mm)
(mm)
(m)
28
16
70
30
12
180g/m
270
230
212
2180g/m
70
30
12
350 g/m
270
230
212
2180g/m
70
30
12
350 g/m
Elbows(90 )
Refrigerant
(g/m)
FG20/B-G
FGR20/B-G
FG25/B-G
FGR25/B-G
FG30/B-G
FGR30/B-G
FG40/B-G
35
16
FG50/B(2)-G
FGR50/B(2)-G
28
16
42
22
FG60/B(2)-G
FGR60/B(2)-G
28
16
42
22
FGR40/B-G
FG55/B-G
FGR55/B-G
FG65/B-G
FGR65/B-G
2)
3)
CONTROL
cross the electric boxes. Please choose the specification of the power cables
according to the power capacity and the installation conditions of the unit. Fix the
wires with wire clamp and assemble the electric cover after confirmation.
If ON/OFF function of the sub room unit is needed, the short wiring between L3
and A should be taken off and wired according to the dashed frame. If all of the
sub rooms are turned off, the unit will be switched off, or you can turn off the unit
from the control panel directly. In the meantime, you can set the parameters on
the control panel.
The wiring schematic of the outdoor unit, please refer to Fig 32, while the power
cord standard and air-switch type, please refer to recommending table 4.
CONTROL
Minimum Sectional
Sectional Area of
Area of Power
Earth Wire(mm2)
Supply Wire(mm2)
10
1.5
1.5
380,3,50
16
2.5
2.5
FG25/B-G(I)
380,3,50
10
1.5
1.5
FGR25/B-G(I)
380,3,50
16
2.5
2.5
Power Supply
Capability of
(V,Ph,Hz)
Air Swith(A)
FG20/B-G(I)
380,3,50
FGR20/B-G(I)
Model
CONTROL
FG30/B-G(I)
380,3,50
10
1.5
1.5
FGR30/B-G(I)
380,3,50
20
4.0
4.0
FG40/B-G(I)
380,3,50
10
1.5
1.5
FGR40/B-G(I)
380,3,50
25
4.0
4.0
FG50/B(2)-G(I)
380,3,50
16
2.5
2.5
FGR50/B(2)-G(I)
380,3,50
25
4.0
4.0
FG60/B(2)-G(I)
380,3,50
16
2.5
2.5
FGR60/B(2)-G(I)
380,3,50
25
4.0
4.0
FG55/B-G(I)
380,3,50
16
2.5
2.5
FGR55/B-G(I)
380,3,50
25
4.0
4.0
FG65/B-G(I)
380,3,50
16
2.5
2.5
FGR65/B-G(I)
380,3,50
25
4.0
4.0
FG20/B-G(O)
380,3,50
32
6.0
6.0
FGR20/B-G(O)
380,3,50
32
6.0
6.0
FG25/B-G(O)
380,3,50
32
6.0
6.0
FGR25/B-G(O)
380,3,50
32
6.0
6.0
FG30/B-G(O)
380,3,50
40
10.0
10.0
FGR30/B-G(O)
380,3,50
40
10.0
10.0
FG40/B-G(O)
380,3,50
50
16.0
16.0
FGR40/B-G(O)
380,3,50
50
16.0
16.0
FG55/B-G(O)
380,3,50
63
25.0
25.0
FGR55/B-G(O)
380,3,50
63
25.0
25.0
FG65/B-G(O)
380,3,50
63
25.0
25.0
FGR65/B-G(O)
380,3,50
63
25.0
25.0
MAINTENANCE
CONTROL
CONTROL
4. MAINTENANCE
4.1. TROUBLE TABLE
Trouble Code
Trouble
Name
Control Description
High Pressure
Protection
E1
pressure)
Pressure Protection
Switch
Indoor
Anti-freezing
E2
Protection
Tube Temp. sensor of the inner fan will keep previous status and E2 will be displayed on
Indoor Unit
error will be cleared and the unit will run at setting mode.
When the suction pressure of system is extremely low, not only
the unit runs badly but also the face of the evaporator is easily
frosted. Once frosting, infernal circle may be caused which makes
more frost. At the same time, refrigerants cannot be completely
evaporated so that the compressor may inhale refrigerants in
Low Pressure
Protection
discharge temp are also low and fluidity of lubricant becomes bad,
which will further affect the lubrication of the unit and damage the
E4
CONTROL
E5
Compressor
Overload Switch of
Compressor
continuously
detected,
it
cannot
automatically
recover.
indoor unit. Compressor and outer fan will stop. At the same time,
Communication
Error
E6
if the indoor unit has not received the message from the outdoor
unit, auxiliary electric heater of the indoor unit will stop. If inner fan
and wired controller have not received the message from the
outdoor unit, error code E6 will be displayed and the unit will be
on standby.
Inner Fan
Protection
E8
Incorrect ON
Protection of
Auxiliary
break up for continuous 3s, all loads will be turned off, E8 will be
displayed and buzzer will sound.
After detecting that the electric heater is incorrectly turned on,
EH
Relay
other loads will stop, inner fan will be turned on, EH will be
Electric Heater
Indoor Ambient
Temp Sensor
F0
Error
if it is normal.
Ambient temp. detected by temp. sensor is an important
F1
Temp. Sensor
Evaporator
it is normal.
If detect that temp. is higher or lower than limit value, it is believed
Temp. Sensor
Error of
F2
Temp. Sensor
Condenser
Sensor Error
Outdoor
Ambient Temp.
CONTROL
Temp. Sensor
Discharge
Temp. Sensor
Error
to judge if it is normal.
F4
Temp Sensor
CONTROL
CONTROL
CONTROL
4.2.4. Overcurrent
Compressor)
Protection(
Overload
Protection
of
CONTROL
Step
Handling Instruction
with hands
on handles.
CONTROL
1.
Unscrew
the bolts on
front panel.
2.
Dismantle
streamlined
1. Streamlined
Dome
the
symmetry
plane
2.
plates
Side Plate
to
disassembly
of
finish
the
the
whole
Left
plate to remove it by
screwdriver.Unscrew the
bolts of right and left side
external casing.
3.
Right
Side Plate
plates to remove it by
screwdriver.
1.Retaining
Plate
Process of installation of external casing isleft and right side platesretaining plate
front and rear cover platestreamlined domefront panel. Please refer to disassembly process
for the cautions.
Disassembly and Assembly of Compressor
Remark : Make sure that there isnt any refrigerant in pipe system and the power supply is cut off before
removal of the compressor..
Step
Illustration
Handling Instruction
CONTROL
source wire
1. Earmark the
colour
wire
corresponding to
the
terminal
removing
when
of
the wire
1. weld off
and
pull
out suction
pinchers.
pipe
and
discharge
pipe
1. Unscrew
the
retaining
nuts of the
compressor
Illustration
magnetic
coil
of
4-way valve.
Remove magnetic coil
Unsolder
the
weld
CONTROL
Body
Magnetic
Coil
Weld
Points (4)
Illustration
Unsolder
weld points
pipe
pinchers.
expansion valve.
Note: When soldering, dont
flame other components and
wrap the valve body with wet
cloth to avoid damage to the
valve.
Disassembly and Assembly of Vapour Liquid Separator
Remark :
Step
Illustration
Handling Instruction
1 Inlet
Pipe
pinchers.
2.
CONTROL
2.
Outlet
Pipe
3. Retaining
Nuts
of
Compressor
Illustration
Unscrew retaining
bolts in corners of top
grill
Handling Instruction
CONTROL
blade
as
shown
above.
Disassemble the wire
of motor from electric
box.
Remove
retaining
bolts of motor.
Remove
motor
upwards.
Illustration
Handling Instruction
1. Disassemble panel
handles
and
hold
it
panel is dismantled.
CONTROL
Retaining Bolts
Illustration
Handling Instruction
1.
Unscrew bolts of
electric box
2. disconnect wiring
3. disassembly of
electric box is
finished.
Unscrew retaining
bolts of the cover to
1. Unscrew
remove it.
bolts
Disconnect power
cord and control wire
and pull them out.
Unscrew retaining
bolts to remove
electric box ( as
shown on left.)
1. Unscrew bolts
and
power
disconnect
cord
on
wiring terminals
1.
Illustration
Handling Instruction
CONTROL
1.
Electrical
Heating
Tube
Illustration
Handling Instruction
1.
Disassembly and Assembly of fan and fan motor
Remark:
Step
Illustration
Handling Instruction
CONTROL
Illustration
Handling Instruction
Unscrew bolts of
retaining plate of motor.
CONTROL
Unscrew bolts of
two belt
Screw bolts of
adjusting plate of motor
and then adjust the
distance between two
belt rollers to strain the
belt.
Disassembly
roller
of
belt
Disassemble
following
the
belt
steps
above.
Anti-clockwise screw
two of screws by inner
hexagon spanner
Clockwise screw
screws by inner
hexagon spanner (the
screw locates the
opposite angle of the
hole without screw.
CONTROL
Disassemble
belt
roller.
CONTROL
CONTROL
5.
6.
CFG(R)20/B-G(O)CFG(R)25/B-G(O)CFG(R)30/B-G(O)parts list
Qty
S/N
Name
Code
01195703P
Heat
Cooling
Heat
Cooling
Heat
Only
Pump
Only
Pump
Only
Pump
0302907601
04145712
3
0733521801
1
1
07109067
15018303
Discharge Tube
04635707
Sub-Assy
03819098
00120040
7
CONTROL
1
1
1
1
1
1
1
00100043
00100049
Gas-liquid Separator
07424144
0467570601
1
1
03639122
04675708
10
01318759
11
Rear Grille
10548211
01125707
01125711
12
Condenser Assy
1
1
01109093
0110909301
01125714
0112571401
13
01258737
14
02118746
15
Streamlined Dome
76318340
16
Fan Blade
10355801
17
Motor
15018761
18
01314301P
19
Support 1
01804632
20
Tube Clip
21400059
21
Support 3
01729161
01804634
22
23
01894602
24
Support plate 3
01894607
25
Supporting Strip
01798797
26
Supporting Strip
01894605
27
Front plate 1
01798808
28
Front plate 2
01538736
29
01538734
30
Electric Box
01419059
31
01405725
32
AC Contactor
44010214
33
AC Contactor
44010229
34
Phase Reverse
Protector
CONTROL
46020052
35
Transformer
43110240
36
Main Board
30224205
37
Terminal Board
42011043
38
Terminal Board
42011103
39
46020114
40
01409075
CONTROL
CFG(R)40/B-G(O)Parts List
Qty
S/N
Name
Code
CFG(R)40/B-N4(O)
Cooling
Heat
Only
Pump
Streamlined Dome
22265801
`01264110P
Fan Blade
10355801
Motor Assy
15404601
Motor SW650A
15704601
Rear Panel
01544104P
01264113P
CONTROL
22414101
01854102P
10
01264116P
11
01314604
12
Condenser Assy
02205302
0220530201
1
1
13
01875304
14
01195210P
15
01285242
16
Gas-liquid Separator
07421104
17
Compressor
00205215
18
Ball Valve
07180005
19
07108627
01854103P
20
21
01395374
22
01424108P
23
Front panel 1
01544101P
24
Cover Plate
01264133P
25
panel
01544102P
26
Front Panel
01544103P
27
Reinforced bar
`02224103P
28
Support plate
01894101P
29
Support platepanel
01894104P
01264111P
04315241
04635245
07423202
04325340
0467525701
01314136P
30
31
32
33
34
35
36
37
38
01264115P
39
AC Contactor
44010229
40
AC Contactor
44010240
41
Phase Reverse
Protector
CONTROL
46020052
42
30224205
43
Transformer
4311024001
46020121
44
45
42011103
46
Terminal Board
42011051
01325243
47
CONTROL
5.
CONTROL
Parts List
CFG(R)20/B-G(I)CFG(R)25/B-G(I)CFG(R)30/B-G(I)Parts List
Qty
S/N
Name
Code
Heat
Cooling
Heat
Cooling
Heat
Only
Pump
Only
Pump
Only
Pump
01259107
SupportSteelBar
01729141
rotate axletree
10549057
15009058
15018303
01845309
10548148
10548150
15009059
10548208
10548211
4
5
01025306
8
1
1
01009128
01025304
01309103
01315319
10
11
overhauling side
Belt
SPA
01539148
76318340
76318317
12
13
Hook
02205302
01875304
01779103
1
1
01875302
14
10548156
15
10548218
16
01309105
17
FrontPanel_OutsideMachine
01285314P
01195302
1
1
1
1
18
MetalBase
01209097
01285312
19
01749058
20
01749057
21
01749056
22
Electric Box
01399145
23
back girder
01779108
24
25
26
27
CONTROL
01389077
01389079
15009059
01315315
1
1
1
1
01309101
01315313
28
front girder
01779106
29
01339099
30
Transformer
43110239
31
AC Contactor
44010232
32
Thermorelay
44020347
33
AC Contactor
44010229
34
Terminal Board
42011257
35
Main Board
30224206
CONTROL
CFG(R)40/B-G(I)CFG(R)50/B(2)-G(I)CFG(R)60/B(2)-G(I)Parts List
Qty
S/N
Name
Code
01265209
CFG(R)40/B-G(I)
Cooling
Heat
Cooling
Heat
Cooling
Heat
Only
Pump
Only
Pump
Only
Pump
1
1
1
1
01265321
01845205
2
01845315
01845213
01375208P
CFG(R)50/B(2)-G(I) CFG(R)60/B(2)-G(I)
CONTROL
01375309P
01375212P
01875208P
4
Evaporator Assy
Side Panel
Side Panel
01545311
1
01545305
01545210
01845210
1
01845316
01545212
01025221
1
01025321
01845207
01875212P
1
01875317P
01025243
01545307
01545315
9
Nut
70310114
10
Blot
70410312
11
Washer
70410309
12
Hook
02139056
13
02169050
14
Retaining Plate
01845319
15
Fan Motor
15014805
1
1
15018611
16
17
rotate axletree
10549057
01285220P
Sub-Assy
01285328P
76318309
18
Belt SPA
76318356
19
Belt Pulley
10548155
10548156
20
Taper Sleeve
10548218
10548220
21
Belt Pulley
10548149
10548150
22
Taper Sleeve
10548213
10548213
23
01805212P
01805320P
24
01285222P
CONTROL
01195305P
25
01425304P
26
01395346
27
01375210P
2
2
1
1
01375307P
28
01375209P
01375308P
01545228P
29
Frame Plate
01545236P
01545235P
30
Motor
15705214
15019241
01545211P
31
Side Panel
01545306P
01545312P
32
Terminal Board
42011257
33
Main Board
30224206
34
Transformer
35
Switch
36
AC contactor
30224207
43110239
46028101
46028103
44010213
37
AC contactor
44010229
38
Wired controller
30294217
39
40110140