Вы находитесь на странице: 1из 15

Paper 3 Set B

15th NATIONAL CERTIFICATION EXAMINATION


FOR
ENERGY MANAGERS & ENERGY AUDITORS August, 2014
PAPER 3:

Energy Efficiency in Electrical Utilities

Date: 24.04.2014

Timings: 0930-1230 HRS

Section I:

Which loss is considered the most unreliable or complicated to measure in electric motor
efficiency testing?
b) rotor Cu loss

d) stray loss

b) best efficiency point


d) none of the above

In case of increased suction lift from open wells, the pump delivered flow rate
a) increases

4.

c) stator Iron loss

The intersection point of the centrifugal pump characteristic curve and the design system
curve is the
a) pump efficiency point
c) system efficiency point

3.

Marks: 50 x 1 = 50

Answer all 50 questions


Each question carries one mark

a) stator Cu loss
2.

Max. Marks: 150

OBJECTIVE TYPE

(i)
(ii)
1.

Duration: 3 HRS

b) decreases

c) remains same

d) none of the above

In pumping systems where static head is a high proportion of the total, the appropriate
solution is
a) install two or more pumps to operate in parallel
b) install two or more pumps to operate in series
c) install two or more pumps to operate in independent operation
d) none of the above

5.

A Plant wants to replace the existing 100 TR water cooled vapour compression
refrigeration system with a waste heat driven vapour absorption chiller. The capacity of
the existing cooling tower
a) needs no change
c) is to be raised to 1.2 times

6.

Shaft power of the motor driving a pump is 30 kW. The motor efficiency is 0.92 and pump
efficiency is 0.5. The power drawn by the motor will be
a) 65.2 kW

7.

b) 15 kW

c) 30 kW

d) 32.6 kW
3

If water is flowing through a cooling tower at 120 m /h with 5 C range, the load on cooling
o
tower at an ambient wet bulb ambient temperature of 33 C is
a) 198.4 TR

8.

b) is to be doubled
d) none of the above

b) 357 TR

c) 158 TR

d) none of the above

In a plant, the loading on a transformer was 1000 kVA with the power factor of 0.88. The
plant improved the power factor to 0.99 by adding capacitors on the load side. The release
in transformer loading( kVA) will be

_______________________
Bureau of Energy Efficiency

Paper 3 Set B

a) 111
9.

c)

999

average maximum wet bulb for rainy months


average maximum wet bulb for summer months
average minimum wet bulb for summer months
average maximum wet bulb for winter months

Which one from the following types of cooling towers consumes least power for the same
operating conditions?
a) counter flow film fill cooling tower
c) counter flow splash fill cooling tower

11.

d) none of the above

The wet bulb temperature normally chosen for designing of cooling tower is
a)
b)
c)
d)

10.

b) 889

b) cross-flow splash fill cooling tow


d) none of the above

Lux is defined as
a) ratio of luminous flux emitted by a lamp to the power consumed by the lamp
b) one lumen per square meter
c) one lumen per square feet
d) none of the above

12.

Which among the following is the most energy efficient lamp for the same wattage rating?
a) HPMV

13.

c) CFL

d) Metal halide

_____ is a measure of effect of light on the perceived colour of objects


a) lux

14.

b) GLS

b) lumens

c) CRI

d) lamp circuit efficacy

Which of the following is the best definition of illuminance?


a) luminous flux incident on an object per unit area
b) flux density emitted from an object without regard for direction
c) time rate of flow of light energy
d) flux density emitted from an object in a given direction

15.

Two most important electrical parameters, which are to be monitored, among the following
for safe operation of Diesel Generator set are:
a) voltage and ampere
c) power factor and ampere

16.

In a DG set, the generator capacity is 1000 kVA with a rated power factor 0.8. It is
consuming 150 litre per hour diesel oil. If the specific fuel consumption of this DG set is
0.25 litres/ kWh at that load, then what is the kVA loading of the set at 0.88 PF?
a) 682 kVA

17.

b) 800 kVA

c) 750 kVA

d) none of the above

The maximum unbalanced load between phases should not exceed _______ % of the
capacity of the DG set
c) 10

18.

b) kW and kVA
d) kVA and ampere

b) 5

c) 1

d) none of the above

The capacity of largest motor that can be started in the given DG set is of kVA rating
of DG set
a) 25%

_______________________
Bureau of Energy Efficiency

b) 50%

c)75%

d)100%

Paper 3 Set B
19.

a) 43
20.

The jacket cooling water in a diesel engine flows at 12.9 m /hr with a range of 10 C and
accounts for 30% of the engine input energy. What will be the hourly Diesel consumptionin
kg with a calorific value of 10,000 kcal/kg
b) 12.9

c) 17.3

d) none of the above

Select the incorrect statement:


a) harmonics occur as spikes at intervals which are multiples of the supply frequency
b) harmonics are not multiples of the fundamental frequency
c) induction motors are not the major sources of harmonics
d) transformers operating near saturation level create harmonics

21.

If the speed of centrifugal fan is reduced to 80% of its rated speed then the power drawn
will _______% of its rated power:
a) 80%

22.

b) 51.2 %

c) 40 %

d) 64 %

The order of movement of thermal energy in HVAC system is:


a) Indoor air - Condenser water - Chilled water - Cooling tower - Refrigerant
b) Chilled water - Indoor air - Refrigerant-Cooling tower - Condenser water
c) Indoor air - Chilled water - Refrigerant-Condenser water- Cooling tower
d) Indoor air - Chilled water Refrigerant - Cooling tower - Condenser water

23.

Which one of the following device will help to eliminate the hunting problems normally
associated with capacitor switching?
a) Maximum Demand Controller
c) Soft Starter

24.

b) Intelligent Power Factor Controller (IPFC)


d) Eddy Current Drives

The occupancy sensors in a lighting installation are best suited for


a) conference halls
c) entrances of offices/buildings

25.

b) large production shops/hangars


d) street lighting

A pure resistive load in an alternating current (AC) circuit draws


a) lagging reactive power
c) leading reactive power

26.

Select the incorrect statement: The advantage of PF improvement by capacitor addition in


an electric network is
a)
b)
c)
d)

27.

active power component of the network is not affected


reactive power component of the network is not affected
2
I R power losses are affected in the system
voltage level at the load end is affected

Heat Rate of a thermal power station is the heat input in kilo Calories or kilo Joules, for
generating
a) one kW of electrical output
c) one kWh of electrical output

28.

b) active power
d) none of the above

b) one kVAh of electrical output


d) one kVA of electrical output

Improving power factor at motor terminals in a plant will


a) increase active power drawn by motor
c) reduce contract demand with utility

_______________________
Bureau of Energy Efficiency

b) reduce system distribution losses


d) increase motor design power factor

Paper 3 Set B
29.

For a 6 pole induction motor operating at 49.5 Hz, the percentage slip at a shaft speed of
950 RPM will be
a) 4.0 %

30.

b) 5.0 %

c) 0.04 %

d) none of the above

A plant had installed three phase shunt capacitors to improve power factor at Motor
Control Circuit (MCC). Busbar three phase Voltages at the main electrical panel of a plant
were balanced but at the Motor Control Circuit (MCC),receiving three phase power from
busbars, the line voltages were found to be unbalanced. The main reason for this
unbalanced voltage at MCC among the following could be
a) PF capacitors were operating at higher supply frequency
b) PF improvement in all phase was not uniform due to blown fuse in one phase of the 3
phase PF capacitors
c) PF capacitors were operating at higher voltage then their rated values
d) PF capacitors were operating at lower voltage then their rated values

31.

A 50 kVAr, 415 V rated power factor capacitor was found to be having terminal supply
voltage of 430 V. The capacity of the power factor capacitor at the operating supply
voltage would be approximately
a) 53.67 kVAr

b) 50 kVAr

c) 46.57 kVAr

d) none of the above

32.

A 75 kW rated squirrel cage induction motor installed with static PF correction capacitors
across the motor terminals got damaged along with capacitors once supply was switched
off due to power failure. The possible reason for the motor burn out among the following
could be
a) motor was oversized
b) motor was undersized
c) charging current of the capacitors was more than the magnetizing current of the motor
d) charging current of the capacitor was only 85% of the motor magnetizing current

33.

An induction motor rated for 75 kW and 94 % efficiency, operating at full load, will
a) deliver 70.5 kW

34.

b) deliver 75 kW

c) draw 75 kW

d) deliver 79.78 kW

Higher chiller COP can be achieved with


a) higher evaporator temperature and higher condensing temperature
b) higher evaporator temperature and lower condensing temperature
c) lower evaporator temperature and higher condensing temperature
d) lower evaporator temperature and lower condensing temperature

35.

Increase in the delivery pressure of a compressor by 1 bar would reduce the power
consumption by
a) 1 to 5 %

36.

c) 11 to 15 %

d) none of the above

The FAD of a reciprocating compressor is directly proportional to


a) pressure

37.

b) 6 to 10 %

b) volume

c) speed

d) all of the above

Which of the following is not true of air receivers in a compressed air system?
a) smoothens pulsating air output
b) increases the compressed air pressure

_______________________
Bureau of Energy Efficiency

Paper 3 Set B
c) stores large volumes of compressed air
d) facilitates draining of moisture
38.

Typical acceptable pressure drop in mains header at the farthest point of an industrial
compressed air network is
a) 1.0 bar

39.

b)expansion valve

b) 4536 kcals

b) 1.5

c) 3000 kcals

c) 0.6

b) 7032 W

b) Energy Efficiency Ratio (EER)


d) none of the above

c) 428.7 BTU/min

d) all of the above

b) 1764 rpm

c) 588 rpm

d) none of the above

In series operation of identical centrifugal fans, ideally


b) static pressure doubles
d) flow goes up by four times

The hydraulic power of a motor pump set is 8 kW. If the power drawn by the motor is 16
kW at 90% efficiency, the pump efficiency will be
a) 55.5%

48.

d) 1.66

A fan with 25 cm pulley diameter is driven by a 2940 rpm motor through a V-belt system. If
the motor pulley is reduced from 20 cm to 15 cm keeping the motor rpm and fan pulley
diameter the same, the fan speed will reduce by

a) flow doubles
c) static pressure goes up by four times
47.

d) 6048 kcals

2 ton of refrigeration (TR) is equivalent to about

a) 1176 rpm
46.

d) evaporator

In the performance assessment of a refrigeration system, which performance ratio (energy


efficiency) does not follow the trend a higher ratio means a more efficient refrigeration
system?

a) 100.8 kcal/min
45.

d) 43.4 C

c) both (a) & (b)

a) Coefficient of performance(COP)
c) kW per ton
44.

c) 40.8 C

If the power consumed by a 1.5 TR refrigeration compressor is 2.5 kW , what is the energy
efficiency ratio?
a) 2.1

43.

b) 35.9 C

A 1.5 ton air conditioner installed in a room and working continuously for one hour will
remove heat of
a) 3024 kcals

42.

d) 0.3 bar

The pressure of refrigerant in vapour compression system changes in


a) compressor

41.

c) 0.5 bar

All other conditions remaining the same in a refrigeration system, at which of the following
condenser temperatures, the power consumption will be the least:
a) 32.6 C

40.

b) 0.7 bar

b) 50%

c) 45%

d) none of the above

The energy saving with variable speed drives in a pumping system will be maximum for
systems with
a) pure static head
b) pure friction head
c) high static head and low friction head d) high static head with high friction head

49.

A process fluid at 50 m /hr, with a density of 0.96, is flowing in a heat exchanger and is to
o
o
be cooled from 36 C to 29 C. The fluid specific heat is 0.78 kcal/kg. If the chilled water

_______________________
Bureau of Energy Efficiency

Paper 3 Set B
o

range across the heat exchanger is 5 C,the chilled water flow rate is
3

a) 67.2 m /hr
50.

b) 52.42 m /hr

c) 50 m /hr

d) none of the above

The inner tube of an L-type pitot tube is used to measure in the air duct
a) total pressure

b) static pressure

b) velocity pressure

d) dynamic pressure

. End of Section I .
Section II: SHORT DESCRIPTIVE QUESTIONS
(i)
(ii)

Marks: 10 x 5 = 50

Answer all Ten questions


Each question carries Five marks

S-1
An energy audit of a fan was carried out. It was observed that the fan was delivering 18,500
3
Nm /hr of air with static pressure rise of 62 mm WC. The power measurement of the 3-phase
induction motor coupled with the fan recorded 3.1 kW/ phase on an average. The motor operating
efficiency was assessed as 88% from the motor performance curves. What would be the fan static
efficiency?
Ans:
3
3
Q = 18,500 Nm / hr.= 5.1388 m /sec
SP = 62 mmWC
St = ?
Power input to motor= 3.1x3=9.3 kW
Power input to fan shaft=9.3 x0.88=8.184 kW
Fan static

Volume in m /sec x Pst in mmWc


102 x Power input to shaft

5.1388 x 62
102 x 8.184

0.38

38%

S-2 A 37 kW, 3 phase, 415 V induction motor draws 56 A and 30 kW power at 410 V . What is the
Apparent and Reactive Power drawn by the motor at the operating load?
Ans:
Apparent power

= 1.7321 x 0.410 x 56 = 39.769 kVA

Reactive power

= squrt (apparent power - active power )

Active power

= 30 kW

Therefore reactive power

= sqrt (1581.57-900)

= 26.1 kVAr

_______________________
Bureau of Energy Efficiency

Paper 3 Set B
S-3

Define Range, approach and effectiveness in cooling tower operation

Ans:
i)

Range is the difference between the cooling tower water inlet and outlet temperature.

ii)

Approach is the difference between the cooling tower outlet cold water temperature and
ambient wet bulb temperature. Although, both range and approach should be monitored, the
`Approach is a better indicator of cooling tower performance.

iii)

Cooling tower effectiveness (in percentage) is the ratio of range, to the ideal range, i.e.,
difference between cooling water inlet temperature and ambient wet bulb temperature, or in
other words it is = Range / (Range + Approach).

S-4

Compute AT & C (Aggregate Technical and Commercial) Losses for the following data:
S. No.
1
2a
2b
2c
3
4a
4b

Description
Input Energy = (Import-Export), MU
Energy Billed (Metered), MU
Energy Billed (Un-Metered), MU
Total Energy Billed ( E1 + E2 )
Amount Billed (Rs. lakhs )
Gross Amount Collected (Rs. lakhs)
Arrears Collected (Rs. lakhs)

Ei
E1
E2
Eb
Ab
AG
Ar

Annual
Data
22
16
1
17
800
820
40

Ans:
Estimation of AT & C Losses
Description

S. No.
1
2a
2b
2c
3
4a
4b
4c
5
6
7

S-5

Input Energy = (Import-Export), MU


Energy Billed (Metered), MU
Energy Billed (Un-Metered), MU
Total Energy Billed ( E1 + E2 )
Amount Billed (Rs. lakhs )
Gross Amount Collected (Rs. lakhs)
Arrears Collected (Rs. lakhs)
Amount Collected without Arrears (Rs.
lakhs)
Billing Efficiency (BE)
Collection Efficiency(CE)
AT& C Loss

Ei
E1
E2
Eb
Ab
AG
Ar
Ac=AG-Ar

Annual
Data
22
16
1
17
800
820
40
780

= Eb/Ei *100%
=Ac/Ab *100%
{1- (BE *CE ) *100%

77.27 %
97.5%
24.7 %

State any three major differences between vapor compression refrigeration (VCR) and Vapour
Absorption Refrigeration (VAR) system?

Ans:
VCR uses electric power for the compressor as main input while VAR uses a source of
heat
VCR uses compounds of hydrogen, fluorine and carbon as refrigerants while VAR
uses water

_______________________
Bureau of Energy Efficiency

Paper 3 Set B
VCR works under pressure while VAR works under vacuum
VCR has a high COP while VAR has a low COP
VAR requires cooling tower capacity double that of VCR
Any other relevant point

S-6

As Energy Manager, what are all the factors you look into for energy saving in operating DG
Sets.?

Ans:
1.Ensuring steady load conditions on the DG set & providing cold and dust free intake air
2.Improving air filtration
3.Ensuring fuel oil storage, handling and operation as per manufacturers guidelines/oil
companys data
4. Consideration of fuel oil additives
5.Calibration fuel injection pumps periodically
6.Ensuring compliance with maintenance check lists
7.Ensuring balanced electrical loading
8.In case of a base load operations, consideration of waste heat recovery system

S-7

A 180 kVA, 0.80 PF rated DG set has diesel engine rating of 210 BHP. What is the maximum
power factor which can be maintained at full load on the alternator without overloading the DG
set? (Assume alternator losses and exciter power requirement as 12.66 kW and there is no
derating of DG set)

Ans:
Engine rated Power

= 210 x 0.746 = 156.66 kW

Rated power available for alternator = 156.66 12.66 = 144 kW


Maximum power factor possible = 144 /180 = 0.8

S-8

An induced draft-cooling tower is designed for a range of 7 C. An energy manager finds the
operating range as 4 C. In your opinion what could be the reasons for this type of situation.

Ans:
1.
2.
3.
4.
5.

There may be excess cooling water flow rate


There may be reduced heat load from the process
Some of the cooling tower cells fan is switched off
Approach may be poor because of high humid condition
Nozzles may be blocked

. End of Section - II .

_______________________
Bureau of Energy Efficiency

Paper 3 Set B

Section III: LONG DESCRIPTIVE QUESTIONS


(i)
(ii)
L-1

Marks: 5 x 10 = 50

Answer all Five questions


Each question carries Ten marks

(a) A 3 phase, 415 V, 75 kW induction motor is drawing 58 kW at a 0.7 PF.


Calculate the capacitor rating requirements at motor terminals for improving PF to 0.95. Also,
calculate the reduction in current drawn and kVA reduction, from the point of installation back
to the generating side due to the improved PF at operating voltage of 415 V.
(b) A process plant consumes of 2,00,000 kWh per month at 0.92 Power Factor (PF). What is
the percentage reduction in distribution losses per month if PF is improved up to 0.96 at load
end?
a)

kVAr Rating

= kW [Tan 1 Tan 2]

Cos 1 = 0.70,

1 = Cos (inv) 0.70 = 45.57, Tan 1 = 1.02

Cos 2 = 0.95,

2 = Cos (inv) 0.95 = 18.2 , Tan 2 = 0.329

kVAr Rating

= 58 kW (1.02 0.329)
= 40.1kVAr

Current drawn at 0.7 PF

= 58 / 3 x 0.415 x 0.7
= 115.27 A

Current drawn at 0.95 PF

= 58 / 3 x 0.415 x 0.95
= 84.94 A

Reduction in current drawn

= 115.27 84.94
= 30.3 A

Initial kVA at 0.7 PF

= 58 / 0.7
= 82.85 kVA

kVA at 0.95 PF

= 58 / 0.95
= 61.05 kVA

Reduction in kVA

= 82.85 61.05
= 21.8 kVA
(OR)

Reduction in kVA
_______________________
Bureau of Energy Efficiency

= (3 VI)old (3 VI)new
9

Paper 3 Set B
= (3 x 0.415 x 115.27) (3 x 0.415 x 84.94)
= 82.85 61.05
= 21.8 kVA
(OR)
= 1.7321 x 0.415 x reduction in current

Reduction in kVA

= 1.7321 x 0.415 x 30.3


= 21.8 kVA

1 - PF1 / PF2

b) % Reduction in distribution losses =

= [1- (0.92/0.96) ]
= 0.0816
= 8.16 %

L-2 The measured values of a 20 TR package air conditioning plant are given below:
Average air velocity across suction side filter: 2.5 m/s
Cross Sectional area of suction: 1.2 m
o

2
o

Inlet air = Dry Bulb:20 C,

Wet Bulb: 14 C,
o

Enthalpy: 9.37 kcal/kg

Outlet air= Dry Bulb: 12.7 C, Wet Bulb: 11.3 C; Enthalpy: 7.45 kcal/kg
3

Specific volume of air: 0.85 m /kg


Power drawn:

by compressor: 9.44 kW
by Pump: 4.86 kW
by Cooling tower fan: 0.87 kW

Calculate:
3

i.
ii.
iii.
iv.
v.

Air Flow rate in m /hr


Cooling effect delivered in kW
Specific power consumption of compressor in kW/TR
Overall kW/TR
Energy Efficiency Ratio in kW/kW

Ans:
3

i. Air flow rate = 2.5*1.2 = 3 m /sec = 10800 m /hr


ii. Cooling Effect delivered = [(9.37-7.45)*10800]/(0.85*3024) = 8.07 TR = 28.37 kW
iii. Compressor kW/TR = 9.44/8.07 = 1.17
iv. Overall kW/TR = (9.44+4.86+0.87)/8.07 = 1.88
v. Energy Efficiency Ratio(EER) in kW/kW = 28.37/9.44 = 3

_______________________
Bureau of Energy Efficiency

10

Paper 3 Set B
L-3

During an energy audit following data were obtained on a 3 phase induction motor:
Rated values:
Operating values:

37 kW,415V, 66 A,0.88 pf
410 V, 49A, 0.76 pf

Note: Motor efficiency in this particular case does not change between 50 100 % loading.
The plant operates for 7000 hours per year with the electricity cost of Rs. 7.00 per unit.
It is proposed to replace the existing motor by a 30 kW energy efficient motor with 92%
efficiency.
a) Determine the rated efficiency and the loading of the existing motor.
b) Calculate the loading with energy efficient motor.
c) If replacing the existing motor with energy efficient motor which costs Rs.75,000,
determine the pay back period for the investment required for the energy efficient motor
over the existing motor. Consider the salvage value of the existing motor as Rs.10,000/.
Ans:
Rated input power
Rated efficiency of the motor

1.732 0.415 66 0.88


41.746 kW
37/ 41.746
88.63%

Actual input power drawn

1.732 0.410 49 0.76


26.44 kW

Loading of the motor


Shaft power or motor output

26.44/41.746 = 0.633 or 63.3%


37x0.633= 23.44 kW

Energy efficient motor rating


Actual output required
% loading of the motor

30 kW
23.44 kW
23.44/30
78 %

Annual energy savings

23.44(1/0.8863 1/0.92) x 7000 x Rs.7


Rs.48020 /-

Payback period

(75,000-10,000)/48020
1.35 years

L 4 : a) The suction head of a pump is 3 m below the pump centerline. The discharge pressure is 2.8
2
3
kg/cm . The flow rate of water is 120 m /hr. Find out the pump efficiency if the actual power
input of the connected motor is 17.0 kW with an operating efficiency of 0.90.
b) A V-belt driven reciprocating instrument air compressor was found to be maintaining a
2
distribution system pressure of 7 kg/cm g. 20% of the instrument air was used for control
2
valves installed in a boiler house and requiring 6.5 kg/cm g, whereas balance 80% of the
instrument
air
was
used
for
other
application
requiring
2
2 kg/cm g. What would you like to advice in this situation?
_______________________
Bureau of Energy Efficiency

11

Paper 3 Set B
Ans:
a)
Discharge Head
Suction Head
Total Head

:
:
:

2.8 kg/cm equals 28 metre head.


- 3 metre.
28 (-3) = 31 metre.
3

Hydraulic power Ph = Q (m /s) xTotal head, hd - hs (m) x

(kg/m ) x g (m/s ) / 1000

Hydraulic Power

(120/3600) x 1000 x 9.81 x 31/1000 = 10.137 kW

Pump Efficiency

100 x 10.137/17x0.9 = 66.2 %

b)
It is advisable to
1)

Provide a separate small air compressor operating at 7 kg/cm2 g near the control valves
and reduce the existing distribution system pressure from 7 kg/cm2g to 2 kg/cm2g for
pneumatic instrument

2)

Since there will be reduced leakage loss due to reduced system pressure, the
compressor unloading may begin due to reduced demand. Reduce appropriately the
motor pulley size in order to match the capacity

L-5

Fill in the blanks for the following:


1. One ton of refrigeration (TR) is equal to 3.516 kW.
2.

A four pole 15kW induction motor operating at 50 Hz, with 1% slip will have rotor input power
of 15.15 kW

3. A Pitot tube is used to measure total pressure and static pressure to determine velocity
pressure of the fluid
4. In case of centrifugal pumps, impeller diameter changes are generally limited to reducing the
diameter to about 75 % of maximum size.
5. The value, by which the pressure in the pump suction exceeds the liquid vapour pressure, is
expressed as Net Positive Suction Head Available (NPSHA).
6. The parameter used by ASME to define fans, blowers and compressors is Specific ratio.
7. It is possible to run pumps in parallel provided their closed valve heads are similar.
8. If the evaporation loss is 16 cubic meters per cell and Cycles of Concentration is 3, the blow
down requirement per cell of a cooling tower is 8 cubic meters per cell
9. A centrifugal pump raises water to a height of 12 metre . If the same pump handles brine with
specific gravity of 1.2, the height the brine will be raised to is 12 metres or the same height
10. Installing the capacitor near motor terminals will increase the design power factor of the motor
- True / False (False)

_______________________
Bureau of Energy Efficiency

12

Paper 3 Set B
L-6

List five energy conservation measures each for any two of the following
a)
b)
c)
d)

Energy use in buildings


Compressed air system
Pumps and pumping systems
Lighting systems

Ans:
a) Energy use in buildings
Air-Conditioning System:
Weather-stripping of Windows and Doors : Minimise exfiltration of cool air and infiltration of
warm air through leaky windows and doors by incorporating effective means of weather
stripping. Self-closing doors should also be provided where heavy traffic of people is
anticipated.
Temperature and Humidity Setting: Ensure human comfort by setting the temperature to
o
o
between 23 C and 25 C and the relative humidity between 55% to 65%.
Chilled Water Leaving Temperature: Ensure higher chiller energy efficiency by maintaining the
o
chilled water leaving temperature at or above 7 C. As a rule of thumb, the efficiency of a
o
centrifugal chiller increases by about 2 % for every 1 C rise in the chilled water leaving
temperature.
Chilled Water Pipes and Air Ducts: Ensure that the insulation of the chilled water pipes and
ducting system is maintained in good condition. This helps to prevent heat gain from the
surroundings.
Chiller Condenser Tubes : Ensure that mechanical cleaning of the tubes is carried out at least
once every six months. Fouling in the condenser tubes in the form of slime and scales reduces
the heat transfer of the condenser tubes and thereby reducing the energy efficiency of the
chiller.
Cooling Towers : Ensure that the cooling towers are clean to allow for maximum heat transfer
so that the temperature of the water returning to the condenser is less than or equal to the
ambient temperature.
Air Handling Unit Fan Speed : Install devices such as frequency converters to vary the fan
speed. This will reduce the energy consumption of the fan motor by as much as 15%.
Air Filter Condition : Maintain the filter in a clean condition. This will improve the heat transfer
between air and chilled water and correspondingly reduce the energy consumption.
b) Compressed Air Systems
Ensure air intake to compressor is not warm and humid by locating compressors in well0

ventilated area or by drawing cold air from outside. Every 4 C rise in air inlet temperature will
increase power consumption by 1 percent.
Clean air-inlet filters regularly. Compressor efficiency will be reduced by 2 percent for every
250 mm WC pressure drop across the filter.

_______________________
Bureau of Energy Efficiency

13

Paper 3 Set B
Compressed air piping layout should be made preferably as a ring main to provide desired
pressures for all users
Compressed air leakage of 40- 50 percent is not uncommon. Carry out periodic leak tests to
estimate the quantity of leakage.
Install equipment interlocked solenoid cut-off valves in the air system so that air supply to a
machine can be switched off when not in use.
Present energy prices justify liberal designs of pipeline sizes to reduce pressure drops.
If pressure requirements for processes are widely different (e.g. 3 bar to 7 bar), it is advisable
to have two separate compressed air systems.
Reduce compressor delivery pressure, wherever possible, to save energy.
Retrofit with variable speed drives in big compressors, say over 100 kW, to eliminate the
`unloaded running condition altogether.
Keep the minimum possible range between load and unload pressure settings.
Automatic timer controlled drain traps wastes compressed air every time the valve opens. So
frequency of drainage should be optimized.
A smaller dedicated compressor can be installed at load point, located far off from the central
compressor house, instead of supplying air through lengthy pipelines.
Misuse of compressed air such as for body cleaning, agitation, general floor cleaning, and
other similar applications must be discouraged in order to save compressed air and energy
Pneumatic transport can be replaced by mechanical system as the former consumed about 8
times more energy.

c) Pumps & Pumping Systems

Ensure adequate NPSH at site of installation

Operate pumps near best efficiency point.

Modify pumping system and pumps losses to minimize throttling.

Adapt to wide load variation with variable speed drives or sequenced control of multiple
units.

Stop running multiple pumps - add an auto-start for an on-line spare or add a booster
pump in the problem area.

Use booster pumps for small loads requiring higher pressures.

Increase fluid temperature differentials to reduce pumping rates in case of heat


exchangers.

Repair seals and packing to minimize water loss by dripping.

Balance the system to minimize flows and reduce pump power requirements.

Avoid pumping head with a free-fall return (gravity); use siphon effect to advantage.

Conduct water balance to minimise water consumption

_______________________
Bureau of Energy Efficiency

14

Paper 3 Set B

In the case of over designed pump, provide variable speed drive, or downsize / replace
impeller or replace with correct sized pump for efficient operation.

Replace old pumps by energy efficient pumps

Reduce system resistance by pressure drop assessment and pipe size optimisation

d) Lighting System
Switch off Lights When Not In Use
Provision of Separate Switches for Peripheral Lighting : A flexible lighting system, which made
use of natural lighting for the peripherals of the room.
Install High Efficiency Lighting System : Use lamps with high luminous efficacy. For example,
replacing incandescent bulbs with compact fluorescent lamps can reduce electricity
consumption by 75% without any reduction in illumination levels.
Fluorescent Tube Ballasts : The ballast losses of conventional ballast and electronic ballast are
12W and 2W respectively. Hence, consider the use of electronic ballast for substantial energy
savings in the lighting system.
Lamp Fixtures or Luminaires : Optical lamp luminaries made of aluminum, silver or multiple
dielectric coatings have better light distribution characteristics. Use them to reduce electricity
consumption by as much as 50% without compromising on illumination levels.
Cleaning of Lights and Fixtures : Clean the lights and fixtures regularly. For best results, dust
at least four times a year.
Use Light Colors for Walls, Floors and Ceilings : The higher surface reflectance values of light
colors will help to make the most of any existing lighting system.
Lighting controls like timer controls, day light controls, voltage controllers, occupancy sensors,
switching controls, PLC controls can be adopted.

. End of Section - III .

_______________________
Bureau of Energy Efficiency

15

Вам также может понравиться