Академический Документы
Профессиональный Документы
Культура Документы
PART I:
1.1
DESCRIPTION
Scope
This work shall consist of furnishing and placing reinforcement bars of the grade,
type and size stated shown in accordance with these Specifications, and in
conformity with the requirements shown on the Drawings.
1.1.1
The materials and workmanship to be employed for the reinforcing
steel works of concrete shall comply with the Building Code Requirements for
Reinforced Concrete ACI 318-02, and these Specifications. In the event of conflict
between ACI Standard and these Specifications, the latter shall be prevailed.
1.1.2
This section specifies the furnishing and placing of reinforcement bars
of the grade, type, and size shown in accordance with these Specifications, and
in conformity with the requirements shown on the Drawings.
1.1.3
Bending schedules shown on the Drawings are for guidance only and
shall be checked by the Contractor according to ACl315-99 or latest edition.
1.2
Tolerances
+6 mm / -3 mm
25
mm
except
that
1.3
1.3.1
Reinforcement for structures shall be handled and stored in a manner
that will prevent bending out of the desired shape and the unnecessary
accumulation of dirt, oil, and paint. As recommendation, Reinforcement shall be
stored on above ground concrete slab under cover, shaded and racked as
necessary.
1.3.2
When placed in the work reinforcement shall be free from dirt, oil,
grease, paint, mill-scale and loose or thick rust.
1.4
Shop Drawings
4-1 / 1
Technical Specifications
4-2: Reinforcement
PART ll:
2.1
PRODUCTS
Materials
2.1.1 General
All mild steel bars shall be plain round bars and shall conform to the following
2
specifications and have a yield stress not less than 235 N/ mm mm2 . (The yield
stress is defined as the stress below which not more than 5% of the test results
fail.) Steel Grade SR 24 shall conform to the latest edition of TIS 20 or ASTM
A615.
All high yield steel bars shall be deformed bars and shall conform to the
following specifications and have a characteristic yield stress not less than 390
N/mm2 or 490 N/mm2 for SD40 and SD50 respectively. Steel Grade SD 40 and
SD 50 shall conform to the latest edition of TIS 24 or AASHTO M31.
Where welding to reinforcement bar is required steel bars shall be weldable
grade conforming to the requirements of ISO 6935-2 or ASTM A706M, carbon
content of 0.24, with maximum carbon equivalent not more than 0.52 percent by
mass.
Where the yield strength (fy) of vertical reinforcing bar in existing columns or
piers, exposed in accordance with Section 4-15, is higher than 60,000 psi or
420 MPa, additional vertical bars of grade SD-40 shall be installed via bonding in
predrilled holes in concrete of the proposed structure in the rate of 1.2 times of
the required quantity. The additional bars shall be arranged to each face of
member in the former installing proportion. The additional bars so arranged shall
be glued by approved epoxy resin and bonded to predrilled concrete hole in such
a way that the bars are yielded by in-place pull- out test prior to the bond being
failed. The Contractor shall propose the method of construction for the approval
of the Engineer before the commencement of work.
Technical Specifications
4-2: Reinforcement
2.2
Ordering Material
The name of the proposed supplier (or suppliers) of the reinforcement shall be
submitted as soon as possible to the Engineer for his approval. The
Contractor shall submit necessary information concerning the supplier as
requested by the Engineer. Copies of orders placed shall be submitted to the
Engineer.
4-2 /8
Technical Specifications
4-2: Reinforcement
The Contractor shall furnish the Engineer with copies of the manufacturer's
certificates of tests for the steel reinforcement to be used in the Works. These
certificates shall include all relevant data on the steel, i.e. breaking strength,
yield strength, characteristics on elongation, chemical composition etc. for
approval by the Engineer. No steel shall be delivered without certificate
guaranteeing the yield stress.
2.3
Conformity Tests
All reinforcement shall be bundled by size with separation of casts and bundle
shall be identified by durable tags bearing the manufacturer's name or mark, the
reinforcement size or designation and the cast mark as appropriate. Upon
delivery to the Site, the Engineer may require the Contractor to carry out
conformity tests on further samples at a laboratory nominated by the Engineer.
Approximately one sample shall be tested from each 50 tons of reinforcement
delivered to the Site. Any steel which as a result of the conformity tests, does not
comply with the foregoing specification, will be rejected and shall be removed
from the Site without delay.
PART Ill:
3.1
EXECUTION
3.1.1
Bars shall be cut and bent cold, unless otherwise permitted by
the Engineer, to dimensions and shapes as shown on the Drawings. Bars
partially embedded in concrete shall not be site bent except as shown on the
Drawings or with the approval of the Engineer.
3.1.2
Stirrups and tie bars in Grade SR 24 shall be bent around a pin
having a diameter not less than four times the minimum bar diameter.
3.1.3
Bends for other bars shall be made around a pin having a diameter
not less than 12 times the minimum bar diameter except for bars larger than 30
mm in which case the bends shall be made around a pin of eight bar diameters.
to American
Concrete
Institute
3.1.5 High tensile steel reinforcement bar must not be re-bent or straightened
on site.
3.2
Technical Specifications
4-2: Reinforcement
3.2.1
All bar reinforcement shall be placed, supported, and secured before
the beginning of concreting operations. The reinforcement shall be checked and
approved by the Engineer before placement of concrete begins. The relation
between the minimum spacing of bars and the maximum size of aggregate shall
be as follows unless otherwise stated by the Engineer. The minimum clear
distance between two bars in a beam or column shall not be less than the
diameter of the bar or 25 mm or the largest size of aggregate plus 1O mm
whichever is the greatest. Laying or driving bars into the concrete after
placement shall not be permitted.
3.2.2
All horizontal reinforcement shall be supported on metal supports or
mortar blocks of approved shape with the wires embedded in them. Supports,
which are in contact with the external face of the concrete will all be mortar
blocks. The use of small stones or wood blocks shall not be permitted.
3.2.3
The reinforcement shall be held securely in place at the exact
position and at the exact spacing as indicated on the Drawings by the use of wire
ties at bar intersections, supports and spacer blocks. Wire ties shall be securely
tied and folded so that they do not project beyond the planes formed by the
reinforcing bars. The adequacy of the supports and ties to secure the
reinforcement properly shall be subjected to the approval of the Engineer.
3.2.4
The number, size, form and position of all steel reinforcing bars, ties,
links, stirrups and other parts of the reinforcement shall be in exact accordance
with the Drawings. They shall be kept in the correct position and with the
required cover without displacement during the process of compacting the
concrete in place in a manner approved by the Engineer. The Contractor shall
provide all necessary distance pieces and spacer bars to maintain the
reinforcement in the correct position. The type of distance pieces shall be subject
to the approval of the Engineer.
3.2.5
Any tie, link or stirrup connecting the bars shall be taut so that the
bars are properly braced and the inside of hooks and bends shall be in actual
contact with the bars around which they are intended to fit.
3.3
Splicing
3.3.1
No splicing shall be made in reinforcement except where shown on
the Drawings and/or shop drawings approved by the Engineer. Splicing of steel
bar reinforcement shall be made in accordance with ACI 315.
3.3.2
Reinforcement shall be furnished in the lengths indicated on the
Drawings. Lap splicing except where shown on the Drawings shall not be
permitted without written approval from the Engineer. If additional lap splices are
used the additional weight occasioned by such lap splices shall not be included in
the measurement of reinforcement for payment.
4-2 /8
Technical Specifications
4-2: Reinforcement
3.3.3
All splices for high yield steel bars shall have a lap length of not less
than 40 diameters of the smaller bar or as shown on the Drawings. All splices for
mild steel bars shall have a lap length of not less than 40 diameters of the bars
when hook is used and 50 diameters for bars without hook or as shown on the
Drawings. Lap splices shall generally be located at points of minimum tensile
strength. Except where otherwise shown on the Drawings lap splices shall be
made with the bars placed in contact and wired securely together.
3.3.4 Welding of reinforcing steel may be done only if approved in writing by the
Engineer.
Before the Engineer approves of welding, the Contractor shall submit such
samples as the Engineer may require for testing and make allowance for the time
elapsing before test results are available. Welding of high yield bars in places of
variable tension shall not be permitted. Welding shall be done only on the
weldable reinforcing steel only.
3.3.5
Welding of reinforcement steel and steel parts shall conform to the
Structural Welding Code AWS 01.4 of the American Welding Society and
applicable special provisions and shall only be done where shown, specified, or
permitted by the Engineer. Every welder shall posses a welding certificate issued
by recognized institutionsapproved institute. The certificate must be available for
inspection by the Engineer.
3.3.6
Mechanical couplers may only be used with prior written approval of
the Engineer and shall in general comply with ACl-318 M-08 Article 12.14.3 and
the requirements below.
All couplers shall be of a type which are simple to be installed and can be
confirmed by quick visual inspection. Couplers shall be correctly installed and
achieve the required full strength connections. Couplers for tension joint shall
develop full tensile strength of the bar away from the joint. Threaded system
shall have prallel metric threads to facilitate fixing with no reduction in crosssection area at the joint location. Tapered thread system are not permitted.
All couplers shall be cleanly stamped with the batch or heat number. This
number shall be traceable to the origin cast. The relevant material mill
certificates for couplers are to be submitted with each delivery. The
certificates shall show the salient material properties of the couplers.
For threaded systems every prepared bar end shall undergo a load test prior to
leaving the supplier's workshop. Minimum test loading shall be to 75% of the
characteristic strength and maximum 100% of the characteristic strength. A
positive indication shall be stamped on the rebar to indicate that this operation
has been carried out.
4-2 /8
Technical Specifications
4-2: Reinforcement
Any special tools and equipment required for use with the couplers shall be as
recommended by Manufacturer for the accepted couplers. Such tools and
equipment shall be serviced and calibrated at intervals recommended by the
Manufacturer. The Contractor shall retain documentation in respect of servicing
and calibration for inspection by the Engineer.
Each couplers shall be visually examined prior to use to ensure the absence of
rust and of any foreign material on the inside surface. All completed couplers
shall be inspected and verified in accordance with the Contractor's accepted
method statement. Couplers that do not meet the acceptance standards shall be
completely removed and the bars re- connected as required.
The Contractor shall submit to the Engineer for his acceptance particularly the
proposed materials and methods of mechanical couplers installation including
the manufacturer's literature.
3.4
Substitution
3.4.1
Substitution of different size bars shall be permitted only with
specific authorization by the Engineer. If steel is substituted, it shall have a crosssectional area equivalent to the design area, or larger. The additional weight
occasioned by such substitution shall not be included in the measurement of
reinforcement for payment.
3.4.2
The Contractor shall provide, in the case of substitutions, at his own
expense and to the approval of the Engineer working drawings of all
reinforcement accompanied by bending schedules and copies of orders placed
for bars.
3.5
Bundled Bars
Where bundled bars are specified on the Drawings, they shall be placed in the
closet possible contact to act as a unit and shall be tightly bound by binding wire,
at centers of not more than 24 diameters of the smallest bar in the bundle.
3.6
Projecting Reinforcement
Where shown on the Drawings, steel reinforcement shall be left projecting for the
purpose of bonding or splicing on subsequent work. Care shall be taken to avoid
damage to the bars after they have been set and any damage to the bars or
their setting shall be repaired by the Contractor at his own expense.
Projecting reinforcement which, in the opinion of the Engineer, requires
protection from corrosion shall be coated with cement slurry or other materials
as directed by the Engineer.
4-2 /8
Technical Specifications
4-2: Reinforcement
Where shown on the Drawings, dowels shall be wrapped with bituminous felt or
other approved material to prevent bond.
Projecting vertical bars which might be hazardous to human health shall be
adequately shielded.
3.7
3.8
Cover to Reinforcement
= 50 mm
= 38 mm
= 50 mm
= 38 mm
END OF SECTION
4-2 /8
Technical Specifications
4-2: Reinforcement