Energy

Yield
Forecast
PV Plant Giurgiu 28 MWp

TV SD Czech
s.r.o.

TV SD Czech s.r.o.
Modansk 96a
147 00 Prague 4
Czech Republic

Evidence number of inspection report


05.474.904
Issued by TV SD Czech s.r.o.

Energy Yield Forecast of


Photovoltaic Power Plant Giurgiu
by PVSYST software

Customer:

Samsung C&T Deutschland GmbH

Order of:

2011-11-29

Evaluated plant:
Location:
Installed capacity:
Year of construction:

PVP Giurgiu
Giurgiu, Romania
28 MWp
2011

Cont ent:

Overview ........................................................................................................................................................ 4
1.

Location .................................................................................................................................................. 4

2.

Input values ........................................................................................................................................... 4


3.1.

Climatology data ........................................................................................................................... 5

3.2.

Shading .......................................................................................................................................... 5

3.3.

Soiling ............................................................................................................................................. 6

3.4.

Mismatch loss................................................................................................................................ 6

3.5.

Technology .................................................................................................................................... 6

3.6.

Calculation does not consider..................................................................................................... 7

4.

Output Value Yield forecast ............................................................................................................. 7

5.

Disclaimer ............................................................................................................................................ 10

6.

Conclusion ........................................................................................................................................... 10

Lis t of fi gu re s:

Fig. 1 Map of global irradiation (source: Meteonorm).................................................................................... 4


Fig. 2 Map of locality (source: Google Map) ................................................................................................... 4
Fig. 3 Comparison of irradiation, source of different databases..................................................................... 5
Fig. 4 Loss due to fading by previous rows ...................................................................................................... 6
Fig. 5 Dotted line fading shape of previous rows ......................................................................................... 6
Fig. 6 Design of shading limit angle 17,7 ........................................................................................................ 7
Fig. 7 Summary of energy yield calculation (based on Meteonorm database) .............................................. 8
Fig. 8 Expected Losses (based on Meteonorm database) ............................................................................... 8
Fig. 9 Summary of energy yield calculation (based on: CM SAF-PVGIS database) .......................................... 9
Fig. 10 Expected Losses (based on CM SAF-PVGIS database) ......................................................................... 9

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 2 of 11

Lis t of a pp end ix e s:

1.

PVSYST report

Doc um ent s pr ov id ed:

Electrical design
Situation schema
Datasheet of inverter, transformer, PV modules
Photo documentation
Filled TS input form

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 3 of 11

Overview
The report deals with yield forecast of projected photovoltaic plant Giurgiu 28 MWp which is
designed as a centralized system (30 inverters 800 kW AC) with fixed module mounting and
large space between the rows which aims to minimize shading losses.
This report includes PVSYST output as well. It briefly describes the input assumptions and
interprets the result of the calculation. PVSYST output is attached in appendix.
(Calculation is based on data provided by customer, 15.12.2011)

1. Location
Location: Giurgiu, Romania
GPS: Latitude [] = 43,8, Longitude [] = 25,9
Altitude: 23 m above sea level
Module area: 197 881 m2
The land is flat with no slope without near obstacles. Far horizon is low and its shading does not
influence considerably the calculation.

Fig. 1 Map of global irradiation (source: Meteonorm)

Fig. 2 Map of locality (source: Google Map)

2. Input values
Input values are described at PVSYST report, page 1,2 (simulation parameters)

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 4 of 11

3.1. Climatology data


The global solar radiation data was generated at Meteonorm database. Meteonorm primarily
contains data from meteorological stations (also satellite data) measured in the period 1981
2000. Generated reference data was interpolated from nearest available weather stations:
Bucuresti (74 km), Pleven (116 km), Craiova (166 km). Also other irradiation data source was
checked (NASA, PVGIS). PVGIS is very near to the Meteonorm data with the difference only less
than 1,5%. For covering timeline from 2001 to 2010 the Climate SAF-PVGIS satellite data have
been taken into consideration, see Fig. 3.
Month
January
February
March
April
May
June
July
August
September
October
November
December
Total

METEONORM
[kWh/m2]
43
64
106
142
180
191
197
174
127
89
48
36
1397

CM SAF-PVGIS
[kWh/m2]
39
65
113
152
193
203
212
190
122
87
49
31
1457

Fig. 3 Comparison of irradiation, source of different databases

3.2. Shading
On the north side there is forest vegetation. This obstacle have no significant effect on power
output. Far horizon is low and its shading has minimal influence on the calculation. Therefore the
simulation counts with no close obstacles. But in case of fixed mounted system there is an effect
of self-shading caused by previous row of modules. The loss is estimated at 2,4 % by
considering of sun shading limit angle 17,66, pitch 7.50 m and titled plane of modules 25. see
Fig. 4 and Fig. 5. Expected albedo is 20%.

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 5 of 11

Fig. 4 Loss due to shading by previous rows

Fig. 5 Dotted line shading shape of previous rows

3.3. Soiling
There are considered losses due to snow coverage during winter time, air pollution and losses
caused by dust layer. Following table describes concrete values for each month. These losses
were based on expert estimates stemming from the experience of this issue. The value of such
losses may depend on weather conditions changes and frequency of cleaning panels.

3.4. Mismatch loss


The modules are not sorted according to Isc, to avoid large mismatch losses. There are six types
(power and manufacture) of modules in PV Plant distributed to thirty inverters. Because of
positive tolerance of panels, we expect 0% loss of module quality and 0.5% for mismatch losses
per year because of sorting panels (Isc).

3.5. Technology
PV plant consists of 118 800 (28 472 kWp) modules on fixed mounted construction system.
(multi-row system)
Construction : azimuth 0,slope of modules 25, PV modules vertically in 2 rows above each. A
sun shading limit angle 17,66.

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 6 of 11

Fig. 6 Design of shading limit angle 17,7

Main components:
PV modules: AUO, EcoDuo PM235P00, 235 Wp, 15 840 pcs
AUO, EcoDuo PM240P00, 240 Wp, 31 680 pcs
AUO, EcoDuo PM245P00, 245 Wp, 11 880 pcs
S-Energy, SM-235-PC8, 235 Wp, 3 722 pcs
S-Energy, SM-240-PC8, 240 Wp, 7 603 pcs
S-Energy, SM-245-PC8, 245 Wp, 2 911 pcs
Inverters: SMA, Sunny Central 800CP, European efficiency 98,4%, 30 pcs
Transformers: SMA 64-05845, 1600 kVA, 15 pcs
Wiring: Expected losses at side DC and AC = up 1,1%.

3.6. Calculation does not consider


Lower production due to broken technology
Grid voltage fluctuation
Degradation of modules efficiency in the next years (average 0,4 0,8% per year)
Climate changes calculation expect average solar radiance described in chapter 3.1

4. Output Value Yield forecast


For the yield calculation the simulation software PVSYST 5.53-2 was used. The calculation was
done on an hourly basis. PVSYST report describes result on page 4.
Configuration design:
Total peak power: 28 472 kWp

24 modules in series (strings), 4 950 strings, 30 inverters

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 7 of 11

GlobHor - Global incident in horizontal plane 1 397 kWh/m2


GlobInc Global incidentin coll. plane 1 560 kWh/m2
E_Grid Energy injected into grid 36 657 MWh/year
PR performance ratio 82.5 %

Fig. 7 Summary of energy yield calculation (based on Meteonorm database)

Fig. 8 Expected Losses (based on Meteonorm database)

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 8 of 11

GlobHor - Global incident in horizontal plane 1 457 kWh/m2


GlobInc Global incidentin coll. plane 1 617 kWh/m2
E_Grid Energy injected into grid 38 124 MWh/year
PR performance ratio 82.8%

Fig. 9 Summary of energy yield calculation (based on: CM SAF-PVGIS database)

Fig. 10 Expected Losses (based on CM SAF-PVGIS database)

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 9 of 11

5. Disclaimer
This yield forecast analysis of the considered power plant was made on the base of available
knowledge on the considered subject and theoretical and practical knowledge of photovoltaic
technologies. The data was processed with maximum professionalism. However, we cannot
accept legal responsibility for errors or discrepancies.

6. Conclusion
The result of annual yield of projected PV system Giurgiu 28 MWp for the first year is calculated
as 36 657 MWh/year (PR = 82,5%) based on solar radiation average of years 1981 2000
Meteonorm database and 38 124 MWh/year (PR = 82,8%) based on solar radiation average of
years 2001 2010 Climate SAF-PVGIS database. Specific production based on Meteonorm
database is 1287 kWh/kWp/year. Specific production based on Climate SAF-PVGIS database is
1339 kWh/kWp/year.
Note: in specific climatic conditions (-4C, STC) Voc of array can be greater than the inverter
absolute maximum input voltage.

The site is considered in each suitable for PV plant.


Our control calculation is designed to reflect the averages of solar radiation, thus ignoring the
reserve for possible annual fluctuations of solar radiation. For any financial model linked to that
value, we recommend to calculate with a few percent tolerance.
For realization of this project it is recommended to install system for measuring weather exposure
and temperature in order to compare sun radiation and real production. Daily comparison of
these data will lead to the definition of defects and will minimize system losses.

In Prague, Czech Republic, on December 15, 2011

Author:

Ing. Jan Vondrovsk

Branch manager:

Ing. Miloslav Vomoil

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 10 of 11

Appendix
1. PVSYST report Meteonorm database
2. PVSYST report Climate SAF-PVGIS database

Inspection report: 05.474.904


F-Q-003-2 (Samsung C&T Deutschland GmbH)

page 11 of 11

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 1/5

Grid-Connected System: Simulation parameters


Project :

Giurgiu_METEONORM

Geographical Site

Giurgiu

Situation
Time defined as

Latitude
Legal Time
Albedo

Country Romania
43.9N
Time zone UT+2
0.20

Meteo data :

Giurgiu, Meteonorm SYN File

Simulation variant :

New simulation variant


Simulation date

Longitude 25.9E
Altitude 23 m

15/12/11 15h46

Simulation parameters
Collector Plane Orientation
180Sheds
Inactive band
Shading limit angle
Shadings electrical effect
Horizon
Near Shadings

Tilt
Pitch
Top
Gamma
Cell size
Average Height

25
7.50 m
0.00 m
17.68
15.6cm

Azimuth 0
Collector width
Bottom
Occupation Ratio
Strings in width

3.36 m
0.00 m
44.8 %
2

0.9

No Shadings

PV Arrays Characteristics (6 kinds of array defined )


Array#1 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

PM240P00_235
AUO
24 modules
In parallel 660 strings
15840
Unit Nom. Power 235 Wp
3722 kWp At operating cond. 3335 kWp (50C)
643 V
I mpp

Array#2 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

PM240P00_240
AUO
24 modules
In parallel 1320 strings
31680
Unit Nom. Power 240 Wp
7603 kWp At operating cond. 6787 kWp (50C)
648 V
I mpp

Array#3 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

PM240P00_245
AUO
24 modules
In parallel 495 strings
11880
Unit Nom. Power 245 Wp
2911 kWp At operating cond. 2589 kWp (50C)
653 V
I mpp

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

SM-235PC8
S-Energy
24 modules
In parallel 660 strings
15840
Unit Nom. Power 235 Wp
3722 kWp At operating cond. 3268 kWp (50C)
632 V
I mpp

Array#4 : PV module

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 2/5

Grid-Connected System: Simulation parameters (continued)


Array#5 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

SM-240PC8
S-Energy
24 modules
In parallel 1320 strings
31680
Unit Nom. Power 240 Wp
7603 kWp At operating cond. 6696 kWp (50C)
640 V
I mpp

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

SM-245PC8
S-Energy
24 modules
In parallel 495 strings
11880
Unit Nom. Power 245 Wp
2911 kWp At operating cond. 2562 kWp (50C)
647 V
I mpp

Array#6 : PV module

Total

Arrays global power

Nominal (STC)
Module area

Total 118800 modules


Cell area 173481 m

28472 kWp
197881 m

Inverter

Model
Manufacturer
Operating Voltage

Array#1:
Array#2:
Array#3:
Array#4:
Array#5:
Array#6:

Number of Inverter
Number of Inverter
Number of Inverter
Number of Inverter
Number of Inverter
Number of Inverter

4.0
8.0
3
4.0
8.0
3

Total Power
Total Power
Total Power
Total Power
Total Power
Total Power

Total

Number of Inverter

30

Total Power 24000 kW AC

Sunny Central 800CP


SMA
570-820 V
Unit Nom. Power 800 kW AC

PV Array loss factors


Thermal Loss factor
Uc (const) 29.0 W/mK
Uv (wind)
=> Nominal Oper. Coll. Temp. (G=800 W/m, Tamb=20C, Wind=1 m/s.)
NOCT
Wiring Ohmic Loss

Array Soiling Losses

Array#1
Array#2
Array#3
Array#4
Array#5
Array#6
Global
Feb.

Mar.

Apr.

May

June

July

4.0%

3.0%

2.0%

1.0%

1.0%

1.0%

1.0%

0.0 W/mK / m/s


45 C
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC

Loss
Fraction
1.0
Aug.
Sep.
Oct.%
1.0%

1.0%

AC
AC
AC
AC
AC
AC

1.0%

Nov.

Dec.

1.0%

3.0%

IAM =

Loss Fraction 0.0 %


Loss Fraction 0.5 % at MPP
1 - bo (1/cos i - 1) bo Parameter 0.05

Inverter voltage
Wires
Iron loss
Resistive/Inductive losses

360 Vac tri


13 m 3x30000 mm
Loss Fraction 0.2 % at STC
8401 W
Loss Fraction 0.0 % at STC
0.0 mOhm
Loss Fraction 1.1 % at STC

System loss factors


AC wire loss inverter to transfo

User's needs :

Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction

Jan.

Module Quality Loss


Module Mismatch Losses
Incidence effect, ASHRAE parametrization

External transformer

1.4 mOhm
0.69 mOhm
1.8 mOhm
1.4 mOhm
0.69 mOhm
1.9 mOhm

3200 kW
6400 kW
2400 kW
3200 kW
6400 kW
2400 kW

Unlimited load (grid)

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 3/5

Grid-Connected System: Horizon definition


Project :

Giurgiu_METEONORM

Simulation variant :

New simulation variant


System type
Average Height
Sheds disposition, tilt
Model
Model
Model
Model
Model
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Main system parameters


Horizon
PV Field Orientation
PV modules
PV modules
PV modules
PV modules
PV modules
PV modules
PV Array
Inverter
Inverter pack
User's needs
Horizon

Height []
Azimuth []
Height []
Azimuth []
Height []
Azimuth []

1.0
-119
0.3
-12
0.0
73

0.6
-119
0.0
4
0.0
82

1.0
-115
0.0
6
0.0
88

Grid-Connected
0.9
25
azimuth
PM240P00_235
Pnom
PM240P00_240
Pnom
PM240P00_245
Pnom
SM-235PC8
Pnom
SM-240PC8
Pnom
SM-245PC8
Pnom
118800
Pnom total
Sunny Central 800CP
Pnom
30.0
Pnom total

Average Height
Albedo Factor

0.9
100 %

1.0
-102
0.0
10
0.0
90

1.4
-94
0.0
24
0.0
97

1.4
-98
0.0
13
0.0
94

0
235 Wp
240 Wp
245 Wp
235 Wp
240 Wp
245 Wp
28472 kWp
800 kW ac
24000 kW ac

Diffuse Factor 0.99


Albedo Fraction 0.95
1.0
-90
0.0
41
0.0
103

0.6
-79
0.0
50
0.3
109

2.2
-55
0.0
58
1.8
112

1.8
-45
0.0
58
2.2
112

3.8
-35
0.0
61
3.0
117

Suneye horizon line


90
Shading limit, angle =17.7
Shading 20 %
Shading 40 %

1: 22 june
2: 22 may - 23 july
3: 20 apr - 23 aug
4: 20 mar - 23 sep
5: 21 feb - 23 oct
6: 19 jan - 22 nov
7: 22 december

75
12h

13h

11h

14h
60
3

10h
Sun height []

15h
9h

45

4
16h

8h

5
17h

30
6

7h

15

18h

6h
19h

Behind
the plane
0
-120

Behind
the plane
-90

-60

-30

0
Azimuth []

30

60

90

120

3.8
-21
0.0
67
3.0
119

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 4/5

Grid-Connected System: Main results


Project :

Giurgiu_METEONORM

Simulation variant :

New simulation variant


System type
Average Height
Sheds disposition, tilt
Model
Model
Model
Model
Model
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Grid-Connected
0.9
25
azimuth
PM240P00_235
Pnom
PM240P00_240
Pnom
PM240P00_245
Pnom
SM-235PC8
Pnom
SM-240PC8
Pnom
SM-245PC8
Pnom
118800
Pnom total
Sunny Central 800CP
Pnom
30.0
Pnom total

Produced Energy
Performance Ratio PR

36657 MWh/year Specific prod.


82.5 %

Main system parameters


Horizon
PV Field Orientation
PV modules
PV modules
PV modules
PV modules
PV modules
PV modules
PV Array
Inverter
Inverter pack
User's needs
Main simulation results
System Production

Normalized productions (per installed kWp): Nominal power 28472 kWp

1287 kWh/kWp/year

Performance Ratio PR

1.0

PR : Performance Ratio (Yf / Yr) : 0.825

Lc : Collection Loss (PV-array losses)


0.66 kWh/kWp/day
Ls : System Loss (inverter, ...)
0.09 kWh/kWp/day
Yf : Produced useful energy (inverter output) 3.53 kWh/kWp/day

0
235 Wp
240 Wp
245 Wp
235 Wp
240 Wp
245 Wp
28472 kWp
800 kW ac
24000 kW ac

Performance Ratio PR

Normalized Energy [kWh/kWp/day]

0.8
6

0.6

0.4

2
0.2
1

Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

Nov

0.0

Dec

Jan

Feb

Mar

Apr

May

Jun

Jul

New simulation variant


Balances and main results

January

GlobHor

T Amb

GlobInc

GlobEff

EArray

E_Grid

EffArrR

kWh/m

kWh/m

kWh/m

MWh

MWh

EffSysR
%

43.4

-0.40

63.7

58.4

1568

1532

12.44

12.15

February

64.0

2.65

83.6

78.9

2124

2077

12.84

12.55

March

105.7

7.39

127.1

121.0

3182

3105

12.65

12.35

April

141.9

12.31

154.0

145.7

3809

3719

12.50

12.21

May

179.6

18.98

180.2

170.3

4287

4185

12.02

11.74

June

191.4

22.10

186.8

176.6

4372

4263

11.83

11.53

July

197.0

24.67

194.5

184.1

4494

4384

11.68

11.39

August

173.5

24.32

183.9

174.5

4260

4159

11.71

11.43

September

127.1

17.81

148.5

141.2

3585

3499

12.20

11.91

October

88.7

12.88

115.3

109.2

2848

2783

12.49

12.20

November

48.0

6.86

67.3

63.1

1687

1646

12.67

12.37

December

36.2

0.78

55.1

49.4

1333

1302

12.23

11.94

1396.5

12.58

1559.9

1472.5

37552

36657

12.17

11.88

Year
Legends:

GlobHor

Horizontal global irradiation

EArray

Effective energy at the output of the array

T Amb

Ambient Temperature

E_Grid

Energy injected into grid

GlobInc

Global incident in coll. plane

EffArrR

Effic. Eout array / rough area

GlobEff

Effective Global, corr. for IAM and shadings

EffSysR

Effic. Eout system / rough area

Aug

Sep

Oct

Nov

Dec

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 5/5

Grid-Connected System: Loss diagram


Project :

Giurgiu_METEONORM

Simulation variant :

New simulation variant

Main system parameters


Horizon
PV Field Orientation
PV modules
PV modules
PV modules
PV modules
PV modules
PV modules
PV Array
Inverter
Inverter pack
User's needs

System type
Average Height
Sheds disposition, tilt
Model
Model
Model
Model
Model
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Grid-Connected
0.9
25
azimuth
PM240P00_235
Pnom
PM240P00_240
Pnom
PM240P00_245
Pnom
SM-235PC8
Pnom
SM-240PC8
Pnom
SM-245PC8
Pnom
118800
Pnom total
Sunny Central 800CP
Pnom
30.0
Pnom total

0
235 Wp
240 Wp
245 Wp
235 Wp
240 Wp
245 Wp
28472 kWp
800 kW ac
24000 kW ac

Loss diagram over the whole year

1397 kWh/m

Horizontal global irradiation


+11.7% Global incident in coll. plane
-0.3% Far Shadings / Horizon
-2.5% Near Shadings
-3.0%

1472 kWh/m * 197881 m coll.

Effective irradiance on collectors

efficiency at STC = 14.45%

PV conversion

42096 MWh

Array nominal energy (at STC effic.)


-4.1%
-4.5%
-1.5%
-0.5%
-0.6%

37567 MWh

PV loss due to irradiance level


PV loss due to temperature
Array Soiling loss
Module array mismatch loss
Ohmic wiring loss
Array virtual energy at MPP

-1.7%
-0.0%
0.0%
0.0%
-0.0%

Inverter Loss during operation (efficiency)


Inverter Loss over nominal inv. power
Inverter Loss due to power threshold
Inverter Loss over nominal inv. voltage
Inverter Loss due to voltage threshold
Available Energy at Inverter Output

-0.1%
-0.6%

AC ohmic loss
External transfo loss

36900 MWh

36657 MWh

IAM factor on global

Energy injected into grid

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 1/5

Grid-Connected System: Simulation parameters


Project :
Geographical Site
Situation
Time defined as

Giurgiu_PVGIS_SAF_PVGIS_SAF
Giurgiu_PVGIS_SAF
Latitude
Legal Time
Albedo

Country Romania

43.9N
Time zone UT+1
0.20

Longitude 25.9E
Altitude 23 m

Meteo data :

Giurgiu_PVGIS_SAF from PVGIS, Synthetic Hourly data

Simulation variant :

New simulation variant


Simulation date

15/12/11 15h39

Simulation parameters
Collector Plane Orientation
180Sheds
Inactive band
Shading limit angle
Shadings electrical effect
Horizon
Near Shadings

Tilt
Pitch
Top
Gamma
Cell size
Average Height

25
7.50 m
0.00 m
17.68
15.6cm

Azimuth 0
Collector width
Bottom
Occupation Ratio
Strings in width

3.36 m
0.00 m
44.8 %
2

0.9

No Shadings

PV Arrays Characteristics (6 kinds of array defined )


Array#1 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

PM240P00_235
AUO
24 modules
In parallel 660 strings
15840
Unit Nom. Power 235 Wp
3722 kWp At operating cond. 3335 kWp (50C)
643 V
I mpp

Array#2 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

PM240P00_240
AUO
24 modules
In parallel 1320 strings
31680
Unit Nom. Power 240 Wp
7603 kWp At operating cond. 6787 kWp (50C)
648 V
I mpp

Array#3 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

PM240P00_245
AUO
24 modules
In parallel 495 strings
11880
Unit Nom. Power 245 Wp
2911 kWp At operating cond. 2589 kWp (50C)
653 V
I mpp

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

SM-235PC8
S-Energy
24 modules
In parallel 660 strings
15840
Unit Nom. Power 235 Wp
3722 kWp At operating cond. 3268 kWp (50C)
632 V
I mpp

Array#4 : PV module

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 2/5

Grid-Connected System: Simulation parameters (continued)


Array#5 : PV module

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

SM-240PC8
S-Energy
24 modules
In parallel 1320 strings
31680
Unit Nom. Power 240 Wp
7603 kWp At operating cond. 6696 kWp (50C)
640 V
I mpp

Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp

SM-245PC8
S-Energy
24 modules
In parallel 495 strings
11880
Unit Nom. Power 245 Wp
2911 kWp At operating cond. 2562 kWp (50C)
647 V
I mpp

Array#6 : PV module

Total

Arrays global power

Nominal (STC)
Module area

Total 118800 modules


Cell area 173481 m

28472 kWp
197881 m

Inverter

Model
Manufacturer
Operating Voltage

Array#1:
Array#2:
Array#3:
Array#4:
Array#5:
Array#6:

Number of Inverter
Number of Inverter
Number of Inverter
Number of Inverter
Number of Inverter
Number of Inverter

4.0
8.0
3
4.0
8.0
3

Total Power
Total Power
Total Power
Total Power
Total Power
Total Power

Total

Number of Inverter

30

Total Power 24000 kW AC

Sunny Central 800CP


SMA
570-820 V
Unit Nom. Power 800 kW AC

PV Array loss factors


Thermal Loss factor
Uc (const) 29.0 W/mK
Uv (wind)
=> Nominal Oper. Coll. Temp. (G=800 W/m, Tamb=20C, Wind=1 m/s.)
NOCT
Wiring Ohmic Loss

Array Soiling Losses

Array#1
Array#2
Array#3
Array#4
Array#5
Array#6
Global
Feb.

Mar.

Apr.

May

June

July

4.0%

3.0%

2.0%

1.0%

1.0%

1.0%

1.0%

0.0 W/mK / m/s


45 C
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC
1.0 % at STC

Loss
Fraction
1.0
Aug.
Sep.
Oct.%
1.0%

1.0%

AC
AC
AC
AC
AC
AC

1.0%

Nov.

Dec.

1.0%

3.0%

IAM =

Loss Fraction 0.0 %


Loss Fraction 0.5 % at MPP
1 - bo (1/cos i - 1) bo Parameter 0.05

Inverter voltage
Wires
Iron loss
Resistive/Inductive losses

360 Vac tri


13 m 3x30000 mm
Loss Fraction 0.2 % at STC
8401 W
Loss Fraction 0.0 % at STC
0.0 mOhm
Loss Fraction 1.1 % at STC

System loss factors


AC wire loss inverter to transfo

User's needs :

Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction
Loss Fraction

Jan.

Module Quality Loss


Module Mismatch Losses
Incidence effect, ASHRAE parametrization

External transformer

1.4 mOhm
0.69 mOhm
1.8 mOhm
1.4 mOhm
0.69 mOhm
1.9 mOhm

3200 kW
6400 kW
2400 kW
3200 kW
6400 kW
2400 kW

Unlimited load (grid)

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 3/5

Grid-Connected System: Horizon definition


Project :

Giurgiu_PVGIS_SAF_PVGIS_SAF

Simulation variant :

New simulation variant


System type
Average Height
Sheds disposition, tilt
Model
Model
Model
Model
Model
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Main system parameters


Horizon
PV Field Orientation
PV modules
PV modules
PV modules
PV modules
PV modules
PV modules
PV Array
Inverter
Inverter pack
User's needs
Horizon

Height []
Azimuth []
Height []
Azimuth []
Height []
Azimuth []

1.0
-119
0.3
-12
0.0
73

0.6
-119
0.0
4
0.0
82

1.0
-115
0.0
6
0.0
88

Grid-Connected
0.9
25
azimuth
PM240P00_235
Pnom
PM240P00_240
Pnom
PM240P00_245
Pnom
SM-235PC8
Pnom
SM-240PC8
Pnom
SM-245PC8
Pnom
118800
Pnom total
Sunny Central 800CP
Pnom
30.0
Pnom total

Average Height
Albedo Factor

0.9
100 %

1.0
-102
0.0
10
0.0
90

1.4
-94
0.0
24
0.0
97

1.4
-98
0.0
13
0.0
94

0
235 Wp
240 Wp
245 Wp
235 Wp
240 Wp
245 Wp
28472 kWp
800 kW ac
24000 kW ac

Diffuse Factor 0.99


Albedo Fraction 0.95
1.0
-90
0.0
41
0.0
103

0.6
-79
0.0
50
0.3
109

2.2
-55
0.0
58
1.8
112

1.8
-45
0.0
58
2.2
112

3.8
-35
0.0
61
3.0
117

Suneye horizon line


90
Shading limit, angle =17.7
Shading 20 %
Shading 40 %

1: 22 june
2: 22 may - 23 july
3: 20 apr - 23 aug
4: 20 mar - 23 sep
5: 21 feb - 23 oct
6: 19 jan - 22 nov
7: 22 december

75
11h

12h

10h

13h
60
3

9h
Sun height []

14h
8h

45

4
15h

7h

5
16h

30
6

6h

15

17h

5h
18h

Behind
the plane
0
-120

Behind
the plane
-90

-60

-30

0
Azimuth []

30

60

90

120

3.8
-21
0.0
67
3.0
119

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 4/5

Grid-Connected System: Main results


Project :

Giurgiu_PVGIS_SAF_PVGIS_SAF

Simulation variant :

New simulation variant


System type
Average Height
Sheds disposition, tilt
Model
Model
Model
Model
Model
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Grid-Connected
0.9
25
azimuth
PM240P00_235
Pnom
PM240P00_240
Pnom
PM240P00_245
Pnom
SM-235PC8
Pnom
SM-240PC8
Pnom
SM-245PC8
Pnom
118800
Pnom total
Sunny Central 800CP
Pnom
30.0
Pnom total

Produced Energy
Performance Ratio PR

38124 MWh/year Specific prod.


82.8 %

Main system parameters


Horizon
PV Field Orientation
PV modules
PV modules
PV modules
PV modules
PV modules
PV modules
PV Array
Inverter
Inverter pack
User's needs
Main simulation results
System Production

Normalized productions (per installed kWp): Nominal power 28472 kWp

1339 kWh/kWp/year

Performance Ratio PR

1.0

PR : Performance Ratio (Yf / Yr) : 0.828

Lc : Collection Loss (PV-array losses)


0.67 kWh/kWp/day
Ls : System Loss (inverter, ...)
0.09 kWh/kWp/day
Yf : Produced useful energy (inverter output) 3.67 kWh/kWp/day

0
235 Wp
240 Wp
245 Wp
235 Wp
240 Wp
245 Wp
28472 kWp
800 kW ac
24000 kW ac

Performance Ratio PR

Normalized Energy [kWh/kWp/day]

0.8
6

0.6

0.4

2
0.2
1

Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

Nov

0.0

Dec

Jan

Feb

Mar

Apr

May

Jun

Jul

New simulation variant


Balances and main results

January

GlobHor

T Amb

GlobInc

GlobEff

EArray

E_Grid

EffArrR

kWh/m

kWh/m

kWh/m

MWh

MWh

EffSysR
%

39.1

-0.60

52.7

48.0

1287

1256

12.34

12.04

February

65.0

2.40

86.3

81.7

2189

2137

12.81

12.51

March

112.5

6.60

135.1

128.1

3421

3342

12.80

12.50

April

152.1

12.20

167.3

159.0

4148

4046

12.53

12.22

May

193.1

18.10

196.1

186.5

4712

4594

12.15

11.84

June

203.4

22.00

198.9

188.8

4677

4562

11.88

11.59

July

212.4

24.10

210.4

200.0

4900

4778

11.77

11.47

August

190.3

23.60

203.8

194.3

4774

4658

11.84

11.55

September

121.8

18.10

140.6

133.3

3399

3320

12.21

11.93

October

87.1

12.90

113.9

107.8

2822

2756

12.52

12.23

November

49.2

6.90

69.9

64.5

1724

1684

12.46

12.17

December

31.3

1.00

41.9

38.0

1016

991

12.24

11.94

1457.3

12.33

1617.0

1530.1

39068

38124

12.21

11.91

Year
Legends:

GlobHor

Horizontal global irradiation

EArray

Effective energy at the output of the array

T Amb

Ambient Temperature

E_Grid

Energy injected into grid

GlobInc

Global incident in coll. plane

EffArrR

Effic. Eout array / rough area

GlobEff

Effective Global, corr. for IAM and shadings

EffSysR

Effic. Eout system / rough area

Aug

Sep

Oct

Nov

Dec

PVSYST V5.53

TUV SUD Czech s.r.o.

15/12/11 Page 5/5

Grid-Connected System: Loss diagram


Project :

Giurgiu_PVGIS_SAF_PVGIS_SAF

Simulation variant :

New simulation variant

Main system parameters


Horizon
PV Field Orientation
PV modules
PV modules
PV modules
PV modules
PV modules
PV modules
PV Array
Inverter
Inverter pack
User's needs

System type
Average Height
Sheds disposition, tilt
Model
Model
Model
Model
Model
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Grid-Connected
0.9
25
azimuth
PM240P00_235
Pnom
PM240P00_240
Pnom
PM240P00_245
Pnom
SM-235PC8
Pnom
SM-240PC8
Pnom
SM-245PC8
Pnom
118800
Pnom total
Sunny Central 800CP
Pnom
30.0
Pnom total

0
235 Wp
240 Wp
245 Wp
235 Wp
240 Wp
245 Wp
28472 kWp
800 kW ac
24000 kW ac

Loss diagram over the whole year

1457 kWh/m

Horizontal global irradiation


+11.0% Global incident in coll. plane
-0.3% Far Shadings / Horizon
-2.3% Near Shadings
-2.9%

1530 kWh/m * 197881 m coll.

Effective irradiance on collectors

efficiency at STC = 14.45%

PV conversion

43743 MWh

Array nominal energy (at STC effic.)


-3.9%
-4.6%
-1.4%
-0.5%
-0.6%

39071 MWh

PV loss due to irradiance level


PV loss due to temperature
Array Soiling loss
Module array mismatch loss
Ohmic wiring loss
Array virtual energy at MPP

-1.8%
-0.0%
0.0%
0.0%
-0.0%

Inverter Loss during operation (efficiency)


Inverter Loss over nominal inv. power
Inverter Loss due to power threshold
Inverter Loss over nominal inv. voltage
Inverter Loss due to voltage threshold
Available Energy at Inverter Output

-0.1%
-0.6%

AC ohmic loss
External transfo loss

38382 MWh

38124 MWh

IAM factor on global

Energy injected into grid