32-TMSS-01, Rev. 0
TABLE OF CONTENTS
1.0
SCOPE
2.0
CROSS REFERENCES
3.0
4.0
32TMSS01R0/DB
General
Switchgear Assembly
Ratings
Indoor Enclosure
Outdoor Enclosure
Primary Bus Conductors and Connections
Power Circuit Breakers
Low Voltage Compartment
Interface
Grounding Switch/Truck
Interlocks and Safety Features
Relays, Meters and Instruments
Instrument Transformers
DC Control Power
Wiring and Terminal Blocks
Device Identification
External Cabling
Grounding
Accessories
Nameplates
Drawings
5.0
TESTS
6.0
DATA SCHEDULE
PAGE NO. 2 OF 35
32-TMSS-01, Rev. 0
1.0
SCOPE
This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of Metalclad Switchgear 11kV, 13.8kV, 33kV or 34.5 kV, intended to be used
in the system of the Saudi Electricity Company, Saudi Arabia.
2.0
CROSS REFERENCES
This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.
This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.
3.0
IEC 60044-1
3.2
IEC 60044-2
Instrument Transformers,
Transformers
3.3
IEC 60051
3.4
IEC 60073
3.5
IEC 60255-21-1
3.6
IEC 62271-200
3.7
IEC 60376
3.8
IEC 60947-5-1
3.9
32TMSS01R0/DB
Part
2:
Inductive
Voltage
PAGE NO. 3 OF 35
3.10
4.0
IEEE C57.13.2
32-TMSS-01, Rev. 0
General
The switchgear shall be air insulated, natural cooled and complete metalclad type for
indoor service and shall be of manufacturer's standard design which meets or exceeds
the requirements of this Specification in all respects.
4.2
Switchgear Assembly
4.2.1
The switchgear assembly shall be of single bus bar type and suitable for
extension at both ends without cutting and drilling. Welding is also
prohibited for field assembly of the cubicles. It shall be possible to
dismantle and remove any middle panel from the switchgear line-up
without dismantling/removing the adjacent switchgear panel.
4.2.2
4.2.3
It shall be possible to move the circuit breaker from service position to test
position and vice versa without opening the panel front door.
4.2.4
The switchgear enclosure, bus bar, bus bar supporting insulators and the
internal barriers shall be adequately rigid and able to withstand short
circuit stresses as demonstrated by test reports of the arc-proof tests of
identical switchgear units.
4.2.5
4.2.6
The switchgear shall have a bus riser transition panel with a removable bus
bar link to effectively isolate the bus-tie breaker.
The removable bus bar link open gap shall have a dielectric withstand
voltage at least 10% in excess of that of the switchgear. Also, sufficient
space and bare bus connectors shall be available at both sides of the bus
bar link, beyond all bolted connections, to facilitate the connection of bus
field grounds and Ductor (Contact Resistance) test leads during
maintenance.
4.3
Ratings
Ratings of the switchgear shall be as specified in Data Schedule.
32TMSS01R0/DB
PAGE NO. 4 OF 35
4.4
32-TMSS-01, Rev. 0
Indoor Enclosure
4.4.1
4.4.2
Each switchgear panel shall be furnished with hinged front door(s) and a
removable, bolted rear panel.
A warning sign shall be fastened by screws or rivets on each rear panel.
The sign shall be written in both Arabic and English, as follows:
""
"DO NOT OPEN THIS PANEL UNLESS THE
GROUNDING SWITCH IS IN ON POSITION".
4.4.3
The door of the low voltage compartment shall have a door stopper to hold
the door in the open position.
4.4.4
The enclosure design shall allow clear access to the primary cable
termination compartments only after opening the bolted panel covers. The
entry of primary cables to the enclosure shall be from the rear bottom of
the switchgear. Adequate clearance shall be provided to permit high
voltage testing of the complete installation and of individual cables.
4.4.5
4.5
4.4.6
4.4.7
Outdoor Enclosure
When specified in Data Schedule, an outdoor enclosure shall be provided. The
outdoor enclosure shall protect the indoor type metalclad switchgear from all
weather conditions. It shall be weatherproof and shall have a degree of protection IP
54 per IEC 60529 or equivalent.
32TMSS01R0/DB
PAGE NO. 5 OF 35
4.5.1
32-TMSS-01, Rev. 0
4.6
32TMSS01R0/DB
4.5.2
The outdoor enclosure shall be supplied with double walls (with thermal
insulation in between) on the roof, doors and all sides of the enclosure.
The distance between walls shall be a minimum of 50mm. The exterior
wall shall be not less than 3mm thick steel plate and the interior wall shall
be a minimum of 1.5mm thick steel plate. The thickness may be modified
to provide equivalent strength and deflection, if approved by SEC.
4.5.3
4.5.4
4.6.2
All bus bars and bus bar risers shall be fully insulated for its thermal
rating. Bus bar connections shall have readily removable insulating covers
or molded boots. Connections (tee-off droppers) between circuit breakers
and main bus bars shall have the continuous current rating of the highest
rated circuit breaker.
4.6.3
4.6.4
PAGE NO. 6 OF 35
4.7
32-TMSS-01, Rev. 0
4.6.5
4.6.6
The bus bar and its connections shall be able to withstand the mechanical
stresses under the specified short circuit conditions.
Power circuit breakers shall be 3-pole, single throw, vacuum or SF6 type,
mounted on a draw-out carriage and shall be physically and electrically
interchangeable with others of the same type and rating within the
switchgear assembly and suitable for local and remote control. The circuit
breakers shall comply with IEC 62271-100 or ANSI C37.06. The SF6 gas
shall conform to IEC 60376 or ASTM D2472.
The circuit breaker operating sequence (operating duty cycle) shall be O0.3s-CO-3min.-CO.
4.7.2
32TMSS01R0/DB
4.7.3
4.7.4
Each circuit breaker shall be provided with one (1) closing coil and two (2)
electrically independent trip coils. The tripping mechanism shall operate
correctly when either or both trip coils are energized. Both positive and
negative of the auxiliary voltage shall be switched when a close or
open/trip operation is executed.
4.7.5
Circuit breakers shall be designed so that they cannot be closed unless the
closing spring is fully charged. For SF6 circuit breakers, low pressure of
Date of Approval: December 25, 2006
PAGE NO. 7 OF 35
32-TMSS-01, Rev. 0
SF6 shall initiate an alarm and shall automatically block closing and
tripping of the breaker.
4.8
4.7.6
4.7.7
4.7.8
It shall be possible to test all controls and protection trip while the circuit
breaker is in the test position.
4.7.9
Each breaker shall have not less than two NO and two NC potential-free
auxiliary contacts, mounted on the breaker for remote interlocking service.
Additionally, four spare NO and four spare NC contacts shall be provided
on each breaker for use on SER (Sequence of Events Recorder) and
SCADA. In addition, contacts shall be provided to enable local and remote
indication of the Service/Test/Withdrawal position. Minimum contact
rating shall be 10A at 125V dc.
4.7.10
32TMSS01R0/DB
One (1) Local/Remote selector switch. Provision shall be made for locking
the switch in either position.
PAGE NO. 8 OF 35
4.8.2
32-TMSS-01, Rev. 0
One (1) circuit breaker control switch. The switch shall have three
positions (trip-normal-close) with a spring return to normal and padlocking
facility in the normal position.
The control switch shall follow the convention of closing the circuit
breaker in the clockwise direction.
4.8.3
breaker closed, one for each trip coil adjacent to the control
switch
breaker open, one for closing coil adjacent to the control
switch
For outgoing and station service feeder panels only, the red and green
lights shall be wired in series with the trip and close coils, respectively to
supervise the status of each coil, in accordance with clause 4.12.8.
For incomers and bus tie breakers, the red and green light indications shall
be achieved through the breaker auxiliary switches. The healthiness of the
breaker trip coils shall be monitored via the trip circuit supervision relays
which are located in the control room.
4.8.4
One (1) digital power demand meter (DPDM) for each incoming and
outgoing feeder panel. A voltmeter shall be provided to indicate voltage
for each bus section.
The DPDM shall have three (3) phase display for instantaneous and
maximum demand for Amperes, Volts, Watts, Vars, Watthours and
Varhours. Each quantity shall be selectable with all three phases being
selected and displayed simultaneously.
4.8.5
One (1) ammeter with a 4-position selector switch for each dedicated
station service transformer panel.
4.8.6
One (1) three phase current transducer or three (3) single phase current
transducers for outgoing feeder panels only.
The transducer shall have a current input of 1 or 5A, 60 Hz, with an output
of 0 - 1mA. The accuracy shall be 0.25% or better. The transducer full
scale output shall represent 110% of the nominal current. Metering
transducers shall be of solid-state design.
4.8.7
32TMSS01R0/DB
PAGE NO. 9 OF 35
4.8.8
One (1) 110Vac or 127Vac fluorescent strip light. The light shall be
controlled by toggle or door switch. Switch shall be identified with
engraved or embossed nameplate.
4.8.9
One (1) thermostatically controlled space heater rated 220 Vac and
designed for continuous operation.
4.8.10
One (1) 15A, 110Vac or 127Vac and one (1) 10A, 220 Vac flush type,
parallel slot, grounding type duplex convenient outlets shall be provided in
the incoming and bus-tie breaker panels.
4.8.11
Lot, Nameplates
4.8.12
Lot, Relays and Relay manufacturer's test blocks (see clause 4.12).
SCADA Interposing Relays for Trip and Close.
4.8.13
4.8.14
4.9
a.
b.
c.
Interface
4.9.1
4.9.2
32TMSS01R0/DB
32-TMSS-01, Rev. 0
The bus bar shutters shall be colored red and shall have white
lettering indicating BUS BAR.
b.
The outgoing feeders shall have shutters, colored yellow with black
lettering indicating CABLE.
c.
The bus tie panel both shutters shall be colored red and shall indicate
BUS BAR 1 or BUS BAR 2 in white lettering, as applicable.
PAGE NO. 10 OF 35
32-TMSS-01, Rev. 0
manual plug and receptacle for disconnection. The male contacts shall be
placed on the removable element while the female receptacles on the
stationary structure. Secondary isolating contacts shall be so positioned or
designed to prevent the danger of electric shock when disconnected.
The manual control connector shall be either interlocked or inaccessible to
prevent connection or disconnection of the control circuits when the circuit
breaker is in the service position.
4.10
Grounding Switch/Truck
4.10.1
4.10.2
4.11
a.
b.
c.
d.
e.
32TMSS01R0/DB
PAGE NO. 11 OF 35
32TMSS01R0/DB
32-TMSS-01, Rev. 0
a.
b.
c.
d.
The breaker truck being moved into the service position unless it is
correctly located.
e.
4.11.2
4.11.3
It shall not be possible to withdraw the breaker from its housing beyond
test position unless the spring stored energy mechanism is automatically or
manually discharged. In case of manual discharge, appropriate warning
plate shall be provided to caution the operator to manually discharge the
spring.
4.11.4
4.11.5
4.11.6
Bus bar grounding switch shall be interlocked with the incoming circuit
breaker and bus section breaker as well as with all outgoing breakers on
the respective bus side, such that the grounding switch cannot be closed
unless all associated circuit breakers are open and withdrawn from service
position, and the associated circuit breakers cannot be closed unless the
bus bar grounding switch is open.
4.11.7
The bus bar grounding truck, when used, shall be so interlocked such that
grounding of the bus bar shall not be possible unless the associated
incoming and bus section breaker(s) as well as all the outgoing feeder
PAGE NO. 12 OF 35
32-TMSS-01, Rev. 0
breakers are open and withdrawn from service position. Manufacturer shall
provide evidence in support of this arrangement.
4.12
4.12.2
4.12.3
32TMSS01R0/DB
4.12.4
4.12.5
4.12.6
Upper edge of protective relays and meters shall be no higher than 2.2m to
allow convenient maintenance, inspection, target reset, and testing from
ground level.
4.12.7
4.12.8
For outgoing and station service feeder panels, each indicating light shall
have a current limiting resistor to facilitate replacing the bulb without
activating the respective trip/close coil. The rating of the resistor shall be
selected to provide adequate illumination of the lamp at normal operating
conditions.
PAGE NO. 13 OF 35
32-TMSS-01, Rev. 0
Shorting of the lamp terminals shall not damage the resistor itself or blow
the control circuit fuses (or trip the control circuit MCBs) considering that
maximum DC control voltage is limited to 110% of its nominal rating.
This shall be met by restricting the current passing through the trip coil to
less than 25% of its minimum pick-up current.
Alternatively, LED indicators may be provided.
The trip 1, trip 2, close and spring charge circuit MCBs shall be located at
the switchgear in the LV compartment.
All switchgear MCBs shall have normally open auxiliary contacts. Each
breaker shall have its MCB contacts connected in series with the Trip
Circuit 1 positive supply located on that breaker. Any MCB operation shall
de-energize the breaker DC supervision relay and provide an alarm.
4.13
Instrument Transformers
4.13.1
4.13.2
4.13.3
4.13.4
CTs for bus bar differential and restricted earth fault (REF) relays shall be
of single-ratio type. Other relaying CTs shall be of dual-ratio type.
Metering CTs shall be of single-ratio type.
Relaying and metering accuracy class for standard burdens shall be as
specified in Data Schedule.
32TMSS01R0/DB
4.13.5
4.13.6
PAGE NO. 14 OF 35
32-TMSS-01, Rev. 0
4.13.7
4.13.8
4.13.9
4.14
DC Control Power
Unless otherwise specified, the nominal DC control voltage for closing and tripping
of all circuit breakers shall be 125 Vdc supplied from station batteries. Trip coils shall
operate satisfactorily between 70 Vdc and 140 Vdc and closing coils shall operate
satisfactorily between 90 Vdc and 140 Vdc. For close & trip coil operation in the event
of failure of auxiliary supply, an emergency capacitor tripping device to be provided.
Voltage dropping resistors shall not be used in the trip coil and closing coil circuits.
4.15
32TMSS01R0/DB
All wiring within the switchgear shall be installed and tested at the factory
unless otherwise specified. All wiring shall be heat and flame retardant,
rated 90C maximum operating temperature, type SIS as listed in
ANSI/NFPA 70 or approved equivalent, rated 600/1000V, with insulated,
tinned, stranded annealed copper conductor, and shall not be smaller than
Date of Approval: December 25, 2006
PAGE NO. 15 OF 35
32-TMSS-01, Rev. 0
2.5 mm. The size of all CT secondary leads/circuits shall not be smaller
than 4mm.
For SCADA digital and analog input signals, SOE, Annunciator and
status/alarm signaling circuits wiring size shall not be less than 0.5mm2 up
to the first termination point, only if the associated device cannot
accommodate larger wire sizes. For SCADA Control Output Signals the
wiring size shall not be less than 1.5mm2.
All wires shall be adequately rated for thermal withstand of short circuit
currents, in accordance with back-up tripping time.
4.15.2
VT circuits:
Red
Alarm circuits:
Blue
CT circuits:
Yellow
32TMSS01R0/DB
4.15.3
All wiring shall be made without splices. The control wires shall be multistranded flexible and shall be terminated with size 1 hooked crimps or ring
type terminals. Spade type, pin type or boot lace type crimp terminals are
not acceptable.
4.15.4
Terminal blocks shall be spring loaded type with screw termination for
size-1 hooked type crimps. If a common termination is required between
terminal blocks, preformed wire jumpers or manufactures own shorting
bar can be used. Compatible end stops, end plates, barriers and terminal
block identifiers shall be used. Groups of terminal blocks shall be
identified using engraved labels. The comparative tracking index of
terminal blocks shall be at least 500 per IEC 60112 or equivalent standard.
Date of Approval: December 25, 2006
PAGE NO. 16 OF 35
32-TMSS-01, Rev. 0
Not more than 2 hook type terminations shall be connected to one side of a
terminal block. In special circumstances where wire sizes exceed the
terminal block capability, correctly sized terminal blocks shall be used
after SEC approval.
In all instances, terminal blocks shall be mounted on DIN rails.
4.15.5
4.15.6
4.15.7
32TMSS01R0/DB
All VT circuits shall be provided with sliding link type terminal blocks to
facilitate isolation of VTs from the circuit to perform voltage injection
tests. These terminal blocks shall be clearly marked with phase, function,
core number and ratio.
PAGE NO. 17 OF 35
32-TMSS-01, Rev. 0
4.15.8
4.15.9
Not less than ten percent (10%) spare terminals shall be provided on each
terminal block.
4.15.10
All spare contacts from protective relays or tripping relays shall be wired
to the terminal blocks for future use. At least two (2) spare (2 NO + 2 NC)
contacts of lockout relay shall be wired to the terminal block for future
use.
4.15.11
4.15.12 Cable supports shall be provided for wiring run directly to instruments or
devices. Wiring extensions from raceways or bundles to instruments and
devices shall be neatly formed, securely tied or clamped and supported to
the switchgear framework. Bends in the wiring shall be carefully made in
such a manner that the insulation is not damaged.
4.15.13 Wiring for lights, space heaters and convenience outlets may be run in the
same raceway in individual panels and in rigid or PVC jacketed flexible
conduits between panels. Wiring of meters/relays mounted on doors shall
be mechanically protected.
4.15.14 All internal wiring terminations shall be identified by legible markings at
the device terminals in accordance with the connection diagrams. Each end
of every wire leaving a terminal block shall be identified indicating local
termination point and destination as per Figure 1. All internal wiring shall
have identification showing both locations of termination at each end of the
wire. Markers shall be of ferrule type, permanently marked and shall be
made of material that will not deform or deteriorate and shall withstand a
temperature of 90C. Adhesive type terminal markers are not acceptable.
4.15.15 Where panels are to be shipped in sections and assembled in the field, the
wiring between sections shall be provided preformed. One end of the wire
shall be terminated on terminal block and the other end shall be bundled
and tagged properly.
32TMSS01R0/DB
PAGE NO. 18 OF 35
4.16
4.17
32-TMSS-01, Rev. 0
Device Identification
4.16.1
4.16.2
External Cabling
4.17.1
Power Cables
a.
b.
Terminal lugs for power cables shall be suitable for use with copper
or aluminum conductor material.
Adequate structural supports (including clamps for XLPE cable) for
outgoing feeder terminations inside the extension box and upto cableentry gland plate shall be provided even when such terminations are
provided by others.
32TMSS01R0/DB
PAGE NO. 19 OF 35
32-TMSS-01, Rev. 0
All terminal lugs for power cables shall be of bolted type with two
crimping elements per lug. MV, LV and control cables shall be
marked and painted R-Y-B to identify individual phase with fire
protective paint.
Terminals for conductors 400mm and larger shall be suitable for 4hole NEMA pad, 12mm (1/2 in.) stud. For conductors smaller than
400mm, terminals shall be suitable for 1-hole NEMA pad, 12mm
(1/2in.) stud.
4.17.2
4.18
32TMSS01R0/DB
Control Cables/Wires
a.
b.
Grounding
4.18.1
An uninsulated electrolytic copper grounding bus sized for the rated short
circuit current and running the entire length of the switchgear assembly
shall be provided. Provision shall be made for extending the ground bus at
either end without any need for cutting or drilling the copper bar.
4.18.2
Two (2) solderless type ground connectors shall be provided on the ground
bus, one on each end section of the bus. The ground connectors shall be
suitable for a bare copper ground conductor 120mm thru 240mm.
4.18.3
All hinged doors and panels shall be properly bonded by unspliced flexible
wire or 10mm2 Cu braids.
4.18.4
4.18.5
PAGE NO. 20 OF 35
4.19
32-TMSS-01, Rev. 0
Accessories
The following accessories shall be supplied as applicable :
4.20
32TMSS01R0/DB
4.19.1
One handling device (adjustable trolly) for removing each size of circuit
breaker from the switchgear assembly, which shall be capable of putting
the circuit breaker on the floor.
4.19.2
A set of each relay manufacturers test plugs accessories for relay testing
and protective relay test set and portable test equipment for meters.
4.19.3
Portable device for racking circuit breaker from one position to the other.
Two such devices shall be provided when one line-up of switchgear is
supplied. One device per line-up shall be provided if more than one line-up
is supplied.
4.19.4
4.19.5
One set of high voltage portable testing plugs of continuous current rating
of 200A for insertion into circuit breaker isolating contacts shall be
provided.
4.19.6
4.19.7
Crank lever or equivalent device for manual charging of the springoperated stored energy closing mechanism of the circuit breaker and
closing grounding switch.
4.19.8
Any special tools required for circuit breaker maintenance and relay
adjustments.
Nameplates
4.20.1
The switchgear assembly shall have a "Danger High Voltage" warning sign
written in Arabic and English.
4.20.2
b.
32-TMSS-01, Rev. 0.
PAGE NO. 21 OF 35
32-TMSS-01, Rev. 0
4.20.3
Each circuit breaker shall have a nameplate as per IEC 62271-100 or ANSI
C37.06.
4.20.4
The circuit breaker operating mechanism, CTs, VTs and FT-1 switches
shall also bear nameplates.
Each FT-1 switch shall have a separate nameplate of dimensions 160mm by
44mm. Minimum letter height shall be 12mm for cubicle/circuit labels and
7mm for all other labels.
4.20.5
4.21
The nameplate for the switchgear assembly and the circuit breakers shall be
made of stainless steel. The nameplate shall be fastened by stainless steel
screws or rivets. Other nameplates for CTs, VTs etc. may be made of noncorrodible material other than plastic.
Drawings
The switchgear manufacturer shall supply the following size A drawings as a
minimum:
5.0
4.21.1
4.21.2
4.21.3
4.21.4
4.21.5
AC Schematic.
4.21.6
DC Schematic.
4.21.7
4.21.8
TESTS
5.1
All equipment shall be tested in accordance with the latest applicable IEC or
ANSI/IEEE Standards.
5.1.1
32TMSS01R0/DB
PAGE NO. 22 OF 35
32-TMSS-01, Rev. 0
5.1.2
5.1.3
5.2
b.
c.
b.
c.
The site tests shall be performed on the metal-clad equipment and its
component in accordance with relevant IEC Recommendations & SEC
Commissioning Test Procedures, TCS-P-105.
Tests for relays, meters and instruments may comply with the manufacturer's
standard tests. Relay circuits shall be tested with simulated fault currents for proper
operation.
EQUIPMENT
32TMSS01R0/DB
APPLICABLE STANDARD
Circuit Breakers
Instrument Transformers
Grounding Switches
IEC 62271-102
PAGE NO. 23 OF 35
32-TMSS-01, Rev. 0
32TMSS01R0/DB
PAGE NO. 24 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
Date:
Date:
DESCRIPTION
'A'
3.0
4.0
'B'
'C'
Switchgear Assembly
Switchgear Model Designation
PAGE NO. 25 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.3
DESCRIPTION
'A'
'B'
'C'
Ratings:
Nominal Voltage (kVrms) of Switchgear &
Breaker (11, 13.8, 33 or 34.5)
Design Ambient Temperature
of Switchgear & Breaker (C)
1.2/50s Lightning Impulse Withstand
Voltage of Auxiliary Circuits (kVpeak)
One Minute Power Frequency Withstand
Voltage of Auxiliary Circuits (kVrms)
Maximum Voltage Withstand (Emergency
conditions) of Switchgear & Breaker
(kVrms) (12.1, 15.2, 36.3 or 38)
1.2/50s Lightning Impulse Withstand
Voltage of Switchgear & Breaker:
To ground and between phases (kVpeak)
Across Isolating Distance (kVpeak)
One Minute Power Frequency Withstand
Voltage of Switchgear & Breaker:
To ground and between phases (kVrms)
Across Isolating Distance (kVrms)
Rated Continuous Current of:
Switchgear Incomer Circuit (Arms)
Switchgear Bus Tie Circuit (Arms)
Switchgear Outgoing Feeder Circuit(Arms)
Switchgear Main Bus bar (Arms)
Circuit Breaker (Arms)
Rated Short-time Withstand Current of
Switchgear, & Breaker (kArms)
Short-time current Duration (s)
Rated Peak withstand current of Switchgear
(kApeak)
32TMSS01R0/DB
PAGE NO. 26 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.4
4.5
DESCRIPTION
'C'
Outdoor Enclosure
Yes/No
*
4.7
'B'
4.6
'A'
1.5
5/80
32TMSS01R0/DB
PAGE NO. 27 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.7
DESCRIPTION
'A'
'B'
'C'
Contd.
Closing Time (max) of Breaker (ms)
Arcing Time
Maximum (ms)
minimum
*
*
*
*
PAGE NO. 28 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.7
DESCRIPTION
'A'
'B'
'C'
Contd.
Rated Single Capacitor Bank Breaking
Current, if applicable (Arms)
Rated Capacitor Bank In-rush Making
Current, if applicable (kApeak)
Rated Transient Recovery Voltage for
Terminal Fault (kVpeak)
Operating Mechanism:
Type
Spare Auxiliary Contacts
Total Number of Normally Open
Total Number of Normally Closed
Rated current (Adc)
Rated voltage (Vdc)
Number of close-open operations
that can be performed by the
mechanism before having recharge
Time required to charge
the closing spring (s)
4.8.7
4.8.8
4.8.9
*
*
*
*
*
*
*
Yes/No
Yes/No
32TMSS01R0/DB
PAGE NO. 29 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
DESCRIPTION
4.13
'A'
'B'
'C'
Yes/No
*
*
Instrument Transformers
Type of CT and Make
120
120
*
2.6xIth
*
CT Ratio(s)
Incomer Circuit
Bus Tie Circuit
Outgoing Feeder Circuit
Protection
Metering
Station Transformer
Bus bar Differential
Restricted Earth Fault
32TMSS01R0/DB
PAGE NO. 30 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.13
DESCRIPTION
'A'
'B'
'C'
Contd.
CT Burden(s) (VA)/Resistive burden -Rb
(ohms)
Incomer Circuit
Bus Tie Circuit
Outgoing Feeder Circuit
*
*
*
*
*
PAGE NO. 31 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.13
DESCRIPTION
'A'
'B'
'C'
Contd.
CT Knee point voltage, Vk/ Secondary
limiting e.m.f (Volts)
4.14
VT Burden (VA)
0.5/3P
DC Control Power
Breaker Charging Motor
Rated Voltage (Vdc)
Voltage Range of Operation (Vdc)
Rated Current (Adc)
Maximum Starting Current (Adc)
*
*
*
*
*
*
32TMSS01R0/DB
PAGE NO. 32 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
4.14
DESCRIPTION
'B'
'C'
Contd.
Breaker Tripping Coil
Voltage Range of Operation (Vdc)
Current at rated voltage (Adc)
4.17
'A'
*
*
4.18
Grounding
Copper grounding bus size (mm x mm)
Recommended Clearances:
In front of the Switchgear (mm)
At rear of the Switchgear (mm)
*
*
*
*
*
*
PAGE NO. 33 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
DESCRIPTION
Panel Weight:
Incoming Feeder Panel (kgs.)
Outgoing/Station Service
Transformer (kgs.)
Bus tie Panel (kgs.)
Bus Riser/Metering Panel (kgs.)
5.0
'A'
'B'
'C'
*
*
*
*
TESTS
Optional or Special Test Requirements (if any)
32TMSS01R0/DB
PAGE NO. 34 OF 35
32-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
A.
B.
C.
FEATURES
Actual Manufacturer
of Equipment/Material
PROPOSED
BY
Vendor/Supplier/
Contractor
Official Seal/Stamp
of the Company &
Date
32TMSS01R0/DB
PAGE NO. 35 OF 35