TRANSFORMER
PRESENTATION
By:
M. RIYAS AHAMED
10/19/2015
OBJECTIVE:
The objective of this present work is to investigate the performance and transient behavior
of conventional electromagnetic current during power system switching faults. This work
has been carried out using MATLAB/Simulink simulation tools.
10/19/2015
INTRODUCTION:
Current Transformer:
Current transformers (CT) are important elements of relay protection because they
are the main source of information for the measuring organs of the devices of relay
protection, and the accuracy of the transformation of primary currents by high voltage and
intervening CT determines the reliability of the operation of the entire protection.
10/19/2015
INTRODUCTION:- (cont.)
Transient:
The electrical transients are well known and unavoidable disturbing events that causes severe
problems to the electric power systems. The origin of transients are switching transients,
lightning, and other faults.
10/19/2015
SCOPE OF WORK:
Different types of switching faults are considered for conventional electromagnetic current
transformers (EMCT). The switching faults include symmetrical & unsymmetrical switching, effect
of current transformer secondary opening, and the effect of load switching. The system is modeled
to be a 120KV constant voltage source supplying a distributed load of 100MVA through a
10/19/2015
SIMULATION:
10/19/2015
TESTING:
Effect of Symmetrical & Unsymmetrical switching.
Effect of CT secondary open.
Effect of Load switching.
10/19/2015
2 +2 2
and
If switching takes place in an instant when = 0, the DC component will be zero and the current
wave will be symmetrical.
If the switch is closed when - = /2, the DC component will be maximum and the first peak
of the resultant current i will approach twice the peak of the final steady state current. It results the
unsymmetrical waveform.
10/19/2015
10/19/2015
10
11
12
Output at
Steady state condition
10/19/2015
13
10/19/2015
14
15
16
CONCLUSION
The simulation results have shown that electromagnetic current transformers (EMCT) can suffer
heavily from transient saturation during switching of heavy load and unsymmetrical switching.
Based on this work it is safe to declare that EMCT can be used for normal monitoring and
measurement applications in utility. It is not good for the reliable protection and control
application in high power application.