Customer:

Consultant:
Document Name: Calculation for Induced Voltage
Cable Installation System: Cross Bonding
No. of Core and Cable Size :single core 630Sqmm
Voltage Grade : 38/66Kv
Cable Laying Formation: Flat formation

OPTION DAs per your Hand wirtten sketch


Definitions/Input Parameters :
D' =
59.1 mm
S =
77.5 mm
I =
450 A
Ik3 =
31,500 A
Ik2 =
31,500 A
Ik1/E =
31,500 A
F =
50 s1
w =
314 s1
L =
700 m

Geometric mean sheath diameter


Axial spacing of phases
Continuous / Operating current
Short circuit current (rms) 3pole
Short circuit current (rms) 2pole
Short circuit current (rms) singlepole; Phasetoearth fault current
System frequency
Angular frequency of the system
Length of earthing section

Normal Operation
I =
450 A
E' =
40.74 V/km
E =
28.51 V /mtr

Sheath Voltage(Outer Sheath)

3 phase symmetrical fault (external)


Ik3 =
31,500 A
E' =
2,851 V/km
E =
1,996 V /mtr
Sheath voltage(Outer Sheath)
Phase to Phase fault (External)
I12 =
Ik2
Ik2 =
31,500 A
E1 = E2 = E
E' =
2,851 V/km
E =
1,996 V /mtr
E'3 =

Fault current between phases 1 and 2


phases affected by fault current
Sheath voltage

332 V/km

Single phase to earth fault (external)


Ik1/E =
31,500 A
Data of earth continuity conductor:
Ac =
240 sqmm (Al)
Rc =
0.0754 /km
Resistance of earth continuity conductor
28 mm
Overall diameter of (stranded) earth continuity conductor
gc =
11 mm
Geometric mean radius of earth continuity conductor (ecc)
Sic =
150 mm
Geometric mean spacing(s) between ecc and cable phases (i)
E'
4,493 V/km
E'
3,145V
Sheath voltage
Internal cable faults (most unfavourable case)
Ik1/E =
31,500 A
Data of cable sheath:
Asc =
206 sqmm
Crosssection of cable screen
Rsc =
0.083 /km
Resistance of cable screen
Ash =
0 sqmm
Crosssection of cable sheath
Rsh =
0.000 /km
Resistance of cable sheath
Rs =
0.083 /km
Resistance of combined sheath
E im
8,479 V/km
E re
5,005 V/km
E' =
9,846 V/km
E =
6,892 V
Sheath voltage