Вы находитесь на странице: 1из 110

ATA 26

Fire Protection

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-1
261

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-2
262

ATA 26
A300/A310

FIRE PROTECTION
SYSTEMS - GENERAL

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-3
263

ATA 26
A300/A310

A300 / A310 Fire Detection and Extinguishing Systems


GENERAL
The Lower Cargo Compartments (FORWARD/FWD, AFT and BULK)
have smoke detection, warning and extinguishing features. Smoke
Detectors are located in the ceiling of these compartment areas
(A300/A310). The Detector Unit(s) (A and B Loops) may vary on some
A310 aircraft with either two (A and B Loops) or four loops (two A Loops
and two B Loops) in each of the three lower bay areas (FWD, AFT and
BULK). The A300 Detector Units (A and B Loops) located in all three
cargo bay areas have two loops in each bay area (FWD, AFT and
BULK) provide signals to the Flight Compartment Overhead Panel
433VU (A300) and 448VU (A310). The CARGO COMPT SMOKE DET
Panel 433VU in the Flight Compartment has Fire Bottle Extinguishing
Controls and Indicators (A300/A310). The FWD or AFT (including
BULK) Cargo Compartments can extinguish fire or smother fire within
these sealed areas with two bottles mounted in the FWD Cargo
Compartment (Located forward right hand side of compartment).
The Avionics Compartment has Smoke Detection System(s) for the
following area(s):

The Fire Protection Systems on the FedEx Airbus Fleet are designed to
detect, warn and extinguish a fire in either Main Engine Nacelle Number
1 or 2. Each Engine Fire Protection Fire Detection Control Unit (FDCU)
provides detection and warnings to the Flight Compartment Overhead
Panel. The Fire Warning Module(s) for Engine 1/FIN 39WD and Engine
2/FIN 40WD (A300/A310) have features for detection, control,
extinguishing and testing the respective system. Each FDCU has BITE
features for testing and troubleshooting the respective engine system.
The APU Fire Protection System consist of a Fire Warning Control
Module/FIN 20WG (A300/A310) on the Flight Compartment Overhead
Panel. A Fire Extinguishing Bottle/FIN 11WF (A300/A310) in the
Fuselage Tail Section located on the forward face of Fuselage Frame
(FR95) (A300/A310). The system detects, warns, and extinguishes fire
automatically on the ground and manual mode of extinguishing during
flight conditions. BITE features are provided on the APU FDCU/FIN
13WG located on Shelf 91VU in the Electronic Rack 90VU in the
Avionics Compartment (A300/A310).

The Main Deck Cargo Compartment (MDCC) is equipped with Smoke


Detection System in the Compartment Zones (MID 1, MID 2 and AFT)
(A300/A310). There are no Fire Extinguishing Bottles for the
Compartment Zones. The detection of smoke in the zones provide
signals to Electronic Rack 80VU in the Avionics Compartment to the
affected MDCC Smoke Detector Control Units/FIN Numbers 50WU1
(MID 1), 50WU2 (MID 2) or 50WU3 (AFT) (A300/A310). The units send
signals to the MAIN DECK CARGO SMOKE DET Panel 433VU on the
Flight Compartment Overhead Panel (A300/A310). The MID 1 (FWD)
Zone is equipped with three Fire Extinguisher Bottles for HAZ CANS
(Hazardous Material) which carry flammable/combustible materials for
customer delivery parcels and cargo items (A300/A310).

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Main Bay Smoke Detection (Avionics areas) (Inertial Reference


System (IRS) Number 2 Unit is incorporated within this detection
system)
Cockpit Smoke Detector (Flight Deck areas)
Minimum Equipment Bay Smoke Detector (Electronic Rack
90VU/Shelf 96VU and IRS 1 and 3 Units, these location(s) are
separately sealed compartments)

The Cockpit and Main Bay Smoke Detection System both utilize the
same Warning Light (AVIONICS SMOKE). The Minimum Equipment
Bay Smoke Detection System provides smoke warnings on the Flight
Compartment Overhead Circuit Breaker (CB) Panel 22VU in the
MINIMUM EQUIPT BAY CB area. The System(s) detect smoke in the
Electronic Equipment Cooling Ducts expelled by malfunctioning
equipment boxes due to internal component or electrical failures.

26-4
264

ATA 26
A300/A310

A300/A310 Fire Detection and Extinguishing Systems - Layout

LOWER

Typical Layout A300/A310

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-5
265

ATA 26
A300/A310

Location of Fire Protection System Circuit Breakers


GENERAL DESCRIPTION
The Monitored CBs have GREEN color pull/push caps with imprinted amperage
rating on the cap in white numbers. The Monitored CBs are incorporated in the
ECAM System and on the Maintenance Panels 472VU (C/B MONITOR Panel)
(A300/A310) to provide warnings to crews. The system will be covered in ATA
Chapter 31 of Level 3 Training Manual.

The Fire Protection Systems Circuit Breaker (CB) Panels on the A300 and A310
aircraft have differences on Panel Locations, Panel Numbers and specific CB
function items. The CB Panels are located in the Flight Compartment area.
The A300/A310 CB Panel 22VU has the following CBs on them for the Fire
Protection Systems on each model of aircraft:

The A300-600 aircraft do not have any Configuration 1 and 2 as defined on the
A310-Series in the FedEx Airbus Fleets. The A310-Series aircraft have
Configuration(s) 1 and 2 due to the mix of Airbus Industries Manufacturers Serial
Number (MSN) within the FedEx Airbus Fleets (A300/A310). The following
aircraft have CB Monitoring of the Fire Protection Systems CBs:

FIRE EXTING/CARGO COMPT BOTTLE (BLT) 1 and 2 (Two CBs)


ENG 1 & 2 SQUIB B/BLT 1 & 2 (Two CBs)

Also, located on Panel 22VU in the MIN EQPT BAY SUPPLY CB area are the
following CBs for the A300/A310 aircraft:

A300- 600 Monitored CBs on CB Panel(s):

Panel 22VU

FIRE EXTING-CARGO COMPT BTL 1 and 2 (Two CBs)

ENG FIRE DET/ENG 1 LOOP A and LOOP B (Two CBs) and WARN
(One CB)
ENG FIRE DET/ENG 2 LOOP A and LOOP B (Two CBs) and WARN
(One CB)

Panel 131VU

APU - FIRE EXTING - SQUIB A and B(Two CBs)

APU - FIRE EXTING - SQUIB TEST (One CB)

APU - FIRE EXTING - AUTO EXTING GND TEST (One CB)

The other Fire Protection System Panels on the A300 and A310 aircraft have
different Panel Number(s) and Location of Panel Area(s):

A300-600 Aircraft Registration Numbers N650FE thru N686FE have the


following features on the Distribution Panel 133VU/ENGINES Section
located on the Flight Compartment rear wall area:

ENG 1 & 2/FIRE EXTING SQUIB A BTL 1 and 2

A310-200 Series Aircraft Registration Numbers N401FE thru N454FE have


the following features on the Distribution Panel 123VU/ENGINES Section
located on the Flight Compartment rear wall area :

ENG 1 & 2/FIRE EXTING SQUIB A BTL 1 and 2

Some of the Fire Protection Systems CBs are monitored to detect CBs which
have been Open or Left Open for flight and/or ground condition(s) by
maintenance personnel. The CB Monitoring System performs these functions to
alert flight or ground crews of these conditions. The Airbus Aircraft Maintenance
Manual (AMM) ATA Chapter 31-69-00 provides information on the CB Monitoring
System for Description, Operation, Test and Adjustment.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-6
266

ATA 26
A300/A310

A300 Fire Protection System - Circuit Breakers Location

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-7
267

ATA 26
A300/A310

A310 Fire Protection System - Circuit Breakers Location


A310-200 Series Monitored CBs on CB Panel(s):
Panel 22VU

AVIONICS SMOKE DET - SUPPLY NORM and STBY (ALL)

AVIONICS SMOKE DET - MONITOR (One CB) (ALL)

ENG FIRE DET - ENG 1 and ENG 2 - LOOP A (Two CBs) For A/C 401
405, 407 - 414

ENG FIRE DET - ENG 1 and ENG 2 - LOOP B (Two CBs) For A/C 401
405, 407 - 414

CARGO SMOKE DET PWR SUPPLY (One CB)


ON A/C 415-415, 420 - 430, 442 - 443, 445 - 450, 453 - 499

FIRE EXTING CARGO COMPT BTL 1 and 2 (Two CBs) (ALL)


Panel 123VU

APU FIRE DET LOOP A and B (Two CBs)

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-8
268

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-9
269

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-10
2610

ATA 26
A300/A310

ENGINE FIRE
PROTECTION SYSTEM

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-11
2611

ATA 26
A300/A310

Engine Fire Protection - Controls & Indicators


ENGINE FIRE PROTECTION CONTROLS

1.

Two identical ENG Fire Control Modules (Panels)/FIN 39WD (Engine 1) and
40WD (Engine 2) with fire handles are provided for control of Fire Detection and
Extinguishing.

The lights extinguish when the temperature, detected by the Fire Loops,
decrease below the warning threshold or lowest level which warning
occurred.

Both Engine Fire Protection Systems are energized when the DC ESS BUS is
powered from various sources. Electrical power can be provided for fire
extinguishing operation from the DC NORMAL BUS FIN1PP to the DC ESS BUS
FIN3PP and from the three Aircraft Batteries (BAT 1/FIN 10PE, BAT 2/FIN 9PE
and BAT 3/FIN 8PE). Also, from the AC ESS BUS (AC ESS BUS1/FIN 3XP1)
(A300/A310). The main bus for electrical power is the DC ESS BUS.

Illumination of the ENG 1 or 2 Fire Light is accompanied by ECAM activation


and illumination of the HP FUEL VALVE Red color light on the ENG 1 or 2
FUEL Lever when selected ON.
2.

ENGINE 1 or 2 FIRE HANDLE


The ENG FIRE handles have two positions. The ENG Fire Warning Light is
integrated into the fire handles. The following condition(s) occur during operation
of the fire handle:

IN :

Normal position, mechanically locked and safety lock device


is lockwired with breakaway wire

PULLED

Pulling the fire handle electrically causes the respective engine to


CLOSE the following system component(s):

ENG FUEL LP VALVE

ENG HYD FIRE VALVE

ENG AIR BLD HP VALVE

ENG BLD VALVE (Pressure Regulating Valve)

X FEED Valve (Pneumatic Cross Feed Valve) (If in AUTO position)

PACK VALVE 1 OR 2 (Associated with relevant engine)

WING ANTI ICE VALVES (Two Normal and two Alternate Valves on
each Wing (A300/A310)

ELEC PWR GEN (De-energized)

CRC (Continuous Repetitive Chime) (Silencing CRC and LOOP


Light extinguishing, SQUIB Light illumination)

ENG ANTI ICE VALVE (Valve will CLOSE due to loss of pneumatic
pressure supply. FAULT Light will illuminate.)

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

ENG 1 or 2 FIRE HANDLE


The eight RED color lights in the handle will illuminate independently of
handle position as long as the respective Engine Fire Warning is activated.

26-12
2612

AGENT 1 or 2 PUSHBUTTON
The Pushbutton Switches (PBsw) controls the ignition of the Squibs and
discharging of the Fire Extinguishing Bottle. The PBsw is ARMED only when
the related ENG FIRE Handle is pulled:

MOMENTARILY PRESSED
With ENG FIRE Handle pulled, the selected Squib (AGENT 1 or 2) is
ignited for fire bottle discharge.

RELEASED
The Squibs (Agent 1 or 2) electrical circuit is de-energized.

SQUIB
The White color light illuminates when the ENG FIRE Handle is pulled to
identify the respective AGENT 1 or 2 PBsw to be activated to discharge
the Fire Bottle. During SQUIB TEST, the light illuminates to indicate a
successful test of the squib electrical circuit.

DISCH
The Amber color DISCH Light illuminates when the related Fire
Extinguisher Bottle is discharged.

ATA 26
A300/A310

Engine Fire Protection - Controls & Indicators

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-13
2613

ATA 26
A300/A310

Engine Fire Protection - Controls & Indicators


3.

SQUIB TEST PUSHBUTTON


The Pushbutton Switch (PBsw) controls the test of the squibs in the
Fire Bottle Discharge Heads and their electrical circuits. When
pressed with the respective ENG FIRE Handle in normal position
(IN), the two SQUIB White color lights illuminate if Squibs and Squib
Circuits are operative.

4.

LOOP A or B PUSHBUTTON
The PBsw allows activation of aural and visual warnings when a fire
(FIRE) or fault (LOOP) signal is generated by the Fire Detection
Control Box (FDCU) for the related LOOP:

After a few seconds:


LOOP A Light remains illuminated
LOOP B Light illuminates
ENG FIRE Lights in the ENG FIRE Handle illuminates
HP VALVE Light on the ENG FUEL Lever illuminates, if the
Lever is selected ON
ECAM activation (MASTER WARN Red Light illuminates
and flashes)

ON (PBsw Pressed In)


Aural and visual warnings are activated when a fire or a fault
signal is generated by the FDCU.
OFF (PBsw Released Out)
Aural and visual warnings are inhibited for the related LOOP.
The OFF light illuminates White color.
LOOP A or B
The Amber color light illuminates when the associated PBsw is
selected ON, and a FIRE or FAULT signal is generated by the
FDCU. The light extinguishes when the respective ENG FIRE
Handle is pulled. During LOOP TEST, the light illuminates to
indicate a successful test.
NOTE: The Engine FIRE Warning is also activated when both
PBsw LOOP A and B are selected OFF and the FDCU
generates a fire signal related to both LOOP A and B, or

LOOP TEST PUSHBUTTON


The PBsw controls the test of both Fire Detection Loops and
ENG FIRE and LOOP local warnings. Both PBsw LOOP A and
B must be selected ON, and the respective ENG FIRE Handle
must be in the normal position (IN) for complete system test.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Released Out
Fire Warnings are canceled:
LOOP B Light remains illuminated
ECAM is momentarily activated (MASTER CAUTION
Light illuminates and flashes)
After a few seconds:
LOOP B Light extinguishes

6.

Both PBsw LOOP A and B are selected ON and the FDCU


generates a fault signal related to both LOOP A and B.
5.

Pressed and Held


LOOP and ENG FIRE Warnings are tested in sequence. A
successful test results in the following indications:
LOOP A Light illuminates
ECAM is momentarily activated (MASTER CAUTION Amber
Light illuminates and extinguishes)

The ENG 1 or 2 FUEL Lever controls the HP Shutoff Valve


(HP SOV). A Red Warning Light with imprinted HP VALVE is
integrated into the Lever Handle. The Red color light illuminates and
HP VALVE is visually readable when an Engine Fire Signal is
generated as long as the ENG 1 or 2 FUEL LEVER is selected ON.
Illumination of the light is inhibited when the ENG 1 or 2 FUEL
LEVER is selected OFF.

NOTE: The Red Light will illuminate in three situations: Light Test/Fire
Conditions/Disagreement of HP SOV Position (ON or OFF).

26-14
2614

ATA 26
A300/A310

Engine Fire Protection - Controls & Indicators (continued)

Engine Fire Protection Controls

Engine Fuel Lever Control

4
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-15
2615

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-16
2616

ATA 26
A300/A310

Warning Light Display Panel (WLDP)--some A310s

NOTE
FedEx A310 Aircraft Registration Number(s) N410FE thru N414FE have the
Warning Light Display Panel (WLDP) installed. The WLDPs will remain installed
till further notice per FedEx Aircraft Engineering Department/Memphis.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-17
2617

ATA 26
A300/A310

Engine Fire and Overheat Detection


GENERAL

The Engine Fire Detection System on the A300-600 and A310-Series Engines
has various Loops and Component Locations. Both types of aircraft use the
Systron Donner System (Manufacturer of System type) on the General Electric
(GE) CF6-80C2A5F (FADEC) (A300), GE CF6-80A3 (A310) and Pratt & Whitney
(PW) JT9D-7R4 Series (A310) engines.
The A300 GE Engine Fire Loops consist of four A Loops and four B Loops
that are connected to the Engine Fire Detection Control Unit (FDCU) in parallel:

Upper Left Turbine/Pylon Sensing Element

Upper Right Turbine/Pylon Sensing Element

Lower Turbine Sensing Element

Gearbox Sensing Element


The A310 GE Engine Fire Loops consist of three A Loops and three B Loops
that are connected the the Engine FDCU in parallel:

Pylon Element

Core Element

Fan Element
The A310 PW Engine Fire Loops consist of three A Loops and three B Loops
that are connected to the Engine FDCU in parallel:

Pylon Element

Left Core Element

Right Core Element

Both FDCU Engine 1 and 2 Circuit Breakers (CBs) are located on CB Panel
22VU MIN EQPT BAY SUPPLY area. The CBs for ENG FIRE DET are:

One Control and Indicating Assembly or Module located on the Flight


Compartment Overhead Panel. Engine 1 Fire Control Module/FIN 39WD on
left hand side of the Overhead Panel and Engine 2 Fire Control Module/FIN
40WD (A300/A310) on the right hand side of the Overhead Panel.

The FDCU processes LOOP A (FAULT or FIRE) signals and LOOP B


(FAULT or FIRE) signals through OR and AND Gates symbols within the
FDCU as shown in the illustration. Further processing is through AND and
OR Gates symbols to the LOOP A Pushbutton Switch (PBsw) and LOOP
B PBsw to provide ECAM activation, ENG FIRE Handle Red Lights
activation, HP VALVE ENG Lever Red Light activation during Fire
Conditions.

When a FAULT occurs within the respective Engine 1 or 2 Fire Detection


and Control System, the ECAM Activation provides Fault Warning on the LH
ECAM Display, Amber color MASTER CAUTION Light and a Single Chime
(SC).

During FIRE CONDITIONS on the respective Engine 1 or 2, ECAM


activation occurs for ENG FIRE Handle, HP VALVE ENG Warning Lights
indication within the Fire Handle and HP Lever. The ECAM activation
provides ENGINE FIRE WARNING on LH ECAM Display and ENGINE
Page on RH ECAM Display for information purposes and parameter data or
exceedance of limitations. A Red color MASTER WARN Light illuminates
and CRC is provided for visual indication and aural sound purposes..

The Fire Sensing Element Assemblies connected in parallel and installed on


the engine around Major Engine Modules and Pylon areas which varies on
type engine and model installed on the FedEx Airbus Fleets.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

ENG 1 (FIN 1WD/LOOP A, 3WD/LOOP B and 5WD/WARN)


(A300/A310).
ENG 2 (FIN 2WD/LOOP A, 4WD/LOOP B and 6WD/WARN)
(A300/A310).

DESCRIPTION
Each Engine Fire Protection System is comprised of:

One Fire Detection Control Unit (FDCU) Engine 1/FIN 11WD and Engine
2/FIN 12WD are installed in the Electronic Rack 90VU/Shelf 96VU in the
Minimum Equipment Bay (A300//A310).

26-18
2618

ATA 26
A300/A310

A300 Engine Fire Detection Loops and Installation Location

GE CF6-80C2A5F (FADEC)
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-19
2619

ATA 26
A300/A310

Main Engine 1 and 2 - Fire and Overheat Detection


GENERAL

The Engine Fire Detection System on the A300-600 and A310-Series Engines
has various Loops and Component Locations. Both types of aircraft use the
Systron Donner System (Manufacturer of System type) on the General Electric
(GE) CF6-80C2A5F (FADEC) (A300), GE CF6-80A3 (A310) and Pratt & Whitney
(PW) JT9D-7R4 Series (A310) engines.
The A300 GE Engine Fire Loops consist of four A Loops and four B Loops
that are connected to the Engine Fire Detection Control Unit (FDCU) in parallel:

Upper Left Turbine/Pylon Sensing Element

Upper Right Turbine/Pylon Sensing Element

Lower Turbine Sensing Element

Gearbox Sensing Element


The A310 GE Engine Fire Loops consist of three A Loops and three B Loops
that are connected the the Engine FDCU in parallel:

Pylon Element

Core Element

Fan Element
The A310 PW Engine Fire Loops consist of three A Loops and three B Loops
that are connected to the Engine FDCU in parallel:

Pylon Element

Left Core Element

Right Core Element

Both FDCU Engine 1 and 2 Circuit Breakers (CBs) are located on CB Panel
22VU MIN EQPT BAY SUPPLY area. The CBs for ENG FIRE DET are:

One Control and Indicating Assembly or Module located on the Flight


Compartment Overhead Panel. Engine 1 Fire Control Module/FIN 39WD on
left hand side of the Overhead Panel and Engine 2 Fire Control Module/FIN
40WD (A300/A310) on the right hand side of the Overhead Panel.

The FDCU processes LOOP A (FAULT or FIRE) signals and LOOP B


(FAULT or FIRE) signals through OR and AND Gates symbols within the
FDCU as shown in the illustration. Further processing is through AND and
OR Gates symbols to the LOOP A Pushbutton Switch (PBsw) and LOOP
B PBsw to provide ECAM activation, ENG FIRE Handle Red Lights
activation, HP VALVE ENG Lever Red Light activation during Fire
Conditions.

When a FAULT occurs within the respective Engine 1 or 2 Fire Detection


and Control System, the ECAM Activation provides Fault Warning on the LH
ECAM Display, Amber color MASTER CAUTION Light and a Single Chime
(SC).

During FIRE CONDITIONS on the respective Engine 1 or 2, ECAM


activation occurs for ENG FIRE Handle, HP VALVE ENG Warning Lights
indication within the Fire Handle and HP Lever. The ECAM activation
provides ENGINE FIRE WARNING on LH ECAM Display and ENGINE
Page on RH ECAM Display for information purposes and parameter data or
exceedance of limitations. A Red color MASTER WARN Light illuminates
and CRC is provided for visual indication and aural sound purposes..

The Fire Sensing Element Assemblies connected in parallel and installed on


the engine around Major Engine Modules and Pylon areas which varies on
type engine and model installed on the FedEx Airbus Fleets.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

ENG 1 (FIN 1WD/LOOP A, 3WD/LOOP B and 5WD/WARN)


(A300/A310).
ENG 2 (FIN 2WD/LOOP A, 4WD/LOOP B and 6WD/WARN)
(A300/A310).

DESCRIPTION
Each Engine Fire Protection System is comprised of:

One Fire Detection Control Unit (FDCU) Engine 1/FIN 11WD and Engine
2/FIN 12WD are installed in the Electronic Rack 90VU/Shelf 96VU in the
Minimum Equipment Bay (A300//A310).

26-20
2620

ATA 26
A300/A310

A310 Engine Fire Detection Loops and Installation Location - GE / PW Engines

PW JT9D-7R4
GE CF6-80A3

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-21
2621

ATA 26
A300/A310

Main Engine 1 and 2 Fire Detection Control Unit (FDCU)


DESCRIPTION

Each card has two separated circuits:

The Fire Detection Control Unit (FDCU) process signals from the Fire
Loop Responders and will provide warnings to the Aircraft Fire Warning
Circuits. These circuits control the appropriate crew warning.

The FAULT Circuit which detects any fault occurring at the Fire
Sensing Element/Responder level:
Gas Leakage
Loss of an Electrical Signal

The FIRE Circuit provides the fire warning to the ECAM System for
ECAM Activation in the Flight Compartment.

The FDCU for Engine 1 (FIN 39WD) and 2 (FIN 40WD) are located in
the Electronic Rack 90VU on Shelf 96VU (Minimum Equipment Bay) in
the Avionics Compartment or Bay.
A Test Instructions Placard is provided on the front face of each FDCU
for Detection LOOP troubleshooting purposes or checking the integrity of
the respective A or B LOOPs during BITE Check.
Note
Deactivation of Circuit Breakers are not required to conduct BITE Check
on the FDCUs during testing, refer to the Airbus Maintenance Manual
(AMM) for proper procedures.
The FDCU has a FAULT circuit for each loop, separated from the FIRE
Warning Circuit. This enables the crew to be aware of any Fire Sensing
Element faulty operation:

Fire Sensing Element leakage


Loss of an electrical signal from the responder

The FDCU has only one electrical connector of the NAS 1599 type for
connection to the system.
The FDCU (One per Engine) comprises two Control Cards which
process a signal sent from the Fire Sensing Element Responders.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Note
The APU FIRE Warning is also activated when both Pushbutton
Switches (PBsw) (LOOP A and LOOP B) are selected OFF and the
FDCU generates a fire signal related to both LOOP A and LOOP B.
Test Circuit Used For Maintenance Purposes
In the case of FAULT is noted that the operation of a LOOP Test, it is
possible to discriminate between the FDCU and the Fire Sensing
Elements without disconnecting the Responders.
On the face of the FDCU are installed:

26-22
2622

A Rotary Selector Switch (Spring Loaded Center Return)


Two pairs of luminescent RED and YELLOW diodes (One pair per
LOOP).
YELLOW diode for FAULT Circuit Unit
RED for ALARM (FIRE) Circuit Unit
FDCU Self-Test Operating Instructions

ATA 26
A300/A310

Main Engine 1 and 2 Fire Detection Control Unit (FDCU) - Component Location

FIN 39WD
FIN 40WD

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-23
2623

ATA 26
A300/A310

Main Engine 1 and 2 Fire System - Systron Donner Fire Sensing Element
OPERATION

ALARM-LOCAL OVERHEAT (FIRE)

The Fire Sensing Element for Alarms and Faults Detection has three
different conditions that are monitored for fire warning activation. The
Fire Control Warning Units process the different Alarms and Faults
condition(s) for Engine 1 and 2. The condition after processing is sent to
the ECAM System for further processing in ECAM Activation.

There are various numbers of Fire Sensing Elements on the different


main engines on the FedEx Airbus Fleets. The Systron Donner System
Fire Sensing Elements are utilized on the FedEx Airbus Fleets.

ALARM-AVERAGE OVERHEAT (OVERHEAT)(FIRE) DETECTION

The Sensing Element Responder Alarm Switch is Normally OPEN.


Overheat expands helium gas as shown in the illustration.
When the Sensing Element is exposed to an increase in
temperature over its length, the internal pressure of the helium gas
increases in proportion to the average temperature change.
When the increasing helium gas pressure reaches the setting value,
this will enable the 28 VDC to flow directly back to the respective
FDCU for the Main Engine 1 or 2 that has an alarm or fault
condition. When the temperature decreases, the helium gas
pressure drops or decreases, the Warning Switch (Common C)
OPENS and the warning is cancelled. The cycle of operation may be
repeated indefinitely without changing the Sensing Element and
Responder.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

The Sensing Element Responder Alarm Switch is Normally OPEN.


Fire Releases hydrogen from the Hydride Core as shown in the
illustration.
When the Sensing Element is exposed to Local High Temperature
condition (In case of Flame or Flames) with a greater value than the
alarm preset one (Called Discrete Value). The central core
(Hydrogen Charge Core Material) inside the sensing element gives
off a considerable volume of hydrogen that rapidly increases the
helium internal pressure.
The Warning Switch CLOSES as described in ALARM-OVERHEAT
DETECTION above. As soon as the temperature drops or
decreases below the Discrete Value (Disappearance of Flame), the
central core begins to absorb the hydrogen that has been give off,
the increased helium gas pressure drops or decreases and the
warning is cancelled. The cycle is reversible and may be repeated
indefinitely. The mode corresponds to the classical detection of a
FIRE, exactly the same indications that are given to the crew for
ALARM-OVERHEAT CONDITION.

FAULT STATE-PRESSURE LOSS (PIPE FRACTURE OR CUT-OFF


DUE TO TORCHING FLAME)

26-24
2624

The INTEGRITY SWITCH (Held Closed by Normal Pressure) as


shown in the illustration.
A second Pressure Switch, INTEGRITY SWITCH that is Normally
Closed enables the Fire Sensing Element to be checked for correct
condition(s). The Integrity Switch is connected to the Fire Sensing
Element Self-Monitoring Circuits (FAULT Circuit). It also serves to
check the correct operation of the Fire Detection Loops (A and B
Loops) during preflight checks or as required.

ATA 26
A300/A310

Main Engine 1 and 2 Fire System - Systron Donner Fire Sensing Element

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-25
2625

ATA 26
A300/A310

Main Engine Number 1 and 2 - Fire Extinguishing System

GENERAL
The Fire Extinguishing System is activated when the Fire and Overheat
Detection System detects a fire. The system has two main effects:
To extinguish, at its early stages, any fire occurring in the Engine
Nacelle protected areas following excessive overheat or flammable
fluid leaks that would endanger the aircraft safety.
To prevent engine fire from spreading by isolating the engine from
the rest of the aircraft. This is achieved by closing various supplies:
Hot Pneumatic Bleed Air
Airframe Fuel Supply to the Engine Fuel System

Electrical Supply from the Engine to the Airframe System

DESCRIPTION

The quantity of extinguishing liquid required is kept in two extinguishing


bottles located in the nacelle fire areas; they are controlled from the
Flight Compartment.

These Extinguishing Bottles are located in the aft part of the Engine
Pylon Assembly. They are connected to the Extinguishing System also
located in the Engine Pylon Assembly.

The two spherical bottles are High Rate Discharge (HRD) type.
Volume 630 Cubic Inches (10.3 Liters)
Contain 16 Pounds/Lbs (7.26 Kilograms/KGS) of
Bromotrifluoromethane (CBrF3) (Halon 1301) type agent.
Bottles are pressurized with agent to One Pound/Lb (2.205 KG) of
gaseous nitrogen.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Nominal Pressure 800 PSIG (55.15 Bars) at 21 Degrees Celsius


ambient temperature.
Each bottle is provided with two outlet ports and only one is
connected to the Extinguishing System through a Discharge Head.
The Second Outlet Port is not used.
The Discharge Head is equipped with a Discharge Cartridge.
The explosive powder cartridge. Two filaments supplied with 28
VDC cause the detonation.
The two filaments are connected to a common ground wire and each
can supply the power required for the detonation in case of failure of
the other filament.
Gas pressure released after cartridge percussion causes rupture of
a leak proof metallic Diaphragm installed on the Discharge Head.
The full quantity of the extinguishing agent contained in the
Extinguisher Bottle is released in the Extinguishing System.
The Diaphragm also functions as an Overpressure Valve in case of
excessive pressure in the Extinguisher Bottle due to overheats
condition in the Engine Pylon Assembly.
A Pressure Switch located on the lower part of each Extinguisher
Bottle between the two Outlet Ports. Pressure Switch can be tested
manually with a 7/32 Inch Allen Wrench inserted into the TEST
Receptacle
Pressure Switch is calibrated between 200 and 400 PSIG (13.79 to
27.58 Bars) depending on the type of Fire Bottle installed. It is
electrically connected to the Amber color DISCH Warning Light in
the Flight Compartment Overhead Panel Engine Fire Handle
Modules 1 (FIN 39WD) and 2 (FIN 40WD).

The Extinguishing System runs in the Engine Pylon Assembly (Out of


the Fire Area). The Extinguisher Bottles are connected to a stainless
steel rigid pipe for Extinguishing Agent distribution to the Engine Core
area(s).

26-26
2626

ATA 26
A300/A310

Main Engine Fire Bottle Installation - Component Locations

A300-600 GE-FADEC Engine

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

A310s with GE-A3 Engine

26-27
2627

A310s with Pratt-Whitney Engine

ATA 26
A300/A310

Main Engine 1 and 2 - Fire and Loop Warnings


DESCRIPTION

The FIRE warning devices are:

When the fire detection control unit generates a fire or a fault signal
related to one or both loops, warnings appear in the cockpit to alert the
crew.

The corresponding ENG FIRE handle

The corresponding Red fire warning light with the inscription HP


VALVE integrated into the ENG FUEL lever when selected ON.

Both LOOP lights (or one if only one LOOP pushbutton switch is
selected ON) on the ENG FIRE panel.

The ECAM

The engine fire warning system generates two different warnings.

the FIRE warning (Red)


the LOOP warning (Amber)

FIRE WARNING
LOOP WARNING
The FIRE warning appears when the fire detection control unit
generates:

A fire signal related to both loops A and B, or

A fire signal related to LOOP A or B when only the respective


pushbutton switch LOOP A or loop B is selected ON, or

A fault signal related to both LOOP A and LOOP B, provided both


pushbutton switches LOOP A and LOOP B are selected ON.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

The LOOP warning appears when the fire detection control unit
generates:

26-28
2628

A fire signal related to only one loop with both pushbutton switches
LOOP A and LOOP B selected ON, or

A fault signal related to only one loop.

ATA 26
A300/A310

Main Engine 1 and 2 - Fire and Loop Warnings

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-29
2629

ATA 26
A300/A310

Main Engine 1 and 2 Fire Extinguishing - LH ECAM List of Actions


OPERATION

EXTINGUISHING PROCEDURE

In the event of Engine Fire Warning, the following Engine Fire


Extinguishing Procedure must be applied for the respective engine:

Extinguishing of the Fire Detection Loops Warning Lights LOOP A


and LOOP B to eliminate the risk of false drills during the following
Steps of the Procedure:

Throttle Control Levers in IDLE position


HP Fuel Shut Off Valve (SOV) CLOSED (Engine Shut Down)

PULL Engine Fire Control Handle which causes:

Closure of LP Fuel Fire Shut Off Valve (Electrically CLOSES)


Closure of Hydraulic Fire Valves (For the Respective Engine)
Engine 1 - GREEN and BLUE Hydraulic Systems
Engine 2 GREEN and YELLOW Hydraulic Systems

Cut Off of all the Pneumatic Air Bleed(s):


Air Conditioning Pack Valve CLOSES associated with the
Respective Engine
Engine Pressure Regulating Valve (Bleed Valve) CLOSES
Pneumatic Bleed Air Cross Feed (X-FEED) Valve CLOSES
Engine High Pressure (HP) Bleed Valve CLOSES
Wing Anti Ice Valves (NORMAL and ALTERNATE) Valves
CLOSE on the Respective Wing
Engine Anti Ice Valve for Nose Cowl Anti Icing CLOSES (On the
Respective Engine)
De-energizing of the Integrated Drive Generator (IDG)
(Generator Field Circuit OPENS)
ECAM System Continuous Repetitive Chime (CRC) is silenced

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Illumination of the SQUIB Warning Lights associated with the


two Fire Extinguisher Bottles
Stop of the Aural Warning by silencing the CRC with the
NORMAL CANCEL Push Button Switch (PBsw) on the Center
Pedestal Panel 417VU.
Wait for 10 Seconds which is the time required to reach
Windmilling during flight for which the Engine Extinguishing
Procedure efficiency will be optimum.

Proceed with extinguisher bottle percussion by pressing the AGENT


Push Button Switch (PBsw) and Fire Extinguishing Bottle DISCHARGE
is indicated by the illumination of the Amber color DISCH legend.
If the FIRE Warning Light does not disappear within 30 Seconds, the
Second Fire Extinguishing Bottle will be squibbed.
Note
The List of the Actions to be performed during the Fire Extinguishing
Procedure is automatically displayed on the LH ECAM Display Unit
simultaneously with the FIRE Warning.
As soon as the Required List of Action(s) displayed on the LH ECAM
Display Unit is accomplished, the Corresponding Line of Action is
automatically cancelled on the LH ECAM Display Unit. This indicates
that the crew has taken the proper action during the Engine Fire
condition.

26-30
2630

ATA 26
A300/A310

Main Engine 1 and 2 Fire Extinguishing System - Sequence of Actions

FILAMENTS

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-31
2631

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-32
2632

ATA 26
A300/A310

Engine Pylon Assembly - Fire Bottle Identification Placards

Outboard Side

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Inboard Side

26-33
2633

ATA 26
A300/A310

Engine Fire Extinguisher Discharge Head - General Removal/Installation


WARNING

WARNING

THE DISCHARGE HEAD CARTRIDGES ARE EXPLOSIVE AND


DANGEROUS DEVICES. REMOVE CARTRIDGES BEFORE
WORKING ON THE EXTINGUISHER ASSEMBLY. PROTECTIVE
CAPS MUST BE INSTALLED DISCHARGE HEAD REMOVAL /
INSTALLATION TO PREVENT DAMAGE TO DISCHARGE
DIAPHRAGM WHICH COULD RESULT IN POSSIBLE INJURY TO
MAINTENANCE PERSONNEL.

THE CLOSURE END MUST BE AIMED AWAY FROM PERSONNEL


AND DOWNWARD TOWARDS THE FLOOR TO PREVENT INJURY TO
PERSONNEL FROM FRAGMENT IN CASE OF ACCIDENTAL FIRING.

NOTE

INSTALLATION INFORMATION

The Engine Fire Extinguishing System comprises two Discharge Heads


in the LH Pylon Assembly and two Discharge Heads in the RH Pylon
Assembly. Installation of the four Discharge Heads are identical, only
one Removal / Installation General Information is provided below:

A new O-Ring is installed on the Discharge Head end fitting.


The Discharge Head Strainer is installed in the Discharge Head
body.
CAUTION

REMOVAL INFORMATION

The Strainer or Screen is removed from the Discharge Head on the


Discharge Outlet Body, and the old O-Ring is removed and discarded
from the Discharge Head end.

ENSURE THAT THE CONNECTING PART OF STRAINER IS


INSTALLED OPPOSITE DISCHARGE HEAD OUTLET.

Lock wire is cut and removed. The Cartridge Cannon Plug is


removed.
A rubber shunt is installed in the Cartridge Electrical Connector for
safety purposes.
The Knurled Nut is loosen manually and Discharge Line disengaged,
and cap line opening.
Hold Discharge Outlet and completely loosen nut on the bottle side.
Remove Discharge Outlet.
Install protective cap on the Fire Extinguisher Bottle Discharge Outlet
port.
The Percussion Cartridge is removed from the Discharge Head and
electrical pins are shunted.
The shunted pins on the Percussion Cartridge are capped with a
protective cap on each end.

Uncap and install the Percussion Cartridge on Discharge Head and


Cartridge is torqued per Airbus AMM.
Protective cap is removed from the Fire Extinguisher Bottle.
The Discharge Head is uncapped and installed under the bottle and
the nut is screwed on without tightening.
The Fire Extinguisher Discharge Line is uncapped for installation.
Line up and position the Discharge Head end with the Discharge Line
Assembly.
Tighten the Knurled Nut by hand on the Discharge Head.
The Discharge Nut is torqued per Airbus AMM.
Remove shunt from Percussion Cartridge Pins. Connect the
Cartridge Cannon Plug to the Percussion Cartridge.

Ensure maintenance work area is clear of all foreign objects, tools and
other miscellaneous items.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-34
2634

ATA 26
A300/A310

Engine Fire Extinguishing Bottle - Pylon Installation and Features

FW

(Squib Discharge light)

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-35
2635

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-36
2636

ATA 26
A300/A310

APU FIRE
PROTECTION SYSTEM

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-37
2637

ATA 26
A300/A310

APU Fire Extinguishing System


GENERAL

NOTE

The APU Fire Extinguishing System has a Single Fire Extinguisher Bottle
located forward of Fuselage Frame (FR) 95. Access to the bottle is
gained through Access Panel 313AL.

Prior to conducting BITE Check on the APU Fire Detection Control Unit
(FDCU) FIN 13WG, pull Circuit Breakers (CBs) A61/FIN 2WF (Squib B)
and B61/FIN 1WF (Squib A) to prevent accidentally firing the APU Fire
Extinguisher Bottle Discharge Cartridge Filaments.

The Extinguisher Bottle FIN 11WF is installed in a support bracket


located on the side fuselage structure.

The DC ESS Bus through DC ESS Bus Sub Bus powers the two squibs
or filaments.

The Extinguisher Bottle has a Single Discharge Head with an explosive


cartridge containing two filaments installed.
DESCRIPTION
The Extinguisher Bottle is connected to a rigid stainless steel pipe which
directs the extinguishing agent, under gaseous nitrogen pressure,
through the APU Fire Wall (FR95) in to the APU Compartment or Bay.
The Fire Extinguisher Bottle, depending on the two Manufacturers Part
Number is fully charged with approximately 5.0 or 5.5, +0.1 to 0.0
Pounds/Lbs (2.27 or 2.47 Kilograms (KGS), +0.5 to 0.0 KGS) of Halon
Extinguishing Agent.
The Fire Extinguisher Bottle is pressurized with 90% Nitrogen Gas plus
10% Helium to 600 +25 to 0.0 PSIG (41.37 +1.7 to 0.0 BAR) at 70
Degrees Fahrenheit (F) (21 Degrees Celcius).

The Fire Extinguisher Bottle has an Over Pressure Relief Diaphragm to


protect the bottle from thermal expansion conditions. In the event of a
thermal expansion condition, the bottle will be relieved overboard on the
lower fuselage area through a Over Pressure Discharge Pipe.
A Red Disc is inserted in the Over Pressure Discharge Pipe port to
prevent foreign debris from entering the port and blocking the port. When
the Extinguisher Bottle discharges due to a thermal expansion condition,
the Red Disc will be blown out to reveal this abnormal condition. The
Red Disc is checked on various inspection checks to ensure that the
Extinguisher Bottle has not accidentally discharged overboard.

The Fire Extinguisher Bottle weighs 11.15 or 11.65 Pounds/Lbs (5.06 or


5.28 KGS) when fully charged with extinguishing agent.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-38
2638

ATA 26
A300/A310

APU Fire Protection Components - Location

FIN 13WG
FR 95

WARNING

FWD

OBSERVE THE CIRCUIT BREAKERS DEACTIVATION DECAL WHEN


PERFORMING BITE CHECK ON APU FDCU/FIN 13WG. FAILURE TO
PULL CBs WILL ACTIVATE EXPLOSIVE CHARGE ON APU FIRE
EXTINGUISHING BOTTLE DISCHARGE HEAD

Located on Electronic Rack 90VU/Shelf Frame 91VU

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-39
2639

ATA 26
A300/A310

APU Fire Detection and Warnings


FIRE DETECTION

FIRE AND LOOP WARNINGS

The APU is equipped with a fire detection system which consists of:
two identical detection loops (A and B) mounted in parallel
and a fire detection control unit

When the fire detection control unit generates a fire or a fault signal
related to one or both loops, warnings appear in the cockpit to alert the
crew. The APU fire warning system generates two different warnings:
The FIRE warning (Red)
The LOOP warning (Amber)

Each detection loop consists of one sensing element located in the APU
compartment.

FIRE WARNING
When a sensing element is subject to heat, a signal is transmitted to a
warning system as soon as a preset level of temperature is reached.

The FIRE warning appears when the fire detection control unit
generates:
A fire signal related to both loops A and B, or
A fire signal related to the loop A or B when only the respective
pushbutton switch LOOP A or LOOP B is selected ON, or
A fault signal related to both loop A and loop B, provided both
pushbutton switches LOOP A and LOOP B are selected ON.

A break in a loop will not affect the warning system; therefore, fire
protection is maintained. However, the test will indicate a loop failure.
The LOOP warning devices are:
The LOOP A (or LOOP B) LIGHTS ON THE APU fire panel.
The ECAM

The fire warning devices are:


The APU FIRE handle
Both LOOP lights (or one if only one LOOP pushbutton switch is
selected ON) on the APU FIRE panel.
The ECAM

When the aircraft is on the ground, additional warnings are triggered in


the event of an APU fire:
The APU FIRE light on the nose gear interphone panel, and
APU shut down and extinguishing sequences are initiated
automatically.

LOOP WARNING
The LOOP warning appears when the fire detection control unit
generates:
A fire signal related to only one loop with both pushbutton switches
LOOP A and LOOP B selected ON, or
A fault signal related to only one loop.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-40
2640

ATA 26
A300/A310

APU Fire and Loop Warnings - Schematic

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-41
2641

ATA 26
A300/A310

APU Fire Detection System - Controls and Indications


1.

LOOP A (B) PUSHBUTTON SWITCH

3.

The pushbutton switch allows activation of aural and visual warnings


when a fire (FIRE) or fault (LOOP) signal is generated by the fire
detection control unit for the related loop.

2.

ON (P/B Switch Pressed-in)


Aural and visual warnings are activated when a fire or a fault
signal is generated by the fire detection control unit.
OFF (P/B Switch Released-out)
Aural and visual warnings are inhibited for the related loop. The
OFF light comes on White.
LOOP A (B)
The light comes on Amber when the associated pushbutton
switch is selected ON, and a fire or a fault signal is generated by
the fire detection control unit. The light goes off when the APU
FIRE handle is pulled. During LOOP TEST, the light comes on to
indicate a successful test.

The APU FIRE handle has two positions. An APU FIRE warning light
is integrated into the handle.
IN
Normal position, mechanically locked
ACTIVATED
Pulling the handle electrically causes:
APU automatic shutdown
APU BLEED VALVE closure
BLEED AIR X FEED VALVE closure (if in auto position)
APU GEN cut off
FUEL APU FIRE VALVE closure
APU ISOL VALVE (Fuel) closure
CRC silencing and LOOP light extinction, SQUIB light
illumination.
4.

LOOP TEST PUSHBUTTON


The pushbutton controls the test of:
both fire detection loops
APU FIRE and LOOP local warnings
ECAM activation.

For Training Purposes Only

AGENT PUSHBUTTON
The pushbutton controls the ignition of the squib and resultant
discharge of fire extinguisher bottle.
The pushbutton is armed only when the APU FIRE handle is pulled.

5.

Both pushbutton switches LOOP A and LOOP B must be selected


ON, and the APU FIRE handle must be in normal position for a
complete system test.

MTT M540000 / R3.3 01AUG01

APU FIRE HANDLE

SQUIB TEST PUSHBUTTON


The pushbutton controls the test of the squib filaments in the
discharge head and their electrical circuit. When pressed with the
APU FIRE handle in normal position, the SQUIB light comes on if
filaments and circuits are operative.

26-42
2642

ATA 26
A300/A310

APU Fire Detection Controls and Indications - Schematic

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-43
2643

ATA 26
A300/A310

APU External Fire Protection Controls


NOSE GEAR CONTROL PANEL 3WC
(Old Interphone Panel on Nose Gear)

APU EMERGENCY/SHUTDOWN PUSHBUTTON SWITCH/FIN 1KL


ON REFUEL/DEFUEL PANEL 110VU

APU FIRE LIGHT

Note

The APU FIRE Light illuminates RED color and are accompanied by an
External Warning Horn when an APU Fire is detected. The External
Warning Horn is located in the aft upper left hand corner of the Nose
Landing Gear Wheel Well.

The Pushbutton Switch can be activated only when the aircraft is on the
Ground. The purpose is to shutdown the APU in the event of a fuel spill
during Refueling or Defueling Operation, or when required for other
reasons requiring emergency shutdown of the APU.

The APU Fire Extinguisher will automatically discharge 10 Seconds after


the Fire is detected and the Fire Warning messages are activated
through the ECAM System.

The 110VU Panel does not have an APU FIRE Light installed on the
panel for APU Fire Indication. The Pushbutton Switch is located on the
forward lower corner of Panel 110VU.

The APU Fire Warning Light will extinguish after the Fire is extinguished

The Pushbutton Switch (PBsw) is located on the Refuel/Defuel Panel


110VU on the RH Air Conditioning Air Intake Fairing on the lower
fuselage area forward of the Right Hand Main Landing Gear Wheel area.
Access to the Panel 110VU is Access Door 144DR. The decal legend on
top of the PBsw position is APU EMERGENCY and the left side of the
PBsw is SHUT DOWN.

APU SHUT OFF PUSHBUTTON SWITCH


Note
The Pushbutton Switch can be activated only when the aircraft is on the
Ground. The purpose is to shutdown the APU in the event of a fuel spill
during Refueling or Defueling Operation, or when required for other
reasons requiring emergency shutdown of the APU.

A Red Protective Hinged Flap guards the PBsw. When momentarily


Pressed-In, in the event of an APU fire, the Automatic Shutdown is
confirmed and the External Warning Horn is silenced.

The Pushbutton Switch (PBsw) is located on the Nose Landing Gear on


the LH side between the two of the Nose Wheel Steering Rack and
Pinion Hydraulic Cylinders. The decal legend on top of the PBsw
position is APU FIRE and the bottom legend is APU SHUT OFF.
A Red Protective Hinged Flap guards the PBsw. When momentarily
Pressed-In, in the event of an APU fire, the Automatic Shutdown is
confirmed and the External Warning Horn is silenced.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-44
2644

ATA 26
A300/A310

APU Emergency Shutdown Controls and Indications


B

Interphone Box 3WC

Refuel/Defuel Panel 110 VU

FWD

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-45
2645

ATA 26
A300/A310

A310 APU Fire Protection System - Tail Section Electrical Connections

NOTE
A 3 0 0 CBS 1 W F A N D 2 W F A R E
LOCATED ON MAIN CBs PANEL
131VU ON THE FLIGHT T DECK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-46
2646

ATA 26
A300/A310

A310 APU Fire Protection System - Tail Section Electrical Connections

NOTE
A300 CBS 1 W F A N D 2 W F A R E
LOCATED ON MAIN CBs PANEL
131VU ON THE FLIGHT T DECK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-47
2647

ATA 26
A300/A310

APU Fire and Loop Fault - Warning Logic

Depicted below are the various warnings displayed in the Flight Compartment in the
event of an APU FIRE or FIRE LOOP FAULT occurs. Also shown are the different
Flight Phases at which the warnings will or will not be displayed.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-48
2648

ATA 26
A300/A310

APU Fire and Loop Warnings - Warning Logic

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-49
2649

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-50
2650

ATA 26
A300/A310

AVIONICS SMOKE
DETECTION SYSTEM

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-51
2651

ATA 26
A300/A310

Avionics Smoke Detection System


GENERAL

DETECTION SYSTEM - COMPONENTS

Avionics Compartment Smoke Detection System comprises:


Ionization Smoke Detectors installed on Air Extraction Ducts
Indicating and Testing Assembly enabling Warning Visualization
Checking of Detection and Indication Circuits
Each Smoke Detector triggers its corresponding Warning Light
together with MASTER WARN Lights flash on CAPT and FO Main
Instrument Panels 3VU and 5VU.
On A310-200 Series FedEx Aircraft N401FE to N414 have the Red
color SMOKE Warning Light on the Warning Light Display Panel
(WLDP) for visual indication instead of MASTER WARN (Red Color)
and MASTER CAUTION (Amber Color) Lights.
A Continuous Repetitive Chime (CRC)
The Warning Level 3 corresponds to an Emergency Configuration
(Example: Avionics SMOKE ) that appears on LH ECAM and ELEC
DC Page on the RH ECAM.

Three Duct Smoke Detectors are installed on Air Extraction Ducts of the
following racks and equipment (A300/A310):

DESCRIPTION

Monitored Rack
or Equipment

Number of
Detectors

Pilots Panels, CB Panels,


Main Racks, Relay Boxes,
AC/DC Transformer,
Rectifiers Static Inverter, IRS2
Minimum Equipment Bay,
Shelf 96VU, IRS 1 and 3

Warning Light
Designation
Location

AVIONIC Overhead Panel,


SMOKE ELEC PWR
424VU

SMOKE

Essential CB
Panel

A Sniffer Fan installed in the Avionics Bay/Right Side Equipment Area


provides olfactory confirmation of smoke through a Sniffer Fan and Hose
Assembly located on the First Officers Side Console. The Avionics
Ventilation Air is extracted from the exhaust duct area forward of the
Overboard/Inboard Blower or Fan for air sampling purposes to detect
presence of SMOKE from the system (A300/A310).

PRINCIPLE OF OPERATION
Detection is carried out by Duct Smoke Detectors that are of the
ionization type and composed of:
A Measurement Chamber in which enters the air to be analyzed
A reference resistor
The chamber is ionized by a source of extremely low radioactivity.
When Smoke Gases enter the detector, they modify the balance
between the
resistor and the ionized chamber which causes a variation from
the detector normal voltage.
From the Reference Setting Threshold of the Measurement
chamber, the Detector Inner Electronic Circuit sends a signal to
the corresponding Flight Compartment Warning.
Detectors are self-contained units that have an Electrical
Connector and Test Receptacle Connector on the unit.
The Smoke Detector Units are directly connected (Without
Intermediate Control Unit) to the Flight Compartment.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Also, the Battery Charge Controllers (Number 1,2 and 3) provide


protection against Overload and Thermal Runaway, and the Battery
Ventilation System discharges overboard any gaseous fumes or smoke.
The separate ducting for ventilation purposes exhaust the fumes and
smoke overboard through an exhaust port located on the lower right side
of the Fuselage Nose Section.
In addition, the Amber color BAT OVHT (Battery Overheat) Light on
ELEC PWR Panel 424VU will illuminate along with ECAM Activation, if
Battery Number 1, 2 or 3 should overheat during electrical system
operation.

26-52
2652

ATA 26
A300/A310

Avionics Smoke Detection - Component Location and Schematic

80VU

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-53
2653

ATA 26
A300/A310

AVIONICS SMOKE SYSTEM - SMOKE WARNING LIGHT


GENERAL

UNDER FLOOR AREA EQUIPMENT

The AVIONICS SMOKE Light illuminates Red color in the Flight


Compartment on the Overhead Panel on the ELEC PWR Panel 424VU
when smoke is detected in the Air Conditioning System Ventilation Ducts.

The Smoke Detector Unit FIN 11WA will provide a signal to ECAM
System for activation and illuminate the AVIONICS SMOKE Warning
Light on ELEC PWR Panel 424VU on the Flight Compartment
Overhead Panel.

The Ventilation Ducts provide cooling and ventilation of the Avionics


Equipment in the Avionics Bay and Flight Deck areas. Some of the
following areas requiring cooling and ventilation are:

Some of the miscellaneous equipment that can cause SMOKE


conditions is listed below, if any of the equipment should malfunction
internally or externally during system operation:

AIRCRAFT BATTERIES
Aircraft Batteries (Number 1, 2 and 3)
Note: The Battery Smoke Detection System has been
deactivated and removed per FedEx Engineering Dept

MINIMUM EQUIPMENT BAY


(MIN EQPT BAY) Smoke Detector Unit FIN 12WA

Minimum Equipment Bay


IRS Units 1 and 3 are on the Minimum Equipment Bay Smoke
Detector Unit FIN 12WA

ELECTRICAL MAIN COMPARTMENT BAY


(ELEC MAIN COMPT BAY) Smoke Detector Unit FIN 11WA

LH Electronic Rack 80VU


RH Electronic Rack 90VU
IRS Unit 2 is on the Electronic Racks 80VU/90VU Smoke
Detector Unit FIN 11WA

FLIGHT COMPARTMENT
(COCKPIT or FLIGHT DECK) Smoke Detector Unit FIN 13WA

There are additional component(s) that are not listed above in the
Avionics Bay that can also cause smoke condition(s) and be detected
by the Smoke Detector Units.

Cockpit Instrument Panels


Overhead Panel
Circuit Breakers Panels
Weather (Wx) Radar Transceiver(s) (Panel 115VU)

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

Windshield Heat Controllers (Left FIN 19DG/Right FIN 20DG


Front Windshields)
Terrain Clearance Avoidance System (TCAS)Unit
Air Traffic Control (ATC) Unit
Transformer/Rectifier Units (TRU) Number 1 FIN 1PU, 2 FIN 2PU
and Essential FIN1PC)
Battery Charge Control Units (BCC) (Number 1 FIN 21PE, 2 FIN
22PE and 3 FIN 23PE)
Static Inverter FIN 4XE
Electrical Relay Racks 103VU, 104VU and 105VU
Electrical Distribution Panels 101VU, 106VU, 107VU and 282VU
Standby Generator Control Unit (GCU) FIN 26XE (If installed in
the aircraft)
Engine 1 FIN 1XU, 2 FIN 2XU and APU FIN 1XS Generator
Control Units (GCU)
Main Avionics Blower Unit FIN 67HQ
Alternate Avionics Blower Unit FIN 72HQ (If installed on some
A310 aircraft) (A300-600 have only the Main Blower Unit)

26-54
2654

ATA 26
A300/A310

AVIONICS SMOKE SYSTEM - SMOKE WARNING LIGHT - PANEL 424VU


A300 / Some A310

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-55
2655

Some A310

ATA 26
A300/A310

Minimum Equipment Bay SMOKE Light


GENERAL
The Minimum Equipment Bay SMOKE Light is located in the Flight
Compartment Overhead Circuit Breakers (CBs) Panel 22VU. The CBs
are identified with Orange Slash ( \\\\\\) markings around the area where
the CBs are located for quick identification purposes during emergency
conditions.
The Ventilation Duct Smoke Detector Unit FIN 12WA will detect the
smoke in the ventilation duct and send a signal to the MIN EQPT
SUPPLY Smoke Light on Distribution Panel 22VU to illuminate in the
event of smoke in the bay from malfunctioning equipment.
ECAM System Activation will occur to provide a Level 3 Warning
Message on the LH ECAM with an Amber color MASTER CAUTION
Light (A300 and Some A310) on the Captain and First Officer (FO)
Instrument Panels. Aircraft equipped the Warning Light Display Panel
(WLDP) on the Center Pedestal located between the Captain and FO
crew positions, will illuminate the Amber color LOOP Light on the WLDP
(On A310 Aircraft/N401FE to N414FE). The Aural Warning is an audible
Single Chime (SC) sound on the two loudspeakers on the Flight
Compartment ceiling area.
In case of illumination of the red SMOKE Warning Light on the Overhead
Panel CBs Panel 22VU, the crew will operate the Sniffer Fan using MIN
EQPT BAY SNIFFER FAN Pushbutton Switch (PBsw) located on Panel
420VU (A300) (Panel 422VU /A310).
The Sniffer Fan FIN56WA will provide a sense of smoke smell
confirmation of any smoke upstream of the ventilation duct inlet area to
the Overboard/Inboard Extract Fan FIN73HR located under the Forward
Cargo Compartment floor area. The Smoke Confirmation Hose
Assembly with a nose smelling device and a flexible flap to prevent
foreign matters or object entry into the hose assembly.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

The following CBs are located in the MIN EQPT BAY SUPPLY panel
area:

COM Passenger Address and VHF 1 (A300/A310)


CABIN PRESS Sys 1 28VDC and 115VAC (A300/A310)
ADS ADC 1 115VAC and 28VAC (A300/A310)
NAVIGATION IRS 1 BAT and 115VAC, and IRS 3 115VAC and
BAT (A300/Some A310)
NAVIGATION IRS 1 115VAC, and IRS 3 115VAC (Some A310)
FUEL TK LO LVL L OUTR & R INR & CTR R, and R OUTR & L
INR & CTR L (A300/A310)
OXYGEN CREW (A300/A310)
AIR BLEED ENG 1 CONTROLLER MONITOR and CTL
(A300/A310)
ENG FIRE DET ENG 1 LOOP A, LOOP B and WARN, and ENG 2
WARN, LOOP A, and LOOP B (A300/A310)
SMOKE AVIONIC DET-DETECTOR and DET-MAIN DECK AND
CARGO (A300)
CARGO SMOKE DET WARN and PWR SUPPLY (Some A310)

The following equipment is located in the Minimum Equipment Bay in


Electronic Rack 90VU on Shelf 96VU. Facing 90VU Rack from Left to
Right:

26-56
2656

Cabin Pressure Controller FIN 105HM (A300/A310)


Fuel Level Amplifier FIN 80QJ (A300/A310)
VHF 1 FIN 1RC1 (A300/A310
Engine 1 Fire Detection Control Unit (FDCU) FIN 11WD
(A300/A310)
Oxygen Control Box FIN 19HT (A300/A310)
Engine 2 Fire Detection Control Unit (FDCU) FIN 12WD
(A300/A310)
Pneumatic Controller 1 FIN 41HA (A300/A310)
ADC 1 FIN 1FL1 (A300/A310)

ATA 26
A300/A310

MIN EQPT BAY SMOKE Light - Circuit Breakers Panel 22VU

PANEL 22VU
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-57
2657

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-58
2658

ATA 26
A300/A310

FIRE PROTECTION SYSTEM


FORWARD - AFT - BULK
CARGO COMPARTMENTS

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-59
2659

ATA 26
A300/A310

A300 / Some A310 Lower Cargo Compartment Smoke Detection System - Schematic

Note
No FWD Cargo
Heat System
FROM HOT AIR
SUPPLY MANIFOLD

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-60
2660

ATA 26
A300/A310

Some A310 Lower Cargo Compartment - Smoke Detection System - Schematic

Note
With FWD Cargo
Heat System

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-61
2661

ATA 26
A300/A310

Some A310 Lower Cargo Compartment - Smoke and Loop Warning System

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-62
2662

ATA 26
A300/A310

Some A310 Lower Cargo Compartment - Smoke Detection System

Ten Detector
(5 Loops)
Configuration No FWD Heat

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-63
2663

ATA 26
A300/A310

Some A310 Lower Cargo Compartment - Smoke Detection System

Ten Detector
(5 Loops)
Configuration with
FWD Cargo Heat

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-64
2664

ATA 26
A300/A310

A300 / A310 Lower Cargo Compartment Smoke Detector - Component Installation

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-65
2665

ATA 26
A300/A310

Some A310 Lower Cargo Compartment - Ten (10) Smoke Detector System
GENERAL
The Cargo Compartment Smoke Detection System consists of Ten
Ionization Smoke Detectors installed in the Cargo Compartment Ceiling,
One Smoke Detection Control Unit FIN 18WH that uses AND/OR Logic
according to the Detector Connection.
SMOKE DETECTION CONTROL UNIT
The Ten-Channel Control Unit is common to the Ten Smoke Detectors
of the three Lower Cargo Compartments. The front face of the Smoke
Detection Control Unit provides for:
Eleven Annunciator Lights indicating any failure in any Smoke
Detectors
Circuitry or in the Control Unit Supply
One TEST Pushbutton Switch (PBsw) for Light Testing
One RESET PBsw for resetting the system in case ELEC & CARGO
COMPT SMOKE DET/CONTROL UNIT Annunciator on
Maintenance Panel 471VU indicates a FAULT.
The Smoke Detection Control Unit is located in the Avionics Bay, on the
Electronics Rack 90VU, Shelf 96VU Minimum Equipment Bay. The Bay
is a sealed compartment area for cooling and smoke detection
purposes.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-66
2666

ATA 26
A300/A310

Some A310 Lower Cargo Compartment - Smoke Detection Control Unit

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-67
2667

ATA 26
A300/A310

ELECT & CARGO COMPT SMOKE DET BITE Test Panel

MAINTENANCE PANEL 494VU


ELEC & CARGO COMPT SMOKE DET PANEL

1.

2.

3.

BTL 1 AND 2 OK LIGHTs


The lights illuminate White color while SQUIB TEST Pushbutton
Switch (PBsw) is pressed-in and held, if the corresponding
CARGO COMPT BTL/1 BTL 2 squib in the respective Fire
Extinguisher Bottle is operative.
SQUIB TEST PBsw
When pressed-in and held, the squibs in the Extinguisher Bottle
Discharge Heads are tested at the same time.

After completion the testing the Smoke Detector(s), the SMOKE


TEST SELECTOR Rotary Switch Knob is re-positioned to the
NORM FLT position. Selected to this position will deactivate the Test
Functions of the Smoke Detectors. The Annunciator Light
TEST in the Push to Test (PTT ) Switch will extinguish.
4.

SMOKE TEST SELECTOR

Note: Some A310 aircraft have six Smoke Detectors or ten


Smoke Detectors installed depending on the FedEx Registration
Number with a A and B LOOP Selector Switch.

Note: Some A310 aircraft have two LOOPS (A and B) in the


Forward (FWD) Cargo Bay, two LOOPS (A and B) in the AFT
Cargo Bay and two LOOPS (A and B) in the BULK Cargo Bay.
Total of six LOOPS.

Note: Some A310 aircraft have four LOOPS (Two A and Two B)
in the FWD Cargo Bay, four LOOPS (Two A and Two B) in the
AFT Cargo Bay and two LOOPS (A and B) in the BULK Cargo
Bay. Total of 10 LOOPS.

A or B Smoke Detectors if the CARGO COMPT LOOP TEST


SEL Switch is placed in the FWD 1 or 2 position

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

PBsw Pressed and Held will initiate the TEST sequence. It is


successful if:
Corresponding Local LOOP A (LOOP B) Light
illuminates
Corresponding Local SMOKE Light illuminates
SMOKE Light illuminates on the Warning Light Display
Panel (WLDP ) associated with CRC (Some A310 aircraft
N401FE to N414FE have WLDPs)

Note
ISOL VALVE FAULT (Isolation Valve Fault) Light illuminates on the Air
Conditioning COMPT TEMP Panel 437VU for the Bulk Cargo Bay
Isolation Valve is re-positioned to the CLOSE position during the TEST.
The Isolation Valve must be RESET after the TEST to the OPEN
position and can be checked on the RH ECAM AIR COND Page for the
proper position after reset is accomplished.

When selecting from the NORM FLT position, to the following


position(s) provides selection of:

PTT PUSHBUTTON SWITCH


The PBsw initiates the TEST of the selected Smoke Detection
System:

Selects Smoke Detection System to be tested. Ten positions


correspond to six Smoke Detectors (A300).

A or B Smoke Detectors if the CARGO COMPT LOOP TEST


SEL Switch is placed in the AFT 1 or 2 position
A or B Smoke Detectors if the CARGO COMPT LOOP TEST
SEL Switch is placed in the BULK 1 or 2 position

26-68
2668

RELEASED The TEST sequence is deactivated


TEST The Light illuminates White color when the Smoke
Test Selector is in any TEST position other than NORM
FLT.

ATA 26
A300/A310

ELEC & CARGO COMPT SMOKE DET Test Panel 494VU

3
4

5
MAINTENANCE PANEL
PANEL 494VU
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-69
2669

ATA 26
A300/A310

ELEC & CARGO COMPT SMOKE DET BITE Test Panel


(A310 with Five (5) Loop Lower Cargo Compartment Smoke Detection System)
MAINTENANCE PANEL
1.

2.

3.

4.

BTL 1 (2) OK Lights


The lights BTL 1 and BTL 2 come on White while SQUIB TEST
pushbutton is pressed, if the corresponding squib in the bottle is
operative.

CARGO COMPT LOOP TEST SEL SWITCH


Selects the type of detectors and circuits to be tested.

SQUIB TEST PUSHBUTTON


When pressed and held, the squibs in the discharge heads are
tested simultaneously.

5.

PTT PUSHBUTTONThe pushbutton initiates the test of the selected


smoke detection system.

SMOKE TEST SELECTOR


Selects smoke detection system to be tested. Selectors on aircraft
with battery smoke detectors have ten (10) positions corresponding
to 14 smoke detectors. Aircraft without the battery detector have
nine (9) positions for 13 detectors.

LOOP A
A detectors and circuits are tested
LOOP B
B detectors and circuits are tested

Pressed and Held


The test sequence is activated. It is successful if:
Corresponding local LOOP A (LOOP B) light comes on
Corresponding local SMOKE light comes on
SMOKE light comes on the WLDP associated with RC.

5 (A detectors if the CARGO COMPT LOOP TEST SEL switch


is selected LOOP A)

NOTE: ISOL VALVE FAULT light comes on COMPT TEMP panel


and must be reset after test.

5 (B detectors if the CARGO COMPT LOOP TEST SEL switch


is selected LOOP B)

Released
The test sequence is deactivated

3 in ventilation ducts from electrical bay.

TEST
The light comes on White when the smoke test selector is in any
test position other than NORM FLT.

The NORM FLT position deactivates the test functions. The TEST
light in the PTT pushbutton is off.
6.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-70
2670

CONTROL UNIT LIGHT


The BITE DISPLAY light comes on White and remains on if a smoke
detection system fails.

ATA 26
A300/A310

ELEC & CARGO COMPT SMOKE DET BITE Test Panel


(A310 with Five (5) Loop Lower Cargo Compartment Smoke Detection System)
1

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-71
2671

ATA 26
A300/A310

AVIONICS SMOKE System - Warning Logic


GENERAL

Aircraft equipped with the Warning Light Display Panel (WLDP) will
illuminate the Amber color LOOP Light on the WLDP (On A310
Aircraft/N401FE to N414FE). Lower Logic Diagram in the illustration.

The SMOKE Warning Logic Illustration on the opposite page shows the
various warnings in the Flight Compartment in the event that smoke is
detected in the MAIN DECK, FWD COMPT, AFT & BULK, DISCH
AGENT 2, AVIONICS, and MINIMUM EQUIPMENT BAY ventilation
ducts or areas.

The Aural Warning is an audible Single Chime (SC) sound on the two
loudspeakers located on the Flight Compartment ceiling area above
Captain and First Officer Seats.

ECAM System Activation will occur to provide a Level 3 Warning


Message on the LH ECAM with a flashing Red color MASTER WARN
Light (A300 and Some A310) on the Captain and First Officer (FO)
Instrument Panels.

The Horizontal Chart for ECAM AUTOMATIC FLIGHT PHASE


INHIBITION shows the 12 Flight Phases from ELEC PWR ON to 5-MIN
LATER vertical columns.
The Left Hand Text Boxes with Numbers 1 to 6 located to the left of the
Text Boxes match the Horizontal Chart for ECAM AUTOMATIC FLIGHT
PHASE INHIBITION Left Hand and Right Vertical Numbered Columns
for sequencing purposes of events.

Aircraft equipped with the Warning Light Display Panel (WLDP) on the
Center Pedestal located between the Captain and FO crew positions,
will illuminate the Red color SMOKE Light on the WLDP (On A310
Aircraft/N401FE to N414FE). Upper Logic Diagram in the illustration.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-72
2672

ATA 26
A300/A310

Cargo Compartment and Avionics SMOKE Warnings - Warning Logic

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-73
2673

ATA 26
A300/A310

Lower Cargo Compartments Fire Extinguishing System


GENERAL
The Fire Extinguishing System in the Lower FWD and AFT/BULK Cargo
Compartments or Bay are designed that in the event of the Smoke
Detection System becoming activated, action can be initiated for fire
fighting. The Extinguishing Agent that is stored in Fire Extinguisher
Bottles behind the RH Side Wall Panels of the FWD Cargo Compartment
can be discharged into the affected compartment.
DESCRIPTION
Two Fire Extinguisher Bottles are located behind the RH Side Wall
Panels between Fuselage Frames (FR) FR29 and 31 (A300) (FR32 and
34 A310) of the Forward (FWD) Cargo Compartment. Each Bottle is
equipped two Discharge Heads that are located over the Rupture Discs.
Each Discharge Head is equipped with an electrically ignited explosive
device (Squib) to rupture the metal diaphragm or disc to release the
extinguishing agent into the Fire Extinguishing System.
The Extinguisher Bottles are connected to the system through the
Discharge Heads through armor wire braided flexible hoses to rigid
pipelines which are connected to spray nozzles located in the FWD, AFT
and BULK cargo compartment ceilings.
The Extinguisher Bottles are charged with Bromotrifluoromethane
(CBrF3) (Halon FE 1301) and pressurized with a Nitrogen (N2) propellant
gas to 360 PSIG at 70F (24.8 BAR at 21C). The two large bottles are
filled with 70 Pounds (31.75 KGS) of Extinguishing Agent (A300/Some
A310).

Extinguisher Bottle Number 1 is connected to the system through the


Discharge Heads. Armor Braided Flexible Hose Assemblies are
connected to the Spray Nozzles located in the FWD, AFT and BULK
Cargo Compartment Ceiling areas.
Extinguisher Bottle Number 2 is connected the system through the
Discharge Heads and through a Flow Metering System (A300/Some
A310). The Flow Metering System consists of two Water Absorbing
Filters, two Solid Particle Filters, two Pressure Reducing Valves, two
Diaphragms and two Check Valves for flow and distribution purposes to
the FWD or AFT/BULK Cargo Compartment(s). The Filters and Pressure
Reducing Valves are installed on a Support Assembly below Extinguisher
Bottle 2.
A temperature-compensated Pressure Switch on each bottle is
electrically connected to the DISCH 1/DISCH 2 Amber color Indicator
Lights on the Flight Compartment Overhead Panel on the CARGO
COMPT SMOKE DET Panel 433VU (A300/A310). This provides the crew
with visual indication that a bottle has been discharged or that the bottle
internal pressure is less than the minimum requirement due to possible
leakage.
Three brackets, welded to each bottle, provide attachment points to the
Airframe Structural area in the FWD Cargo Compartment.
A SQUIB TEST Panel 494VU is provided on the Maintenance Panel
(A300) and Panel 471VU on the Maintenance Panel 471VU (A310) to
check the serviceable condition of the Discharge Cartridges (Squibs).

Some A310 Aircraft have one Large Bottle filled with 70 Pounds (31.75
KGS) and one small bottle with 23 Pounds (10.45 KGS) of Extinguishing
Agent. Both bottles regardless of the two Large Bottles (A300/Some
A310) or one Large and one Small Bottle (Some A310 Only)
Configuration each have a Pressure Relief Valve. The valves are
connected to the FWD Cargo Compartment Spray Nozzles through armor
braided flexible hoses and rigid pipelines.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-74
2674

ATA 26
A300/A310

A300 / Some A310 Lower Cargo Compartment Fire Bottles with Flow Metering

NOTE
FLOW METERING SYSTEM
DESIGNED FOR ETOPS OPERATION
ETOPS= EXTENDED RANGE OPERATIONS
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-75
2675

ATA 26
A300/A310

Some A310 Lower Cargo Compartment Fire Bottles with Flow Metering
Configuration 01
NOTE

One Large and One Small


bottle

FLOW METERING SYSTEM


DESIGNED FOR ETOPS OPERATION
ETOPS= EXTENDED RANGE OPERATIONS

Configuration 02
Two Large Bottles

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-76
2676

ATA 26
A300/A310

LOWER CARGO COMPT SMOKE DETECTION PANEL 433 VU


OPERATION
As soon as a Smoke Warning is given, the Air Conditioning System in
the endangered cargo compartment is automatically switched off.
When the Smoke Warning Red color light is illuminated on the CARGO
COMPT SMOKE DET Panel 433VU (A300/A310) located on Flight
Compartment Overhead Panel provides a warning to the crew that
Smoke and/or Fire Conditions have occurred.
There are two Extinguisher AGENT (1/2) Selector Switches that are
locked in the Neutral (Center) position by switch safety gates with
breakaway lock wire. The LH AGENT Switch and SMOKE Indicator
Light are for the FWD Cargo Compartment. The RH AGENT Switch and
SMOKE Indicator Light are for the AFT/BULK Cargo Compartment.
Operation of the Fire Extinguishing System is the same for the FWD
Cargo Compartment and the AFT/BULK Cargo Compartment. By
breaking the breakaway lock wire, opening the safety gate and placing
the AGENT Switch in AGENT 1 position, the appropriate squib in Fire
Extinguisher Bottle 1 will be electrically ignited rupturing the Extinguisher
Bottle diaphragm or disc. The Extinguishing Agent is forced under
pressure through the delivery pipelines and out of the Spray Nozzles in
the appropriate cargo compartment. After a maximum period of 60
Seconds, the Low Pressure Indicating System is activated for Fire
Extinguisher Bottle 1 and the DISCH 1 Amber color Indicator Light on
the CARGO COMPT SMOKE DET Panel 433VU will illuminate
(A300/A310).

The appropriate Squib in Fire Extinguisher Bottle 2 Discharge Head is


electrically ignited, rupturing the diaphragm or disc, and discharging the
Extinguisher Agent into the same Cargo Compartment as Extinguisher
Bottle 1 was initially discharged in for the Smoke and/or Fire Condition.
After a maximum period of 60 Seconds the Low Pressure Indicating
System is activated for Fire Extinguisher Bottle 2 and the DISCH 2
Amber color Indicator Light will illuminate.
Electrical Interlock Circuit with two Interlock Relays, Relay FIN 22WM
prevents Bottle 2 from being discharged before Bottle 1 into the
AFT/BULK Cargo Bay. Relay FIN 23WM prevents Bottle 2 from being
discharged before Bottle 1 into the FWD Cargo Bay. The two Relays
located in Panel 282VU in the Avionics Bay prevents Fire Extinguisher
Bottle 2 from being discharged before Extinguisher Bottle 1 and ensures
that both bottles are discharged into the same Cargo Compartment.
The quantity of Fire Extinguishing Agent carried in the system ensures
effective fire retarding action in the affected Cargo Compartment to allow
the flight to continue for a Maximum Period of 90 Minutes (One Hour and
30 minutes) after Fire Extinguisher Bottle 1 is initially discharged.
A SQUIB TEST can be performed on the Maintenance Panel ELEC &
CARGO COMPT SMOKE DET Panel 494 (A300) and 471VU (A310) for
checking the service condition of all four squibs without electrically
igniting them. By pressing the SQUIB TEST PBsw, BTL 1 OK and BTL
2 OK White color Indicator Lights will illuminate when all the Squibs are
electrically

The concentration of Extinguishing Agent is designed to be fire retardant


for 60 Minutes (One Hour). When the Fire Extinguishing System is
initially operated, a Timing Circuit is activated and after 60 Minutes the
DISCH AGENT 2 Amber color Indicator Light on CARGO COMPT
SMOKE DET Panel 433VU illuminates, reminding the crew to discharge
the Second Fire Extinguisher Bottle. The AGENT Switch must then be
moved from AGENT 1 position to AGENT 2 position. The Time Delay
Relay FIN 14WM is located in Panel 282VU in the Avionics Bay.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-77
2677

ATA 26
A300/A310

Some A310 Lower Cargo Compartment Fire Bottles with Flow Metering
Configuration 01
One large and one small bottle

Configuration 02
Two large bottles

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-78
2678

ATA 26
A300/A310

Some A310 Lower Cargo Compartment Fire Protection Panels - Ten (10) Detector System
MONITORING AND INDICATING
The CARGO COMPT SMOKE DET Panel 433VU on the Flight
Compartment Overhead Panel are located three SMOKE Red color
Warning Lights, six LOOP/OFF PBsw(s) corresponding to the Four
Smoke Detectors in the FWD and AFT Cargo Bays, and Two Smoke
Detectors in the BULK Cargo Bay.
A LOOP TEST PBsw enables the Test System to check for electrical
continuity of the Smoke Detectors and associated circuitry to be tested
on the Maintenance Panel 472VU, where are located one ELEC &
CARGO COMPT SMOKE DET/CONTROL UNIT Annunciator indicating
any FAULT in the operation of the electronic unit:
Ten-position Smoke Detector Test Selector Switch common to
Avionic and Cargo Compartment Smoke Detectors.
PTT PBsw Enabling Circuit selected by the Test Selector Switch to
be tested.
PTT PBsw is ON in any position to be tested and is OFF in Normal
Flight Position (NORM FLT ).
LOOP Selector Switch (LOOP A or B).

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-79
2679

ATA 26
A300/A310

Aft Cargo Compartment Smoke Detection - Warning Logic


SYSTEM FAULT INDICATION
AFT CARGO COMPARTMENT SMOKE DETECTION - WARNING
LOGIC MAINTENANCE TEST
1.
2.
3.

After a test with negative result, a spurious warning or a nondetection, the faulty detector will be isolated by the switches
Check of the Control Unit-to-MW LOOP by testing each detector
with the selector switches
Check of the detection function on one LOOP A or B and of MW
SMOKE connection select A channel for FWD Cargo Compartment
Detection (LOOP A PBsw Pressed-In and LOOP B Released-Out)
and press LOOP TEST PBsw.
LOOP A, SMOKE (Panel) SMOKE (NM) are triggered for the
FWD cargo compartment
LOOP A, LOOP B, SMOKE (Panel), SMOKE (MW) are triggered
for the AFT and BULK Cargo Compartments.
Select B channel for the FWD Cargo Compartment Detection
(LOOP A Released-Out and LOOP B Pressed-In) and Press
LOOP TEST PBsw.
LOOP B SMOKE (Panel), SMOKE (MW) are triggered for the
FWD Cargo Bay
LOOP A, LOOP B, SMOKE (Panel) and SMOKE (MW) are
triggered for the AFT and BULK cargo compartments.

Loop Inhibition can be checked for the FWD Cargo Compartment


Detection by applying the same procedure for AFT and BULK Cargo
Bays. NOTE 1: Testing of each Detector is f the Ten Position Selector
Switch and LOOP A/LOOP B Switch. For Example: With switch in LOOP
A position and Selector Switch in FWD 1 position, Detector A1 is tested.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-80
2680

ATA 26
A300/A310

A300 / Some A310 Lower Cargo Compartment Smoke Detection - Controls and Indications
FWD/AFT & BULK SMOKE Lights (red)
Illuminates when smoke is detected by any detector in the FWD or (AFT
& BULK) cargo compartment.

5.

DISCH 1(2) Lights (amber)


Illuminates when the related bottle pressure drops below a
predetermined level.

1.

FWD SMOKE Light is accompanied by:


Closure of related isolation valves.
EQUP COOL vents overboard.

6.

DISCH AGENT 2 Light (amber)


Illuminates one hour after discharge of AGENT 1 to serve as a
reminder for AGENT 2 discharge. The second bottle maintains the
necessary agent concentration in the affected compartment.

2.

AFT & BULK SMOKE Light is accompanied by:


Closure of BULK compartment isolation valve.
ISOL VALVE FAULT light illumination.
Closure of BULK compartment hot air valve.
BULK compartment extract fan de-powered.

The DISCH AGENT 2 Light extinguishes after AGENT 2 is fully


discharged through the metering valve.
NOTE: Lower cargo compartments of the Non-ETOPS configured
A310s have a 2-bottle fire suppression system that is similar to the A300
system except it has only 90 minutes of fire suppression capability.

AGENT 1(2) Selectors


Guarded (safety-wired) - Squibs are de-energized.
3.

AGENT 1 Switches (spring-loaded) - Squib fires bottle 1 into the


FWD or AFT & BULK compartment as selected.

4.

AGENT 2 Switches (spring-loaded) - Agent 2 is active only after


AGENT 1 is discharged (into the same compartment). Squib fires
bottle 2 into the FWD or AFT & BULK compartment as selected.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-81
2681

ATA 26
A300/A310

A300 / Some A310 Lower CARGO COMPT SMOKE DET Controls and Indications

1
3

5
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-82
2682

6
ATA 26
A300/A310

Some A310 Lower CARGO COMPT SMOKE DET Panel 433 VU - Ten (10) Detector System
DESCRIPTION
5.
1.

FWD, AFT BULK CARGO COMPT SMOKE LIGHTS


The SMOKE Red color illuminates when smoke is detected in the
respective Cargo Compartment. Illumination of a SMOKE Light is
accompanied by ECAM Activation.

2.

DISCH 1 and DISCH 2 LIGHTS


A light illuminates Amber color when the related Extinguisher
Bottle is discharge. The light extinguishes only when the empty
Extinguisher Bottle has removed and replaced with a new
Extinguisher Bottle.

3.

DISCH AGENT 2 LIGHT


The light illuminates Amber color 60 Minutes (One Hour) after
discharge of Extinguisher Bottle 1 (AGENT 1) for either the FWD
or AFT/BULK Cargo Compartment. It serves as a reminder to
discharge Extinguisher Bottle 2 to maintain the necessary
Extinguishing Agent concentration in the affected Cargo
Compartment. The light extinguishes when Extinguisher Bottle 2
(AGENT 2) has been discharged.

4.

FWD, AFT, BULK CARGO COMPT AGENT SWITCHES


Both switches are guarded with Safety Gates and lock wired with
breakaway wire. The switches control the ignition of the Squibs
and discharging the Extinguishing Agent from the selected
Extinguisher Bottle to the affected Cargo Compartment with the
Smoke and/or Fire Condition:

AGENT 1
The Squib of Extinguisher Bottle 1 is ignited for discharge to the
affected Cargo Compartment (FWD or AFT/BULK)
AGENT 2
The Squib of Extinguisher Bottle 2 is ignited for discharge to
The affected Cargo Compartment (FWD or AFT/BULK), if the
AGENT Switch has been initially selected to AGENT 1
NEUTRAL (CENTER POSITION)
Discharge Heads on Bottle 1 and 2 are de-energized

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

FWD, AFT, BULK CARGO COMPT LOOP A/B PBsw


The PBsw controls the activation of the related Smoke Detection
Loop for each Cargo Compartment:
ON (PBsw Pressed-In)
The LOOP is activated for Smoke Detection
OFF (PBsw Pressed-In)
The LOOP is deactivated. The OFF White color light illuminates
LOOP A/B
The light illuminates Amber color when the active LOOP
generates a Warning Signal. During LOOP TEST, the light
illuminates to indicate a successful test

6.

LOOP TEST PBsw


When pressed, a test of one or both Fire Detection Loops is
activated, depending on LOOP A/B PBsw selection:
TEST: LOOP A/B
With both LOOPS activated, a successful test is indicated by
illumination of:
LOOP A/B Light
SMOKE Light on the CARGO COMPT SMOKE DET Panel
433VU (Some A310)
ECAM Activation which includes:
WARNING LIGHT DISPLAY PANEL (WLDP) on some
A310. No WLDP on A300 Aircraft
TEST: LOOP A/B
With LOOP A/B PBsw selected OFF , a successful test is
indicated by illumination of:
LOOP A/B Light
SMOKE Light on the CARGO COMPT SMOKE DET PANEL
433VU
ECAM Activation
NOTE
After the Test, Bulk Cargo Compartment Ventilation System Isolation
Valve must be RESET by Releasing Out the ISOL VALVE PBsw and
Pressing-In (Latch-In) on the Flight Compartment Overhead Panel on the
COMPT TEMP Panel 437VU.

26-83
2683

ATA 26
A300/A310

Some A310 Lower CARGO COMPT SMOKE DET Control Panel 433 VU

1
5

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-84
2684

ATA 26
A300/A310

FIRE PROTECTION SYSTEM


MAIN DECK CARGO
COMPARTMENT (MDCC)

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-85
2685

ATA 26
A300/A310

Main Deck Cargo Compartment (MDCC) Smoke Detection System


GENERAL

The main deck cargo compartment smoke detection system consists of:
Twenty ionization smoke detectors installed at floor level.
A sniffer pipe system connecting smoke detectors to the avionics
cooling air extraction system.
Three smoke detection control units which take into account
AND/OR logics according to detectors connection.
An indicating monitoring and testing assembly:
to show warnings
to check the detection and monitoring circuits.
DESCRIPTION
Principle
Detection is carried out by duct smoke detectors which are of the
ionization type. The duct smoke detectors are installed in pairs at cargo
compartment floor level and located as follows:
Six detectors in the MID1 cargo compartment: Two at the front, two
at the center and two at the rear of the compartment.
Six detectors in the MID2 cargo compartment: Two at the front, two
at the center and two at the rear of the compartment.
Eight in the AFT cargo compartment: Two at the front, two at the
center, two at the rear and two at the external rear of the
compartment.

COMPONENT LOCATION
FIN
1WU
2WU
3WU
4WU
5WU
6WU
7WU
8WU
9WU
10WU
11WU
12WU
13WU
14WU
15WU
16WU
17WU
18WU
19WU
20WU

FUNCTIONAL DESIGNATION
DET A2 COMPT SMOKE, MIDDLE 1 CARGO
DET A1 COMPT SMOKE, MIDDLE 1 CARGO
DET B2 COMPT SMOKE, MIDDLE 1 CARGO
DET B1 COMPT SMOKE, MIDDLE 1 CARGO
DET A1 COMPT SMOKE, MIDDLE 2 CARGO
DET A3 COMPT SMOKE, MIDDLE 1 CARGO
DET B1 COMPT SMOKE, MIDDLE 2 CARGO
DET B3 COMPT SMOKE, MIDDLE 1 CARGO
DET A3 COMPT SMOKE, MIDDLE 2 CARGO
DET A2 COMPT SMOKE, MIDDLE 2 CARGO
DET B3 COMPT SMOKE, MIDDLE 2 CARGO
DET B2 COMPT SMOKE, MIDDLE 2 CARGO
DET A2 COMPT SMOKE, AFT CARGO
DET A1 COMPT SMOKE, AFT CARGO
DET B2 COMPT SMOKE, AFT CARGO
DET B1 COMPT SMOKE, AFT CARGO
DET A4 COMPT SMOKE, AFT CARGO
DET A3 COMPT SMOKE, AFT CARGO
DET B4 COMPT SMOKE, AFT CARGO
DET B3 COMPT SMOKE, AFT CARGO

For each zone, the detectors are connected to a smoke detection control
unit located in the Avionics Compartment, LH electronics rack 80VU
Each detector pair operates according to the dual loop logic of the
corresponding control unit.
In each pair, a detector is for LOOP A and the other for LOOP B.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-86
2686

ATA 26
A300/A310

A300 / A310 Main Deck Cargo Smoke Detectors - 20 Detector Units


A300

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

A310

26-87
2687

ATA 26
A300/A310

A300/A310 Main Deck Cargo Compartment Smoke Detection Control Unit - Component Location

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-88
2688

ATA 26
A300/A310

A300/A310 MDCC Smoke Detector - Installation View


A300
MDCC = MAIN DECK
CARGO COMPARTMENT

A310

Filter

Suction
Flow

B Loop

A Loop
MTT M540000 / R3.3 01AUG01
For Training Purposes Only

26-89
2689

ATA 26
A300/A310

A300 MID 1 / MID 2 / AFT MDCC Smoke Detection and Loop System
In normal operation, MAIN DECK CARGO COMPT SMOKE DET/LOOP
A and LOOP B pushbutton switches are pressed in and extinguished. If
there is smoke, smoke detector A triggers LOOP A warning light, smoke
detector B triggers LOOP B and illumination of both triggers SMOKE
warning light on the overhead panel with :

On CAPT and F/O main instrument panels 3VU and 5VU, MASTER
WARN warning lights come on.
triggering of the repetitive chime
triggering of the R ECAM display unit (system display) and L ECAM
display unit (warning display)
closure of :
bulk cargo ventilation
pack 2 if pack 2 is on
two isolation valves
hot air supply.
opening of bypass valve

LOOP Warning Configuration


In case only one LOOP warning light comes on on the overhead panel
(LOOP A for example) with MASTER CAUTION warning light coming on
CAPT and F/O main instrument panels 3VU and 5VU without illumination
of SMOKE warning light, there are two possibilities :
either a spurious detection by one of the smoke detectors of a same
loop (A1, A2 or A3, or A4 (if installed)).
or a true detection by one of the smoke detectors of one loop without
detection of one smoke detector of the other loop (B1, B2 or B3 or
B4 (if installed)).

AIRBUS AIRCRAFT MAINTENANCE MANUAL (AMM) TERMS


A300-600 MDCC = MAIN DECK CARGO COMPARTMENT
A310-200 UDCC = UPPER DECK CARGO COMPARTMENT
or
A310-200 MDCC = MAIN DECK CARGO COMPARTMENT

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-90
2690

ATA 26
A300/A310

A300 MID 1 & 2 MDCC Detection and Loop System - Warning Logic

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-91
2691

ATA 26
A300/A310

A300 MID 1/MID 2/AFT MDCC Smoke Detection and Loop System
Confirmation of one of the two possibilities is obtained by pressing the
corresponding OFF switch to release itIt must come on while LOOP
warning light goes offAfter that carry out test of the other loop (B)

If the test indicates a correct operation, i.eif LOOP warning light of


the other loop (B1, B2 or B3 or B4 (if installed)) comes on, it means
that smoke detectors of that loop function correctly and
consequently that detection through the first loop (A1, A2 or A3 or
A4 (if installed)) is spurious

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-92
2692

If the test indicates a faulty operation, i.eif LOOP warning light of the
other loop (B1, B2 or B3 or B4 (if installed)) remains off, it means
that at least one smoke detector of that loop do not function and
consequently that detection through the first loop is correct : it is the
case of a true warningThe faulty smoke detector will be isolated by
means of the ten-position smoke detector test selector switch on the
maintenance panel.

ATA 26
A300/A310

A300 Aft MDCC Smoke Detection and Loop System - Warning Logic

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-93
2693

ATA 26
A300/A310

MAIN DECK CARGO SMOKE DET Control Panel 433VU

1
2
3
4

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-94
2694

ATA 26
A300/A310

A310 MID 1/MID 2/AFT MDCC Smoke Detection


If the test indicates a correct operation, i.e. if LOOP Legend of the other
loop (B1, B2 or B3 or B4 (if installed)) comes on, it means that smoke
detectors of that Loop function correctly and consequently that detection
through the first loop (A1, A2 or A3 or A4 (if installed)) is spurious.
If the test indicates a faulty operation, i.e. if LOOP warning light of the

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

other Loop (B1, B2 or B3 or B4 (if installed)) remains off, it means that at


Least one smoke detector of that Loop does not function and
consequently that detection through the first Loop is correct, the warning
is a true warning. The faulty smoke detector will be isolated by means of
the ten-position MAIN DECK CARGO SMOKE DET selector switch on
the Lateral panel.

26-95
2695

ATA 26
A300/A310

A310 MID 1/MID 2/AFT MDCC Smoke Detection


Operation in Normal (true) Warning Configuration. In normal operation,
LOOP A/OFF and LOOP B/OFF push-button switches are pressed and
legends are off. If there is smoke, smoke detector A triggers LOOP A
Legend illumination, smoke detector B triggers LOOP B Legend
illumination and illumination of both LOOP legends triggers SMOKE
warning light on the overhead panel with:
Illumination of SMOKE warning light on WLDP;
Activation of repetitive chime;
AIR COND page display (flow diagram) on R ECAM display unit;
Message displayed on L ECAM display unit;
Closure of:
- bulk cargo compartment isolation valve;
- pack 2 flow control valve if packs 1 and 2 operate;
- two isolation valves;
- hot air supply valve;
opening of bypass valve.

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

LOOP Warning Configuration


In case only one LOOP Legend of LOOP/OFF push-button switch comes
on, on the overhead panel (LOOP A for example) with LOOP warning
Light on WLDP and without illumination of SMOKE warning Light (on
overhead panel), there are two possibilities: Either a spurious detection
by one of the smoke detectors of a same loop (A1, A2 or A3, or A4 (if
installed)); or a true detection by one of the smoke detectors of one Loop
without detection of one smoke detector of the other loop (B1, B2 or B3
or B4 (if installed)).
Confirmation of the real status is obtained by releasing the
corresponding LOOP/OFF push-button switch (OFF Legend comes on
and LOOP Legend goes off). Press LOOP TEST push-button switch to
test the other Loop (B).

26-96
2696

ATA 26
A300/A310

A300 MDCC Smoke Detection - Controls, Indications, BITE Test

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-97
2697

ATA 26
A300/A310

MAIN DECK CARGO SMOKE DET Control Panel 433VU


OPERATION

the SMOKE warning. When only one Smoke Detector senses SMOKE,
only LOOP Warning Light of the corresponding Loop is triggered on the
Flight Compartment Overhead Panel on MAIN DECK CARGO SMOKE
DET Panel 433VU.

Operation in Normal (True) Warning Configuration


In normal operation, MAIN DECK CARGO COMPT SMOKE DET Panel
433/ LOOP A and LOOP B Pushbutton Switches are Pressed-In and
Extinguished. If there is Smoke, Smoke Detector A triggers LOOP A
Warning Light, Smoke Detector B triggers LOOP B and illumination of
both LOOPS (A and B) triggers SMOKE Warning Light on the Flight
Compartment Overhead Panel:

ADDITIONAL FIRE SHUT OFF PROCEDURE INFORMATION


The fire shut off procedure can be released by the smoke signal
from the Smoke Detection System or by releasing the Pushbutton Switch
(PBsw) MAIN DECK CARGO VALVES located on the Flight
Compartment Overhead Panel on the VENT Panel 438VU.

On Captain and First Officer (FO) Main Instrument Panels 3VU


(Captain) and 5VU (FO), MASTER WARN Red color warning lights
illuminates (A300/Some A310). Red color SMOKE Light illuminates
on the Warning Light Display Panel (WLDP) (On Some A310).
Triggering of the Continuous Repetitive Chime (CRC) for Aural
Warning Sound on the Flight Compartment Loudspeakers on the
ceiling
Triggering ECAM Activation for RH ECAM (System Display) and LH
ECAM (Warning Display) for Smoke Condition and Information
Bulk Cargo Ventilation Isolation Valve CLOSES
Pack 2 CLOSES, if Pack 2 ON
Two Isolation Valves CLOSE under Forward Cargo Compartment
Floor area for the:
RH Valve FIN 102HG for the AFT Temperature Zone Riser Duct
LH Valve FIN 103HG for the MID Temperature Zone Riser Duct
Hot Air Supply Manifold Pressure Regulating and Shut Off Valve
(PRSOV) CLOSES
Cold Air Manifold Bypass Valve FIN 101HG OPENS to dump cold air
into the inlet area of the Forward Outflow Valve and flows into the Air
Conditioning Bay and overboard through the Main Gear Wheel Wells

When the MAIN DECK CARGO VALVE PBsw is released out or a


Smoke Signal is sent from one of the three Main Deck Smoke Detection
System Control Unit(s) located in the Electronic Rack 80VU/Shelves
85VU and 86VU. At this time the Smoke Detection System Interface
Relay FIN 100WU located on Relay Panel 103VU in the Avionics Bay
forward area is actuated will cause the following:

Bypass Valve 101HG OPENS


CLOSING of Pack Flow Control Valve 2 (If Pack 1 and 2 are running)
Pack Flow Control Valve 1 is set to 100% flow rate
CLOSING of the Hot Air Supply Manifold PRSOV
Closing of the Bulk Cargo Isolation Valve located on the RH Side of
the Bulk Cargo Bay
When the Cold Air Manifold Supply Bypass Valve is FULLY
OPEN, the Cold Air Manifold Supply Isolation Valves (RH FIN
102HG and LH FIN 103HG) CLOSE
The crew confirms the Automatic Action by releasing the associated
illuminated PBsw:
Releasing MAIN DECK CARGO VALVES PBsw (If Fire Shut Off is
initiated by the Main Deck Cargo Smoke Detection System)
Confirmation of Pack SHUT OFF
Confirmation of Bulk Cargo Isolation Valve CLOSED
Confirmation of Hot Air Supply Manifold PRSOV CLOSED

Risks of spurious SMOKE Warnings due to a faulty operation of one


Smoke Detector are avoided due to the fact that both Detectors (One in
each Loop/A LOOP and B Loop) must detect simultaneously to trigger

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-98
2698

ATA 26
A300/A310

A300 MDCC Smoke Detection - Controls, Indications, BITE Test

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-99
2699

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Configurations - Extinguisher Bottles 1, 2 and 3


The fire extinguishing system consists of three fire extinguisher bottles,
aluminum tubes, flexible rubber hoses, several quick-disconnects and a
multi-way valve.
The fire extinguisher bottles are located at STA1340/FR18 (A300/A310)
on the compartment floor fixed in a mounting with removable clamps.
The hoses of the fire extinguisher bottles are connected to the fire
extinguishing lines via quick disconnects. Above the bottles at
STA1393/FR19 (A300) - FR18 (A310) the multi-way valve is mounted at
the sidewall. It enables the operator to choose between three container
arrangement configuration possibilities:

The system has four connecting points for cargo containers. Two are
located at STA1446/FR20 (A300/A310), one at the left and one at the
right sidewall. Another one is located at STA1923/FR29 (A300) STA1393/FR19 (A310) at the left sidewall.
The connections between these connecting points and the cargo
containers are realized by flexible rubber hoses and quick-disconnect
couplings. When not in use, the rubber hoses are fixed in stowage
positions located next to the connecting points. The stowage positions
consist each of a quick disconnect blanked on one side which is
mounted on a bracket at the sidewall.

Configuration 1 - Three LD3 containers


Configuration 2 - One LD3 and one LD6 container
Configuration 3 - One LD3 and two LD6 containers

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-100
26100

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Configurations - Extinguisher Bottles 1, 2 and 3

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-101
26101

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Fire Extinguishing System


The MDC Compartment Cargo Container Fire Extinguishing System
(referred to as fire extinguishing system) is installed in the front section
of the MDC compartment between STA1340/FR18 (A300/A310) and
STA1923/FR29 (A300) - FR35 (A310) and allows to fill a single cargo
container with fire extinguishing agent, if necessary. The connection

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

between the fire extinguisher bottles and the cargo containers is realized
by fire extinguishing lines consisting of tubes, flexible hoses and quick
disconnects. A multi-way valve enables the operator to choose between
three cargo container configurations.

26-102
26102

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Fire Extinguishing System

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-103
26103

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Configurations - Extinguisher Bottles 1, 2 and 3


The fire extinguishing system consists of three fire extinguisher bottles,
aluminum tubes, flexible rubber hoses, several quick-disconnects and a
multi-way valve.
The fire extinguisher bottles are located at STA1340/FR18 (A300/A310)
on the compartment floor fixed in a mounting with removable clamps.
The hoses of the fire extinguisher bottles are connected to the fire
extinguishing lines via quick disconnects. Above the bottles at
STA1393/FR19 (A300) - FR18 (A310) the multi-way valve is mounted at
the sidewall. It enables the operator to choose between three container
arrangement configuration possibilities:

The system has four connecting points for cargo containers. Two are
located at STA1446/FR20 (A300/A310), one at the left and one at the
right sidewall. Another one is located at STA1923/FR29 (A300) STA1393/FR19 (A310) at the left sidewall.
The connections between these connecting points and the cargo
containers are realized by flexible rubber hoses and quick-disconnect
couplings. When not in use, the rubber hoses are fixed in stowage
positions located next to the connecting points. The stowage positions
consist each of a quick disconnect blanked on one side which is
mounted on a bracket at the sidewall.

Configuration 1 - Three LD3 containers


Configuration 2 - One LD3 and one LD6 container
Configuration 3 - One LD3 and two LD6 containers

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-104
26104

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Configurations - Extinguisher Bottles 1, 2 and 3

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-105
26105

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Fire Extinguishing System - Components


Fire Extinguisher Bottle
The fire extinguisher bottle consists of a cylindrical metal container with
a flat bottom and an operating head on the top. The operating head
includes the handle with activating lever and safety pin and a pressure
gage.

The positions are visually indicated. A placard next to the valve shows
the lever positions in relation to the cargo container arrangement

The pressure gage is divided into three zones: a red area 'RECHARGE,'
a green area and another red area 'OVERCHARGE.' The green area
shows the correct filling condition at approx. 150 PSI (10.3 bar).

Operation
After receipt of a smoke warning signal on cockpit overhead warning
panel 448VU, one or more fire extinguisher bottles must be manually
activated. The lever of the multi-way valve must be in the required
position and the flexible hoses must be connected to the connecting
points of the fire extinguishing lines and the cargo containers.

An information label which informs the operator how to use and to check
the fire extinguisher bottle is bonded to the container bottle. When
correctly filled, the bottle contains 14 lbs. (6.35 kg) Halon 1211
extinguishing agent.
Multi-way Valve
The multi-way valve is a four-position selector valve with three inlet and
three outlet ports. The valve is manually operated by a pivoted lever.
The four possible positions are:

configurations. The multi-way valve makes it possible to connect each


fire extinguisher bottle to each cargo container.

When the safety pin is removed, the release handle at the top of the fire
extinguisher bottle can be pulled. The extinguishing agent then flows
through the multi-way valve into the chosen cargo container.

All Containers
Container 1
Container 2
Container 3

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-106
26106

ATA 26
A300/A310

A300/A310 MDCC Fire Extinguisher Bottle and Multi-way Valve

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-107
26107

ATA 26
A300/A310

A300/A310 MDCC Fire Extinguishing - Lines and Connectors


Fire Extinguishing Lines and Connectors
The fire extinguishing lines consist of aluminum tubes which are
mounted with clamps to the fuselage structure.
The connection between the fire extinguisher bottles to the fire
extinguishing lines and the connection between the connecting points to

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

the related cargo container is realized by flexible rubber hoses via quick
disconnect couplings.
The fire extinguishing lines are designed to release the extinguishing
agent from one fire extinguisher bottle into a cargo container within
approx. 20s.

26-108
26108

ATA 26
A300/A310

A300/A310 MDCC Cargo Container Fire Extinguishing - Pipework and Connectors

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-109
26109

ATA 26
A300/A310

THIS PAGE INTENTIONALLY


LEFT BLANK
ATA 26 -END
COURSE CODE - M540000

MTT M540000 / R3.3 01AUG01


For Training Purposes Only

26-110
26110

ATA 26
A300/A310

Вам также может понравиться