CT Measuring vs Protection
Measuring CT
Protection CT
Copyright
CT Standards
IEC/AS 60044-1: Instrument transformers - Part 1 Current transformers (ed. 1.2 2003)
IEC/AS 60044-6: Instrument transformers - Part 6
Requirements for protective current transformers for
transient performance
IEC/AS 60044-8: Instrument transformers -Part 8 Electronic current transformers
AS 1675: Current Transformers Measurement &
Protection (now superseded)
BS7626 (BS 3938): Specification for current
transformers (now superseded)
Copyright
CT AS 60044 - 1 Class P
Rated Composite Error at ALF
(turn ratio error, iron / copper
losses, saturation)
AS 60044:
5P20 5VA
AS 1765:
5P 100 F20
Conversion:
Vref I sec = VA ALF
Copyright
CT AS 60044 - 1 Class PX
(similar to BS 3938 Class X
AS 1675 Class PL)
Dimensioning
Rated resistive
factor (Kx)
burden (Rb)
CT Dimensioning
Operational Accuracy Limit Factor ALF
ALF' = ALF
Pi + PN
Ri + RN
= n
Pi + PB
Ri + RB
P + PB
Ri + RB
ALF = ALF' i
= ALF'
Pi + PN
Ri + RN
Rated CT burden:
Internal CT burden:
PN
Pi=Ri I2N2
Actually connected
burden :
PB= RB I2N2
CT Dimensioning
Operational Accuracy Limit Factor ALF
I
ALF ' K OD SC
IN
Where KOD is the total
over-dimensioning factor:
K OD K TF K Rem
K Rem
% remanence
= 1+
100
Theory:
No saturation during
BMax
XN
K'
TF
=
=
1
+
T
N
=
1
+
total fault duration:
B~
No saturation for
the specified time tM:
RN
tM
tM
T
N TS
K ' 'TF = 1+
(e TN e TS
TN TS
Practice:
K OD = KTF
Remanence only considered in extra high
voltage systems (EHV)
KTF-values acc. to relay manufacturers guides
Copyright
CT Dimensioning
Choice of CT rated power
Rated burden > total connected burden
For GIS and MV switchboard with modern
relays/measuring devices, class P 1A CTs
with small rated burden are sufficient, e.g.
5VA, 10VA
Choice of Accuracy Limit Factor
Relay manufacturers recommendation
should be followed + engineering secuirty
factor
CT performance depends on operational
ALF
Copyright
CT Dimensioning
Choice of CT Ratio
CT ratio should be based on the protected object,
however, it may need to be go higher:
limitation of difference in CT ratio for low impedance
differential protection as recommended by the relay
manufacturer
Avoid excessive over-dimensioning:
Imax, switchgear / Ipri-rated > 100 !
Such CT can damage the relay because there is no CT saturation
Copyright
CT Dimensioning
Choice of Measuring CT
For classes 0.1 1, the accuracy is based on a total connected
burden between 25% to 100% of the rated burden
For classes 0.1, 0.2 and 0.2S with rated burden < 15VA, an
extended range of burden can be specified (from 1VA to 100% of
the rated burden)
For classes 3 and 5, the accuracy is based on a total connected
burden between 50% to 100% of rated burden
Instrument security factor (FS) defines the maximum secondary
current that will flow under short circuit of primary circuit
Instrument security factor (FS) is based on the rated burden
Under-burdened measuring CT can damage connected
instrument during short circuit or overload of the primary circuit
Copyright
CT Dimensioning
Overcurrent Protection
CT saturation is allowable provided the remaining fundamental current is
higher than I>> setting
Copyright
CT Dimensioning
Differential Protection
Differential protection should be stable on external faults
High sensitivity for internal fault
Protected Object
Relay
Type
min. saturation
free time (ms)
min. over
dimensioning
KTF
min. saturation
free time (ms)
min. over
dimensioning
KTF
Generator
7UM6
0.75
1.20
Transformer
7UT6
0.75
1.20
7SD52
0.50
1.20
7SD61
0.50
1.20
7SD600
1.20
1.00
Busbar
7SS52
0.50
0.50
7SS600
0.75
Copyright
CT symmetry
0.75
4
0.75
Siemens.