Project:
WIND CALCULATION FOR CANOPY
L. L. C.
ROARK
CONSULTING
1. Scope of work:
2.
Materials:
Structural Steel
Structural steel shall be designed in accordance with the specification given in steel
construction manual - AISC 14th edition LRFD Method.
Structural Steel Shapes:
Shapes
ASTM Designation
Mechanical Properties
A992
Fy = 50 ksi
Fu = 65 ksi
HSS
A500 Gr. B
Fy = 46 ksi
Fu = 58 ksi
Plate
A36
Fy = 36 ksi
Fu = 58 ksi
4. Loading:
Dead Load
3 psf
Live Load
5 psf
Wind Load
L. L. C.
ROARK
CONSULTING
5. Load Combinations
1.2DL+1.6LL
7.
Deflection Limits
1.0LL
L/360
1.0DL + 1.0LL
L/240
H/120
L. L. C.
ROARK
CONSULTING
16-6
Exposure Category
00
qh
0.00256 Kz Kzt Kd V2
Kz
0.865
Kzt
Kd
0.85
115 mph
0.00256 (0.865)(1)(0.85)(115)2
24.89 psf
0.85
Cpi
+0.18
-0.18
Where,
Therefore,
qh
L. L. C.
ROARK
CONSULTING
-
Per ASCE 7-10 Code for Bldgs. of Any Height with Gable Roof <= 45o or Monoslope Roof <= 3o
Using Part 1 & 3: Analytical Procedure (Section 30.4 & 30.6)
Job Name:
CANOPY
Subject:
Job Number:
AZ15156
Originator:
Checker:
Input Data:
Wind Speed, V =
Bldg. Classification =
Exposure Category =
Ridge Height, hr =
Eave Height, he =
Building Width =
Building Length =
Roof Type =
Topo. Factor, Kzt =
Direct. Factor, Kd =
Enclosed? (Y/N)
Hurricane Region?
Component Name =
Effective Area, Ae =
Overhangs? (Y/N)
115
II
C
16.50
16.50
20.42
34.08
Monoslope
1.00
0.85
Y
N
Decking
695.92
N
Resulting
Parameters and
Coefficients:
Roof Angle, =
Mean Roof Ht., h =
0.00
16.50
deg.
ft. (h = he, for roof angle <=10 deg.)
L. L. C.
ROARK
CONSULTING
Component
Decking
For z = hr:
For z = he:
For z = h:
0.87
0.87
24.92
24.92
9.47
9.47
-26.92
-26.92
-31.90
-31.90
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 2 (edge), 'a' =
3.00
ft.
3. Width of Zone 3 (corner), 'a' =
3.00
ft.
4. For monoslope roofs with <= 3 degrees, use Fig. 30.4-2A for 'GCp' values with 'qh'.
5. For buildings with h > 60' and > 10 degrees, use Fig. 30.6-1 for 'GCpi' values with 'qh'.
6. For all buildings with overhangs, use Fig. 30.4-2B for 'GCp' values per Sect. 30.10.
7. If a parapet >= 3' in height is provided around perimeter of roof with <= 10 degrees,
Zone 3 shall be treated as Zone 2.
8. Per Code Section 30.2.2, the minimum wind load for C&C shall not be less than 16 psf.
Zone 3
(-)
-31.90
-31.90
-31.90
-31.90
-31.90
L. L. C.
ROARK
CONSULTING
Wind load of canopy walls are calculated based on ASCE 7-10, Chapter 30, and Part 1 section
30.1.1Wind Load -Components and Cladding
For West Elevation:
WIND LOADING ANALYSIS - Wall Components and Cladding
Per ASCE 7-10 Code for Buildings of Any Height
Using Part 1 & 3:
Analytical Procedure
(Section 30.4 & 30.6)
Job Name:
Job Number:
CANOPY
AZ15156
Subject:
Originator:
Checker:
Input Data:
Wind Speed, V =
Bldg. Classification =
Exposure Category =
Ridge Height, hr =
Eave Height, he =
Building Width =
Building Length =
Roof Type =
Topo. Factor, Kzt =
Direct. Factor, Kd =
Enclosed? (Y/N)
Hurricane Region?
Component Name =
Effective Area, Ae =
115
II
C
16.50
16.50
20.42
34.08
Monoslope
1.00
0.85
Y
N
Wall
323.76
Roof Angle, =
0.00
16.50
deg.
ft. (h = he, for roof angle <=10
deg.)
Resulting Parameters
and Coefficients:
L. L. C.
ROARK
CONSULTING
=
zg =
Kh =
9.50
900
0.87
(Table 26.9-1)
(Table 26.9-1)
(Kh = Kz evaluated at z = h)
Component
For z = he:
For z = h:
16.50
16.50
0.87
0.87
24.92
24.92
20.94
20.94
-23.18
-23.18
20.94
20.94
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 5 (end zones), 'a' =
3.00
ft.
3. Per Code Section 30.2.2, the minimum wind load for C&C shall not be less than 16 psf.
-23.93 psf governs the wind force on fabric. (For West Elevation)
-23.93
-23.93
L. L. C.
ROARK
CONSULTING
Wind load of canopy walls are calculated based on ASCE 7-10, Chapter 30, and Part 1 section
30.1.1Wind Load -Components and Cladding
For North & South Elevation:
WIND LOADING ANALYSIS - Wall Components and Cladding
Per ASCE 7-10 Code for Buildings of Any Height
Using Part 1 & 3:
Analytical Procedure
(Section 30.4 & 30.6)
Job Name:
Job Number:
CANOPY
AZ15156
Subject:
Originator:
Checker:
Input Data:
Wind Speed, V =
Bldg. Classification =
Exposure Category =
Ridge Height, hr =
Eave Height, he =
Building Width =
Building Length =
Roof Type =
Topo. Factor, Kzt =
Direct. Factor, Kd =
Enclosed? (Y/N)
Hurricane Region?
Component Name =
Effective Area, Ae =
115
II
C
16.50
16.50
20.42
34.08
Monoslope
1.00
0.85
Y
N
Wall
193.99
Roof Angle, =
0.00
16.50
deg.
ft. (h = he, for roof angle <=10
deg.)
Resulting Parameters
and Coefficients:
L. L. C.
ROARK
CONSULTING
=
zg =
Kh =
9.50
900
0.87
(Table 26.9-1)
(Table 26.9-1)
(Kh = Kz evaluated at z = h)
Component
For z = he:
For z = h:
16.50
16.50
0.87
0.87
24.92
24.92
21.82
21.82
-24.06
-24.06
21.82
21.82
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 5 (end zones), 'a' =
3.00
ft.
3. Per Code Section 30.2.2, the minimum wind load for C&C shall not be less than 16 psf.
-25.69 psf governs the wind force on fabric. (For North & South Elevation)
-25.69
-25.69
L. L. C.
ROARK
CONSULTING
16.5/0.42
39.6
2.0
Therefore,
P = 24.92(0.85)(2.0)(0.42)
= 17.79 plf