Академический Документы
Профессиональный Документы
Культура Документы
Relay Applications
Objectives
PJM2014
1/13/14
Basic Concepts
in
Protection
PJM2014
1/13/14
PJM2014
1/13/14
The Source
Utility Distribution System
200 A
Protected
Receptacles
15 A
15 A
72 Plasma TV
Individual Device Fuse
15 A
Individually-protected
Branch Circuits
Basic Concepts
PJM2014
1/13/14
Basic Concepts
PJM2014
1/13/14
Basic Concepts
PJM2014
1/13/14
Relay Scheme
Components
PJM2014
1/13/14
DC Control Systems
The power source used for controlling power system equipment must be
highly reliable and not subject to interruption by power system transients
or outages
AC
Protection and control circuits are individually fused to guard against
disrupting the entire DC system for problems on a particular branch circuit
10
1/13/14
DC Control Systems
Full DC
Voltage
DC
Voltage
PJM2014
DC
Voltage
Intentional ground
reference connection
1/13/14
DC Control Systems
Illustration Of Actual Battery Ground Indicating Lamps
1/13/14
DC Control Systems
PJM2014
13
1/13/14
Overview of Power
System Protection
PJM2014
1/13/14
OVERLAPPING ZONES
OF PROTECTION!
PJM2014
15
1/13/14
PJM2014
16
1/13/14
PJM2014
17
1/13/14
Instrument Transformers
PJM2014
18
1/13/14
PJM2014
19
1/13/14
PJM2014
20
1/13/14
Slipover CTs
Slipover CTs
Similar to the bushing CTs pictured above, the window CTs below have a single turn primary
winding comprised of the primary current conductor passing through the center of the CT
Primary Conductors
PJM2014
1/13/14
PJM2014
22
1/13/14
PJM2014
23
1/13/14
PJM2014
24
1/13/14
C1
C2
Grounding Switch
PJM2014
C3
Relays
25
1/13/14
Capacitor
Stacks
Transformer
Enclosure
Grounding
Switch
26
PJM2014
27
1/13/14
Relay Devices
PJM2014
1/13/14
Definition
PJM2014
30
1/13/14
General Functions:
Protective
remove a system disturbance from the power system
Regulating
insures system is operated within proper guidelines
Auxiliary
Other less critical functions (i.e. alarms, reclosing. etc.)
PJM2014
31
1/13/14
Electromechanical
Solid State
PJM2014
Microprocessor
1/13/14
Relay Function
IEEE
#
Device
Relay Function
21
Distance
Relay
63
Pressure
Relay
25
Synchronizing
Relay
67
Directional
Overcurrent
27
Undervoltage
Relay
78
Out-of-Step
49
Thermal Relay
79
Reclosing
Relay
50
Instantaneous
Overcurrent
81
Frequency
Relay
51
Time
Overcurrent
86
Lockout
Relay
52
Circuit
Breaker
Circuit Breaker
87
Differential
Relay
59
Overvoltage
Relay
94
Tripping
Relay
Overcurrent
PJM2014
34
1/13/14
T
I
M
E
1X
10X
100X
Current
Inverse Curve Characteristic
PJM2014
35
1/13/14
Over/Under Voltage:
PJM2014
36
1/13/14
Directional Capability
Required Inputs: Current and Voltage
Can be a stand alone relay or associated with another relay element
Directionality makes the life of a protection engineer much easier
from a relay coordination point of view
PJM2014
37
1/13/14
38
1/13/14
Sub C
Sub B
Reactance
Sub C
Sub B
Zone 2 Element (Time Delayed)
Sub A
Resistance
PJM2014
1/13/14
Note that Zone 1 can only be set to see, at most, 90% of the
protected line
Cannot be set to see 100% of the line
Relay would not be able to distinguish between an internal or external
fault
Setting relay to see 100% of line to obtain instantaneous clearing
would most likely result in an overtrip
PJM2014
40
1/13/14
PJM2014
41
1/13/14
Differential
Required input: Current from CTs
Relay generally operates very fast (1 cycle)
Normal protection for Generators, Transformers and
Bus sections
CTs supplying the relay should be matched so that currents
into the zone of protection are equal to those currents
that leave
The difference/mismatch in current is observed in the relays
operate coil
PJM2014
42
1/13/14
Differential Relay
PJM2014
43
1/13/14
Differential Operation
PJM2014
44
1/13/14
PJM2014
45
1/13/14
Lockout Relays
Lockout Relays
Special devices operated by dozens of functions that protect
generators, transformers, busses and various other pieces of
switchyard equipment
Relay itself doesnt protect anything; instead, it has multiple contacts
that cause multiple devices, like circuit breakers, to operate in order to
de-energize or isolate failed equipment
Serve an important function: if they failed to trip for a fault, for
example, the switchyard GCB would stay closed and the equipment
would remain energized
Because its so important, the electrical coil that trips the lockout relay
is monitored continuously by an amber lamp located immediately
above the relay
PJM2014
46
1/13/14
Generator Lockouts
PJM2014
The amber lamp is normally lit to indicate three important things about the
Lockout Relay:
1) There is DC control power available to the lockout relay
2) The lockout relay operating coil is electrically intact
3) The lockout relay is reset and ready to trip
If the lamp isnt lit, it means theres no DC power available or that the lockout coil
has burned openin either case the lockout wouldnt be able to trip, making this a
very serious situation that has to be resolved immediately
The Lockout Relay target is an orange semaphore directly above the relay
handle. When the lockout operates, the amber light goes out and this colored
target appears
The Lockout relay handle being at an angle instead of being perpendicular to the
floor is another indicator of lockout operation
47
1/13/14
RESET
PJM2014
TRIPPED
48
1/13/14
PJM2014
1/13/14
PJM2014
50
1/13/14
PJM2014
51
1/13/14
Quick Review
See example
PJM2014
52
1/13/14
Inductive
Reactance
Inductive
Reactance
Sub B
Sub B
Shunt Capacitance
For Overhead Lines, this
can generally be ignored.
Line Angle
Sub A
Resistance
PJM2014
1/13/14
PJM2014
54
1/13/14
System Stability
If stability studies indicate that delayed clearing of faults on a
transmission line cause a Generator to go unstable, it
indicates that both the primary and backup protective
schemes must clear all faults instantaneously
These studies are done as part of the initial
engineering process
PJM2014
55
1/13/14
Relay Coordination:
If protection studies determine that coordination of backup
relay schemes can not be achieved, dual pilot protection
schemes must be employed on the line to be protected
Typically happens on Long Line/Short Line situations.
See example
PJM2014
56
1/13/14
(some R+jX)
Sub A
Sub B
Sub C
C
Sub B Required
Zone 1 relay.
B
PJM2014
Sub A Required
Zone 2 relay.
1/13/14
PJM2014
58
1/13/14
PJM2014
Directional Comparison
Direct Under-reaching Transferred Trip
Permissive (Over & Under-reaching)
Phase Comparison
AC Pilot Wire
Optical Fiber Differential
59
1/13/14
AND
60
1/13/14
To Initiate Trip:
Over-reaching Relay must operate
Absence of Blocking Signal from remote end
In digital logic:
Over-reaching Relay
AND
Trip
Blocking Signal
Invert
PJM2014
61
1/13/14
PJM2014
62
1/13/14
CCVT
PJM2014
1/13/14
PJM2014
1/13/14
OR
PJM2014
1/13/14
To Initiate Trip:
Under-reaching Relay must operate
OR
Under-reaching Relay
OR
Trip
66
1/13/14
PJM2014
67
1/13/14
68
1/13/14
To Initiate Trip:
Under-reaching Relay must operate
OR
Over-reaching
Relay
Trip Signal from
Remote End
AND
OR
Under-reaching
Relay
PJM2014
69
Trip
1/13/14
PJM2014
70
1/13/14
AND
PJM2014
71
1/13/14
To Initiate Trip:
Over-reaching Relay must operate
AND
Over-reaching Relay
Trip Signal from
Remote End
PJM2014
AND
72
Trip
1/13/14
PJM2014
73
1/13/14
TRIP
Received
Lamp
GUARD
Received
Lamp
MAINT SWITCH
To Key TRIP
For Radial Line
Operation
Illustrations Of
Typical POTT Scheme
Indications and Controls
PJM2014
Phase Comparison
PJM2014
75
1/13/14
CT's
W A VE T RA P
CT's
F3
F2
COUPLING
CAPACITOR
MIXING
NETWORK
AND
LEVEL
DETECTOR
TRANSMITTER
COMPARER
COMPARER
MIXING
NETWORK
AND
LEVEL
DETECTOR
RECEIVER
RF CHOKE
PJM2014
COUPLING
CAPACITOR
RF CHOKE
76
RECEIVER
TRANSMITTER
1/13/14
AC Pilot Wire
PJM2014
77
1/13/14
Sub A
Sub B
A
Restraint
Mixing
Network
V
A
Restraint
Insulating
T ransform er
Mixing
Network
Insulating
T ransform er
Operating
Operating
PJM2014
V
B
Pilot Wires
78
1/13/14
PJM2014
79
1/13/14
PJM2014
80
1/13/14
PJM2014
81
1/13/14
PJM2014
82
1/13/14
PJM2014
83
1/13/14
PJM2014
84
1/13/14
PJM2014
85
1/13/14
PJM2014
86
1/13/14
Reclosing Practices
PJM2014
87
1/13/14
Reclosing Practices
PJM2014
88
1/13/14
Reclosing Practices
PJM2014
89
1/13/14
Reclosing Practices
Manual Reclosing
PJM2014
90
1/13/14
Reclosing Practices
Manual Reclosing
Also used for Try Back (testing) of a line after a fault
Company policy should be followed when fault testing is
being considered
The operator should consider the effects that testing may have on the
electrical system (shocking the system again)
If possible, it is always better to request a patrol of line before trying
to restore it to service
PJM2014
91
1/13/14
Reclosing Practices
PJM2014
92
1/13/14
PJM2014
93
1/13/14
Risks Involved
PJM2014
94
1/13/14
Risks Involved
PJM2014
95
1/13/14
1)
2)
3)
4)
5)
PJM2014
96
1/13/14
PJM2014
97
1/13/14
PJM2014
98
1/13/14
PJM2014
99
1/13/14
PJM2014
1/13/14
Relay Testing
PJM2014
101
1/13/14
PJM2014
102
1/13/14
PJM2014
103
1/13/14
Protection Practice:
PJM2014
104
1/13/14
PJM2014
1/13/14
PJM2014
106
1/13/14
PJM2014
107
1/13/14
Fault analysis
Breakers 1
thru 7 trip
open. Where
is the likely
fault location?
PJM2014
1/13/14
Fault analysis
PJM2014
1/13/14
PJM2014
110
1/13/14
Transformer Protection
PJM2014
1/13/14
Transformers:
PJM2014
112
1/13/14
Transformer Protection
External to Tank
1)
2)
3)
4)
PJM2014
113
1/13/14
Transformer Protection
PJM2014
114
1/13/14
PJM2014
1/13/14
PJM2014
1/13/14
Transformer Protection
PJM2014
117
1/13/14
Transformer Protection
PJM2014
118
1/13/14
Inrush Current
Applied Voltage
1/13/14
Transformer Protection
PJM2014
120
1/13/14
Transformer Protection
Bottom Line:
The differential relay is the ideal device for transformer protection in
that it takes advantage of the zone type of protection to provide
sensitive high speed clearing of transformer faults
PJM2014
121
1/13/14
Transformer Protection
PJM2014
122
1/13/14
Transformer Protection
PJM2014
123
1/13/14
Transformer Protection
PJM2014
124
1/13/14
Transformer Protection
PJM2014
125
1/13/14
Transformer Protection
PJM2014
126
1/13/14
127
1/13/14
Illustration Of
Microprocessor Based
Thermal Device
Liquid Temperature
is the upper unit
Winding Temperature
is the lower unit
1/13/14
Transformer Protection
PJM2014
129
1/13/14
Transformer Protection
PJM2014
130
1/13/14
Fault
PJM2014
131
1/13/14
Transformer Protection
PJM2014
132
1/13/14
Transformer Protection
PJM2014
133
1/13/14
Transformer Protection
PJM2014
134
1/13/14
Transformer Protection
PJM2014
135
1/13/14
PJM2014
136
1/13/14
Bus Protection
PJM2014
1/13/14
Ring Bus
Improved Flexibility, may be difficult to relay.
PJM2014
138
1/13/14
PJM2014
1/13/14
PJM2014
1/13/14
PJM2014
1/13/14
PJM2014
1/13/14
Bus Protection
PJM2014
143
1/13/14
Bus Protection
Generally, the CTs used for Bus Protection are located on the
line or equipment side of the circuit breaker. Consequently,
the CB is within the protection zone of the bus differential
and the line or piece of equipment (overlapping zones
of protection)
CTs that are connected in the differential scheme should be of
an accuracy class that can withstand maximum expected fault
currents (i.e. CTs should not saturate). Failure of application
engineers to insure this could lead to a misoperation
PJM2014
144
1/13/14
Bus Protection
PJM2014
145
1/13/14
Bus Protection
PJM2014
146
1/13/14
Bus Protection
PJM2014
147
1/13/14
If the bus trips and locks out, no testing via SCADA should
occur until the station is inspected by authorized personnel
PJM2014
148
1/13/14
Generator Protection
PJM2014
1/13/14
D. C. Excitation
System
Prime
Mover
Generator
Synchronizing
CB
Generator
Step Up
Transformer
System
Aux.
Load
High Voltage
Bus
Emergency Diesel
Generator
Start Up
Transformer
PJM2014
1/13/14
Station Arrangement
PJM2014
151
1/13/14
Station Arrangement
Generator In-Service
Startup Transformer is out of service
Plant auxiliary loads are supplied from the station service transformer
PJM2014
152
1/13/14
Station Arrangement
Station Blackout
Generator has just tripped or was already off line
The startup transformer can provide no help because this portion of
the high voltage system is interrupted
Emergency generators (diesel) are used to supply the plant auxiliary
load until the system is restored
PJM2014
153
1/13/14
PJM2014
1/13/14
PJM2014
Winding Faults
Overheating
Loss of Field
Single Phasing
Overloading
Overspeed
Motoring (turbine)
Overexcitation
155
1/13/14
PJM2014
156
1/13/14
PJM2014
157
1/13/14
PJM2014
158
1/13/14
Overall
Unit Protection
PJM2014
1/13/14
PJM2014
160
1/13/14
Ground Relay
Generator CB
To Excitation
System
Unit Differential
Relay
D.C. Field
GEN
Distribution
T ransformer
Main Power
Transformer
Generator Differential
Relay
Xfmer Diff. Relay
Station Bus
Protection
Station
Service
Load
Station Service
Transformer
Start Up
Transformer
Station Service
Bus
PJM2014
Start Up CB
161
1/13/14
Generator Differential
Wraps only the Stator Windings of the Generator
Sensitive to phase and some ground faults
Operation of this relay will initiate a unit trip
PJM2014
162
1/13/14
Generator Differential
C
B
Rotor
(DC Field)
A
Armature and
Stator Windings
High
Impedance
Neutral
87
PJM2014
163
Differential Relay
(B & C Phases are similar)
1/13/14
Overall Differential
Wraps the Generator, Gen. Step-up Transformer & Station
Service Transformer
Sensitive to phase & some ground faults
Backs up the Gen. Diff, GSU Diff., Station Service Diff, etc
Less sensitive than the Gen. Diff
Operation of this relay will initiate a unit trip
PJM2014
164
1/13/14
TO
GRID SYSTEM
TO
EXCITATION
SYSTEM
D.C.
FIELD
GENERATOR
C.B.
GEN.
GENERATOR
NEUTRAL
TO GROUND
87
STATION
LOADS
ST AT IO N
S ERVI CE
BUS
(LO W VO LT A G E)
PJM2014
STATION
BUS
(HIGH VOLTAGE)
MAIN POWER
TRANSFORMER
TO
GRID SYSTEM
STATION
SERVICE
TRANSFORMER
165
1/13/14
Overcurrent Protection
Provide Backup Protection for Gen. Diff Scheme
Protects the generator from system faults that are not cleared within a
predetermined time interval
Coordinated with System Overcurrent schemes
Usually time delayed to minimize tripping for transient surges
or synchronizing
Will initiate a unit trip
PJM2014
166
1/13/14
Generator
To GSU
Transformer
CT
51G
PT
51
51 - Backup Overcurrent
46 - Negative Sequence
40 - Loss of Field
81 - Underfrequency
PJM2014
46
32
40
59
81
167
1/13/14
PJM2014
168
1/13/14
PJM2014
169
1/13/14
PJM2014
170
1/13/14
Generator
Generator
Transformer
51G
59
High Resistance
Neutral
PJM2014
171
1/13/14
PJM2014
172
1/13/14
PJM2014
173
1/13/14
Overexcitation Protection
Concern is for the Generator Field and main GSU transformer since
overexcitation can cause damaging overheating due to core saturation
in a very short time
For GSU transformer protection, a Volts/Hertz relay is applied
Operation of relay will trip unit
PJM2014
174
1/13/14
Underfrequency Protection
If System Load exceeds the capability of the machine, the frequency
will decay
In PJM, machines are typically set for 57.5 hz with a 5.0 second
time delay
System load shedding schemes are used to dump load as required
If not enough load is disconnected and frequency drops, relay will initiate
a unit trip
If unit tripping occurs, pull out your Black Start Restoration guide
because it will be needed!
PJM2014
175
1/13/14
PJM2014
1/13/14
PJM2014
177
1/13/14
Summary
178
1/13/14
Questions?
PJM2014
1/13/14
Disclaimer:
PJM has made all efforts possible to accurately document all
information in this presentation. The information seen here
does not supersede the PJM Operating Agreement or the
PJM Tariff both of which can be found by accessing:
http://www.pjm.com/documents/agreements/pjmagreements.aspx
For additional detailed information on any of the topics
discussed, please refer to the appropriate PJM manual
which can be found by accessing:
http://www.pjm.com/documents/manuals.aspx
PJM2014
180
1/13/14
PJM2014
181
1/13/14