Вы находитесь на странице: 1из 117

TECHNICAL SUBMITTAL

FIRE PUMP SET


HORIZONTAL END SUCTION
(500 GPM @ 6 BAR)
BRISTOL UL PUMP
CONTRACTOR
M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE
PROJECT
REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL
LOCATION
ABU DHABI - AL SHAWAMEKH PLOT NO: P2

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

Revision No.

Vendor Doc. No.

BFE-FP
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION

QTY

DIESEL FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

TECHNICAL SUBMITTAL
FIRE PUMP
Suction and discharge gauge

A1.

B.

C.

0
Rev

fghgh

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2. Automatic electric pump controller, suitable for 60 HP, Y-Delta
3. Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

Vanessa Asprer
Prepared by

Nasser Mansour
Checked

2
1
1

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:

Issued for Approval


Description

1
1

Nasser Mansour
Approved

9-Sep-15
Date

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

01

Revision No.

Vendor Doc. No.

BFE-VDI
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

Suction and discharge gauge

QTY
1

VENDOR DOCUMENT INDEX


A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Vendor Ref. No.

Doc. Seq. No.

BFE-2218

Revision No.

01

Vendor Doc. No.

BFE-VDI
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

VENDOR DOCUMENT INDEX


Seq.
No.

Customer
Doc. No.

Vendor Doc. No.

Rev.

01

BFE-VDI

Vendor Document Index

9-Sep-15

02

BFE-ED

Equipment Description

9-Sep-15

03

BFE-SVL

Sub-Vendors List

9-Sep-15

04

DDSC-4010

Diesel Fire Pump Data Sheet &


Curve

9-Sep-15

05

DGAD-5007

Diesel Fire Pump General


Arrangement Drawing

9-Sep-15

06

DCSD-6007

Diesel Fire Pump CrossSectional Drawing

9-Sep-15

07

DED-7006

Diesel Fire Pump Engine Data

9-Sep-15

08

DCD-8001

Diesel Fire Pump Controller


Data

9-Sep-15

09

EDSC-9010

Electric Fire Pump Data Sheet


& Curve

9-Sep-15

10

EGAD-E1010

Electric Fire Pump General


Arrangement Drawing

9-Sep-15

11

ECSDE-1004

Electric Fire Pump CrossSectional Drawing

9-Sep-15

12

EED-E2104

Electric Fire Pump Motor Data

9-Sep-15

13

ECD-E3002

Electric Fire Pump Controller


Data

9-Sep-15

14

JPD-J4001

Jockey Pump Data

9-Sep-15

15

JPCD-J5001

Jockey Pump Controller Data

9-Sep-15

Pressure Gauge

9-Sep-15

Casing Relief Valve

9-Sep-15

Flow Meter

9-Sep-15

Fuel Tank Drawing

9-Sep-15

Tag No.

ACC-A6001

CERT

16

Vendor Document Title

17

BFE-UL / CDC

UL Certificate

9-Sep-15

PRO

ACCESSORIES

JOCKEY PUMP

ELECTRIC FIRE PUMP

DIESEL FIRE PUMP

Part

Customer Approval
A-Approved
B-Approved w/
First Submission
Date
comments
D-Disapproved

18

BFE-CO/PRO

Supplier Company Profile

9-Sep-15

Latest
Submission
Date

Remarks

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

02

Revision No.

Vendor Doc. No.

BFE-ED
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

Suction and discharge gauge

QTY
1

EQUIPMENT DESCRIPTION
A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Vendor Ref. No.

Doc. Seq. No.

BFE-2218

02

Revision No.

Vendor Doc. No.

BFE-ED
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

A1.

B.

C.

fghgh

ITEM DESCRIPTION

QTY

DIESEL FIRE PUMP


Q = 500 GPM H=6 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF14, 71HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:
Suction and discharge gauge

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Flow meter GERAND venture type model K-500-6" Grooved ends

1
1

ELECTRIC FIRE PUMP


Q = 500 GPM H=6 BAR
BRISTOL pump model IS 80/260 H horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V
2. Automatic electric pump controller, suitable for 60 HP, Y-Delta
3. Accessories:
Suction and discharge gauge
Casing relief valve 1/2"
JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller

2
1
1

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

03

Revision No.

Vendor Doc. No.

BFE-SVL
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

Suction and discharge gauge

A1.

B.

SUB-VENDORS LIST
MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Vendor Ref. No.

Doc. Seq. No.

BFE-2218

03

Vendor Doc. No.

BFE-SVL
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SUB-VENDORS LIST
1.

Diesel Engine

CLARKE

2.

Diesel Controller

TORNATECH

3.

Electric Motor

NIDEC- US MOTOR

4.

Electric Controller

TORNATECH

5.

Jockey Pump

RV

6.

Jockey Controller

TORNATECH

7.

Casing Relief Valve :

8.

Gauges

WIKA

9.

Flow meter

GERAND

CASH-ACME

Revision No.

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

Revision No.

04

Vendor Doc. No.

DDSC-4010
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

QTY

DIESEL FIRE PUMP


DATA SHEET AND CURVE
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Fire Pumps - End Suction


Bristol End Suction Pumps are designed according to NFPA 20 for Fire Fighting applications. This pump
is designed with latest technology and has premium components for fast maintenance and absolute
efficiency.

Performance Range
- Capacity

: From 50 GPM up to 1000 GPM

- Head

: From 40 MTR up to 160 MTR

Features
-

Available in electric motor driven or engine driven configuration


Dynamic balanced impellers
Available in clockwise or counter-clockwise rotation to simplify pump
room layout
UL Certificate No. : Ex16459

Material Construction
-

Shaft
Casing
Impeller
Shaft Seal

: Stainless Steel
: Ductile Iron
: Bronze
: Packing Gland-Immersion Graphite

General Information for Centrifugal Fire Pumps, End Suction


Model

Rated Capacity
(GPM)

Size (In)

Rated Net Pressure


Range (psi)

Approx Speed
(RPM)

Model
IS65 320H

Rated Capacity
(GPM)

Size (In)

Rated Net Pressure


Range (psi)
97-181

Approx Speed
(RPM)

IS32 200

50

2x1

62-95

2950

300

3 x 2

IS32 200

50

2x1

55-85

2800

IS65 320H

300

3 x 2

98-152

2600

2800

IS32 260

50

2x1

113 - 130

2950

IS65 320H

300

3 x 2

82-128

2400

4x3

IS32 260

100

2x1

103 - 125

2950

IS80 - 260

400

105-139

2950

IS50 320H

50

2 x 2

103-167

2600

IS80 - 260

500

4x3

101-137

2950

IS50 320H

50

2 x 2

88-142

2400

IS80 320H

300

4x3

159-203

2950

IS50 320H

100

2 x 2

178-298

3500

IS80 320H

300

4x3

143-183

2800

IS50 320H

100

2 x 2

132-210

2950

IS80 320H

400

4x3

158-203

2950

IS50 320H

100

2 x 2

119-189

2800

IS80 320H

400

4x3

142-183

2800

IS50 320H

100

2 x 2

102-166

2600

IS100 320H

400

5x4

123-158

2950

IS50 320H

100

2 x 2

87-141

2400

IS100 320H

400

5x4

110-142

2800

IS50 320H

150

2 x 2

177-296

3500

IS100 320H

400

5x4

98-172

2600

IS50 320H

150

2 x 2

132-209

2950

IS100 320H

400

5x4

83-147

2400

IS50 320H

150

2 x 2

118-188

2800

IS80 320H

450

4x3

157-203

2950

IS50 320H

150

2 x 2

99-165

2600

IS80 320H

450

4x3

140-182

2800

IS50 320H

150

IS50 320H

200

84-140

2400

IS100 320H

450

5x4

122-158

2950

2 x 2

173-296

3500

IS100 320H

450

5x4

110-142

2800

2 x 2

IS50 320H

200

2 x 2

127-209

2950

IS100 320H

450

5x4

98-172

2600

IS50 320H

200

2 x 2

113-188

2800

IS100 320H

450

5x4

83-147

2400

IS65 320H

200

3 x 2

159-290

3500

IS80 320H

500

4x3

155-202

2950

2950

IS80 320H

500

4x3

136-182

2800

5x4

122-158

2950

IS65 320H

200

3 x 2

108-201

IS65 320H

200

3 x 2

97-181

2800

IS100 320H

500

IS65 320H

200

3 x 2

104-158

2600

IS100 320H

500

5x4

110-142

2800

IS65 320H

200

3 x 2

88-133

2400

IS100 320H

500

5x4

97-172

2600

IS65 320H

250

3 x 2

157-290

3500

IS100 320H

500

5x4

82-147

2400

IS65 320H

250

3 x 2

107-201

2950

IS100 320H

750

5x4

119-147

2950

IS65 320H

250

3 x 2

97-181

2800

IS100 320H

750

5x4

104-131

2800

IS65 320H

250

3 x 2

102-155

2600

IS100 320H

750

5x4

89-166

2600

IS100 - 260

750

5x4

113-139

2950

1000

5x4

104-131

2950

IS65 320H

250

3 x 2

85-131

2400

IS65 320H

300

3 x 2

155-289

3500

IS65 320H

300

3 x 2

107-201

2950

IS100 - 260

Characteristics

Discharge

Wear Ring
Lantern Ring

Wear Ring

Gland Cover
Impeller

Shaft Sleeve

Casing

Shaft

Suction

Bearing (Outboard)
Bearing (Inboard)

Description
-

Discharge
Wear Ring
Bearing (Ind. & Out.)
Packing Gland
Shaft
Gland Cover
Lantern Ring
Impeller
Suction
Casing

:
:
:
:
:
:
:
:
:
:

Vertical Discharge on the center line


Bronze - Is standard for the certified ANSI pumps Radially split casing with flanged connections
Deep Grooved Ball Bearing
Immersion Graphite Rope
Stainless Steel - Sleeve shaft as standard for extended seal life
Bronze - to house a gland seal
Bronze - to keep packing lubricated
Bronze - Enclosed impeller design ensures maximum efficiency
Horizontal End Suction ANSI 150# or 300# flange drilling is available based on material selection
Ductile Iron 65-45-12 - Heavy-duty power frame

Dimensions

Pump - Table of Dimension in (mm)


MODEL

Ff

IS32 - 200

80

360

160

183.5

70

100

50

267

49

110

140

190

240

22.225

4.7x4.7x32

IS32 - 260

100

360

180

228

95

125

65

267

49

110

140

250

320

22.225

4.7x4.7x32

IS50 - 320H

125

470

225

285.6

95

79.4

110

IS65 - 320H

125

470

225

284

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS80 - 260

125

470

200

280

120

140

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS80 - 320H

125

470

250

317

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS100 - 260

140

470

225

280

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS100 - 320H

142

470

250

316

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

125

65

342

140

280

345

28.575

6.35x6.35x44.5

Flange - Table of Dimension in (mm)


SUCTION

DISCHARGE

MODEL

IS32 200

IS32 260

ID

OD

50.8

152

50.8

152

dp
4 holes 19
On PCD 120
4 holes 19
On PCD 120

ID

OD

32

117

32

117

4 holes 19
IS50 320H

63.5

178

IS65 320H

76

190

IS80 260

101.6

228.6

IS80 - 320H

101.6

228.6

IS100 260

127

254

IS100 320H

127

228.6

On PCD 133
4 holes 19
On PCD 152
8 holes 19
On PCD 190
8 holes 19
On PCD 190

8 holes 19
On PCD 216

4 holes 16
On PCD 90
4 holes 16
On PCD 90
4 holes 19

50.8

152

63.5

178

76.2

190.5

76.2

190.5

101.6

228.6

101.6

228.6

8 holes 19
On PCD 190

dp

On PCD 120
4 holes 19
On PCD 140
4 holes 19
On PCD 152
4 holes 19
On PCD 152
8 holes 19
On PCD 190
8 holes 19
On PCD 190

IS80-260 - 2950

Curve No.

2950 rpm
1 Stage

Max Diameter

264 mm

Min. Diameter

230 mm

UL IS80-260-001
Max Speed

Suction

100 mm

Discharge

80 mm

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

Revision No.

05

Vendor Doc. No.

DGAD-5007
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

QTY

DIESEL FIRE PUMP


GENERAL ARRANGEMENT
AND DRAWING
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

06

Revision No.

Vendor Doc. No.

DCSD-6007
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

QTY
1

DIESEL FIRE PUMP


CROSS SECTIONAL DRAWING
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

07

Revision No.

Vendor Doc. No.

DED-7006
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

DIESEL FIRE PUMP


ENGINE DATA
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

MODELS
JU4H-UF10
JU4H-UF12
JU4H-UF14

FIRE PUMP ENGINES

JU4H-UF20
JU4H-UF22
JU4H-UF24

JU4H-UF34
JU4H-UFH0
JU4H-UFH2

JU4H-UF40
JU4H-UF42
JU4H-UF50

JU4H-UF52
JU4H-UF54

UK Purchased
FM-UL-cUL APPROVED RATINGS KW/BHP
RATED SPEED

JU4H
MODEL

1470

UF10

1760
31

41

2100
38

2350

51

UF12

41

55

41

55

54

72

54

72

2600
44

2800

59

UF14

52

UF20

45

60

50

67

UF22

56

3000

70

53

71

75

UF24

60

80

62

83

UF34

78

104

86

115

108

145

108

145

UFH0

54

73

66

88

73

UFH2
UF40
59

79

98

70

94

78

105

79

106

79

106

82

110

97

130

95

127

95

127

UF42
UF50

98

73

UF52

74

99

79

106

95

127

UF54

SPECIFICATIONS
ITEM

JU4H MODELS
UF10/12/14

UF20/22/24

Number of Cylinders
Aspiration

Compression Ratio

UFH0/H2

UF40/42

UF50/52/54

4
NA

Rotation*
Weight kg (lb)

UF34

CW
413 (910)

424 (935)

17.6:1

17.0:1

Displacement l (cu. in.)

4.5 (275)

Engine Type

4 Stroke Cycle Inline Construction

Bore & Stroke mm ( in.)

106 x 127 (4.19 x 5.00)

Installation Drawing

D545

Wiring Diagram AC

C07591

Wiring Diagram DC

C07575

Engine Series

John Deere 4045 Series

Abbreviations: CW Clockwise NA Naturally Aspirated T Turbocharged


*Rotation viewed from Heat Exchanger / Front of engine

CERTIFIED POWER RATING

ENGINE RATINGS BASELINES

Each engine is factory tested to verify power and performance.

Engines are to be used for stationary emergency standby fire pump service only. Engines
are to be tested in accordance with NFPA 25.

Although FM-UL ratings are shown at specific speeds, Clarke engines can be
applied at any intermediate speed. To determine the intermediate speed power;
make a linear interpolation from the Clarke FM-UL
FM UL power curve
curve. Contact Clarke or
your Pump OEM Representative to obtain details.

Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) Hg barometer and
77F
77
F (25C)
(25 C) inlet air temperature [approximates 300 ft.
ft (91.4
(91 4 m) above sea level] by the
testing laboratory (see SAE Standard J 1349).
A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)

FM

A deduction of 1 percent from engine horsepower rating as corrected to standard SAE


conditions shall be made for diesel engines for every 10F (5.6C) above 77F (25C)
ambient temperature.

MODELS
JU4H-UF10
JU4H-UF12
JU4H-UF14

FIRE PUMP ENGINES

JU4H-UF20
JU4H-UF22
JU4H-UF24

JU4H-UF34
JU4H-UFH0
JU4H-UFH2

JU4H-UF40
JU4H-UF42
JU4H-UF50

JU4H-UF52
JU4H-UF54

ENGINE EQUIPMENT
EQUIPMENT

STANDARD

OPTIONAL

Air Cleaner

Direct Mounted, Washable, Indoor Service with Drip Shield

Disposable, Drip Proof, Indoor Service Outdoor Type


24V-DC, 40 Amps; with Belt Guard

Alternator

12V-DC, 42 Amps; with Poly-Vee Belt and Guard

Exhaust Protection

Blankets on Naturally Aspirated Models, Metal Guards on Manifolds


and Turbocharger on Turbocharged Models

Coupling

Bare Flywheel

Listed Driveshaft and Guard, UF10/12/14, UF20/22/24 CDS10SC; UFH0/H2, UF40/42 CDS20-SC; UF50/52/54 CDS30-S1

Exhaust Flex Connection

For NA Engines - Stainless Steel, Clamped, 3


For T Engines Stainless Steel, Clamped, 4

Stainless Steel Flex, Clamped, 4 & 5

Flywheel Housing

SAE #3

Flywheel Power Take Off

11.5 SAE Industrial Flywheel Connection

Fuel Connections

Fire Resistant, Flexible, USA Coast Guard Approved, Supply and


Return Lines

Fuel Filter

Primary Filter with Priming Pump

Fuel Injection System

Stanadyne Direct Injection

Engine Heater

230V-AC, 1000 Watt

Governor, Speed

Constant Speed, Mechanical

115V-AC, 1000 Watt

Heat Exchanger

Tube and Shell Type, 4 BAR (60 PSI), BSP(F) Connections

Instrument Panel

English and Metric, Tachometer, Hourmeter, Water Temperature,


Oil Pressure and Two (2) Voltmeters

Junction Box

Integral with Instrument Panel; For DC Wiring Interconnection to


Engine Controller

Lube Oil Cooler

Engine Water Cooled, Plate Type

Lube Oil Filter

Full Flow with By-Pass Valve

Lube Oil Pump

Gear Driven,
Driven Gear Type

Manual Start Control

On Instrument Panel with Control Position Warning Light

Overspeed Control

Electronic with Reset and Test on Instrument Panel

Raw Water Solenoid Operation

Automatic from Fire Pump Controller and from Engine Instrument


Panel

Run Stop Control

On Instrument Panel with Control Position Warning Light

Run Solenoid

12V-DC Energized to Run

12V-DC Energized to Stop; 24V-DC Energized to Run; 24V-DC


Energized to Stop

Starters

Two ((2)) 12V-DC

Two ((2)) 24V-DC

Throttle Control

Adjustable Speed Control, Tamper Proof

Water Pump

Centrifugal Type, Poly-Vee Belt Driven

Abbreviations: DC Direct Current, AC Alternating Current, SAE Society of Automotive Engineers, NA Naturally Aspirated, T- Turbocharged, BSP(F) British
Standard Pipe Thread (Female)

UK, Ltd.
Grange Works, Lomond Rd., Coatbridge, ML5-2NN
United Kingdom
Tel +44-1236-429946
Fax +44-1236-427274
www.clarkefire.com
C133432 revJ
12NOV14

Fire Protection Products, Inc.


3133 E. Kemper Rd., Cincinnati, Ohio 45241
United States of America
Tel +1-513-475-FIRE (3473) Fax +1-513-771-0726
www.clarkefire.com

Specifications and information contained in this brochure subject to change without notice.

FIRE PUMP MODEL: JU4H-UF14


Heat Exchanger Cooled
Naturally Aspirated
4.5L 4 Cylinder
60

55
53
52

50

45

44

41
40

35

30
1750

2000

2250

RESTRICTED:

2500
2750
ENGINE SPEED - RPM

3000

3250

USE ONLY FOR STAND-BY FIRE PUMP APPLICATIONS

ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77F (25C) AIR INLET TEMPERATURE
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)

KEN WAULIGMAN 27OCT06

NAMEPLATE kW (MAXIMUM PUMP LOAD)


THIS DRAWING AND THE INFORMATION HEREIN ARE OUR
PROPERTY AND MAY BE USED BY
OTHER ONLY AS AUTHORIZED BY
US. UNPUBLISHED -- ALL RIGHTS
RESERVED UNDER THE
COPYRIGHT LAWS.

CREATED

DATE CREATED

05/19/04

ENGINE MODEL JU4H-UF14


DRAWING NO.

C131943

REV

JU4H-UF14
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Basic Engine Description
Engine Manufacturer
Ignition Type
Number of Cylinders
Bore and Stroke - mm (in)
'LVSODFHPHQW/ LQ
Compression Ratio
Valves per cylinder
Intake
Exhaust
Combustion System
Engine Type
Fuel Management Control
Firing Order (CW Rotation)
Aspiration
Charge Air Cooling Type
Rotation, viewed from front of engine, Clockwise (CW)
Engine Crankcase Vent System
Installation Drawing
Weight - kg (lb)
Power Rating
Nameplate Power - kW (HP)
Cooling System - [C051001]
Engine Coolant Heat - kW (Btu/sec)
Engine Radiated Heat - kW (Btu/sec)
Heat Exchanger Minimum Flow
& ) 5DZ+20 - L/min (gal/min)
& ) 5DZ+20 - L/min (gal/min)
Heat Exchanger Maximum Cooling Raw Water
Inlet Pressure - bar (psi)
Flow - L/min (gal/min)
Typical Engine H22SHUDWLQJ7HPS& ) [1]
Thermostat
6WDUWWR2SHQ& )
)XOO\2SHQHG& )
Engine Coolant Capacity - L (qt)
&RRODQW3UHVVXUH&DSN3D OELQ
0D[LPXP(QJLQH&RRODQW7HPSHUDWXUH& )
0LQLPXP(QJLQH&RRODQW7HPSHUDWXUH& )
+LJK&RRODQW7HPS$ODUP6ZLWFK& )
Electric System - DC
System Voltage (Nominal)
%DWWHU\&DSDFLW\IRU$PELHQWV$ERYH& )
Voltage (Nominal)
Qty. Per Battery Bank
SAE size per J537
&&$#& )
Reserve Capacity - Minutes
Battery Cable Circuit, Max Resistance - ohm
Battery Cable Minimum Size
0-3.1m Circuit Length[2]
3.1m-4.1m Circuit Length[2]
4.1m-5.1m Circuit Length[2]
Charging Alternator Maximum Output - Amp,
6WDUWHU&UDQNLQJ$PSV5ROOLQJ#& ) 

John Deere Co.


Compression (Diesel)
4
106 (4.19) X 127 (5)
4.5 (275)
17.6:1
1
1
Direct Injection
In-Line, 4 Stroke Cycle
Mechanical, Rotary Pump
1-3-4-2
Natural
None
Standard
Open
D545
413 (910)

2350
41 (55)

2600
44 (59)

2800
52 (70)

3000
53 (71)

2350
31.7 (30)
12.7 (12)

2600
33.8 (32)
13.7 (13)

2800
35.9 (34)
14.8 (14)

3000
38 (36)
15.8 (15)

30.3 (8)
37.9 (10)

34.1 (9)
41.6 (11)

37.9 (10)
45.4 (12)

41.6 (11)
49.2 (13)

14 (203)
98.4 (26)
76.7 (170) - 87.8 (190)
76.7 (170)
87.8 (190)
14 (14.79)
68.9 (10)
93.3 (200)
71.1 (160)
96.1 (205)
Standard
12
12
1
8D
1400
430
0.0012

00
000
0000
40
225

Optional
24
[C07633]

[C071363]
[C07888/C07889]

24
2
8D
1400
430
0.0012

00
000
0000
55
250

NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. 1Engine H2O temperature is
dependent on raw water temperature and flow. 2Positive and Negative Cables Combined Length.

[C07633]

[C071366]
[C07819/C07820]

Page 1 of 2

JU4H-UF14
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Exhaust System
([KDXVW)ORZPPLQ IWPLQ
([KDXVW7HPSHUDWXUH& )
Maximum Allowable Back Pressure - kPa (in H20)
Minimum Exhaust Pipe Dia. - mm (in) [3]

2600
15 (531)
568 (1055)
7.5 (30)
76.2 (3)

2800
16.5 (581)
556 (1033)
7.5 (30)
76.2 (3)

3000
17.8 (630)
543 (1010)
7.5 (30)
76.2 (3)

Fuel System
2350
2600
Fuel Consumption - L/hr (gal/hr)
11.7 (3.1)
12.9 (3.4)
Fuel Return - L/hr (gal/hr)
34.1 (9)
36 (9.5)
Fuel Supply - L/hr (gal/hr)
45.8 (12.1)
48.8 (12.9)
)XHO3UHVVXUHN3D OELQ
20.7 (3) - 41.4 (6)
Minimum Line Size - Supply - in.
.50 Schedule 40 Steel Pipe
Pipe Outer Diameter - mm (in)
21.5 (0.848)
Minimum Line Size - Return - in.
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter - mm (in)
17.1 (0.675)
Maximum Allowable Fuel Pump Suction Lift
0.8 (31)
with clean Filter - mH20 (in H20)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft) 1.4 (4.5)
Fuel Filter Micron Size
2

2800
13.6 (3.6)
37.5 (9.9)
51.1 (13.5)

3000
14.8 (3.9)
39 (10.3)
53.7 (14.2)

Heater System
Engine Coolant Heater
Wattage (Nominal)
Voltage - AC, 1 Phase
Part Number

Air System
&RPEXVWLRQ$LU)ORZPPLQ IWPLQ
Air Cleaner
Part Number
Type
Cleaning method
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in H20)
Clean Air Cleaner - kPa (in H20)
0D[LPXP$OORZDEOH7HPSHUDWXUH $LU7R(QJLQH,QOHW & ) [4]
Lubrication System
2LO3UHVVXUHQRUPDON3D OELQ
/RZ2LO3UHVVXUH$ODUP6ZLWFKN3D OELQ
,Q3DQ2LO7HPSHUDWXUH& )
Total Oil Capacity with Filter - L (qt)
Lube Oil Heater
Wattage (Nominal)
Voltage
Part Number

2350
13.3 (469)
584 (1083)
7.5 (30)
76.2 (3)

Standard

Optional

1000
230 (+5%, -10%)
[C122192]

1000
115 (+5%, -10%)
[C122188]

2350
4.7 (166)
Standard
[C03249]
Indoor Service Only,
with Shield
Washable
2.5 (10)
1.2 (5)
54.4 (130)

2600
5.3 (186)

2800
5.7 (202)
Optional
[C03327]
Canister,
Single-Stage
Disposable

3000
6.2 (218)

2.5 (10)
1.2 (5)

345 (50) - 655 (95)


138 (20)
104 (220) - 118 (245)
14.7 (15.5)
Optional

Optional

150
240V (+5%, -10%)
C04431

150
120V (+5%, -10%)
C04430

Performance
2350
2600
2800
3000
%0(3N3D OELQ
462 (67)
448 (65)
496 (72)
469 (68)
Piston Speed - m/min (ft/min)
597 (1958)
661 (2167)
711 (2333)
762 (2500)
Mechanical Noise - dB(A) @ 1m
C131536
Power Curve
C131943
3Based on Nominal System. Back pressure flow analysis must be done to assure maximum allowable back pressure is not exceeded. (Note:
PLQLPXPH[KDXVW3LSHGLDPHWHULVEDVHGRQIHHWRISLSHRQHHOERZDQGDVLOHQFHUSUHVVXUHGURSQRJUHDWHUWKDQRQHKDOIRIWKHPD[LPXP
allowable back pressure.) 45HYLHZIRUKRUVHSRZHUGHUDWHLIDPELHQWDLUHQWHULQJHQJLQHH[FHHGV) & >@LQGLFDWHVFRPSRQHQWUHIHUHQFHSDUW
number.

Page 2 of 2
C131263 Rev L
DP 09JAN15

CLARKE
JU4H, JU4R & JU6H, JU6R ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner
Type.... .. Indoor Usage Only
Oiled Fabric Pleats
Material.....Surgical Cotton
Aluminum Mesh
Air Cleaner - Optional
Type. Canister
MaterialPleated Paper
Housing..
Enclosed
Camshaft
Material... Cast Iron
Chill Hardened
Location...... In Block
Drive...Gear, Spur
Type of Cam...... Ground
Charge Air Cooler (JU6H-60,62,68,74,84, ADK0,
AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8, AARG,
ADP8, ADP0, ADT0, AD88, ADR8, AD98, ADS0, ADW8,
ADX8, AD98 only)
Type.. ...Raw Water Cooled
Materials (in contact with raw water)
90/10 CU/NI
Tubes
Headers 36500 Muntz
Covers
83600 Red Brass
Plumbing 316 Stainless Steel/ Brass
90/10 Silicone
Charge Air Cooler (JU6R-AA67, 59, 61, PF, Q7, RF,
S9, 83 only)
Type...Air to Air Cooled
Materials
CoreAluminum

Cylinder Head
Type.. Slab 2 Valve
Material. Annealed Gray Iron
Cylinder Liners
Type.. Centrifugal Cast, Wet Liner
Material...Alloy Iron Plateau, Honed
Fuel Pump
TypeDiaphragm
DriveCam Lobe
Heat Exchanger (USA) - JU4H & JU6H Only
TypeTube & Shell
Materials
Tube & HeadersCopper
ShellCopper
ElectrodeZinc

Heat Exchanger (UK) - JU4H & JU6H Only


TypeTube & Bundle
Materials
Tube & HeadersCopper
Shell... Aluminum
Injection Pump
Type.. Rotary
DriveGear
Lubrication Cooler
TypePlate

Coolant Pump
Type. Centrifugal
DrivePoly Vee Belt

Lubrication Pump
TypeGear
DriveGear

Coolant Thermostat
Type
Non Blocking
Qty 1

Main Bearings
TypePrecision Half Shells
Material
Steel Backed-Aluminum
Lined

Cooling Loop (Galvanized)


Tees, Elbows, PipeGalvanized Steel
Ball ValvesBrass ASTM B 124,
Solenoid ValveBrass
Pressure RegulatorBronze
Strainer Cast Iron (1/2" - 1" loops) or
Bronze (1.25" - 2" loops)

Cooling Loop (Sea Water)


Tees, Elbows, Pipe316 Stainless Steel
Ball Valves316 Stainless Steel
Solenoid Valve316 Stainless Steel
Pressure Regulator/Strainer Cast Brass ASTM B176
C87800
Cooling Loop (316SS)
Tees, Elbows, Pipe316 Stainless Steel
Ball Valves316 Stainless Steel
Solenoid Valve316 Stainless Steel
Pressure Regulator/Strainer 316 Stainless Steel
Connecting Rod
Type
I-Beam Taper
MaterialForged Steel Alloy
Crank Pin Bearings
Precision Half Shell
Type
Number1 Pair Per Cylinder
MaterialWear-Guard

Fire Protection Products

Piston
Type and MaterialAluminum Alloy with
Reinforced Top Ring Groove
CoolingOil Jet Spray
Piston Pin
TypeFull Floating - Offset
Piston Rings
Number/Piston 3
Top Keystone Barrel Faced Plasma Coated
SecondTapered Cast Iron
ThirdDouble Rail Type
w/Expander Spring
Radiator - JU4R & JU6R Only
Type Plate Fin
Materials
Core Copper & Brass
Tank & Structure.. Steel
Valves
Type.. Poppet
Arrangement Overhead Valve
Number/Cylinder
1 intake
1 exhaust
Operating MechanismMechanical Rocker Arm
Type of Lifter.. Large Head
Replaceable
Valve Seat Insert

Crankshaft
MaterialForged Steel
Type of Balance
Dynamic
Cylinder Block
Type
One Piece with
Non-Siamese Cylinders
MaterialAnnealed Gray Iron

C13615 04NOV14

JU4H-UF14

Stationary Fire Pump Engine Driver


EMISSION DATA
EPA 40 CFR Part 60
4 Cylinders
Four Cycle
Lean Burn
Naturally Aspirated

500 PPM SULFUR #2 DIESEL FUEL


RPM

BHP (3)

FUEL
GAL/HR
(L/HR)

2800

70

3000

71

GRAMS / HP- HR
(4)

EXHAUST
CFM
F (C)
(m3/min)

NMHC

NOx

CO

3.6 (13.6)

0.77

3.79

2.38

0.16

1033 (556)

581 (16)

3.9 (14.8)

0.83

3.64

2.80

0.18

1010 (543)

630 (18)

PM

Notes:
1) 4045DF159 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77F (25 C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .

CLARKE
FIRE PROTECTION PRODUCTS
C131867 REV.C
01NOV 07 KRW

3133 EAST KEMPER ROAD


CINCINNATI, OH 45241

PAGE 1 OF 2

John Deere Power Systems


3801 W. Ridgeway Ave., PO Box 5100
Waterloo, Iowa USA 50704-5100

31 October 2007
Subject:

Fire Pump Ratings Conformance to EPA 40 CFR Part 60 (NSPS requirements)

All John Deere stationary fire pump engines conform to the requirements of 40 CFR Part 60. All such
engines include an emission label, stating the engine conforms to the requirements of 40 CFR Part 60. An
example of the emission label is show below:

This label applies to all of the following engine models, sold to Clarke Fire Protection, for use in stationary
fire pump applications:

All engines conforming to 40 CFR Part 60 (identified by emission label, as shown above) are covered under
the emissions warranty of 40 CFR Part 89.
Sincerely,
Kyle J. Tingle
Regional Sales Manager, JDPS
Page 2 of 2

CLARKE

www.clarkefire.com

Fire Protection Products

JU4H-UF14
FIRE PUMP DRIVER

NOISE DATA

Mechanical Engine Noise *


RPM

BHP

2800

70

101.6

3000

71

102.6

OVERALL 31.5 Hz
dB(A)
dB(A)

Octave Band
500 Hz 1k Hz
dB(A)
dB(A)

63 Hz
dB(A)

125 Hz
dB(A)

250 Hz
dB(A)

64.0

69.7

86.4

85.8

92.4

63.9

70.5

85.2

86.6

94.8

2k Hz
dB(A)

4k Hz
dB(A)

8k Hz
dB(A)

16k Hz
dB(A)

97.2

95.5

92.3

84.3

73.1

98.2

97.0

96.0

87.5

73.8

2k Hz
dB(A)

4k Hz
dB(A)

8k Hz
dB(A)

16k Hz
dB(A)

97.4

93.6

84.3

77.9

Raw Exhaust Engine Noise **


RPM

BHP

2800-3000

70-71

OVERALL 31.5 Hz
dB(A)
dB(A)
104

63 Hz
dB(A)

125 Hz
dB(A)

250 Hz
dB(A)

93.8

98.2

92.9

Octave Band
500 Hz 1k Hz
dB(A)
dB(A)
95.1

94.7

* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 23ft (7m), 90 horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the
engine.
The above data reflects values for a typical engine of this model, speed and power in a free-field environment.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the
overall noise levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.

C131536 revC 3JUL13 DSP

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

08

Revision No.

Vendor Doc. No.

DCD-8001
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

DIESEL FIRE PUMP


CONTROLLER DATA
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data Submittal Documents


Model GPD
Diesel Engine Driven Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections
Note: The drawings included in this package are for controllers covered under our standard offering.

Actual AS BUILT drawings may differ from what is shown in this package.

October 2013

Technical Data
GPD Diesel Fire Pump Controller
Built to NFPA 20 (latest edition)
Standard,
Listings,
Approvals and
Certifications

Underwriters Laboratory (UL)

UL218 - Fire Pump Controllers


CSA C22.2 No. 14 Industrial Control Equipment

FM Global

Class 1321/1323

New York City

Accepted for use in the City of New York by the Department of Buildings

Optional

CE Mark

Enclosure

Various EN, IEC & CEE directives and standards

Protection Rating
Standard: NEMA 2 (IP31)
Optional
NEMA 12
NEMA 3
NEMA 3R
NEMA 4

NEMA 4X-304 sst painted


NEMA 4X-304 sst brushed finish
NEMA 4X-316 sst painted
NEMA 4X-316 sst brushed finish

Accessories
Bottom entry gland plate
Lifting Lugs
Keylock handle

Ambient
Temperature
Rating

Paint Specifications
Red RAL3002
Powder coating
Glossy textured finish

Standard
5C to 40C / 41F to 104F
Optional
5C to 50C / 41F to 122F
5C to 55C / 41F to 131F
AC

General

IP54
IP55
IP65
IP66

DC
Grounding system
Battery chargers

120V / 1ph / 60hz


208V to 240V / 1ph / 50-60hz
12VDC
24VDC
Negative
Two independent fully automatic
10A continuous charge
500mA trickle charge

Battery 1 & Battery 2 voltage


Electrical Reading Battery 1 & Battery 2 charging amperage
Charging mode
Pressure Reading

Pressure and
Event Recorder

October 2013

Continuous system pressure display


Cut-in and Cut-out pressure setting
Pressure readings with date stamp
Event recording with date stamp
Under regular maintained operation, events can be stored in memory for up to 5 years
Data viewable on operator interface display screen
Downloadable by USB port to external memory device

Technical Data
GPD Diesel Fire Pump Controller

Pressure sensing

Audible Alarm

Visual & Audible


Alarms

Remote Alarm
Contacts

ViZiTouch
Operator Interface

Pressure transducer and run test solenoid valve assembly for fresh water application
Pressure sensing connection 1/2 Female NPT
Drain connection 3/8
Rated for 0-500psi Working pressure (calibrated at 0-300psi)
Externally mounted with protective cover
4 alarm bell - 85 dB at 10ft. (3m)
Visual only
Periodic test
Engine run
Main switch in HAND
Main switch AUTO
o
Pump room temperature ( F or oC)
Visual and Audible
Battery #1 & battery #2 failure
Overspeed
Charger #1 & Charger #2 failure
Low oil pressure
AC power available
High engine temperature
Low pump room temperature
Fail to start
System overpressure
High fuel level

Cranking Cycle
Main switch in OFF
Low fuel level
Water reservoir low
Fuel tank leak
Fail when running

SPDT-8A-250V.AC
Engine run (2x) (1x field re-assignable)*
Common controller trouble
Charger #1 & Charger #2 failure
Pressure line failure
Common engine trouble
Overspeed
Battery #1 & battery #2 failure
High engine temperature
Fail when running
DC failure
Fail to start
Fuel injection malfunction** Loss of continuity (starter) #1 and/or #2 Low oil pressure
ECM selector switch in alternate position***
Common pump room alarm (field re-assignable)*
Low suction pressure
Water reservoir low
Low fuel level
Low pump room temperature
Water reservoir empty
High fuel level
High pump room temperature
AC Failure
Fuel tank leak
H-O-A selector switch in AUTO (field re-assignable)*
H-O-A selector switch in OFF or HAND
Free (field programmable)*
Embedded micro-computer with software PLC logic
4.2 color touch screen (HMI technology)
Upgradable software
Expandable storage
Multi-language

*Except if option C13 is ordered. Tornatech reserves the right to use any of these four alarm points for special specific application requirements
**Applicable to electronic engines only.
*** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.

October 2013

Technical Data
GPD Diesel Fire Pump Controller

Operation

Selector Switch

Hand-Off-Auto
Behind lockable and breakable cover

Automatic Start

Start on pressure drop


Remote start signal from automatic device

Manual Start

Crank 1 and Crank 2 start pushbuttons


Run test pushbutton
Deluge valve start
Remote start from manual device

Crank Cycle

6 consecutive cycle attempts


3 X 15s crank from battery 1 or 2 alternatively
15s rest in between each crank attempt
Manual with Stop pushbutton
Automatic after expiration of minimum run timer ***

Stopping

Field Adjustable &


Visual Countdown

Timers
Actuation

Visual Indication

Mode

Alarm and
shutdown
schedule

Minimum run timer ***(off delay)


Sequential start timer (on delay)
Periodic test timer
Pressure
Non-pressure
Automatic
Non-automatic

Automatic Start

Manual or Remote start

Run Test or periodic test

High Coolant

Alarm only

Alarm only

Shutdown

Low Oil Pressure

Alarm only

Alarm only

Shutdown

Overspeed

Shutdown

Shutdown

Shutdown

Wall Mount
Starting Voltage

Approx. shipping
dimensions in inches
(mm)

12V.DC

24V.DC

Floor Mount

Approx. Shipping
Weight in Lbs (kg)

Approx. shipping
dimensions in inches
(mm)

Approx. Shipping
Weight in Lbs (kg)

32 "L x 29 "W x 16 "h


(813 x 737 x 407 )

110 (50)

32L x 29w x 26h


(813 x 737 x 661)

130 (59)

32 "L x 29 "W x 16 "h


(813 x 737 x 407)

130 (59)

32L x 29w x 26h


(813 x 737 x 661)

150 (68)

*** Automatic shutdown shall be approved by the AHJ.

October 2013

Technical Data
GPD Diesel Fire Pump Controller
C14

Delayed automatic start on AC power failure


(factory set at 15 minutes)

C15

Low zone pump control function

C16

Medium zone pump control function

C17

High zone pump control function

C19

Lockout/interlock circuit from equipment installed inside the


pump room

D4

Pressure transducer and run test solenoid valve for fresh


water rated for 0-500PSI (for calibration purposes only)

System overpressure alarm contact (For engines with PLD)


(Form C-SPDT)

D6

Pressure transducer and run test solenoid valve for sea


water rated for 0-500PSI

Extra controller trouble alarm contact (Form C-SPDT)

D7A

Low fuel level float switch supplied as separate item (1-1/4)

A12

Extra engine trouble alarm contact (Form C-SPDT)

D7B

Low fuel level float switch supplied as separate item (1-1/2)

Ax

Additional engine alarm contact (Form C-SPDT)


(specify function)

D8A

High fuel level float switch supplied as separate item (1-1/4)

D8B

High fuel level float switch supplied as separate item (1-1/2)

B1

Low fuel level alarm contact (Form C-SPDT)

D9A

Anti-condensation heater & thermostat

B2

Water reservoir level low alarm contact (Form C-SPDT)

D9B

Anti-condensation heater & humidistat

B3

Water reservoir empty alarm contact (Form C-SPDT)

D9C

Anti-condensation heater & thermostat & humidistat

B4

Low pump room temperature alarm contact (Form C-SPDT)

B5

High fuel level alarm contact (Form C-SPDT)

D11

Low suction pressure transducer for fresh water rated at


0-300PSI with visual indication and alarm contact

B6

Low system (discharge) pressure alarm contact


(Form C-SPDT)

D11A

Low suction pressure transducer for sea water rated at


0-300PSI with visual indication and alarm contact

B7

Low suction pressure alarm contact (Form C-SPDT)

D12

Tropicalization

B8

Pump on demand alarm contact (Form C-SPDT)

D25

Mounting stand

B9

Fuel tank leak alarm contact (Form C-SPDT)

D25A

Mounting stand SST- 304 painted

B10

Main relief valve open alarm contact (Form C-SPDT)

D25B

Mounting stand SST- 304 brushed finish

B11

Flow meter loop valve open alarm contact (Form C-SPDT)

D25C

Mounting stand SST- 316 painted

B12

Water reservoir level high alarm contact (Form C-SPDT)

D25D

Mounting stand SST- 316 brushed finish

B13

High pump room temperature alarm contact (Form C-SPDT)

D26

Combined low and high fuel level float switch (1-1/4)

Bx

Additional pump room alarm contact (Form C-SPDT)


(specify function)

D26A

Combined low and high fuel level float switch (1-1/2)

D27

Fuel level probe (1-1/4) Level indication

C5

CE Mark with factory certificate

D28

Field programmable I/O board - 8 Input / 5 output

C6

Nickel Cadmium battery chargers

D29

Field programmable I/O board - 8 Input / 10 output

C7

Engine block heater circuit (same voltage as battery charger


primary)

D30

Redundant pressure transducer for fresh water rated for


0-500PSI (calibrated at 0-300PSI)

C8

Foam pump application w/o pressure transducer and run


test solenoid valve

D31

Redundant pressure transducer for sea water rated for


0-500PSI (calibrated at 0-300PSI)

C9

Non pressure actuated controller w/o pressure transducer


and run test solenoid valve

D32

Modbus RTU provision

D32A

Modbus TCP/IP provision

C13

Louver activation circuit (battery power specific)

D33

Window kit for operator interface

A1

Periodic test alarm contact (Form C-SPDT)

A2

Overspeed alarm contact (Form C-SPDT)

A3

Low oil pressure alarm contact (Form C-SPDT)

A4

High coolant temperature alarm contact (Form C-SPDT)

A5

Failure to start alarm contacts alarm contact (Form C-SPDT)

A6

Battery 1 & 2 failure alarm contact (2 x Form C-SPDT)

A7

Charger 1 & 2 failure alarm contact (2 x Form C-SPDT)

A8

AC failure alarm contact (Form C-SPDT)

A9
A11

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

October 2013

Technical Data
GPD Diesel Fire Pump Controller
L01

Other language and English (bilingual)

L11

Czech

L02

French

L12

Portuguese

L03

Spanish

L13

Dutch

L04

German

L14

Russian

L05

Italian

L15

Turkish

L06

Polish

L16

Swedish

L07

Romanian

L17

Bulgarian

L08

Hungarian

L18

Thai

L09

Slovak

L19

Indonesian

L10

Croatian

L20

Slovenian

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

October 2013

Technical Data
GPD Diesel Fire Pump Controller
ViZiTouch Operator Interface
3

PMS 295

PMS 361

Noir

10

1
12

11

13

1 - Power on LED
2 - Color touch screen
3 - Alarm LED
4 - HOME page button
5 - ALARM page button
6 - CONFIGURATION page button
7 - HISTORY page button

October 2013

14

8 - USB port
9 - CRANK 1 button
10 - CRANK 2 button
11- Contextual navigation pad
12 - STOP button
13 - RUN TEST button
14 - HELP button

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

Revision No.

09

Vendor Doc. No.

EDSC-9010
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

ELECTRIC FIRE PUMP


DATA SHEET & CURVE
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Fire Pumps - End Suction


Bristol End Suction Pumps are designed according to NFPA 20 for Fire Fighting applications. This pump
is designed with latest technology and has premium components for fast maintenance and absolute
efficiency.

Performance Range
- Capacity

: From 50 GPM up to 1000 GPM

- Head

: From 40 MTR up to 160 MTR

Features
-

Available in electric motor driven or engine driven configuration


Dynamic balanced impellers
Available in clockwise or counter-clockwise rotation to simplify pump
room layout
UL Certificate No. : Ex16459

Material Construction
-

Shaft
Casing
Impeller
Shaft Seal

: Stainless Steel
: Ductile Iron
: Bronze
: Packing Gland-Immersion Graphite

General Information for Centrifugal Fire Pumps, End Suction


Model

Rated Capacity
(GPM)

Size (In)

Rated Net Pressure


Range (psi)

Approx Speed
(RPM)

Model
IS65 320H

Rated Capacity
(GPM)

Size (In)

Rated Net Pressure


Range (psi)
97-181

Approx Speed
(RPM)

IS32 200

50

2x1

62-95

2950

300

3 x 2

IS32 200

50

2x1

55-85

2800

IS65 320H

300

3 x 2

98-152

2600

2800

IS32 260

50

2x1

113 - 130

2950

IS65 320H

300

3 x 2

82-128

2400

4x3

IS32 260

100

2x1

103 - 125

2950

IS80 - 260

400

105-139

2950

IS50 320H

50

2 x 2

103-167

2600

IS80 - 260

500

4x3

101-137

2950

IS50 320H

50

2 x 2

88-142

2400

IS80 320H

300

4x3

159-203

2950

IS50 320H

100

2 x 2

178-298

3500

IS80 320H

300

4x3

143-183

2800

IS50 320H

100

2 x 2

132-210

2950

IS80 320H

400

4x3

158-203

2950

IS50 320H

100

2 x 2

119-189

2800

IS80 320H

400

4x3

142-183

2800

IS50 320H

100

2 x 2

102-166

2600

IS100 320H

400

5x4

123-158

2950

IS50 320H

100

2 x 2

87-141

2400

IS100 320H

400

5x4

110-142

2800

IS50 320H

150

2 x 2

177-296

3500

IS100 320H

400

5x4

98-172

2600

IS50 320H

150

2 x 2

132-209

2950

IS100 320H

400

5x4

83-147

2400

IS50 320H

150

2 x 2

118-188

2800

IS80 320H

450

4x3

157-203

2950

IS50 320H

150

2 x 2

99-165

2600

IS80 320H

450

4x3

140-182

2800

IS50 320H

150

IS50 320H

200

84-140

2400

IS100 320H

450

5x4

122-158

2950

2 x 2

173-296

3500

IS100 320H

450

5x4

110-142

2800

2 x 2

IS50 320H

200

2 x 2

127-209

2950

IS100 320H

450

5x4

98-172

2600

IS50 320H

200

2 x 2

113-188

2800

IS100 320H

450

5x4

83-147

2400

IS65 320H

200

3 x 2

159-290

3500

IS80 320H

500

4x3

155-202

2950

2950

IS80 320H

500

4x3

136-182

2800

5x4

122-158

2950

IS65 320H

200

3 x 2

108-201

IS65 320H

200

3 x 2

97-181

2800

IS100 320H

500

IS65 320H

200

3 x 2

104-158

2600

IS100 320H

500

5x4

110-142

2800

IS65 320H

200

3 x 2

88-133

2400

IS100 320H

500

5x4

97-172

2600

IS65 320H

250

3 x 2

157-290

3500

IS100 320H

500

5x4

82-147

2400

IS65 320H

250

3 x 2

107-201

2950

IS100 320H

750

5x4

119-147

2950

IS65 320H

250

3 x 2

97-181

2800

IS100 320H

750

5x4

104-131

2800

IS65 320H

250

3 x 2

102-155

2600

IS100 320H

750

5x4

89-166

2600

IS100 - 260

750

5x4

113-139

2950

1000

5x4

104-131

2950

IS65 320H

250

3 x 2

85-131

2400

IS65 320H

300

3 x 2

155-289

3500

IS65 320H

300

3 x 2

107-201

2950

IS100 - 260

Characteristics

Discharge

Wear Ring
Lantern Ring

Wear Ring

Gland Cover
Impeller

Shaft Sleeve

Casing

Shaft

Suction

Bearing (Outboard)
Bearing (Inboard)

Description
-

Discharge
Wear Ring
Bearing (Ind. & Out.)
Packing Gland
Shaft
Gland Cover
Lantern Ring
Impeller
Suction
Casing

:
:
:
:
:
:
:
:
:
:

Vertical Discharge on the center line


Bronze - Is standard for the certified ANSI pumps Radially split casing with flanged connections
Deep Grooved Ball Bearing
Immersion Graphite Rope
Stainless Steel - Sleeve shaft as standard for extended seal life
Bronze - to house a gland seal
Bronze - to keep packing lubricated
Bronze - Enclosed impeller design ensures maximum efficiency
Horizontal End Suction ANSI 150# or 300# flange drilling is available based on material selection
Ductile Iron 65-45-12 - Heavy-duty power frame

Dimensions

Pump - Table of Dimension in (mm)


MODEL

Ff

IS32 - 200

80

360

160

183.5

70

100

50

267

49

110

140

190

240

22.225

4.7x4.7x32

IS32 - 260

100

360

180

228

95

125

65

267

49

110

140

250

320

22.225

4.7x4.7x32

IS50 - 320H

125

470

225

285.6

95

79.4

110

IS65 - 320H

125

470

225

284

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS80 - 260

125

470

200

280

120

140

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS80 - 320H

125

470

250

317

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS100 - 260

140

470

225

280

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

IS100 - 320H

142

470

250

316

120

160

80

342

79.4

110

140

315

400

28.575

6.35x6.35x44.5

125

65

342

140

280

345

28.575

6.35x6.35x44.5

Flange - Table of Dimension in (mm)


SUCTION

DISCHARGE

MODEL

IS32 200

IS32 260

ID

OD

50.8

152

50.8

152

dp
4 holes 19
On PCD 120
4 holes 19
On PCD 120

ID

OD

32

117

32

117

4 holes 19
IS50 320H

63.5

178

IS65 320H

76

190

IS80 260

101.6

228.6

IS80 - 320H

101.6

228.6

IS100 260

127

254

IS100 320H

127

228.6

On PCD 133
4 holes 19
On PCD 152
8 holes 19
On PCD 190
8 holes 19
On PCD 190

8 holes 19
On PCD 216

4 holes 16
On PCD 90
4 holes 16
On PCD 90
4 holes 19

50.8

152

63.5

178

76.2

190.5

76.2

190.5

101.6

228.6

101.6

228.6

8 holes 19
On PCD 190

dp

On PCD 120
4 holes 19
On PCD 140
4 holes 19
On PCD 152
4 holes 19
On PCD 152
8 holes 19
On PCD 190
8 holes 19
On PCD 190

IS80-260 - 2950

Curve No.

2950 rpm
1 Stage

Max Diameter

264 mm

Min. Diameter

230 mm

UL IS80-260-001
Max Speed

Suction

100 mm

Discharge

80 mm

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

10

Revision No.

Vendor Doc. No.

EGAD-E1010
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

QTY
1

ELECTRIC FIRE PUMP


GENERAL ARRANGEMENT
DRAWING
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

11

Revision No.

Vendor Doc. No.

ECSDE-1004
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

QTY
1

ELECTRIC FIRE PUMP


CROSS SECTIONAL DRAWING
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

12

Revision No.

Vendor Doc. No.

EED-E2104
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

ELECTRIC FIRE PUMP


MOTOR DATA
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Horizontal A.C. Motors


Open Dripproof
Fire Pump Motors

Fire pump applications per NFPA 20 where


contaminants are minimal

5-250 horsepower open dripproof, standard and


energy efficient designs

180T - 320 T rolled steel frame construction,


360T - 440T cast iron frame construction

All motors meet Canadian CSA-390


Table 2 efficiency requirements

Motors are suitable for wye-delta


start on 250 frame and larger

Vertical JPV hp ratings

Allguard Motor Quality System

Product Overview
U.S. Electrical Motors introduces a special three
phase open dripproof motor which is UL listed
for fire pump applications. These motors meet
UL-1004A and NFPA20, Standard for the
Installation of Centrifugal Fire Pump
Specification.

UL Listed
Fire Pump Motor
Control No. 55XL
E187977

412919

Fire pump motors are available in the open


dripproof design, as well as FUT and UT
(Aluminum frame TEFC Unimount), FCT and CT
(Cast Iron frame TEFC Hostile Duty), TU, AU,
RU and HU (Vertical motor designs), frames
143T through 449J.

U.S. Electrical Motors was the first to market


with a UL approved Fire Pump motor, meeting
the requirements which became effective
January 1, 1998. The following product
definition covers three phase 140-440 frame
These motors for fire pump applications meet open dripproof motors for fire pump service.
the special design requirements listed below to Any feature not specifically described is per
qualify for U.S. Electrical Motors UL-listed fire NEMA MG-1 standards.
pump ratings.

Fire Pump Motor Agency Listings:

All motors are designed to meet NEMA CSA...............Approved


Design B limitations per NEMA MG1UL..................Recognized construction
1993.
listed for fire pump service
All motors are rated 500 horsepower or
less and 600 volts or less.

Calculated safe stall time exceeds 12


seconds (cold).

All motors meet Canadian CSA-390


Table 2 efficiency requirements.

Motors are suitable for wye-delta start


on 250 frame and larger.

Dual voltage ratings suitable for Part


Wind Start (on low voltage) as well as
460 volt ratings on 125 horsepower and
larger.

All motors depict the UL file number Fire


Pump tag , as shown below.

Fire Pump Motor Highlights


World Motor & Standard Efficient Open Dripproof
(types FD & FR, D & R)
General:
Horsepower Range.........................1 through 500
Frame Range...................................143T through 449T
Poles.................................................2 through 6
Enclosure.........................................Open dripproof
Ambient............................................40 degrees C
Altitude..............................................3300 feet
Electrical:
Phase...............................................Three
Frequency........................................60/50 hertz on tri-voltage
60 hertz only on single volt
Voltage (60 hz)................................200, 200/400, 208-230/460,
460 or 575

*60 hertz only on D & R


standard efficient

Mechanical:
Mounting..........................................Rigid base, F-1 standard
F-2 convertible
Leads
Quantity 140-210 frame
9 dual volt, 3 single volt
250 frame-125HP
12 dual volt, 6 single volt
150 HP & up
12 - 460 volt, 6 - 575 volt
Length
6 inches from CB base
Termination 140-280 frame
Pigtail
320-360
Compression lug
Insulation.........................................Class F system, nameplated B
Balance............................................NEMA standard
Lifting Provisions............................Standard on 210 through 440 frame
Bearings, Type...............................Ball, C-3 fit. Sealed on 140 frame
Double shielded 180-360 frame
Open on 400-440 frame
Bearings, Size.................................Match current D
Bearings, Lock................................Provision for
Relube Provisions..........................140 frame lubed for life
Regreasable on 180-440 frame
at 12:00 and 6:00 position
Conduit Box ...................................Diagonally split box - 4 position
conduit entrance. Meets NEC volumes

Fire Pump Motors


World Motor & Standard Efficient Open Dripproof
(types FD & FR, D & R)
Construction Materials:
Frame.............................................Steel with welded base,
140 - 320 frame
Cast iron 360-440 frame
End Bells........................................Aluminum on 140-250
Cast Iron, 280-440 frame
Conduit Box ...................................Steel
Rotor ..............................................Die cast aluminum,
Stator.............................................Electrical grade steel
Shaft...............................................Carbon steel
Paint, primer..................................Cast iron parts only
Paint, Finish Coat..........................World Motor gray
Connection Diagram.....................Oversized mylar
Performance:
Duty Cycle.......................................Continuous
Service Factor:
60 Hertz
1.15
50 Hertz
1.0
50 Hz not available for std efficient
Temperature Rise..........................Class B @ 1.15
Electrical Design.............................B
Efficiency
Nominal
Per NEMA 12-10
For std efficient: Per current type
Guaranteed 20% losses
Conversion Kits:
C-Face............................................No
D-Flange.........................................No
Brake...............................................No
Space Heater.................................Yes
Canopy Cap...................................Yes

Emerson Motors
8100 West Florissant Avenue, St. Louis, MO 63136
WWW Home Page: http://www.usmotors.com
REGIONAL OFFICES
DOMESTIC U.S. SALES
INTERNATIONAL SALES
MONTREAL, QUEBEC/CANADA
TORONTO, ONTARIO/CANADA

PDS 222-218

02/01

PHONE
(888) 637-7333
(314) 553-3185
(800) 361-5509
(905) 475-4670

FAX
(314) 553-1101
(314) 553-2135
(514) 332-5912
(905) 475-4672

REGIONAL OFFICES
MONTERREY, MEXICO
CARACAS, VENEZUELA
BOGOTA, COLOMBIA

PHONE
(52) 8-389-1312
(58) 02-2377522
(57)1- 439-5420

2001 U.S. Electrical Motors - Prices, specifications and ratings subject to change without notice.

FAX
(52) 8-389-1310
(58) 02-2329727
(57)1- 439-5417

Printed in the U.S.A

Page 1 of 1

Model Number:
Status:
Motor Type:
Frame:
MPI:
HP:
POLES:
VOLTS:
HZ:
SERVICE FACTOR:
EFFICIENCY (%):

DI=4501
PUB
FD
326
125313
60.00
2
415
50
1.15
S.F.
FULL
3/4
1/2
1/4

91.5
92.4
93.9
94.1
91.9

S.F.
FULL
3/4
1/2
1/4
NO LOAD
LOCKED ROTOR

87.2
87.9
87.5
83.7
68.0
6.2
34.8

S.F.
FULL
3/4
1/2
1/4
NO LOAD
LOCKED ROTOR

90.0
77.0
57.0
40.0
24.9
17.4
419.0
F
B
2955
92.4
91.0
10.6
50
3300
70.0

POWER FACTOR (%):

AMPS:

NEMA CODE LETTER


NEMA DESIGN LETTER
FULL LOAD RPM
NEMA NOMINAL EFFICIENCY (%)
GUARANTEED EFFICIENCY (%)
MAX KVAR
AMBIENT (C)
ALTITUDE (FASL)
SOUND PRESSURE (DBA @ 1M)
TORQUES:
BREAKDOWN{% F.L.}
LOCKED ROTOR{% F.L.}
FULL LOAD{LB-FT}
SAFE STALL TIME-HOT (SEC)

252
155
106.7
10

NEMA Nominal and Guaranteed Efficiencies are up to 3,300 feet above sea level and 25 C ambient.
The Above Data Is Typical, Sinewave Power Unless Noted Otherwise

NIDEC MOTOR CORPORATION


ST. LOUIS, MO
Nidec trademarks followed by the symbol are registered with the U.S. Patent and Trademark Office.

http://nmcmotor.com/CIMWebViewer/CIMWebViewerPerfData.asp?MI=1

5/21/2014

HORIZONTAL MOTORS

EFFECTIVE:

11-MAY-11

PRINT:

OPEN DRIPPROOF
FRAME: 320TS
TYPE: D

SUPERSEDES:

17-APR-02

07-2200

SHEET:

1 OF 1

AB

BS

AC
N
T

W
V
ES
P

O
AF
D

U
AA SIZE
CONDUIT

BA

2F

2E

A
H
4 HOLES

IN
MM

UNITS
IN
MM

FRAME
324TS
326TS

25.75
654

8.00
203

6.25
159

12.50
318

.25

V
U
-.001 MIN

AA

AB

.50
13

2.00
2.00

12.69
322

15.00
381

14.00
356

2.19
56

1.875
47.63

3.50
89

UNITS

2F
.03

IN
MM
IN
MM

10.50
267
12.00
305

1: ALL ROUGH DIMENSIONS MAY VARY BY .25" DUE


TO CASTING AND/OR FABRICATION VARIATIONS.
2: LARGEST MOTOR WIDTH.
3: TOLERANCE UNITS ARE IN INCHES ONLY.

4.25
108

15.13
384

14.19
360

.69
18

2.31
59

3.81
97

AC

AF

BA

BS

ES
MIN

SQ
KEY

9.31
237

3.25
83

5.25
133

11.50
292

2.03
52

.500
12.70

4: STANDARD ASSEMBLY POSITION F-1 IS SHOWN.


F-2 IS PROVIDED WHEN SPECIFIED. CONDUIT OPENINGS
MAY BE LOCATED IN STEPS OF 90 REGARDLESS OF LOCATION.
STANDARD AS SHOWN WITH CONDUIT OPENING DOWN.

07-2200/B

ISSUED BY

Nidec Motor Corporation


St. Louis, Missouri

INFORMATION DISCLOSED ON THIS DOCUMENT


IS CONSIDERED PROPRIETARY AND SHALL NOT BE
REPRODUCED OR DISCLOSED WITHOUT WRITTEN
CONSENT OF NIDEC MOTOR CORPORATION

R. KING
APPROVED BY

M OT O R S

K. POTTER

IHP_DP_NMCA (MAR-2011) SOLIDEDGE

UNITS

ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS


D
H
2E
G
B
C
E
J
+.05
-.06
.03

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

13

Revision No.

Vendor Doc. No.

ECD-E3002
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

ELECTRIC FIRE PUMP


CONTROLLER DATA
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data Submittal Document


Model GPW
Full Service Reduced Voltage
Wye-delta Open
Electric Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers covered under our standard offering.

Actual AS BUILT drawings may differ from what is shown in this package.

February 2014

Technical Data
Model GPY Electric Fire Pump Controller
1M

3L3

From normal
incoming power through
Disconnecting Means
(IS/CB)*

T2

3L1

T1

CR4

2M

1M

CR5

1S

CR5

T5

T4
2M

3L1

T3

3L2

T6

2M

1S

1S

3L2

Starting Method: Reduced Voltage


Wye-delta open
Typical Voltage Applied at Start: 100%
Inrush Current: 33% of normal load current
Starting Torque: 33%
Motor Type: Wye-delta
No. of Contactors: 2 at 58%, 1 at 33% of motor FLC
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC

Built to NFPA 20 (latest edition)


Standard,
Listings,
Approvals and
Certifications

Underwriters Laboratory (UL)

UL218 - Fire Pump Controllers


CSA C22.2 No. 14 Industrial Control Equipment

FM Global

Class 1321/1323

New York City

Accepted for use in the City of New York by the Department of Buildings

Optional

CE Mark

Enclosure

Protection Rating
Standard: NEMA 2 (IP31)
Optional
NEMA 12
NEMA 3
NEMA 3R
NEMA 4
Accessories
Bottom entry gland plate
Lifting Lugs
Keylock handle

Various EN, IEC & CEE directives and standards

NEMA 4X-304 sst painted


NEMA 4X-304 sst brushed finish
NEMA 4X-316 sst painted
NEMA 4X-316 sst brushed finish

IP54
IP55
IP65
IP66

Paint Specifications
Red RAL3002
Powder coating
Glossy textured finish

*Please see Disconnecting Means details on page 3.

February 2014

Technical Data
Model GPY Electric Fire Pump Controller

Shortcircuit
Withstand
Rating

Standard 100kA

200V to 208V
60Hz

220V to 240V
60Hz

380V to 416V
50 Hz / 60Hz

440V to 480V
60Hz

575V to 600V
60Hz

HP (kw)
5-150 (3.7 - 110)

5-200 (3.7 - 147)

5-300 (3.7 - 220)

5-450 (3.7 - 335)

n/a

Standard 50kA

200 (147)

250 (184)

350 - 450 (257 - 335)

500 (373)

Optional 100kA

n/a

n/a

n/a

n/a

5-500
(3.7- 373)

Optional 150kA

Ambient
Temperature
Rating
Surge
Suppression

Disconnecting
Means

Standard:
5C to 40C / 41F to 104F

Surge arrestor rated to suppress surges above line voltage


Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
- Circuit breaker continuous rating not less than 115% of motor full load current
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
Common flange mounted operating handle

Service Entrance
Rating

Suitable as service entrance equipment

Emergency Start
Handle

Flange mounted
Pull and latch activation

Locked Rotor
Protector

Optional:
5C to 50C / 41F to 122F
5C to 55C / 41F to 131F

Integrated limit switch


Across the line start (direct on line)

Operate shunt trip to open circuit breaker


Factory set at 600% of motor full load current

Electrical
Readings

Voltage phase to phase (normal power)


Amperage of each phase when motor is running

Pressure
Readings

Continuous system pressure display


Cut-in and Cut-out pressure settings

Pressure and
Event recorder

Pressure Sensing

February 2014

Trip between 8 and 20 seconds

Pressure readings with date stamp


Event recording with date stamp
Under regular maintained operation, events can be stored in memory for up to 5 years.
Data viewable on operator interface display screen
Downloadable by USB port to external memory device
Pressure transducer and run test solenoid valve assembly for fresh water application
Pressure sensing line connection 1/2 Female NPT
Drain connection 3/8
Rated for 0-500PSI working pressure (calibrated at 0-300psi)
Externally mounted with protective cover

Technical Data
Model GPY Electric Fire Pump Controller
Audible Alarm

Visual Indications
& Alarms

Remote Alarm
Contacts

ViZiTouch
Operator Interface

4 alarm bell - 85 dB at 10ft. (3m)


Power available
Phase reversal
Motor run
Pump room alarm
Motor trouble
Phase loss
Phase unbalance
Low water level

Manual start
Deluge valve start
Remote automatic start
Remote manual start
Overcurrent
Undercurrent
Undervoltage
Overvoltage

SPDT-8A-250V.AC
Power available
Phase reversal
Motor run
Common pump room alarm (field re-assignable)**
Overvoltage
Undervoltage
Low pump room temperature
High Pump room temperature
Common motor trouble (field re-assignable)**
Overcurrent
Fail to start
Undercurrent
Ground fault
Free (field programmable)**

Phase unbalance

Embedded microcomputer with software PLC logic


4.2 color touch screen (HMI technology)
Upgradable software
Expandable storage
Multi-language
Automatic Start

Manual Start

Operation

Locked rotor
Periodic test
Fail to start
Low discharge pressure
Low pump room temperature
Pump room temperature (F or C)
Pump on demand/Automatic start
Emergency start

Stopping
Timers

Start on pressure drop


Remote start signal from automatic device
Start pushbutton
Run test pushbutton
Deluge valve start
Remote start from manual device
Manual with Stop pushbutton
Automatic after expiration of minimum run timer ***
Field Adjustable &
Visual Countdown

Actuation
Visual Indication
Mode

Minimum run timer ***(off delay)


Sequential start timer (on delay)
Periodic test timer
Pressure
Non-pressure
Automatic
Non-automatic

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
***Can only be used if approved by the AHJ

February 2014

Technical Data
Model GPY Electric Fire Pump Controller
A4

Flow switch provision

C20

Manual start alarm contact (Form C-SPDT)

A8

Foam pump application w/o pressure transducer and run


test solenoid valve

C21

Deluge valve start alarm contact (Form C-SPDT)

C22

Remote automatic start alarm contact (Form C-SPDT)

A9

Low zone pump control function

C23

Remote manual start alarm contact (Form C-SPDT)

A10

Medium zone pump control function

C24

High pump room temperature alarm contact (Form C-SPDT)

A11

High zone pump control function

Cx

A13

Non-pressure actuated controller w/o pressure transducer


and run test solenoid valve

Additional visual and alarm contact


(specify function) (Form C-SPDT)

D1

A16

Lockout/interlock circuit from equipment installed inside the


pump room

Low suction pressure transducer for fresh water rated at


0-300PSI with visual indication and alarm contact

D1A

Low suction pressure transducer for sea water rated at


0-300PSI with visual indication and alarm contact

B11

Built in alarm panel (120V.AC supervisory power) providing


indication for:
Audible alarm & silence pushbutton for motor run, phase
reversal, loss of phase.
Pilot lights for loss of phase & supervisory power available

D5

Pressure transducer and run test solenoid valve for fresh


water rated for 0-500PSI (for calibration purposes only)

D5D

Pressure transducer and run test solenoid valve


for sea water rated for 0-500PSI

B11B

Built in alarm panel same as B11 but 220-240VAC


supervisory power

D10

Omit mounting feet (when applicable)

B19

High motor temperature thermistor relay c/w visual


indication and alarm contact (Form C-SPDT)

D13

B21

Ground fault alarm detection c/w visual indication and alarm


contact (Form C-SPDT)

High withstand rating for:


208V to 480V = 150kA
600V = 100kA

D14

Anti-condensation heater & thermostat

C1

Extra motor run alarm contact (Form C-SPDT)

D14A

Anti-condensation heater & humidistat

C4

Periodic test alarm contact (Form C-SPDT)

D14B

Anti-condensation heater & thermostat & humidistat

C6

Low discharge pressure alarm contact (Form C-SPDT)

D15

Tropicalization

C7

Low pump room temperature alarm contact (Form C-SPDT)

D18

CE Mark with factory certificate

C10

Low water reservoir level alarm contact (Form C-SPDT)

D26

Modbus RTU provision

High electric motor temperature alarm contact


(Form C-SPDT)

Modbus TCP/IP provision

C11

D26A
D27

C12

High electric motor vibration c/w visual indication and alarm


contact (Form C-SPDT)

Motor heater connection (external single phase power


source and heater on/off contact)

D27A

C14

Pump on demand/automatic start alarm contact


(Form C-SPDT)

Motor heater connection (internal single phase power


source and heater on/off contact)

D28

Customized drawing set

C15

Pump fail to start alarm contact (Form C-SPDT)

D34

Field programmable I/O board - 8 Input / 5 output

C16

Control voltage healthy alarm contact (Form C-SPDT)

D35

Field programmable I/O board - 8 Input / 10 output

C17

Flow meter valve loop open c/w visual indication and alarm
contact (Form C-SPDT)

D36

Redundant pressure transducer for fresh water rated for


0-500PSI (calibrated at 0-300PSI)

C18

High water reservoir level c/w visual indication and alarm


contact (Form C-SPDT)

D36A

Redundant pressure transducer for sea water rated for


0-500PSI (calibrated at 0-300PSI)

C19

Emergency start alarm contact (Form C-SPDT)

D37

Window kit for operator interface

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

February 2014

Technical Data
Model GPY Electric Fire Pump Controller
L01

Other language and English (bilingual)

L11

Czech

L02

French

L12

Portuguese

L03

Spanish

L13

Dutch

L04

German

L14

Russian

L05

Italian

L15

Turkish

L06

Polish

L16

Swedish

L07

Romanian

L17

Bulgarian

L08

Hungarian

L18

Thai

L09

Slovak

L19

Indonesian

L10

Croatian

L20

Slovenian

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

February 2014

Technical Data
Model GPY Electric Fire Pump Controller
ViZiTouch Operator Interface
3

PMS 295

PMS 361

Noir

9
10

11

12

1 - Power on LED
2 - Color touch screen
3 - Alarm LED
4 - HOME page button
5 - ALARM page button
6 - CONFIGURATION page button
7 - HISTORY page button

February 2014

13

8 - USB port
9 - START button
10 - Contextual navigation pad
11 - STOP button
12 - RUN TEST button
13 - HELP button

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

14

Revision No.

Vendor Doc. No.

JPD-J4001
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

JOCKEY PUMP DATA


Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends
ELECTRIC FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

2013

.08

RV,RVA
Vertical Multistage Centrifugal Pump
50Hz

Product introduction

Vertical Multistage Centrifugal Pump

Pump

Terminal box positions

RVA and RV are non-s elf priming vertical multistage


centrifugal pump, the pumps are available with standard moto r, the inlet and outle t are located at the
pump bottom at the same plane (inline type).
All pump s are equipped with a maintenance-free
mechanical seal set of the cartridge type.

As standard the terminal box is mounted on the suction


side of the pump, meanwhile, 0 ,90 ,180 ,270 could be
adjusted according to the following proceeding:
1.If necessary, disassembling the protective cover of
the shaft connector, but did not disassembling the
shaft connector.
2.Disassembling the motor fixation screws.
3.Turn the motor to the required direction.
4.Fasten the motor screws.
5.Install the shaft connector's protective cover.
The voltage and frequency are marked on the label,
the correct power should be confirm with the label
before usage.
To ensure the electric connection is conformity to the
drawing marked on the label inside the terminal box.

Fig.1 RVA

Motor
motor base
pump cover

Fig2. Terminal box positions

outer sleeve
fasten bolt
Impellers
hydraulic stack

Position 1

position 2

position 3

Position4

Viscosity

pump body

The pumping of liquids with densities or kinematic viscosities higher than those of water will cause a considerable pressure drop, a drop in the hydraulic performance
and a rise in the power consumption.
In such situations the pump should be fitted with a larger
motor, if in doubt, contact.

Base

Motor
Fig.3 Relationship between motor output (P2)
and temperature

RVA and RV are fitted with a totally enclosed


fan-cooled 2-pole three-phase standard motor.
From 0.37kW to 2.2kW, are also available with
single-phase motor.(1*220-230V/240V).

P2
[%]
100
90
80
70
60
50

Motor Protection
Single-phase motor have a built-in thermal overload switch.
Three-phase motors must be connected to a motor
protective circuit breaker according to local regulations.

20 25 30 35 40 45 50 55 60 65 70 75 80
o
t[ C]
1000
2250 3500 m

Ambient temperature
Ambient temperature: maximum+40 , if the ambient
temperature exceeds +40 , or the pump is installed
at an altitude exceeding 1000 meters, the motor must
not be fully loaded due to the risk of overheating.
Overheating may result from excessive ambient temperatures or the low density and consequently low
cooling effect of the air.
In such cases ,it may be necessary to use a motor with
a higher rated output.

Example:
From the Fig.3, the pump is installed at an altitude exceeding altitude 3500 meters, P2 will decrease to 88%,
if the ambient temperature is up to 70 , P2 will decrease
to 78%.

Construction

Vertical Multistage Centrifugal Pump

RV1,2,3,4,5

RVA1,2,3,4,5

Sectional drawing

Sectional drawing

1
2
3
4
5
6
7
8
9
10

1
2
3
4
5
6
7
8
9
10
14

13
12
11

Material RV
No.

Description

15
13
12
11

Material RVA
Material

EN/DIN

AISI/ASTM

No.

Description

Material

EN/DIN

Cast iron

EN-JL1030

AISI/ASTM

Motor

Motor

Shaft connector

Shaft connector

Pump head

Pump head

Mechanical seal

Mechanical seal

Shaft

S.S

AISI420

Shaft

S.S

1.4057

AISI431

Outlet

S.S

1.4301

AISI304

Outlet

S.S

1.4301

AISI304

Impeller

S.S

1.4301

AISI304

Impeller

S.S

1.4301

AISI304

Hydraulic stack

S.S

1.4301

AISI304

Hydraulic stack

S.S

1.4301

AISI304

Inlet

S.S

1.4301

AISI304

Inlet

S.S

1.4301

AISI304

10

Pump body

Cast iron

EN-JL1030

ASTM25B

10

Pump body

S.S

1.4301

AISI304

11

Neck ring

PTFE

11

Neck ring

PTFE

12

Outer sleeve

12

Outer sleeve

1.4301

AISI304

13

O-ring

13

O-ring

14

Bottom base

Cast iron

15

Pump cover

S.S

Cast iron

S.S

EN-JL1030

1.4301

ASTM25B

AISI304

EPDM/FKM

S.S

ASTM25B

EDM/FKM

EN-JL1030
1.4301

ASTM25B
AISI304

Operating and inlet pressures

Vertical Multistage Centrifugal Pump

Maximum operating pressure and temperature range

DIN-FGJ

PJE

UNION

Max. permissible operating pressure

Liquid temperature range

RV,RVA1

25bar

-20 oC to +104 oC

RV,RVA2

25bar

-20 oC to +104 oC

RV,RVA3

25bar

-20 oC to +104 oC

RV,RVA4

25bar

-20 oC to +104 oC

RV,RVA5

25bar

-20 oC to +104 oC

16bar

-20 oC to +104 oC

25bar

-20 oC to +104 oC

RV,RVA10-1
RV,RVA10-12

RV,RVA10-10
RV,RVA10-17

RV,RVA15-1

RV,RVA15-8

16bar

-20 oC to +104 oC

RV,RVA15-9

RV,RVA15-12

25bar

-20 oC to +104 oC

RV,RVA20-1

RV,RVA20-7

16bar

-20 oC to +104 oC

RV,RVA20-8

RV,RVA20-10

25bar

-20 oC to +104 oC

RV,RVA32-1-1

RV,RVA32-5

16bar

-20 oC to +104 oC

RV,RVA32-6-2

RV,RVA32-8

25bar

-20 oC to +104 oC

RV,RVA32-9-2

RV,RVA32-10-2

30bar

-20 oC to +104 oC

RV,RVA45-1-1

RV,RVA45-4

16bar

-20 oC to +104 oC

RV,RVA45-5-2

RV,RVA45-6-1

25bar

-20 oC to +104 oC

30bar

-20 oC to +104 oC

RV,RVA45-6

RV,RVA45-7

RV,RVA64-1-1

RV,RVA64-3

16bar

-20 oC to +104 oC

RV,RVA64-4-2

RV,RVA64-5-2

25bar

-20 oC to +104 oC

RV,RVA90-1-1

RV,RVA90-3

16bar

-20 oC to +104 oC

25bar

-20 oC to +104 oC

RV,RVA90-4-2

Operating range of the shaft seal

Fig.4 Operating range of standard shaft seals

The operating range of the shaft seal depends on


operating pressure, pump type, type of shaft seal
and liquid temperature.The range shown in fig 4.
Applies to clean water and water with glycol liquids.

P[bar]
35

30
25
H
Q HQUE
U
E HQUV

20
15
10

H
Q
U
E

HQUE
HQUV

5
0
-40

10

- 20

20

40

60

80

1 00

1 20 1 40
t[ oC]

Selection and sizing

Vertical Multistage Centrifugal Pump

Minimum inlet pressure-NPSH


Calculation of the inlet pressure "H" is recommended
in these situations :
the liquid temperature is high.
the flow is significantly higher than the rated flow.
water is drawn from depths.
water is drawn through long pipes.
inlet conditions are poor. to avoid cavitation, make sure
that there is a minimum pressure on the suction side of
the pump.
The maximum suction lift "H" in metres head can be
calculated as follows:
H=Pb*10.2-NPSH-Hf-Hv-Hs

Fig.13 Mimimum inlet pressure-NPSH

Hf

P b = Barometric pressure in bar.


(Barometric pressure can be set to 1 bar).
in closed systems,P b indicates the system pressure
in bar.

tm
[ oC]

Hv
[m]

190

126

180

100

170

79

160

62

150

130

45
40
35
30
25

120

20

110

15

140

NPSH
Pb

Hv

100
90

NPSH = Net positive suction Head in metres head.


(To be read from the NPSH curve at the highest flow
the pump will be deivering).

80
70
60

Hf = Friction loss in suction pipe(unit:m).


(At the highest flow the pump will be delivering.)

50
40

Hv = Vapour pressure (unit:m).


(To be read from the vapour pressure scale).

30
20

Hs = safty margin=minimum 0.5 metres head.

10

If the "H" calculted is positive,the pump can operate


at a suction lift of maximum "H" metres head. If the
"H" calculted is negative,
an inlet pressure of minimum "H" metres
head is required.
Example:
P b =1bar
pump model:RVA10,50Hz
flow: 10m3/h
NPSH(P36 reference:2.1 metres head.
liquid temperature:+50C
Hv(reference picture4):1.3metres head.
H=P b *10.2-NPSH-Hf-Hv-Hs
H=1*10.2-2.1-3.0-1.3-0.5=3.3(metres)
It means the pump can operate at a suction lift
of maximum 3.3 metres head.
exchaged meter head to bar:
1 metre head=1*0.0981=0.0981bar
exchaged metre head to kpa:
1 metre head=1*9.81=9.81kpa.

14

12
10
8.0
6.0
5.0
4.0
3.0
2.0
1.5
1.0
0.8
0.6
0.4
0.3
0.2
0.1

Performance Curve
0

0
P
(kPa)

H
(m)

2200

220

RV4-50Hz
8

12

16

20

12

24 Q(US.GPM)

16

20 Q(IMP.GPM)
RV4
50Hz

-22

H
(ft)
700

2000

200
-19

1800

180

1600

160

1400

140

1200

120

1000

100

600
-16

50Hz
-14

-12

600

400

-10
-8

800

500

80

300

-7
-6

60

200

-5
400
200
0

-4
-3

40

100

-2

20

0
0.0
0.0

0.5

1.0

0.2

1.5
0.4

2.0

2.5

0.6

3.0
0.8

3.5

4.0

1.0

4.5
1.2

5.0

5.5

Q(m 3/h)
Q(L/S)

1.4

Eta(%)

P 2 (kW)
0.30

Eta
P2

0.20

60
40

0.10

20

0.00

0
0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

Q(m 3/h)

NPSH
(m)

NPSH
(f t)

4.0

12
9
6
3
0

3.0
NPSH

2.0
1.0
0.0
0.0

0.5

1.0

1.5

2.0

2.5

3.0

30

3.5

4.0

4.5

5.0

5.5

Q(m 3/h)

Technical Data

RV4-50Hz

Performance table
Power
P 2(kW)

Model

Q
(m 3/h)

1.0

2.0

3.0

4.0

4.5

5.0

5.5

6.0

RV4-2

0.37

22

21

19.5

18

17

16

14

13

RV4-3

0.55

31

29.5

28

24

22

21

19

18

RV4-4

0.75

40

38

35

31

29

27

24

22

RV4-5

1.1

50

48

44

40

38

34

30

26

RV4-6

1.1

59

57

53

49

45

41

36

30

RV4-7

1.5

71

69

65

59

55

50

43

36

RV4-8

1.5

83

80

78

71

65

59

51

42

RV4-10

2.2

103

100

95

87

80

79

73

54

RV4-12

2.2

122

119

113

103

96

88

78

68

RV4-14

3.0

139

134

128

118

111

102

90

79

RV4-16

3.0

158

153

145

134

126

116

103

89

RV4-19

4.0

186

180

170

155

145

133

117

98

RV4-22

4.0

216

208

197

182

172

159

143

126

H
(m)

Dimensions and weights

Installation sketch

Dimensions(mm)
Model

Weight
(kg)

B1

B2

B1+B2

RV4-2

262

205

467

133 102

25

RV4-3

280

205

485

133 102

25

RV4-4

299

205

504

133 102

26

RV4-5

322

241

563

154

111

26

RV4-6

340

241

581

154

111

28

RV4-7

358

241/293

599/651

154

111

33

RV4-8

376

241/293

617/669

154

111

33

RV4-10

420

275/293

695/713

177 116

35

RV4-12

456

275/293

731/749

177 116

35

RV4-14

492

275/293

767/785

177 116

38

RV4-16

528

275/293

803/821

197 116

38

RV4-19

602

305

907

197 148

48

RV4-22

656

305

961

197 148

53

D1

D2

D2

B2

D1

FGJ(DIN-ANSI-JIS)
PN25(DN32/DN25)

B1

G1/2

24.5 X19

G1/2

140

89

56
75

100

20

32

20

100
155

180

250

210

4- 13

31

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

15

Revision No.

Vendor Doc. No.

JPCD-J5001
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

JOCKEY PUMP
CONTROLLER DATA
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends

ELECTRIC FIRE PUMP


Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data Submittal Document


Model JP3
Across the Line Start
Jockey Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers covered under our standard offering.

Actual AS BUILT drawings may differ from what is shown in this package.

November 2014

Technical Data
Model JP3 Jockey Pump Controller
JP3

Starting Method: Full Voltage


Across the line (Direct on line)
Typical Voltage Applied at Start: 100%
Inrush Current: 6 x normal load current
Starting Torque: 100%
Motor Type: Across the line (Direct on line)
No. of Contactors: 1 at 100% of horsepower
Min. ampacity of motor conductors: 3 at 125% x 100% of Full load Current (FLC)
Underwriters Laboratory (UL) UL508A - Industrial Pump Controllers
Listing

CSA

CSA C22.2 No. 14 Industrial Control Equipment

New York City

Accepted for use in the City of New York by the Department of Buildings

Optional

CE Mark

Enclosure

Protection Rating
Standard: NEMA 2 (IP31)
Optional
NEMA 12
NEMA 3
NEMA 3R
NEMA 4
Accessories
Wall mounting lugs ( x4)

November 2014

Various EN, IEC & CEE directives and standards

NEMA 4X-304 sst painted


NEMA 4X-304 sst brushed finish
NEMA 4X-316 sst painted
NEMA 4X-316 sst brushed finish
Paint Specifications
Red RAL3002
Powder coating
Glossy textured finish

Technical Data
Model JP3 Jockey Pump Controller

Fuseless Motor
Starter

Main disconnect - rotary type - door interlocked


Thermo-magnetic motor protector
Contactor

Control Circuit

24V.AC

iPD+ Operator
Interface

Solid state controls


All adjustments on door front
Navigation pushbuttons

Pressure Sensing

Pressure transducer for fresh water application 316 stainless steel construction
Rated for 0-600psi working pressure
Pressure sensing line connection Male NPT

Visual Indications

Manual motor start/run LED


Automatic motor start/run LED
Pressure reading
Start pressure
Stop pressure
System pressure
System pressure diagnostic LEDs
Green: system pressure at or above stop pressure
Yellow: system pressure between start and stop pressure
Red: system pressure at or below start pressure
AUTO mode
OFF mode

Timers
Operators

Operation

November 2014

Minimum run timer (off delay)


Delay start timer (on delay)
Visual countdown
OFF-AUTO pushbutton
Start and Stop pushbutton
Automatic Start

Start on pressure drop

Manual Start

Start pushbutton

Stopping

Stop pushbutton

Timers

Field adjustable &


visual countdown

Minimum run timer (off delay)


Delay start timer (on delay)

Technical Data
Model JP3 Jockey Pump Controller
A4

Elapsed time meter (time totalizer)

L01

Other language and English (bilingual)

A5

Motor run alarm contact

L02

French

A6

Loss of power alarm contact

L03

Spanish

A7

Overload or short circuit alarm contact

L04

German

A7A

Overload pilot light

L05

Italian

D12

CE Mark c/w externally mounted wetted parts

L06

Polish

D13A

Externally mounted wetted parts

L07

Romanian

D14

Export packing for 1 controller

L08

Hungarian

D18

Audible alarm

L09

Slovak

D19

Anti-condensation heater and thermostat

L10

Croatian

D20

Anti-condensation heater and humidistat

L11

Czech

D21

Tropicalization

L12

Portuguese

D22

Phase reversal / failure pilot light and alarm contact

L13

Dutch

D23

Controller power healthy pilot light and alarm contact

L14

Russian

D24

Pump failure via current sensing relay with pilot light and dry
alarm contact

L15

Turkish

D25

Low zone pump control function

L16

Swedish

D26

Mid zone pump control function

L17

Bulgarian

D27

High zone pump control function

L18

Thai

D28

Selector switch in auto alarm contacts

L19

Indonesian

D29

Selector switch in off alarm contacts

L20

Slovenian

D30

Motor heater circuit

D32

Service entrance rated - 100kA short circuit withstand rating:


120V/1ph (0.5hp max.)
240V/1ph (1hp max.)
200V-208V - 60hz (2hp max.)
220V-240V - 60hz (3hp max.)
380V-416V - 50hz - 60hz (5hp max.)
440V-480V - 60hz (5hp max.)

D33

Service entrance rated - 65kA short circuit withstand rating:


120V/1ph (0.5hp max.)
240V/1ph (1hp max.)
200V-208V - 60hz (3hp-15hp max.)
220V-240V - 60hz (515hp max.)
380V-416V - 50hz - 60hz (7.5hp - 40hp max.)
440V-480V - 60hz (7.5hp-40hp max.)

D34

Service entrance rated - 42kA short circuit withstand rating:


600V - 60hz (7.5hp max.)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

November 2014

Technical Data
Model JP3 Jockey Pump Controller
iPD+ Operator Interface

HAND

AUTO

5
8

1 - Power on LED
2 - System status LED
3 - Digital display
4 - Hand start LED
5 - START pushbutton

November 2014

6 - STOP pushbutton
7 - Auto start LED
8 - Navigation keypad
9 - ON - OFF pushbutton

PER QUOTE DRAWING No.

Jockey Pump Controller


Across the Line / 3 Phase

Dimension

0
1

DD/MM/YY

DESCRIPTION

REV.

Model:JP3

8
NYC
Dpt of Building
Approved

First Issue
Dimension Table and Notes

04/07/14
17/10/14

Drawing No.

FU1
B

JP3-DI500 /E

Built to the latest edition of the UL 508A & CSA C22.2 No.14

DS
B

XTR1

D
F

1L1

3L2

5L3

2T1

4T2

6T3

Underwriters
Laboratories Inc.
LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX

NYC

Main Disconnect
ON

G
Y

OFF

HAND

AUTO

G
D

DS

OL1

C1

PT1
DANGER
Rating
Label

Sensing Line
Connection

Standard Internal Layout

"[9] x4

1/4 " M.NPT

Dimension*
Maximum Motor Horsepower
200-208V
3HP
5HP
10HP
20HP
25HP

220-240V
3HP
5HP
10HP
20HP
30HP

380-416V
7.5HP
10HP
20HP
40HP
50HP

440-480V
7.5HP
10HP
20HP
50HP
60HP

575-600V
10HP
15HP
25HP
50HP
60HP

Dimension Enclosure
AXBXC

Dimension Door
DXE
10- "X12- "
10- "X12- "
10- "X12- "

Dimension Anchor
FXG

TBD

TBD

TBD

A
H

Notes:
- Standard NEMA: NEMA 2
- Standard Paint : Textured Red RAL 3002.
- All Dimensions are in Inches [Millimeters]
- Use Watertight Conduit and Connector Only.
- Protect Equipment Against Drilling Chips.
- Door Swing Equal to Door Width
0

- Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
-*Dimension may change depending on option required. Consult Factory for exact
dimensions.
2

I
Projection

Jockey Pump Controller


Across the Line / 3 Phase
A

L2

DD/MM/YY

DESCRIPTION
First Issue
Remove Dimension Table

04/07/14
17/10/14

Built to the latest edition of the UL 508A & CSA C22.2 No.14

Drawing No.

JP3-WS500 /E

L3

PT1

Pressure Sensor
Type 0-100mV

0
1

8
NYC
Dpt of Building
Approved

REV.

Model:JP3

Wiring schematic
L1

PER QUOTE DRAWING No.

DS

Red

White

Green

Black

B W G R
FU1

5 S

HAND

AUTO

J5

H2

X1 3

H1

X2

PsInPsOutPsOut+
PsIn+

XTR1

J9

C
J8

"IPD+"

RESET
G

J19
A2
A1
A2
A1

OUT2

OUTPUT ON

OUT1

F5

24Vdc

J2

J3

J1
24Vac

24Vac

A2 A1
22 8

3 1

OL1

14

13

A1

C1

A2

OL1

H
C1

G
T1 T2 T3

P1
0

- Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
1

PER QUOTE DRAWING No.

Jockey Pump Controller


Across the Line / 3 Phase

Line and Motor Terminal Size

0
1

DD/MM/YY

DESCRIPTION

REV.

Model:JP3

8
NYC
Dpt of Building
Approved

First Issue
Remove Dimension Table

04/07/14
17/10/14

Built to the latest edition of the UL 508A & CSA C22.2 No.14

Drawing No.

Power Connections and Motor Connections

JP3-TD500 /E

3 Phases
Incoming Power

Bonding Ground

L1 L2 L3
DS

C1
T1 T2 T3

Line Terminals (L1,L2,L3,GND)


Maximum Motor Horsepower

200-208V
7.5HP
10HP
15HP

220-240V
10HP
10HP
15HP

380-416V
15HP
20HP
25HP

440-480V
20HP
25HP
30HP

575-600V
15HP
25HP
40HP

Wire Size Copper Only

Torque

Wire Size Ground Copper Only

#14 AWG - #8 AWG


#12 AWG - #4 AWG
#4 AWG - #1/0 AWG

1.8 Nm
1.8 Nm
5.65 Nm

#14 AWG - #2 AWG


#14 AWG - #2 AWG
#6 AWG - #2 AWG

Motor Terminals (T1,T2,T3,GND)

Maximum Motor Horsepower

200-208V
3HP
5HP
10HP
20HP
25HP

220-240V
3HP
5HP
10HP
20HP
30HP

380-416V
7.5HP
10HP
20HP
40HP
50HP

440-480V
7.5HP
10HP
20HP
50HP
60HP

575-600V
10HP
15HP
25HP
50HP
60HP

Wire Size Copper Only

Torque

Wire Size Ground Copper Only

#14 AWG - #10 AWG


#14 AWG - #8 AWG
#14 AWG - #6 AWG
#10 AWG - #3 AWG
#10 AWG - #2 AWG

1.7 Nm
1.7 Nm
2.25 Nm
5 Nm
11.3 Nm

#14 AWG - #2 AWG


#14 AWG - #2 AWG
#12 AWG - #2 AWG
#12 AWG - #2 AWG
#12 AWG - #2 AWG

Vendor Ref. No.

Doc. Seq. No.

BFE-2218

16

Revision No.

Vendor Doc. No.

ACC-A6001
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

ACCESSORIES
Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends
ELECTRIC FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

Bourdon Tube Pressure Gauges

Pressure Gauges

Black Polycarbonate Case


Copper Alloy Wetted Parts
UL Listed / FM Approved
Sprinkler Gauges Type 111.10SP

Application
Fluid medium which does not clog connection port or
corrode copper alloy. Specifically designed for the fire
sprinkler industry.
Sizes
4" (100 mm)
Accuracy
+ 3/2/3% of span (ASME B40.1 Grade B)
Ranges
0/80 PSI retard to 250 PSI (Air)
0/300 PSI (Water)
Working Range
Steady:
3/4 of full scale value
Fluctuating: 2/3 of full scale value
Short time: full scale value
Operating Temperature
Ambient:
-40F to 140F (-40C to 60C)
Media:
max. 140F (+60C)
Temperature Error
Additional error when temperature changes from reference
temperature of 68F (20C) +0.4% for every 18F (10C)
rising or falling. Percentage of span.

Standard Features
Connection
Material: copper alloy
Lower mount (LM)
1/4" NPT limited to wrench flat area
Bourdon Tube
Material: copper alloy
C-type
Movement
Copper alloy
Dial
White aluminum with stop pin. Black and red markings
Pointer
Black aluminum- non- adjustable
Case
Black polycarbonate

Order Options (not all options are UL or FM approved)


Brass threaded or press fit restrictor
Cover ring
Glass window
Black painted steel case
Stainless steel case
Special case colors
Special connections limited to wrench flat area
Nickel plated connection
Custom dial layout
Other pressure scales available:
Bar, kPa, MPa, Kg/cm 2 and dual scales
DIN standards

Window
Snap-in clear polycarbonate
Approvals
UL Listed (UL-393)
Factory Mutual Approved

APM 111.10SP
(APM 01.01.4)

Dimensions:

A* NOMINAL SIZE
111.10SP WEIGHT KEY
mm
4"
0.35 lbs.
LM
in

A*

100 83.5
4.0

C
30

11.5 3.75

3.29 1.18 0.45 0.15

--

14

1/4

0.55

THE MEASURE OF

Total Performance

TM

Ordering Information:
State computer part number (if available) / type number / size /
range / connection size and location / options required.
Specifications given in this price list represent the state of engineering at the time of printing.
Modifications may take place and the specified materials may change without prior notice

05/01

WIKA Instrument Corporation


1000 Wiegand Boulevard
Lawrenceville, Georgia 30043-5868
Tel: 770-513-8200 Fax: 770-338-5118
http://www.wika.com e-mail: info@wika.com

Specifications: BY003 Issue Date July 2003

FW and FWC Miniature Relief Valves


DESCRIPTION
The Cash Acme FW miniature relief valves are designed for commercial and
industrial applications including thermal expansion protection, static pressure
and over-pressure relief, very low capacity pump relief, and other uses of
similar nature where tight shut-off is required.
The Cash Acme FW and FWC Valves are small, low-cost relief valves suitable for
static over-pressure protection. A calibrated adjusting screw allows for occasional
changes in pressure setting without the use of a pressure gauge (FWC only). Brass
bodies come with male inlet and female outlet, silicone seat and stainless steel
spring. The FW and FWC valves have standard factory pressure settings of 125 psi.

Cash
Acme
FW

FEATURES AND BENEFITS


Offers protection against problematic and over-pressure conditions:
Thermal expansion protection, static pressure and over-pressure
relief, very low capacity pump relief and other uses of similar
nature where tight shut-off is required.
Commercial and industrial applications:
Designed to meet the needs of a wide variety of water systems.

Cash
Acme
FWC

Every valve is tested for performance prior to shipping:


Specify and install with confidence!

SPECIFICATION
FW: A miniature relief valve shall be installed to relieve pressure for applications
where tight shut-off is required. The valve shall be of bronze construction with a male
inlet and female outlet. The valve shall have a silicone seat and a stainless steel
pressure spring. The valve shall be a Cash Acme FW Relief Valve.
FWC: A miniature relief valve shall be installed to relieve pressure for applications
where tight shut-off is required. The valve shall be of bronze construction with a male
inlet and female outlet. The valve shall have a silicone seat and a stainless steel
pressure spring. The valve shall have a calibrated adjusting screw. The valve shall be
a Cash Acme FWC Relief Valve.

Cash Acme 2400 7th Avenue SW Cullman, AL 35055-0278 1-877-700-4242 Fax: 1-877-700-4280 www.cashacme.com

A Division of the Reliance Worldwide Corporation

Specifications: BY003 Issue Date July 2003

FW and FWC Miniature Relief Valves


TYPICAL INSTALLATION

ACME FACTORY

Cash
Acme
E-41

Cash
Acme
FWC

Cash
Acme
E-56

Water
Meter

SPECIFICATION DATA
Performance:
Set pressure range . . . . . . . . . .15 - 200 psi (Type F) and 25 - 175 psi (Type FWC)
Maximum temperature . . . . . . .210 F
Service . . . . . . . . . . . . . . . . . . .Water

Cash
Acme
FW

Materials:
Body . . . . . . . . . . . . . . . . . . . . .Brass
Pressure Spring . . . . . . . . . . . .Stainless steel
Seat Disc . . . . . . . . . . . . . . . . .Silicone
B

CONNECTIONS
Threaded (NPT) . . . . . . . . . . . .male inlet and female outlet

Cash
Acme
FWC

Dimensions

FW - 1/2"

1 3/16"

1 11/32"

1 1/2"

FW - 3/4"

1 3/16"

1 11/32"

1 1/2"

FWC - 1/2"

1 3/16"

2 5/8"

1 1/2"

1 1/4"

2 5/8"

1 1/2"

FWC -

3 4"

Cash Acme 2400 7th Avenue SW Cullman, AL 35055-0278 1-877-700-4242 Fax: 1-877-700-4280 www.cashacme.com

A Division of the Reliance Worldwide Corporation


CAC0081 7.03 Printed in USA

Vendor Ref. No.

Doc. Seq. No.

BFE-2218

17

Revision No.

Vendor Doc. No.

BFE-UL / CDC
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

CERTIFICATE

Suction and discharge gauge


A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends
ELECTRIC FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

QTY
1

1
1
1

2
1
1

QWZU.EX16459 - Centrifugal Fire Pumps, End Suction

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/show...

QWZU.EX16459
Centrifugal Fire Pumps, End Suction
Page Bottom

Centrifugal Fire Pumps, End Suction


See General Information for Centrifugal Fire Pumps, End Suction
BRISTOL FIRE ENGINEERING L L C

EX16459

AL QUOZ INDUSTRIAL AREA 3


PO BOX 74582
DUBAI, UNITED ARAB EMIRATES
Rated
Capacity
GPM

Size
In.

Model
Dsg

Rated Net
Pressure
Range
psi

Max
Working
Pressure
psi

Approx
Speed
RPM

50

2 X 1 1/4

IS32-200

62-95

2950

230

50

2 X 1 1/4

IS32-200

55-85

2800

230

50

2 X 1 1/4

IS32-260

113-130

2950

230

100

2 X 1 1/4

IS32-260

103-125

2950

230

50

2 1/2 X 2

IS50-320H

103-167

2600

220

50

2 1/2 X 2

IS50-320H

88-142

2400

220

100

2 1/2 X 2

IS50-320H

178-298

3500

330

100

2 1/2 X 2

IS50-320H

132-210

2950

240

100

2 1/2 X 2

IS50-320H

119-189

2800

240

100

2 1/2 X 2

IS50-320H

102-166

2600

220

100

2 1/2 X 2

IS50-320H

87-141

2400

220

150

2 1/2 X 2

IS50-320H

177-296

3500

330

150

2 1/2 X 2

IS50-320H

132-209

2950

240

150

2 1/2 X 2

IS50-320H

118-188

2800

240

150

2 1/2 X 2

IS50-320H

99-165

2600

220

150

2 1/2 X 2

IS50-320H

84-140

2400

220

200

2 1/2 X 2

IS50-320H

173-296

3500

330

200

2 1/2 X 2

IS50-320H

127-209

2950

240

200

2 1/2 X 2

IS50-320H

113-188

2800

240

200

3 X 2 1/2

IS65-320H

159-290

3500

330

200

3 X 2 1/2

IS65-320H

108-201

2950

220

200

3 X 2 1/2

IS65-320H

97-181

2800

220

200

3 X 2 1/2

IS65-320H

104-158

2600

220

200

3 X 2 1/2

IS65-320H

88-133

2400

220

250

3 X 2 1/2

IS65-320H

157-290

3500

330

250

3 X 2 1/2

IS65-320H

107-201

2950

220

250

3 X 2 1/2

IS65-320H

97-181

2800

220

250

3 X 2 1/2

IS65-320H

102-155

2600

220

250

3 X 2 1/2

IS65-320H

85-131

2400

220

300

3 X 2 1/2

IS65-320H

155-289

3500

330

300

3 X 2 1/2

IS65-320H

107-201

2950

220

QWZU.EX16459 - Centrifugal Fire Pumps, End Suction

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/show...

300

3 X 2 1/2

IS65-320H

97-181

2800

220

300

3 X 2 1/2

IS65-320H

98-152

2600

220

300

3 X 2 1/2

IS65-320H

82-128

2400

220

300

4X3

IS80-320H

159-203

2950

220

300

4X3

IS80-320H

143-183

2800

220

400

4X3

IS80-260

105-139

2950

230

400

4X3

IS80-320H

158-203

2950

220

400

4X3

IS80-320H

142-183

2800

220

400

5x4

IS100-320H

123-158

2950

220

400

5x4

IS100-320H

110-142

2800

220

400

5x4

IS100-320H

98-172

2600

220

400

5x4

IS100-320H

83-147

2400

220

450

4X3

IS80-320H

157-203

2950

220

450

4X3

IS80-320H

140-182

2800

220

450

5x4

IS100-320H

122-158

2950

220

450

5x4

IS100-320H

110-142

2800

220

450

5x4

IS100-320H

98-172

2600

220

450

5x4

IS100-320H

83-147

2400

220

500

4X3

IS80-260

101-137

2950

230

500

4X3

IS80-320H

155-202

2950

220

500

4X3

IS80-320H

136-182

2800

220

500

5x4

IS100-320H

122-158

2950

220

500

5x4

IS100-320H

110-142

2800

220

500

5x4

IS100-320H

97-172

2600

220

500

5x4

IS100-320H

82-147

2400

220

750

5x4

IS100-320H

119-147

2950

220

750

5x4

IS100-320H

104-131

2800

220

750

5x4

IS100-320H

89-166

2600

220

750

5x4

IS100-260

113-139

2950

230

1000

5x4

IS100-260

104-131

2950

230

Last Updated on 2014-06-27


Questions?

Print this page

Terms of Use

Page Top
2014 UL LLC

When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment database for
additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's
Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for
the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any
manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent
to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: " 2014 UL LLC".

QYZS.EX3971 - Pump Controllers, Fire

Page 1 of 3

QYZS.EX3971
Pump Controllers, Fire
Page Bottom

Pump Controllers, Fire


See General Information for Pump Controllers, Fire
TORNATECH INC

EX3971

#132
7075 PLACE ROBERT-JONCAS
ST LAURENT, QC H4M 2Z2 CANADA
Fire Pump Controllers: Model AF, AFP, AFR, AFY, ATF, ATR, ATP or ATY followed by C or N, followed by additional suffixes. All of the above
controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:

Circuit Breaker

Max Short Circuit


Current RMS
Symmetrical Amps

Max V AC

MZMH6-63, -100,

208; 240

25000; 42,000

480

65,000

-160, -250
MZMH6-63, -100,
160, -250
The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the normal power source side is determined by the transfer switch as indicated below:
Max Controller Short Circuit
Withstand Rating

ASCO Transfer Switch


9403704

22KA, 480 VAC Max

94031004

22KA, 480 VAC Max

94032604

35KA, 480 VAC Max

The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.
Model AL or AL1 followed by additional suffixes.
All of the above controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:

Circuit Breaker

Max Short Circuit


Current RMS
Symmetrical Amps

Max V AC

NZM6B-63,

480

25,000

-100, -160
The controllers provided with automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the entire controller is determined by the transfer switch as indicated below:
ASCO Transfer Switch

Max Controller S. C. Withstand Rating

9403704

22KA, 480 VAC Max

94031004

22KA, 480 VAC Max

94032604

25KA, 480 VAC Max

The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.
Authorities having jurisdiction should be consulted in all cases.
Model FPD Series controller for engine-driven centrifugal fire pumps.
Models FPA, FPP, FPR, FPS, FPV, FPW, FPY, VPA, VPR, and VPS may be followed by additional suffixes. The withstand ratings are as follows:
Withstand Ratings of Controllers Without Transfer Switch:
Short Circuit Withstand Ratings
(Ampere Symmetrical)

file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QYZS.EX3971...

6/11/2014

QYZS.EX3971 - Pump Controllers, Fire

Page 2 of 3

VOLTAGE

OPTIONAL
HIGH

STANDARD

200 to 480 V

100,000A RMS

150,000A RMS

575 to 600 V

50,000A RMS

100,000A RMS

Model ATG or VPG. The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high fault
currents. The withstand rating of the normal power side is the same as the withstand ratings of controllers without transfer switches. The
withstand rating of the alternate power side is determined by the transfer switch as indicated by the following tables:
Withstand ratings of controllers with 120 A Tornatech Inc. Transfer Switch
200-208V
50/60 Hz

230-240V
50/60 Hz

380-416V
50/60 Hz

440-480V
50/60 Hz

600V
60Hz

MAX HP

MAX HP

MAX HP

MAX HP

MAX HP

Withstand
Rating (A)

40

40

65,000

60

75

25,000

100

18,000

Withstand Ratings For Controllers with Ascolectric Transfer Switches

Transfer
Switch
(A)

200-208V
50/60 Hz
Max HP

100

Withstand
Rating

230-240V
50/60 Hz
Max HP

Specific**
Withstand
Rating
(A)

Time
(Cycles)

(A)

30

30

10000

1.5

22000

150

50

50

1000

1.5

22000

400

150

150

35000

42000

600

N/A

N/A

50000

65000

**Tested and found suitable for 100kA


Withstand Ratings for Controllers with Ascolectric Transfer Switches, Continued

Transfer
Switch
(A)

Withstand Rating

600V
60 Hz
Max HP

Specific Withstand
Rating
(A)

Time
(Cycles)

(A)

100

75

10000

1.5

N/A

150

150

1000

1.5

N/A

400

400

22000

N/A

600

N/A

N/A

N/A

N/A

Model ATU:

Normal Power Side:

Same as withstand rating of controller without transfer switch.

Alternate Power Side:

Same as withstand rating of controller without transfer switch.

Model FPL, GPL:

Limited Service controllers with withstand ratings as follows:

Short Circuit Withstand Ratings of Limited Service Controllers Without Transfer Switches
VOLTAGE

OPTIONAL
HIGH

STANDARD

200 to 480 V

25,000 A RMS

65,000 A RMS

575 to 600 V

18,000 A RMS

25,000 A RMS

Model LTG, GLG:

Automatic transfer switch for connection to a generator set.

Model LTU, GLU:

Automatic transfer switch for connection to a 2

nd

utility.

Withstand ratings of Controller with transfer switch Model FPAT (Tornatech):


Model LTG:

Normal Power Side:

Same as withstand rating of controller without transfer switch.

Alternate Power Side:

Withstand rating only applies when the generator


set is protected by a molded case circuit breaker

TRANSFER SWITCH
AMPERES
120

200-480 V
H.P.
30

WITHSTAND RATING
AMPERES
25,000

file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QYZS.EX3971...

6/11/2014

QYZS.EX3971 - Pump Controllers, Fire

Page 3 of 3

TRANSFER SWITCH
AMPERES

600 V
H.P.

120

WITHSTAND RATING
AMPERES

30

Model LTU:

18,000

Normal Power Side:

Same as withstand rating of controller without transfer switch.

Alternate Power Side:

Same as withstand rating of controller without transfer switch.

Withstand ratings of controller with transfer switch Model 940 (Ascolectric):


Model LTG:

Normal Power Side:

Same as withstand rating of controller without transfer switch.

Alternate Power Side:

Withstand rating only applies when the generator set is protected


by a molded case circuit breaker not exceeding the ampere rating of
the transfer switch.

Transfer
Switch A

Withstand Rating

200-480 V
Max HP

120

30
Transfer
Switch A

Model LTU:

10,000

1.5

22,000

Withstand Rating

600 V
Max HP

120

Specific Withstand
Rating A

Time

30

Specific Withstand
Rating A

Time

10,000

1.5

N/A

Normal Power Side:

Same as withstand rating of controller without transfer switch.

Alternate Power Side:

Same as withstand rating of controller without transfer switch.

Models CPA, CPP, CPR, CPS, CPV, CPW, CPY, may be followed by additional suffixes. The withstand ratings are as follows:
Withstand ratings of controllers without transfer switch:
Short circuit withstand ratings (ampere symmetrical)
voltage

standard

optional

200 to 480 V

100 kA

150 kA

575 to 600 V

50 kA

100 kA

Model CPU - The controllers provided with automatic transfer switches are suitable for use on circuits capable of delivering high fault currents.
The withstand rating of the normal power side and the alternate power side is the same as the withstand ratings of controllers without transfer
switches.
Model CPU
Short circuit withstand rating for alternate power circuit with transfer switch (RMS
Symmetrical)
V

Standard

High
(optional)

200 to 480 V

100 kA

150 kA

575 to 600 V

50 kA

100 kA

Model GPD Series controller for engine-driven centrifugal fire pumps.


Battery chargers, BCE10, followed by 12 or 24, followed by 120 or 220.
Fire pump controllers, Models GPA, GPP, GPR, GPS, GPV, GPY and GPW.
Transfer switch, Model GPU.
Last Updated on 2013-01-03
Questions?

Print this page

Terms of Use

Page Top
2014 UL LLC

When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a nonmisleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: " 2014 UL LLC".

file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QYZS.EX3971...

6/11/2014

QXZF.EX5189 - Fire Pump Motors

Page 1 of 1

QXZF.EX5189
Fire Pump Motors
Page Bottom

Fire Pump Motors


See General Information for Fire Pump Motors
NIDEC MOTOR CORP

EX5189

8050 W FLORISSANT AVE


SAINT LOUIS, MO 63136-1414 USA

Poles

Number
of
Speeds

RPM

Phases

Ins
Class

Frame 182 thru


215 (v) (+)

15hp

190660

1.15

50

QXZF

Frame 250 thru


286 (v) (+)

7.5-60hp

190660

1.15

50

QXZF

Frame 320 thru


5012 (v) (+)

40500hp

190660

1.15

50

QXZF

Frame 56 thru
145 (v) (+)

3hp

190660

1.15

40

QXZF

Model
No.

Output

Volts

FL
Amps

Service
Factor

Prot.
Type

Rated
Ambient
(C)

CCN

(+) - Motors have also been evaluated as inverter duty (PRHJ) motors.
(v) - Voltage range details: 190, 200, 208, 230, 380, 400, 415, 460, 575, 660 or 208-230/460.
Trademark and/or Tradename: "Nidec Motor Corporation"
Last Updated on 2014-03-27
Questions?

Print this page

Terms of Use

Page Top
2014 UL LLC

When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a nonmisleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: " 2014 UL LLC".

file:///D:/BFE-PUMP/NM/PUMP%20SUBMITTAL/CERTIFICATES/QXZF.EX5189...

6/11/2014

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps

QYLU.EX6155
Internal-combustion Engines for Driving Stationary Fire Pumps
Page Bottom

Internal-combustion Engines for Driving Stationary Fire Pumps


See General Information for Internal-combustion Engines for Driving Stationary Fire Pumps
CLARKE U K LTD

EX6155

GRANGE WORKS
LOMOND RD
COATBRIDGE, ML5 2NN UNITED KINGDOM
DIESEL ENGINES RATED AT SPECIFIC SPEEDS

No. of
Cylinders

Model
JU4H-UF10

JU4H-UF12

JU4H-UF14

JU4H-UF20

JU4H-UF22

JU4H-UF24

JU4H-UF30

JU4H-UF32

JU4H-UF34

Rated
Speed
(rpm)

Rated
HP

41

1760

51

2100

55

2350

55

2350

59

2600

55

2350

59

2600

70

2800

71

3000

60

1760

67

2100

72

2350

72

2350

75

2600

72

2350

75

2600

80

2800

83

3000

64

1760

79

2100

85

2350

85

2350

85

2600

85

2350

85

2600

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

1/8

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps


4

104

2800

115

3000

63

1470

73

1760

73

1760

88

2100

98

2350

98

2350

99

2600

94

1760

105

2100

106

2350

106

2350

106

2600

79

1470

110

1760

130

2100

127

2350

127

2350

127

2600

122

2350

139

2600

145

2800

145

3000

79

1470

110

1760

DQ6H-UFKA4G

290

1760

DQ6H-UFKA48

240

1470

DQ6H-UFKA50

340

2100

DQ6H-UFKA60

345

1760

360

2100

DQ6H-UFKA88

375

1760

DQ6H-UFKA98

300

1470

410

1760

265

1760

280

2100

286

2350

DP6H-UFKA62

300

2350

JU6H-UFD0

110

1760

144

2100

148

2350

JU4H-UFH8

JU4H-UFH0

JU4H-UFH2

JU4H-UF40

JU4H-UF42

JU4H-UF50

JU4H-UF52

JU4H-UF54

JU4H-UF58

DP6H-UFKA50

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

2/8

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps


JU6H-UFD2

JU6H-UF30

JU6H-UF32

JU6H-UF34

JU6H-UFG8

JU6H-UFM8

JU6H-UFM0

JU6H-UFM2

JU6H-UF58

JU6H-UF50

JU6H-UF52

JU6H-UF54

JU6H-UF68

JU6H-UF60

JU6H-UF62

148

2350

148

2600

94

1470

140

1760

160

2100

160

2350

160

2350

160

2600

160

2350

160

2600

160

2800

175

3000

130

1470

149

1760

136

1470

175

1760

175

1760

207

2100

200

2350

200

2350

200

2600

138

1470

183

1760

138

1470

183

1760

210

2100

210

2350

210

2350

210

2600

210

2350

216

2600

216

2800

216

3000

175

1470

200

1760

175

1470

200

1760

240

2100

240

2350

240

2350

240

2600

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

3/8

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps


JU6H-UF84

243

2350

247

2600

259

2800

275

3000

JU6H-UFABL0

173

1760

JU6H-UFABL0

173

2100

JU6H-UFABL0

173

2350

JU6H-UFABL2

173

2350

JU6H-UFABL2

173

2600

JU6H-UFABL8

136

1470

JU6H-UFABL8

173

1760

JU6H-UFKARG

252

1760

JU6H-UFKAQ8

227

1760

JU6H-UFKAS0

260

2100

JU6H-UFKAPG

220

1470

JU6R-UFKAL7

170

1760

DP6H-UFKA88

290

1760

DQ6H-UFKA40

310

2100

DR8H-UFKA5G

450

1470

DR8H-UFKA68

495

1760

DR8H-UFKA62

497

1900

500

2100

500

2350

385

1470

460

1760

472

1900

490

2100

490

2350

10

522

1470

10

587

1760

10

600

1900

10

614

2100

10

606

2350

DT2H-UFKA58

12

700

1470

DT2H-UFKA50

12

800

1760

12

800

1900

12

800

2100

12

700

1760

12

700

2100

DP6H-UFKAX8

240

1470

JU6R-UFKARF

247

1760

DR8H-UFKA40

DS0H-UFKA68

DS0H-UFKA60

DT2H-UFKA20

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

4/8

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps


JU6R-UFKAPF

203

1470

JU6R-UFKAS9

252

2100

JU6H-UFKAQ8

227

1760

JU6R-UFKAQ7

222

1760

DR8H-UFKA92

596

2100

DR8H-UFKA98

556

1760

DS0H-UFKAM0

10

520

1760

DS0H-UFKAM0

10

530

2100

DS0H-UFKA92

10

722

2100

DS0H-UFKA98

10

650

1760

DT2H-UFKA88

12

875

1760

DIESEL ENGINES RATED FOR USE WITHIN SPEED RANGES


Minimum
No. of
Cylinders

Model
JU4H-UF10

Rated
Speed
(rpm)

Maximum
Rated
HP

Rated
Speed
(rpm)

Rated
HP

1760

41

2100

51

2100

51

2350

55

JU4H-UF12

2350

55

2600

59

JU4H-UF14

2350

55

2600

59

2600

59

2800

70

2800

70

3000

71

1760

60

2100

67

2100

67

2350

72

JU4H-UF22

2350

72

2600

75

JU4H-UF24

2350

72

2600

75

2600

75

2800

80

2800

80

3000

83

1760

64

2100

79

2100

79

2350

85

JU4H-UF32

2350

85

2600

85

JU4H-UF34

2350

85

2600

85

2600

85

2800

104

2800

104

3000

115

JU4H-UFH8

1470

63

1760

73

JU4H-UFH0

1760

73

2100

88

2100

88

2350

98

JU4H-UFH2

2350

98

2600

99

JU4H-UF40

1760

94

2100

105

2100

105

2350

106

2350

106

2600

106

1760

110

2100

130

JU4H-UF20

JU4H-UF30

JU4H-UF42

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

5/8

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps


JU4H-UF58

1470

79

1760

110

JU4H-UF50

1470

79

1760

110

1760

110

2100

130

2100

130

2350

127

JU4H-UF52

2350

127

2600

127

JU4H-UF54

2350

122

2600

139

2600

139

2800

145

2800

145

3000

145

DQ6H-UFKA60

1760

345

2100

360

DQ6H-UFKA98

1470

300

1760

410

DP6H-UFKA50

1760

265

2100

280

2100

280

2350

286

1760

110

2100

144

2100

144

2350

148

JU6H-UFD2

2350

148

2600

148

JU6H-UF30

1470

94

1760

140

1760

140

2100

160

2100

160

2350

160

JU6H-UF32

2350

160

2600

160

JU6H-UF34

2350

160

2600

160

2800

160

3000

175

JU6H-UFG8

1470

130

1760

149

JU6H-UFM8

1470

136

1760

175

JU6H-UFM0

1760

175

2100

207

2100

207

2350

200

JU6H-UFM2

2350

200

2600

200

JU6H-UF58

1470

138

1760

183

JU6H-UF50

1470

138

1760

183

1760

183

2100

210

2100

210

2350

210

JU6H-UF52

2350

210

2600

210

JU6H-UF54

2350

210

2600

216

2800

216

3000

216

JU6H-UF68

1470

175

1760

200

JU6H-UF60

1470

175

1760

200

1760

200

2100

240

2100

240

2350

240

JU6H-UF62

2350

240

2600

240

JU6H-UF84

2350

243

2600

247

2800

259

3000

275

1470

136

1760

173

JU6H-UFD0

JU6H-UFABL8

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

6/8

10/1/2014

QYLU.EX6155 - Internal-combustion Engines for Driving Stationary Fire Pumps


JU6H-UFABL0

1760

173

2350

173

JU6H-UFABL2

2350

173

2600

173

JU6R-UFKAD9

1760

107

2100

139

2100

139

2350

141

JU6R-UFKAD1

2350

141

2600

139

JU6R-UFKA29

1470

92

1760

137

1760

137

2100

155

2100

155

2350

153

JU6R-UFKA31

2350

153

2600

151

JU6R-UFKA33

2800

148

2960

146

2960

146

3000

161

JU6R-UFKAG7

1470

128

1760

146

JU6R-UFKAL9

1760

170

2100

168

2100

168

2350

166

JU6R-UFKAL1

2350

166

2600

164

JU6R-UFKAM7

1470

134

1760

172

JU6R-UFKAM9

1760

172

2100

202

2100

202

2350

193

JU6R-UFKAM1

2350

193

2600

191

JU6R-UFKA57

1470

136

1760

180

JU6R-UFKA49

1760

180

2100

205

2100

205

2350

200

JU6R-UFKA51

2350

200

2600

201

JU6R-UFKA53

2800

204

2960

202

2960

202

3000

202

10

1760

542

1900

575

10

1900

575

2100

575

DP6H-UFKA70

2100

312

2350

316

JU6R-UFKA67

1470

170

1760

195

JU6R-UFKA59

1760

195

2100

232

2100

232

2350

228

JU6R-UFKA61

2350

228

2600

226

JU6R-UFKA83

2800

239

3000

260

DS0H-UFKAN0

Last Updated on 2014-07-30


Questions?

Print this page

Terms of Use

Page Top
2014 UL LLC

When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYLU.EX6155&ccnshorttitle=Internal-combustion+Engines+for+

7/8

Vendor Ref. No.

BFE-2218

Doc. Seq. No.

18

Revision No.

Vendor Doc. No.

BFE-CO/PRO
Contractor Name:

M/S. LAZOURDY CONTRACTING AND GENERAL MAINTENANCE


Project Name:

REHABILITATION WORKS FOR THE THEATER AT AL FATEH SCHOOL

SEQ.
A.

ITEM DESCRIPTION
DIESEL FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Diesel engine CLARKE model JU4H-UF24, 83HP, at 3000RPM, dual
lead acid batteries, muffler.
2.
Automatic diesel pump controller arranged for 12V.
3.
Accessories:

QTY
1

SUPPLIER COMPANY PROFILE


Suction and discharge gauge

A1.

B.

MAIN ACCESSORIES
a. Fuel system and direct reading fuel gauge
b. Fuel meter GERAND venture type model K-500-6" Grooved ends
ELECTRIC FIRE PUMP
Q = 500 GPM H=7 BAR
BRISTOL pump model IS 80/260 horizontal end suction, complete with:
1 . Electric motor 60 HP at 2950 RPM, ODP enclosure 50C ambient,
Class F insulation, 1.15 service factor, 3/50/415 V, Y-Delta starting
2.
3.

C.

fghgh

Automatic electric pump controller, suitable for 60 HP, Y-Delta


Accessories:
Suction and discharge gauge
Casing relief valve 1/2"

JOCKEY PUMP
Q = 15 GPM H=7 BAR
BRISTOL / RV pump model RV4-8 complete with:
1 . Electric motor 2 HP at 2950 RPM, 3/50/415 V, TEFC enclosure.
2.
Automatic jockey pump controller, suitable for 2HP

1
1
1

2
1
1

Fire Pumps

Bristol: A History & Future.


In 1971, seven emirates joined forces to create the United Arab Emirates, with the goal of becoming a growing leader on an international
scale. The UAEs focus has always been the safety of its land and people, BRISTOL was established in support of that same vision.
BRISTOL FIRE ENGINEERING, part of the Concorde Corodex Group, is the leading fire-fighting and fire protection nmanufacturer in the
Middle East and has been unsurpassed in innovative fire-fighting solutions for more than 44 years.
We have been steadfast in our developments and have grown to become pioneers in the industry for unmatched quality and dependability,
longstanding commitment and unwavering dedication.
Our headquarters and manufacturing facility started in the UAEs Emirate of Dubai, producing world-class fire-fighting systems and equipment
in cooperation with international know-how and technology with a grand vision to expand globally.
We strive to continue to adopt the highest international and national standards in line with the UAEs goal to become the safest country in the
world.
BRISTOL was one of the first fire-fighting companies in the Middle East to receive an ISO 9001 certification, placing great emphasis on
achieving local and international approvals on product certifications such as Kite Mark, LPBC, UL listing, and FM approval. Moreover, Bristol
is certified to of ISO 14001 and OHSAS 18001.
We focus on innovation by means of continual research and development of advanced fire-fighting solutions, ensuring we not only meet, but
exceed the demands of our rapidly changing market.
For decades, we have been proudly supplying various government entities and sectors such as the oil and gas, commercial, and industrial
industries across the globe with world-class equipment and services.
BRISTOL has been serving Middle Eastern, African, Asian, and European markets for more than three decades with a vision to expand further.
Paving the road towards safety for more than four decades, and counting: BRISTOL.

Вам также может понравиться