Вы находитесь на странице: 1из 15

Plumbing Calculation

Rev-01

Water Supply Calculation Sheet

Project Title
Building Owner
Project Location
Project City
Project Co`
Client Name
Company Name
Company Phone
Company E-mail
Company P.O.Box
Date of Project
Project Description
Code Reference
Approving Agency
Designed by
Buliding Lowest Level
Building Highest Level
Roof and SiteTotal Area
Storage for Rain Water
Storage for Septic tank
Number of Typical Floors
Comment

:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:

El- Thani Tower


Shekh Abd. EL Aziz el Thany
EL - Dafna
Doha
Qatar
Shekh Abd. EL Aziz el Thany
Gulf Consulting Group
00974 - 4364455
gcgqatar@qatar.net.qa
8387
###
2B + G + 22 Resdintinal and Commerical Building
International Plumping Code
Qatar Palaning
Eng. Ahmed M. Sami
0
m
135
m
7135
m2
2
Days
3
Days
16
Floor

Prepared By
Gulf Consulting Group
Eng. Ahmed M. Sami
###

Plumbing Calculation
Rev-01

1- Building specification :
so get total building height (static head)

135

288
2
576
180
103.68

Bed room
Person
Person
L/day
m3

2- For residential :
No. of bed room in the building :
No. of person in the room :
No of person
Assume daily water consumption in L/s/person
Then the total water consumption of building

3- For commercial center:daily water consumption = total area of all commercial floors / 10 m2 per person
* daily water consumption per person
Assumption daily consumption per person in liter/day
70
Liter/Day/Person
m2
Area of total commercial floors
8180
m3
Daily water consumption
57.26

4- For Office Building 8 Hour Shift :NO. of Person


assume daily water consumption in L/s/person
Daily water consumption

0
60
0

Person
L/day
m3

0
60
0

Person
L/day
m3

0
170
0

room
L/room
m3

5-For Factories 7 Hour Shift :NO. of Person


assume daily water consumption in L/s/person
Daily water consumption

6-For Hotels up to 3 Stars :NO. of room


Assume daily water consumption in L/room
Daily water consumption

7-For Hotels up to 4 Stars With All Services :NO. of rooms


Assume daily water consumption in L/room
Daily water consumption

0
700
0

room
L/room
m3

8-For Hotels up to 5 Stars With All Services :NO. of rooms


Assume daily water consumption in L/room
Daily water consumption

0
1200
0

room
L/room
m3

0
30
0

car
L/car
m3

0
1
30
0

Person
meal
L/meal
m3

9-For Car Parking :NO. of cars


Assume daily water consumption in L/car
Daily water consumption

10-For Restaurant and Cafes Per Meal :NO. of Person


Assumed no. of meal per person
Assume daily water consumption in L/s/meal
Daily water consumption

11-For Laundry in Hotels Per Bed :NO. of Bed


Assume daily water consumption in L/bed
Daily water consumption

0
130
0

Bed
L/bed
m3

0
600
0

Bed
L/bed
m3

0
75
0

Student
L/student/day
m3

0
20
0

Passenger
L/passenger/day
m3

0
10
0

Person
L/person/day
m3

0
50
0

Person
L/person/day
m3

0
75
0

Person
L/person/day
m3

0
40
0

Person
L/person/day
m3

0
30
0

Person
L/person/day
m3

0
120
0

Unit
L/toilet
m3

12-For Laundry in Hospital Per Bed :NO. of Bed


Assume daily water consumption in L/bed
Daily water consumption

13-For School :NO. of Student


Assume daily water consumption in L/student
Daily water consumption

14-For Airport :NO. of Passenger Per Day


Assume daily water consumption in L/passenger
Daily water consumption

15-For Meeting Area :NO. of person


Assume daily water consumption in L/person
Daily water consumption

16-For Public Building :NO. of person


Assume daily water consumption in L/person
Daily water consumption

17-For Camps :NO. of person


Assume daily water consumption in L/person
Daily water consumption

18-For Swimming Pools & Shore :NO. of person


Assume daily water consumption in L/person
Daily water consumption

19-For Mosque :NO. of person


Assume daily water consumption in L/person
Daily water consumption

20-For Public Toilet Per Unit :NO. of toilet Unit


Assume daily water consumption in L/toilet
Daily water consumption

21-For Public Urinal :NO. of urinal


Assume daily water consumption in L/urinal
Daily water consumption

0
40
0

urinal
L/urinal
m3

0
60
0

Lavatory
L/lavatory
m3

0
560
0

Lavatory
L/shower
m3

0
400
0

Caw
L/caw
m3

22-For Public Lavatory :NO. of Lavatory


Assume daily water consumption in L/Lavatory
Daily water consumption

23-For Public Shower :NO. of showers


Assume daily water consumption in L/shower
Daily water consumption

24-For Public Slaughterhouse :NO. of Caw


Assume daily water consumption in L/caw
Daily water consumption

25-For Commercial Laundry Per Kg of Clothes :NO. of Kg


Assume daily water consumption in L/kg
Daily water consumption

0
35
0

kg
L/kg
m3

0
0
0
0
0
0
0
0
0

caw
calf
goat & sheep
horses
Chicken
Chicken
duck
Camel
m3

26-For Farms :No. of Caws


No. of Calf
No. of goats & sheep
No. of horses
No. of egg Chicken
No. of turkey Chicken
No. of ducks
No. of camel
Daily water consumption

27- Irrigation water consumption calculations


water consumption for irrigation changed according to kind of planters exists
Unit
no. of palm trees
2
Unit
no. of spreading
5
Unit
no of evergreen
9
m2
area of grass
5
m3
get daily water consumption for irrigation
0.56

OR
Insert Total Green Area for The Building
Assume 1 cm of water per 1 m2
Daily water consumption

100

m2

m3

Daily Domestic Water Consumption :water consumption per day for the building

162

m3

Daily Irrigation Water Consumption:water consumption per day for the building

m3

Total Daily Water Consumption For the Building :total consumption of water per day
163
muliplay the water consumption in 10% safety f 179

m3
m3

Total Rain Water Holding Tank


Rain water per 1 day
Rain water storage capacity

143 m3
2 days

Under Ground or Ground Water Tank


359

m3

the storage will be for 1 day

179

m3

Rain Water Holding Tank


the storage will be fo2 day

286

m3

458

m3

the storage capacity for 2 days

Roof Water Tank Capacity

Septic Tank
the storage will be fo3

day

Table of total fixtures

ENTER NO. OF UNIT ACCORDING TO FIXTURE TYPE PRIVATE OR PUBLIC

Fixture type :

private

FIXTURES / POINT NO.


Water closet (flush valve)
Water closet (flush tank)
Water Bidet
Hose for W.C
Lavatory (& H.B.)
Kitchen sink
Service sink office,ect
Shower
Bath tub
Dishwashing machine
Laundry 8 Ib
Laundry 16 Ib
Ablution (Public)
Urinal (1" flush valve)
Urinal (3/4" flush valve)
Urinal (flush tank)
Drinking fountain 3/8 in
SUM
Fixture type :

Total
fixtures

B3

B2

B1

G.F.

F.F

2nd.F

3rd F

4th F.

5th F

6th F

TYP. F

1
0
0
0
0
0
0
1
0
0
6
0
0
0
0
0
0

1
0
1
1
0
1
0
1
0
0
0
1
0
0
1
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0

26

10
6
10
10

426
0
257
1
416
257
0
170
96
160
166
1
0
0
1
0
0
1951

B3

B2

B1

G.F.

F.F

2nd.F

3rd F

4th F.

5th F

6th F

TYP. F

Total
fixtures

1
1
1
1
1
1
1

0
0
0
3
0
0
0

0
0
0
0
0
3
3

0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0
0
0
0
0

1
1
1
4
1
4
4

16
26
16

public

FIXTURES / POINT NO.


Water closet (flush valve)
Water closet (flush tank)
Water Bidet
Hose for W.C
Lavatory (& H.B.)
Kitchen sink
Service sink office,ect

Shower
Bath tub

1
1

0
3

0
0

3
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

4
4

Dishwashing machine
Laundry 8 Ib
Laundry 16 Ib
Ablution (Public)
Urinal (1" flush valve)
Urinal (3/4" flush valve)
Urinal (flush tank)
Drinking fountain 3/8 in
SUM

1
1
1
1
1
1
1
1

0
0
0
3
0
0
2
0

0
0
0
0
0
0
2
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

1
1
1
4
1
1
5
1
39

1 Pump will Calculated according to the type of project


2
3 Put ( X ) Beside The Type of Project
4
5
Appartemen x
Hotels & Club
Hospital
6
7
School
Office
Industerial
8
9 Put ( X ) Beside The Type of Heater Used
10
Don`t Mark 2 Point
11
Individual Heaters
12
13
x
Centeral Heater
14
15 Total length of water pipe for lift pump from ground to roof water tank 176 m
30 No. of Lift Pump To be Used
=
3
Duty +
1
StandBy
31 No. of Boster Pump To be Used =
5
Duty +
1
StandBy
32
33 Lift Pump Selection
34
Pump Flow
160 GPM
35
Pump Head
283 PSI
36
Pump HP
45 HP
37
No. of Pumps
3 Duty + 1
StandBy
38
39 Boster Pump Selection
43
Pump Flow
81 GPM
44
Pump Head
35 PSI
45
Pump HP
3 HP
46
No. of Pumps
5 Duty +
1 StandBy
47
48 Pressure Vessel
49
Volume of Vessel
568 Liters
50
51

Filter will Calculated According to it's Location :Put ( X ) Beside The Type of Project
Ground Floor

Roof Floor

No. of Filters Will be used


=
Enter Total Length of Pipe From Main Tank To Filteration=
Level Difference From Ground Tamk To Filteration Tank =
Enter Total Volume of Receving Water tank
=
No. of Pumps Will Be Used
=

g
3
10
2
40
2

Filter Selection
Filter Capacity
Filter Working Pressure
No. of Filters
Maximum Losses in Filter
Filteration Pump Capcity
Filteration Pump Head

58
22
3
15
88
26.4

GPM
Psi
Unit
Psi
GPM
Psi

No.
m
m
m3
Duty +

StandBy

Irrigation Pump Selection


Put ( X ) Beside The Type of Irrigation
Manual Syste

Automatic system

Insert No. of Irrigation Pump Will be Used


Enter Total Time to Finish Manual Irrigation
=
Enter Difference in Head Between Pump & Irrigation Line
Enter Total Lengh Of Irrigation Pipe
=

1
3
0.3
80

Irrigation Pump Selection :Pump Capacity


Pump Head
Pump HP
Pumps
Pressure vesel

1.5
GPM
50
Psi
0.08
HP
1 Duty, 1 StandBy
85
Liters

Watting For Automatic System Calculation

Duty
Hours
m
m

StandBy

Individual Water Heater Selection For Each Bath :Calculation Will be According to Type of The Building & Fixture Unit Methods:PUT ( X ) Beside Your Type of The Place:Appartement House

Hospital

Industerial

Club

Hotels

Office Building

Private residence

School

YMCA

GYM
Fixture

QTY

Demand Total Gallon/Hr

0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

private lav.
public lav.
bathtub
dishwasher
foot basin
kitchen sink
laundry
pantry sink
shower
service sink
hydrotherapentic shower
hubbard bath
leg bath
arm bath
sitz bath
continuous flow bath
circular wash sink
semicircular wash sink

2
6
20
100
3
20
28
10
75
20
400
600
100
35
30
165
20
10

Water Heater Selection :Heater Storage Capacity


Heater Power

=
=

80
2

Liters
KW

0
6
20
100
3
0
0
0
0
0
0
0
0
0
0
0
0
0

Sump Pit will size according to The Drainage of Fixture Unit in


1st & 2nd Basement + The Drainage from Kitchen + Drainage of Laundries
No. of Laundry in Basement
No. of Person Will Served by Restaurant
No. of Cars In Basement
Time Required to Empty the Sum pit
Sum pit Depth
Difference from low level and high level
Total length for Pressure pipe

=
=
=
=
=
=
=

10
200
100
10
2
7
10

Unit
Person
Car
min
m
m
m

Submersible Pump & Sump Pit Capacity


Sump Pit Volume
Sump Pit Dimension
Submersible Pump Capacity
Submersible Pump Head
Submersible Pump HP

= 1.3 m3
= 0.8 m X 0.8 m X
= 2.2
Litters / Sec
= 15 m
= 1 HP

2 m

Individual Water Heater Selection For Each Bath :Calculation Will be According to Type of The Building & Fixture Unit Methods:PUT ( X ) Beside Your Type of The Place:Appartement Hou

Hospital

Industerial

Club

Hotels

Office Building

Private residence

School

YMCA

GYM
PUT ( X ) Beside Your Type of The Pipe:Insulated Pipes

Non-Insulated Pipes

PUT ( X ) Beside Your Type of The Pipe:Sch-40

Fixture
private lav.
public lav.
bathtub
dishwasher
foot basin
kitchen sink
laundry
pantry sink
shower
service sink
hydrotherapentic shower
hubbard bath
leg bath
arm bath
sitz bath
continuous flow bath
circular wash sink
semicircular wash sink

Brass
Copper

K-Copper

QTY

Demand

Total Gallon/Hr

90
15
30
10
20
60
15
20
30
2
0
0
0
0
0
0
0
0

2
4
20
15
3
10
20
5
30
20
0
0
0
0
0
0
0
0

180
60
600
150
60
600
300
100
900
40
0
0
0
0
0
0
0
0
2990

0.3

DEMAND FACTOR

897
897

Probable Maximum Demand


Heater or coil Capacity

1.25

STORAGE CAPACITY Factor

1121.25

Storage Tank Capacity GALLO

Insert Pipe Length For Supply Network as We Don`t Know the Return Pipe Size
Pipe Diameter
Length of 1/2 " pipe
Length of 3/4 " pipe

Length in meter

Q loss

400
120

14000
5160

Length of 1 " pipe


Length of 1-1/4 " pipe
Length of 1-1/2 " pipe
Length of 2 " pipe
Length of 2-1/2 " pipe
Length of 3 " pipe
Length of 4 " pipe
Length of 5" pipe
Length of 6 " pipe
Length of 8 " pipe

300
232
132
120
105
100
100
100
130
150

Total Heat loss From Supply Pipes

15900
15080
9636
10920
11340
12900
16300
19900
30290
44850
206276

Total Farther Pipe length Supply & Return

= 120 m

Conclusion for Centeral Water System


Heat or coil Capacity
Storage Tank Capacity

897 Gallon / Hour


1121.3 Gallon

Circulation Pump Selection : Pump Flow


Pump Head
Pump HP

35