Академический Документы
Профессиональный Документы
Культура Документы
Bus 3
j0.5
j0.25
j0.2
j0.2
j0.4
Bus 2
j0.2
j0.5
Eg1
-
j0.25
j0.2
~-E
j0.4
g3
Ground
Positive sequence diagram of the sample system
j0.2
j0.5
j0.2
j0.25
j0.4
Ground
Negative sequence diagram of the sample system
j0.04
j1.0
0(X)
j0.4
3*j0.02
j0.08
j0.8
0(Y)
0(W)
0(Z)
Zero sequence diagram of the sample system
Note: Alphabets W, X, Y and Z in parentheses after bus no. 0 (representing ground) are
just for indicative purposes to illustrate the computation for elements of YBus.
Inspection method is used to obtain YBus for the sequence network diagram in question.
1
1
1
Y11 y 12 y 10(W ) y 10(X )
j13.5
j0.4 (j0.04 3* j0.02) j1.0
1
1
1
Y22 y 12 y 20(Y)
Y j 2.5 3.75
0
0
0
12.5
0
0.0845 0.0536
1
0
0
ZBus YBus j 0.0563 0.3042
0
0
0
0.08
On similar lines:
0
Bus
1
Bus
2
Bus
Problem#2
G1
T1
T2
M1
~
~
M2
20 kV base
G1
T2
T1
(20:230 kV)
230 kV base
(220:13.2 kV)
13.8 kV base
M1
~
~
M2
Zpu,new Zpu,old
V
V
LL base,old
LL base,new
S3base,new
S3base,old
For T1:
Zpu,new 0.10
300
0.857
350
For T2:
13.2 0.0915
Zpu,new 0.1
2
13.8
2
V32base(LL)
S3base
230 kV
300 MVA
176.3
ZTr.line 0.5 64 32
ZTr.line(pu)
32
0.1815
176.3
For M1:
For M2:
ZT1
ZLine
j0.0857
ZG1
j0.1815
j0.2
ZT2
j0.0915
j0.2745 ZM1
EG1
-
j0.5490
ZM2
M2
~-E ~-E
M1
M2
Reference
Positive sequence diagram of the sample system
Note that the negative sequence reactances of the system are equal to the positive
sequence reactances. Hence the negative sequence reactance diagram is identical to the
positive sequence diagram except that all the voltage sources are de-energized.
Per unit globalization for zero sequence network:
The zero sequence reactance of the transformers is equal to the positive sequence
reactance.
For T1:
300
Zpu,new 0.10
0.857
350
For T2:
13.2 0.0915
Zpu,new 0.1
2
13.8
2
For M2:
20
1.333
300
Motor circuit base impedance:
Zbase
13.8
Zbase
0.635
300
In the zero sequence impedance diagram for the generator:
0.4
3Zn 3
0.9 pu
1.333
In the zero sequence impedance diagram for the motor M1:
0.4
3Zn 3
1.89 pu
0.635
For the transmission line zero sequence impedance:
ZTr.line 1.5 64 96
ZTr.line(pu)
96
0.5445
176.3
ZT1
j0.0857
ZLine
j0.5445
ZT2
j0.0915
j0.05 ZG1
ZM1
j0.686
3Zn(M1)
j0.9 3Zn(G1)
j1.890
Reference
Zero sequence diagram of the sample system
Elements of the zero sequence bus admittance matrix:
1
(j0.05 j0.9)
1
Y22 y 20
(j0.686 j1.89)
Y12 y 12 Y21 0
Y11 y 10
ZM2
M2
j1.372
Note: See what happens to the structure of the zero sequence diagram of the sample system if bus 1 is
moved after the secondary of T1 in the given single line diagram! The cross-check for the zero sequence
impedance matrix in the exercise was accidentally given for a different arrangement of buses. This goes on
to show that the arrangement of buses (i.e., is a transformer indicated in the single line diagram as
connected between two unique buses? Or, if there is only one bus shown near a transformer, where is this
bus located on the primary side or on the secondary side?) DOES matter in how the zero sequence
impedance diagram is obtained, thus affecting the zero sequence impedance matrix.
Solution to the above quirk: Always represent a transformer as being connected between two unique
buses. (Create a dummy bus if needed!)
For example:
ZT1
j0.0857
ZLine
j0.5445
ZT2
j0.0915
j0.05 ZG1
ZM1
j0.686
3Zn(M1)
j0.9 3Zn(G1)
j1.890
Reference
Elements of the YBus for the above Zero Sequence Network representation:
1
1
Y11 y 12 y 10
j0.5445 j0.0857
1
1
Y22 y 12 y 20
j0.5445 j0.0915
ZM2
M2
j1.372