Вы находитесь на странице: 1из 8

Electrical Power and Energy Systems 73 (2015) 192199

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Application of GaborWigner transform to inspect high-impedance


fault-generated signals
Jiang-Yong Cheng a, Shyh-Jier Huang a,, Cheng-Tao Hsieh b
a
b

Department of Electrical Engineering, National Cheng Kung University, Tainan 70101, Taiwan
Department of Electrical Engineering, Kun Shan University, Tainan 70101, Taiwan

a r t i c l e

i n f o

Article history:
Received 28 June 2014
Received in revised form 4 May 2015
Accepted 5 May 2015
Available online 19 May 2015
Keywords:
GaborWigner transform
High-impedance faults
Cross-terms

a b s t r a c t
The GaborWigner transform was adopted in this study to explore the electric signals generated by
high-impedance faults (HIFs). This method excels at detecting non-stationary signals and featuring high
resolutions, while the effects of cross-term problem of Wigner distribution can be meanwhile decreased.
To conrm the feasibility of this method, the approach was tested under different scenarios with comparisons to practical waveforms. Test results support the practicality of the method for the inspection of
high-impedance fault-generated signals.
2015 Elsevier Ltd. All rights reserved.

Introduction
High-impedance faults often occur when an overhead ground
wire is broken and falls to a ground with high resistance, such as
a tar road, cement oor, grass, or sand. When this fault occurs,
the magnitude of current is low because impedances of some
grounds are very high. Therefore, it may not be easy to detect such
faults solely by using traditional protection devices. Worst of all, an
electric wire falling on a high-impedance fault may produce arcs,
endangering the personal safety and causing property damages
[15]. From perspectives of public safety and operational reliability, an effective detection of high-impedance faults serves as a very
important topic to study.
In the last decades, several researches have been devoted to this
fault detection study. Some studies were focused on adjusting the
over-current protection devices [6]. Yet, if the device was not
carefully designed, errors may occur due to the short of
signal-discrimination capability. A grounding relay was applied
to detect; however, under an extremely unbalanced load or multiple grounding contacts, a sufcient reliability was hard to reach
[7]. Based on the second-order [8], the third-order [9,10], and the
high-frequency harmonics current [11], the changes in harmonic
currents of feeders were closely tracked, anticipating the features
of high-impedance fault would be better comprehended.
Subsequently, signal processing methods including Kalman lters
[12], articial neural networks (ANNs) [13,14], and decision trees
Corresponding author. Tel.: +886 6 2757575x32506; fax: +886 6 234 5482.
E-mail address: clhuang@mail.ncku.edu.tw (S.-J. Huang).
http://dx.doi.org/10.1016/j.ijepes.2015.05.010
0142-0615/ 2015 Elsevier Ltd. All rights reserved.

[15] were also proposed. Among these methods, although the


Kalman lter was applied in the inspection of non-stationary signals, it came with the demerits of requiring great amounts of computation and additional efforts for accuracy of parameters. As for
the application of ANNs, it needs to build complex non-linear systems by learning examples. If the number of samples was insufcient or training procedures were inappropriate, the probability
of detection will be highly affected. It is worth mentioning that
most signal-processing approaches utilized the Fourier transform
as the analysis basis; however, by transforming all the information
in time domain to frequency domain, relationships between time
and frequency were found difcult to grasp, hence causing the difculty of visualizing event dynamics. By automatically adjusting
the window function to adapt to the required resolution, the wavelet transform was emerged, by which both time and frequency
information were simultaneously presented [1619]; yet an inappropriate selection of the mother wavelet may still affect the computation performance.
In this study, a GaborWigner transform (GWT) is proposed to
detect high-impedance faults. This method is expected to integrate
the merits of Gabor transform (GT) with Wigner distribution such
that the fault-detection performance can be signicantly
enhanced. On one hand, the Wigner distribution was witnessed
to own the characteristics of higher timefrequency resolution
and energy concentration, but on the other hand, its cross-terms
problem may hinder a further development. Although the
Gaussian-like window function of Gabor transform was proved
suitable for analyzing non-stationary signals [20], it came with a
limited degree of resolution. Therefore, by combining the merits

193

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

of these two methods as a whole, the method suggested in this


study will not only solve the cross-term problem, but also exhibit
the advantage of higher resolution for the visualization of events.
Features of this method include the following:

effectiveness of Gabor transform, hence motivating the inclusion of


Wigner distribution proposed in this study.

(1) The proposed method is very simple in concept and easy to


implement. It is capable of zooming in the area of interest for
a clearer visualization.
(2) With the increasing concern of power system faults, the proposed method can be extended as a useful tool in addition to
existing approaches.
(3) The method is benecial to analyze any non-stationary signals, presenting a high potential of inspecting other
disturbances.

The Wigner distribution depicts the energy density of a signal in


the timefrequency plane. In the calculation process, the
time-domain signal f(t) is used twice, which is also called bilinear
analysis. Since the Wigner distribution comes with a higher time
frequency resolution and energy concentration, it is often used in
engineering applications which is dened as

The organization of this paper is made as follows:


Section Proposed method introduces the proposed method, Secti
on Detecting process shows the detection process, Section Test
results provides the test results, and Section Conclusion presents
a conclusion.

x1t + cos2 x2t will bring the auto terms of cos2 x1t and cos2 x2t
along with the cross terms of cos(x1 + x2)t + cos(x1  x2)t, yet
the frequency of x1 + x2 and x1  x2 is away from that of the

The Wigner distribution

WDt; x


s   s
f t f t  ejxs ds
2
2
1
1

For example, after the employment of (3), a signal of f(t) = cos2

Proposed method

The GaborWigner transform

Among several timefrequency analysis approaches, the


short-time Fourier transform is one of the most used tools to investigate the non-stationary signals. The most signicant difference
between the short-time Fourier transform and the Fourier transform is the use of windows function w(s) in limited time. By moving the windows function on the time axis and spectrogram of the
Fourier transform, the timefrequency analysis of the signal may
be comprehended. The short-time Fourier transform is dened as

wsf t sejxs ds

1

where t is a sliding variable of time, x is the frequency, s is the signal function in the time-domain, and w(s) is the window function.
The Gabor transform (GT) can be seen as a type of short-time
Fourier transform, which replaces the window function with
Gaussian function as shown below

GTt; x

r Z
1
1
gsf t sejxs ds
2p 1

GWTt; x GT A t; xWDB t; x

Frequency (Hz)

where A and B are constants. When the prime number of the GT is


greater than that of the Wigner distribution, the GWT is inclined to
the GT. When the prime number of the GT is lower than that of the
Wigner distribution, the GWT is inclined toward the Wigner distribution. Thus, it is necessary to select an appropriate prime number
for the GT and the Wigner distribution. Based on the suggestions,
this study set the values of A and B at 2.6 and 0.6 [21].
Through the employment of this approach, the study made simulations on various signals to verify its applicability and reliability.
First, three types of signals were used to verify the resolution of
timefrequency analysis: Example 1 is focused on real signals;
Example 2 on complex signals; and Example 3 on multiple complex signals. This is followed by the application of GWT to analyze
signals of high-impedance faults by comparing analysis results
between the GT and the Wigner distribution.
Example 1 (Real signals). This test focuses on real signals. The
equation is assumed as follows:

f t cos6t  0:05t 2

Fig. 1(ac) individually shows the results of GT, Wigner distribution,


and GWT. The horizontal axis represents time and the vertical axis

Frequency (Hz)

where g(s) is the Gaussian function and the duration of g(t) window is
2T along with T = 1/60 [s]. This Gabor transform detects the time and
frequency of a non-stationary signal simultaneously, yet its analyzing
performance is easily affected by the window width. A narrow window may hinder from the sufcient resolution to distinguish those
signals with similar frequencies, while a wide window may cause
the difculty of immunity from neighboring high-frequency disturbances [21,22]. Special attentions are suggested to ensure the

In view of GT short of clarity along with Wigner distribution of a


cross terms problem, an approach combining these two transforms
but without these demerits have been proposed [21], in which the
method is called GaborWigner transform (GWT) with the expression made below:

Frequency (Hz)

The Gabor transform

STFTt; x

original signal. In other words, the nuisance of cross terms formed


during the calculation of Wigner distribution, possibly leading to
the insufcient signal discernment.

Time (s)

Time (s)

Time (s)

(a)

(b)

(c)

Fig. 1. The timefrequency spectrum of real signals. (a) GT. (b) Wigner distribution. (c) GWT.

194

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

Example 2 (Complex signals). This example uses a complex signal.


It is dened as

f t ej0:15t

Fig. 3(ac) shows the results by using GT, Wigner distribution and
GWT, where the horizontal axis represents the time and the vertical
axis represents the frequency. Calculated values are displayed by
various shades of colors, where the lighter color is for a larger value
and the deeper color for a smaller one. From this example, the
results of GT does not have cross terms problem, but the resolution
is seen to be the lowest. The Wigner distribution has a higher resolution, yet its cross terms lead to an unexpected line draw. Only the
plot of Fig. 3(c) owns a sufcient resolution while the cross terms
problem is solved as well.
The prime numbers in the complex signals in the GT and the
Wigner distribution are 2.6 and 0.6, respectively. By multiplying
the two functions, GT2.6(t, x)WD0.6(t, x) is obtained. To verify if the
selected prime number is appropriate, smaller prime numbers of
the GT and the Wigner distribution are compared. Fig. 4(a) shows
that when the function in the GWT is GT2.6(t, x)WD0.06(t, x), the
spectrum is inclined toward the GT and has lower resolution.
Fig. 4(b) shows that when the window function is GT0.4(t, x)
WD0.6(t, x), the spectrum is inclined toward the Wigner distribution
and has cross terms problems.

Frequency (Hz)

Frequency (Hz)

represents frequency. Analyzed values are displayed by various


shades of color. Lighter colors represent greater values, and darker
colors represent lower values.
Fig. 1(a) shows the results of GT. Although it does not have a
cross terms problem, the resolution is lower. Fig. 1(b) shows the
Wigner distribution. Although it has a higher resolution, it has a
cross terms problem. Fig. 1(c) shows the proposed approach combining the advantages of both: a better resolution and an elimination of cross terms.
Because of asymmetrical characteristics of Fourier transform, if
f(t) is a real function, then the Wigner distribution and
GaborWigner distribution will generate both positive and negative frequencies, in which a negative frequency does not have
physical meaning. However, to clearly demonstrate the cross
terms, the negative frequency is partially shown.
The selected prime numbers A and B in (7) are 2.6 and 0.6,
respectively. The two functions are then multiplied by
GT2.6(t, x)WD0.6(t, x). To verify if the selected prime number is
appropriate, smaller prime numbers of the GT and the Wigner distribution are compared. In Fig. 2(a), where the selection in the GWT
is GT2.6(t, x)WD0.06(t, x), the spectrum is inclined to the GT function and has a lower resolution. In Fig. 2(b), where the selection
is GT0.4(t, x)WD0.6(t, x), the spectrum is inclined to the Wigner
distribution and has a cross terms problem.

Time (s)

Time (s)

(a)

(b)

Frequency (Hz)

Frequency (Hz)

Frequency (Hz)

Fig. 2. The effects of the prime number on the GWT. (a) The prime number of the GT is larger. (b) The prime number of the Wigner distribution is larger.

Time (s)

Time (s)

Time (s)

(a)

(b)

(c)

Frequency (Hz)

Frequency (Hz)

Fig. 3. The timefrequency spectrum of complex signals. (a) GT. (b) Wigner distribution. (c) GWT.

Time (s)

(a)

Time (s)

(b)

Fig. 4. The effects of the prime number on the GWT. (a) The prime number of the GT is greater. (b) The prime number of the Wigner distribution is greater.

195

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

Example 3 (Multiple complex signals). This example uses multiple


complex signals. The equation is

f t ej0:0015t

4 j0:06t 3 j0:3t2 jt

Fig. 5, the waveform of using the GT, the Wigner distribution, and
the GWT are all depicted. The horizontal axis represents time, and
the vertical axis represents frequency. Analyzed values are displayed
by various shades of color. Lighter colors represent greater values,
and darker colors represent lower values. Except from an additional
draw caused by the cross terms as shown in Fig. 5(b), both of Fig.
5(a) and (c) are able to demonstrate the resultant frequency distribution on the time axis; yet the resolution of Fig. 5(c) is a better one.
To verify if the selected prime number is appropriate, a lower
prime number of the GT and a lower prime number of the Wigner
distribution are compared. In Fig. 6(a), when the selected prime
number in GWT is GT2.6(t, x)WD0.06(t, x), the spectrum is inclined
toward the GT function and has a lower resolution. In Fig. 6(b), when
the selected window function is GT0.4(t, x)WD0.6(t, x), the spectrum
is inclined toward the Wigner distribution and has a cross terms
problem.
The examples show that the GWT not only has a higher resolution, but also overcomes the cross terms problem in the Wigner
distribution. It is also worth noting that for a polyharmonic signal
including harmonics of 60 Hz, 120 Hz, 180 Hz, the harmonic of
120 Hz will be still distorted by the cross-term solved with 60 Hz
and 180 Hz harmonics. Although this situation appears very seldom, yet special attentions may need to be paid for such rare cases.
As for the GWT applied for the inspection of high-impedance faults
in this study, it comes with a high suitability when compared to
some published techniques. In the following sections, the GT, the
Wigner distribution, and the GWT will be compared to verify the
applicability of GWT for the HIF investigated in this study.
Detecting process

this study for determining duration of HIF cycles. The HIFs at


30 kHz were sampled before the high-impedance signals were analyzed. The sampling frequency of, 30 kHz which was sufcient for
enabling HIF signal analysis, and 300,000 sampling points were
obtained. The GWT was applied to the sampled signals to conduct
computation and analysis. When the GWT analysis and computation were completed, the HIF duration (i.e. Tth) was determined.
When the selected values of Tth were excessively low, non-HIF signals might be erroneously considered HIF signals. Conversely,
when the selected values of Tth were extremely high, HIF detection
was delayed. Therefore, to select appropriate Tth values, this study
adopted the Tth value (i.e., Tth = 5) used by [23] as the threshold
value. When the detected signal did not exceed the set threshold
value, the signal was considered to be a non-HIF signal and the
detection continued by sampling next piece of data. When the
detected signals exceeded the threshold value, they were
considered HIF signals. This process enabled the precise detection
of the exact time when HIFs occurred, thereby preventing result

Frequency (Hz)

Frequency (Hz)

Frequency (Hz)

Fig. 7 presents the GWT ow diagram, where T represents the


duration of HIF cycles and Tth denotes the threshold values set in

Fig. 7. The detection ow diagram.

Time (s)

Time (s)

(a)

(b)

Time (s)

(c)

Frequency (Hz)

Frequency (Hz)

Fig. 5. The timefrequency spectrum of complex signals. (a) GT. (b) Wigner distribution. (c) GWT.

Time (s)

(a)

Time (s)

(b)

Fig. 6. Effects of the prime number on the GWT. (a) The prime number of the GT is greater. (b) The prime number of the Wigner distribution is greater.

196

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

wet sand, wet soil, and wet meadow soil). The study [24] indicated
that the HIF current of cement was the lowest followed by the HIF
current of wet sand. The HIF current of wet meadow soil was high.
All experiments consisted of single line-to-ground faults. HIFs in
cement were detected on sunny days. In addition, HIFs in wet sand,
wet soil, and wet meadow soil were detected on rainy days.
Moreover, all of the signals were obtained by conducting actual
measurements, rather than simulations.

30 MVA
100 MVA
161 kV

161 kV / 22.8kV

Overhead feeder
5-kM

Load

Experiment 1: The HIFs in cement

HIF Modle

Fig. 8. The HIF single-line diagram of the power distribution system.

misinterpretation. To verify that the proposed method was appropriate for detecting HIFs, experiments were conducted; these
experiments are discussed in the following section.

Test results
In this section, the experimental results are provided. First, the
HIF signals in cement ooring and arc furnace load switches were
detected and compared. This was set as the baseline and used to
compare HIF and non-HIF signals. Subsequently, because the HIF
electric current in various substances differ [24], this method
was used to detect the HIFs in various substances (i.e., cement,

Fig. 8 shows an HIF single-line diagram of the power distribution system at Southern Taiwan Science Park. In this diagram, a
161 kV bus is used to transfer electricity from a substation containing 161/22.8 kV to an overhead feeder of 5 km, and nally to the
load. HIFs were detected in the overhead feeder (Fig. 8). In this
experiment, the ground was cement, the weather was sunny, and
the temperature was approximately 32 C. The obtained
single-line diagram data is presented in Fig. 8.
The HIF current waveforms in cement are presented in Fig. 9(a).
The horizontal axis represents time [s] and the vertical axis represents electric current (p.u.).
To verify the HIF detection efcacy of the proposed method, the
HIF signal of cement (Fig. 9(a)) was analyzed and computed using
the Gabor transform (GT), Wigner distribution (WD), and the GWT.
Fig. 9(b), (c), and (d) show the timefrequency analysis diagrams
obtained using the GT, WD, and the GWT, respectively. The horizontal axes represent time [s] and the vertical axes represent the
frequency (Hz) of the HIF signals. The second vertical axes represent the amplitude values (per-unit value) obtained by conducting
analysis. When amplitude was high, the frequency spectrum colors
brightened. Conversely, when the amplitude was low, the frequency spectrum colors were dim. The symmetry characteristics
of the Fourier transform were previously introduced in

1
0.9

Current (p. u.)

0.7
0.6
0.5
0.4
0.3

Amplitude (p. u.)

Frequency (Hz)

0.8

0.2

Fault Begins

0.1
0

Time (s)

Time (s)

(a)

(b)
1

0.9

0.9

0.8

0.8

0.4
0.3

Frequency (Hz)

Frequency (Hz)

0.5

0.7
0.6
0.5
0.4
0.3

0.2

0.2

0.1

0.1

Time (s)

(c)

Amplitude (p. u.)

0.6

Amplitude (p. u.)

0.7

Time (s)

(d)

Fig. 9. The timefrequency diagram of the HIFs in the cement ground: (a) The HIF waveforms in cement; (b) GT timefrequency diagram; (c) WD timefrequency diagram;
and (d) GWT timefrequency diagram.

Amplitude (p. u.)

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

Fault Begins

Time (s)
Fig. 10. The cement HIF amplitude detected using the GWT.

by applying the GT. However, the GWT does not present cross
terms. Hence, the timefrequency diagrams show that noise signals were detected only when the frequency was 60 Hz.
However, because timefrequency diagrams cannot show the
exact time or amplitudes of the HIFs, plotting frequency spectrum
waveforms at 60 Hz was required to exhibit the HIF times and
amplitudes.
The timefrequency diagrams show that compared with the GT
and WD, the GWT is a superior method. Fig. 10 shows the amplitudes of the waveforms presented in Fig. 9(d) at a 60 Hz frequency.
Based on this gure, before 0.04 s (t), the value of the detected current was 0. The current could only be detected after t = 0.04 s.
Additionally, the value exceeded the set threshold value (i.e., 5
cycles) and were thus determined to be HIFs. Moreover, because
of the high impedance in cement, the HIF current was low. At
0.040.14 s, the amplitude value was approximately 0.1 p.u., which
was a low value. This gure shows that the GWT can be used to
accurately detect the occurrence of HIFs, without delaying the
detection of the HIF occurrence intervals. Hence, the proposed
method is suitable for detecting HIFs.
The results of Experiment 1 were used to present the GT, WD,
and GWT differences. In addition to accurately detecting HIF time
of occurrence, the GWT does not misjudge non-HIF signals.
Hence, the GWT is suitable for HIF detection. To further ensure that
the GWT precisely detect HIFs in various substances, switching
events and overhead feeders were used to measure the signals in
wet sand, wet soil, and wet meadow soil. The measurement results
were used to determine whether the GWT could accurately detect
the HIF occurrence times.
Experiment 2: Transient switching events
Under normal system operations, switching events related to
arc furnaces or other transient phenomena may distort the current
waveforms. Therefore, these phenomena must be distinguished
from the HIFs. Fig. 11(a) shows the current waveforms of a 35%
loaded arc furnace that was connected to the system. Based on this
gure, transient switching events occurred at approximately 0.038,
0.08, 0.105, and 0.14 s.
Fig. 11(b) presents the current values obtained using GWT analysis. At 00.14 s, all the amplitude values obtained by applying the
GWT were 0, indicating that the GWT did not erroneously consider
transient switching events as HIFs.
Experiment 3: The HIFs in wet sand
In Experiment 3, the contact ground was wet sand (Fig. 12(a));
the current value began to increase at 0.05 s. This indicated that an
HIF occurred. However, this signal cannot be used to indicate the
differences between the HIFs in wet sand and cement. Therefore,
the GWT was used to distinguish the various substances.

Current (p. u.)

Amplitude (p. u.)

Section Proposed method. When f(t) represented a real number


function, the timefrequency diagrams obtained by applying the
GT, WD, and GWT all showed both positive and negative frequencies. The negative frequencies were not physically meaningful for
the real number signals. However, although the negative frequency
in this experiment was 60 Hz, the negative frequencies were displayed to exemplify the presence of cross terms.
As mentioned in Section Proposed method, regarding the
timefrequency diagram shown in Fig. 9(b), using the GT cannot
simultaneously maintain high resolution in the time and frequency
domains, thus resulting in the poor resolution in either domain. In
Fig. 9(b), to detect HIFs, satisfactory time resolution was presented,
which resulted in the poor frequency resolution. The electric power
frequency provided by the Taiwan Power Company is typically
60 Hz. In the timefrequency diagram, the frequency spectrum distributed near 60 Hz is broad, thereby showing the low-frequency
resolution of this method. When analyzing HIFs, the
low-frequency resolution affected detection and therefore was
inapplicable to detecting HIFs. Fig. 9(c) presents the timefrequency diagram derived by using the WD. As mentioned in
Section Proposed method, the WD yields high time and frequency
resolutions. However, the WD has the disadvantage of producing
cross terms. Hence, as shown in the timefrequency diagrams,
noise signals that were caused by the cross terms were detected
when using frequencies other than 60 Hz. Because the WD offers
a high timefrequency resolution, the width of the WD frequency
spectrum distributed near 60 Hz was smaller than that produced
using the GT. In addition, as shown in the gures, when the frequency was 0 Hz, the GT method yielded cross terms noise signals,
which inuenced the HIF detection results. Thus, the GT was also
unsuitable for detecting HIFs. Fig. 9(d) shows the GWT timefrequency analysis diagram. Based on the theories introduced in
Section Proposed method, the GWT yields a high timefrequency
resolution. The gure shows that the GWT derived frequency spectrum width distributed near 60 Hz was smaller than that derived

197

Time (s)

Time (s)

(a)

(b)

Fig. 11. Transient switching events: (a) The current waveforms of transient switching events and (b) the amplitude obtained using the GWT.

198

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

Fig. 12(b) shows the signal amplitude after the current was analyzed and computed using the GWT. The results indicate that the
GWT could detect when the HIFs began occurring. The signal began
at .05 s and continued for ve cycles, indicating that this was an
HIF signal. In addition, a comparison of wet sand and cement
showed that when t = 0.14 s, the amplitude was 0.3 p.u. Because
the impedance of wet sand was smaller than that of cement, the
HIF current in wet sand was greater than that in cement. The gure
also indicates that the wet sand yielded higher amplitude than that
of cement.

0.05 s, the GWT amplitude was 0 p.u., because HIF was not
detected. At 0.05 s, the HIFs began occurring, as demonstrated by
the increased amplitude in Fig. 13(b). At 0.14 s, the amplitude
was measured at 0.37 p.u. and remained at this level for more than
ve cycles. Hence, this phenomenon was considered to be an HIF. A
previous study [24] indicated that the HIF current in wet soil was
higher than that in cement and wet sand. The amplitude displayed
in this gure was also higher than that for cement and wet sand,
thereby verifying the accuracy of the results.

Experiment 5: The HIFs in wet meadow soil


Experiment 4: The HIFs in wet soil
In this experiment, the measured ground was wet soil. Fig. 13(a)
shows the HIF waveforms, indicating that, the current value began
to rapidly increase at approximately 0.05 s, indicating the occurrence of HIFs.
Fig. 13(b) shows the HIF signal analysis and computation results
obtained using the GWT. In this gure, the horizontal axis represents time and the vertical axis represents amplitude. Before

The nal experiment in this study was conducted to measure


the HIF of wet meadow soil. The curves in Fig. 14(a) are the waveforms of the HIF currents. The current is displaying at a per-unit
value. Based on this gure, the approximate occurrence time of
HIFs was 0.05 s.
Fig. 14(b) shows the current values that were computed using
the GWT. Based on the gure, the HIFs in wet meadow soil
occurred at .05 s, which indicated the detection accuracy. The

Current (p. u.)

Amplitude (p. u.)

Fault Begins

Fault Begins

Time (s)

Time (s)

(a)

(b)

Amplitude (p. u.)

Current (p. u.)

Fig. 12. The HIFs of wet sand: (a) The HIF waveforms of wet sand and (b) the currents obtained using the GWT.

Fault Begins

Fault Begins

Time (s)

Time (s)

(a)

(b)

Fig. 13. The HIFs in the wet soil ground: (a) The HIF waveforms of wet soil and (b) the amplitude obtained using the GWT.

Amplitude (p. u.)

Current (p. u.)

Fault Begins

Fault Begins

Time (s)

Time (s)

(a)

(b)

Fig. 14. The HIFs of wet meadow soil: (a) The HIF current waveforms wet meadow soil and (b) the amplitude obtained using the GWT.

J.-Y. Cheng et al. / Electrical Power and Energy Systems 73 (2015) 192199

current value remained elevated for ve cycles after 0.05 s., verifying that the signal was an HIF signal. In addition, at 0.14 s, the HIF
current in the wet meadow soil was 0.7 p.u. Thus, the impedance in
wet meadow soil is lower than that in cement, wet sand, and wet
soil. The results in the gure indicated that the amplitude in wet
meadow soil was also higher than that in cement, wet sand, and
wet soil.
The results of the ve experiments show that the GWT can
accurately detect the HIF occurrence time in various substances.
Additionally, non-HIF signals were not erroneously considered to
be HIF signals. These experimental results verify that in addition
to the mentioned advantages, the GWT can be used to detect HIFs.
Conclusion
This study applied the GWT method for inspecting the
high-impedance fault generated signals. This proposed approach
is proved to be effective to solve the cross-term problems of
Wigner transform as well. Compared with the conventional
Fourier transform, this proposed GWT method owns a potential
of extending to analyze other non-stationary signals so as to forewarn the occurrence of power quality events with a higher efciency. At this time, we are assessing the possibility of
implementing the GWT method through hardware design, anticipating a further enhancement of monitoring performance. The
results will be reported in the near future.
References
[1] Ko YS. A self-isolation method for the HIF zone under the network-based
distribution system. IEEE Trans Power Delivery 2009;24(2):88491.
[2] Elkalashy NI, Lehtonen M, Darwish HA, Taalab A-MI, Izzularab MA. DWT-based
detection and transient power direction based location of high impedance
fault due to leaning trees in unearthed MV networks. IEEE Trans Power
Delivery 2008;23(1).
[3] Elkalashy NI, Lehtonen M, Darwish HA, Izzularab MA, Taalab A-MI. Modeling
and experimental verication of high impedance arcing fault in medium
voltage networks. IEEE Trans Dielectr Electr Insul 2007;14(2):37583.
[4] Bhalja BR, Maheshwari RP. High-resistance faults on two terminal parallel
transmission line: analysis, simulation studies, and an adaptive distance
relaying scheme. IEEE Trans Power Delivery 2007;22(2):80112.
[5] Gautam S, Brahma SM. Detection of high impedance fault in power
distribution systems using mathematical morphology. IEEE Trans Power Syst
2013;28(2):122634.
[6] Huang CL, Chu HY, Chen MT. Algorithm comparison for high impedance fault
detection based on staged fault test. IEEE Trans Power Delivery
1988;3(4):142735.

199

[7] Lee RE, Bishop MT. A comparison of measured high impedance fault data to
digital computer modeling results. IEEE Trans Power Appar Syst
1985;104(10):27548.
[8] Russell BM, Mehta K, Chinchali RP. An arcing fault detection technique using
low frequency current components performance evaluation using recorded
eld data. IEEE Trans Power Delivery 1988;3(4):1493500.
[9] Sharaf AW, Snider LA, Debnath K. A third harmonic sequence ANN based
detection scheme for high impedance faults. In: Canadian conference on
electrical and computer engineering. Vancouver, Canada; September 1993. p.
8026.
[10] Jeerings DI, Linders JR. Unique aspects of distribution system harmonics due to
high impedance ground faults. IEEE Trans Power Delivery 1990;5(2):108694.
[11] Aucoin BM, Russell BD. Distribution high impedance fault detection using high
frequency current components. IEEE Trans Power Appar Syst
1982;101(6):1596606.
[12] Girgis AA, Chang W, Makram EB. Analysis of high impedance fault generated
signals using a Kalman ltering approach. IEEE Trans Power Delivery
1990;5(4):171424.
[13] Michalik M, Lukowicz M, Rebizant W, Lee SJ, Kang SH. New ANN-based
algorithms for detecting HIFs in multigrounded MV networks. IEEE Trans
Power Delivery 2008;23(1):5866.
[14] Samantaray SR, Panigrahi BK, Dash PK. High impedance fault detection in
power distribution networks using time-frequency transform and
probabilistic neural network. IET Gener Transm Distrib 2008;2(2):26170.
[15] Sheng Y, Rovnyak SM. Decision tree-based methodology for high impedance
fault detection. IEEE Trans Power Delivery 2004;19(2):5336.
[16] Michalik M, Lukowicz M, Rebizant W, Lee SJ, Kang SH. Verication of the
wavelet-based HIF detecting algorithm performance in solidly grounded MV
networks. IEEE Trans Power Delivery 2007;22(4).
[17] Torres V, Ruiz PHF. High impedance fault detection using discrete wavelet
transform. In: IEEE conference on electronics, robotics and automotive
mechanics. Morelos, Mexico; November 2011. p. 3259.
[18] Sedighi AR, Haghifam MR, Malik OP, Ghassemian MH. High impedance fault
detection based on wavelet transform and statistical pattern recognition. IEEE
Trans Power Delivery 2005;20(4):241421.
[19] Ali MS, Bakar AHA, Mokhlis H, Aroff H, Illias HA, Aman MM. High impedance
fault localization in a distribution network using the discrete wavelet
transform. In: IEEE international conference on power engineering and
optimization. Kuala Lumpur, Malaysia; June 2012. p. 34954.
[20] Huang SJ, Huang CL, Hsieh CT. Application of Gabor transform to Supervise
power system transient harmonics. IEE Proc: Gener Transm Distrib
1996;143(5):4616.
[21] Pei SC, Ding JJ. Relations between Gabor transforms and fractional Fourier
transforms and their applications for signal processing. IEEE Trans Signal
Process 2007;55(10):483950.
[22] Cho SH, Jang G, Kwon SH. Time-frequency analysis of power-quality
disturbances via the GaborWigner transform. IEEE Trans Power Delivery
2010;25(1):4949.
[23] Etemadi AH, Pasand MS. High-impedance fault detection using multiresolution signal decomposition and adaptive neural fuzzy inference system.
IET Gener Transm Distrib 2008;2(1):1108.
[24] Tengdin J. High impedance fault detection technology. Report of IEEE power
system relay committee working group D12, March 1966. P. 112.

Вам также может понравиться