EXPERIMENT NO. 4
Flow Ratio Plant Control (WF922)
OBJECTIVES
1.
2.
3.
4.
To identify the major components of the flow ratio process control system.
To perform start-up procedures systematically.
To study single loop flow control using PID controller.
To study flow ratio control using linear PID controller.
a)
b)
c)
That ratio control requires that the control valve be installed on the CF line.
The range of the Ratio value, which can be set, is limited by the available
process flow rate, range ability of the flow meter and the control valve.
The process plant can be operated either by DCS or by the SCADA system.
KEYWORDS
Measurement:
i.
FT22, vortex flow meter.
ii.
FE21, Orifice flow element with FT21, a differential flow transmitter
with square extractor.
Control type:
i.
Single feedback PID flow control: FIC21, panel mount PID controller
ii.
Ratio control: FIC21 with remote set point from the Wild Flow (WF)
multiplied by the instrument ratio factor, R.
Final control element:
i.
FCV21, control valve complete with Positioner (PP) and Current-toAir (I/P) converter, FCY21.
Other Measurements: FI22: variable area flow meter (Rotameter); PG21, PG22:
Pressure gauges; TG21: Temperature gauge.
c)
d)
Others: PRV21, PRV22A, PRV22B: Pressure relief valves; IAS: Instrument air
supply to the FCY21 and PP Selector switch whereby either FT21 or FT22 can
be selected to be either the Controlled Flow (CF) or Wild Flow (WF).
e) Annunciators: FAH: High flow limit alarm for the Controlled Flow (CF) stream;
FAL: Low flow limit alarm for the Controlled Flow (CF) stream.
c) Shut the manual drain valve at the bottom of the tank T21.
d) Shut the interconnecting manual valve MVX.
Walk around the plant and identify the components given below and mark them in the P&I
diagram provided at the end of the lab manual.
4. Shut the manual discharge valve at the discharge of pump P20. Check and adjust the
NOTE that at the Recorder FR21:
Switch ON the main power supply at the front cubicle. The panel instruments will lit
up.
c)
d)
4. Make sure pump P21 is ON and its by-pass valve B21 is fully shut.
5. FIC21 remais in Auto (A) mode and observe the response.
1. Start with using one WF pump only. Start pumps P21 (CF pump) and P22A (WF pump).
Shut fully their manual by pass valves (B21, B22A as well as B22B) but open fully their
discharge manual valves.
2. Set the R=1 at CGN1 at the PARAMETER page on controller panel.
3. Switch the controller FIC21 to Cascade(C) mode so that the controller is functioned as
RATIO CONTROLLER.
(How to change Cascade (C) Mode: From Manual (M) mode, press Auto(A ) then press
Cascade(C))
4. Observe the recorder FR21 (Red pen/Channel1) and FT22 (Green pen/Channel 2). Wait
till the Red (FT21) and Green (FT22) pen are almost steady (i.e. within 0.02 to 0.05
m3/hr) or it continues to oscillate even after 3 cycles.
5. Note and calculate the Process Flow Ratio (PR) (computed from the actual process flow
rate, then, compare PR to R).
6. Observe also the PV and SV when the flow rate is steady. (Is PV = SV?)