Академический Документы
Профессиональный Документы
Культура Документы
Total,
Lindsey Oil Refinery,
Humberside, England
Project No.
64566-13
Project Name
Document No.
64566-13/P.02/0011/A4
Revision
Prepared by
HELY
Checked by
BLGJ
Approved by
BLJ
Submitted by:
Jacobs Nederland B.V.
Plesmanlaan 100, 2332 CB Leiden
P.O. Box 141, 2300 AC Leiden
The Netherlands
TABLE OF CONTENTS
1.0
INTRODUCTION
2.0
PROCES DESCRIPTION
2.1
2.1.1
2.1.2
2.1.3
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.3
3.0
3.1
3.1.1
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.4
3.4.1
3.4.2
TREATMENT OF CATALYST
Claus Catalyst Reactivation
NORMAL OPERATION
Operating Variables and Control
Plugging of Sulfur Locks
Ammonia Combustion
Draining K.O. Drums
Points for Consideration
PROCESS CONTROL, ALARM AND SAFEGUARDING SYSTEMS
Process Instrumentation
Instrument Alarm System
Safeguarding System
Controller, Alarm and Trip Settings
Relief Valves
TEMPERATURE RUNAWAYS
Fire inside the Claus Reactors
Fire in the Sulfur Pit
4.0
COMMISSIONING
4.1
4.1.1
4.1.2
4.2
4.2.1
4.2.2
INTRODUCTION
CLEANING OF WASTE HEAT BOILERS AND CONDENSERS
COMMISSIONING OF UTILITY AND INSTRUMENT SYSTEMS
NATURAL GAS INTAKE AND DRYING OUT
Introduction
Detailed Outline
Page 2 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.3
4.3.1
4.3.2
CATALYST LOADING
Stopping the unit
Catalyst loading
5.0
STARTUP
5.1
5.2
5.3
5.3.1
5.3.2
5.4
5.4.1
5.4.2
5.5
6.0
SHUTDOWN
6.1
6.2
6.2.1
6.2.2
6.3
6.3.1
6.3.2
6.4
6.4.1
6.4.2
6.4.3
GENERAL
SHUTDOWN PROCEDURE FOR SHORT PERIOD (HOT STANDBY)
Simplified Outline
Detailed Outline
SHUTDOWN PROCEDURE FOR LONG PERIOD (COMPLETE SHUTDOWN)
Simplified Outline
Detailed Outline
RESTART AFTER AN AUTOMATIC SHUTDOWN (TRIP)
Restart when the Unit is Hot and Sulfur is inside the Equipment
Restart when the Unit is Cold and Sulfur is inside the Equipment
Restart when no Sulfur is inside the Equipment
7.0
SAFETY
7.1
7.2
7.3
7.4
7.4.1
7.4.2
7.4.3
7.4.4
7.4.5
7.5
8.0
TROUBLE SHOOTING
8.1
8.2
8.2.1
8.2.2
INTRODUCTION
PROCESS PROBLEMS
General
Burner & Combustion Chambers
Page 3 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.2.3
8.2.4
8.2.5
8.2.6
8.2.7
8.2.8
8.2.9
8.3
8.3.1
8.3.2
8.3.3
8.3.4
8.3.5
8.3.6
8.4
Reactor Stages
Incinerator
Sulfur Degassing Vessel
Poor Sulfur Recovery
Pressure Drop
Plugging
Temperature Runaways
MECHANICAL PROBLEMS
Running Equipment
Ignitors
Boiler or Condenser Leakage
Refractory Material
Fluctuations and Hydrocarbon carry-over
Corrosion
CRITICAL AREAS IN SULFUR RECOVERY PLANT OPERATION
9.0
MAINTENANCE
9.1
9.1.1
9.1.2
9.1.3
9.1.4
9.1.5
9.1.6
9.1.7
9.1.8
9.1.9
9.1.10
9.1.11
9.1.12
9.1.13
9.1.14
9.1.15
9.1.16
9.1.17
9.1.18
EQUIPMENT
Knock-out Drums
Preheaters
Burners
Combustion Chambers
Waste Heat Boiler
Sulfur Condensers
Reactors
Sulfur Coalescer
Incinerator
Incinerator Waste Heat Boiler
Steam Superheater
Sulfur Locks
Sulfur Storage Tank
Sulfur Degassing Vessel
Steam Coil in Sulfur Degassing Vessel
Running Equipment
Piping and Valves
Analyzers
Page 4 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
1.0
INTRODUCTION
The Sulfur Recovery Unit is designed to recover sulfur from sour gases originating
from the following sources:
The process design is based on the CLAUS process to recover elementary sulfur
from an H2S containing gas stream.
The SRU consists of a thermal stage, in which H2S is partially burnt with air, followed
by three catalytic Claus stages. The tail gas from the final stage is routed to the
incinerator.
Facilities are provided for continuous degasification of the produced sulfur to reduce
its H2S content.
The instructions contained herein are presented as a general guide to aid in safe
startup and operation of the unit.
Operating experience will indicate where a procedure should be modified to improve
the performance of the unit.
These instructions are to be used in combination with:
Process Flow Scheme.
Piping and Instrument Diagram.
Description of Logic System for Startup and Shutdown Operation.
Cause & Effect Diagram for Normal Operation.
Basis of design.
Process control narrative(s).
Page 5 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
2.0
PROCES DESCRIPTION
2.1
2.1.1
Claus Process
Thermal reaction stage
In the applied sulphur recovery process, known as conventional Claus process, 'air to - acid gas ratio' is maintained to produce an H2S - to - SO2 ratio of exactly 2/1 in
the catalytic effluent gases. This is the optimum ratio of H2S - to - SO2 for the Claus
reaction.
The main reaction in the main burner and reaction furnace is:
3
H 2S + O 2 SO 2 + H 2 O + heat
2
The major percentage of the residual H2S combines with the SO2 to form sulphur,
according to equilibrium reaction:
3
2H2 S + SO 2
S 2 + 2H2 O - heat
2
By this reaction, known as the Claus reaction, sulphur is formed in vapour phase in
the main burner and reaction furnace.
Catalytic Claus stage
The downstream catalytic reaction stage further increases the overall conversion to
sulphur. In the first, second and third reactor the following reaction takes place:
2 H2S + SO2 3/x Sx + 2 H2O + heat
The Claus equilibrium is shifted to the sulphur side by making use of a Claus
catalyst. Condensation and removal of sulphur after the first, second, and third
reactor enables further conversion of sulphur in the next catalytic stage.
2.1.2
Page 6 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
elemental sulphur. Furthermore, the removal of H2S from the sulphur promotes the
decomposition of the polysulphides into H2S and sulphur.
H2Sx H2S + Sx-1
H2S + O2 1/x Sx + H2O
2.1.3
Incinerator
The tail gas resulting from the Claus stage and vent gas from the sulphur degassing
still contains traces of sulphur compounds. These sulphur compounds are oxidized
in the incinerator at elevated temperatures. The main reactions are:
H2S + 3/2 O2 SO2 + H2O
1/x Sx + O2 SO2
COS + 3/2 O2 SO2 + CO2
Page 7 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
2.2
2.2.1
2.2.2
Thermal Stage
Main Air Blower 13B-01A/B supplies the air to the main burner. The main air blower
also supplies air to the sulphur degassing system. The combustion temperature in
the combustion chamber has to be sufficiently high (above 1250C) for NH3
destruction in the reaction furnace. The air to the main burner is exactly sufficient to
accomplish the complete oxidation of all hydrocarbons and ammonia present in the
feed gases and to burn H2S.
The combustion air to the main burner is controlled by the Advanced Burner Control
system (ABC system). This system is based on the feed forward control. Reference
is made to the control description, doc. no. 64566-13/P.02/0007/P.
The required quantity of air is calculated by measuring the acid feed gas flow, the
SWS Ammonia gas flow and natural gas flow and multiplying each flow with its own
individual air demand (feed forward control). This results in a total air demand and
this signal sets the flow control system in the air supply. The flow control system
adjusts the position of two control valves.
The system adjusts immediately a small control valve in the trim air line, after which
the bigger main valve follows with a delay. The final situation is that the flow through
the control valve in the trim air line is again in the optimum of its range to cope
Page 8 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
quickly with flow changes. Then the total air flow through the main air and the trim
air lines corresponds with the total amount of acid gas feed.
The combustion temperature has to be sufficiently high (1250C minimum) to obtain
a proper destruction of NH3. The feed gas does not contain sufficient combustibles
to obtain this temperature. Therefore preheating of the acid gas using jacketed
piping is required. When even with preheating this temperature is not met, Natural
gas has to be co-fired in the main burner. The Natural gas is used instead of
Refinery Fuel Gas as it has a more stable in composition, to enable better ratio
control of the air to fuel ratio. Excess sub or over stoichiometric combustion may
lead to damage of the catalyst.
The supply of Oxygen will be via a dedicated gun to the main burner. This will only
be used when operating away from the base design case where an increased
throughput or Ammonia destruct options are required.
To remove the heat generated in the main burner 13F-01, the gas passes through
the tube bundle located in Waste Heat Boiler 13E-01. The gas is cooled, thereby
generating saturated high pressure steam, which is collected in Waste Heat Boiler
Steam Drum which is a part of the waste heat boiler. The WHB high pressure steam
combines with the steam generated from the Incinerator WHB (13E-11). The
combined saturated HP steam is routed through a Steam Dryer (13D-11), before
partly supplying the Re-heaters (13E-03/05/07). Any excess being superheated (in
the Incinerator 13E-12) and exported into the HP steam header. Boiler feed water
is introduced to the steam drum of the waste heat boiler on level control.
The process gas is cooled further in the First Sulphur Condenser 13E-02. The
sulphur vapour in the process gas is condensed and separated from the gas. Liquid
sulphur from the first sulphur condenser is directed to the Sulfur degassing vessel
13D-08 via its Sulphur lock 13D-06A. A demister pad is installed in the outlet
channel of the first sulphur condenser to recover liquid sulphur, entrained as mist
with the process gas.
In the sulphur condenser low pressure steam is generated.
2.2.3
Page 9 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
In the reactor, the H2S and SO2 in the process gas react over the catalyst until
equilibrium is reached. The inlet temperature of the reactor is maintained at 240C
to favour COS and CS2 conversion. The process gas from the reactor passes into
the Second Sulphur Condenser 13E-04, is cooled and the sulphur in the gas is
condensed and separated from the gas. Liquid sulphur from the second sulphur
condenser is directed to the Sulphur degassing vessel via its Sulphur lock 13D-06B.
A demister pad is installed in the outlet channel of the second sulphur condenser to
recover liquid sulphur, entrained as mist with the process gas. Like in the first
sulphur condenser low pressure steam is generated.
The gas stream from the second sulphur condenser is heated again in the Second
Reheater 13E-05, to obtain the optimum temperature (210C) for the catalytic
conversion in the Second Claus Reactor 13D-04 which contains an alumina oxide
type catalyst. The steam flow to the second reheater is adjusted by a temperature
controller at the inlet of the reactor. The inlet temperature is lower than in the first
reactor to promote a high conversion of H2S and SO2 into sulphur.
In the reactor, the H2S and SO2 in the process gas react over the catalyst until
equilibrium is reached. The process gas from the reactor passes into the Third
Sulphur Condenser 13E-06, is cooled and the sulphur in the gas is condensed and
separated from the gas. Liquid sulphur from the third sulphur condenser is directed
to the Sulphur degassing vessel via its Sulphur lock 13D-06C. A demister pad is
installed in the outlet channel of the third sulphur condenser to recover liquid
sulphur, entrained as mist with the process gas.
The first, second and third sulphur condensers are combined in one shell. Boiler
feed water is introduced to the shell side of the condensers on level control. The
condensers generate low pressure steam which is used for plant heating, the
surplus is exported to the refinery steam network.
The gas stream from the third sulphur condenser is heated again in the Third
Reheater 13E-07, to obtain the optimum temperature (195C) for the catalytic
conversion in the Third Claus Reactor 13D-05. This reactor contains alumina oxide
type catalyst. The steam flow to the third reheater is adjusted by a temperature
controller at the inlet of the reactor; the inlet temperature is lower than in the first two
reactors to promote a high conversion of H2S and SO2 into sulphur.
The process gas from the third Claus reactor passes to the fourth Sulphur
condenser 13E-08, is cooled and sulphur in the gas is condensed and separated
from the gas. Liquid sulphur is directed to the Sulphur degassing vessel via its
Sulphur lock 13D-06D. A demister pad is installed in the outlet channel of the fourth
sulphur condenser to recover liquid sulphur, entrained as mist with the process gas.
Page 10 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Boiler feed water is introduced to the shell side of the fourth condenser on level
control. The 4th condenser generates a small amount low pressure steam that is not
used for plant heating and is condensed back using the LLP Steam condenser 13E09. Part of this condensate is used in the sulphur cooler 13E-10, part of the
Degassing Vessel 13D-08, and returned into the closed system as LLP steam
upstream of the air cooler 13E-09.
The process gas flows from the fourth sulphur condenser into the downstream
Coalescer 13D-07, provided with a demister pad, in which the last traces of liquid
sulphur are separated from the gas and the liquid sulphur is sent to Sulphur
degassing vessel via its Sulphur lock 13D-06E.
2.2.4
Incinerator
The Claus tail gas and the vent gas from the sulphur degassing vessel contain
residual H2S and other sulphur compounds, which cannot be released directly to the
atmosphere. These gases are therefore thermally incinerated in incinerator to
convert residual H2S and sulphur compounds into SO2. The Ammonia stream from
the SWS will normally be fed direct to the Incinerator from the Sour Gas Knock Out
Drum 13D-02. There is an option to feed to thermal section for Ammonia
destruction, but this will not be the normal operating case. Additionally the vent
gases from the SWS buffer tanks are also fed to the incinerator.
The gases to be oxidised are heated by mixing with hot flue gas, obtained by
combustion of fuel gas in Incinerator burner 13F-02.
The fuel gas flow to the burner is adjusted by control of the temperature in the flue
gas leaving the incinerator. The combustion air for the fuel gas is provided by the
Incinerator blower 13B-02. Main air blower 13B-01B can also be used as a spare
for the incinerator blower using the pressure letdown control valve PCV010
The air supply to the incinerator is divided in three stages:
1. Primary air used for substoichiometric combustion of fuel gas
2. Staged air for supply of air to the flue gas from the burner to obtain
overstoichiometric combustion of the fuel gas.
3. Secondary air for combustion (oxidation) of the process gas
The primary air flow is ratio controlled by the fuel gas flow. The resulting primary air
flow rate is 80% of the amount required for stoichiometric combustion of the fuel
gas. This reduces the formation of NOx in the burner.
The staged air flow is also ratio controlled by the fuel gas and amounts to 30% of
the air flow rate required for stoichiometric combustion of the fuel gas.
Page 11 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
An oxygen analyser is situated in the oxidiser flue gas and is provided with an
oxygen controller. The signal from the oxygen controller is the setpoint of the flow
controller of the secondary air. The staged air flow and secondary air flow rates are
therefore adequate to supply sufficient oxygen to burn the un-burnt fuel gas and to
incinerate the combustibles in the process gas. It results in an oxygen excess of
2.1 vol.% in the incinerator flue gas. The oxygen excess ensures that the flue gas
contains less than 10 ppm vol. H2S.
The flue gas leaving the incinerator is cooled to about 500 C in the Steam
Superheater 13E-12, prior to entering the incinerator waste heat boiler 13E-11. Here
the flue gas is further cooled (to 300oC), thereby producing saturated HP steam.
This is combined with the main WHB (13E-01) steam as described above.
2.2.5
Page 12 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
The storage tank can contain 10 days sulphur production. Sulphur from storage tank
is pumped by the Sulphur transfer Pump 13P-02 to the solidification unit.
Page 13 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
2.3
UTILITY SYSTEMS
High Pressure (HS) Steam
Saturated HS steam is generated in both waste heat boilers (13E-01/11). It is
utilized as heating medium for the steam Reheaters (13E-03/05/07). Surplus HS
steam is superheated via a coil between the Incinerator (13F-04) and Incinerator
WHB (13E-11), and is routed to the HS steam system.
During start-up and shutdown when the waste heat boiler produces insufficient HS
steam it might be necessary to import HS steam from the refinery system to supply
steam to the reheaters.
Low Pressure (LS) Steam
Saturated LS steam is generated in the first three sulphur condensers (13E02/04/06) and used for plant heating (e.g. for degassing, tracing/jacketing of
pipelines). The remainder is discharged into the LS steam system. An MP steam
import line is in place to support in the internal LP header in the event of drop in
pressure.
During hot standby LS steam is supplied to the main burner for cooling of the fuel
gas flame, as air cooling is not allowed under these circumstances.
Discontinuous steam purges may be required as smothering medium during a
temperature run-away in the sulphur vessel.
When the equipment in the unit is cold (below 100C), steam should not be
introduced into the main burner, neither for cooling nor for purging.
Boiler feed water
Boiler feed water is supplied to the waste heat boilers and the sulphur condensers.
Fuel gas
Fuel gas is fired in the incinerator burner. During startup, hot standby and shutdown
or in the case that the flame temperature is lower then 1250C.
Nitrogen
A continuous small nitrogen purge is required for the flame scanners, sight glasses
and pyrometer of the main burner and the relief line of the SWS gas knock out drum.
During startup it is also used for purging the main burner and the reaction furnace.
Condensate recovery
Page 14 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
All the steam used for heating within the plant shall be recovered. Each item is first
routed to a steam trap, to take care of the correct conditions within the item where
the heating takes place.
The condensates from the LS steam used for internal heating are routed to the
condensate return header. The steam generated on the 4th condenser 13E-08 is
condensed by the LLP Steam condenser 13E-09 and drained back to the flash
drum. A small part of this condensate is used in the sulphur cooler 13E-10, with the
LLP steam generated returned upstream of the LLP Steam condenser 13E-09.
Blow down recovery
The blow down of both waste heat boilers and the sulphur condensers are routed to
the Blow down Drum 13D-10, where it is completely flashed to atmospheric
pressure. The blow down water is quenched with Raw water to approx. 60C before
being routed to the sewer.
Page 15 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
3.0
3.1
TREATMENT OF CATALYST
3.1.1
An increase of the H2S content in the gas to the second reactor is obtained by
operating the main burner with a deficiency of air. Therefore, an adjustment of the
ratio air-to-feed gas or set point of the H2S analyzer controller has to be made.
Page 16 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
In order to reach the maximum temperature in the reactor, the steam supply to the
reheater is fully open and the plant throughput is decreased to approximately 50% of
the design feed.
Catalyst reactivation is advised after each shutdown operation.
The first reactor contains a titanium-based catalyst, which is insensitive for sulfation,
with a top layer of alumina type catalyst. The top layer protects the titanium catalyst
against soot deposition. Because of the elevated temperature in the first reactor and
the high H2S content, sulfation of the top layer will hardly occur.
Sulfur removal (heat soak)
During operation, sulfur is absorbed inside the pores of the catalyst. This has no
adverse effect on the performance of the plant. When, however, during operation the
bed temperature is lower than the sulfur dewpoint, sulfur condenses on the surface
of the catalyst, which reduces the catalyst activity. This applies only for the catalyst
in the 2nd and 3rd reactor as the 1st reactor operates always far above the sulfur
dewpoint.
The dewpoints of the gas leaving the 1st, 2nd and 3rd reactors are 247C, 216C and
182C, respectively.
As soon as a decline in temperature difference over a reactor becomes noticeable
from the daily operating figures, the most likely reason is that too much sulfur has
accumulated on the catalyst. To remove the sulfur from the concerned catalyst bed,
the reactor inlet temperature should be increased approximately 20 C for a period
of at least 24 hours. Reduce plant capacity if required to obtain this temperature
increase. It should be noted that this operation does not reverse the aging of Claus
catalyst.
Page 17 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
3.2
NORMAL OPERATION
3.2.1
Page 18 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
At a lower inlet temperature of the second reactor, sulfur vapor may condense on
the catalyst bed, resulting in reduced catalyst activity. At higher temperatures, less
H2S is converted as the equilibrium shifts to H2S and SO2.
At high throughput, the reactor inlet temperatures are 240C and 205C,
respectively. When the unit operates at low throughput (below 40% of design), it is
advised to increase the inlet temperature of the second reactor by 10-15C, to
compensate for heat losses to obtain a safe dew point margin. This prevents sulfur
condensation on the catalyst bed. The reactor inlet temperatures are automatically
controlled: the controllers adjust control valves in the steam supply lines to the
reheaters.
The difference between the inlet and bottom temperature of the reactor is a measure
for the conversion rate in the catalyst bed. As soon as a decline in temperature
difference across the second reactor becomes noticeable from the daily operating
figures, the inlet temperature should be temporarily increased. In this way
condensed sulfur evaporated from the catalyst bed. It is pointed out that
condensation of sulfur on the catalyst is the most likely reason for deterioration of
the catalyst.
Page 19 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Page 20 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
The next stage is the "staged" air, supplied after the flame zone. The staged air flow
is also ratio controlled by the natural gas flow, but moreover the output of the oxygen
controller is added to the air flow rate, calculated from the natural gas flow.
Consequently, free oxygen is available for the incineration of non-recovered sulfur
components. The oxygen-analyser is controlled at an oxygen content of 1.7% by
volume.
The flue gas leaving the incinerator is discharged via the stack to the atmosphere.
The operating temperature in the incinerator is 760C. It is obtained from:
1. Combustion of fuel gas in the incinerator burner.
2. Combustion of the combustibles present in the tail gas.
At lower temperatures than 725C the H2S content in the flue gas will increase. This
might be partly compensated by increasing the O2 concentration. A higher
temperature will result in higher fuel gas consumption. In the Claus mode, the tail
gas contains considerably more H2S. In order to keep the H2S content in the flue gas
below 10 ppm vol., the operating temperature should be increased.
A low O2 concentration has the same effect as a low temperature: the H2S content
increases. More O2 means that too much air is supplied, resulting in high fuel gas
consumption.
The flue gas leaving the incinerator is discharged via the stack to the atmosphere.
Apart from at initial startup, the incinerator should be started before the main burner
at subsequent startups. Then poisonous gas that might still be present in the
equipment, is converted and released via the stack.
Steam Superheater
The steam superheater should always have steam flowing through the tubes when
the incinerator is in operation. The steam flow prevents overheating of the tubes.
During startup, when no steam is jet produced by the waste heat boiler in the unit,
steam has to be imported from the refinery. When the Waste heat boiler produces
enough steam, the steam import from the refinery system can be stopped.
Sulfur degasser
Liquid sulphur coming from the condensers is cooled in the sulphur cooler before
entering the degassing vessel. This liquid sulfur contains about 300 ppm wt H2S. To
reduce this to less than 10 ppm wt, the sulfur is stripped in the degassing vessel.
Page 21 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Two bubble columns are located in the stripping section. Air distribution spargers are
provided at their bottom sides.
The stripping air to the spargers is supplied by the main air blower (13B-01A/B). The
function of the air is to obtain forced sulphur circulation in and around the bubble
columns, to strip the dissolved hydrogen sulphide from the liquid sulphur and to
oxidize the major part of the H2S to sulphur. Furthermore, the removal of H2S from
the sulphur promotes the decomposition of polysulphides into dissolved H2S and
sulphur. In this way, sulphur with a H2S content of less than 10 ppm wt is obtained.
3.2.2
3.2.3
Ammonia Combustion
The feed gas from the Sour Water Stripping Unit contains ammonia. It is imperative
that the ammonia is converted in the combustion chamber as completely as possible
so that the process gas through the equipment contains only a few ppms of
ammonia. Incomplete conversion of ammonia will cause plugging by ammonium
salts on the coldest spots in the equipment (condenser outlets)
Good ammonia conversion is ensured when the temperature of combustion in the
main burner and combustion chamber is sufficiently high and the residence time is
long enough. Especially the combustion temperature should be at least 1250C
during the whole operation period when the SWS off-gas is treated, also during
upsets and low capacity operation. At turndown conditions (amine gas 20% and
SWS off-gas 100%), the temperature in the combustion chamber is still sufficient for
complete conversion of ammonia.
3.2.4
Page 22 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
H2S and SO2 are extremely poisonous gases. Utmost care must be taken to
avoid exposure of personnel and environment to these gases, e.g. when
draining H2S containing liquid or when taking gas samples.
In special circumstances, protective masks must be worn (see Section 7).
The lower and upper explosion limits of H2S in a gas-air mixture are 4.3 and
45.5 vol.%, respectively. In the stoichiometric ratio with air, it explodes violently
when ignited.
The boiler water in the waste heat boiler and sulfur condensers should be
sampled periodically to check the concentration of solids.
The maximum allowable total concentration of solids in the waste heat boiler is
3000 ppm, of which a maximum 250 ppm of suspended solids is permitted. The
maximum allowable total concentration of solids in the sulfur condensers is
3500 ppm with maximum 300 ppm of suspended solids.
Higher figures might lead to dirt and scale deposition and finally to damage of
the boiler and condensers. The concentration of solids can be adjusted by
varying the blowdown rate.
A frequent inspection of the sulfur flow from the sulfur locks and the flame color
as well as reading of the main burner inlet pressure may give an early warning
before plugging by sulfur and/or ammonia salts might occur.
Page 23 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
To prevent damage of the burner, it is strongly advised to operate the air side of
the burner at a pressure drop of at least 1.0 mbar.
During the (fuel gas) ignition stage in the burner, the maximum amount of fuel
gas allowed to be present inside the burner/combustion chamber is restricted to
avoid an excessive pressure rise when the actual ignition takes place. For this
reason the burner/combustion chamber are purged before admitting fuel gas to
remove any combustibles that might be left from a previous ignition trial. The
equipment is capable to stay leak tight after a pressure rise during ignition or
explosion, but the internals may be damaged.
The windows of the flame scanners and the pyrometer should be cleaned on a
regular basis.
Reactor stages
Runaway temperatures in the Claus reactors should be avoided during hot
standby and shutdown. When the temperature tends to rise to 400C the air-tofuel gas ratio at the main burner should be reduced in order to obtain
substoichiometric conditions. Introduce nitrogen to the reactor for additional
cooling.
Care should be taken that the ratio fuel gas-air and/or acid gas-air at the line
burners is correct. Too little air might result in deposition of soot on the catalyst
Page 24 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
bed (higher pressure drop and less sulfur conversion) and too much air in
sulfatation of the catalyst (less sulfur conversion).
Soot, however, can only be removed during a shutdown period by replacing the
top layer of the catalyst bed.
Incinerator
The incinerator is started-up before the main burner to convert any hazardous
gas, which might leave the unit during the purging and ignition phases of the
main burner. This does not apply to the initial heating up and drying out phases.
Then the temperature rise of the incinerator should occur gradually and Claus
off-gas from the main burner is required as a cooling medium.
Sulfur Degassing Vessel
Too high a liquid sulfur temperature should be avoided. Above 155C the
viscosity of the sulfur rises rapidly and may harm the sulfur pumps. Therefore,
the steam coils should only be in operation when no sulfur is produced in the
unit, unless the sulfur temperature drops below 125C.
Page 25 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
3.3
3.3.1
Process Instrumentation
An extensive number of control instruments, indicators and warning devices are
provided to ensure efficient and safe operation of the unit and to enable a
comprehensive analysis of the unit whilst in operation.
3.3.2
3.3.3
Safeguarding System
Automatic safeguarding system
A comprehensive logic system has been designed and incorporated in order to
provide maximum protection for personnel, environment and equipment during
startup, shutdown and normal operation steps to avoid creation of dangerous
situations resulting from abnormal process conditions.
The actions of the logic system are described in the Cause and Effect Diagram for
normal operation reference doc. Nr. 20507-64566-13/P.03/0001 and in the
Description of Logic System for Startup and Shutdown Operation, reference doc.nr.
20570-64566-13/P.02/0011.
Emergency shutdown
Emergency shutdown is initiated by actuating either the board mounted or the field
mounted emergency switches in case of extreme situations, not covered by the
automatic safeguarding system, e.g. heavy leakage or plant fire.
3.3.4
3.3.5
Relief Valves
Relief valves are installed to provide adequate equipment protection in case of a
pressure rise.
Page 26 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
3.4
TEMPERATURE RUNAWAYS
3.4.1
3.4.2
Page 27 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.0
COMMISSIONING
4.1
INTRODUCTION
A systematic program of startup preparations must be drawn up and carried out to
ensure that the startup properly proceeds with the minimum delay. This is
particularly important when the unit has to be brought on stream together with other
units within a limited period.
The activities during the commissioning period are:
1. The construction of the plant as a whole must be checked in detail against
design and equipment specifications.
2. Chemical cleaning (boiling-out) of the waste heat boiler.
3. Commissioning of utility systems, instrumentation and testing of running
equipment.
4. Natural/Fuel gas intake and drying-out.
5. Loading of catalyst.
6. Heating-up and preparation for startup.
The unit area should be cleaned of all unnecessary construction materials, which
might burn, and the area around the unit should be cleared sufficiently to provide
complete safety of movement for operating and fire fighting personnel. This should
be carried out before the introduction of natural/fuel gas into the plant equipment. All
fire fighting and gas protection facilities within the unit should be available for
immediate use.
Page 28 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.1.1
4.1.1.1
Page 29 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
3. Add the Na3PO4 to the water content via a manhole etc. and close the manhole.
The vent remains open.
4. Supply LP steam via the steam hose to the boiler. Close the vent when steam is
discharged. Let the pressure rise to LP steam refinery pressure and close the
steam supply. Maintain the water level by blowing-down some boiler water each
1-2 hours. Wait until the pressure has dropped to 1 barg and repeat this step at
least 5 times.
5. After the 5th time of supplying LP steam to the boiler, wait until the pressure has
dropped to 1 barg. Then open the vent. Drain the total boiler content.
6. Clean the boiler by supplying boiler feed water to normal level and drain the
contents. Repeat this several times until the water is clear and has obtained a
pH of approximately 9. If scaling material still comes out of the boiler after
several water washes, it is advised to repeat the scaling removal procedure
(step 2). Make sure that no air can enter the boiler after the cleaning (new rust
formation). Air ingress can be prevented by keeping the boiler under nitrogen
pressure or steam pressure. During cleaning with water, special attention should
be paid to removal of scale and rust at instrument connections.
4.1.1.2
Sulfur Condensers
Removal of scale is not required. Therefore only the removal of oil and grease is
applicable.
Follow the method as described in Step 1 for the Waste Heat Boiler. The steam
supplied should be LP steam instead of MP steam. On conclusion, clean the
condenser by supplying boiler feed water to normal level and drain the contents.
Repeat this several times until the water is clear and has obtained a pH of 9.
Page 30 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.1.2
Page 31 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
maximum. Repeat the same, then using the main air controller FCV-046.
What about air lines to Incinerator, Degassing Vessel and jump over line.
When the blow-through/testing operation is completed, the air supply to the
burner is closed with RBV-045. Shutdown the blowers.
4. Check the positions of all non-return valves located in the steam pipe work,
associated with the boiler, condensers and steam heaters. Grease and exercise
all valves, especially plug valves.
Ensure that all level gauge glasses and instruments are clean.
5. It is strongly advised to strip down the burner and ignition lance for cleaning.
Check the burner sight glasses.
6. Slowly supply MP steam to the plant heating system (5LP Header), utilising the
Desuperheater 13DS-2 with LP Condensate (Hot Water) acting as the quench.
However, before systematically commissioning each individual steam trap, open
all low drain points, thereby flushing any dirt out of the pipe work.
When the condensate emitting from the above mentioned drain points run clean,
the steam traps are commissioned and the drain valves are closed, thereby
directing all condensate to the condensate system.
Ensure that the condensate disposal system has been commissioned.
7. Check all steam traced and steam jacketed equipment and lines for heating
efficiency, using thermal crayon or a lump of sulfur.
8. Ensure all valves downstream of the isolating blinds of the boiler feed water
supply lines situated at the battery limit are closed and reposition the isolating
blinds to open position.
9. Commission boiler feed water to the waste heat boilers and the sulfur
condensers as follows:
Waste heat boilers 13E-01/11
Ensure that all boiler feed water valves at the waste heat boiler are closed.
Commission the level control loop of the waste heat boiler. The control valve
will open.
Open fully the battery limit valve of the boiler feed water supply line.
Open the vent on the waste heat boiler.
Open cautiously the block valve upstream the control valve and flush clean
the boiler feed water line up to the bleeders of the control valve until the
water becomes clear.
Page 32 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Open fully the valves located downstream of the control valve, with the
exception of the block valve. Make sure that the bypass is closed.
Open slightly the block valve in the boiler feed water line at the waste heat
boiler to prevent hammering and start filling.
Open the drain valve of the waste heat boiler to drain initial dirty water, until
the water becomes clear.
Close the drain valve and establish a normal operating level.
Maintain a constant check on the level gauge during filling. The low level
alarm lights will be automatically extinguished. When the control valve is fully
closed, fully open the block valve at the waste heat boiler.
1st, 2nd, 3rd Sulfur condensers 13E-02/04/06
The following applies to combined 1st, 2nd, and 3rd sulfur condensers 13E02/04/06.
Ensure that all boiler feed water valves at the condensers are closed.
Commission the level control loops of the condensers. The control valves will
open.
Open fully the battery limit valve of the boiler feed water supply line.
Open the vents on the condensers.
Open the block valve upstream the control valve and flush clean the boiler
feed water line up to the bleeders of the control valve until the water
becomes clear.
Open fully the valves (located downstream of the control valve, with the
exception of the block valve. Make sure that the bypass is closed.
Open slightly the block valve in the boiler feed water line at the condensers to
prevent hammering and start filling.
Open the drain valve of the condensers to drain initial dirty water, until the
water becomes clear.
Close the drain valve and establish a normal operating level.
Maintain a constant check on the level gauge during filling. The low level
alarm lights will be automatically extinguished. When the control valve is fully
closed, fully open the block valve at the condenser.
4th Sulfur condenser
Ensure that the globe valve in the boiler feed water supply line at the
condenser is closed. Open the block valve near the condenser inlet.
Open the vent on the condenser.
Open slightly the globe valve in the boiler feed water line to prevent
hammering and start filling.
Page 33 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Open the drain valve of the condenser to drain initial dirty water, until the
water becomes clear.
Close the drain valve and establish a normal operating level.
Maintain a constant check on the level gauge during filling. The low level
alarm lights will be automatically extinguished. When the normal level has
been established, the globe valve in the boiler feed water line should be
closed.
11. Ensure that sulfur lines, sulfur locks and sulfur pit are completely free of foreign
materials.
12. Fill all sulfur locks with solid or liquid sulfur by removing the top blind flange.
Ensure that the individual locks are completely filled before re-installing the blind
flanges.
13. Ensure that the discharge valves of the sulfur pumps and valves in the sulfur
rundown lines are closed.
14. Leak testing of the unit has to be carried out with nitrogen or maximum available
air blower pressure.
Special attention should be paid to the acid gas feed system.
15. Check if the igniter functions properly by testing it outside the burner.
16. Commission the following control loops:
Temperature control loops of the reactor inlets (TCV-078, TCV-089, and
TCV-098).
Steam pressure controllers of the 4th condenser 13E-08: PC-106, acting on
the steam condenser and PC-411B, acting on the steam blow-off line. The
initial set point of PC-411A should be 1.8 barg.
Pressure controllers in HP steam and 5LP steam.
Relevant loops in the utility systems.
Page 34 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.2
4.2.1
Introduction
Prior to the initial startup phase of the unit, it is necessary to accomplish a complete
drying out of the reaction furnace and incinerator. This is performed by increasing
the temperatures at a controlled rate of 15 to 20C per hour, until a temperature of
300C is reached.
After about 52 hours the drying out phase is complete (see figure 2) and the heating
up of the reaction furnace can be continued until the operating temperatures are
reached.
Next, the unit is cooled-down to enable loading of the catalyst.
In the initial startup phase, the incinerator should only be started when the Claus
section produces an off-gas, as this gas acts as a cooling medium allowing for a
gradual heating-up of the thermal incinerator. Once the incinerator is hot, it can be
operated without Claus tail gas.
Remarks
1. The drying-out and heating-up procedures as described below, indicated in
figure 2, are to be considered as guidance only. The refractory lining
manufacture should supply dedicated drying out curves for all refractory.
Simplified Outline
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Remove all isolating blinds, except for feed gases and oxygen.
Reset the logic system.
Start the air blower.
Commission the remaining utility systems.
Dry-out the unit with hot air.
Purge the main burner with nitrogen.
Admit natural gas to the main burner.
Start the reheaters of the catalytic reactors.
Start the incinerator burner.
Further dry-out and heat-up the unit.
Page 35 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.2.2
Detailed Outline
Preparations
1. All isolating blinds situated at the unit and battery limits are removed, except at
acid feed gas lines.
2. Check the permissives to start the main burner.
Check the liquid level in the waste heat boiler (LT-072/073).
Ensure that natural gas for the main burner is available (PI-061).
Ensure that the emergency shutdown switches HY-070/071 and RBV064/066 are in the correct position.
3. Reset the logic system for the main burner by HS-217.
4. Start one of the air blowers. Confirm that the blower vents properly to the
atmosphere to prevent surging.
5. Commission all utility systems.
6. Open the air supply to the main burner with RBV-045. Adjust an initial air flow
rate of 30% on FCV-047 trim air controller. Gradually increase the air flow to
maximum. Repeat using the main air controller FCV-046.
4.2.2.1
Page 36 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
case ignition is hard to obtain with this flow rate, it can be manually increased
within a certain range by varying the output of controller FCV-046/047. The
natural gas flow rate is such that the combustion is stoichiometric. In addition,
the natural gas flow (FCV-062) can be manually adjusted within a certain range.
The settings are determined empirically.
Remark
Normally the burner can be started quickly with the predefined positions on the
air and natural gas controllers. These settings correspond with stoichiometric
combustion at the minimum air flow with the corresponding natural gas flow.
However, due to the actual burner dimensions and location of the tip of the
igniter, it is sometimes easier to obtain ignition at other flow rates. This should
be empirically found. Once these flow rates have been adjusted in the DCS,
they can be used for subsequent startups.
4. One minute after ignition following controllers are accessible for the operator.
FCV-047, acting on the trim air valve.
FCV-046, acting on the main air valve.
FCV-062, natural gas.
5. After establishing a stable flame, the size of the flame should be restricted.
Decrease the natural gas flow to its minimum value of 18 kg/h and adjust the air
flow to 987 kg/h. This results in a 330% of stoichiometric burn, i.e. with 230%
excess air.
Switch FCV-062 (natural gas) and FC-046 (combustion air) to AUTO mode.
After switching FC-046 to CASCADE, the ratio between natural gas and air can
be adjusted with HS-206. FC-047 can be taken into operation to allow the
operator to increase the air flow during warming-up.
4.2.2.2
Page 37 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4.2.2.3
4.2.2.4
4.2.2.5
Start of incinerator
When the main burner is in operation, sufficient off-gas is produced to start heatingup procedure of the incinerator.
Reference is also made to the Safeguarding narrative.
Document no 20507-64566-13/P.02/0015
1. Check the permissives to start the incinerator burner.
Check the liquid level in the incinerator waste heat boiler (LT-179/180).
Ensure that fuel gas for the incinerator burner is available (PT-159).
Ensure that the emergency shutdown switches are in the correct position
(HS-166/167 for the incinerator).
2. Reset the logic system for the incinerator by HS-257.
3. Start the incinerator air blower. Confirm that the blower vents properly to the
atmosphere to prevent surging.
Page 38 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4. Commission the instrument air supply for purging to prevent sooting of the flame
scanner and sight glasses.
5. The ignition sequence is started with an air purge of the incinerator and
proceeds automatically until ignition is obtained. Open RBV-144 by actuating
HS-258. Ensure that the air flow is above the trip setting of FALL-147. The
purge is completed after 3 minutes.
6. When the purge is completed, the next step is automatically started. The igniter
is inserted and energized and the fuel gas valves are opened. Within 5 seconds
ignition should be obtained, otherwise the unit is tripped.
In case ignition is hard to obtain at the pre-defined air flow rate, it can be
manually increased within a certain range by varying the output of controller
FCV-146. The fuel gas flow rate is such that the combustion is stoichiometric. In
addition, the fuel gas flow (FCV-160) can be manually adjusted within a certain
range. The settings are determined empirically.
Remark
Normally the burner can be started quickly with the predefined positions on the
air and fuel gas controllers. These settings correspond with stoichiometric
combustion. However, due to the actual burner dimensions and location of the
tip of the igniter, it is sometimes easier to obtain ignition at other flow rates. This
should be empirically found. Once these flow rates have been adjusted in the
DCS, they can be used for subsequent startups.
7. One minute after ignition following controllers are accessible for the operator.
FCV-146, primary air.
FCV-148, staged air.
FCV-160, fuel gas.
8. After establishing a stable flame, the size of the flame should be restricted.
Decrease the fuel gas flow to its minimum value of 29 kg/h and adjust the air
flow to 356.5 kg/h. This results in a 330% of stoichiometric burn, i.e. with 230%
excess air. Switch FCV-160 (fuel gas), FCV-146 (primary air) and FCV-148
(staged air) to AUTO mode.
After switching FCV-146 to CASCADE, the ratio between fuel gas and air can
be adjusted with HC-160C. The staged air flow on FCV-148 should initially be
maximum to provide as much cooling as possible.
Remark
During the initial startup the off-gas from the main burner provides sufficient cooling,
so that a gradual heating-up is obtained. Once the refractory in the incinerator is
Page 39 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
dried-out, a faster temperature rise is allowed. Therefore, at the next startup the
incinerator is started before the main burner.
4.2.2.6
Page 40 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
2. The generation of steam from the waste heat boiler starts with increasing heat
input. When a large amount of steam is exhausted, the vent is closed.
Check again that the condensate disposal system has been correctly
commissioned.
4.2.2.7
4.2.2.8
Page 41 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Figure 2: drying out & heating up (to be confirmed with refractory vendor information)
Temperature
1200C
drying-out
heating-up
1000C
800C
Comb. Chamber
Incinerator
600C
400C
Claus reactors
SUPERCLAUS reactor
200C
0C
0
20
Page 42 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
40
52
60
80
100
Time (hours)
120
CATALYST LOADING
After the initial drying-out and heating-up procedure, the unit is shut down to allow
opening of the equipment to start loading of catalyst into the reactors.
4.3.1
3. Close the steam supply to the 4th condenser and the blow-down valve.
4. The unit will gradually cool down.
5. Close the natural gas supply to the main burner with HS-219. The air is
automatically tripped as well.
6. Shutdown the incinerator.
7. Reset the logic system for the main burner by HS-218.
8. Open the air supply to the main burner with HS-206. Adjust an initial air flow
rate of 30% on FC-046. Gradually increase the air flow to maximum. Both
control valves FCV-046 and FCV-047 can be used.
9. Install spectacle blinds in the natural gas at the battery limit.
10. When the temperature is no longer decreasing, open the upper manhole on the
reactor.
11. As soon as the reactor temperatures are sufficiently low, catalyst loading can
take place.
4.3.2
Catalyst loading
1. Remove the pipe or bellow between the reactor outlet and the condenser inlet
and place a temporary blind at the condenser inlet. In this way, no catalyst dust
will come into the condenser.
2. Check the interior of the reactor for cleanliness, with particular attention to the
area beneath the support grid.
3. Indicate on the wall the required heights for ceramic balls and catalyst. The
height of the catalyst bed is approximately 10% higher than indicated on the
data sheet. After some time of operation, the bed height specified in the data
sheet will be obtained as the catalyst density will increase to the normal bulk
packed density.
4. First reactor
From the top of the grid support, the following heights are applicable:
Bottom layer (support balls): indication at 100 mm.
The bottom layer (height: 100 mm) consists of 6 mm ceramic balls for
support of the catalyst bed.
Bottom catalyst layer (CRS-31): indication at 814 mm.
The bottom catalyst layer (normal height: 740 mm) consists of CRS-31
catalyst. Initially the catalyst bed is 10% higher than indicated on the
equipment drawing. The catalyst will shrink to its normal height after some
time of operation.
Top catalyst layer (CR-3S): indication at 286 mm.
The top catalyst layer (normal height: 260 mm) consists of CR-3S catalyst.
Initially the catalyst bed is 10% higher than indicated on the equipment
drawing. The catalyst will shrink to its normal height after some time of
operation
5. Second reactor
From the top of the grid support, the following heights are applicable:
Bottom layer (support balls): indication at 100 mm.
The bottom layer (height: 100 mm) consists of 6 mm ceramic balls for
support of the catalyst bed.
Catalyst layer (CR-3S): indication at 1100 mm.
The catalyst layer (normal height: 1000 mm) consists of CR-3S catalyst.
Initially the catalyst bed is 10% higher than indicated on the equipment
drawing. The catalyst will shrink to its normal height after some time of
operation.
6. Third reactor
From the top of the grid support, the following heights are applicable:
Page 44 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
General remarks
Care must be taken to minimize the creation of catalyst fines during the loading
of the reactors. Catalyst dust and fines are to be removed with the help of an air
flow through the reactor.
For this reason, the pipe between reactor outlet and condenser inlet should be
removed and a temporary blind at condenser inlet should be installed.
This procedure has to be followed for each reactor separately.
During catalyst loading some dust is produced which should not be inhaled.
Personnel who are outside the reactor during loading should wear dust masks.
Inside the reactor, a positive pressure air mask should be worn. Eye contact
and prolonged skin contact with the catalyst should be avoided by wearing the
relevant protective clothing.
The catalyst bed heights indicated on the reactor walls are approximately 10%
higher than indicated on the equipment drawings. After some time of operation, the values of
the equipment drawings will be obtained when the catalysts have been settled.
The catalyst should be protected against water.
Page 45 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
5.0
STARTUP
5.1
Start of incinerator
1. Check the permissives to start the incinerator burner.
Check the liquid level in the incinerator waste heat boiler (LYLL-180).
Ensure that fuel gas for the incinerator burner is available (PYLL-272).
Ensure that the emergency shutdown switches are in the correct position (HS166/167).
2. Reset the logic system for the incinerator by HS-257.
3. Start the incinerator air blower. Confirm that the blower vents properly to the
atmosphere to prevent surging.
4. Commission the instrument air supply for purging to prevent sooting of the
flame scanner and sight glasses.
5. The ignition sequence is started with an air purge of the incinerator and
proceeds automatically until ignition is obtained. Open RBV-144 by actuating
HS-258. Ensure that the air flow is above the trip setting of FYLL-147. The
purge is completed after 3 minutes.
6. When the purge is completed, the next step is automatically started. The igniter
is inserted and energized and the fuel gas valves are opened. Within 5 seconds
ignition should be obtained, otherwise the unit is tripped.
In case ignition is hard to obtain at the pre-defined air flow rate, it can be
manually increased within a certain range by varying the output of controller
FC-146. The fuel gas flow rate is such that the combustion is stoichiometric. In
addition, the fuel gas flow (FC-256) can be manually adjusted within a certain
range. The settings are determined empirically.
7. One minute after ignition following controllers are accessible for the operator.
Page 46 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Page 47 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
the natural gas flow (FC-062) can be manually adjusted within a certain range.
The settings are determined empirically.
Remark
Normally the burner can be started quickly with the predefined positions on the
air and natural gas controllers. These settings correspond with stoichiometric
combustion at the minimum air flow with the corresponding natural gas flow.
However, due to the actual burner dimensions and location of the tip of the
igniter, it is sometimes easier to obtain ignition at other flow rates. This should
be empirically found. Once these flow rates have been adjusted in the DCS,
they can be used for subsequent startups.
7. One minute after ignition following controllers are accessible for the operator.
FC-046, acting on the trim air valve.
FC-047, acting on the main air valve.
FC-062, natural gas.
8. After establishing a stable flame, the size of the flame is restricted. Decrease
the natural gas flow to its minimum value of 18 kg/h and adjust the air flow to
987 kg/h. This results in a 330% of stoichiometric burn, i.e. with 230% excess
air.
Switch FC-062 (natural gas) and FC-046/047 (total air) to AUTO mode.
After switching FC-062 to CASCADE, the ratio between natural gas and air can
be adjusted with HC-062. FC-047 can be taken into operation to allow the
operator to increase the air flow during warming-up.
Page 48 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Remarks
Please note that the above procedure only applies when the unit does not
contain sulfur, since excess air is introduced. At temperatures above 200C in
combination with the presence of sulfur, excess air may lead to sulfur fires.
Reference is made to Section 2.5 "Actions in case of automatic shutdown
(Trip)" for the startup procedures in case sulfur is present in the unit.
The presence of sulfur in the unit after a shutdown should be avoided.
Reference is made to Section 2 for the proper shutdown procedures.
After a trip, the unit is brought on-stream as soon as possible. Then the unit is
still hot, so introduction of excess air for cooling is not required and should be
avoided. Natural gas shall be burnt substoichiometrically, see also remark a).
Page 49 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
5.2
Range
H2S
0.2 - 7
vol.%
H2S
(H2S + SO2)
SO2
O2
100 - 2000
0.2 - 7
50 - 8000
5 - 23
ppm vol
vol.%
ppm vol
vol.%
Page 50 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
1000 - 1300
240
750 - 800
C
C
C
11. Check the supply of air and nitrogen for purging the flame scanners and the
sight glasses.
12. Make tools such as locks, keys, valve handles, wrenches, sealing tape and
soap for leak testing available.
13. Check if the H2S monitor for personnel protection has been commissioned and
set at the correct alarm setting.
14. Ensure that the sulfur locks are filled with liquid sulfur.
15. Commission the tail gas H2S/SO2 analyzer.
16. Take care that a portable O2 analyzer for stack gas is available.
17. Check the level in the Acid gas knock-out drum 13D-01.
18. Check the level in the Sour gas knock-out drum 13D-02.
Page 51 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
5.3
5.3.1
Simplified Outline
Adjust the air and natural gas flows to the main burner
Adjust the "air-to-amine acid feed gas" ratio as well as the "air-to-SWS acid
feed gas" ratio.
Admit amine acid feed gas to the main burner.
Switch the flow control for the amine acid feed gas to AUTO and gradually
increase its feed gas flow.
Stop the natural gas supply to the main burner when desired.
Regenerate the Claus catalyst if required.
Increase the feed gas flow to the maximum available quantity.
Adjust the inlet temperatures of the Claus reactors to design conditions.
Admit SWS acid feed gas when desired.
1.
2.
3.
4.
5.
6.
7.
8.
9.
5.3.2
Detailed Outline
Adjusting air and natural gas
Adjust the natural gas combustion in the main burner to 95% of stoichiometric
combustion (HC-062). Note that FC-062 is in CASCADE mode and that FC-047
should be switched to CASCADE before feed gas intake.
Page 52 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8. Switch AC-111 to AUTO mode and maintain the (H2S-2SO2) value at -0.5 vol.%
9. Check the H2S content in the process gas from the fourth condenser with
Drger tubes and compare this with the H2S analyzer.
10. Ensure that sulfur is running by opening the funnels. Use air masks and eye
protection equipment, refer to Section 7.2.
11. Check the O2 content of the incinerator flue gas with Drger tubes or portable
analyzer. It should be approx. 1.6 vol.%.
12. As soon as the unit runs stable, the natural gas supply to the main burner can
be stopped.
Decrease the natural gas flow with FC-062.
Stop the natural gas supply with HS-219 and close the quenching steam in
case it was in operation.
Note that the temperature in the combustion chamber must be kept above
930C when firing H2S acid gas in order to have a stable flame.
13. Increase the amine feed gas flow to maximum. When desired switch FC-018 to
CASCADE with the pressure controller that is located in the amine unit.
14. Decrease the Claus reactor inlet temperatures to the normal value of 240C
(first reactor), 210C (second reactor) and 195C (third reactor).
Page 53 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
5.4
5.4.1
5.4.2
Page 54 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
5.5
Page 55 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
6.0
6.1
SHUTDOWN
GENERAL
A proper shutdown procedure is most important. Sulfation of the catalyst, plugging
after restart and corrosion are mostly the result of misoperation or wrong
procedures during shutdown. Therefore, a scheduled shutdown should be carefully
carried out.
During normal operation sulfur vapor is absorbed in the pores of the Claus catalyst.
Prior to a scheduled shutdown it is necessary to remove the sulfur from the catalyst
to prevent that the sulfur inside the catalyst is exposed to air at elevated
temperatures, which results in runaway temperatures. The procedure also prevents
sulfur solidification inside the catalyst.
For this purpose, the inlet temperatures of the Claus reactors are raised 15C to
30C above the normal operating temperature and operated at this temperature for
48 hours prior to shutdown.
In this way the absorbed sulfur is removed from the catalyst pores and is
subsequently condensed in the sulfur condensers and drained to the sulfur pit. This
operation is called heat soak.
After 48 hours of operation at elevated temperature, the feed gas supply is stopped
and the unit is purged with inert gas.
The inert gas is obtained by substoichiometric combustion (substoichiometric
means shortage of air) of natural gas and air in the main burner. The
substoichiometry can visually be checked by means of the flame color. Blue means
excess air, pink blue means stoichiometric combustion, pink means slightly
substoichiometric combustion and yellow means deep substoichiometric
combustion.
Steam is supplied to the burner to prevent overheating of the reaction furnace.
Moreover, it increases the inert gas flow through the unit. The steam to natural gas
ratio is approximately 4 on weight basis.
During this operation the air flow to the main burner is 68.4 kg/h at a natural gas
flow of 36 kg/h. Steam for cooling is approximately 140 kg/h.
When it is planned to shutdown the unit completely, the inlet temperatures of the
Claus reactors are raised as high as possible during the substoichiometric natural
gas combustion in the main burner. This operation is called sulfur stripping. No
excess air should be introduced via the main burner during this operation as the air
will react with the sulfur on the catalyst which may result in too high a catalyst
temperature and sulfation of the catalyst.
On the other hand, the incinerator should be operated with excess air to convert
any sulfur vapor into sulfur dioxide.
Page 56 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Page 57 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Page 58 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
6.2
6.2.1
6.2.2
Detailed Outline
Reducing feed gas flows and increasing reactor inlet temperatures
1. Switch FC-023 to AUTO mode and reduce the SWS acid feed gas flow,
followed by a complete stop with HS-203.
2. Switch FC-018 to AUTO mode and reduce the Amine acid feed gas flow to
30%.
3. Increase the inlet temperatures of the first, second and third reactor as high as
possible. Maintain this situation for 48 hours.
4. Open the natural gas supply to the main burner with HS-219. Adjust a flow rate
of 58 kg/h, corresponding with the hot standby flow.
Shut off the feed gas
1. Start the steam supply to the main burner (HS-220) in order to avoid too high a
temperature in the combustion chamber.
2. Stop the feed gas flow with HS-202. By doing so, also AC-111 is switched to
MANUAL mode. The steam supply to the main burner should now be 15 kg/h.
Note that it is essential that the steam to natural gas ratio is approximately 4
(on weight basis).
Maintain the acid gas preheater in operation.
3. Ensure that the combustion in the main burner is substoichiometric.
4. Open the steam supply to the steam coils in the sulfur pit.
5. Close the hand valves in the boiler water supply and return lines of the sulfur
cooler.
Page 59 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
6.3
6.3.1
Simplified Outline
1. Stop the SWS acid gas feed supply and reduce the Amine acid gas feed flow to
30%.
2. Make the Claus reactor inlet temperatures as high as possible at 48 hours prior
to feed gas shut-off.
3. Commission natural gas and steam to the main burner and shut-off the feed
gas.
4. Raise the Claus reactors inlet temperatures as high as possible and maintain
these conditions for at least 24 hours.
5. Make a plot of the Claus reactor temperatures and the SO2 content in the tail
gas.
6. Reduce the Claus reactor bed temperatures to 200C.
7. Slowly introduce excess air to remove the remaining sulfur and FeS from the
unit.
8. Keep all plant heating systems in operation.
9. Gradually cool down the unit.
10. Shutdown the incinerator.
6.3.2
Detailed Outline
Initially follow the shutdown procedure for short period (Section 3.2.2).
Strip sulfur from the catalyst
1. Check the natural gas and air supplies to the main burner. The air to natural
gas ratio should be slightly substoichiometric.
Check the O2 content in the flue gas from the main burner.
2. Make the inlet temperatures of the Claus reactors as high as and maintain
these temperatures for at least 24 hours.
3. Keep all plant heating systems in operation.
4. Make a plot of the top, bottom and outlet temperatures of the Claus reactors.
Take readings every 5 minutes for the first hour and every 15 minutes
thereafter.
Make also a plot of SO2 content in the tail gas. Take readings every 10 minutes
during the first hour and every 30 minutes thereafter.
5. If the temperature in a reactor tends to rise above 350C, the corresponding
steam reheater should be shutdown. Restart the steam reheater when the
reactor temperature has dropped below 150C.
If the temperature still tends to rise to 380C, it might be considered to inject
nitrogen into the reactor inlet.
A temperature of 400C is the absolute maximum for the catalyst bed.
Page 60 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
1000 - 1400
250
750
C
C
C
Page 61 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
limit. When it is necessary to open the sulfur lines and locks, the locks can be
emptied by blowing with steam or nitrogen.
Otherwise, sulfur may be kept as liquid in the sulfur locks by maintaining the
supply of heating steam.
10. Block-off the boiler feed water supply and close the blow down valves at the
waste heat boiler and sulfur condensers.
11. Vent and drain the waste heat boiler and sulfur condensers if necessary.
12. Check if all shutdown valves are closed.
13. Install spectacle blinds at the battery limits, except for the LP steam for internal
heating.
Remark
During the shutdown phase it must be constantly born in mind that a rapid
temperature drop is undesirable because:
Lining materials may be damaged.
High thermal stresses or contraction may deform piping and equipment,
causing leaks after a restart.
Solidification of sulfur may occur.
Page 62 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
6.4
6.4.1
1000 - 1300
240
750 - 800
C
C
C
6.4.2
Restart when the Unit is Cold and Sulfur is inside the Equipment
1. Start the incinerator (see Section 2.1).
2. Start the purge/ignition procedures for the main burner (see Section 2.1).
3. After establishing a stable fuel gas flame, adjust the minimum design air flow of
987 kg/h through the trim air line and a fuel gas flow of 440 kg/h, corresponding
with 15% to 20% overstoichiometric combustion. Steam cooling is not allowed,
as it will condense on the cold walls of the downstream equipment. Only admit
steam to the burner when all equipment have reached a temperature of at least
80C.
When available, nitrogen can be supplied to the burner for cooling. Carefully
watch the temperature in the combustion chamber. In case the temperature
rises too rapidly, the burner should be stopped temporarily.
Watch the unit temperatures carefully. Be aware that sulfur fires may start, as
excess air is present. Ignition of FeS on the equipment walls might also occur.
Page 63 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
4. Start the reheaters. Slowly increase the temperatures of the reactor beds. The
Claus reactors temperatures should be restricted to 120C to avoid a sulfur fire
in the catalyst.
5. As soon as the equipment temperatures are above 80C steam can be supplied
to the main burner. Increase the natural gas flow to 58 kg/h to obtain
substoichiometric combustion. From now on, it is easier to have the
temperatures under control.
6. Continue with the heating-up procedure for the combustion chamber, incinerator
and reactor stages (see Section 2.1). The temperature rise in the combustion
chamber and incinerator is maximum 50C.
7. Adjust following temperatures:
Combustion chamber
Claus reactors inlet
Incinerator
1000 - 1300
240
750 - 800
C
C
C
6.4.3
Page 64 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.0
SAFETY
The following information deals with the prevention of possible dangerous situations
encountered in the Sulfur Recovery Unit.
7.1
Page 65 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.2
Page 66 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
c. Eye protection
To prevent irritation of the eyes full goggles with water dams are recommended.
The water dams prevent fogging of the lenses, which should be made of safety
glass.
Page 67 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.3
Page 68 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.4
TOXICOLOGICAL DATA
Tables of H2S and SO2 effects are given below, followed by a summary of some of
their properties.
7.4.1
Effect
vol.%
1.
0.14
2.
0.77
3.
Noticeable odor
4.6
4.
Obnoxious odor
7.0
5.
MAC2)
10
0.001
6.
50 - 100
0.005 - 0.010
78 - 128
0.008 - 0.013
170 - 255
0.017 - 0.026
198 - 283
0.020 - 0.028
200 - 300
0.02 - 0.03
11.
355 - 496
0.036 - 0.050
12.
425 - 580
0.043 - 0.058
13.
500 - 700
0.05 - 0.07
14.
700 - 1000
0.07 - 0.10
7.
8.
9.
10.
0.085 - 0.2
1)
Page 69 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.4.2
Effect
vol.%
1.
2.
7.4.3
0.002
0.005 - 0.010
0.040
Page 70 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.4.4
7.4.5
Sulfur Dust
Sulfur dust in the atmosphere has a highly irritating effect upon the human eye.
Therefore, safety goggles should be worn when working in an atmosphere where
dust contaminates the air. This cannot be overemphasized.
Page 71 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
7.5
Page 72 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.0
8.1
TROUBLE SHOOTING
INTRODUCTION
The aim of this section is to draw the attention of operating personnel to some
undesirable conditions which may arise during otherwise normal operation and to
the means to prevent or remedy them. For other conditions not normally
encountered, see Section 6.5 ("Automatic Shutdown").
The operating problems in a sulfur recovery plant can be categorized into process
and mechanical problems. The process problems and operational hazards are
related to the sulfur recover unit such as poor sulfur recovery, pressure drop
problems, sulfur plugging and temperature runaways are discussed in this Section.
Mechanical problems which can occur are related to the bearings of running
equipment, ignition of burners, boiler leakage, refractory material and corrosion.
8.2
8.2.1
PROCESS PROBLEMS
General
a. Sudden temperature changes should be avoided whenever possible, since they
might cause leaks at flanges or loosening of iron sulfide scale from the
equipment walls.
b. During startup the acid gas shall not be burnt with too much air. It would result
in high flame temperatures that could damage the lining of the combustion
chamber and the tube plate of the waste heat boiler, if they are subjected to this
condition during a prolonged period of time. Moreover, the SO2 emission from
the stack would be excessively high.
c.
H2S and SO2 are extremely poisonous gases. Utmost care must be taken to
avoid exposure of personnel and environment to these gases, e.g. when
draining H2S containing liquid or when taking gas samples.
In special circumstances, protective masks must be worn (see Section 7).
d. The lower and upper explosion limits of H2S in a gas air mixture are 4.3 and
45.5 vol.%, respectively. In the stoichiometric ratio with air, it explodes violently
when ignited.
e. At a temperature of approximately 230C, auto-ignition of liquid sulfur will occur
when in contact with air. Sulfur dust will ignite at approximately 190C.
Page 73 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
f.
The waste heat boilers and condensers need to be checked regularly for the
boiler water quality. For this purpose, use the sample cooler to retrieve the
sample. In view of deposits in the sample lines and for the sake of good
sampling, flush the sample line at least for 10 minutes before taking a sample.
The maximum allowable total concentration of solids in the waste heat boiler is
3000 ppm, of which a maximum 250 ppm of suspended solids is permitted. The
maximum allowable total concentration of solids in the sulfur condensers is
3500 ppm with maximum 300 ppm of suspended solids.
Higher figures might lead to dirt and scale deposition and finally to damage of
the boiler and condensers. The concentration of solids can be adjusted by
varying the blowdown rate.
8.2.2
By a high unit pressure alarm the operator can first shutdown the SWS feed gas
supplies. In this way the unit throughput is reduced and the unit pressure will
decrease.
During the (natural gas) ignition stage in the main burner, the maximum amount
of natural gas allowed to be present inside the burner/combustion chamber is
restricted to avoid an excessive pressure rise when the actual ignition takes
place. For this reason the burner/combustion chamber are purged before
admitting natural gas to remove any combustibles that might be left from a
previous ignition trial.
The equipment is capable to stay leaktight after a pressure rise during ignition
or explosion, but the internals may be damaged.
Page 74 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.2.3
Reactor Stages
a. Runaway temperatures in the Claus reactors should be avoided during hot
standby and shutdown. When the temperature tends to rise to 350C the air - to
natural/acid gas ratio at the main burner should be reduced in order to obtain
substoichiometric conditions, and/or nitrogen can be introduced. Introduce 5 LP
Steam to the reactor for additional cooling (see also section 8.2.9).
b. Care should be taken that the ratio fuel gas-air at the main burner is correct.
Too little air might result in deposition of soot on the catalyst bed (higher
pressure drop and less sulfur conversion) and too much air in sulfation of the
catalyst (less sulfur conversion).
Soot, however, can only be removed during a shutdown period by replacing the
top layer of the catalyst bed.
c.
8.2.4
Incinerator
a. The incinerator is started-up before the main burner to convert any hazardous
gas, which might leave the unit during the purging and ignition phases of the
main burner.
b. To prevent damage of the burner, it is strongly advised to operate the air side of
the burner at a pressure drop of at least 1.2 mbar.
Page 75 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.2.5
8.2.6
Another cause of low sulfur recovery can be a poor acid gas/air ratio control. In
refineries, often the acid gas composition is not known and usually it fluctuates
during operation. The H2S/SO2 analyser corrects for this, but it is advised to
adapt the air/acid gas ratio if there is a continuous correction by the analyzer.
d. Good sulfur separation after each condenser is also important. For this
purpose, all sulfur condenser outlet channels have been provided with demister
pads. Furthermore, a coalescer with demister downstream the last condenser
has been provided.
e. In the main burner, COS and CS2 are formed as by-products. They are present
especially when large amounts of CO2 and/or hydrocarbons are present in the
feed gas. If they pass through the unit untouched, they account for some loss of
sulfur recovery. However, at a sufficiently high temperature (higher than 300C),
COS and CS2 are largely hydrolyzed to H2S in the first Claus reactor. Therefore
it is important to maintain the 1st reactor outlet temperature above 300C.
Page 76 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.2.7
Pressure Drop
Soot, corrosion products such as FeS or refractory fines or ammonium salts can be
the cause of an increasing pressure drop over the unit.
Soot is formed when hydrocarbon carry-over from the amine regeneration units
occur. The flow ratio controller cannot follow such upsets, and hydrocarbons are
carried through the whole unit and too little H2S is burnt in the main burner.
Sometimes a fire starts in the incinerator and/or stack due to combustion of large
quantities of H2S.
Soot is deposited on the catalyst and the sulfur produced is brown or black under
such conditions. Hydrocarbon carry-over can be prevented by better operation
and/or modifications to the amine regeneration units.
Another possibility of soot formation occurs when the burners are fired at very low
air/natural gas ratios. It is recommended to keep the ratio at 90 - 95% stoichiometry.
This can be checked visually by observing the color of the flame, which should be
salmon pink when natural gas is fired. Always stay above 80% stoichiometry to
prevent soot formation.
A common refinery regeneration procedure to remove soot is to burn off the soot at
500C flame front temperature. This procedure, however, is not recommended as
this high temperature will promote sulfur fires and sintering of the catalyst. Jacobs
Nederland B.V. policy is to replace 10 cm top layer of the catalyst as standard
procedure at each turn-around or at shutdown caused by too high pressure drop.
Sulfur demisters may be plugged by sulfur. Therefore, all demisters have been
located in an outlet channel provided with a steam tracing to keep the outlet
channel hot. The demisters can easily be removed through the drawers.
The pressure drop in a sulfur recovery unit is proportional to the square of the
throughput. Operators should daily check the plant pressure drop to make sure they
notice early warnings in case the pressure drop starts to deviate. To simplify their
work the pressure drop can be said to be proportional to the square of the air flow.
As the pressure drop, divided by the square of the air flow, should be a constant
figure, early warning of pressure drop problems can be found by daily plotting this
ratio.
8.2.8
Plugging
Sulfur plugging
Sulfur plugging problems are usually experienced in sulfur lines and sulfur locks.
When plugging is caused by pure solid sulfur, for example due to a malfunctioning
steam trap, is easily removed by heating. Sulfur, however, in combination with
corrosion products, refractory and/or catalyst fines may give grey sulfur (concrete
sulfur) which is difficult to remove. At initial startup the catalyst beds should be air
Page 77 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
blown to remove fines (see Section 4.5). Careful cleaning of the tubes of waste heat
boiler, sulfur condensers, sulfur lines and sulfur locks will eliminate plugging
problems at startup.
Temperature Runaways
Fire inside the Claus reactors
During the shutdown phase and hot standby operation a rapid temperature rise in
one of the catalyst beds (temperature runaway) may occur when too much air is
supplied to the main burner. Then the sulfur, absorbed in the catalyst, reacts
violently with the oxygen in the air, resulting in a fire. A fire inside the reactor bed
Page 78 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Page 79 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.3
MECHANICAL PROBLEMS
8.3.1
Running Equipment
Problems with running equipment mainly concern bearings. The engineering
companies and manufacturers should pay proper attention to the bearing design to
prevent those problems. Sulfur pump bearings, for example, should have a
clearance of 0.6 mm and heating steam may not exceed 160oC because sulfur
viscosity rapidly rises above 155C, especially when degassed sulfur is pumped.
8.3.2
Ignitors
The main problems are ignition difficulties and damage to the ignitor tip by
overheating if they are not withdrawn properly after ignition. Ignition problems are
often caused by short circulating due to moisture. Another cause can be excessive
back pressure in the burner chamber, in combination with an inert gas atmosphere.
Overheating of the ignitor connection can be prevented by adequate
cooling/purging with either air or inert gas.
8.3.3
8.3.4
Refractory Material
Selection and correct installation of refractory material in Claus plants is important
to prevent cracking and collapse. Experience has shown that refractory lining for the
main combustion chamber should be made of brick. Concrete lining for these high
temperature applications gives disappointing results because of the difficulty of
making a homogeneous mixture when it is installed. Radiation walls, on the other
end, should preferably not be made of brick but of castable matrix blocks, fitted
together without using mortar. The advantage of such walls is that they can be
easily removed and reinstalled at turnarounds.
Refractory lining of the waste heat boiler tube sheet should be made of castable
material, such as (with a high Al2O3 content, >94%), in combination with ceramic
ferrules. The hot gas part of the incinerator should be made of bricks, refractory
linings of the incinerator can be made of castable material.
Page 80 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.3.5
8.3.6
Corrosion
Corrosion in Claus plants during normal operation is limited, if the related piping is
adequately steam heated and properly insulated. Severe corrosion may take place
when a Claus plant is out of operation for longer periods and the plant is
insufficiently purged and dried with inert gas. Corrosion is then caused by H2O, O2,
SO2 and CO2. Proper shutdown procedures and purging with a dry inert gas will
avoid severe corrosion problems. Leakage of acid gases to atmosphere has to be
prevented to avoid outside corrosion. Steel parts in the sulfur collecting pit are
sensitive to corrosion.
Page 81 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
8.4
PHENOMENON OBSERVED
COUNTERMEASURES IN
DESIGN/OPERATION
c.
2.
a.
b.
c.
d.
Page 82 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
REACTORS
a.
Accumulation of soot.
PHENOMENON OBSERVED
COUNTERMEASURES IN
DESIGN/OPERATION
b. Sulfation.
c. Temperature runaway.
(Claus reactors)
d.
e.
4.
REHEATERS
a.
5.
SULFUR CONDENSERS
a.
b.
6.
a.
b.
Steam leakage.
Page 83 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
PHENOMENON OBSERVED
c.
7.
a.
b.
COUNTERMEASURES IN
DESIGN/OPERATION
Page 84 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
9.0
MAINTENANCE
9.1
EQUIPMENT
9.1.1
a.
b.
c.
d.
e.
f.
Knock-out Drums
Clean the inside of the knock out drum from loose scale and dirt.
Clean the demister mat with steam.
Pressure test the steam coil, which is at the outside of the drum.
Check the condition of the demister support.
Outlet nozzle at the bottom should be freed from dirt.
Check the condition and mounting of the gas inlet device.
9.1.2
Preheaters
a. Clean the shell side and tubes at the outside, in such a way that they are freed
from any loose scale and dirt.
b. Pressure test the steam side of the preheater for approx. 2 hours after cleaning
activities.
c. Check the steam traps.
9.1.3
Burners
a. Remove the burners from the equipment.
b. Check if the metal parts of the burners have not been damaged by overheating.
Measure the dimensions of the burner gun and air nose. If significant deviations
are observed LD Duiker, the burner manufacturer, should be contacted.
Attention should be given to the vanes of the air register, the burner gun and tip
and the air nose. Replace damaged parts.
c. Check the electric ignitor. The tip may have to be replaced.
d. Check the refractory lining on cracks.
e. Clean the burners, including sight glasses and flame detectors.
f. Clean the air chamber of the burners and check if the drains are clean.
9.1.4
Combustion Chambers
a. Check the refractory lining of the chamber, bricks which are not in correct
position have to be replaced. Castable refractory, which is damaged, should be
repaired.
b. Inspect if the matrix blocks of the protection wall are still in place. Replace those
matrix blocks which are cracked.
c. Replace the ceramic well of the temperature indicator (instrument department).
d. Clean the chamber from dust.
Page 85 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
9.1.5
9.1.6
Sulfur Condensers
a. Remove rust and scale from the inlet channel. Check the condition of the lining
in the inlet channel. If the concrete surface is not flat, fill the holes with concrete
and smoothen surface. Clean the tube plate and check for leaking tubes and
tube welds. Leaking tubes can be plugged off to maximum 5% of the total
number of tubes per condenser. If the lowest row of tubes has to be plugged off,
install additional concrete layer in the inlet channel to prevent collection of
sulfur. Leaking tube welds should be repaired.
b. Tubes to be wire brushed and to be air blown inside, in such a way that they are
freed from any loose scale and dirt.
c. Remove rust and scale from the outlet channel. Sulfur outlet nozzle to be wire
brushed. Check the condition of the lining in the outlet channel. If the concrete
surface is not flat, fill the holes with concrete.
d. Check the condition of the wire mat. If the mat is fouled and cleaning is
impossible, the wire mat has to be replaced.
e. Pressure test the steam coil, which is installed below the demister.
f. Clean the waterside of the Claus condenser. Special attention should be paid to
the blow down drain nozzle.
g. Pressure test the water side of the Claus condenser for approximately 2 hours
after cleaning activities.
h. Bank testing of the safety relief valves.
Page 86 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
9.1.7
Reactors
a. Open the top manholes of the reactors (catalyst should be protected during
rainfall).
b. Check the condition of the top layer of the catalyst. In case only the top layer is
soothed (black), the top 100 mm is replaced. If the catalyst is heavily soothed,
the recommended procedure for removing the soot is by screening. The
catalyst has to be taken out of the reactor. Never burn off carbon deposits.
c. Take catalyst samples from each reactor, halfway each catalyst layer. The
samples are sent to the catalyst manufacturer for analysis. Sampling of the
catalyst is advised some time prior to the maintenance shutdown.
d. Check the condition of the concrete lining as far as possible. If the refractory
material is dropped or loose from the cracks, which are usually present, the
refractory should be repaired.
e. Remove the expansion bellows from the gas outlet piping for cleaning and
examination of the bottom part of the reactor.
f. Check the condition of the support grid and gauze.
g. Check the expansion bellows.
h. Lock the expansion bellows before removing them.
i. Leak test the expansion bellows.
9.1.8
Sulfur Coalescer
a. Clean the inside of the coalescer from loose scale and dirt.
b. Check the condition of wire mat. If the mat is fouled and cleaning is impossible,
the wire mat has to be replaced.
c. Check the condition of the demister support.
d. Sulfur outlet nozzle to be wire brushed.
e. Check the condition and the mounting of the gas inlet device.
9.1.9
Incinerator
a. Check the condition of the concrete lining. If refractory material is dropped or
loose from the cracks, which are usually present, the refractory should be
repaired.
b. Clean the chamber from dust.
c. Check the air distributors for corrosion.
9.1.10
Page 87 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
c. Tubes to be wire brushed inside and to be air blown, in such a way that they
are freed from any loose scale and dirt before new lining is applied.
d. Remove rust and scale from outlet channel. Check the conditions of lining in
outlet channel and repair if required.
e. Clean the waterside of the boiler. Special attention should be paid to the
bottom of the boiler and the blow-down drain.
f. Pressure test the waterside of the boiler for approximately 2 hours after
cleaning activities.
g. Check the main steam valve.
h. Bank testing of the safety relief valves.
i. Check the condition of the connection from the incinerator waste heat boiler to
the steam superheater. Check refractory lining and repair if required.
9.1.11
Steam Superheater
a. Clean the shell side and tubes at the outside, in such a way that they are
freed from any loose scale and dirt before new lining is applied.
b. Pressure test the steam side of the superheater for approximately 2 hours
after cleaning activities.
c. Check the steam traps.
d. Check the conditions of the flue duct from the steam superheater to the stack.
Check the flue duct lining and repair if required.
9.1.12
a.
b.
c.
d.
e.
f.
9.1.13
9.1.14
Sulfur Locks
Remove as much as possible the sulfur from the locks as follows:
- Close the valve in the sulfur rundown line.
- Connect steam or nitrogen hose on the utility connection of the sulfur lock.
- Admit steam or nitrogen to the sulfur lock, thereby removing sulfur from the
lock.
- Disconnect steam hose.
Remove the sulfur locks from their shafts.
Remove the bottom flange of the sulfur lock and clean the inside of the lock.
Pressure test the steam jacketing of the locks.
Check the valves.
Check the condition of funnels.
Sulfur Storage Tank
a. Sulfur storage tank should be pumped out and cleaned completely.
b. Inlet and outlet vent pipes to be wire brushed.
c. Pressure test the steam coil, which is at the outside of the sulfur storage tank.
Page 88 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
9.1.16
Running Equipment
a. For inspection and maintenance of all running equipment, reference is made to
the maintenance instruction manual of the manufacturers.
b. Suction screens of pumps and blowers to be cleaned and checked.
9.1.17
9.1.18
Analyzers
a. Clean sample valves and sample lines (with steam).
b. Clean internal of analyzers according to the manufacturers instructions
Page 89 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
ATTACHMENTS
SAFETY DATA SHEETS FOR CLAUS
CATALYST
Page 90 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc
Page 91 of 91
/var/www/apps/conversion/tmp/scratch_6/294995142.doc