DB_Turbine_flow_sensors 05/2014
87
Measuring principle
The liquid flowing into the turbine flow sensor is split into
individual jets by the guiding blade. These jets hit the rotor
evenly from different directions, setting the rotor in motion. The
rotation speed of the rotor is then converted to an electrical
pulse signal (frequency): The rotors are fitted with magnets
and a Hall effect sensor detects the rotation of the rotor. The
VTI series has stainless steel pins in the rotor. An inductive
proximity switch detects the rotor rotation.
Sensor housing
Cable
Hall-Sensor
Pipe section
Turbine system
Rotor
Magnet
Guiding blades
88
Turbotron VT series
The turbine flow sensors of the product line Turbotron are sensors for flow measurement or dosing applications for liquids.
Because of the very compact design, the very wide measuring range and the convincing precision of measurements, the Turbotron
has almost unlimited applications. Depending on the ordered version, the Turbotron is available with nominal diameters DN 15,
DN 20, DN 25 and DN 40.
Advantages
Universal application thanks to :
Fixed pulse rate, thus practically no serial deviation
Wide measuring range from 1:20 to 1:42 (depends on model),
therefore universally applicable
High degree of accuracy ensures reliable measurement
results
High quality sapphire bearing, low abrasion and extremely
long running period
Specially designed guiding blades ensures uniform flow to
the rotor from four sides, thus tremendous reduction of wear
Any position can be versatile installed
Permanent operating temperatures
up to 150 C (VTP version)
Compact dimensions
Proven in numerous OEM-applications
Service-friendly
Long endurance
Temperature measurement can be integrated (option)
89
Type VTH 15
Type VTM 15
Type
VTH 15
economy-priced type
for standard and serial applications
VTM 15
Plastic PPO
Brass
Measurement range
Accuracy
0.4 l/min
Reproducibility
0.1 l/min
Signal output
Medium temperature
Max. 85 C
Pressure rating
PN 10
Nominal diameter
DN 15
Process connection
Sensor
Output signal
Pulse rate / K-factor
Resolution
Signal shape
Signal current
855 pulses/litre
1.2 ml/pulse
Square wave signal NPN open collector
Max. 10 mA
915 pulses/litre
1.1 ml/pulse
Square wave signal NPN open collector
Max. 10 mA
Electrical connection
Power supply
4.5...24 VDC
Degree of protection
IP54
0.5 mm
Brass
2...20 l/min
Max. 120 C
Options
Screen filter
Integrated
temperature sensor
Approvals
90
Type VTP 15
Type VTI 15
Type
VTP 15
high pressures,
high temperatures
VTI 15
magnet-free rotor, high
measurement accuracy, high resolution
Brass
Measurement range
Accuracy
0.2 l/min
Reproducibility
0.1 l/min
0.05 l/min
Signal output
Medium temperature
Max. 150 C
Max. 85 C
Pressure rating
PN 10
Nominal diameter
DN 15
Process connection
Sensor
Output signal
Pulse rate / K-factor
Resolution
Signal shape
Signal current
915 pulses/litre
1.1 ml/pulse
Square wave signal NPN open collector
Max. 10 mA
1795 pulses/litre
0.6 ml/Pulse
Square wave signal PNP or NPN open collector
Max. 50 mA
Electrical connection
Power supply
4.5...24 VDC
10...30 VDC
Degree of protection
IP54
0.5 mm
Stainless steel
G male thread or
G female thread
Plastic PPO
Brass
Options
Screen filter
Integrated
temperature sensor
Approvals
91
Union nut
Gasket
Hat filter
VTH / VTI
Characteristic curve
VTM
Characteristic curve
930
2500
910
900
1500
920
VTI
2000
VTH
1000
500
10
15
20
25
30
35
40
870
860
850
2,5
2
1,5
1
0,5
0
0
10
15
20
25
10
15
880
92
890
30
35
40
20
25
30
Materials
Medium
VTH 15 K5-.. VTH 15 MS-.. VTM 15 MS-.. VTP 15 MS-.. VTP 15 VA-.. VTI 15 K5-..
contacting
Pipe section
PPO
Noryl GFN3
Sensor housing
Union nut
Brass
Brass
PA 66
Brass
VTI 15 MS-..
Stainless
steel 1.4571
PPO
Noryl GFN3
Brass
Stainless
steel 1.4571
Turbine system /
rotor
PEI ULTEM
PEI ULTEM
O-ring / gasket
NBR
FKM
NBR
Bearing system /
shaft
Bearings support
Arcap AP1D
Rotor assembly
Temperature
sensor
(optional)
Brass or
Stainless steel 1.4571
Screen filter
Brass or
Stainless steel 1.4571
POM / Stainless steel
93
Options
Options
Integrated temperature sensor with plug connection M8
resistance thermometer Pt100 or Pt1000,
class B, 3-wire, immersion tube brass or stainless steel
Integrated temperature sensor with fixed cable,
resistance thermometer Pt100 or Pt1000, class B,
PTC or NTC on request
immersion tube brass or stainless steel
Screen filter, hat shape, in the inlet
On request delivered
Optional seal materials
94
NBR
FKM
EPDM
Order code
Order example
VT1541
Type
VT / VTP / VT 15
VT1541
K5
H*
A*
K5
MS
VA
I
H
D
P
N
P
S
0
B
C
2
9
D
E
7
A
MS
VA
MS
VA
MS
VA
MS
VA
Process connection
G male
G female (possible only with VTP in stainless steel)
Options
Filter
Screen filter
None
Electronics
Including transducer 4...20 mA
A4
I4
H
0
A
B
C
D
A4
6
7
4
VT1531MSMNP
0A4
VT1531MSMNP
0A4
2A4
7A4
* If you do not require one of the options, digits of the order code do not apply
95
Accessory
Connection adapters Turbotron VT 15
Supplied piecewise including required seals.
Hose barb 10, PA 6.6
Tmax = 20 C, PN10
Tmax = 60 C, PN2.5
Order code VT1317
Screw coupling
G-ISO 228 male, brass
Tmax = 110 C, PN16
Order code VT1320
Screw coupling
G-ISO 228 male, brass
Tmax = 110 C, PN16
Order code VT1324
Screw coupling
G-ISO 228 female
Brass galvanized
Tmax = 110 C, PN16
Order code VT1321
Screw coupling
G-ISO 228 female, brass
Tmax = 110 C, PN16
Order code VT1325
Length
3m
5m
10 m
2m
5m
10 m
96
Order code
XVT 2053
XVT 2009
XVT 2070
VT 1331
XVT 2190
XVT 2191
XVT 2192
97
Turbotron VT 25
VTH / VTM / VTI 25
Typ VTH 25
Type
VTH 25
economy-priced type for
standard and serial applications,
VTM 25
higher pressure,
plug connection
Brass
Brass
Measurement range
Accuracy
Reproducibility
0.5 %
Plastic PP
VTI 25
magnet-free rotor,
plug connection
Stainless steel
Brass
Plastic PP
Max. 60 C
Max. 60 C / 5 bar
Max. 30 C / 10 bar
Signal output
< 1 l/min
Medium temperature
Max. 85 C
Pressure rating
PN 10
Nominal diameter
DN 25
Process connection
Sensor
65 pulses/litre
15 ml/pulse
Square wave signal
NPN open collector
Max. 19 mA
65 pulses/litre
15 ml/pulse
Square wave signal
NPN open collector
Max. 19 mA
65 pulses/litre
15 ml/pulse
Square wave signal
PNP open collector
Max. 200 mA
Electrical connection
Power supply
10...30 VDC
optional 4.5...26.5 VDC
6.5...24 VDC
short circuit proof and
reverse polarity protected
Degree of protection
IP54
< 0.63 mm
Output signal
Pulse rate / K-factor
Resolution
Signal shape
Signal current
Options
Screen filter
98
PN 50
PN 10
10...30 VDC
approx. 2000
3 x 0.25 mm
Knurled
union nut
Union nut
Sealing
R 1
G 1 A
44.6
19
74
44
Characteristic curve
70
60
50
40
30
20
10
0,1
0,5
1,0
10
20 22
50
100
200
Pressure drop
0,7
0,6
0,5
0,4
0,3
0,2
0,1
VTH 25 MS-180, 1
VTH 25 MS-180, 1
20
40
60
80
100
120
140
160
180
200
220
240
99
Materials
Medium
contacting
VTM 25 MS-180
VTM 25 VA-180
VTI 25 MS-180
VTI 25 K6-180
Pipe section
Brass,
CW602N*
Brass,
CW602N*
Stainless steel
1.4571
Brass,
CW602N*
PP
Turbine cage
Rotor
Rotor assembly
Shaft
Bearings
Saphir / PA
Housing for
Hall sensor
O-ring
EPDM
Screen filter
(option)
Associated O-ring
Stainless steel
1.4301
EPDM
Spacer
* optional CW724R
100
PP
Brass,
CW602N/
CW614N
Stainless steel
1.4571
PA66-natur
PP
Options
Screen filter with O-ring, in the inlet
Order example
VT2511
MS
HN
P000
F*
E*
Type
VT 25
VT2511
MS
K6
VA
Version
VTH
Standard
Option
10...30 VDC
4.5...26.5 VDC
VTM
VTI
HN
HK
MN
IP
Electrical connection
Cable (only VTH)
4 pin connector M12 x 1 (only VTM, VTI)
P000
S000
Options
Filter
Flat filter (only brass or stainless steel version)
None
F
0
Electronics
Incl. transducer 4...20 mA
Corresponds with 0...60 l/min
Corresponds with 0...100 l/min
Corresponds with 0...160 l/min
Switching output VE
Switching output VE with pulse output
Version for local display TD 32500 (display must be ordered separately)
E
F
G
6
7
4
* If you do not require any of the options, digits of the order code do not apply.
101
Accessory
Connection adapters Turbotron VT 25
supplied piecewise including required seals.
Plastic version
Tmax = 20 C, PN10
Tmax = 60 C, PN2.5
Brass version
Material of flat seal: Centelen
Tmax = 85 C
Welding coupling PP
Order code VT1303
Bonding coupling PVC
Order code VT1304
erter
integri ratursensor
Tempe -Leiter
Pt100/3
Screw coupling
with temperature sensor
G1-ISO 228
Order code VT1310
Hose barb PP
Available in
3 diameters
d = 25 Order code VT1307
d = 30 Order code VT1308
d = 32 Order code VT1309
Screw coupling
R1-DIN EN 10226-1 2004-10
Order code VT25Z00000005
Screw coupling
R1-DIN EN 10226-1 2004-10
Order code VT25Z00000006
flat filter
O-ring
Soldering coupling
28 mm
PN 16
Order code VT1312
flat filter
Screw coupling
G1
Order code VT1333
O-ring
Length
Order code
3m
5m
10 m
XVT 2053
XVT 2009
XVT 2070
102
VT 1331
103
Turbotron VT 40
VTH / VTM / VTI 40
Type VTH 40
Type
VTH 40
economy-priced type for
standard and serial applications
VTM 40
for higher pressure,
plug connection
VTI 40
magnet-free rotor,
plug connection
Brass
Brass
Brass
Measurement range
Accuracy
Reproducibility
0.5 %
Signal output
Medium temperature
Max. 85 C
Max. 85 C
Max. 60 C
Pressure rating
PN 10
PN 50
PN 10
Nominal Diameter
DN 40
Process connection
Sensor
26.6 pulses/litre
37.6 ml/pulse
Square wave signal
NPN open collector
Max. 19 mA
26.6 pulses/litre
37.6 ml/pulse
Square wave signal
NPN open collector
Max. 19 mA
26.6 pulses/litre
37.6 ml/pulse
Square wave signal
PNP open collector
Max. 200 mA
Electrical connection
Power supply
10...30 VDC
optional 4.5...26.5 VDC
6.5...24 VDC
short circuit proof and
reverse polarity protected
Degree of protection
IP54
< 0.63 mm
Output signal
Pulse rate / K-factor
Resolution
Signal shape
Signal current
104
10...30 VDC
Pressure drop
2,0
1,8
1,6
1,4
1,2
1,0
0,8
0,6
0,4
0,2
0
1
11
13
15
17
19
21
23
25
105
Medium contacting
VTH 40 MS-410
VTM 40 MS-410
Pipe section
Brass CW724R
Turbine cage
Rotor
Rotor assembly
Shaft
Bearing
Sapphire / PA
O-ring
EPDM
POM
Screen filter
Retaining ring
Bronze
Brass, CW602N/CW614N
VTI 40 MS-410
PA66-natural
Options
Turbine flow transmitter, analog output 4...20 mA
Order example
VT4025MS
HN
P000F
E*
Type
VT 40
VT4025MS
Version
VTH
Standard
Option
10...30 VDC
4.5...26.5 VDC
VTM
VTI
HN
HK
MN
IP
Electrical connection
Cable (only VTH)
4 pin connector M12 x 1 (only VTI, VTM)
P000F
S000F
Options
Electronics
Including transducer 4...20 mA
Corresponds with 0...150 l/min
Corresponds with 0...250 l/min
Corresponds with 0...400 l/min
Switching output VE
Switching output VE with pulse output
Version for local display TD 32500 (display must be ordered separately)
* If you do not require any of the options, digits of the order code do not apply.
106
E
F
G
6
7
4
Accessory
Connection adapters Turbotron VT 40
Supplied piecewise including required seals.
Brass version
Material of flat seal: Centelen
Tmax = 85 C
rter
integrieratursensor
Tempe -Leiter
Pt100/3
Screw coupling
with temperature sensor
G 1-ISO 228
Order code VT1311
Screw coupling
R 1-DIN EN 10226-1 2004-10
Order code VT40Z00000002
Screw coupling
G 2-ISO 228
Order code VT40Z00000001
Soldering coupling
42 mm
PN 16
Order code VT1313
Length
Order code
3m
5m
10 m
XVT 2053
XVT 2009
XVT 2070
VT 1331
107
Type Turbotron AI
Technical data
Output signal
4...20 mA
Accuracy
1.25 % of reading*
Current limit
Approx. 26 mA
Scaling
Power supply
18...30 VDC
30 mA
Max. burden
Residual ripple
Type
Electrical connection
Casing material
Order code
108
Type VT..15..VE
109
Technical data
Technical data
Set point range (with decreasing flow) / accuracy
DN 15
0.5...29.5 l/min / 2 % of set point + accuracy of turbine flow sensor
DN 25
3...100 l/min / 4 % of set point + accuracy of turbine flow sensor
DN 40
7...275 l/min / 6 % of set point + accuracy of turbine flow sensor
Switching hysteresis
Power supply
12...24 VDC
Current consumption
Max. 25 mA
Degree of protection
Casing
Display, internal
Electrical connection
Order code
110
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.5
5.5
7.5
9.5
11.5
15.5
19.5
24.5
29.5
10
12
15
18
20
25
30
35
40
50
70
100
10
12
14
17
20
22
27
33
38
44
55
75
105
Switch position
10
15
20
25
30
35
40
50
65
80
100
130
160
200
275
10
13
19
24
30
35
40
47
58
75
90
115
150
190
230
310
* The specified values refer to operation with water at 20 C. Monitoring of fluids with higher viscosities is possible with the effect of deviations from the mentioned
values. If you order at least 25 units, individual set point tables can be implemented.
111
Type TU 7050
Mode A
Two identical turbine flow sensors operate one set
point each.
Mode B
One turbine flow sensor operates a pair of alarm set
points (pre-alarm & main-alarm or min. & max.).
The TU 7050 provides a failsafe mechanism as any malfunction
of the flow sensor would immediately trigger the low flow alarm
setting. The set points are very easily adjusted via the very
visible, rotary dial settings and additional oversight is offered by
2 LED lights. The red LED will light in a no-flow condition and a
green LED indicates flow.
Technical data
Signal input
LED green = ok
0.5...29.5 l/min
3...100 l/min
7...275 l/min
Outputs
30 VDC / 1 A
Power supply
12...24 VDC 10 %
Casing
0...60 C / -10...80 C
112
Hysteresis
0.5 l/min
2...10 l/min
3...35 l/min
150 VAC / 400 mA
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.5
5.5
7.5
9.5
11.5
15.5
19.5
24.5
29.5
10
12
15
18
20
25
30
35
40
50
70
100
10
12
14
17
20
22
27
33
38
44
55
80
110
Switch position
10
15
20
25
30
35
40
50
65
80
100
130
160
200
275
10
13
19
24
30
35
40
47
58
75
90
115
150
190
230
310
* The specified values refer to operation with water at 20 C. Monitoring of fluids with higher viscosities is possible with the effect of deviations
from the mentioned values. If you order at least 25 units, individual set point tables can be implemented.
Order example
EU70500
H152296
Type
TU 7050
EU70500
H152296
D152296
I152296
P152296
H252296
P252296
H402296
P402296
113
TD 32500
Options
Additional temperature display, input for resistance
thermometer Pt100 / 3-wires
79
65
TD 32 500
114
Technical data
TD 32500
Signal input
Fequency signal from flow sensor 0.5...2000 Hz, pulse rate programmable
Programming
Display
Programmable units
Power supply
12...24 VDC
12 VDC
Ambient temperature
-10...60 C
Casing
IP65
Electrical supply
Order example
ED325
0I000
009
Type
TD 32500
ED325
Input
Flow sensor
Flow sensor and Pt100
6
7
Outputs
None
Analogue output
Pulse + frequency divider
Analogue + frequency divider
0I000
AI000
FI000
BI000
Alarm output
None
2, programmable
009
299
Electrical connection
2 m cable
Plug M12 x 1
1
2
Number of pins/leads
Laid down by SIKA, depending on requirements
115
Type VTH 15
Type VTH 20
TypeVTH
Typ
VTH2525
116
Technical data
Push in turbine
Flow range
Accuracy
Reproducibility
Signal output
Medium temperature
Nominal diameter
Pressure drop
Materials
Turbine capsule
Rotor
Rotor assembly
Bearings
Approvals
VTH 15
VTH 20
VTH 25
0.2 %
From 0.3 l/min
Max. 85 C
DN 15
Approx. 500 mbar at 20 l/min
PEI ULTEM
PEI ULTEM
Hard ferrite magnets
Sapphire / hard metal
AD3004
VT20Z000000001
VT25Z000000021
VT2000
VT2228
VT2228
G A
PPO Noryl GFN 1630 V
EPDM
G A
PPO Noryl GFN 1630 V
EPDM
VT25Z000000002
VT25Z000000002
0.5 %
< 1 l/min
Max. 85 C
DN 25
< 100 mbar at 80 l/min
Order Code
Technical data
Hall effect sensor
Nominal pulse rate
Frequency output
Power supply
Electrical connection
Nominal pressure
Process connection
Material sleeve
Material O-Ring
Approvals
Order code
Technical data
Sleeve for hall effect sensor
Process connection
Material sleeve
Material O-Ring
Order code
Delivering lots from 50 units
Stated values may vary depending on geometry of fittings
117
118
119
VTY 10 MS-30
Measurement range
Accuracy
Signal output
Nominal diameter
Pressure rating
Medium temperature
Ambient temperature
Process connection
Sensor
Output signal
Pulse duty ratio
Pulse rate / K-factor
Electrical connection
Power supply
Materials
Turbine body
Rotor
Magnet
Shaft
Axial bearing
Radial bearing
Approval
1...30 l/min
0.3 l/min
From 0.7 l/min
From 0.6 l/min
DN 10
PN 10
Max. 70 C, temporary 95 C
0...70 C
G male
G male
Hall effect sensor
Square wave-Frequence signal, NPN open collector
50:50
495 pulses/l
530 pulses/l
PVC-cable, double insulated (1 m), optional single wire
4,5...24 VDC
Order code
Delivering lots from 100 units
120
VTY 10 K5-30
Brass
PPO Noryl GFN3
Hard ferrite
Stainless steel / Hard metal
Sapphire
PEEK Victrex
VY1030MSHN10A3
VY1030K5HN10A4
VTY 10 K5-30
30
n 15
vtx 10-30
n 12,7
12
19
13
50
50
Pressure drop
0,9
0,9
0,8
0,8
Pressure drop
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
SW19
G 1/2A
38
G 3/4A
27,5
vty 10 k5-30 - 2
10
15
20
25
30
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
500
500
400
400
600
300
200
100
20
25
30
20
25
30
Characteristic curve
600
15
Characteristic curve
10
10
15
20
25
30
300
200
100
10
15
121
Type VTY
Technical data
VTY 10-30
Flow range
1...30 l/min
Signal output
Accuracy
0.3 l/min
Nominal diameter
DN 10
Pressure rating
Medium temperature
Max. 85 C, temporary 95 C
Ambient temperature
0...70 C
50:50
495 pulses/l
Material
Turbine body
Rotor
Magnet
Shaft
Axial bearing
Radial bearing
Approval
Order code
Delivery lots from 100 units
Stated values may vary depending on geometry of fittings.
122
VY1030K50000YY
15
12,7
38,2
vty 10-30
12,7
38,2
13
15
15
12,7
38,2
38,2
vty 10-30
Characteristic curve
Pressure drop
600
0,9
500
400
300
200
100
38,2
10
15
20
25
30
13
15
13
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
10
15
20
25
30
38,2
123
124
Measuring principle
The VTR sensor consists of the measuring turbine and a pickup mounted on the outside. The liquid flows into the measuring
turbine and causes the rotor to move. Due to the characteristic
internal diameter the speed of rotation is directly proportional
to the flow rate. The moving rotor blades are detected by the
pick-up and this is converted into a pulsed signal proportional
to the flow rate.
For use in
Cooling circuits
Petrochemicals
Chemical industry
Water conditioning
Plastics and hydraulics
125
Technical data
Accuracy
Reproducibility
Response time
< 50 ms up to DN 40
> 50 ms up to DN 300
Process connections
Pressure drop
Minimum pressure
Pressure rating
Mediums temperature
Max. 150 C
Options
Local display TD 32500
126
Type
Nominal
diameter
Flow range
Dimensions
DN
[m/h]
[l/min]
B [mm]
C max [mm]
D [mm]
VTR 1010
10
0.11...1.1
1.8...18.3
64
150
127
VTR 1015-S
15
0.22...2.2
3.7...36.7
64
150
127
VTR 1015
15
0.4...4
6.7...66.7
64
150
127
VTR 1020
20
0.8...8
13.3...133
83
150
140
VTR 1025
25
1.6...16
26.7...267
G1
88
200
152
VTR 1040
40
3.4...34
56.7...567
G 1
114
200
178
VTR 1050
50
6.8...68
113...1133
G2
132
200
197
VTR 1075
80
13.5...135
225...2250
200
254
VTR 1100
100
27...270
450...4500
300
356
VTR 1150
150
55...550
917...9167
300
360
VTR 1200
200
110...1100
1833...18333
350
457
VTR 1250
250
190...1900
3173...31730
350
457
VTR 1300
300
270...2700
4509...45090
400
457
127
Order codes
Thread connection male
Order example
VS
1071VA
ISP0
A3
Type
VTR
Nominal size / flow range
DN 10 / 0.11...1.1 m/h
DN 15 / 0.22...2.2 m/h
DN 15 / 0.4...4 m/h
DN 20 / 0.8...8 m/h
DN 25 / 1.6...16 m/h
DN 40 / 3.4...34 m/h
DN 50 / 6.8...68 m/h
VS
Process connection male threaded G
male thread G
male thread G
male thread G
male thread G
male thread G 1
male thread G 1
male thread G 2
1071VA
1572VA
1573VA
2074VA
2575VA
4076VA
5077VA
A3
A4
A4
A4
A5
A7
A8
Sensor
Inductive pick-up VISPP (included in the scope of delivery)
Optional pick-up (seperate order)
ISP0
0000
Flange connection
Order example
VS
1071VA
ISP0
Type
VTR
VS
1071VA
1572VA
1573VA
2074VA
2575VA
4076VA
5077VA
7578VA
1H79VA
HF81VA
2H82VA
ZF83VA
3H84VA
Sensor
Inductive pick-up VISPP (included in the scope of delivery)
Optional pick-up (seperate order)
ISP0
0000
Process connection
DIN flange stainless steel
ANSI flange stainless steel
PN 6 / #150
PN 16 / #300
PN 25 / #400
PN 40 / # 600
128
G
I
1
2
3
4
Accessories
Pick-ups
Type
VISPP
Inexpensive,
fitted as standard
Output signal
Sinus wave
Measuring principle
Inductive
Temperature range
-20...120 C
VISPP-HT
For high medium
temperature
VSAPPS*
Square wave
signal
VSAPPSHT*
Square wave
signal, for high
medium
temperature
VSANTD
For TD 32500
(local display)
Power supply
-20...85 C
-20...100 C
-20...85 C
10...30 VDC
Via TD 32 500
Degree of protection
IP54
IP67
IP65
Electrical connection
Cable socket
Inclusive
Accessory
* Adapter VT1140 sold separately ** Notice the max. medium temperature of measuring turbine (150 C).
Connection cables
Connection cables
Length
Order code
3m
5m
10 m
XVT 2053
XVT 2009
XVT 2070
VT 1331