Академический Документы
Профессиональный Документы
Культура Документы
discussions, stats, and author profiles for this publication at: http://www.researchgate.net/publication/268037903
READS
161
5 AUTHORS, INCLUDING:
He Jinliang
Xiao Zhang
Tsinghua University
Tsinghua University
4 PUBLICATIONS 5 CITATIONS
SEE PROFILE
SEE PROFILE
Shuiming Chen
R. Zeng
Tsinghua University
Tsinghua University
SEE PROFILE
SEE PROFILE
a r t i c l e
i n f o
Article history:
Available online 12 August 2014
Keywords:
Lightning impulse
Bundled conductors
Attenuation
Deformation
Traveling lightning overvoltage
a b s t r a c t
Comprehensive study of the impulse corona characteristics is helpful to understand the transient process
and guarantee a suitable insulation design of power transmission systems. In this paper, rst the attenuation and deformation characteristics of lightning overvoltage traveling along a 500 kV experimental
transmission line are tested. Then the lightning impulse corona characteristics on different bundled conductors commonly used in the 1101000 kV power transmission lines are experimentally investigated,
the impulse corona QV data measured in the corona cage is transformed into those on the corresponding
overhead lines. The inuence of bundle geometry on corona is analyzed. Attenuation and deformation
effects of lightning impulse corona along transmission lines are evaluated by comparing the simulation
and test results. Simulation shows the amplitude and wave-front steepness attenuate remarkably, and
the deformation of the voltage mainly happens when the impulse voltage exceeds the corona inception
one.
2014 Elsevier B.V. All rights reserved.
1. Introduction
When lightning transient travels along an overhead line, the
voltage waveform will be deformed and attenuated by several
factors, including frequency dependent behavior of the conductor impedance, skin effect and the impulse corona discharge [13].
Among them, the corona decreases the conductor impedance and
increases the coupling factors between lines as well. In order to
precisely calculate the lightning overvoltage of power systems, the
characteristics of the impulse coronas on different transmission
bundled lines need to be tested and analyzed comprehensively
[4,5].
Many researchers have studied the physics and discharge process of impulse corona [68]. In 1954, Wagner and Lloyd rstly
carried out impulse corona experiments on an outdoor overhead
line and measured the deformed voltage waveform [9]. Corona
cage experiments were conducted by Maruvada in 1970s to analyze the lightning and switching impulse corona on 4 different
kinds of bundled conductors [10]. During recent decades, several
other experiments have been carried out to obtain the lightning
Voltage divider
Measuring point 3
Matched
impedance
Voltage divider
Measuring point 2
Test line
Voltage divider
Measuring point 1
200 m
Lead
150 m
UHV support
insulator
4800 kV Impulse
voltage generator
30
-500
0
-300
-600
-1000
-900
-1200
0.0
-1500
Fig. 1. Experiment setup of lightning impulse corona on the test line.
At head end
At the middle point
At the tail end
0.0
2.0x10
-5
-6
2.0x10
4.0x10
-6
4.0x10
-5
-5
6.0x10
Time (s)
2. Lightning impulse corona experiment on the specimen
transmission line
First, a 200 m testing section of 500 kV transmission line is set
up to investigate the inuence of lightning impulse corona on the
wave deformation over actual high-voltage bundled transmission
lines. In this experiment, lightning impulse voltages are applied by
the generator at the head end of the line, and the noninductive
matching resistor is connected between the line and the ground at
the tail end. Impulse voltage dividers are installed to measure the
traveling instantaneous voltages at different points along the line.
2.1. Equipment setup
The diagram and the photograph of the experiment setup are
shown in Figs. 1 and 2(a) respectively. The experiment setup consists of a 4800 kV/720 kJ impulse generator as shown in Fig. 2(b), the
test line, impulse voltage dividers, the lead wire and the matching
resistor.
The length of the test line is 200 m, with bundled conductors
of 4LGJ630/45 s450, the same as applied on 500 kV AC power
31
Fig. 4. Electric-eld on the conductor surface: (a) overhead line (b) in the corona cage.
20 nrb Em
[1 + (rs /rb )(n 1)]
qc
Ccage
(2)
uline =
qc
Cline
(3)
where Ccage and Cline are the capacitance to the ground from the
bundle in the corona cage and on overhead line, respectively.
In this way, Eq. (4) is used to determine the relationship of the
voltages applied on the conductors under these two cases when the
corona degrees in both cases reach the similarity:
uline =
ucage Ccage
Cline
(4)
Corona cage
Shielding
section
measuring
section
Shielding
section
Tested conductors
Coaxial
cable
Impulse Divider
generator
Coaxial
cable
Data
acquisition
(1)
Fig. 5. Experiment setup of HV corona cage.
Measure
capacitor
Negative
Positive
Geometric capacitance
30
q(C/m)
32
qp
20
qn
10
400
u(kV)
800
1200
u
When the impulse voltage exceeds the corona inception value,
charges are generated in the space around the conductors, the
QV curve deviates from the geometrical capacitance and increases
rapidly after the knee point. Therefore, the knee point of the QV
curve is usually reckoned as the corona inception voltage of the
conductors.
It rst appeared in the test results of paper [18] that the knee
points of the same conductors under different amplitudes of positive lightning impulse are different, and the corona inception delay
time is proposed to indicate this phenomenon in our previous paper
[17]. The inception voltage, knee point voltages and corona onset
delay times on ten types of bundle conductors measured under
different magnitudes of positive lightning impulse are presented
in Table 1.
The values of inception voltage in Table 1 are obtained from
switching impulse experiments carried out on the same bundles, because the wave front time of the switching impulse is
250 s, hundred order times of the lightning impulse corona delay
time. The deviation between the knee point voltage on the QV
curves and the corona inception voltage increase with the lightning
impulse voltage amplitude on the same bundled conductors.
4.2. Inuence of the bundle parameters on lightning impulse
corona characteristics
In this section, the specic relation between lightning corona
characteristics and conductor parameters, namely the bundle spacing, number and radius of subconductors are analyzed base on
experimental results.
In general, when the bundle spacing or the number and radius
of the subconductors increase, the knee point of the QV curves is
enhanced, while the steepness of the curve slows down after the
corona inception point, resulting in a decreased area of the whole
curve as well.
When the voltage exceeds the corona inception value, the average dynamic capacitance Cdav is dened as (see Fig. 6):
2.8
(5)
2630 s450
4630 s450
6630 s450
2.6
Cdav/C0
q
Cdav =
u
Fig. 6. Corona QV curve of the same conductor under lightning impulse of different
polarities.
2.4
2.2
2.0
1.8
1.5
2.0
2.5
3.0
umax/u0
Fig. 7. Inuence of bundles to the relative lightning impulse dynamic capacitance.
33
2.4
2.4
2.2
Cdav/C0
Cdav/C0
2.2
2.0
4300 s450
4500 s450
4630 s450
2.4
2.6
2.8
3.0
6630 s400
6630 s450
6630 s500
1.8
1.8
2.2
2.0
1.6
3.2
1.6
1.8
umax/u0
2.0
umax/u0
Fig. 8. Relative lightning impulse dynamic capacitance under different subconductor radius.
Fig. 9. Inuence of bundle spacing on the relative lightning impulse dynamic capacitance.
Table 1
Corona inception delay time of UHV conductors under positive lightning impulse.
Conductor
Corona inception
voltage (kV)
Magnitude of impulse
voltage umax (kV)
4LGJ300/50 s450
410
1026
1150
1274
620
710
780
51.2%
73.2%
90.2%
0.45
0.59
0.65
4LGJ500/35 s450
430
1039
1166
1298
740
780
820
72.1%
81.4%
90.7%
0.74
0.70
0.67
4LGJ630/45 s450
450
980
1117
1247
710
770
810
57.8%
71.1%
80.0%
0.78
0.76
0.71
6LGJ300/50 s375
530
1046
1169
1291
800
870
920
50.9%
64.2%
73.6%
0.76
0.83
0.81
6LGJ400/35 s400
540
910
1034
1154
770
800
840
42.6%
48.1%
55.6%
0.88
0.75
0.69
6LGJ630/45 s400
560
912
1037
1164
760
810
840
35.7%
44.6%
50.0%
0.80
0.70
0.62
8LGJ500/35 s400
625
935
1052
1180
780
820
850
24.8%
31.2%
36.0%
0.60
0.53
0.45
8LGJ630/45 s400
640
984
1130
1247
800
860
900
25.0%
34.4%
40.6%
0.50
0.47
0.50
10LGJ630/45
s350
700
914
1046
1166
800
860
920
14.3%
22.9%
31.4%
0.72
0.73
0.70
12LGJ630/45
s300
770
918
1039
1155
860
900
970
11.7%
16.9%
26.0%
0.85
0.84
0.86
34
15
W(J/m)
2630 s450
4630 s450
6630 s450
10
0
1.5
2.0
2.5
3.0
umax/u0
Fig. 10. Energy dissipated by lightning impulse corona under different numbers of
subconductors.
6630 s400
6630 s450
6630 s500
W(J/m)
10
q=
1.2
1.6
2.0
umax/u0
Fig. 11. Energy dissipated by lightning impulse corona under different bundle spacing.
W(J/m)
Cgeo u
q0 (u/u0 )
Ccond =
15
4300 s450
4500 s450
4630 s450
10
2.0
2.5
3.0
umax/u0
Fig. 12. Inuence of subconductor radius on the energy dissipated by lightning
impulse corona.
u < u0
k
Cgeo
q0
dq
k uk1
=
k
du (u0 )
(6)
u u0
Cgeo
u < u0
u u0 ,
u
>0
t
(7)
u
<0
t
Without corona(Calculated)
With corona(Calculated)
Measured waveform
-500
-1000
-1500
0.0
3.0x10
35
-5
6.0x10
-5
6. Conclusions
Time (s)
Fig. 13. Simulated and measured results of the impulse voltage at the end of the
test line.
0.5 km
1 km
2 km
u(kV)
-2000
-4000
-6000
-8000
0
10
20
30
40
50
t(s)
Fig. 14. Lightning surges along the UHV line without corona.
0
0.5 km
1 km
2 km
u(kV)
-2000
-4000
The impulse corona on the bundled conductors has noticeable inuence on the deformation and attenuation of the lightning
transients. First, during a measurement carried out on a segment of
overhead 500 kV test line, 8.5% decrease of the voltage amplitude
and 7% increase of wave-front time are obtained under a lightning
impulse voltage of 1320 kV, 2.6/50 s.
The QV data measured in the corona cage need to be transformed into that on the corresponding overhead lines, considering
the geometry of the bundles and the cage. Impulse voltage of lower
amplitude should be applied in the corona cage test to generate the
similar surface eld around the bundle as on overhead lines. Based
on comprehensive experiments on different bundled conductors
applied in 1101000 kV power systems, it is found that under a
normalized impulse voltage Umax /U0 ranging from 1.5 to 3.0, the
relative lightning impulse dynamic capacitance increases signicantly with the number and radius of subconductors, but rst rises
and then declines with the bundle spacing. The energy dissipated
by impulse corona increases most signicantly with the number
of subconductors, and subconductor radius presents a weak inuence, whereas bundle spacing has the weakest correlation with the
energy dissipated by lightning impulse corona.
The empirical formulas describing impulse corona characteristics derived from experiments are applied in simulations. The
simulated impulse voltage agrees with the tested result on the
wave-front, but deviates on the wave-tail, since hysteresis in the
QV curve is not modeled. Simulation of an actual double circuit
UHV AC transmission line shows signicant attenuation on both the
amplitude and wave-front steepness under infulence of impulse
corona. The deformation of the voltage mainly happens when the
voltage exceeds the corona inception value.
Acknowledgments
-6000
0
10
t(s)
20
Fig. 15. Lightning surges along the UHV line with corona.
to investigate the lightning surge on the double-circuit UHV AC system operating in East China. The transmission line is represented
by a number of distributed-parameter sections of 50 m in length,
while the model of corona capacitance is connected at junctions
between each section. When a negative 2.6/50 s lightning current
of 50 kA strikes the phase line, the transients on the line at different
distances from the striking point are illustrated in Figs. 14 and 15,
without and with consideration of impulse corona respectively.
36
[5] T.A. Ametani, T. Kawamura, A method of a lightning surge analysis recommended in Japan using EMTP, IEEE Trans. Power Del. 20 (2) (2005) 67875.
[6] T. Noda, N. Nose, N. Nagaoka, A. Ametani, A wave-front-time dependent corona
model for transmission-line surge calculations, Elect. Eng. Jpn. 129 (1) (1999)
68775.
[7] M. Davila, G. Cinvestav, J. Naredo, P. Moredo, A. Ramirez, Practical implementation of a transmission line model for transient analysis considering corona
and skin effects, in: IEEE PowerTech Conference, Bologna, 2003, pp. 2326.
[8] V.V. Bochkovskii, Impulse corona on single and bundled conductors, Elektrichestvo 7 (1966) 2228 (in Russian).
[9] C.F. Wagner, B.L. Loyd, Effects of corona on traveling waves, AIEE Trans. Power
App. Syst. 74 (1955) 858872.
[10] P.S. Maruvada, H. Menemenlis, R. Malewski, Corona characteristics of conductor bundles under impulse voltages, IEEE Trans. Power App. Syst. 96 (1) (1977)
102115.
[11] X.R. Li, O.P. Malik, Z.D. Zhao, A practical mathematical model of corona for
calculation of transients on transmission lines, IEEE Trans. Power Del. 4 (2)
(1989) 11451152.
[12] M. Mohammadi, B. Vahidi, Model of corona for transient study, in: IEEE TENCON2005, Melbourne, Australia, 2005, pp. 24012404.
[13] R. Davis, R.W.E. Cook, W.G. Standring, The surge corona discharge, The Institution of Electrical Engineers Monograph, 1960, No. 415 S.
[14] P.S. Maruvada, H. Menemenlis, R. Malewski, Characteristics of conductor bundles under impulse voltages, IEEE Trans. Power App. Syst. 96 (1) (1977)
102115.
[15] J.L. He, P.C. Yang, S.M. Chen, R. Zeng, Lightning impulse corona characteristic
of 1000 kV UHV transmission lines, in: International Symposium on Lightning
Protection (XII SIPDA), Belo Horizonte, Brazil, 711, 2013, pp. 152156.
[16] W.V. Mangoldt, Electrical fundamentals of bundle conductors, in: Bundelleitungen, Siemens-Schuckert-Werke A.G, Germany, 1942.
[17] P.C. Yang, S.M. Chen, J.L. He, Lightning impulse corona characteristic of 1000 kV
UHV transmission lines and its inuences on lightning overvoltage analysis
results, IEEE Trans. Power Del. 28 (4) (2013) 25182525.
[18] T. Narita, S. Okabe, Propagation characteristics of lightning surge with corona
discharge on UHV designed transmission line, Trans. IEE Jpn. 122-B (2) (2002)
307313 (in Japanese).
[19] G.V. Podporkin, A.D. Sivaev, Lightning impulse corona characteristics of conductors and bundles, IEEE Trans. Power Del. 12 (4) (1997) 18421847.
[20] S.J. Carneiro, J.R. Marti, Evaluation of corona and line models in electromagnetic
transients simulations, IEEE Trans. Power Del. 6 (1) (1991) 334342.