Table 1: Standards
BS 7671:2008+A3:2015
Installation Method:
Insulation:
Cores:
Armour:
Material:
SI
ON
Table 2: Cable
E, F, G In free air or on a perforated cable tray
etc, horizontal or vertical Touching
Mineral Bare and Not Exposed to Touch
Single core
Armoured
Copper
Table 3: Load
10,00
1,00
0,0
100
Radial
ER
LV
Table 4: Supply
Phases:
1 phase
Voltage (V):
230
Permissible Voltage Drop (%):
2,50
Length:
50,00
Upstream Fault Level (kA):
1,00
Source Impedance, Ze (Ohms):
0,00
Frequency (Hz)
50
System Grounding:
TN-C-S
TR
IA
Table 5: Protection
Protection Provided:
Overload and short-circuit protection
Miniature Circuit Breaker (MCB)\Type C (BS
Protective Device:
EN 60898)\80 A
Nominal Tripping Current, In (A):
80,0
Conventional Tripping Current (A): 116,0
Instantaneous Tripping Current (A): 800,0
Short-circuit Clearing Time (s):
0,100
Earth Fault Clearing Time (s):
0,400
Page 1 of 3
15/10/2015, 3:43
Table 6: Results
Minimum conductor crosssectional area (mm2)
10,0
2
10,0
2
16,0
1
ON
Active Conductor:
Neutral Conductor:
Earth Conductor:
No. of circuits
PASS
PASS
PASS
PASS
PASS
PASS
PASS
TR
IA
LV
ER
SI
Page 2 of 3
15/10/2015, 3:43
ON
SI
0,96
0,42
1,92
11,50
0,110000
0,000000
0,873
2,200000
0,000000