CableCALC Pro BS7671 Report

15/10/2015, 3:43

Table 1: Standards
BS 7671:2008+A3:2015

Installation Method:
Insulation:
Cores:
Armour:
Material:

SI

ON

Table 2: Cable
E, F, G In free air or on a perforated cable tray
etc, horizontal or vertical Touching
Mineral Bare and Not Exposed to Touch
Single core
Armoured
Copper
Table 3: Load
10,00
1,00
0,0
100
Radial

ER

Design Current, Ib (A):


Power Factor (lagging):
Phase Angle (degrees):
Efficiency (%):
Circuit Arrangement:

LV

Table 4: Supply
Phases:
1 phase
Voltage (V):
230
Permissible Voltage Drop (%):
2,50
Length:
50,00
Upstream Fault Level (kA):
1,00
Source Impedance, Ze (Ohms):
0,00
Frequency (Hz)
50
System Grounding:
TN-C-S

TR

IA

Table 5: Protection
Protection Provided:
Overload and short-circuit protection
Miniature Circuit Breaker (MCB)\Type C (BS
Protective Device:
EN 60898)\80 A
Nominal Tripping Current, In (A):
80,0
Conventional Tripping Current (A): 116,0
Instantaneous Tripping Current (A): 800,0
Short-circuit Clearing Time (s):
0,100
Earth Fault Clearing Time (s):
0,400

CableCALC Pro BS7671 (V2.3)

Software by Electrotechnik www.ELEK.com.au

Page 1 of 3

CableCALC Pro BS7671 Report

15/10/2015, 3:43

Table 6: Results
Minimum conductor crosssectional area (mm2)
10,0
2
10,0
2
16,0
1

ON

Active Conductor:
Neutral Conductor:
Earth Conductor:

No. of circuits

PASS
PASS
PASS
PASS
PASS
PASS
PASS

TR

IA

LV

ER

SI

Table 7: Calculation Checks


Protective device rating (In = 80,0 A) is Less Than or Equal To the effective
circuit current-carrying capacity (Iz = 90,0 A).
Effective circuit current-carrying capacity (Iz = 90 A) is Greater Than or
Equal To the design load current (Ib = 10 A).
Protective device rating (In = 80,0 A) is Greater Than or Equal To the
design load current (Ib = 10,0 A).
Actual voltage drop (0,42 %) is Less Than or Equal To the permissible
voltage drop as specified by the user (2,50 %).
Actual earth loop impedance (Zs = 0,125 Ohms) is Less Than or Equal To
the device earth loop impedance (0,273 Ohms).
Short-circuit performance of active conductors (Smin = 1,5 mm2) is
Adequate.
Short-circuit performance of protective conductors (Smin = 2,9 mm2) is
Adequate.

CableCALC Pro BS7671 (V2.3)

Software by Electrotechnik www.ELEK.com.au

Page 2 of 3

CableCALC Pro BS7671 Report

15/10/2015, 3:43

ON

Table 8: Current-carrying Capacity: PASS


Effective Current-carrying Capacity of Circuit, Iz (A):
90,00
Effective Spare Current-carrying Capacity of Circuit (A):
10,00
Overall Correction Factor:
1,000
Conductor Operating Temperature (deg.C.):
30,49
Tabulated Current-carrying Capacity of Cable (A):
45,00
TABLE:
4D5
Column No.:
2
Table 9: Voltage Drop: PASS

SI

0,96
0,42
1,92
11,50
0,110000
0,000000
0,873
2,200000
0,000000
4D5
8

LV

ER

Voltage Drop (V):


Voltage Drop (%):
Voltage Drop (mV/A/m):
Permissible Voltage Drop (mV/A/m):
Circuit Resistance, R1 (Ohms):
Circuit Reactance, X1 (Ohms):
Temperature Correction Factor, Ct:
Tabulated Resistance (mV/A/m):
Tabulated Reactance (mV/A/m):
TABLE:
Column No.:

IA

Table 10: Earth Fault Loop Impedance: PASS


Protective Device Impedance, Zmax (Ohms):
0,273125
Actual Earth Fault Loop Impedance, Zs (Ohms):
0,125283
External Earth Fault Loop Impedance, Ze (Ohms):
0,000000
Impedance of Live Conductors, Z1 (Ohms):
0,055000
Impedance of Protective Conductors, Z2 (Ohms):
0,070283

TR

Table 11: Short-circuit Performance - Active Conductors: PASS


Phase-to-neutral Short-circuit Current, Ipn (A):
676
Material, Initial (ti) and Final Temperature (tf) Constant, K:
142,35
Min. Cross-sectional Area of Active Conductors, (mm2):
1,50
Table 12: Short-circuit Performance - Protective Conductors: PASS
Phase-to-earth Short-circuit Current, Ipe (A):
647
Material, Initial (ti) and Final Temperature (tf) Constant, K:
142,35
Min. Cross-sectional Area of Protective Conductors, (mm2): 2,88

CableCALC Pro BS7671 (V2.3)

Software by Electrotechnik www.ELEK.com.au

Page 3 of 3