Академический Документы
Профессиональный Документы
Культура Документы
TRANSFORMER
PREFACE
CURRENT
TRANSFORMER
Acknowledgment
The Technical Data Given in this book is for
information purpose. This Book is combined effort
of experience experts and based on Standards.
It is my great pleasure and honor to introduce this
Book. I am sure it will be used fruitfully by all
persons involved in the implementation of Current
Transformer
-Adhish Gupta
Electrical Engineer
Please provide your feedback at
www.eazyword.com
www.eazyword.com is an online Professional graphic designing organization established in 2013 with a vision of providing
Graphic Designing services at nominal rates, During initials days of trouble, eazyword.com were in only logo designing field
,Sincere efforts were being used to improve quality & Skills in delivering the professional designing. People start appreciating
sincere dedication shown by organization towards the work and efforts enables us to expand in the area of Book, Magazine &
other designs. Current transformer- Edition 2015 being the one of the result of our sincere effort. In this Book ,We have kept a
space for reader of any kind. We have used a professional technique in this book which enables reader to learn basic &
Important facts quickly without going deeply.
Please provide your feedback regarding book designing at: design.team@eazyword.com or by filling the feedback form at
www.eazyword.com
eazyword.com
Contents
1. Introduction to basic theory
1.1 Let us understand current transformer 1
1.2 Working & main constructional parts of current transformer 1
1.3 Ideal Transformer 2
1.4 C.T equivalent Circuit 3
1.5 Phasor Diagram 4
1.6 General principle of measuring current and voltage 4
1.7 Exciting Current 4
1.8 Why secondary of a CT never kept open? 5
5.1.1
Rated burden of CT 18
5.1.2
Actual burden of CT 18
5.1.3
5.1.4
5.1.5
Rated frequency 22
5.1.6
5.1.7
5.1.8
5.2
5.3
5.4
5.5
5.6
What is CT Burden? 18
Interesting facts 18
4 or 6 wire connection 19
Interesting facts 21
Difference between Dynamic peak Value and Rated Thermal short
Circuit current 21
5.7
5.8
Interesting facts 28
Secondary circuit characterstics 23 to 33
5.8.1
5.8.2
Accuracy Classes 27
5.8.3
Rated output 28
5.8.4
5.8.5
5.8.6
5.9
5.10
5.11
5.11.1
to 33
Definite time over current protection 30
Generator Differential 32
5.11.3.2
Motor Differential
5.11.3.3
Transformer Differential 33
32
6. How to do CT Selection
6.1
6.2
8.4
8.4.1
8.4.2
Procedure of IR test 47
8.4.3
Polarity test 47
8.4.4
Burden test 48
8.4.5
8.4.6
8.5
8.6
8.7
8.8
Advantage of IR test 46
Interview question: What happen if Transformer is given DC supply? 47
Factors which caused Burden error 48
Interview question: What will be the turns ratio required to match an
9. Terms &
Definitions
52 to 54
Did you know? Metering
function of current
transformer 54
Bibliography 59
Applicable standards 60
51
Introduction to
Basic Theory
CHAPTER-1
Primary Conductor
Hollow core
Ammeter
C.T
Is
Secondary Winding
Primary Current, Ip
Secondary Winding
Circuit Symbol
Working: A time varying voltage is applied to the primary winding which drives magnetic flux in the core and
induces a voltage in the secondary winding. The transformer draws an exciting current to maintain the flux in a core.
"Rate of change of flux linkage with respect to time is directly proportional to the induced EMF in a
conductor or coil".
Faradays laws of Electromagnetic Induction
Is
Ip
Es
IP = N x IS
Eqn.1
ES d
dt
Where:-
Figure-1.0
N = Turns ration of turns between primary & secondary winding .Mostly, the primary of a CT is a straight
through bar or in other words we can say a single turn.
Es = Is x Z
Eqn.2
Np
Ip
Ns
Is
Ek
ZCT
ZB
transformer (volts)
Vt
Vt
= Is . ZB
= Ek - Is. ZCT (Volts)
Eqn.3
EK = 4.44 X B X A X f X N
(Volts)
Eqn.4
Ek
B
A
=
=
f
=
N
=
x2 =
Example: 1
Suppose a CT with Ratio 2000 / 5A is given having Max Flux Density = 1.6 T , Core C.S.A = 20 cm2,RS = 0.31 &
IMAX Primary = 40 kA. Then, find the maximum secondary burden permissible in terms of ohm if no saturation is to
occur.
Sol:
BURDEN
= 284 Volts
= 284 / 100
= 2.84 Ohms
Xs
Rs
Is
Ip
Xm
Rm
Ie
Vt
Figure-1.2
Where:
Ie
Is
Zb
N
Ze
Zb
=
=
=
=
=
Es
Vt
Ip
ZCT
=
=
=
=
Secondary excitation impedance in ohms (Rm+jXm) C.T. terminals impedance in ohms (Rs+jXs)
Phasor Diagram
Where:
Ep
Im
Es
Ie
Ip
Ic
Is
=
=
=
=
=
=
=
=
Primary voltage
Magnetising current
Secondary voltage
Ip/N
Excitation current
Flux
Primary current
Iron losses (hysteresis & eddy currents)
Secondary current
Figure-1.3
Current transformer
For a Closed-circuited transformer the following is valid:
Ip X N1 = Is X N2
Eqn.5
IP = N x IS
As per Eqn.1
This equation gives current transformation in proportion to the primary and secondary turns. A current transformer is
ideally a short-circuited transformer where the secondary terminal voltage is zero and the magnetizing current is
negligible.
2. Voltage transformers
For a Voltage transformer in no load the following is valid:
Ep
Es
Np
Ns
Eqn.6
This equation gives voltage transformation in proportion to the primary and secondary turns.
A voltage transformer is ideally a transformer under no-load conditions where the load current is zero.
Exciting
Current
In an ideal current transformer, the primary ampere-turns are equal to the secondary ampereturns. However, every core material requires some energy to produce the magnetic flux which
induces the secondary voltage necessary to deliver the secondary current. This energy is
provided by exciting current .Thus, in an actual current transformer, the secondary ampereturns are equal to the primary ampere-turns minus the exciting ampere-turns.
Ip
I2 = N1 X I1
N2
Is
Figure-1.4
Eqn.7
BURDEN
The current transformation requires a small amount of energy to magnetize the iron core that creates small energy
losses such as eddy currents, and heat caused by current flowing through the windings. Therefore, the secondary
current is not a perfect representation of the primary current. Hence Eqn.7 is modified to Eqn.8, where Ie represent
Exciting current.
Ie
Burden
Eqn.8
I22
Exciting
Impedance
I2 = N1 X I1 - Ie
N2
(N1/N2) x I1
Figure-1.5
The diagram shows that not all the equivalent primary current passes through the secondary circuit. Part of it
consumed by the core, which means that the primary current is not reproduced exactly. The relation between
the currents is stated in Eqn.8 (Figure-1.6)
Thus, primary current contains two components:
An exciting current Ie, which magnetizes the core and supplies the eddy current and hysteresis losses, etc.
A remaining primary current component (I1-Ie), which is available for transformation to secondary current in the
inverse ratio of turns.
Why
secondary
Of CT never kept
open?
Current transformer
CHAPTER-2
To make power system more sensitive towards detecting even the smallest fault protection relays are used which isolate
the fault by tripping CBs. Current transformer is responsible to give fault current related feedback signal to respective relay
to operate when secondary current of CT exceeds the threshold value of relay (Generated Feedback signal of transformer
is in form of small current which is ranges from 0A to 5 A).
a.
b.
c.
Permanent monitoring of network electrical parameters by reliable and properly selected current transformers
supplying protection relays allows rapid isolation of the faulty area. These relays must ignore transient and normal
disturbances but systematically trip when a destructive fault has to be eliminated. Thus, correct selection of Current
transformer is necessary otherwise it can lead to malfunctions in the protection channel causing destruction of
equipment and create danger to the operator.
2. On the other hand, under-estimation of the short-circuit current can lead to failure to
detect the fault, thus destroying the equipment, placing the operator in danger and
generating operating downtime.
3. An output power or accuracy error can result in a malfunction or in failure to trip of the
protection devices, thus destroying the equipment, placing the operator in danger and
generating operating downtime.
4. An error in defining the accuracy class of a metering winding will lead to incorrect
energy billing and thus a loss of income for the electrical utility or the customer
Necessary
information
required to specify the CT
with single primary are:
a.
b.
c.
d.
e.
f.
g.
Insulation Level(KV)
Short-Circuit Current Withstand Capacity(KA)
Short-Circuit Duration(S)
Nominal Primary Current(A)
Number of secondary Winding
Associated Protection & Metering with Secondary
Output Power(Including relay and wire
Consumption)(VA)
h. Accuracy Class
a. ALF(Protection)
b. SF(Metering)
i. Nominal Secondary Current(A)
Definition of protection
The protection functions of a network are intended to monitor one or more parameters of the installation, for
example: currents, voltage, temperature, frequency, etc. These values are permanently measured and
compared with set points or thresholds beyond which the situation is defined as abnormal and dangerous.
When a fault occurs, the protection device issues a tripping signal. Then, in order to durably isolate the faulty part, it
prevents reclosing until the device has been repaired. It can also generate an alarm to inform maintenance personnel
and enable them to take the necessary action.
Importance of CT
Current transformers are used to supply information
to the protective relays and/or current, power and
energy metering instruments. For this purpose they
must supply a secondary current proportional to the
primary current flowing through them and must be
adapted to network characteristics: voltage,
frequency and current.
Instrument Class
An instrument CT requires good accuracy around the
nominal current value. The metering instruments do not
need to withstand currents as high as the protection
relays. This is why the instrument CTs, unlike the
protection CTs, have the lowest possible Safety Factor
(SF) in order to protect these instruments through earlier
Saturation.
Table.-2.0
Example: 2
CT Rating Plate indicates the following details, an
example of representation of protection CT
Rated primary current: 200 A,
Rated secondary current: 5 A.
15 VA 5P 10
Accuracy limit factor = 10
Accuracy class = 5P
Accuracy power = 15 VA
Its accuracy load: Pn = 15 VA
Its accuracy limit factor is ALF = 10
For I = ALF X In, its accuracy is 5% (5P)
Interesting Facts
It should be remembered when two or more devices are required to be connected at the
secondary terminal of a CT, Devices must be connected in series across the winding. This is
exactly the opposite of the method used to connect two or more loads to be supplied by a
voltage or power transformer where the devices are paralleled across the secondary winding.
Current transformer
Classification
CHAPTER-3
Current transformers are classified based on construction and application. Classifications according to both are explained
below:
Figure-3.0
Figure-3.2
Interesting Facts
Ring type (or rectangular type) CTs are normally preferred over other types of CTs. because
they are simple in construction, mechanically stronger and cheaper. In a ring type/bar primary
type CTs the working ampere-turns are determined by the primary current and therefore
necessarily, the accuracy that can be offered with these CTs becomes progressively inferior as
the rated primary current decreases.-If higher accuracy and burdens are required for CTs of low
primary current wound types CTs are used.
2. Current transformers are classified In accordance with their nature of application
Figure-3.3
Figure-3.4
c. Interposing Transformer
Transformer
differential
relays
compare the phase and magnitude of
the current entering one winding of
the transformer with that leaving via
the other winding(s). Any difference in
phase or magnitude between the
measured quantities will cause
current to flow through the operate
winding of the relay. If this current
exceeds the relay setting, tripping of
the transformer circuit breakers will
be initiated.
Figure-3.5
10
To enable a comparison to be made, the differential scheme should be arranged so that the relay will see rated current
when the full load current flows in the protected circuit. In order to achieve this, the line current transformers must be
matched to the normal full load current of the transformer. Where this is not the case it is necessary to use an auxiliary
interposing current transformer to provide amplitude correction. The connection of the line CTs should compensate for
any phase shift arising across the transformer. Alternatively the necessary phase correction may also be provided by the
use of an interposing CT.
Thus, the main function of an interposing CT is to balance the currents supplied to the relay where there
would otherwise be an imbalance due to the ratios of the main CTs. Interposing CTs are equipped with a
wide range of taps that can be selected by the user to achieve the balance required.
Earth
Fault
Relay
Core
Figure-3.6
An earth fault relay, connected to the secondary winding, is energized only when there is residual current in the primary
system. The advantage in using this method of earth fault protection lies in the fact that only one CT core is used in
place of three phase CTs whose secondary windings are residually connected. In this way the CT magnetizing current
at relay operation is reduced by approximately three-to-one, an important consideration in sensitive earth fault relays
where a low effective setting is required.
Core Balance CTs are special CTs used to detect Earth faults & usually used for Restricted Earth Fault Protection.
It is a ring type CT through which the cables carrying current of all the three phases (R, Y & B) are passed through.
Under normal operating conditions, summation of current through the three phases shall be equal to zero. In event of a
fault (as shown in Figure-3.6), the summation of the current shall no longer remain zero (zero sequence current shall flow
during earth fault) & thus the fault can be detected.
Core-balance transformers are normally mounted over a cable at a point close up to the cable gland of switchgear or
other apparatus. Physically split cores (slip-over types) are normally available for applications in which the cables are
already made up, as on existing switchgear.
11
Remanence
Remanent flux can be set up in the core of a current transformer under operating or test conditions. During operating
conditions, remanent flux can be left in the core while the primary current is interrupted and the flux density in the core of
the transformer is high. Remanence flux may be left in the core of transformer during clearing of fault current, testing such
as resistance or continuity measurements.
The remanent flux in the core depends on many factors such as
Magnitude of primary current,
Impedance of the secondary circuit
Amplitude and time constant of any offset transient.
Since the impedance of the secondary circuit is generally fixed, the magnitude of remanent flux is governed by the
magnitude of the symmetrical component of the primary current and the magnitude of the offset transient prior to the
primary current interruption.
Maximum remanent flux can be obtained under conditions whereby the primary current is interrupted while the
transformer is in a saturated state.
When the current transformer is next energized, the flux changes required will start from the remanent value. If the required
change is in the direction to add to the remanent flux, a large part of the cycle may find the current transformer saturated.
When this occurs, much of the primary current is required for excitation and secondary output is significantly reduced and
distorted on alternate half cycles.
When excitation is removed during high magnitude fault events, this remnant flux can be quite high. The remnant flux
essentially shifts the normal operating flux of CT and will require either more or less exciting current .During a subsequent
fault; this remnant flux can push the core deeper into saturation.
This phenomenon is illustrated in Figure-3.7
(B)
(A)
Flux
Density
Magnetizing Force
Figure-3.7
How to
correct
remanance
Remnant
flux
The flux in the core of a CT is a function of both the excitation voltage and the magnetic properties of the
core itself. When excitation is removed from the CT, same of the magnetic domains retain a degree of
orientation relative to the magnetic field that was applied to the core. This is known as remnant flux.
12
Error calculations
CHAPTER-4
True ratio
current vector. It is usually
express inRatio
minutes
Marked
RCF=
True ratio=
Eqn.9
Eqn.10
Eqn.11
PACF=
Eqn.12
Eqn.13
The factor by which the reading of a watt meter or the registration of a watt hour meter must be multiplied to
correct for the effect of ratio error and phase angle is the Transformer Correction Factor (TCF)
Where:
13
Interesting Facts
The phase error is generally not significant where as amplitude of the current is
important, but phase error matters significantly when the CT is used in measuring
power, when voltage and current signals are multiplied together. Accordingly,
applications requiring accurate power measurements should use a CT with low phase
error. For highest accuracy, a non-opening nickel iron alloy toroidal core provides
the most inductance, and therefore the least error.
Example: 3
If a CT with RCF of 1.0020 has a phase angle error = +15 and is used for measuring a load whose power factor is
0.500 lagging, determine its phase angle correction factor, PACF?
Sol:
RCF=1.0020
The primary current lags the line voltage by an angle whose cosine equals the power factor.
The secondary current leads the primary current by 15'. Therefore, the primary current
actually lags the primary voltage by 59 45'.
cos-1 (0.500) = 60 =
Or
cos = cos 60 = 0.500
= 60 = 59 60'
( - ) = 59 60' - 0 15' = 59 45
Thus,
cos ( - ) = cos 59 45' = 0.5038
Using Eqn.12
PACF =
Using Eqn.13
Cos
0.500
=
Cos (-)
0.5038
= 0.9925
14
Esi = I2 X Z (Volts)
Eqn.14
Z=
Eqn.15
(Ri+ Rb) + X b
Z =Impedance,
Ri =Winding Resistance,
Rb=Load Resistance,
Xb=Load Inductance,
2. The inductive flux density necessary for inducing the voltage Esi can be calculated from
Where
f =Frequency in Hz,
Aj = Core Are in MM2,
N2=Number of secondary turns,
B =Magnetic Flux in Tesla,
As per Eqn.4
B=
Esi
X 2 X f X Aj X N2
Eqn.16
Ie=
HXL
Eqn.17
N2
Where
H =Exciting force in At/m,
L = Length of magnetic path in Mtr,
N2=Number of secondary turns,
Xb
Eqn.18
(Ri+ Rb)
5. Current error
The error with a transformer introduces into the measurement of a current and which arises
from the fact that actual transformation ratio is not equal to the rated transformer ratio. The
current error expressed in percentage is given by the formula:
(Ka X Is - Ip)
Ip
X 100
Eqn.19
15
.
Where
CURRENT ERROR AT
RATED CURRENT (%)
1
PHASE DISPLACEMENT AT
RATED
CURRENT(Minutes)
60
COMPOSITE ERROR
RATEDACCURACY LIMIT
PRIMARY CURRENT(%)
5
5P
10P
10
15P
15
Table-4.0
Example: 4
1 VA ammeter is connected to the secondary of CT (2000/5A) measuring current of 4.9A when primary current
flowing through it is 2000A, then find out how much current error will be there if CT rated Burden is given as 15VA?
Sol:
As mentioned above,
Primary Current, Ip= 2000A
Secondary Current, Is=4.9 A
Thus, Transformation Ratio, Kn= 2000/5 =400
Using Eqn.19
Current error (%) = {(400 x 4.9 2000) x100}/2000 = -2%
Here, negative sign figure represents secondary current is lower than the rated nominal value.
16
6. Composite Errors(c):
Under-Steady Conditions, the R.M.S value of the difference between the instantaneous values of the
primary current, and the instantaneous values of the actual secondary current multiplied by the rated
current transformation ratio, the positive signs of the primary and secondary current corresponding to
the convention for terminal marking is generally expressed as percentage of the primary current
according to the following formula;
c = 100
Ip
1 T
(kn is - ip ) dt
T 0
Eqn.20
Where
Error
reduction
Can be done by:
1.
17
Terms to be used in
Specifying CT
CHAPTER-5
1.
Pn = In X Rn
Eqn.21
Where,
Pn =
In =
Rn=
What
Is
CT Burden ?
or
As per IEC 60044-1
Pr = In X Rp
Eqn.22
Pr =
In =
Rp=
Interesting Facts
CT performance is characterized by:
1.
2.
3.
4.
5.
Turns ratio,
Turns ratio error (ratio correction factor),
Saturation voltage,
Phase angle error, and
Rated secondary circuit load (burden).
18
4- or 6-wire connection
If 6-wire connection is used, the total length of the wire, naturally, will be two times the distance between the CT and the
relay. However, in many cases a common return conductor is used .Then, instead of multiplying the distance by 2, a factor
of 1.2 is typically used. This rule only applies to the 3-phase connection.
The factor 1.2 allows for a situation, where up to 20% of the electrical conductor length, including terminal resistances, uses
6-wire connection and at least 80% 4-wire connection.
6 wire CT connection
Figure-5.0
4 wire CT connection
Suppose, the distance between the CT and the relay is 10 meters. Then, total length is 2 x 10 m = 20 meter for
6-wire connection whereas for 4-wire connection total length is 1.2 x 10=12 meter
Example: 4
The distance between the CTs and the protection relay is 10Mtr. 4Sq.MM CU Conductors in the 4-wire connection
are used. The burden of the relay input is less than 15m (5A input).Calculate the actual burden of the CT at 75C.
Sol:
Resistivity of Cu Conductor, =0.0216m (75C)
Resistance, R =
( X L)/A
Eqn.23
Using Eqn.23
Hence,
R=0.0648
19
Ksi = (Ith/In)
Eqn.24
Scale order of
Ksi
Ksi<100
Where,
100<Ksi<300
100<ksi<400
400<Ksi<500
Ksi>500
Manufacturing
Standard
Sometime difficult for
some secondary
characteristics
Difficult
Limited to some
secondary
characteristics
Very often impossible
Table-5.0
Knowing
over
current
coefficient allows us to know
whether a CT will be easy to
manufacture or not.
Each CT Must be able to thermally and dynamically withstand the defined shortcircuit current in defined duration (usually, 1sec is preferred) passing through its
primary current circuit until the fault is effectively broken.
For easier production we can:
20
Difference between Dynamic peak Value and Rated Thermal short Circuit current
Rated Thermal short Circuit
current
This is the maximum (R.M.S) Primary
current, which the transformer can
withstand keeping secondary winding
short circuited for a period of one
second, without reaching a temperature
that would be disastrous to the
insulation.
Interesting Facts
Dynamic peak Current (Idyn) is always greater than rated thermal short-circuit current, as per
electrical standards, value of Idyn in terms of Ith is stated given below.
IEC 50Hz
IEC 60Hz
ANSI/IEEE 60Hz
2.5 X Ith
2.6 X Ith
2.7 X Ith
Example: 5
Effect of reducing short circuit current duration / surge current Factor
Suppose we have following figures for a particular project
The short-time current for periods
other than one second Ix can be
calculated by using the following
formula:
Short-Circuit VA = 250MVA
Operational Voltage = 11KV
Rated Primary Current (In)= 20 A
Rated thermal short-circuit current (Ith)=
250 X 10 KVA
11 X 1.732KV
= 9622 A
Ix =
Using Eqn.24
It
x
Eqn.25
Where,
X=the actual time in seconds
21
Why?
6. Rated Voltage of the primary Circuit(Upr): This defines the insulation level of Equipment
Rated CT Voltage > Rated Installation Voltage
Generally we choose the rated voltage
based on the duty voltage, Us, according to
the figure:
Figure-5.0
7.
Ips
Ips
Ips
Ips
Ips
=
=
=
=
=
S / (1.732 X U)
S / (1.732 X U)
S / (1.732 X U)
P / (1.732 X U X Cos X )
(1.3 X Q) / (1.732 X U)
Eqn.26
Eqn.27
Eqn.28
Where,
S =
U =
P =
Q =
Ips =
**=Motor Efficiency
**In Case of Capacitor Feeder, 1.3 is a derating coefficient to take account of temperature rise due to capacitor harmonics.
22
a. Current Transformer must be able to withstand more than the rated current on a constant basis
which is normally expressed as 120%,150% and 200% of the rated primary current and this is
called extended current rating.
b. In the case of an ambient temperature greater than 40C for the CT ,the CTs nominal Current
(ipn) must be greater than Ips multiplied by the derating factor corresponding to type of feeder
or Cubicle.As a general rule derating factor is of 1% Ipn per degree above 40C.
c. Temperature rise depends on three parameters:
1. Rated current
2. Ambient temperature
3. Feeder type or cubicle type and its IP(Protection index)
How to
Choose
CT secondary
output?
The standard CT secondary current ratings are 1A & 5A, the selection is based
on the lead burden used for connecting the CT to meters/Relays.5A CT can be
used where Current Transformer & protectives device are located within same
Switchgear Panel where as 1A CT is preferred if CT leads goes out of the
Switchgear.
See example: 6 for better understanding
23
Example: 6
Lets consider 11kV/220KV transformer for transferring power from generator (at 11KV) (not shown) to Power grid
(220KV).Suppose CT-A & CT-B is used for GT Differential protection. Distance between the CT-A and 87 GT differential
protection relay of 1VA is 15Mtr whereas distance between CT-B and 87 GT differential protection relay is 40 Mtr.
POWER GRID
Rp or Rct 5 , states
that the burden imposed
by CT winding and
connecting lead between
CT & relay should be less
than 5 .
CT-B
87 GT Differential
Protections
Relay
TRANSFORMER
Rp or Rct 2 , states that
the burden imposed by CT
winding and connecting
lead between CT & relay
should be less than 2 .
CT-A
GENERATOR
Figure-5.1
** Cable resistance increase as cable length increase, Increase in the resistance will increased the burden on CT
24
Suppose a. 4Sq.MM CU Conductors cable is suggested to connect 87 GT differentials relay from CT-A and CT-B
Case-1
Total Burden imposed on CT by connecting lead (4 Sq.MM) of length 15Mtr and relay is calculated as follows:
4- or 6-wire connection
Refer page-19
Considering 4 wire system, 1.2 factor is
introduced in calculating Rp.
Selected CT specification
5VA
5P
10
2500/5
Burden
Accuracy Class
ALF
1/500 turn ratio
Selected CT specification
2VA
5P
10
1200/1
Burden
Accuracy Class
ALF
1/1200 turn ratio
CONCLUSION:
If we make comparison between 2500/5 & 1200/1 CT in selection, we will find that the 2500/5 CT is quite preferable as 5A
secondary CT is much cheaper than 1A secondary CT regardless of burden imposed of 5A secondary CT is higher than 1A
secondary CT because 5A secondary CT have 500 turns in its secondary that make it smaller in size as compare to 1 A
secondary which is expensive as well as require large area to accommodate in electrical panels.
Hence in this case we can go for 5VA CT 2500/5 for 15 Mtr Connecting lead length.
Case-2
Total Burden imposed on CT by connecting lead (4 Sq.MM) of length 40Mtr and relay is calculated as follows:
25
Selected CT specification
10 VA
5P
10
2500/5
Burden
Accuracy Class
ALF
1/500 turn ratio
Selected CT specification
2VA
5P
10
1200
Burden
Accuracy Class
ALF
1/1200 turn ratio
CONCLUSION:
If we make comparison between 2500/5 & 1200/1 CT in selection, we will find that the1200/1 CT is quite preferable as 1A
secondary CT is comparable cheaper than 5A secondary CT because 1A secondary CT burden is quite lower than 5A
secondary CT. Hence, we can say with the increase of distance beyond 30 Mtr between CT and relay ,1A secondary CT is
more preferable than 5A secondary because burden imposed on CT due to the connecting length drastically increased
for a distance greater than 30 mtr.
COMPARISON:
Case-1
Case-2
26
For burdens
0.1
25-100% of
rated burden
0.2
25-100% of
rated burden
<15 VA
1VA-100%
0.2S**
25-100% of
rated burden
<15 VA
1VA-100%
0.5
25-100% of
rated burden
0.5S**
25-100% of
rated burden
1.0
25-100% of
rated burden
3.0
50-100%
5.0
50-100%
5P and
5PR ***
10P and
10PR ***
PX ****
100%
100%
Ek, Ie, Rct 5)
at % rated
current
Ratio error %
5
20
100
120
5
20
100
120
1
5
20
100
120
5
20
100
120
1
5
20
100
120
5
20
100
120
50
120
50
120
100
ALF x In
100
ALF x In
-
0.4
0.20
0.1
0.1
0.75
0.35
0.2
0.2
0.75
0.35
0.2
0.2
0.2
1.5
0.75
0.5
0.5
1.5
0.75
0.5
0.5
0.5
3.0
1.5
1.0
1.0
3.0
3.0
5.0
5.0
1.0
52
3.0
10 2
-
Phase
displacement
minutes
15
8
5
5
30
15
10
10
30
15
10
10
10
90
45
30
30
90
45
30
30
30
180
90
60
60
60
-
Application
Laboratory
Precision
revenue
metering
Precision
revenue
metering
Standard
commercial
metering
Precision
revenue
metering
Industrial
grade
meters
Instruments
Instruments
Protection
Protection
Protection
Table-5.2
A 5P10 CT means 10 times rated current has a maximum error of 5% and only 1% at nominal current whereas 10P15 CT means 15
times rated current has a maximum error of 10% and 3% at nominal current.
27
1. For classes 0.1 0.2 0.5 1, the current error and phase
displacement at rated frequency shall not exceed the values given in
Table-5.2 when the secondary burden is any value from 25-100% of the
rated burden.
2. For classes 0.2S 0.5S, the current error and phase displacement at
rated frequency shall not exceed the values given in Table-5.2 when the
secondary burden is any value from 25-100% of the rated burden
Definition of ISF
ISF or Instrument Security Factor of current transformer is defined as the ratio between the limit primary
current (Ipl) to the rated primary current (Ipn).
The instrument limit primary current of metering CT is the value primary current beyond which CT core becomes
saturated
SF = Ipl/Ipn
Eqn.29
The rated Instrument Security Factor (SF) indicates the over current as a multiple of the rated current at which the
metering core will saturate. It is thus limiting the secondary current to SF times the rated current. The safety of the
metering equipment is greatest when the value of SF is small. Typical SF factors are 5 or 10. It is a maximum value
and only valid at rated burden.
To protect the instruments and meters from being damaged by high currents during fault conditions, a metering
core must be saturated typically between 5 and 20 times the rated current. Normally energy meters have the lowest
withstand capability, typically 5 to 20 times rated current.
Interesting Facts
.
28
Definition of ALF
ALF usually defined for the protection class current transformer, ALF can be stated as the ratio of
accuracy limit primary current to the rated primary current
Fa Fn X
Sin=Rct X In
Sn = Rn X In
Sa = Rp X In
Sin + Sn
Sin + Sa
Eqn.30
Eqn.31
Eqn.32
Eqn.33
Fa Fn X
Rct + Rn
Eqn.34
Rct + Rp
Where,
Fn
Fn
Sin
Sn
Sa
29
Example: 7
Suppose we have selected the below given CT for our purpose
CT is rated as 300/5, 5P20, 10 VA
Suppose internal secondary coil resistance of the CT is 0.07 and the secondary Side burden (including
wires and relay) is 0.117
Let us find out whether we have choosen right CT or not?
Sol:
Using Eqn.30,31,32
Fn = 20 (CT data 5P20),
Sin = (5A)^2 0.07 =1.75 VA
Sn = 10 VA (from CT data),
Sa = (5A)^2 0.117 = 2.925 VA
Using Eqn.34
.
Fa 20 X
1.75+10
1.75+ 2.9225
= 50.3
Hence, Fa > Fn
It shows we have chosen right CT
Where,
Ir
Isn
30
ALF > 20 X Ir
Eqn.36
Special Cases:
1.
Eqn.37
Eqn.38
Eqn.39
3. Differential Protection :
For differential Protection, many manufactures recommend Class X CTs with Vk given below
Vk a X If (Rct + Rb + Rr)
Eqn.40
Where,
Vk
a
Rct
Rb
Rr
If
Icc
Kn
= current
CT ratio calculation in determining the knee point voltage for differential protection
Fault
31
Eqn.41
Figure-5.2
Where,
Eqn.44
Where,
Figure-5.3
Eqn.46
32
Figure-5.4
The main purpose of calculating the knee point voltage is to identify the core saturation characteristics.
This is mainly done on protection CT's. Knee Point Voltage signifies saturation level of CT core. Knee
point calculation is done for CTs used for differential protection and REF.
The Knee Point Voltage of CT varies from Relay to Relay as per their implementation for different Protection
Secondary voltage
Interesting Facts
Figure-5.5
Figure-5.6
Exciting Current
33
How to do
CT Selection
CHAPTER-6
Lets start with an example, this will make easy to understand the selection criteria for CT
Example: 8
Objective:
Selection of 600/1 Current transformer specification of a bus bar differential protection for Line feeder using
relay MICOM 746(An Areva Product).
Required parameters to specify CT:
i)
ii)
iii)
iv)
v)
Points to be remembered:
1. Lead Resistance ,R l = 2 X single lead resistance for single phase
= 1 X single lead resistance for three phases
2. Knee Point Voltage for External Fault is
Eqn.48
Eqn.49
4 mm - Copper
Resistance per km
5.9 /km
Tentative Distance
95 Mtr
2 X 95 Mtr
1 x 95 Mtr
Similarly
Total resistance for single
phase fault current shall be
34
0.005 X 600/1 =3
For If=11.58KA
Fault occurs here is
called internal faults
B
B
Figure-6.0
Legends
A- 220KV Feeder
B- 220 KV Busbar
C- 220KV Grid line
Load Flow
A
B
35
>37.335 V
Case:2
>68.723 V
From case (1) and case (2), one can conclude that maximum value of Vk requirement shall be > 68.7236 V.
The Value is divided by 600 to connect the fault current equivalent to secondary circuit.
Therefore Selected CT Specification is:
Rated primary current
Rated secondary current
Accuracy class
Maximum secondary winding resistance (Rct)
Maximum exciting current (Ie) at the rated
knee-point(Vk/2)
Rated knee-point voltage (Vk)
600 A
1A
PX
3
Assumed
Assumed
As per protection
class
As per
manufacture
catalogue
30 mA
As per standard
100V
Nearest value of
68.7236 which can
be manufactured
Example: 9
Objective:
Selection of Current transformer specification for energy metering for Line feeder using relay MICOM 746(An
Areva Product).
Required parameters to specify CT:
vi)
vii)
viii)
ix)
x)
In case of selection of CT for metering purpose, we do not need to calculate knee point voltage as protection
CT operating threshold usually kept very high to allow a relatively accurate measurement of the fault
current.Therefore, there is need to calculate knee point voltage in case of protection CT. Same is not true for
CT selected for Metering purpose. The metering instruments do not need to withstand currents as high as the
protection relays. This is why the instrument CTs, unlike the protection CTs, have the lowest possible Safety
Factor (SF) in order to protect these instruments from earlier Saturation.
36
Points to be remembered:
1. Lead Resistance ,R l = 2 X single lead resistance for single phase
= 1 X single lead resistance for three phases
4 mm - Copper
Resistance per km
5.9 /km
Tentative Distance
90 Mtr
2 X 90 Mtr
Secondary current is 1 A as
600/1 CT is used in this example
600 A
1A
Rated Output
15VA
Accuracy Class
0.2
Safety Factor/Security
Factor
While considering the application of a CT it should be remembered that the total burden imposed on the
secondary winding is not only the sum of the burden(s) of the individual device (s) connected to the winding but
also includes the burden imposed by the connecting cable and the resistance of the connections.
38
Why measuring CT
is not advisable to
use as protection
CT?
Measurement of current
The output required from a current transformer depends on the application and the type of load connected
to it:
1. Metering equipment or instruments, like kW, kVar, Amp instruments or kWh or kVArh meters, are
measuring under normal load conditions. These metering cores require high accuracy, a low
burden (output) and a low saturation voltage. They operate in the range of 5-120% of rated current
according to accuracy classes:
a. - 0.2 or 0.5 as per IEC
b. - 0.15 or 0.3 or 0.6 as per IEEE
2.
For protection relays and disturbance recorders information about a primary disturbance must be
transferred to the secondary side. Measurement at fault conditions in the over current range
requires lower accuracy, but a high capability to transform high fault currents to allow protection
relays to measure and disconnect the fault.
a. Typical relay classes are 5P, 10P, PR, PX or TP (IEC) or C 100-800 (IEEE)
Remember:
To protect the instruments and meters from being damaged by high currents during fault conditions, a
metering core must be saturated typically between 5 and 20 times the rated current. Normally energy
meters have the lowest withstand capability, typically 5 to 20 times rated current.
Measuring C.T.s
Require good accuracy up to approx 120% rated
current.
Knee Point
Protection C.T.s
Accuracy not as important as above.
Ankle Point
39
Example: 10
Find maximum secondary burden permissible if no saturation is to occur.
Details of CT are given below:
C.T. Ratio = 2000 / 5A
RS = 0.31 Ohms
IMAX Primary = 40 kA
SOL
Number of turns, N = 2000 / 5 = 400 Turns
Max. Current to flow at secondary of CT, IS MAX = 40,000 / 400 = 100 Amps
Maximum Secondary Winding Voltage:
Eqn.46
Eqn.50
EK = 4.44 x B x A x f x N Volts
where :-
Eqn.47
EK
B
A
=
=
f
N
=
=
Using Eqn.50
INTERESTING FACTS
40
Current Transformer
Transient Performance
CHAPTER-7
Introduction
CT output is impacted drastically when the CT operates in the nonlinear region of its excitation characteristic. Operation in
this region is initiated by:
AC
Ip
DC
t
DC Components produces almost constant
magnetic flux in comparison with magnetic flux
produced by 50Hz.
IS
t
Figure-7.0
41
Vs(t)=Vm sin(wt + )
Eqn.51
Figure-7.1
I (0) =0
Eqn.52
e-(R/L)t
Eqn.53
Where,
Z=
R2+L2
= tan -1 L
R
X=L
Eqn.54
Eqn.55
Pure Resistive
0.5
Eqn.56
Figure-7.2
Eqn.57
42
How
Does
CT saturation
How ?
Occurs
Ks =
Vs
Isec x Zs
Ts = -X/R
2f
Eqn.56
x ln
1- Ks-1
X/R
)
Eqn.57
Ks
Vs
Isec
Zs
f
X
R
=
=
=
=
=
=
=
Saturation Factor
Saturation Voltage of CT (Volt)
Sec. Current at the CT
Total Sec. Impedance of CT circuit
System frequency
System reactance
System resistance
To Avoid Saturation, CT shall have enough capacity to develop the following voltage:
Vs =1+ X
R
I (Rct + Rb + Rr)
X f
Eqn.58
X/R ratio is important because it determines the peak asymmetrical fault current. X/R ratio is
responsible for the decaying DC component in fault current.
As per C37-110.1996, primary current asymmetry and CT saturation due to DC offset current
component are the primary component while performing CT calculation whereas symmetrical
primary current is no longer acceptable while performing CT calculation.
With the increase of X/R ratio the difference between the min-fault current and the steady state fault
current increases. This means that for highly reactive fault path the current measured by CT in the
first few cycles is significantly smaller than the actual fault current. As right after a fault occurs, the
current waveform is no longer sine wave. Instead, it can be represented by the sum of a sine wave
and a decaying exponential. This decaying exponential or DC wave added to sine wave (as shown in
Figure-7.0) causes the current to reach a much larger value than that of the sine wave alone and thus
becomes asymmetrical current waveform(Combination of sine wave and decaying exponential
waveform).
43
Current Transformer
C H A P T E R -8
1.
Insulation tester
3.
5.
Multimeter
Primary
injection Kit
2.
Polarity Tester
4.
Variac (0-2KV)
6.
2.5Sq.MM
connecting wire
44
Verify nameplate & Ratings mentioned on nameplate. It should be in accordance with the
approved drawings and specifications.
Inspect for any physical damage/ defects and mechanical condition.
Verify correct connection of transformers with system requirements.
Verify that adequate clearances exist between primary and secondary circuit wiring.
Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method.
Verify that all required grounding and shorting connection has been done.
Verify all shorting blocks are in correct position, either grounding or open as required.
Verify single point grounding of each core done properly. Grounding point shall be nearer to the
CT location. However grounding shall be at relay point in case of several CT secondaries
connected together like differential protection.
TYPE TEST
Type tests are intended to verify compliance
with the requirements laid down in the relevant
Standards for a given type of equipment. Type
tests are carried out on a sample of such
equipment or on such parts of equipments
manufactured to the same or similar design.
They shall be carried out on the initiative of the
manufacturer.
ROUTINE TEST
Routine tests are intended to detect faults in
materials and workmanship. They are carried
out on every equipment after its assembly or on
each transport unit. Routine Tests on
equipments are normally undertaken at the
manufacturer's premises
Routine Tests on equipments are not intended
to be repeated on site.
45
Nominal Circuit
Voltage (Vac)
250
Test Voltage
(Vdc)
500
Insulation
Resistance (M)
25
600
1000
100
1000
1000
100
2500
1000
500
5000
2500
1000
8000
2500
2000
15000
2500
5000
25000
5000
20000
15000
100000
Advantage
Of the IR test
Nominal
Circuit
Voltage
(Vac)
Extra low
Voltage
Test
Voltage
(Vdc)
Insulation
Resistance
(M)
250
0.5
Up to 500V
500
1.0
Above
500V
1000
1.0
Table-8.1
Table-8.0
46
PRIMARY
WINDING
SECONDARY
WINDING
PRIMARY
WINDING
M 500V
Figure-8.0
SECONDARY
WINDING
M 500V
Figure-8.1
TEST 2
Secondary winding to core
TEST 1
Primary winding to core
Insulation resistance of the order of several hundred/thousand mega ohms to infinity is necessary between phase
conductor and earth, between two or more phase conductors, between phase conductors and the neutral
conductor, between two conducting parts separated by insulation.
2. Polarity Test
Polarity test is conducted to confirm the polarity marking on the CT primary and secondary and verify
it is matching with concerned drawing. Moreover it gives an idea, how to connect the secondarys to
make the protection like directional, differential and metering function properly.
Isolate CT secondary from the load and put the galvanometer across the secondary of CT as shown in Figure-8.2
Battery 9V
+Ve
-Ve
S1
S2
P1
How to test
CT Polarity?
Interview
Question
No back E.M.F is induced while DC supply is given to transformer in the transformer primary
winding. Importance of Back E.M.F is that it limits the current drawn by the machine. In the
absence of back E.M.F transformer starts drawing excessive currents that leads to the
burning of primary winding.
47
3. Burden Test
Eqn.59
Burden testing of metering class CT involves measuring the secondary current of the CT while introducing
additional burden in graduated steps up to the rated burden of the CT and assuming constant customer
load during the duration of the test. If the measured secondary current remains constant during the
duration of the test then the CT is deemed to have passed the burden test as rated. Thus, this test ensures
CTs ability to feed the rated burden as mentioned on nameplate. If the Connected load is changing during
the burden test then the secondary current will correspondingly change giving a false indication of burden
error. This is a major limitation of burden testing
Hence when a burden error is detected a tightening of the screws in that circuit will usually correct the
error. Otherwise, a search for and elimination of the high burden component will be necessary.
Burden
ERROR
Caused by:
Note:
48
Demagnetisation
Before starting the test, demagnetize the core by Injecting voltage on secondary terminals and increase
voltage gradually till there is considerable increment in current with a small voltage increment. Now start
decreasing the voltage to zero, the rate at which increased.
Magnetisation test
Now increase the voltage and monitor the excitation current up to the CT reaching near to saturation point.
Record the reading of voltage and current at several points. Plot the curve and evaluate the Vk and Img
from the graph
Example: 11
Objective:
Study on current transformer-Protection CT magnetization curve test
Suppose we have selected Protection Current transformer 5P 10 for some application in which CT secondary
wire resistance is 0.1.
Errors in C happened because of excitation current, therefore, in order to check CT functioning is correct or not, it
is essential to plot excitation curve.
The magnetization current Ie of a CT depends on the cross section, length of the magnetic circuit, the number of
turns in the windings, and the magnetic characteristics of the material.
From Eqn.2
Es = Is x Z
primary current and therefore the secondary current is increased, these currents reach a point where the core
commences to saturate and the magnetization current becomes sufficiently high to produce an excessive error.
While investigating the behavior of a CT, the excitation current should be measured at various values of voltage,
this test is also known as secondary injection test.
49
Voltage (V)
Magnetizing
Current (mA)
28
35
43
11
48
13
55
15
64
17
72
19
83
20
92
Table-8.2
Vk
20
15
1
5
10
0
20
30
40
50
60
70
80
90
100
110
120
130
50
To protect against insulation failure, do not exceed more than 1000 volts on any of the
secondary windings of the CT under test
R, Y and B Temporary shorted
To Relay
Figure-8.4
Primary Injection
Interview
Question
What will be the turns ratio required to match an 80 source to a 320 load?
V1 X I1=V2 X I2
Eqn.60
( VV12 )2 =
V1
V2
V1 X V1 = V2 X V2
R1
R2
2 = 320
V1
80
V2
R1
R2
Eqn.61
N1 =2
N2
51
Terms and
1. Instrument transformer: A transformer intended to supply measuring instruments, meters, relays and other
similar apparatus.
2. Current Transformer: A current transformer in which the secondary current, in normal conditions of use ,is
substantially proportional to the primary current and differs in phase from it by an angle which is approximately
zero for an appropriate direction of connections.
3. Primary Winding: The winding through which the current to be transformed flows.
4. Secondary Winding: the winding which supplies the current circuits of measuring instruments, relays or similar
apparatus.
5. Rated Primary current: The value of primary current on which the performance of the transformer is based.
6. Rated Secondary current: The value of secondary current on which the performance of the transformer based.
7. Actual Transformation Ratio: The ratio of primary current to secondary current.
8. Current Error Ratio: The error which a transformer introduces into measurement of a current and which arises
from the fact that the actual transformation ration is not equal to the rated transformation ratio
(Ka X Is - Ip)
Ip
X 100
Eqn.62
Where
9. Phase Displacement: Difference in phase between the primary and secondary current vectors, the directions of
vectors being so chosen that the angle is zero for prefect transformer.
Phase error is said to be positive when the secondary current vector leads the primary current vector. It is usually
expressed in minutes or centiradians.
10. Accuracy Class: A designation assigned to current transformer the error of which remain within specified limits
under prescribed conditions of use.
11. Burden: the impedance of secondary circuit in ohms and power-factor. The burden is usually expressed as the
apparent power in volt-amperes absorbed at a specific power factor and at the rated secondary current.
52
12. Rated Burden: The value of apparent power (in Volt-ampere at specific power factor) which the transformer intended
to supply to the secondary circuit at the rated secondary current and with rated burden connected to it.
13. Highest voltage for equipment: the highest r.m.s phase to phase voltage for which a transformer is designed in
respect of its insulation.
14. Rated Insulation Level: the combination of voltage values which characterizes the insulation of a transformer with
regard to its capability to withstand dielectric stresses.
15. Rated short-time thermal current(Ith): the r.ms value of the primary current which a transformer will withstand for
one second without suffering harmful effects, the secondary winding being short-circuited.
16. Rated Dynamic current(Idyn): the peak value of primary current which a transformer will withstand without being
damaged electrically or mechanically by resulting electromagnetic forces, the secondary winding being short-circuited
17. Rated continuous thermal current(Icth):the value of current which can be permitted to flow continuously in the
primary winding ,the secondary winding being connected to the rated burden, without the temperature rise exceeding
the values specified.
18. Exciting Current: the r.m.s value of the current taken by the secondary winding of current transformer, when a
sinusoidal voltage of rated frequency is applied to the secondary terminals, the primary and any other windings
winding being open-circuited.
19. Secondary winding resistance (Rct): Secondary winding d.c resistance in ohm connected to 75C or such other
temperature as may be specified.
24. Protective current transformer: a current transformer intended to supply protective relay
25. Rated accuracy limit primary current: the ratio of the rated accuracy limit primary current to the rated primary
current
26. Accuracy limit factor: the ratio of the rated accuracy limits primary current to the rated primary current.
53
27. Secondary limiting e.m.f: the product of accuracy limits factor, the rated secondary current and the vectorial sum
of the rated burden and the impedance of the secondary winding.
28. Saturation Flux: the peak value of flux which would exist in a core in the transition from the non-saturated to the
fully saturated condition and deemed to be that point on the B-H characteristics for the core concerned at which
10% increase in B causes H to be increased by 50%.
29. Remanent flux: the value of flux which would remain in the core 3 Min after interruption of an exciting current of
sufficient magnitude to induce the saturation flux.
30. Remanence Factor(Kr): the ratio Kr=100 X (Saturation Flux / Remanent flux),expressed in %
31. Rated knee point E.M.F: the minimum sinusoidal e.m.f( r.m.s) at rated frequency when applied to the secondary
terminal of the transformer ,all other terminal being open-circuited, which when increased by 10% causes the r.m.s
exciting current to increase by no more than 50%.Note: Actual knee point e.m.f > rated knee point e.m.f
32. Turns ratio error: the difference between the rated and actual turns ratios, expressed in %
Turn ratio Error (%) = (Actual turns ratio Rated turns ratio)
X 100
Rated Turns ratio
Eqn.63
33. Dimensioning Factor (Kx):a factor assigned by the purchaser to indicate the multiple rated secondary current
(Isn) occurring under power system fault conditions, inclusive of safety factor ,up to which the transformer is
required to meet performance requirements.
Metering Functions of a
Current Transformer
Current across the secondary winding of
a transformer is directly proportional to
the current across the primary winding.
Direct measurement of current across
the secondary winding allows an indirect
calculation of the current conducted
across
the
primary
winding.
Measurements may be used for
calculating energy usage in power
supply billing.
54
Current Transformer
Summary
C H A P T E R -10
Power grid transformers may be used to increase or decrease the current of the
power supply. A step-up transformer decreases the current and increases the
voltage of power from an energy plant generator before transmission over long
distance power lines. This reduces the costs of transmission by permitting use of
smaller power lines with less energy loss. Step-down transformers increase current
at the point of use.
3
4
55
The principal requirements of a measuring CT are that, for primary currents up to 120%
or 125% of the rated current, its secondary current is proportional to its primary current to
a degree of accuracy as defined by its Class (See table 5.2) and, in the case of the more
accurate types, that a specified maximum phase angle displacement is not exceeded.
A desirable characteristic of a measuring CT is that it should saturate when the
primary current exceeds the percentage of rated current specified as the upper limit
to which the accuracy provisions apply.
Protection CT
On the other hand the reverse is required for the protective type CT, the principal purpose
of which is to provide a secondary current proportional to the primary current when
it is several, or many, times the rated primary current. The measure of this
characteristic is known as the Accuracy Limit Factor (A.L.F.).
A protection type CT with an A.L.F. of 10 will produce a proportional current in the
secondary winding (subject to the allowable current error) with primary currents up to a
maximum of 10 times the rated current.
INTERESTING FACTS
It should be remembered when using a CT that where there are two or more devices
to be operated by the secondary winding, they must be connected in series across
the winding. This is exactly the opposite of the method used to connect two or more
loads to be supplied by a voltage or power transformer where the devices are
paralleled across the secondary winding.
Comparison face
Power Transformer
Current transformer
No. of cores
One core
At least more than one
turns
MVA
Voltage reduction
Parallel
Series
56
Points to be remembered
Frequency affects
At very low frequency, lines of flux generated by the primary current begin to appear as DC;
a C/T needs the AC CYCLE changes to induce the secondary current. With toroidal C/T,
you will experience a drop in accuracy if the frequency goes down from 60 Hz. One can
manufacture a C/T with an exotic metal core that is not quite as affected as the silicon
grain oriented steel most commonly used, but the improvement would be questionable and
at high cost.
9
10
The rated Instrument Security Factor (FS) indicates the over current as a multiple of the
rated current at which the metering core will saturate. It is thus limiting the secondary
current to FS times the rated current. The safety of the metering equipment is greatest
when the value of FS is small. Typical FS factors are 5 or 10. It is a maximum value and
only valid at rated burden.
To protect the instruments and meters from being damaged by high currents during
fault conditions, a metering core must be saturated typically between 5 and 20 times
the rated current. Normally energy meters have the lowest withstand capability,
typically 5 to 20 times rated current.
Accuracy limit factor for Protection CT
Require accuracy up to many times rated current, thus use grain orientated silicon steel
with high saturation flux density that makes Protection CT to operate from ankle point to
knee point
CT Selection
11
If you want an indication, the first thing you need to know is what degree of accuracy is
required. For example, if you simply want to know if a motor is lightly or overloaded, a panel
meter with 2 to 3% accuracy will likely suit your needs. In that case the current
transformer needs to be only 0.6 to 1.2% accurate. On the other hand, if you are going
to drive a switchboard type instrument with 1% accuracy then you need a current
transformer with a 0.3 to 0.6 accuracy.
You must keep in mind that the accuracy ratings are based on rated primary current
flowing. As mentioned earlier, the rated accuracies are at stated burdens. You must take
into consideration total burden which includes the burden of the current transformers
secondary winding, the burden of the leads connecting the secondary to the load, and of
course, the burden of the load itself. The current transformer must be able to support the
total burden and to provide the accuracy required at that burden. If you are going to drive a
relay you must know what relay accuracy the relay will require.
57
Points to be remembered
12
Interposing CTs
Interposing CTs are used when the ratio of transformation is very high. It is also
used to correct for phase displacement for differential protection of transformer.
13
The CBCT, also known as a zero sequence CT, is used for earth leakage and earth fault
protection.In the CBCT, the three core cable or three single cores of a three phase
system pass through the inner diameter of the CT.
When the system is fault free, no current flows in the secondary of the CBCT. When
there is an earth fault, the residual current (zero phase sequence current) of the system
flows through the secondary of the CBCT and this operates the relay. In order to design
the CBCT, the inner diameter of the CT, the relay type, the relay setting and the primary
operating current need to be furnished
14
CT Secondary Load
15
CT Accuracy
16
17
The CT secondary load = Sum of the VAs of all the loads (ammeter, watt meter,
transducer etc.) connected in series to the CT secondary circuit + the CT secondary
circuit cable burden.
Accuracy of a CT is another parameter which is also specified with CT class. For example,
if a measuring CT class is 0.5M (or 0.5B10), the accuracy is 99.5% for the CT, and the
maximum permissible CT error is only 0.5%.
CT Magnetization
As in all transformers, errors arise due to a proportion of the primary input current being
used to magnetize the core and not transferred to the secondary winding. The proportion of
the primary current used for this purpose determines the amount of error. Thus, essence of
good design of measuring current transformers is to ensure that the magnetizing current
is low enough to ensure that the error specified for the accuracy class is not
exceeded. This is achieved by selecting suitable core materials and the appropriate crosssectional area of core.
Standard CT burdens are defined in IEEE Std. C57-13-1993
Metering burdens are B0.1, B0.2, B0.5, B0.9, and B1.8 where each number represents the
total impedance at a 0.9 power factor. VA for each burden is 2.5, 5.0, 12.5, 22.5, and 45.
Relay burdens are B1, B2, B4 and B8 where each number represents the total impedance
at a 0.5 power factor
58
BIBLIOGRAPHY
General Requirements for Transformers, Regulators, and Reactors Publ. C57.11 1948;
American Standard Requirements, Terminology, and Test Code for Instrument
Transformers Publ. C57.13-1954; and Guide for Loading and Operation of Instrument
Transformers Publ. C57.33, American Standards Assoc., Inc., 70 East 45th St., New
York 17, N. Y.
Application Guide for Grounding of Instrument Transformer Secondary Circuits and
Cases Publ. 52, American Institute of Electrical Engineers, 33 West 39th St., New York
18,
ASA C57.23, see Reference 1.
A Simple Method for the Determination of Bushing-Current-Transformer
Characteristics by S. D. Moreton, AIEE Trans., 62 (1943), pp. 581-585. Discussions,
pp. 948-952.
A Simple Method for Determination of Ratio Error and Phase Angle in Current
Transformers by E. C. Wentz, AIEE Trans., 60 (1941), pp. 949-954. Discussions, p.
1369.
A Proposed Method for the Determination of Current-Transformer Errors, by G.
Camilli and R. L. Ten Broeck, AIEE Trans., 59 (1940), pp. 547-550. Discussions, pp.
11381140.
Overcurrent Performance of Bushing-Type Current Transformers by C. A. Woods, Jr.,
and S. A. Bottonari, AIEE Trans., 59 (1940), pp. 554-560. Discussions, pp. 1140-1144.
Computation of Accuracy of Current Transformers by A. T. Sinks, AIEE Trans., 59
(1940), pp. 663-668. Discussions, pp. 1252-1253.
ASA C57.13, see Reference 1.
Current Transformers and Relays for High-Speed Differential Protection, with
Particular Reference to Offset Transient Currents by W. K. Sonnemann and E. C. Wentz,
AIEE Trans., 59 (1940), pp. 481-488. Discussions, p. 1144.
Transient Characteristics of Current Transformers during Faults, by C. Concordia,,
C. N. Weygandt,, and H. 3. Shott, AIEE Trans., 61 (1942), pp. 280-285. Discussions,
pp. 469-470
Transient Characteristics of Current Transformers during Faults, Part II, by F. S. Rothe
and C. Concordia, AIEE Trans., 66 (1947), pp. 731-734.
The Effect of Current-Transformer Residual Magnetism on Balanced-Current or
Differential Relays by H.T. Seeley, AIEE Trans., 62 (1943), pp. 164-168. Discussions,
p. 384.
Peak Voltages Induced by Accelerated Flux Reversals in Reactor Cores Operating above
Saturation Density by Theodore Specht and E. C. Wentz, AIEE Trans., 65 (1946),
pp. 254-263.
Overvoltages in Saturable Series Devices, by A. Boyajian and G. Camilli, AIEE Trans.,
70
(1951), pp. 1845-1851. Discussions, pp. 1952-1853.
59
Applicable standards
IEC
IEC 185:1987
IEC 44-6:1992
CTs
CTs
EUROPEAN
BS 7626
BS 7628
CTs
CT+VT
BRITISH
BS 3938:1973
BS 3941:1975
CTs
VTs
AMERICAN
ANSI C51.13.1978
CANADIAN
CSA CAN3-C13-M83
AUSTRALIAN
AS 1675-1986
CTs
60