Testing Procedure:
1. INSULATION RESISTANCE TEST:
1.
2.
Between Secondary:
Measure Insulation resistance value using 500V Megger between
the Secondary terminals (if the CT Secondary is multicore),
The minimum Insulation Resistance value should be:
5.0 Mega Ohms.
3.
Secondary to Earth:
Measure Insulation resistance value using 500V Megger between
the Secondary terminal and Earth.
The minimum Insulation Resistance value should be:
5.0 Mega Ohms.
2. POLARITY TEST:
2.
3.
5.
4. RATIO TEST:
1.
2.
Connect the primary injection kit between the terminals P1 and P2.
3.
Check initially the current injection unit is zero, then inject 20%
current of actual ratio; by using tong tester check the primary
current value and note down the reading.
4.
By using leakage tester check the secondary current value and note
down the reading.
5.
6.
The calculated ratio value should be the actual ratio value of CT.
7.
1.
3. Inject the voltage in order of 10V, 20V, 30V up to knee point voltage.
SECONDARY VOLTAGE
KNEE POINT
Protective CT
Characteristic
KNEE
POIN
T
5. At the time of continuousMeetering
applying voltage,
the knee point voltage will
CT
attain in certain point, that
point
is
called
knee
point voltage,
Characteristic
SECONDARY VOLTAGE
EXCITING CURRENT
10% Increase in
secondary voltage
KNEE
POINT
50% Increase in
exciting current
6. At knee point voltage 10% of increase in voltage, 50% of increase in
Excitation current will develop.
EXCITING CURRENT