DESCRIPTION
PolyGard
DGC5
Enclosure Type B
FEATURES
Continuous monitoring
RS-485 digital bus, serial
communication
Up to (98) remote RS-485 digital
communicating transmitter inputs;
or combination of (48) RS-485
digital & (48) 4-20 mA
analog transmitters
Four (4) digital inputs
Up to (5) built-in or remote
RS-485 relay/AO modules:
- Up to (30) relay outputs,
five-stage control,
fail-safe assignable
- Up to (12) 4-20 mA outputs,
selectable for low, high or
averaging
One (1) 24 VDC supply output
Built-in horn
SPECIFICATIONS
Electric
Power supply
Power consumption
RF/EMI protected
Type of Control
General
Digital inputs/outputs,
serial communications
-standard
-optional, add-ons
- protection
All trademarks and copyrights are the property of their respective owners.
DGC5
SPECIFICATIONS
Type of Control (cont)
- device configuration
Stage level / setpoint
- hysteresis/
switching differential
Digital inputs
- application
Relay outputs
w/status LEDs
- standard
- optional, add-ons
- each stage level (S1-S5)
- sensor fail-safe
Time delay switching
VDC output supply
Analog output
Audible alarm
Alarm acknowledgment
User Interface
Keypad type
Touch buttons
Status LEDs
Digital display
- unit display
BACnet Interface,
optional*
Coupler module
Communication
Sensor values
Connector
Interface
Description
Object types
LON Interface,
optional*
Coupler module(s)
LONWORKS
-device category
-communication
-LONWORKS version
-LONWORKS object
-standard program ID
-standard networks &
configuration variables
Modbus Interface,
optional*
Module
Communication
Interface
Description
Addresses
- 1000 to 1098
- 2000 to 2048
- 3000 to 3098
- 0 to 6
- 8 to 19
DGC5
SPECIFICATIONS
Data Logging,
optional
Activation
Log rate
Capacity
Environmental
Permissible ambient
- working temperature
- storage temperature
- humidity
- working pressure
Physical
Enclosure (panel)
- material
- conformity
- color
- protection
- installation
Cable entry
Wire connection
Wire size
- power supply input
- inputs/outputs
Enclosure type A
- dimensions (H x W x D)
- weight
Enclosure type B
- dimensions (H x W x D)
- weight
Enclosure type C
- dimensions (H x W x D)
- weight
Approvals / Listings
- unit rating
- enclosure (panel)
Warranty
Polycarbonate, impact
resistance EN 50102/IK08,
flammability rating UL 94-5V
UL Type 1, UL508/UL 50
standards
Light gray, smoked gray for cover
NEMA 4X (IP65)
Wall (surface) mounted
10 holes for 1/2 in. conduit,
covered
Terminal blocks,
Push-on connect and screw type
for lead wire
Min. 16 AWG (1.5 mm2)
Max. 14 AWG (2.5 mm2)
Min. 20 AWG (0.5 mm2)
Max. 16 AWG (1.5 mm2)
11.0 x 12.0 x 5.7 in.
(280 x 306 x 145 mm)
7.7 lbs. (3.5 kg)
16.9 x 12.0 x 5.7 in.
(430 x 306 x 145 mm)
10.4 lbs. (4.7 kg)
22.8 x 12.0 x 5.7 in.
(580 x 306 x 145 mm)
13.9 lbs. (6.2 kg)
DGC5
ORDERING INFORMATION
DGC5 - A 0 2 - 1 0 00 US
C5 Upwards Communication Gateways
00
B1
B2
B3
B4
L1
L2
L3
L4
M1
None
BACnet; for 98 DT5 Transmitters; 0250 ppm CO (C5-BAC-98)
BACnet; for 48 DT5-AT/LC Transmitters; 0250 ppm CO (C5-BAC-48-48)
BACnet; for 98 DT5 Transmitters; 0100% (C5-BAC-98-1)
BACnet; for 48 DT5-AT/LC Transmitters; 0100% (C5-BAC-48-48-1)
LON; for 56 DT5 Transmitters (C5-LON-DA)
LON; for 98 DT5 Transmitters (2x = C5-LON-DA+DB)
LON; for 28 DT5-AT Transmitters (C5-LON-NLA)
LON; for 48 DT5-AT Transmitters (2x = C5-LON-NLA+NLB)
Modbus; for DT5 or DT5-AT Transmitters (Integrated at Controller module)
None
(5) Relays / (2) 4-20 mA (1x EP5-05)
(10) Relays / (4) 4-20 mA (2x EP5-05 )
1 Port/Trunk Module
2 Port/Trunk Modules
3 Port/Trunk Modules
4 Port/Trunk Modules
5 Port/Trunk Modules
6 Port/Trunk Modules
7 Port/Trunk Modules
8 Port/Trunk Modules
(1x CON5-A)
(2x CON5-A)
(3x CON5-A)
(4x CON5-A)
(5x CON5-A)
(6x CON5-A)
(7x CON5-A)
(8x CON5-A)
98 DT Transmitters
(GC5-98)
48 DT-AT Transmitters (GC5-48-48)
98 DT Transmitters
(w/ data logging)
48 DT-AT Transmitters (w/ data logging)
Enclosure Options
0
1
2
3
None
Keylock with 2 Keys (ENCL-A)
Keylock with 2 Keys (ENCL-B)
Keylock with 2 Keys (ENCL-C)
Enclosure Type
A
B
C
Encl. A
Encl. B
0
1
2
10
8
4
Encl. C
2
3
4
10
7
4
Note:
Outputs:
DGC5
Enclosure Types A, B and C
Expansion Configuration for DGC5-A, Enclosure A:
* Up to max (4) CON5-A RS-485 Serial Port/Trunk
Connector Modules
Expansion Configuration for DGC5-B, Enclosure B:
* Up to max (4), possibly (8) CON5-A RS-485 Serial
Port/Trunk Connector Modules
* (1), possibly (2) EP5-05 Relay/AO Expansion Modules
* (1), possibly (2) C5-... BACnet or LON Couplers
Example of max space available for controller,
modules and couplers:
(1) GC5-98 + (5) CON5-A + (1) EP5-05 + (1) C5-...
Expansion Configuration for DGC5-C, Enclosure C:
* Up to max (4), possibly (8) CON5-A RS-485 Serial
Port/Trunk Connector Modules
* (2), possibly (4) EP5-05 Relay/AO Expansion Modules
* (1), possibly (2) C5-... BACnet or LON Couplers
Example of max space available for controller,
modules and couplers:
(1) GC5-98 + (4) CON5-A + (2) EP5-05 + (2) C5-...
Enclosure Type A
Enclosure Type B,
See page 1
Enclosure Type C
C5-LON-NLB LON Coupler: > (20) SNVTs for DT5 transmitters (29.1-48.1)
> (20) SNVTs for AT transmitters (29.2-48.2)
> (6) SNVTs for (30) digital relay status bits
> (12) SNVTs for (12) analog values with
minimum/average/maximum function
Note to ordering number L2 and L4 LON Coupler Combinations:
C5-LON-DA and C5-LON-DB combination (L2) with GC5-98 controller; and
C5-LON-NLA and C5-LON-NLB combination (L4) with GC5-48-48 controller
provides total added SNVTs for sensor/transmitters points; but provides only
(6) SNVTs for six REL5-5R-2A relay/AO modules (total of 30 relays), and (12)
SNVTs for twelve 4-20 mA output signals.
DGC5
PolyGard DGC5 Multi-Point RS-485 Digital Gas Detection and Control System
Upwards Communication, BACnet, LON or Modbus
DGC5
C5 Com.
Coupler(optional)
EP5-05
(optional)
GC5-48-48
CON5-A
DT5..
AT..
DT5..
AT..
Digital Service
via Laptop
DT5..
REL5-5R-2A-120
Remote Relay/AO Unit
- (5) SPDT Relay Outputs, 8 A
- (2) 4-20 mA Outputs
- Transformer
120/208/240, 24 VAC
AT..
AT..
DT5..
DT5..
AT..
EP5-05
(optional)
CON5-B
DGC5
USER INTERFACE & CONTROLLER
Keypad User Interface
System Operation
Alarm 1
Alarm 2 - n
INTEC
Power
13.06.13 11:45am
Fault
Main Menu
System Errors
Relay Status
Sensor Readings
SP Setup
Data Logger
System Setup
-
-
-
-
-
DGC5
FIELD WIRING CONFIGURATION
Green/Ye
Gray
Gray
Blue
Green/Ye
G
X
H
N
G
120 VAC
Input Power
(see ill. 2)
(see ill. 1)
1
1 2 3 4 5 6
X1
7 8 9 10 11 12 13 14 15
X2
Alarm 1
Alarm 2- n
INTEC Controls
10.21.13 10:28am
Power
Fault
DIN Rail
GC5-...
X10
X11
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Optional:
Modbus Interface
(see ill. 8)
Digital Analog
Inputs Outputs
(see ill. 6)
24 VDC
Output
(see ill. 4)
1 2 3 4 5 6 7 8
X2
X2
(see ill. 5)
C5 Comm.
Coupler
RS-485 Communication,
factory wired
RS-485
1
1 2 3 4 5 6 7 8
Optional:
BACnet
X1
X1
CON5-A
1 2 3 4
C5 Communication Coupler
Optional: LON
DIN Rail
X1
X10
X11
1 2 3 4
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
(see ill. 3)
Communication Output
24 VDC
Output
Terminal 1
block X1 2
Circuit breaker
1F1
L
N
G
VV+
Power
Unit
Top
Bottom
Horn
Gray
Blue
Green/Yellow
AC hot
AC neutral
Earth ground
Terminal block
ill. 1
DGC5
FIELD WIRING CONFIGURATION (cont...)
Binary - Relay Outputs R01 to R05
()
(+)
***
#3
#2
#1
D2
NC
9 10 11 12 13 14 15
R01
R02
R03
R04
Normal condition (factory default)
D1
COM
COM
NO
NC
COM
NO
NC
COM
NO
NO
COM
NC
NC
1H1
NO
D3
X2
R05
D4
D5
ill. 2
Terminal block X1
9 10 11 12
X11
ill. 4
ill. 5
ill. 3
9 10 11 12
(A)
9 10 11 12
X11 C5 coupler
Upwards LON
communication to BAS
(B)
9 10 11 12
0 VDC
MOD_A
MOD_B
X2
X11
5 6 7 8
1 2 3 4
C5 Communication Coupler,
BACnet, optional
ill. 7b
4-20 mA signal
The current signal is sourced
by the DGC5 system
to remote control or BAS,
selectable current or
averaging, 500 max. load
ill. 7a
X11
4-20 mA (AO02)
Com
4-20 mA (AO01)
ill. 8
RJ45
Upwards BACnet
communication
to BAS
DGC5
FIELD WIRING CONFIGURATION (cont...)
(A) (B)
(+)
()
24 VDC
(B)
(A)
RS-485
X2
CON trunk/bus
protector module
(+) ()
B 7
A 6
X4
X4
Notes:
Do not connect power to A and B,
this may damage the transmitters and
possibly the trunk/bus protector CON
module linked on the daisy-chain trunk.
Daisy-chain between transmitters and
CON module A to A, B to B. Do not
cross A to B, this creates malfunction of
communication.
(A) (B)
X4
X4
(+) ()
(A) (B)
24 VDC
RS-485
ill. 6