HYDRONIC

292 - 604

WSAN-2

AIR TO WATER HEAT PUMP FOR OUTDOOR


INSTALLATION

Cooling

Heating

[kW]

[kW]

292

77.8

86.7

323

90.9

100.9

404

104.4

115.4

464

119.2

129.8

524

132.0

148.0

564

141.1

155.8

604

148.1

166.4

The WSAN series heat pumps are designed for outdoor installation, to produce chilled water for air-conditioning and hot water for heating.
The units are designed for optimum efficiency and feature compact dimensions. Hermetic scroll compressors are used. The units feature
an innovative controller with microprocessor for the control and optimisation of all the functions, increasing energy efficiency at partial
loads. A hot-galvanized and painted plate structure with pre-painted aluminium external panelling ensures maximum weatherability. The
uniform distribution of the weight of the unit is guaranteed by the base structure, made up of galvanized and painted plate section bars,
featuring holes to simplify the lifting and earthing of the unit. All the units are carefully assembled and tested in the factory and are ready to
start operation as soon as the electrical and water connections have been completed (the unit is fitted as standard with a hydronic
assembly), significantly reducing installation costs.

Clivet is partecipating in the EUROVENT Certification Programme.


Products are listed in the EUROVENT Directory of Certified Products
and in the site www.eurovent-certification.com.
CERTIFIED QUALITY SYSTEM ISO 9001 : 2000

BT02F014GB-00

Size

REPLACE: DB1001IESN2-3

R-407C

HYDRONIC
292 - 604

STANDARD UNIT SPECIFICATIONS


COMPRESSOR
Scroll compressor complete with: overload thermal protection, high refrigerant
discharge temperature, rubber antivibration mounts, oil charge, acoustic and
weather proof cabinet.
STRUCTURE
hot-galvanized and painted plate structure with pre-painted aluminium external
panelling to ensure maximum weatherability. The uniform distribution of the
weight of the unit is guaranteed by the base structure, made up of galvanized
and painted plate section bars, and featuring holes to simplify the lifting and
earthing of the unit.
AIR EXCHANGER
heat exchange coil with aluminium fins and copper tubes in staggered rows.
The coils are complete with integral subcooling circuit which assures the correct power supply of the expansion valve. Available in different options as per
optional list.
WATER EXCHANGER
the differential pressure switch on the water side is supplied as standard.
an electric heater protects the exchanger against the danger of frost.
direct expansion heat exchanger, braze-welded AISI 316 stainless steel plates
with large exchange surface and complete with external heat/anti-condensate
insulation. Two independent water / freon circuits, with cross-flow to optimise
heat exchange.
FAN
helical fans with die-cast aluminium blades, directly coupled to a three-phase
electric motor with external rotor, with built-in thermal overload protection, IP
54 index of protection. Housed inside a specially-shaped aerodynamic nosepieces to increase efficiency and minimise noise levels; fitted with safety grills.
REFRIGERANT CIRCUIT
the units are made with two independent refrigerant circuits, each with:
high pressure safety valve
solenoid valves
thermostatic expansion valves with equalizer
high pressure switch
low pressure switch
high and low pressure gauges
low pressure safety valve
replaceable antacid solid cartridge dehydrator filter
liquid line shut-off valve
compressor discharge shut-off valve
compressor suction shut-off valve
liquid receiver
liquid flow and moisture indicator
non-return valve
4-way reverse cycle valve
inlet liquid separator

isolating transformer for auxiliary circuit power supply


compressor control contactor
fan control contactors
phase-cutting fan speed control
Electrical panel made from hot-galvanized and painted plate.
the Power Section includes:
Compressor timer / operation signal LED
UP and DOWN buttons to increase and decrease the values
ON/OFF and alarm reset buttons
display of the set values, the error codes and the parameter index
interface terminal with 4 row x 20 character LCD display
H2o antifreeze and high refrigerant gas pressure pre-alarm function that reduces cooling capacity to avoid unit shut-down
possibility of communication with ZONE MASTER system (optional)
input for demand limit (power input limited according to time bands or by external signal)
emergency stop button
relay for remote cumulative fault signal
automatic compressor start rotation control
remote ON/OFF control
serial port with MODBUS (RS 485) output for remote communication
compressor operating hour display
self-diagnosis system with immediate display of the error code
compressor overload protection and timer
antifreeze protection
proportional + integral water temperature control
the control section includes:
HYDRAULIC CIRCUIT
hydronic system with vessel expansion, steel mesh mechanical filter and water
side shut-off valve.
Closed couple pumps with high efficiency impellers. Maximum operating pressure 1000kPa. Temperature range from -10C to 60C. Maximum glycol concentration 35%.
ACCESSORIES
copper / tinned copper condenser coils
copper / copper condenser coils
copper / aluminium condenser coils with acrylic lining
copper / aluminium condenser coils with Fin Guard (Silver) treatment
spring antivibration mounts
low outside temperature kit with variable speed fans and INVERTER.
set point compensation with 4-20 mA signal
finned coil protection grill.
remote microprocessor control unit
unit without hydronic assembly
pump for useful heads other than standard
Flow Switch
phase monitor
compressor overload circuit breakers
power factor correction capacitors (cosfi > 0.9)

ELECTRICAL PANEL
fan overload circuit breakers
compressor fuses and thermal overload relay
main door lock isolator switch

Configuration Code

BT02F014GB-00

WSAN-2

323

ST

(1) VERSION

(2) ACOUSTIC CONFIGURATION

Standard (S)
Standard

Low noise (LN)


this configuration is obtained by inserting the compressors in a soundproofed
chamber and reducing the speed of the fans, with a larger condensing section.
Standard (ST)
see description on page 2

(1) ENERGY RECOVERY


Partial Recovery (D)
made using tube bundle exchangers to recover the desuperheating heat, up to
25% of the total heat of the unit.
Total Recovery ( R)
made using tube bundle exchangers to recover 100% of the condensing heat
for production of hot water.

(1) LOW TEMPERATURE


Low water temperature (B)
this version allows unit operation in the range of water and glycol mix temperatures between +5C and -8C.
Two versions are available
- Unit for low temperatures only
- Unit with double working set point
(For special conditions contact our sales office)
2

(3) ENERGY EFFICIENCY


Temperate Climate (T)
standard

(4) HEAT EXCHANGERS APPROVALS


U = UDT (Poland)
C = CLIVET (Internal testing)
CE = PED (European testing)

HYDRONIC
292 - 604

SOUND LEVELS
Acoustic configuration: Standard (ST)
Sound Power Level (dB)
Size

Octave band (Hz)

Sound
pressure
level

Sound
power level

500 1000 2000 4000 8000

63

125

250

dB(A)

dB(A)

292

88

86

82

75

68

90

91

91

72

91

323

92

94

93

90

88

84

76

70

74

93

404

93

95

94

91

89

85

77

71

75

93

464

95

96

95

93

90

86

78

73

77

95

524

95

96

95

93

91

87

79

73

77

95

564

95

96

95

93

91

87

80

73

77

95

604

95

96

95

93

90

87

80

73

77

95

Sound
pressure
level

Sound
power level

the sound levels refer to the unit at full load, in the rated test conditions.
The sound pressure level refers to a distance of 1m from the external surface of the
units operating in an open field.
data refers to the following conditions :
evaporator water = 12/7C
room temperature = 35C

Acoustic configuration: Low noise (LN)


Sound Power Level (dB)
Size

Octave band (Hz)


63

125

250

500 1000 2000 4000 8000

dB(A)

dB(A)

292

84

83

82

79

76

72

67

57

63

81

323

86

86

84

80

78

73

67

60

65

83

404

88

88

86

82

80

75

67

62

66

85

464

89

89

87

84

81

75

69

62

67

86

524

89

89

87

85

82

75

70

62

68

86

564

89

89

87

84

81

76

71

62

68

86

604

88

88

87

83

81

77

72

62

68

86

BT02F014GB-00

EVAPORATOR PRESSURE DROP

HYDRONIC
292 - 604

PUMP PERFORMANCE
PUMP PERFORMANCE(1)
Q = WATER FLOW
DP = PRESSURE DROP

292

dP
340 kPa

P OM P A 6

320 kPa
300 kPa
280 kPa
260 kPa

P OM P A 5

240 kPa
220 kPa
200 kPa
180 kPa

P OM P A 3

160 kPa

P OM P A 2

140 kPa
120 kPa

P O M P A 1 ( st d)

100 kPa
80 kPa
3.0l/s

3.5l/s

4.0l/s

4.5l/s

5.0l/s

5.5l/s

6.0l/s

PUMP PERFORMANCE(2)
Q = WATER FLOW
DP = PRESSURE DROP

323 - 404

dP
340 kPa
320 kPa

P OM P A 6

300 kPa
280 kPa
260 kPa
P OM P A 5

240 kPa
220 kPa
200 kPa
180 kPa

P OM P A 3

160 kPa

P OM P A 2

140 kPa
120 kPa
100 kPa

P O M P A 1 ( st d)

80 kPa
3.5l/s

4.0l/s

4.5l/s

5.0l/s

5.5l/s

6.0l/s

6.5l/s

7.0l/s

7.5l/s

Q
PUMP PERFORMANCE(3)

340
320
300
280
260
240
220
200
180
160
140
120
100
80

Q = WATER FLOW
DP = PRESSURE DROP

464 - 524

dP
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
kPa
4.5l/s

P OM P A 6

P OM P A 5

P OM P A 4

P OM P A 3
P O M P A 2 ( st d)

5.0l/s

5.5l/s

6.0l/s

6.5l/s

Q 7.0l/s

7.5l/s

8.0l/s

8.5l/s

9.0l/s

BT02F014GB-00

PUMP PERFORMANCE(4)

140 kPa
120 kPa
100 kPa
80 kPa
5.5l/s

Q = WATER FLOW
DP = PRESSURE DROP

564 - 604

dP
340 kPa
320 kPa
300 kPa
280 kPa
260 kPa
240 kPa
220 kPa
200 kPa
180 kPa
160 kPa

P OM P A 6

P OM P A 5

P OM P A 4

P O M P A 3 ( st d)

6.0l/s

6.5l/s

7.0l/s

7.5l/s

Q 8.0l/s

8.5l/s

9.0l/s

9.5l/s

10.0l/s

HYDRONIC
292 - 604

CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS


% ethylene glycol by weight
Freezing temperature
Safety temperature
Cooling Capacity Factor
Compressor input Factor
Evaporator Glycol solution flow Factor
Pressure drop Factor

C
C
Nr
Nr
Nr
Nr

5%
-2.0
3.0
0.995
0.997
1.003
1.029

10%
-3.9
1.0
0.990
0.993
1.010
1.060

15%
-6.5
-1.0
0.985
0.990
1.020
1.090

20%
-8.9
-4.0
0.981
0.988
1.033
1.118

25%
-11.8
-6.0
0.977
0.986
1.050
1.149

30%
-15.6
-10.0
0.974
0.984
1.072
1.182

35%
-19.0
-14.0
0.971
0.982
1.095
1.211

40%
-23.4
-19.0
0.968
0.981
1.124
1.243

The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.

FOULING CORRECTION FACTOR


m C/W
0.44 x 10^(-4)
0.88 x 10^(-4)
1.76 x 10^(-4)

F1
1.00
0.97
0.94

FK1
1.00
0.99
0.98

F2
1.00
0.97
0.92

FK2
1.00
1.08
1.05

F1 = Cooling capacity correction factors


FK1 = Compressor power input correction factor
F2 = Cooling capacity correction factors
FK2 = Compressors input power correction factors

EXCHANGER OPERATING LIMITS

CLIVET (C)
UDT (PL)
PED (CE)

DPr (S - B)
kPa
3450
3450
3450
3450

DPw
kPa
2500
2500

EVAPORATOR
Dteo (S - B)
C
6
-8
6
-8
6
-8

Dtei
C
22
22
22

DT
C
5
5
5

DPr
kPa
3450
3450
3450

CONDENSER
DPw
Dtci
kPa
C
2500
15
2500
15
2500
15

Dtco
C
53
53

BT02F014GB-00

DPr = Maximum operating pressure on refrigerant side


DPw = Maximum operating pressure on water side
DTeo = Minimum water temperature at evaporator outlet
DTei = Maximum water temperature at evaporator inlet
DT = difference between inlet / outlet water temperature = 5C
DTci = Minimum water temperature at condenser inlet
DTco = Maximum water temperature at condenser outlet

HYDRONIC
292 - 604
Acoustic configuration: Standard (ST)

GENERAL TECHNICAL SPECIFICATIONS


Size

292

323

404

464

524

564

604

COOLING
Cooling capacity
Compressor power input
Total power input
EER
HEATING

kW
kW
kW
Nr

77.8
25
29
2.69

90.9
29.1
33
2.75

104.4
31.6
37.5
2.78

119.2
37.3
43
2.77

132
42.9
48.7
2.71

141.1
47.7
53.4
2.64

148.1
52.3
58.1
2.55

Heat output
Compressor power input
Total power input
COP
COMPRESSOR

kW
kW
kW
Nr

86.7
27.1
30.9
3.2

100.9
31.4
35.2
3.21

115.4
36.3
42.1
3.18

129.8
41.1
46.2
3.16

148
46.8
51.9
3.16

155.8
50.1
54.7
3.11

166.4
54.3
59
3.06

Type of compressors
No. of Compressors
Std Capacity control steps
Oil charge (C1)
Oil charge (C2)
Oil charge (C3)
Oil charge (C4)
Refrigerant charge (C1)
Refrigerant charge (C2)
Refrigerant charge (C3)
Refrigerant charge (C4)
Refrigerant circuits
EVAPORATOR

3
Nr
Nr
l
l
l
l
kg
kg
kg
kg
Nr

scroll
2
2
6.6
6.6
0
0
24
24
0
0
2

scroll
3
3
6.6
3.3
3.3
0
24
13.5
13.5
0
2

scroll
4
4
3.3
3.3
3.3
3.3
13.5
13.5
13.5
13.5
2

scroll
4
4
3.3
3.3
3.3
3.3
13.5
13.5
16
16
2

scroll
4
4
3.3
3.3
3.3
3.3
16
16
16
16
2

scroll
4
4
3.3
3.3
6.6
6.6
16
16
17.5
17.5
2

scroll
4
4
6.6
6.6
6.6
6.6
17.5
17.5
17.5
17.5
2

Type of evaporator
Water flow-rate
Pressure drop
Useful pump discharge head
Water content
EXTERNAL SECTION FANS

4
l/s
kPa
kPa
l

PHE
3.7
27.4
130
5.9

PHE
4.3
23.5
115
7.8

PHE
5
29
100
7.8

PHE
5.7
27
120
9.4

PHE
6.3
33
105
9.4

PHE
6.7
29
120
11

PHE
7.1
33
110
11

Type of fans
Number of fans
Fan RPM
Standard air flow
Installed unit power
CONNECTIONS

5
Nr
rpm
l/s
kW

AX
2
870
12200
2

AX
2
870
11600
2

AX
3
870
17700
2

AX
3
870
17500
2

AX
3
870
17200
2

AX
3
870
17200
2

AX
3
870
17200
2

mm

2" 1/2

2" 1/2

2" 1/2

2" 1/2

2" 1/2

2" 1/2

2" 1/2

kg
kg

1432
1447

1531
1548

1686
1703

1740
1759

1770
1789

1822
1842

1865
1885

Length
Depth
Height
EXPANSION VESSEL

mm
mm
mm

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

Expansion vessel capacity


Maximum water side pressure
Nitrogen buffer pressure
STORAGE

l
kPa
kPa

12
800
150

12
800
150

16
800
150

16
800
150

18
800
150

18
800
150

18
800
150

200

200

200

200

200

200

200

kPa
kPa

550
600

550
600

550
600

550
600

550
600

550
600

550
600

Water fittings
STANDARD UNIT WEIGHTS
Shipping weight
Operating weight
DIMENSIONS

BT02F014GB-00

Storage capacity
HYDRAULIC CIRCUIT
Max water side pressure
Safety valve calibration
(1) data refers to the following conditions :
evaporator water = 12/7C
room temperature = 35C
(2) data refers to the following conditions :
condenser water = 40/45C
room temperature = 7C (RH = 85%)
(3) SCROLL = scroll compressor
(4) PHE = plates
(5) AX = axial-flow fan

HYDRONIC
292 - 604
Acoustic configuration: Standard (ST)

ELECTRICAL DATA
Size

292

323

404

464

524

564

604

29.2
29.2
4
2
3.1
71.7

19.5
29.2
19.5
4
2
3.1
81.5

19.5
19.5
19.5
19.5
4
3
3.1
95.3

25.3
19.5
25.3
19.5
4
3
3.8
107.6

25.3
25.3
25.3
25.3
4
3
3.8
119.2

29.2
25.3
29.2
25.3
4
3
5
128.1

29.2
29.2
29.2
29.2
4
3
5
135.9

Compressor 1 (400/3/50)
A
Compressor 2 (400/3/50)
A
Compressor 3 (400/3/50)
A
A
Compressor 4 (400/3/50)
External Fan (400/3/50)
A
A
Pump (400/3/50 )
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

175
175
14
14.6

130
175
130
14
14.6

130
130
130
130
14
14.6

175
130
175
130
14
19

175
175
175
175
14
19

175
175
175
175
14
24.8

175
175
175
175
14
24.8

Compressor 1 (400/3/50)
Compressor 2 (400/3/50)
Compressor 3 (400/3/50)
Compressor 4 (400/3/50)
External Fan (400/3/50)
Pump (400/3/50 )
Total (400/3/50 )
M.I.C. MAXIMUM INRUSH CURRENT

kW
kW
kW
kW
kW
kW
kW

17.3
17.3
2
1.1
40.4

11.3
17.3
11.3
2
1.1
45.7

11.3
11.3
11.3
11.3
2
1.1
53

14.5
11.3
14.5
11.3
2
1.5
59.8

14.5
14.5
14.5
14.5
2
1.5
66.2

17.3
14.5
17.3
14.5
2
1.9
72.1

17.3
17.3
17.3
17.3
2
1.9
77.7

217.5

207.8

205.8

257.3

268.9

273.9

281.7

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

292

323

404

464

524

564

604

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS


Compressor 1 (400/3/50)
Compressor 2 (400/3/50)
Compressor 3 (400/3/50)
Compressor 4 (400/3/50)
External Fan (400/3/50)
Number of fans
Pump (400/3/50 )
Total (400/3/50 )
L.R.A. LOCKED ROTOR AMPERES

A
A
A
A
A
Nr
A
A

Value (400/3/50 )
POWER SUPPLY
power supply
voltage unbalance: max 2 %
power supply: 400/3/50 Hz +/-10%

Acoustic configuration: Standard (ST)

OPERATING LIMITS (Cooling)


Size
CONDENSER
Max air intake temperature
Max air intake temperature
Min. air intake temperature
Min. air intake temperature

1
2
3
4

C
C
C
C

46
52
-10
12

45
51
-10
12

47
53
-10
12

47
53
-10
12

47
53
-10
12

44
50
-10
12

44
50
-10
12

5
5

C
C

18
-5.5

18
-5.5

18
-5.5

18
-5.5

18
-5.5

18
-5.5

18
-5.5

OPERATING LIMITS (Heating)


Max air temperature inlet (WB)
Min air inlet temperature (W.B.)

Note: For ambient lower than 5C the low ambient temperature control with inverter is
recommended
(1) unit at full load: evaporator water 12/7C
(2) capacity-controlled unit (automatic capacity control)
(3) with electronic low ambient temperature control, unit at partial load and motionless
external air
(4) with electronic low ambient temperature control, unit at partial load with air speed 1 m/
sec
(5) unit at full load
condenser water = 40/45C

BT02F014GB-00

EVAPORATOR

HYDRONIC
292 - 604
ACOUSTIC CONFIGURATION: STANDARD (ST)

COOLING PERFORMANCE
CONDENSER AIR INTAKE TEMPERATURE (C)
Size

292

323

404

464

524

BT02F014GB-00

564

604

To
(C)

25

30

35

40

43

46

kWe

kWf

kWe

kWf

kWe

kWf

kWe

kWf

kWe

kWf

kWe

kWf

kWe

83.7

20.2

79.6

22.4

77.9

23.3

75.2

24.8

70.6

27.4

67.6

29.0

64.6

30.7

86.5

20.4

82.3

22.6

80.6

23.5

77.8

25.0

73.0

27.6

70.0

29.2

66.9

30.9

89.3

20.5

85.0

22.7

83.2

23.7

80.4

25.1

75.5

27.8

72.4

29.4

69.2

31.1

92.1

20.7

87.6

22.9

85.8

23.9

82.9

25.3

77.8

27.9

74.7

29.6

71.4

31.3

10

94.9

20.9

90.3

23.1

88.3

24.0

85.4

25.5

80.2

28.1

76.9

29.8

73.5

31.5

11

97.6

21.0

92.8

23.3

90.9

24.2

87.8

25.7

82.5

28.3

79.1

30.0

75.6

31.7

97.7

23.4

92.8

26.0

90.8

27.1

87.6

28.9

82.1

31.9

78.6

33.9

101.3

23.6

96.3

26.2

94.2

27.3

90.9

29.1

85.2

32.1

81.6

34.1

104.7

23.8

99.5

26.4

97.4

27.5

94.0

29.3

88.2

32.3

84.5

34.3

108.0

24.0

102.7

26.6

100.5

27.7

97.0

29.5

91.0

32.5

87.3

34.5

10

111.1

24.2

105.7

26.8

103.4

27.9

99.8

29.6

93.7

32.7

89.8

34.7

11

114.1

24.4

108.5

27.0

106.1

28.1

102.5

29.8

96.2

32.9

92.2

34.9

111.8

25.5

106.5

28.3

104.3

29.5

100.9

31.5

95.0

35.0

91.3

37.3

87.5

39.8

115.6

25.6

110.2

28.4

107.9

29.7

104.4

31.6

98.2

35.2

94.3

37.4

90.2

39.9

119.4

25.8

113.9

28.6

111.5

29.8

107.9

31.8

101.4

35.3

97.3

37.6

93.1

40.0

123.2

25.9

117.5

28.8

115.1

30.0

111.3

31.9

104.7

35.4

100.5

37.7

96.2

40.0

10

127.0

26.0

121.0

28.9

118.6

30.2

114.7

32.1

108.0

35.5

103.8

37.8

99.4

40.1

11

130.7

26.2

124.6

29.1

122.0

30.3

118.1

32.2

111.4

35.7

107.2

37.9

127.8

30.2

121.7

33.4

119.1

34.8

115.1

37.0

108.1

41.0

103.7

43.5

99.2

46.2

132.2

30.4

125.9

33.7

123.3

35.1

119.2

37.3

112.0

41.2

107.5

43.7

102.8

46.4

136.5

30.6

130.1

33.9

127.4

35.3

123.2

37.5

115.8

41.4

111.2

43.9

106.4

46.6

140.8

30.9

134.2

34.1

131.4

35.5

127.1

37.7

119.5

41.7

114.8

44.2

109.9

46.8

10

145.1

31.1

138.2

34.4

135.4

35.8

130.9

38.0

123.1

41.9

118.3

44.4

113.2

47.0

11

149.3

31.3

142.2

34.6

139.2

36.0

134.7

38.2

126.7

42.1

121.7

44.6

141.5

34.8

134.8

38.6

132.0

40.1

127.6

42.6

119.9

46.9

115.1

49.6

110.1

52.4

146.3

35.1

139.4

38.8

136.5

40.4

132.0

42.9

124.1

47.2

119.2

50.0

114.1

52.9

151.0

35.4

143.9

39.1

140.9

40.7

136.3

43.2

128.3

47.5

123.2

50.3

118.0

53.2

155.7

35.7

148.4

39.4

145.4

41.0

140.6

43.5

132.3

47.8

127.1

50.6

121.7

53.5

10

160.4

36.1

152.9

39.8

149.8

41.3

144.9

43.8

136.3

48.1

131.0

50.9

125.4

53.7

11

165.1

36.4

157.3

40.1

154.1

41.7

149.1

44.1

140.3

48.4

134.7

51.1

152.1

38.7

144.5

42.8

141.3

44.5

136.5

47.2

128.0

52.0

122.8

55.1

157.2

39.1

149.4

43.2

146.1

44.9

141.1

47.7

132.4

52.5

127.0

55.5

162.2

39.4

154.2

43.6

150.9

45.4

145.7

48.1

136.8

52.9

131.2

55.9

167.2

39.8

159.0

44.0

155.6

45.7

150.2

48.5

141.0

53.3

135.2

56.3

10

172.2

40.2

163.7

44.3

160.2

46.1

154.7

48.8

145.1

53.7

139.2

56.7

11

177.1

40.5

168.4

44.7

164.7

46.4

159.1

49.2

149.2

54.0

143.0

57.1

160.1

42.4

151.8

46.9

148.4

48.8

143.2

51.8

134.3

57.0

128.7

60.4

165.4

42.8

157.0

47.4

153.5

49.3

148.1

52.3

138.8

57.6

132.9

60.9

170.6

43.2

162.0

47.8

158.4

49.7

152.9

52.8

143.2

58.1

137.1

61.4

175.8

43.6

167.0

48.2

163.3

50.2

157.6

53.2

147.6

58.5

141.3

61.9

10

181.0

44.0

171.9

48.7

168.0

50.6

162.1

53.6

151.9

59.0

145.5

62.3

11

186.1

44.4

176.6

49.1

172.7

51.0

166.6

54.0

156.1

59.4

149.6

62.7

kWf = Cooling capacity in kW


kWe = Compressor power input in kW
To = Evaporator water outlet temperature in C
DT = difference between inlet / outlet water temperature = 5C

32

kWf

HYDRONIC
292 - 604
ACOUSTIC CONFIGURATION: STANDARD (ST)

HEATING PERFORMANCE

292

323

404

464

524

564

604

Ta
(C)
DB/WB

CONDENSER WATER INLET / OUTLET TEMPERATURE (C)


30 / 35

35 / 40

40 / 45

45 / 50

kWt

kWe

kWt

kWe

kWt

kWe

-5 / -5.4

65.4

20.9

65.5

23.0

64.4

26.0

0 / -0.6

74.2

21.3

73.9

23.5

72.6

26.4

5 / 3.9

84.0

21.6

83.2

23.9

81.7

48 / 53

kWt

kWe

kWt

kWe

26.9

79.7

30.5

78.1

33.1

7 / 6.1

89.4

21.8

88.3

24.1

86.7

27.1

84.8

30.8

83.4

33.3

10 / 8.2

94.9

22.0

93.4

24.3

91.7

27.3

90.0

31.0

88.8

33.5

103.1

31.5

102.6

34.0

15 / 13

108.8

22.5

106.3

24.9

104.4

27.8

-5 / -5.4

74.9

24.1

74.1

26.9

72.1

30.2

0 / -0.6

86.4

24.5

85.0

27.4

83.7

30.7

82.6

34.5

5 / 3.9

98.3

24.9

96.5

27.8

95.1

31.2

94.2

34.9

7 / 6.1

104.5

25.1

102.7

28.0

100.9

31.4

99.3

35.1

98.5

37.5

10 / 8.2

110.6

25.2

108.8

28.2

106.6

31.5

104.0

35.2

102.3

37.7

15 / 13

125.4

25.6

124.0

28.6

120.0

31.9

113.6

35.5

108.5

37.8

-5 / -5.4

86.1

27.9

85.6

31.3

83.9

35.2

0 / -0.6

98.2

28.3

97.3

31.8

96.0

35.7

94.4

40.1

5 / 3.9

111.7

28.8

110.2

32.2

108.7

36.1

107.2

40.5

106.3

43.3

7 / 6.1

119.1

28.9

117.3

32.4

115.4

36.3

113.5

40.7

112.4

43.5

10 / 8.2

126.7

29.1

124.4

32.6

122.0

36.5

119.5

40.8

117.9

43.6

15 / 13

145.8

29.5

142.5

33.0

138.2

36.9

133.1

41.1

129.7

43.7

-5 / -5.4

98.8

31.8

98.0

35.4

97.5

39.6

0 / -0.6

112.0

32.2

110.2

36.0

108.9

40.2

108.2

45.1

5 / 3.9

126.8

32.7

124.2

36.5

122.3

40.8

121.0

45.7

120.5

48.8

7 / 6.1

134.9

33.0

132.1

36.8

129.8

41.1

128.1

45.9

127.3

49.1

10 / 8.2

143.1

33.2

140.2

37.0

137.6

41.3

135.4

46.1

134.4

49.3

154.2

46.6

15 / 13

163.9

33.8

160.8

37.7

157.5

41.9

-5 / -5.4

110.7

36.1

110.6

40.1

110.0

44.7

0 / -0.6

126.2

36.7

125.3

40.9

124.4

45.6

123.6

50.8

5 / 3.9

143.0

37.4

141.4

41.6

139.8

46.4

138.4

51.7

137.6

55.2

145.0

55.5

7 / 6.1

152.1

37.7

150.0

42.0

148.0

46.8

146.1

52.1

10 / 8.2

161.2

38.0

158.7

42.3

156.3

47.1

153.8

52.4

172.4

53.0

15 / 13

183.8

38.8

180.4

43.2

176.6

47.9

-5 / -5.4

117.5

38.7

117.7

43.0

116.6

48.0

0 / -0.6

134.4

39.4

133.0

43.8

130.8

48.9

127.7

54.5

5 / 3.9

152.3

40.1

149.6

44.6

146.9

49.7

144.3

55.3

142.8

59.0

7 / 6.1

161.8

40.4

158.4

45.0

155.8

50.1

153.8

55.7

153.0

59.4

10 / 8.2

171.3

40.7

167.3

45.3

164.8

50.5

163.7

56.2

163.7

59.9

15 / 13

194.5

41.5

189.4

46.2

187.7

51.4

189.3

57.1

-5 / -5.4

123.6

41.7

123.0

46.5

122.7

52.1

0 / -0.6

142.0

42.6

141.1

47.5

140.3

53.1

139.5

59.3

5 / 3.9

160.6

43.4

159.0

48.4

157.6

53.9

156.6

60.1

156.1

64.0

7 / 6.1

170.3

43.7

168.0

48.8

166.4

54.3

165.3

60.4

164.9

64.4

10 / 8.2

179.8

44.1

176.9

49.2

174.9

54.7

173.9

60.8

173.7

64.6

15 / 13

202.7

44.9

197.9

50.0

195.1

55.6

194.3

61.5

BT02F014GB-00

Size

Ta = evaporator inlet air temperature


kWt = Condenser output in kW
kWe = Compressor power input in kW
DT = difference between inlet / outlet water temperature = 5C

HYDRONIC
292 - 604
Acoustic configuration: Low noise (LN)

GENERAL TECHNICAL SPECIFICATIONS


Size

292

323

404

464

524

564

604

COOLING
Cooling capacity
Compressor power input
Total power input
EER
HEATING

kW
kW
kW
Nr

75.3
26.3
28.8
2.61

87.8
30.7
33.2
2.65

101.5
33.2
36.9
2.75

115.3
39.4
42.8
2.69

127.4
45.4
49
2.6

135.6
50.6
54.1
2.5

141.9
55.7
59.3
2.39

Heat output
Compressor power input
Total power input
COP
COMPRESSOR

kW
kW
kW
Nr

85.5
27
29.3
3.17

98.4
31.3
33.6
3.14

113
36.2
39.8
3.12

128.4
41
43.9
3.13

144.5
46.6
49.5
3.1

153.9
50
52.3
3.08

163.3
54.1
56.6
3.02

Type of compressors
No. of Compressors
Std Capacity control steps
Oil charge (C1)
Oil charge (C2)
Oil charge (C3)
Oil charge (C4)
Refrigerant charge (C1)
Refrigerant charge (C2)
Refrigerant charge (C3)
Refrigerant charge (C4)
Refrigerant circuits
EVAPORATOR

3
Nr
Nr
l
l
l
l
kg
kg
kg
kg
Nr

scroll
2
2
6.6
6.6
0
0
24
24
0
0
2

scroll
3
3
6.6
3.3
3.3
0
24
13.5
13.5
0
2

scroll
4
4
3.3
3.3
3.3
3.3
13.5
13.5
13.5
13.5
2

scroll
4
4
3.3
3.3
3.3
3.3
13.5
13.5
16
16
2

scroll
4
4
3.3
3.3
3.3
3.3
16
16
16
16
2

scroll
4
4
3.3
3.3
6.6
6.6
16
16
17.5
17.5
2

scroll
4
4
6.6
6.6
6.6
6.6
17.5
17.5
17.5
17.5
2

Type of evaporator
Water flow-rate
Pressure drop
Useful pump discharge head
Water content
EXTERNAL SECTION FANS

4
l/s
kPa
kPa
l

PHE
3.6
27
130
5.9

PHE
4.2
23
115
7.8

PHE
4.8
28.5
100
7.8

PHE
5.5
26.5
120
9.4

PHE
6.1
32.5
105
9.4

PHE
6.5
28.5
120
11

PHE
7
32.5
110
11

Type of fans
Number of fans
Fan RPM
Standard air flow
Installed unit power
CONNECTIONS

5
Nr
rpm
l/s
kW

AX
2
650
9170
1.3

AX
2
650
9000
1.3

AX
3
650
13200
1.3

AX
3
650
13000
1.3

AX
3
650
12900
1.3

AX
3
650
12900
1.3

AX
3
650
12900
1.3

mm

2" 1/2

2" 1/2

2" 1/2

2" 1/2

2" 1/2

2" 1/2

2" 1/2

kg
kg

1463
1478

1562
1579

1717
1734

1771
1790

1801
1820

1853
1873

1896
1916

Length
Depth
Height
EXPANSION VESSEL

mm
mm
mm

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

3250
1095
2030

Expansion vessel capacity


Maximum water side pressure
Nitrogen buffer pressure
STORAGE

l
kPa
kPa

12
800
150

12
800
150

16
800
150

16
800
150

18
800
150

18
800
150

18
800
150

200

200

200

200

200

200

200

kPa
kPa

550
600

550
600

550
600

550
600

550
600

550
600

550
600

Water fittings
STANDARD UNIT WEIGHTS
Shipping weight
Operating weight
DIMENSIONS

BT02F014GB-00

Storage capacity
HYDRAULIC CIRCUIT

10

Max water side pressure


Safety valve calibration
(1) data refers to the following conditions :
evaporator water = 12/7C
room temperature = 35C
(2) data refers to the following conditions :
condenser water = 40/45C
room temperature = 7C (RH = 85%)
(3) SCROLL = scroll compressor
(4) PHE = plates
(5) AX = axial-flow fan

HYDRONIC
292 - 604
Acoustic configuration: Low noise (LN)

ELECTRICAL DATA
Size

292

323

404

464

524

564

604

29.2
29.2
2.3
2
3.1
68.3

19.5
29.2
19.5
2.3
2
3.1
78.1

19.5
19.5
19.5
19.5
2.3
3
3.1
90.2

25.3
19.5
25.3
19.5
2.3
3
3.8
102.5

25.3
25.3
25.3
25.3
2.3
3
3.8
114.1

29.2
25.3
29.2
25.3
2.3
3
5
123

29.2
29.2
29.2
29.2
2.3
3
5
130.8

Compressor 1 (400/3/50)
A
Compressor 2 (400/3/50)
A
Compressor 3 (400/3/50)
A
A
Compressor 4 (400/3/50)
External Fan (400/3/50)
A
A
Pump (400/3/50 )
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

175
175
4.7
14.6

130
175
130
4.7
14.6

130
130
130
130
4.7
14.6

175
130
175
130
4.7
19

175
175
175
175
4.7
19

175
175
175
175
4.7
24.8

175
175
175
175
4.7
24.8

Compressor 1 (400/3/50)
Compressor 2 (400/3/50)
Compressor 3 (400/3/50)
Compressor 4 (400/3/50)
External Fan (400/3/50)
Pump (400/3/50 )
Total (400/3/50 )
M.I.C. MAXIMUM INRUSH CURRENT

kW
kW
kW
kW
kW
kW
kW

17.3
17.3
1.25
1.1
38.9

11.3
17.3
11.3
1.25
1.1
44.2

11.3
11.3
11.3
11.3
1.25
1.1
50.7

14.5
11.3
14.5
11.3
1.25
1.5
57.5

14.5
14.5
14.5
14.5
1.25
1.5
63.9

17.3
14.5
17.3
14.5
1.25
1.9
69.9

17.3
17.3
17.3
17.3
1.25
1.9
75.5

214.1

204.4

200.7

252.2

263.8

268.8

276.6

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

292

323

404

464

524

564

604

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS


Compressor 1 (400/3/50)
Compressor 2 (400/3/50)
Compressor 3 (400/3/50)
Compressor 4 (400/3/50)
External Fan (400/3/50)
Number of fans
Pump (400/3/50 )
Total (400/3/50 )
L.R.A. LOCKED ROTOR AMPERES

A
A
A
A
A
Nr
A
A

Value (400/3/50 )
POWER SUPPLY
power supply
voltage unbalance: max 2 %
power supply: 400/3/50 Hz +/-10%

Acoustic configuration: Low noise (LN)

OPERATING LIMITS (Cooling)


Size
CONDENSER
Max air intake temperature
Max air intake temperature
Min. air intake temperature
Min. air intake temperature

1
2
3
4

C
C
C
C

44
50
-10
12

43
49
-10
12

45
51
-10
12

44
50
-10
12

44
50
-10
12

41
47
-10
12

41
47
-10
12

5
5

C
C

19
-5.5

19
-5.5

19
-5.5

19
-5.5

19
-5.5

19
-5.5

19
-5.5

OPERATING LIMITS (Heating)


Max air temperature inlet (WB)
Min air inlet temperature (W.B.)

Note: For ambient lower than 5C the low ambient temperature control with inverter is
recommended
(1) unit at full load: evaporator water 12/7C
(2) capacity-controlled unit (automatic capacity control)
(3) with electronic low ambient temperature control, unit at partial load and motionless
external air
(4) with electronic low ambient temperature control, unit at partial load with air speed 1 m/
sec
(5) unit at full load
condenser water = 40/45C

BT02F014GB-00

EVAPORATOR

11

HYDRONIC
292 - 604
ACOUSTIC CONFIGURATION: LOW NOISE (LN)

COOLING PERFORMANCE
CONDENSER AIR INTAKE TEMPERATURE (C)
Size

292

323

404

464

524

BT02F014GB-00

564

604

To
(C)

25

30

35

40

43

46

kWe

kWf

kWe

kWf

kWe

kWf

kWe

kWf

kWe

kWf

kWe

kWf

kWe

81.6

21.3

77.3

23.6

75.6

24.6

72.8

26.1

68.1

28.8

65.1

30.5

62.0

32.2

84.3

21.5

79.9

23.8

78.1

24.8

75.3

26.3

70.4

29.0

67.4

30.7

64.2

32.4

87.0

21.7

82.5

24.0

80.6

25.0

77.8

26.5

72.7

29.2

69.6

30.9

89.6

21.9

85.0

24.3

83.1

25.2

80.1

26.8

75.0

29.4

71.8

31.1

10

92.2

22.1

87.5

24.5

85.5

25.5

82.4

27.0

77.1

29.7

73.8

31.4

11

94.8

22.3

89.9

24.7

87.8

25.7

84.7

27.2

79.2

29.9

75.8

31.6

94.9

24.7

89.7

27.5

87.6

28.6

84.4

30.4

78.8

33.6

75.4

35.5

98.6

25.0

93.3

27.7

91.2

28.9

87.8

30.7

82.1

33.8

78.5

35.8

102.0

25.2

96.6

27.9

94.4

29.1

91.0

30.9

85.0

34.1

81.4

36.1

105.1

25.4

99.6

28.2

97.3

29.3

93.8

31.1

87.7

34.3

10

108.0

25.6

102.3

28.4

100.0

29.5

96.4

31.3

90.1

34.5

11

110.6

25.9

104.7

28.6

102.3

29.8

98.6

31.6

92.1

34.7

109.2

26.7

103.7

29.8

101.4

31.0

97.9

33.0

91.7

36.6

87.8

38.8

83.7

41.1

113.0

26.9

107.4

29.9

105.1

31.2

101.5

33.2

95.1

36.7

91.1

39.0

87.0

41.4

116.8

27.1

111.0

30.1

108.6

31.4

104.9

33.4

98.4

36.9

94.3

39.2

90.1

41.6

120.5

27.3

114.5

30.3

112.1

31.6

108.2

33.6

101.5

37.1

97.3

39.4

93.0

41.8

10

124.0

27.5

117.9

30.5

115.3

31.8

111.4

33.8

104.5

37.3

100.2

39.6

95.8

42.0

11

127.5

27.7

121.1

30.7

118.5

32.0

114.4

34.0

107.4

37.5

103.0

39.8

98.5

42.1

124.6

31.9

118.2

35.4

115.5

36.8

111.4

39.1

104.4

43.1

100.0

45.6

95.6

48.2

128.8

32.2

122.2

35.7

119.4

37.1

115.3

39.4

108.0

43.4

103.6

45.9

99.0

48.5

132.9

32.5

126.1

36.0

123.3

37.4

119.0

39.7

111.6

43.7

107.0

46.2

137.0

32.7

130.0

36.2

127.2

37.7

122.7

40.0

115.1

44.0

110.3

46.5

10

141.0

33.0

133.9

36.5

131.0

38.0

126.4

40.2

118.5

44.2

113.5

46.8

11

145.0

33.3

137.7

36.7

134.7

38.2

130.0

40.5

121.8

44.5

116.6

47.0

137.6

36.9

130.6

40.8

127.7

42.5

123.2

45.0

115.4

49.5

110.6

52.3

105.6

55.3

142.1

37.3

135.0

41.2

132.0

42.8

127.4

45.4

119.4

49.9

114.4

52.7

109.2

55.7

146.7

37.7

139.3

41.6

136.2

43.2

131.5

45.8

123.2

50.3

118.1

53.1

151.2

38.0

143.6

41.9

140.4

43.6

135.5

46.1

127.0

50.6

121.7

53.5

10

155.6

38.4

147.8

42.3

144.5

44.0

139.5

46.5

130.8

50.9

125.3

53.7

11

160.0

38.8

151.9

42.7

148.6

44.3

143.4

46.9

134.5

51.2

128.9

54.0

147.3

41.2

139.5

45.5

136.3

47.3

131.3

50.1

122.7

55.1

152.2

41.6

144.1

45.9

140.8

47.8

135.6

50.6

126.7

55.6

157.0

42.0

148.7

46.4

145.2

48.2

139.9

51.1

130.7

56.0

161.7

42.5

153.2

46.8

149.6

48.7

144.2

51.5

134.6

56.5

10

166.4

42.9

157.6

47.3

153.9

49.1

148.3

51.9

138.5

56.9

11

171.0

43.3

161.9

47.7

158.2

49.5

152.4

52.4

154.8

45.3

146.2

50.1

142.7

52.1

137.3

55.2

128.1

60.5

159.8

45.8

151.0

50.6

147.4

52.6

141.9

55.7

132.3

61.1

164.7

46.2

155.8

51.1

152.1

53.1

146.3

56.2

136.4

61.7

169.6

46.7

160.4

51.6

156.6

53.6

150.7

56.7

140.4

62.2

10

174.5

47.2

165.0

52.1

161.0

54.1

155.0

57.2

144.5

62.7

11

179.2

47.7

169.4

52.6

165.3

54.6

159.1

57.8

kWf = Cooling capacity in kW


kWe = Compressor power input in kW
To = Evaporator water outlet temperature in C
DT = difference between inlet / outlet water temperature = 5C

12

32

kWf

HYDRONIC
292 - 604
ACOUSTIC CONFIGURATION: LOW NOISE (LN)

HEATING PERFORMANCE

292

323

404

464

524

564

604

Ta
(C)
DB/WB

CONDENSER WATER INLET / OUTLET TEMPERATURE (C)


30 / 35

35 / 40

40 / 45

45 / 50

kWt

kWe

kWt

kWe

kWt

kWe

-5 / -5.4

63.1

20.8

62.8

23.2

63.8

26.0

0 / -0.6

72.6

21.2

71.9

23.6

71.9

5 / 3.9

82.7

21.6

81.6

24.0

80.7

48 / 53

kWt

kWe

kWt

kWe

26.4

72.5

29.5

26.8

80.0

29.9

79.7

31.9

7 / 6.1

88.0

21.8

86.7

24.3

85.5

27.0

84.3

30.1

83.6

32.1

10 / 8.2

93.4

22.0

91.9

24.5

90.3

27.2

88.7

30.3

87.8

32.3

100.3

30.8

99.0

32.8

15 / 13

106.5

22.4

104.5

25.0

102.4

27.8

-5 / -5.4

73.9

24.1

74.0

26.9

73.2

30.3

0 / -0.6

84.2

24.5

83.3

27.3

82.4

30.7

81.3

34.5

5 / 3.9

95.4

24.8

94.0

27.7

92.7

31.1

91.5

34.9

7 / 6.1

101.5

25.0

100.0

27.9

98.4

31.3

96.8

35.0

95.8

37.5

10 / 8.2

107.5

25.2

106.1

28.1

104.3

31.5

102.2

35.2

100.7

37.6

15 / 13

122.7

25.5

121.5

28.6

119.0

31.9

115.2

35.6

112.3

37.9

-5 / -5.4

81.8

27.7

81.7

31.1

82.8

35.0

0 / -0.6

95.2

28.2

94.4

31.7

94.4

35.5

95.2

39.8

5 / 3.9

109.0

28.7

107.5

32.1

106.5

36.0

106.1

40.2

106.1

43.0

7 / 6.1

116.1

28.9

114.4

32.3

113.0

36.2

111.9

40.4

111.4

43.2

10 / 8.2

123.2

29.0

121.2

32.5

119.4

36.4

117.8

40.6

116.9

43.3

15 / 13

140.2

29.4

137.8

32.9

135.2

36.8

132.2

41.0

-5 / -5.4

94.2

31.6

94.1

35.4

95.8

39.5

0 / -0.6

109.0

32.1

108.0

36.0

107.8

40.2

108.5

44.7

5 / 3.9

124.1

32.6

122.5

36.5

121.1

40.7

120.0

45.3

7 / 6.1

131.9

32.9

130.2

36.8

128.4

41.0

126.6

45.6

125.4

48.5

10 / 8.2

139.6

33.1

137.8

37.0

135.8

41.3

133.5

45.9

132.0

48.8

151.5

46.5

15 / 13

158.3

33.6

156.5

37.6

154.3

41.8

-5 / -5.4

103.5

35.9

106.4

40.1

108.5

44.5

0 / -0.6

122.2

36.6

122.0

40.8

121.8

45.4

121.5

50.4

5 / 3.9

140.0

37.2

138.1

41.5

136.5

46.2

135.1

51.3

134.4

54.6

7 / 6.1

148.8

37.6

146.5

41.9

144.5

46.6

142.6

51.8

141.5

55.0

10 / 8.2

157.3

37.9

154.9

42.2

152.6

47.0

150.2

52.1

148.7

55.5

169.5

53.0

15 / 13

176.8

38.6

175.3

43.0

172.9

47.8

-5 / -5.4

114.8

38.6

114.7

42.4

114.9

47.7

0 / -0.6

131.2

39.2

130.5

43.3

129.7

48.7

128.7

55.6

5 / 3.9

148.3

39.9

147.0

44.1

145.5

49.6

143.7

56.5

142.5

61.3

7 / 6.1

157.2

40.2

155.7

44.4

153.9

50.0

151.9

56.9

150.6

61.7

10 / 8.2

166.0

40.6

164.3

44.8

162.4

50.3

160.3

57.2

159.0

61.9

15 / 13

187.5

41.3

185.4

45.6

183.4

51.1

181.6

57.8

180.7

62.3

-5 / -5.4

127.5

42.2

125.2

46.6

0 / -0.6

141.4

43.0

140.2

47.4

137.3

52.9

5 / 3.9

157.5

43.7

156.6

48.2

154.4

53.7

150.9

60.0

7 / 6.1

166.4

44.1

165.4

48.6

163.3

54.1

160.0

60.4

157.5

64.7

10 / 8.2

175.7

44.4

174.3

49.0

172.0

54.5

168.8

60.9

166.3

65.1

15 / 13

199.2

45.2

196.5

50.0

193.2

55.6

BT02F014GB-00

Size

Ta = evaporator inlet air temperature


kWt = Condenser output in kW
kWe = Compressor power input in kW
DT = difference between inlet / outlet water temperature = 5C

13

HYDRONIC
292 - 604

DIMENSIONAL DRAWING
DIMENSIONAL DRAWING(1)
(1) COMPRESSOR
(2) PLATE EXCHANGER
(3) FINNED EXCHANGER
(4) HOLE TO HANG UNIT
(5) LIFTING HOLES
(6) LIFTING LUGS
(7) ELECTRICAL PANEL
(8) POWER INPUT
(9) SOUNDPROOFED CABIN
(10) CENTRIFUGAL PUMP
(11) EXCHANGER WATER INLET
(12) EXCHANGER WATER OUTLET

7
3

9
2

8
8
160

10

2
1

350

10

12
4-5

148

85

85

861
2990
L

200

11

4-5

4-5

148

59

175

2990

4-5
977
W

59

175

W2

59

W1

59

977

"G"

W3

W4

DIMENSIONAL DRAWING
Acoustic configuration: Standard (ST)
Size
H
L
M
N
O
P
W
OD

292

323

404

464

524

564

604

mm
mm
mm
mm
mm
mm
mm
mm

2030
3250
1628
1622
533
562
1095
2" 1/2

2030
3250
1671
1579
541
554
1095
2" 1/2

2030
3250
1693
1557
551
544
1095
2" 1/2

2030
3250
1697
1553
551
544
1095
2" 1/2

2030
3250
1704
1546
553
542
1095
2" 1/2

2030
3250
1717
1533
558
537
1095
2" 1/2

2030
3250
1728
1522
562
533
1095
2" 1/2

292

323

404

464

524

564

604

mm
mm
mm
mm
mm
mm
mm
mm

2030
3250
1636
1614
538
557
1095
2" 1/2

2030
3250
1678
1572
545
550
1095
2" 1/2

2030
3250
1699
1551
555
540
1095
2" 1/2

2030
3250
1703
1547
555
540
1095
2" 1/2

2030
3250
1709
1541
557
538
1095
2" 1/2

2030
3250
1722
1528
562
533
1095
2" 1/2

2030
3250
1733
1517
565
530
1095
2" 1/2

Acoustic configuration: Low noise (LN)


Size

BT02F014GB-00

H
L
M
N
O
P
W
OD

14

HYDRONIC
292 - 604

WEIGHT DISTRIBUTION
WEIGHT DISTRIBUTION(1)

85

2990

175

W2

59

W1

59

977

"G"

W3

W4

WEIGHT DISTRIBUTION
Acoustic configuration: Standard (ST)
Size
W1
W2
W3
W4
Operating weight
Shipping weight

kg
kg
kg
kg
kg
kg

292

323

404

464

524

564

604

361
385
340
362
1447
1432

369
416
358
405
1548
1531

391
455
396
461
1703
1686

403
471
408
477
1759
1740

405
479
415
490
1789
1770

409
492
427
514
1842
18222

412
503
437
533
1885
1865

292

323

404

464

524

564

604

363
391
348
376
1478
1463

371
423
367
419
1579
1562

393
461
405
475
1734
1717

405
477
417
491
1790
1771

408
485
424
504
1820
1801

411
498
436
528
1873
1853

414
509
446
547
1916
1896

Size
W1
W2
W3
W4
Operating weight
Shipping weight

kg
kg
kg
kg
kg
kg

BT02F014GB-00

Acoustic configuration: Low noise (LN)

15

HYDRONIC
292 - 604

1500

1500

1500

FUNCTIONAL CLEARANCES

900

The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited.