Вы находитесь на странице: 1из 22

TATA CONSULTING ENGINEERS

SECTION: TITLE

TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SHEET i OF iii

DESIGN GUIDE
FOR
GENERATOR SYSTEM FAULT CALCULATION

TATA CONSULTING ENGINEERS


414, Veer Savarkar Marg
Prabhadevi
MUMBAI 400 025

FLOPPY NO
FILE NAME

REV.NO

: TCE.M6-EL-CD-DOC-003
: M6-700-6621.DOC

R0

ISSUE

INITIALS

SIGN

PPD.BY

BHR/BS

Sd/-

CKD.BY

HDM

Sd/-

APP.BY

PKS

Sd/-

DATE

INITIALS

SIGN

INITIALS

SIGN

INITIALS

SIGN

R0

1992.03.30
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:REV SHT

SHEET ii OF iii

REVISION

REV. NO.

DATE

DESCRIPTION

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS

SECTION:CONTENTS

TCE.M6-EL-700-6621

SHEET iii OF iii

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

CONTENT

SR.NO.

TITLE

SHEET NO.

1.0

SCOPE

2.0

ABBREVIATIONS USED

3.0

REFERENCE DIAGRAM

4.0

DATA

5.0

PROCEDURE

6.0

DISCUSSION

7.0

REFERENCE

8.0

ANNEXURE-1 ONE LINE DIAGRAM

9.0

ANNEXURE-2 DATA REQUIRED FROM THE

GENERATOR MANUFACTURER
10.0

ANNEXURE-3 SAMPLE CALCULATION

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:WRITE-UP

SHEET 1 OF 19

1.0

SCOPE

1.1

The scope of this design guide is to provide a detailed method to calculate the fault
currents when a 3 phase fault occurs at any point in the following sections of the
power plant electrical network.
a)

The generator main power evacuation circuit consisting of the generator,


the main bus duct till generator transformer and the section upto the grid.

b)

The unit auxiliary transformer section consisting of tap off section of the
busduct upto the unit auxiliary transformer.

1.2

The fault currents calculated would be required to assign the rating of the
equipment operating in the electrical network indicated above such as Extra High
Voltage Circuit Breaker, Bus Duct and Generator Circuit Breaker (if provided)

2.0

ABBREVIATIONS USED
GT
:
UAT :
EHVCB:
GCB :
SEB :
pu
:

Generator Transformer
Unit Auxiliary Transformer
Extra High Voltage Circuit Breaker
Generator Circuit Breaker
State Electricity Board
Per Unit

3.0

REFERENCE DIAGRAM

3.1

A schematic diagram indicating the equipment such as Generator, GT, UAT,


EHVCB and GCB is given in Annexure-1.

4.0

DATA
To calculate the fault currents, the ratings/data of the following equipment/system
are required.

4.1

GRID : Following details/data of the grid to which the generator is connected are
required.
i)

The voltage level in kV.

ii)

The maximum rms symmetrical fault level in kA.

iii)

The X/R Ratio


ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:WRITE-UP

SHEET 2 OF 19

4.2

Generator

4.2.1

The data required from the generator manufacturer to carryout the fault calculations
are listed in Annexure-2.

4.2.2

Tolerances on the machine parameters shall be specifically confirmed with the


manufacturer, in the absence of this confirmation, tolerances as per IEC-34 or
relevant standards shall be applied.

4.3

Generator Transformer

4.3.1

The following parameters of the GT are required for fault calculation:


a)
b)
c)

Rated primary and secondary voltages.


Rated maximum 3 phase MVA of the transformer
Reactance and resistance values of the transformer.

The resistance of the transformer shall be found using the full load copper losses in
case the values of the resistances are not directly available.
4.3.2

Tolerances as confirmed by the transformer manufacturer shall be applied. If the


tolerances are not furnished by the manufacturer, the tolerances as per relevant
standards shall be applied.

4.4

Bus Ducts

4.4.1

The values of resistance and reactance of the busduct are very small quantities of
the order of micro ohms. Hence these parameters need not be considered for
calculation.

5.0

PROCEDURE

5.1

All calculations shall be made in p.u. system.

5.2

The base MVA and base kV shall preferably be taken as the rated MVA and rated
kV of the generator.

5.3

(Base kV)2 L-L


Base Impedance = ------------------------ OHMS
Base MVA (3 ph)

5.4

Actual Impedance in ohms


P.U. Impedance = -----------------------------------Base Impedance in ohms
ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

5.5

SECTION:WRITE-UP

SHEET 3 OF 19

P.U. Impedance on any other MVA and kV can be converted to the P.U. Impedance
on base MVA & base kV as follows:
Zpu (New)
Zpu (Old)

Zpu (new)

=
=

P.U. Impedance on base MVA and base kV


P.U. Impedance on any other MVA and kV

Zpu (old) x

MVA (new) kV2 (old)


-------------- x ----------MV (old)
kV2 (new)

6.0

DISCUSSION

6.1

A sample calculation to calculate the symmetrical fault current, the DC component,


the asymmetrical fault current and the momentary current has been given in
Annexure-3 for a typical 500 MW plant having a generator circuit breaker. The
calculation steps have been explained in detail and the same procedure shall be
adopted for units of other ratings also.

6.2

While specifying the rating of the equipment operating in the electrical network
considered in this design guide such as GCB and EHVCB, etc., the results obtained
from the calculations shall be indicated in the data sheet-A of the relevant
specification.

7.0

REFERENCES

7.1

The general theory of electrical machines- Adkins B. Chapman & Hall Ltd. 1962.

7.2

ANSI/IEEE Std. C.37.5-1979 IEEE Guide for calculation of fault currents for
application of AC High Voltage Circuit Breakers rated on a total current basis.

7.3

Elements of Power System Analysis W.D.Stevenson Jr.

7.4

IEEE C37.013-1989 Standard for AC High Voltage Generator Circuit Breakers


rated on a symmetrical current basis.

7.5

IEC-56 High Voltage AC Breakers-Publication 1987

7.6

IEC-34 Rotating Electrical Machines

7.7

Control and Stability of Electric Power Systems Anderson and Fouad.

ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-2

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

SHEET 5 OF 19

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

ANNEXURE-2
DATA REQUIRED FROM THE GENERATOR MANUFACTURER
Sl.No. Machine Parameters

Symbol

Unit

1.

Rated Voltage (L-L) rms

kV

2.

Rated MVA

MVA

MVA

3.

Rated Power Factor

cos

4.

Rated Current (rms)

Amps

5.

Frequency

Hz

6.

Armature resistance at 750 C

Ra

ohms

7.

Saturated Direct Axis Steady State Reactance

Xd

p.u.

8.

Saturated Direct Axis Transient Reactance

Xd

p.u.

9.

Saturated Direct Axis Subtransient Reactance

Xd

p.u.

10.

Saturated Quadrature Axis Steady State Reactance Xq

p.u.

11.

Saturated Quadrature Axis Subtransient Reactance Xq

p.u.

12.

Direct Axis Short Circuit Transient Time Constant Td

Sec

13.

Direct Axis Short Circuit


Sub-transient Time Constant

Td

Sec

14.

Armature Short Circuit Time Constant

Ta

Sec

15.

Quadrature Axis Short Circuit


Sub-transient Time Constant

Tq

Sec

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 6 OF 19

ANNEXURE-3
SAMPLE CALCULATION
1.0

This section outlines the detailed procedure for calculation of fault current in the
generator-generator transformer, UAT tap off section. Reference to the figure in
Annexure-1 shall be made.
The calculations are split into 5 parts.

1.1

Part-1 : Calculates 3 phase fault currents at any point between the generator and
generator transformer when generator alone is contributing to the fault.

1.2

Part-2 : Calculates 3 phase fault current at any point between GT and EHVCB
when grid/generator is contributing to the fault when the value of 3 phase
symmetrical fault current is known.

1.3

Part-3 : Calculates the 3 phase fault currents at the point considered in part 1 when
grid alone is feeding the fault.

1.4

Part-4 : Calculates the 3 phase fault currents on the UAT tap off part of the busduct
when both the grid and generator are feeding the fault.

1.5

Part-5 : Gives a summary of sizing the equipment performing in this section of the
electrical network considered.

2.0

ASSUMPTIONS MADE IN THE CALCULATIONS

2.1

For conservation fault estimation, the saturated value of the reactances are
considered.

2.2

The speed of the machine is assumed to be constant for about 60 to 80 milliseconds


(3 to 4 cycles) even after the instant of short circuit.

2.3

The switching angle A defines the point in the AC cycle at which the short circuit
occurs. The fault current at = 00 for unloaded generator case gives the maximum
DC component & = 900 gives the zero DC component. Hence = 00 is assumed.
The power angle is the angle between E the generated voltage and Vt the terminal
voltage of the generator is equal to zero since the value of E and Vt are same for
unloaded generator.

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 7 OF 19

2.4

The fault current fed from generator will be maximum when the value of and
are nearly equal. This is applicable for loaded as well as unloaded cases prior to
occurrence of the fault. For engineering applications the value of fault current
under generator unloaded conditions is adequate.

2.5

The calculations are done using general theory of electrical machines which is
based on a general machine concept. This is required to incorporate the finite effect
of saliency present in the turbo-generators which takes into consideration the
differences between the values of direct and quadrature axis reactances and time
constants and thus give accurate results.

2.6

The generator circuit breaker shall be sized such that the maximum values of the
symmetrical short circuit current, DC component shall be taken from part 1 and part
3 of the calculation.

2.7

Equivalent system (grid) X/R ratio at typical locations (for quick approximations)
are given below.
Type of Circuit

X/R

1.

Synchronous machines connected through transformers


rated 100 MVA and larger

40-60

2.

Synchronous machines connected through transformers


rated 25 to 100 MVA for each three-phase bank.

30-50

3.

Remote synchronous machines connected through


transformers rated 100 MVA or larger for each threephase bank, where the transformers provide 90 percent or
more of the total equivalent impedance to the fault point.

30-50

4.

Remote synchronous machines connected through


transformers rated 10 MVA to 100 MVA for each threephase bank, where the transformers provide 90 percent or
more of the total equivalent impedance to the fault point.

15-40

5.

Remote synchronous machines connected through other


types of circuits, such as; transformers rated 10 MVA or
smaller for each three-phase bank, transmission lines,
distribution feeders, etc.

15 or less

ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-3

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

SHEET 8 OF 19

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

General Calculations
Base kV
=
21 kV
Base MVA =
659 MVA

Base Impedance =

(Base kV)2
(21)2
------------- = ------- = 0.669
Base MVA 659

Following table furnish the parameters of generator, generator transformer and grid.
Refer Annexure-2 for details required for generator.
a)

GENERATOR

Sl.
No.

Parameter

Actual Value

P.U. Value

P.U Value
with tolerance

1.

Vt = Terminal Voltage

21.0 kV

1.0

1.05

2.

MVA

659

1.0

1.0

3.

Rated Current

18,118A

1.0

1.0

4.

Power factor

0.85

5.

Rated frequency

50 Hz

6.

Xd

2.16

1.728

7.

Xq

2.16

1.728

8.

Xd

0.271

0.2168

9.

Xd

0.193

0.1544

10.

Xq

0.212

0.1696

11.

Ra at 750 C

0.00176 ohms

0.00263

0.00263

12

Td

0.98 sec

13.

Td

0.03 sec

ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-3

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

SHEET 9 OF 19

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

14.

Tq

0.075 sec

15.

Ta

0.2 sec

SR.
No.

Parameter

b)

GENERATOR TRANSFORMER

1.

Actual Value

P.U. Value

P.U
Value
with tolerance

HV Volts (LL)

400 kV

2.

LV Volts

21 kV

3.

MVA

630 MVA

4.

Impedance, Zt

15%

0.1569

0.1412

5.

Resistance, Rt

0.005 ohms

0.0075

0.0075

6.

Inductance, Xt

0.141

c)

GRID

1.

Voltage level

400 kV

2.

Fault current

40 kA

3.

Fault MVA

27712 MVA

4.

Grid X/R

40

Notes:
a)

20% negative tolerance on the value of generator reactance, 5% positive


tolerance on generator terminal voltage and 10% negative tolerance on
transformer reactance are considered in this particular example. However
the tolerances shall be taken as per relevant standards when the
manufacturer does not indicate the tolerances in his data sheets.

b)

The transformer resistance value Rt shall be obtained from copper losses or


from transformer winding resistance test.

c)

Xt the transformer reactance = (Zt2 Rt2)1/2

d)

400 kV grid fault level = 40 kA = 27712 MVA


ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-3

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

SHEET 10 OF 19

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

659
Grid fault impedance in pu = ------------ = 0.02378 pu
27712
PART-1

Vt peak

(2)1/2 x Vt 00

(2)1/2 x 1.05 00

= 1.4849 pu

2 XdXq
Factor, Xm = --------------- =
(Xd + Xq)

2 x 0.1544 x 0.1696
------------------------- =
(0.1544 + 0.1696)

0.1616 pu

2 XdXq
= --------------- =
(Xq - Xd)

2 x 0.1544 x 0.1696
------------------------- =
(0.1696 - 0.1544)

3.4456 pu

Factor, Xn

Breaker opening time = 60 milliseconds for GCB & EHVCB

2f radians = 314.1593 radians = 18,000 degrees

2ft

= 00

= 18000 x 60 x 10-3 = 1080 degrees

& = 00

The steady state value of the voltage before short circuit can be analysed to be made up of
2 components namely Direct and Quadrature axes.
The direct axis component Vd

= (2)1/2 Vt sin

The quadrature axis component Vq = - (2)1/2 Vt cos


The direct axis component Vd = 0 since the value of = 00
and Vq = - 1.4849 pu.
The complete expression for the fault current in each phase consists of 2 components Ia1 &
Ia2 whose equations are given below for phase a. The value of fault currents in the other
two phases b & c can be calculated substituting by (- 2/3) and ( - 4/3)
respectively.

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 11 OF 19

Equation 1 :
Ia1 = [ Vq/xd +(Vq/Xd Vq/Xd) e- t/Td + (Vq/Xd Vq/Xd) e t/Td] cos (t +)
- Vq/Xm e-t/Ta cos - Vq/Xn e-t/Ta cos (2t + )
Equation 2 :
Ia2 = - [ Vd/xq +(Vd/Xq Vd/Xq) e- t/Tq ] sin (2t +)
+ Vd/Xm e-t/Ta sin - Vd/Xn e-t/Ta sin (2t + )
The total fault current in phase a : Ia = Ia1 + I a2
The equation 2 reduces to zero since Vd = 0
Equation 1 consists of 3 parts
Part a :
Iac1 = [ Vq/xd +(Vq/Xd Vq/Xd) e- t/Td + (Vq/Xd Vq/Xd) e t/Td] cos (wt +)
is called the AC fundamental
Part-b :
Iac2 = (- Vq/Xn) e-t/Ta cos (2wt + )
is called the second harmonic component
Part c :
Idc = (- Vq/Xm) e-t/Ta cos
is called the DC component of the fault current.
Total AC component of the fault current = (Part a + Part b) pu
Total symmetrical Iac (rms) = (Iac1 + Iac2) / 2 pu
Iac peak = Iac x 2 pu
% DC component = (Idc /Iac peak) x 100
Total Iac asymmetrical

= (Idc2 + Iac2 rms)1/2


ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 12 OF 19

Substituting the values of the parameters in equation 1 we get by simplifying:


Iac1
Iac2
Idc

=
=
=

- 6.8669 pu
0.3192 pu
6.80699 pu

Iac1 + Iac2
Symm Iac rms = --------------------- = 4.6299 pu
2
(Iacrms2 + Idc2)1/2

Asymm Iac rms

Iactual

I base x I pu

8.23 pu

Symm Iac rms

18118 x 4.6299

83.88 kA

Asymm Iac rms

18118 x 8.23

149.11 kA

Idc

18118 x 6.80699

123.33 kA

% DC

123.33 x 100
= ----------------------- 2 x 83.88

103.97%

A computer package SMS is available which calculates the fault currents which have been
computed above manually.

ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-3

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SHEET 13 OF 19

PART-2
a)

Grid Feed
The symmetrical fault current fed from the
400 kV grid Iacgrms =

40 kA

X/R ratio of the grid =

40

Iacg (peak)

40 x 2

X/R

56.57 kA

0.127 sec

2FL / R

L
40
Time constant , = ------ = ----------R
2 x 50
t = EHVCB opening time
Idc

= 60 milliseconds

= DC current due to X/R of 40 =


Idc

Iac g (peak) e-t/

56.57 e 60X.001 / 0.127

Idc

=
35.27 kA
Idc x 100
% DC component = -------------- =
Iacg (peak)

35.27
-------- x 100 = 62.35%
56.57

Total Asymmetrical Current = (Iac2grms +Idc2 )


b)

53.33 kA

Generator Feed
The generator feed to the fault current when a fault occurs after EHVCB can be
computed by using equation 1 referred in part A of the calculations. However the
value of reactances such as Xd, Xd, Xd, Xq, Xq etc. get modified as Xd + Xt,
Xd + Xt, Xd+Xt, Xq+Xt, Xq+Xt etc. respectively where Xt is the GT reactance.
The armature time constant Ta which is approximately equal to Ld/Ra becomes
(Ld + Lt)/(Ra + Rt)
where Ld = Xd/ 2f and Lt = Xt / 2f
Substituting the values in equation 1 we get,
ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-3

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

Iac rms=

2.833 x 18118 =

51.33 kA

Idc

2.569 x 18118 =

46.545 kA

SHEET 14 OF 19

Iac asymm = (51.332 + 46.5452)1/2 = 69.3 kA


These values are on 21 kV side of the GT
I
The values on 400 kV side of the GT = -----------(400 + 21)
The value of Iac rms on 400 kV side = 51.33 x 1 / 19.05 = 2.69 kA
Similarly on 400 kV side Iac asymm = 3.64 kA
Idc
= 2.44 kA

% DC component

4.2325 x 100
= -------------------- 2 x 4.67

64.08%

Comparing grid feed and generator feed for the fault considered, we find that the
grid feed is much larger than the generator feed because of the impedance of the
GT. Hence EHVCB should be sized to perform for grid feed.

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 15 OF 19

PART 3

The fault current fed from grid alone when a 3 phase fault occurs anywhere
between the generator and generator transformer LV bushing is calculated in this
section.
400 kV
The grid impedance = ---------------=
5.774 ohms
3 x 40
Zg =

5.744 ohms

X/R of the grid =

40

Rg = Xg/40 ohms & Xg = 40 Rg


But Z2 = R2
Rg2 =
Rg2 =

+
Zg2

X2
- Xg2

Zg2 - (40 Rg)2

Rg2 (1 + 1600) = Zg2


Rg2

(5.774)2
= ----------------(1600 + 1)

0.020824 ohms

Xg = Zg2 - Rg2 = 5.7742 - 0.020824 = 5.7722 ohms


Assuming 630 MVA and 400 kV the rating of transformer as base MVA and base
kV on EHV side of the transformer, the base impedance.
4002
= ----- =
253.97 ohms
630
The fault impedance of the grid in p.u.
5.774
= ---------= 0.02273 p.u.
253.97

ISSUE
R0
FORM NO. 120 R1

SECTION:
ANNEXURE-3

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SHEET 16 OF 19

The fault reactance of the grid in p.u.


5.7722
= ---------= 0.02273 p.u.= Xg
253.97
The fault resistance of the grid in p.u.
0.020824
= -------------- = 0.000082 p.u.
253.97
The p.u. impedance of the GT

= 0.1412 p.u.

For a fault between the generator and generator transformer,


The total fault impedance = 0.1412 + 0.02273 = 0.16393 p.u.

Fault MVA

Base MVA
= -------------------Fault impedance

630
= ---------- = 3847.79 MVA
0.16393

Symmetrical fault current Igrms


on 21 kV side
Ig peak = 105.79 x 2
0.02273
Lg = ------------- pu
2 x 50

Similarly Lt

3847 .79
= ------------ =
3 x 21

105.79 kA

149.605 kA

= 0.00007235 pu & Rg = 0.000082 pu

0.1408
= ------------2 x x 50

= 0.00044 pu & Rt = 0.0075 pu

The effective time constant to


(Lg + Lt)
calculate DC component
T = ---------(Rg + Rt)

0.00051
= ------------ = 0.06726 secs
0.00758

Assuming 60 milliseconds is required for EHVCB to break fault currents


t

60 x 10-3 sec

Idc

(Igpeak) x e-t/C

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

Idc

149.605 x e-60 x 10 3/0.06726

Idcg

61.3 kA on 21 kV side

Asumm Iacg = Idcg2 + Igrms2

% DC component =

SECTION:
ANNEXURE-3

SHEET 17 OF 19

= 105.792 + 61.32 = 122.27 kA

61.3
---------- x 100
149.605

41%

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 18 OF 19

PART-4

This part calculates the fault currents on the UAT tap off portion of the busduct.
The total fault current will be equal to the sum of the fault currents fed from the
generator and the grid.
Hence the total fault current will be equal to the sum of the fault currents calculated
in Part 1 and Part 3.
Total Iac symm

83.88 kA + 105.79 kA = 189.67 kA

Total Iac asymm

149.11 + 122.27

Total Idc

123.33 kA + 61.3 kA = 184.63 kA

= 271.36 kA

ISSUE
R0
FORM NO. 120 R1

TATA CONSULTING ENGINEERS


TCE.M6-EL-700-6621

DESIGN GUIDE FOR


GENERATOR SYSTEM FAULT CALCULATION

SECTION:
ANNEXURE-3

SHEET 19 OF 19

PART-5
SUMMARY OF SIZING EQUIPMENT PERFORMING IN THE SECTION
OF THE NETWORK UNDER CONSIDERATION
1. GCB : Symmetrical Breaking Capacity

= 106 kA (grid feed)

DC current = 123.33 kA (generator feed)


123.33
% DC component = ------------------ x 100 = 82.3%
106 x 2
Asymmetrical breaking capcity

Peak Fault Making Current

106 x 2.55

162.62 kA
= 271 kA

GCB shall be sized for the above values of the short circuit current. The generator
circuit breaker as per IEEE C 37.013 1989 meeting the above rating shall be
specified.
2. EHVCB:

Symmetrical Breaking Capacity

40 kA

% DC component

63%

Asymmetrical Breaking Capacity

54 kA

Peak fault making current

= 40 x 2.55

= 102 kA

3. BUSDUCT
a)

Main busduct between generator and generator transformer (Higher of the


generator & grid feed shall be taken)
Short time current
Momentary rating

b)

=
=

106 kA for 1 second


271 kA (Peak)

Portion of the busduct from UAT tapoff point till UAT HV terminals.

This portion of the bus duct is susceptible to fault currents fed from both generator
and EHV grid.
Hence short time current = 84 kA + 106 kA = 190 kA for 1 sec.
Momentary rating
=
190 x 2.55
= 485 kA (Peak)
ISSUE
R0
FORM NO. 120 R1

Вам также может понравиться