Introduction

Industry leading energy saving

New intelligent VRF control

12

Industry leading pipe length for greater flexibility

15

Other features
Outdoor units

17

Outdoor units line-up

19

Outdoor units specifications

21

Indoor units
Indoor units line-up

27

4-way Air Discharge Cassette Type

28

Compact 4-way Cassette (600x600) Type

30

2-way Air Discharge Cassette Type

32

1-way Air Discharge Cassette Type

34

Concealed Duct Type


Concealed Duct High Static Pressure Type

36
38

Slim Duct Type

40

Ceiling Type

42

High-wall Type (3 series)


Floor Standing Concealed Type

44
45

Floor Standing Cabinet Type

46

BI-flow Console Type

47

Floor Standing Type


AHU DX Connectivity Kit

48
49

Air to Air Heat Exchanger


Air to Air Heat Exchanger with DX-coil & Humidifier
Fresh Air Intake Indoor Unit Type

50
52
54

Mini-SMMS

56

Super Heat Recovery Multi System-i (SHRM-i)

58

SHRM-i Outdoor units lineup

60

Outdoor Units Specifications


Refrigerant piping design

61
65

Indoor Units Accessories

68

Remote Controller

70

Central Controller

72

Advance Controller systems

74

Open Network systems

76

Application Controls

78

SMMS-i selection Tools

83

Conversion Table

85

44

Advancing the eco-evolution


As relative newcomers in the evolution of the Earth, its undeniable that humankind has had a greater
impact on our planets eco-system than any other life form. All organisms to some extent affect change on
our global environment, but none quite as quickly and drastically as humans. Many scientists agree that
human activity has accelerated pollution and climatic changes beyond the natural evolutionary process.
Globally, levels of carbon dioxide and average regional temperatures rise at alarming rates, impacting
nature and civilization. And the quality of air we breathe continues to deteriorate in the cities we live in.
Whatever the causes, the message is clear: the future is up to us all, and we can do more to make things
better.
The core of Toshiba Air Conditionings philosophy is a profound respect for our global environment and the
passionate pursuit toward improving the quality of life for our customers worldwide.
As part of that global commitment, we develop cutting-edge technologies and advancements that serve
the benefit of people everywhere, by offering an ideal balance of comfort and ecologically superior
products.
We advance R&D in the field of super energy-efficient, cleaner technologies and innovative products that
not only use significantly less energy but help maintain air quality through state-of-the-art air purification
systems for the home and business.
We endeavour to lead by example by delivering the highest quality environmental systems that give added
value, and contribute responsibly to the advancement of humankind.
We call this vision, Advancing the eco-evolution.

Toshiba solutions
Toshiba offers a solution for all applications: residential, light
commercial and larger commercial buildings. Residential indoor units
are designed to blend perfectly with all interiors and incorporate
advanced filtration systems to deliver optimum indoor air quality. For
small commercial premises, products are designed to deliver top
performance combined with energy efficiency.
For larger applications, VRF systems combine flexibility, energy
efficiency and respect for the environment, with a wide choice of
stylish indoor units.

Absolute comfort
Toshibas commitment to society drives a company-wide focus on
attention to the details through every stage of the development
process, from design to user field tests. Installations using our
products and systems therefore feature a higher standard of indoor air
quality, sound levels, energy savings, and environmental awareness.

55

66

Innovation
The new SMMS-i offers innovations in
every savings with highly efficient
DC twin rotary compressors and
advanced vector-controlled inverters boasting COP of 6.41* at 50%
partial Load.

*8HP outdoor unit


Calculated based on JRA4048:2006 specification.

Intelligence
The intelligent VRF ensures precise
control over cooling on a room by
room basis, delivering consistent
temperature to even the furthest
room from the unit.

Imagination
With flexible layout variations
beyond imagination, this extremely
versatile system can accomodate up
to an impressive 235 metres in
length and maximum height of 40
metres between indoor units.

Industry leading energy savings


Energy-effient performance for greater eco-consciousness
Adopting the highly efficient new DC twin-rotary compressors and advanced vectorcontrolled inverters realizes a COP of 6.41 (under 50% partial load). Greater operating
performance is now possible when operating under a constant load.

6.41

4.52
COP
5.50
3.52

6.26
4.15
EER
5.60
3.28

DC Twin Rotary Compressor :


Toshiba has continuously improved its compressor technology, arriving at a solution called DC Twin Rotary
Compressor. It is a double cam rotary compressor which has several features which increases its performance
and reliability. The opposed double blade design yields mechanical stability and less vibration that could
cause stress on other components. In fact being able to reduce the rpm without causing instability enables
improved temperature control when less capacity is required. An added benefit offered by the DC Twin rotary
compressors, and with refrigerant R410a, is that it is more efficient than scroll compresors.

Twin Rotary Compressor Operation :


The compression ratio in the cylinder is variable
A change of the driving compression ratio of the outer
refrigerant cycle
The compression ratio in the cylinder accords with
driving compression ratio
Over compression and lack of compression are very
small in the cylindersmall in the cylinder
Thus resulting into Higher Efficiency.

New DC Twin-Rotary Compressor


Three new DC Twin-Rotary compressors that feature outstanding
capacity under partial load drive for 14HP and 16HP outdoor unit
models, while two are used by other outdoor unit models
( 8HP-12HP).

refrigerant cycle
The compression ratio in the cylinder accords with
driving compression ratio
Over compression and lack of compression are very
small in the cylindersmall in the cylinder

Thus resulting into Higher Efficiency.

New DC Twin-Rotary Compressor


Three new DC Twin-Rotary compressors that feature outstanding
capacity under partial load drive for 14HP and 16HP outdoor unit
models, while two are used by other outdoor unit models
( 8HP-12HP).

Industry
leading
energy
savings
Industry
leading
energy
savings
7

Introducing high-performance outdoor units


with 3 compressors and 3 inverters*1

(14HP, 16HP)

Improved Motor Efficiency : Surface area of the rotor magnet (magnetic material Neodymium, Iron
and Boron increased and the slits aded, resulting higher effiency.

Increase of magnetic flux densit

Newly Designed Compression Path : The optimization of discharge port positioning reduces
compression loss and dead volume, resulting into higher energy efficiency as well as comfort levels.

More Precise Components :

The Blade thickness is reduced.


The Back side are of blade is reduced.
Which reduces the pressing load and friction resistance and helps to achieve bettor motor efficiency and higher
product efficiency.

Fast-calculating vector-controlled inverter


control over operation to match the

Variable compression ratio


Toshiba twin rotary compressor have variable discharge pressure which minimising energy loss as compared
to other compression tecnology e.g in below figure, Toshiba compressor deliver the capacity at that level
where ever it is required.

0 degree opening

270 degree opening


(Rated condition)

90 degree opening
(Part load condition)

180 degree opening


(Part load condition)

Fast-calculating vector-controlled inverter


All-inverter control realizes finer control over
operation to match the load on the system
Toshiba SMMS-i leads the industry in controlling
*1
all 3 compressors with a dedicated inverter
board that taps the compressors full potential
to provide smoother operation.

*1 14,16HP models

Smooth sine curve

Circuit board

The fast calculating vector


controlled inverter produces a
smooth sine curve that improves
operating efficiency.

The vector controlled inverter


quickly converts current into a
smooth sine curve to achieve
smoother operation of the
compressors DC motor.

59

High-efficiency DC twin-rotary compressors


Every outdoor unit incorporates three new DC twin-rotary compressors* and three inverter drives this
is unique to Toshiba and the air conditioning industry.

Vector-controlled inverter
DC fan motor

Outdoor units are fitted with three DC twin-rotary compressors* (switch to all-inverter models)

* 14,16 HP Outdoor units

Reliability

Rotation between outdoor units

Compressor

Compressor

Compressor

Compressor

Compressor

As the compressors are all inverter driven, power surges


are eliminated. Over or under-utilisation of power,
typical for non-inverter compressors is eliminated, and
there is no on/off power surge as the system adjusts to
the demand required by the occupant or system. The use
of inverter compressors reduces the risk of compressor
failure, more common in standard non-inverter systems.

Compressor

Compressor

A (Header unit)

Compressor

With dual-rotation, the load is distributed more evenly


this means that the operating sequence of the outdoor
units and the individual compressors is rotated to spread
the operating hours more evenly.

Compressor

Sequencing of individual compressors

System with controlled


reliability and savings
Operate
Operate

Conventional
system

Operate

Stop

Energy savings
During operation the system determines which heat
exchanger can be used most efficiently and selects the
compressor to deliver the power required. Inverter
systems save energy as continuous operation offers the
same capacity with lower power consumption. This
benefits all occupants by maintaining even room
temperatures, as well as the environment by reducing
energy consumption.

ON

ON

Inverter
Fixed-speed
compressor compressor

OFF OFF
3

Fixed-speed Fixed-speed
compressor compressor

ON

OFF

ON

OFF

Inverter
Inverter
compressor compressor

Inverter
Inverter
compressor compressor

Using greater heat exchanger


volume is more efficient

Backup operation
Incase of 1 system, 1 compressor broken, SMMSi can
output 67% of capacity.

NO.1

NO.2

NO.3

heat exchangers

10

10

11

DC twin-rotary compressor advantage


Each SMMS-i uses twin-rotary inverter compressors that feature more stable energy efficiency through their
full range of compressor rotation than do scroll type compressors.
Scroll compressors can achieve high- efficiency operation, but only within in a narrow range.
As VRF systems require a wide range of capacity, the twin-rotary compressor is best suited for use.
Run Time Equalization for compressors : The SMMS-i systems operation combines a highly efficient
running speed and highly efficient compressors. The operating time of the compressors is equalized. Under
low-load conditions, there is the advantage of the system running at low capacity and yielding stable
operation even under low temperature conditions.
Inverter + Fixed Speed

All Inverter twin - rotary

Efficiency

Low efficiency in operation


with FIX compressors.

System operates in high efficient


compressor combination and rpm.

Reliability

Inverter compressor has to


run all the time. Limited
condition
in
compressor
backup operation.

System operates in high efficient


compressor combination and rpm.

Comfort

Output capacity fluctuation


by fixed compressor ON/OFF
operation.

Min. output can meet Min. capacity


indoor units demand Stable operation in low temperature condition.

Active Oil Management system : As a system, it has more than 1 compressor. This running compressor can
get oil and refrigerant from other compressor or modular quickly without any additional power
consumption.
Discharge

RUN
Comp.1

Oil Flow

Comp.2

Discharge

Oil from other two compressors


Oil Balance
circuit

Comp.3

Stop
Stop
Oil tank

64 steps for condenser fan : reduced noise level : By making it possible to control the fan inverter in 64
steps, all the compressors can be run at low speeds, and the overall level of noise from the outdoor units
is reduced approx by 10dB(A).

Outdoor
noise (dB)

Time (h/year)
300
250
200

55
Auto silent operation

50

150
45

100

40

50

35

0
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38

Outdoor temperature C

Approx.
10 dB (A)

10
12

5
Oversupplied

New intelligent VRF control


Differing pipe lengths result in
inconsistent performance levels
when several indoor units are
connected to a system. This
imbalance is caused by pressure
loss and thermal leaks that inhibit
the supply of the right amount of
refrigerant to each indoor unit.

Undersupplied
Without intelligent VRF control

Total system control and consistent


room-to-room temperature
Intelligent VRF control provides precise
control over each indoor unit. For example,
the upper floor indoor units of VRF systems
without intelligent of refrigerant, causing a
delay before indoor units on lower floors
would reach efficient operating levels.
Toshibas SMMS-i monitors the flow of
refrigerant to each indoor unit, while also
tracking the model of the indoor unit, the
pipe length between it and the outdoor unit,
as well as data on operating conditions. The
system computers the amount of refrigerant
required by each indoor unit and controls
the units pulse motor valve to ensure
optiomal supply across the system.
Can be adjusted to maintain
consistent temperature
With intelligent VRF control

12

11
13

Infinity variable control


Ultra-precise 0.1 Hz control over compressor rotation speed

Infinity variable control adjusts compressor rotation speed in near-seamless 0.1 Hz steps. Responding
precisely to the capacity needs of the moment, this fine control minimizes energy loss when changing
frequencies, and also creates a comfortable environment subject to minimal temperature variations.

d s
W orl in*
bestlass
its c

SMMS-i
Current-SMMS

New-SMMSi

Compressor Hz

0.1Hz

Capacit

*As of december 2009 (according to independent Toshiba testing)

Advanced I/F Technology : Microprocessor has been improved by


replacing conventional single MCU with dual MCU system consisting
of a main and a sub MCU, which significantly enhanced the capacity
of the interface PC board (I/F). The dual MCU system enables
high-speed operation by parallel processing and fast handling of a
wide variety of capacity requirements from each indoor unit.

High speed data transmission - Operated control data in I/F is


transmitted to four IPDUs at high speed so that excellent load
following capability with finer capacity control is provided in no
time.
Ultra Precise IPDU technology - The intelligent power The intelligent power drive unit (IPDU) receives
instructions from I/F and executes appropriate and precise control over all compressors and fans. RISC (a
reduced instruction set computer which adopts simplified instructions to provide high-speed
performance, for short, RISC) type 32bit CPU processor is introduced which enables amazing ultra precise
drive control of 0.1 Hz per one step and realize stable temperature environment.

12
14

Optimal refrigerant control


When a multiple number of indoor units are connected, an insuficient or excess amount of
refrigerant may be supplied to indoor units depending on the difference in length of the connection
pipe from the outdoor unit.
This is caused by pressure loss and heat leaks as the refrigerant travels through the pipes, resulting
in incorrect amounts of refrigerant being supplied to the indoor units.
Optimal refrigerant flow control featuring intelligent control over the refrigerant sensors and
opening rate of individual pulse motor valves realizes stable indoor temperatures throughout a
building with height differences of up to 40m between indoor units.

Outdoor unit

Pulse motor valve

Heat
exchanger
B

TC2 TCJ

Indoor unit

Refrigerant
sensor (In)

Capacity

The surplus represented by (B) is diminished and the deficiency represented by


(C) is compensated for.

TC1
Refrigerant
sensor (Out)

The surplus represented by (A) is diminished


and the deficiency represented by (D) is
compensated for.
Target capacity

(A)

(B)

(C)

(D)

14

13
15

Industry leading pipe length for greater flexibility


Layout flexibility with few design limitations

System layouts can use a maximum equivalent distance of up to 235 metres. This makes

System
layouts can use a maximumnyequivalent
distance of up to 235 metres. This makes it much
it much easier to design f
small rooms, or for tenants who often
easier
to
design
for
floors
with
many
small
rooms,
or for tenants who often rearrange their floor
rear
ayouts.
layouts.

175m

Current SMMS

coverage requires
two systems

60 m

Conventional VRF

Farthest equivalent length

235m

ds
Wortl in *
bes lass
its c

Main piping length

120 m

SMMS-i
coverage achieved
by a single system

1st branching piping length

90 m

*As of December 2009 (According to independent TOSHIBA testing)

1416
16

Greater support for height differences


Toshiba SMMS-i leads the industry with support for height
differences of up to 40 meters between indoor units on a single
system. For instance, in an 11-story building, this is enough height
to fully cover the entire floor as well as the elevator halls.

----------------------- -------11F

10F
9F
8F
Height between outdoor
& indoor units *2

70m

Height between
indoor units *1

40m

Single system

7F
6F
5F
4F
3F
2F

1F
----------------------

*1 Calculated at 3.5 meters per floor


*2 40 meters incase of Indoor unit above outdoor unit

Piping

A change from T-shape to Y-shape branching joints on the gas pipes


between SMMS-i outdoor units results in equalized flow to each
branch that enables more reliable operation.
To indoor units

Liquid piping
To indoor units
Gas piping
Modification point

Outdoor unit connection piping kit


(RBM-BT14E, RBM-BT24E)

1715

18

Other Features
Outdoor unit

Refrigerant flow
Gas refrigerant

Toshibas own PMV (pulse motor valve)


control prevents unneeded refrigerant
from flowing to indoor units that are not
operating at any given time. Benefits
include the prevention of by-pass loss and
finer control over the compressor
capacity of the outdoor unit.

Indoor unit

Heat exchanger

Max

Mid

Liquid
refrigerant

Mini

Stop

PMV
Temprerature sensor

Operating temperature range


SMMS-i extends the high end of its cooling
functions outdoor temperature operating
range up to 43C. This enables wider
applications and use of the system in hot
regions.

SMMS-i
Outdoor temp. range when cooling*

-5C to 43C

Outdoor temp. range when heating*

-20C to 15C

*Cooling: CDB, Heating: CWB

SMMS-i

-20C

-15C

0C

15C

Other features
519

16
18

Inverter box inspection window


The SMMS-i inverter box window enables
easier maintenance. The window opens
quickly to allow inspection of the PCB,
test run operations, repairs, and control
over address settings.

Square carrying holes


Square holes added to the lower corners
of the SMMS-i outdoor units facilitate
safer and surer lifting by a crane. Belts
passed through the dedicated corner
holes
maintain their position and the
balance of the load throughout the
lifting operation.

17
19
20

Outdoor units
Standard model

Capacity

5HP

6HP

8HP

10HP

M odel Name (M M Y-)

M AP0501HT8P-E

M AP0601HT8-PE

Cooling capacity (kW)

14.0

16.0

22.4

28.0

33.5

40.0

45.0

Heating capacity (kW)

16.0

18.0

25.0

31.5

37.5

45.0

50.0

14HP

M AP0804HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1404HT8P-E

Capacity

18HP

20HP

22HP

24HP

M odel Name (M MY-)

AP1814HT8P-E

AP2014HT8P-E

AP2214HT8P-E

AP2414HT8P-E

Units in combination
(M MY-)

12HP

26HP
AP2614HT8P-E

16HP
M AP1604HT8P-E

28HP

30HP

32HP

AP2814HT8P-E

AP3014HT8P-E

AP3214HT8P-E

M AP1004HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E


M AP0804HT8P-E M AP1004HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1404HT8P-E M AP1604HT8P-E

Cooling capacity (kW)

50.4

56.0

61.5

68.0

73.0

78.5

85.0

90.0

Heating capacity (kW)

56.5

63.0

69.0

76.5

81.5

88.0

95.0

100.0

Capacity

34HP

36HP

38HP

40HP

42HP

44HP

46HP

48HP

M odel Name (M MY-)

AP3414HT8P-E

AP3614HT8P-E

AP3814HT8P-E

AP4014HT8P-E

AP4214HT8P-E

AP4414HT8P-E

AP4614HT8P-E

Units in combination
(M MY-)

AP4814HT8P-E

M AP1204HT8P-E M AP1204HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E


M AP1204HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1404HT8P-E M AP1604HT8P-E M AP1604HT8P-E M AP1604HT8P-E
M AP1004HT8P-E M AP1204HT8P-E M AP1004HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1204HT8P-E M AP1404HT8P-E M AP1604HT8P-E

Cooling capacity (kW)

96.0

101.0

106.5

112.0

118.0

123.5

130.0

135.0

Heating capacity (kW)

108.0

113.0

119.5

127.0

132.0

138.0

145.0

150.0

* Power: 3-phase 50 Hz 400V (380 - 415V)


* The source voltage must not uctuate more than 10% .
* Rated conditions
Cooling: Indoor air temperature 27C DB/19C WB, outdoor air temperature 35C DB
Heating: Indoor air temperature 20C DB, outdoor air temperature 7C DB/6C WB

21

18
20

High efficiency model

Capacity

16HP

24HP

26HP

28HP

30HP

M odel Name (M MY-)

AP1624HT8P-E

AP2424HT8P-E

AP2624HT8P-E

AP2824HT8P-E

AP3024HT8P-E

Units in combination
(M MY-)

M AP0804HT8P-E
M AP0804HT8P-E

M AP0804HT8P-E
M AP0804HT8P-E
M AP0804HT8P-E

M AP1004HT8P-E
M AP0804HT8P-E
M AP0804HT8P-E

M AP1004HT8P-E
M AP1004HT8P-E
M AP0804HT8P-E

M AP1004HT8P-E
M AP1004HT8P-E
M AP1004HT8P-E

Cooling capacity (kW)

45.0

68.0

73.0

78.5

85.0

Heating capacity (kW)

50.0

76.5

81.5

88.0

95.0

Capacity

32HP

34HP

36HP

38HP

40HP

42HP

44HP

46HP

48HP

M odel Name (M MY-)

AP3224HT8P-E AP3424HT8P-E AP3624HT8P-E AP3824HT8P-E AP4024HT8P-E AP4224HT8P-E AP4424HT8P-E AP4624HT8P-E AP4824HT8P-E

Units in combination
(M MY-)

MAP0804HT8P-E
MAP0804HT8P-E
MAP0804HT8P-E
MAP0804HT8P-E

MAP1004HT8P-E
MAP0804HT8P-E
MAP0804HT8P-E
MAP0804HT8P-E

MAP1004HT8P-E
MAP1004HT8P-E
MAP0804HT8P-E
MAP0804HT8P-E

MAP1004HT8P-E
MAP1004HT8P-E
MAP1004HT8P-E
MAP0804HT8P-E

MAP1004HT8P-E
MAP1004HT8P-E
MAP1004HT8P-E
MAP1004HT8P-E

MAP1204HT8P-E
MAP1004HT8P-E
MAP1004HT8P-E
MAP1004HT8P-E

MAP1204HT8P-E
MAP1204HT8P-E
MAP1004HT8P-E
MAP1004HT8P-E

MAP1204HT8P-E
MAP1204HT8P-E
MAP1204HT8P-E
MAP1004HT8P-E

MAP1204HT8P-E
MAP1204HT8P-E
MAP1204HT8P-E
MAP1204HT8P-E

Cooling capacity (kW)

90.0

96.0

101.0

106.5

112.0

118.0

123.5

130.0

135.0

Heating capacity (kW)

100.0

108.0

113.0

119.5

127.0

132.0

138.0

145.0

150.0

Y-shape branching joint

Branch headers

Outdoor unit connection piping kit

Appearance

(4-branch headers)

M odel name

RBM-BY55E RBM-BY105E RBM-BY205E RBM-BY305E RBM-HY1043E RBM-HY2043E RBM-HY1083E RBM-HY2083E

Max.4 branches
Max.8 branches
Total 14.2
Total 6.4 or
Total below
or more Total 25.2
Total 14.2
more and
(Classi cation according to
6.4
and below or more Total below Total 14.2 or Total below or more
indoor unit capacity code )
below 14.2
more and
25.2
14.2
and below
14.2
below 25.2
25.2
Usage

RBM -BT14E

RBM -BT24E

Total below 26.0

Total 26.0 or more

19
21

22

Outdoor unit specications


Standard model (Single unit)

Technical specifications

Equivalent HP
Heat Pump
Cooling Only

5HP
6HP
8HP
10HP
12HP
14HP
16HP
(M MY-) MAP0501HT8P-E MAP0601HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1404HT8P-E MAP1604HT8P-E
M odel name
(M MY-) MAP0501T8P-E MAP0601T8P-E MAP0804T8P-E MAP1004T8P-E MAP1204T8P-E MAP1404T8P-E MAP1604T8P-E
Outdoor unit type
Inverter
Cooling capacity (* 1)
(kW)
14.0
16.0
22.4
28.0
33.5
40.0
45.0
Heating capacity (* 1)
(kW)
16.0
18.0
25.0
31.5
37.5
45.0
50.0
2
Power supply (* )
3phase 4wires 50Hz 400V (380-415V)
3.65
4.64
5.40
7.41
9.55
11.50
13.70
Power consumption
(kW)
Cooling
3.84
3.45
4.15
3.78
3.51
3.48
3.28
EER (Energy E ciency Ratio)
Electrical
characteristics
Power consumption
(kW)
3.84
4.56
5.53
7.50
10.20
11.20
14.20
Heating
1
(* )
4.17
3.95
4.52
4.20
3.68
4.02
3.52
COP (Coe cient of Performance)
External dimensions (Height /Width /Depth)
(mm) 1,800 /990 /750 1,800 /990 /750 1,830 /990 /780 1,830 /990 /780 1,830 /990 /780 1,830 /1,210 /780 1,830 /1,210 /780
228
228
242
242
242
330
330
Heat Pump
(kg)
Total weight
Cooling only
(kg)
227
227
241
241
241
329
329
Compressor
M otor output
(kW)
1.1 x 2
1.4 x 2
2.3 x 2
3.1 x 2
4.2 x 2
3.0 x 3
3.6 x 3
M otor output
(kW)
0.6
0.6
1.0
1.0
1.0
1.0
1.0
Fan unit
Air volume
(m3/h)
9,000
9,000
9,900
10,500
11,600
12,000
13,000
Gas side
(mm)
15.9
19.1
22.2
22.2
28.6
28.6
28.6
M ain
Refrigerant piping
pipe
Liquid side
(mm)
9.5
9.5
12.7
12.7
12.7
15.9
15.9
diameter Balance pipe
(mm)
9.5
9.5
9.5
9.5
9.5
9.5
9.5
Sound pressure level (Cooling/Heating)
(dB(A))
55 /55
56 /56
55 /56
57 /58
59 /62
60 /62
62 /64
Sound power level (Cooling/Heating)
(dB(A))

77 / 78
78 /79
82 /83
82 /83
83 /84

Standard model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

Outdoor unit type


Heat Pump
M MYOutdoor unit
model
Cooling Only
M MY1
Cooling capacity (* )
(kW)
(kW)
Heating capacity (* 1)
2
Power supply (* )
Power consumption
(kW)
Cooling
EER (Energy E ciency Ratio)
Electrical
1
characteristics (* )
Power consumption
(kW)
Heating
COP (Coe cient of Performance)
Heat Pump
(kg)
Total weight
Cooling only
(kg)
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
Air volume
(m3/h)
Gas side
(mm)
Refrigerant piping M ain pipe diameter Liquid side
(mm)
Balance pipe
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))

18HP
AP1814HT8P-E
AP1814T8P-E
MAP1004HT8P-E MAP0804HT8P-E
MAP1004T8P-E MAP0804T8P-E
50.4
56.5

242
241
3.1 x 2
1.0
10,500

12.81
3.93
13.03
4.34

242
241
2.3 x 2
1.0
9,900

28.6
15.9
9.5
59.5 /60.5

20HP
AP2014HT8P-E
AP2014T8P-E

22HP
AP2214HT8P-E
AP2214T8P-E

Inverter
MAP1004HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1004HT8P-E
MAP1004T8P-E MAP1004T8P-E MAP1204T8P-E
MAP1004T8P-E
56.0
61.5
63.0
69.0
3phase 4wires 50Hz 400V (380-415V)
14.82
16.96
3.78
3.63
15.00
17.70
4.20
3.90
242
242
242
242
241
241
241
241
3.1 x 2
3.1 x 2
4.2 x 2
3.1 x 2
1.0
1.0
1.0
1.0
10,500
10,500
11,600
10,500
28.6
34.9
15.9
19.1
9.5
9.5
60.0 /61.0
61.5 / 63.5

Standard model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

24HP
AP2414HT8P-E
AP2414T8P-E
MAP1204HT8P-E MAP1204HT8P-E
MAP1204T8P-E MAP1204T8P-E
68.0
76.5
19.66
3.46
21.13
3.62

242
242
241
241
4.2 x 2
4.2 x 2
1.0
1.0
11,600
11,600
34.9
19.1
9.5
62.0 /65.0

Technical specifications
M MYM MY-

Outdoor unit type


Heat Pump
M MYOutdoor unit
model
Cooling Only
M MYCooling capacity (* 1)
(kW)
(kW)
Heating capacity (* 1)
Power supply (* 2)
Power consumption
(kW)
Cooling
EER (Energy E ciency Ratio)
Electrical
characteristics (* 1)
Power consumption
(kW)
Heating
COP (Coe cient of Performance)
Heat Pump
(kg)
Total weight
Cooling only
(kg)
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
Air volume
(m3/h)
Gas side
(mm)
Refrigerant piping M ain pipe diameter Liquid side
(mm)
Balance pipe
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))

26HP
AP2614HT8P-E
AP2614T8P-E

28HP
AP2814HT8P-E
AP2814T8P-E
Inverter
MAP1604HT8P-E
MAP1004HT8P-E
MAP1604HT8P-E
MAP1204HT8P-E
MAP1604T8P-E
MAP1004T8P-E
MAP1604T8P-E
MAP1204T8P-E
73.0
78.5
81.5
88.0
3phase 4wires 50Hz 400V (380-415V)
21.11
23.25
3.46
3.38
21.70
24.65
3.76
3.57
330
242
330
242
329
241
329
241
3.6 x 3
3.1 x 2
3.6 x 3
4.2 x 2
1.0
1.0
1.0
1.0
13,000
11,500
13,000
11,600
34.9
34.9
19.1
19.1
9.5
9.5
63.5 /65.0
64 /66.5

30HP
AP3014HT8P-E
AP3014T8P-E
MAP1604HT8P-E MAP1404HT8P-E
MAP1604T8P-E
MAP1404T8P-E
85.0
95.0

330
329
3.6 x 3
1.0
13,000

25.20
3.37
25.40
3.74

34.9
19.1
9.5
64.5 /66.5

330
329
3.0 x 3
1.0
12,000

20
22

23

Standard model
M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

Outdoor unit type


Heat Pump
M MYOutdoor unit
model
Cooling Only
M MY1
Cooling capacity (* )
(kW)
1
Heating capacity (* )
(kW)
2
Power supply (* )
Power consumption
(kW)
Cooling
EER (Energy E ciency Ratio)
Electrical
1
characteristics (* )
Power consumption
(kW)
Heating
COP (Coe cient of Performance)
Heat Pump
(kg)
Total weight
Cooling only
(kg)
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
Air volume
(m3/h)
Gas side
(mm)
Refrigerant piping M ain pipe diameter Liquid side
(mm)
Balance pipe
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))

32HP
AP3214HT8P-E
AP3214T8P-E

34HP
36HP
AP3414HT8P-E
AP3614HT8P-E
AP3414T8P-E
AP3614T8P-E
Inverter
MAP1604HT8P-E
MAP1604HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E
MAP1604T8P-E
MAP1604T8P-E
MAP1204T8P-E
MAP1204T8P-E
MAP1004T8P-E MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E
90.0
96.0
101.0
100.0
108.0
113.0
3phase 4wires 50Hz 400V (380-415V)
27.40
27.06
28.93
3.28
3.55
3.49
28.40
28.60
30.84
3.52
3.78
3.66
330
330
242
242
242
242
242
242
329
329
241
241
241
241
241
241
3.6 x 3
3.6 x 3
4.2 x 2
4.2 x 2
3.1 x 2
4.2 x 2
4.2 x 2
4.2 x 2
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
13,000
13,000
11,600
11,600
10,500
11,600
11,600
11,600
34.9
34.9
41.3
19.1
19.1
22.2
9.5
9.5
9.5
65.0 /67.0
63.5 /66.0
64.0 /67.0

Standard model

Technical specifications

Equivalent HP
Heat Pump
Cooling Only

38HP
AP3814HT8P-E
AP3814T8P-E

40HP
42HP
AP4014HT8P-E
AP4214HT8P-E
M MYM odel name
M MYAP4014T8P-E
AP4214T8P-E
Outdoor unit type
Inverter
Heat Pump
M MY- MAP1604HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1604HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1604HT8P-E MAP1404HT8P-E MAP1204HT8P-E
Outdoor unit
model
Cooling Only
M MY- MAP1604T8P-E MAP1204T8P-E MAP1004T8P-E MAP1604T8P-E MAP1204T8P-E MAP1204T8P-E MAP1604T8P-E MAP1404T8P-E
MAP1204T8P-E
1
Cooling capacity (* )
(kW)
106.5
112.0
118.0
1
(kW)
119.5
127.0
132.0
Heating capacity (* )
3phase 4wires 50Hz 400V (380-415V)
Power supply (* 2)
Power consumption
(kW)
30.66
32.80
34.47
Cooling
EER (Energy E ciency Ratio)
3.47
3.41
3.42
Electrical
1
characteristics (* )
Power consumption
(kW)
32.14
35.29
35.46
Heating
COP (Coe cient of Performance)
3.72
3.60
3.72
Heat Pump
(kg)
330
242
242
330
242
242
330
330
242
Total weight
Cooling only
(kg)
329
241
241
329
241
241
329
329
241
Compressor
M otor output
(kW)
3.6 x 3
4.2 x 2
3.1 x 2
3.6 x 3
4.2 x 2
4.2 x 2
3.6 x 3
3.0 x 3
4.2 x 2
M otor output
(kW)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Fan unit
Air volume
(m3/h)
13,000
11,600
10,500
13,000
11,600
11,600
13,000
12,000
11,600
Gas side
(mm)
41.3
41.3
41.3
Refrigerant piping M ain pipe diameter Liquid side
(mm)
22.2
22.2
22.2
Balance pipe
(mm)
9.5
9.5
9.5
Sound pressure level (Cooling/Heating)
(dB(A))
65.0 /67.0
65.0 /67.5
65.5 /67.5

Standard model
M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

Outdoor unit type


Heat Pump
M MYOutdoor unit
model
Cooling Only
M MY1
Cooling capacity (* )
(kW)
1
(kW)
Heating capacity (* )
2
Power supply (* )
Power consumption
(kW)
Cooling
EER (Energy E ciency Ratio)
Electrical
1
characteristics (* )
Power consumption
(kW)
Heating
COP (Coe cient of Performance)
Heat Pump
(kg)
Total weight
Cooling only
(kg)
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
Air volume
(m3/h)
Gas side
(mm)
Refrigerant piping M ain pipe diameter Liquid side
(mm)
Balance pipe
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))

44HP
AP4414HT8P-E
AP4414T8P-E

46HP
AP4614HT8P-E
AP4614T8P-E
Inverter
MAP1604HT8P-E MAP1604HT8P-E MAP1204HT8P-E MAP1604HT8P-E MAP1604HT8P-E MAP1404HT8P-E MAP1604HT8P-E
MAP1604T8P-E MAP1604T8P-E MAP1204T8P-E MAP1604T8P-E MAP1604T8P-E MAP1404T8P-E MAP1604T8P-E
123.5
130.0
138.0
145.0
3phase 4wires 50Hz 400V (380-415V)
36.95
38.90
3.34
3.34
38.85
39.60
3.55
3.66
330
330
242
330
330
330
330
329
329
241
329
329
329
329
3.6 x 3
3.6 x 3
4.2 x 2
3.6 x 3
3.6 x 3
3.0 x 3
3.6 x 3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
13,000
13,000
11,600
13,000
13,000
12,000
13,000
41.3
41.3
22.2
22.2
9.5
9.5
66.0 /68.5
66.5 /68.5

*1 Rated conditions Cooling :Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating :Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB
The standard piping means that main pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0meter height.
*2 The source voltage must not ucture more than 10% .

48HP
AP4814HT8P-E
AP4814T8P-E
MAP1604HT8P-E
MAP1604T8P-E
135.0
150.0
41.10
3.28
42.60
3.52
330
329
3.6 x 3
1.0
13,000
41.3
22.2
9.5
67.0 /69.0

MAP1604HT8P-E
MAP1604T8P-E

330
329
3.6 x 3
1.0
13,000

21
23

24
High efciency model (Combination)
M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

Outdoor unit type


Heat Pump
M MYOutdoor unit
model
Cooling Only
M MY1
Cooling capacity (* )
(kW)
(kW)
Heating capacity (* 1)
Power supply (* 2)
Power consumption
(kW)
Cooling
EER (Energy E ciency Ratio)
Electrical
characteristics (* 1)
Power consumption
(kW)
Heating
COP (Coe cient of Performance)
Heat Pump
(kg)
Total weight
Cooling only
(kg)
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
Air volume
(m3/h)
Gas side
(mm)
Refrigerant piping M ain pipe diameter Liquid side
(mm)
Balance pipe
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))

16HP
AP1624HT8P-E
AP1624T8P-E

24HP
26HP
AP2424HT8P-E
AP2624HT8P-E
AP2424T8P-E
AP2624T8P-E
Inverter
M AP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E
MAP0804T8P-E
MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E
MAP0804T8P-E
MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E
45.0
68.0
73.0
50.0
76.5
81.5
3phase 4wires 50Hz 400V (380-415V)
10.89
16.58
18.31
4.13
4.10
3.99
11.06
17.18
18.56
4.52
4.45
4.39
242
242
242
242
242
242
242
242
241
241
241
241
241
241
241
241
2.3 x 2
2.3 x 2
2.3 x 2
2.3 x 2
2.3 x 2
3.1 x 2
2.3 x 2
2.3 x 2
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
9,900
9,900
9,900
9,900
9,900
10,500
9,900
9,900
28.6
34.9
34.9
15.9
19.1
19.1
9.5
9.5
9.5
58.0 /59.0
60.0 /61.0
60.5 /61.5

High efciency model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

Outdoor unit type


Heat Pump
M MYOutdoor unit
model
Cooling Only
M MY1
Cooling capacity (* )
(kW)
(kW)
Heating capacity (* 1)
2
Power supply (* )
Power consumption
(kW)
Cooling
EER (Energy E ciency Ratio)
Electrical
1
characteristics (* )
Power consumption
(kW)
Heating
COP (Coe cient of Performance)
Heat Pump
(kg)
Total weight
Cooling only
(kg)
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
Air volume
(m3/h)
Gas side
(mm)
Refrigerant piping M ain pipe diameter Liquid side
(mm)
Balance pipe
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))

28HP
AP2824HT8P-E
AP2824T8P-E

30HP
32HP
AP3024HT8P-E
AP3224HT8P-E
AP3024T8P-E
AP3224T8P-E
Inverter
MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E
MAP1004T8P-E
MAP1004T8P-E MAP0804T8P-E MAP1004T8P-E MAP1004T8P-E
MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E
78.5
85.0
90.0
88.0
95.0
100.0
3phase 4wires 50Hz 400V (380-415V)
20.27
22.75
21.79
3.87
3.74
4.13
20.53
22.71
22.12
4.29
4.18
4.52
242
242
242
242
242
242
242
242
242
241
241
241
241
241
241
241
241
241
3.1 x 2
3.1 x 2
2.3 x 2
3.1 x 2
3.1 x 2
3.1 x 2
2.3 x 2 2.3 x 2 2.3 x 2
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
10,500
10,500
9,900
10,500
10,500
10,500
9,900
9,900
9,900
34.9
34.9
34.9
19.1
19.1
19.1
9.5
9.5
9.5
61.5 /62.5
62.0 / 63.0
61.0 /62.0

High efciency model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

MAP0804HT8P-E
MAP0804T8P-E

242
241
2.3 x 2
1.0
9,900

Technical specifications
M MYM MY-

34HP
AP3424HT8P-E
AP3424T8P-E

36HP
AP3624HT8P-E
AP3624T8P-E

Outdoor unit type


Inverter
Heat Pump
M MY- MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP0804HT8P-E
Outdoor unit
model
Cooling Only
M MY- MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E MAP0804T8P-E MAP1004T8P-E MAP1004T8P-E MAP0804T8P-E MAP0804T8P-E
Cooling capacity (* 1)
(kW)
96.0
101.0
1
(kW)
108.0
113.0
Heating capacity (* )
2
3phase 4wires 50Hz 400V (380-415V)
Power supply (* )
Power consumption
(kW)
24.00
25.72
Cooling
EER (Energy E ciency Ratio)
4.00
3.93
Electrical
1
characteristics (* )
Power consumption
(kW)
24.70
26.06
Heating
COP (Coe cient of Performance)
4.37
4.34
Heat Pump
(kg)
242
242
242
242
242
242
242
242
Total weight
Cooling only
(kg)
241
241
241
241
241
241
241
241
Compressor
M otor output
(kW)
3.1 x 2
2.3 x 2
2.3 x 2
2.3 x 2
3.1 x 2
3.1 x 2
2.3 x 2
2.3 x 2
M otor output
(kW)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Fan unit
Air volume
(m3/h)
10,500
9,900
9,900
9,900
10,500
10,500
9,900
9,900
Gas side
(mm)
34.9
41.3
Refrigerant piping M ain pipe diameter Liquid side
(mm)
19.1
22.2
Balance pipe
(mm)
9.5
9.5
Sound pressure level (Cooling/Heating)
(dB(A))
62.0 / 63.0
62.5 /63.5

22
24

25

High efciency model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

38HP
AP3824HT8P-E
AP3824T8P-E

40HP
AP4024HT8P-E
AP4024T8P-E

Outdoor unit type


Inverter
Heat Pump
M MY- MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP0804HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E
Outdoor unit
model
Cooling Only
M MY- MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP0804T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E
Cooling capacity (* 1)
(kW)
106.5
112.0
(kW)
119.5
127.0
Heating capacity (* 1)
3phase 4wires 50Hz 400V (380-415V)
Power supply (* 2)
Power consumption
(kW)
27.68
29.64
Cooling
EER (Energy E ciency Ratio)
3.85
3.78
Electrical
characteristics (* 1)
Power consumption
(kW)
28.03
30.42
Heating
COP (Coe cient of Performance)
4.26
4.17
Heat Pump
(kg)
242
242
242
242
242
242
242
242
Total weight
Cooling only
(kg)
241
241
241
241
241
241
241
241
Compressor
M otor output
(kW)
3.1 x 2
3.1 x 2
3.1 x 2
2.3 x 2
3.1 x 2
3.1 x 2
3.1 x 2
3.1 x 2
M otor output
(kW)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Fan unit
10,500
10,500
10,500
9,900
10,500
10,500
10,500
10,500
Air volume
(m3/h)
Gas side
(mm)
41.3
41.3
Refrigerant piping M ain pipe diameter Liquid side
(mm)
22.2
22.2
Balance pipe
(mm)
9.5
9.5
(dB(A))
63.0 /64.0
63.0 /64.0
Sound pressure level (Cooling/Heating)

High efciency model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
M MYM MY-

42HP
AP4224HT8P-E
AP4224T8P-E

M MYM MY-

46HP
AP4624HT8P-E
AP4624T8P-E

44HP
AP4424HT8P-E
AP4424T8P-E

Outdoor unit type


Inverter
Heat Pump
M MY- MAP1204HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1004HT8P-E
Outdoor unit
model
Cooling Only
M MY- MAP1204T8P-E MAP1004T8P-E MAP1004T8P-E MAP1004T8P-E MAP1204T8P-E MAP1204T8P-E MAP1004T8P-E MAP1004T8P-E
Cooling capacity (* 1)
(kW)
118.0
123.5
(kW)
132.0
138.0
Heating capacity (* 1)
3phase 4wires 50Hz 400V (380-415V)
Power supply (* 2)
Power consumption
(kW)
32.04
34.19
Cooling
EER (Energy E ciency Ratio)
3.68
3.61
Electrical
characteristics (* 1)
Power consumption
(kW)
32.70
35.40
Heating
COP (Coe cient of Performance)
4.04
3.90
Heat Pump
(kg)
242
242
242
242
242
242
242
242
Total weight
Cooling only
(kg)
241
241
241
241
241
241
241
241
Compressor
M otor output
(kW)
4.2 x 2
3.1 x 2
3.1 x 2
3.1 x 2
4.2 x 2
4.2 x 2
3.1 x 2
3.1 x 2
M otor output
(kW)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Fan unit
Air volume
(m3/h)
11,600
10,500
10,500
10,500
11,600
11,600
10,500
10,500
Gas side
(mm)
41.3
41.3
Refrigerant piping M ain pipe diameter Liquid side
(mm)
22.2
22.2
Balance pipe
(mm)
9.5
9.5
Sound pressure level (Cooling/Heating)
(dB(A))
64.0 /65.5
64.5 /66.5

High efciency model (Combination)


M odel name

Equivalent HP
Heat Pump
Cooling Only

Technical specifications
48HP
AP4824HT8P-E
AP4824T8P-E

Outdoor unit type


Inverter
Heat Pump
M MY- MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1004HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E MAP1204HT8P-E
Outdoor unit
model
Cooling Only
M MY- MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E MAP1004T8P-E MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E MAP1204T8P-E
Cooling capacity (* 1)
(kW)
130.0
135.0
1
Heating capacity (* )
(kW)
145.0
150.0
2
3phase 4wires 50Hz 400V (380-415V)
Power supply (* )
Power consumption
(kW)
36.88
38.76
Cooling
EER (Energy E ciency Ratio)
3.52
3.48
Electrical
1
characteristics (* )
Power consumption
(kW)
38.57
40.80
Heating
COP (Coe cient of Performance)
3.76
3.68
Heat Pump
(kg)
242
242
242
242
242
242
242
242
Total weight
Cooling only
(kg)
241
241
241
241
241
241
241
241
Compressor
M otor output
(kW)
4.2 x 2
4.2 x 2
4.2 x 2
3.1 x 2
4.2 x 2
4.2 x 2
4.2 x 2
4.2 x 2
M otor output
(kW)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Fan unit
Air volume
(m3/h)
11,600
11,600
11,600
10,500
11,600
11,600
11,600
11,600
Gas side
(mm)
41.3
41.3
Refrigerant piping M ain pipe diameter Liquid side
(mm)
22.2
22.2
Balance pipe
(mm)
9.5
9.5
Sound pressure level (Cooling/Heating)
(dB(A))
65.0 /67.5
65.0 /68.0

*1 Rated conditions Cooling :Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating :Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB
The standard piping means that main pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0meter height.
*2 The source voltage must not ucture more than 10% .

23
25

26
Model : MMY-MAP0501, MAP0601 (SMMS)
Mounting surface of bottom plate

990

755
(Anchor bolt pitch)

630
80

610

4-15x20
(Long hole)

100

700
(Anchor bolt hole pitch)

Foundation

80

100

B
9.5
9.5

790
(Including steady leg)

A
15.9
15.9

750
755
(Anchor bolt pitch)

Applied model
MMY-MAP0501
MMY-MAP0601

Foundation

165

700
(Anchor bolt hole pitch)

1800

1640

280

Refrigerant pipe
connecting port
(Gas side) A

280

88

*1
241

700

Refrigerant pipe
connecting port
(Liquid side)B

Balance pipe
connecting port

2-60x150 square hole


(for freight handling)

500

9.5

*1 Cutting position of L-shape pipe


when pipe at gas side is connected
(Recommended pipe connecting position)

(Note)
1. If there is an obstacle at the upper side of the outdoor unit,
set the top end of the outdoor unit 2000mm apart from the obstacle.
2. Limit the height of the obstacle surrounding the outdoor unit to
800mm or less from the bottom end of the outdoor unit.
3. Draw out the pipe procured locally to the front of the outdoor unit
horizontally and keep 500mm or more between the outdoor unit
and traversing pipe if placing pipe transversely.

(Unit: mm)

Model: MMY-MAP0804, MAP1004, MAP1204

100

Foundation

50

700
(Anchor bolt hole pitch)

Foundation

755
(Anchor bolt pitch)

60
670

100
610

4-15x20
(Long hole)

990

60

700

(Anchor bolt hole pitch)

790
(Including steady leg)

755
(Anchor bolt pitch)

C
1,830
1,800

780

Mounting surface of bottom plate

B
12.7
12.7
12.7

1595

(75)*1

2-60x200 square hole


(for freight handling
)

500
Balance pipe
connecting port
9.5

(220)*1

273
284

687

Applied model
MMY-MAP -E
Other models

A
22.2
22.2
28.6

Applied model
MMY-MAP0804
MMY-MAP1004
MMY-MAP1204

L-shape pipe
Refrigerant pipe connecting port
(Gas side)A
Refrigerant pipe connecting port
(Liquid side) B

(Note)
1. If there is an obstacle at the upper side of the outdoor unit,
*1 Recommended cutting
set the top end of the outdoor unit 2000mm apart from the obstacle. position of L-shape pipe
2. Limit the height of the obstacle surrounding the outdoor unit to
800mm or less from the bottom end of the outdoor unit.
3. Draw out the pipe procured locally to the front of the outdoor unit
horizontally and keep 500mm or more between the outdoor unit
and traversing pipe if placing pipe transversely.

(Unit: mm)

24

275

26

Model: MMY-MAP1404, MAP1604

100

1210

Foundation

1595

50

920
(Anchor bolt hole pitch)

Foundation

755
(Anchor bolt pitch)

60
670

610

920 (Anchor bolt hole pitch)

60

4-15x20 (Long hole)

780
790
(Including steady leg)

755
(Anchor bolt pitch)

C
1,830
1,800

100

Mounting surface of bottom plate

B
15.9
15.9

2-60x200 square hole


(for freight handling)

620
Balance pipe
connecting port
9.5

284

(220)*1

221

687

(75)*1

85

Applied model
MMY-MAP -E
Other models

A
28.6
28.6

Applied model
MMY-MAP1404
MMY-MAP1604

L-shape pipe
Refrigerant pipe connecting port
(Gas side) 28.6
Refrigerant pipe connecting port

(Liquid side) 15.9


(Note)
1. If there is an obstacle at the upper side of the outdoor unit,
set the top end of the outdoor unit 2000mm apart from the obstacle.
*1 Recommended cutting
2. Limit the height of the obstacle surrounding the outdoor unit to
position of L-shape pipe
800mm or less from the bottom end of the outdoor unit.
3. Draw out the pipe procured locally to the front of the outdoor unit
horizontally and keep 500mm or more between the outdoor unit
and traversing pipe if placing pipe transversely.

(Unit: mm)

27 29

VRF Indoor Units Range


Type

4-way air discharge


cassette type

Compact 4-way
cassette (600 x 600)
type

2-way air discharge


cassette type

1-way air discharge


cassette type

Concealed duct type

Concealed duct
high static pressure
type

Slim duct type

Ceiling type - 7 series

Model Name

Equivalent
HP

Cooling
Heating
capacity (kW) capacity (kW)

MMU-AP0094HP-E
MMU-AP0124HP-E
MMU-AP0154HP-E
MMU-AP0184HP-E
MMU-AP0244HP-E
MMU-AP0274HP-E
MMU-AP0304HP-E
MMU-AP0364HP-E
MMU-AP0484HP-E
MMU-AP0564HP-E

1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00

2.80
3.60
4.50
5.60
7.10
8.00
9.00
11.20
14.00
16.00

3.20
4.00
5.00
6.30
8.00
9.00
10.00
12.50
16.00
18.00

MMU-AP0074MH-E
MMU-AP0094MH-E
MMU-AP0124MH-E
MMU-AP0154MH-E
MMU-AP0184MH-E

0.80
1.00
1.25
1.70
2.00

2.20
2.80
3.60
4.50
5.60

2.50
3.20
4.00
5.00
6.30

MMU- AP0072WH
MMU-AP0092WH
MMU-AP0122WH
MMU-AP0152WH
MMU-AP0182WH
MMU-AP0242WH
MMU-AP0272WH
MMU-AP0302WH
MMU-AP0362WH
MMU-AP0482WH
MMU-AP0562WH

0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00

2.20
2.80
3.60
4.50
5.60
7.10
8.00
9.00
11.20
14.00
16.00

2.50
3.20
4.00
5.00
6.30
8.00
9.00
10.00
12.50
16.00
18.00

MMU-AP0074YH-E
MMU-AP0094YH-E
MMU-AP0124YH-E

0.80
1.00
1.25

2.20
2.80
3.60

2.50
3.20
4.00

MMU-AP0154SH-E
MMU-AP0184SH-E
MMU-AP0244SH-E

1.70
2.00
1.25

4.50
5.60
7.10

5.00
6.30
8.00

Air-to-Air Heat
Exchangers

MMD-AP0076BHP-E
MMD-AP0096BHP-E
MMD-AP0126BHP-E
MMD-AP0156BHP-E
MMD-AP0186BHP-E
MMD-AP0246BHP-E
MMD-AP0276BHP-E
MMD-AP0306BHP-E
MMD-AP0366BHP-E
MMD-AP0486BHP-E
MMD-AP0566BHP-E

0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00

2.20
2.80
3.60
4.50
5.60
7.10
8.00
9.00
11.20
14.00
16.00

2.50
3.20
4.00
5.00
6.30
8.00
9.00
10.00
12.50
16.00
18.00

Air-to-Air Heat
Exchangers with
DX-coil + Humidifier

MMD-AP0184H-E
MMD-AP0244H-E
MMD-AP0274H-E
MMD-AP0364H-E
MMD-AP0484H-E
MMD-AP0724H-E
MMD-AP0964H-E

2.00
2.50
3.00
4.00
5.00
8.00
1.000

5.60
7.10
8.00
11.20
14.00
22.40
28.00

6.30
8.00
9.00
12.50
16.00
25.00
31.50

MMD-AP0054SPH-E
MMD-AP0074SPH-E
MMD-AP0094SPH-E
MMD-AP0124SPH-E
MMD-AP0154SPH-E
MMD-AP0184SPH-E
MMD-AP0244SPH-E
MMD-AP0274SPH-E

0.6
0.80
1.00
1.25
1.70
2.00
2.50
3.00

2.20
2.20
2.80
3.60
4.50
5.60
7.10
8.00

2.50
2.50
3.20
4.00
5.00
6.30
8.00
9.00

MMC-AP0157HP-E
MMC-AP0187HP-E
MMC-AP0247HP-E
MMC-AP0277HP-E
MMC-AP0367HP-E
MMC-AP0487HP-E
MMC-AP0567HP-E

1.70
2.00
2.50
3.00
4.00
5.00
6.00

4.50
5.60
7.10
8.00
11.20
14.00
16.00

5.00
6.30
8.00
9.00
12.50
16.00
18.00

Model Name

Equivalent
HP

MMK-AP0073H
MMK-AP0093H
MMK-AP0123H
MMK-AP0153H
MMK-AP0183H
MMK-AP0243H

0.80
1.00
1.25
1.70
2.00
2.50

2.20
2.80
3.60
4.50
5.60
7.10

2.50
3.20
4.00
5.00
6.30
8.00

MML-AP0074H-E
MML-AP0094H-E
MML-AP0124H-E
MML-AP0154H-E
MML-AP0184H-E
MML-AP0244H-E

0.80
1.00
1.25
1.70
2.00
2.50

2.20
2.80
3.60
4.50
5.60
7.10

2.50
3.20
4.00
5.00
6.30
8.00

Bi Flow Console type

MML-AP0074NH-E
MML-AP0094NH-E
MML-AP0124NH-E
MML-AP0154NH-E
MML-AP0184NH-E

0.80
1.00
1.25
1.70
2.00

2.20
2.80
3.60
4.50
5.60

2.50
3.20
4.00
5.00
6.30

Floor standing
concealed type

MML-AP0074BH-E
MML-AP0094BH-E
MML-AP0124BH-E
MML-AP0154BH-E
MML-AP0184BH-E
MML-AP0244BH-E

0.80
1.00
1.25
1.70
2.00
2.50

2.20
2.80
3.60
4.50
5.60
7.10

2.50
3.20
4.00
5.00
6.30
8.00

Floor standing type

MMF-AP0154H-E
MMF-AP0184H-E
MMF-AP0244H-E
MMF-AP0274H-E
MMF-AP0364H-E
MMF-AP0484H-E
MMF-AP0564H-E

1.70
2.00
2.50
3.00
4.00
5.00
6.00

4.50
5.60
7.10
8.00
11.20
14.00
16.00

5.00
6.30
8.00
9.00
12.50
16.00
18.00

Type

High wall type 3 series

Floor standing
cabinet type

VN-M150HE
VN-M250HE
VN-M350HE
VN-M500HE
VN-M650HE
VN-M800HE
VN-M1000HE
VN-M1500HE
VN-M2000HE

Air Flow in CMH


150
250
350
500
650
800
1000
1500
2000

MMD-VN(K)502HEXE
MMD-VN(K)802HEXE
MMD-VN(K)1002HEXE

Air Flow in CMH


500
800
950

New AHU DX
Coil Interface

MM-DXC010
MM-DXC012

AHU DX Valve
Kit

MM-DXV080
MM-DXV140
MM-DXV280

Fresh air intake


indoor unit type

Cooling
Heating
capacity (kW) capacity (kW)

MMD-AP0481HFE
MMD-AP0721HFE
MMD-AP0961HFE

5.00
8.00
10.00

14.20
22.40
28.00

8.90
13.90
17.40

30
28

4-way Air Discharge Cassette Type


Individual louver control
The angles of each of the four louver can be set individually
* Enables airflow to be adapted to user preferences.
Condensate drain pump included.
(1) Standard swing

(2) Diagonally
opposite swing

(3) Turn-around
swing

Easy installation

MMU-AP*** 4HP

The panel is attached using the bolt already installed on the


indoor unit.

REMOTE CONTROLS

RBC-U31PGP(W)-E
RBC-AX32U(W)-E
RBC-AX32U(WS)-E

RBC-AMS41E

RBC-AMS51E

Technical specifications
Model name

MMU

Cooling/Heating capacity*1

(kW)

Electrical
characteristics

3.6/4.0

External
dimensions:
Width
Main unit
(Ceiling panel)*
Depth

Total weight: Main unit (Ceiling panel)*


Standard air flow
(High/Mid/Low)
Motor output
Gas side

0.021/0.021

5.6/6.3

0.023/0.023 0.026/0.026

Model

7.1/8.0

8.0/9.0

9.0/10.0

11.2/12.5

14.0/16.0

16.0/18.0

0.036/0.036

319 (30)*

256 (30)*

(mm)

840 (950)*

(mm)

840 (950)*

(kg)

18 (4)*

(m3/h)

800/730/680

(W)
(mm)
(mm)

Drain port

(nominal
dia.)
(dB(A))

0.043/0.043 0.088/0.088 0.112/0.112 0.112/0.112

RBC-U31PGP(W)-E/RBC-U31PGSP(W)-E*/RBC-U31PGSP(WS)-E* (Thailand)

(mm)

Liquid side

Sound pressure level*2 (High/Mid/Low)

4.5/5.0

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power consumption
50 Hz/60 Hz (kW)

Height

Connecting
pipe

2.8/3.2

Power requirements

Appearance (Ceiling panel)

Fan unit

AP0094HP-E AP0124HP-E AP0154HP-E AP0184HP-E AP0244HP-E AP0274HP-E AP0304HP-E AP0364HP-E AP0484HP-E AP0564HP-E

25 (4)*

20 (4)*
930/830/790 1050/920/800

1290/920/800

14
9.5

1320/1110/850 1970/1430/1070 2130/1430/1130 2130/1520/1230

20

68

12.7

72

15.9

6.4

9.5
25 (Polyvinyl chloride tube)

30/29/27

31/29/27

32/29/27

35/31/28

38/33/30

* Preliminary *Figures in parentheses are for ceiling panels.


*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

43/38/32

46/38/33

46/40/33

29

MMU-AP0094HP to MMU-AP0564HP
Wireless sensor mounting section
(RBC-AX31U can be connected four corners)

323

269

Knockout for
fresh air intake 100
416.5

45
690 20 Hanging bolt pitch

860 to 910 ceiling open dimension


For branch duct knockout square
hole 150 (Also located on the back)

Bottom face
of ceiling

129

16.5

Drain pipe
connecting port

Ceiling panel (Sold separately)

41.5

105

106.5
Refrigerant pipe
connecting port
(Liquid side)

157
397.5

112

189

337.5

Refrigerant pipe
connecting port
(Gas side)

72

263

*(319)
256

*(137)

351

77 105 74

35

105

101 120
30

Stand-up 850 or less

Stand-up
661 or less

*(183)

300 or less

384

163.5
256.5

223.5

132

480

196.5

Hanging bolt M10 or


W3/8 procured locally

172

950 Panel external dimension

*( ): AP0364 to AP0564

Check port
(
450)

44

Z
Z View

200

860 to 910 ceiling open dimension

64

15
5

Bottom face
of ceiling

950 Panel external dimension

57

18
7

.5
28

32

780 Hanging bolt pitch

61

Air outlet 518

Electric parts box

408

30

Wiring connection port

For branch duct knockout


square hole 150

Bottom face of ceiling


Drain standing-up size

*The figure shows the RBC-U31PG(W)-E panel

(Unit: mm)

Options
Air discharge direction kit

Auxiliary fresh air flange


TCB-FF101URE2

Fresh air filter chamber


TCB-BC1602UE

TCB-GFC1602E

Fresh air inlet box


TCB-GB1602UE2

Ceiling panel
RBC-U31PG(W)-E
RBC-U31PGS(W)-E*
RBC-U31PGS(WS)-E*

Spacer for height adjustment


TCB-SP1602UE

Air inlet grill

32
30

Compact 4-way Cassette (600 x 600) Type


Perfect for grid system ceiling

Designed for simple & easy


installation and maintenance

This compact unit (575 575


mm) fits perfectly into
ceilings and matches standard
architectural modules, without the need to cut ceiling
tiles.

The slim design is only 268 mm in


height even when an electrical box
is located inside the unit.
Easy installation is also possible
using the panel adjust pocket. Use
the adjust pocket function for
fine adjustments after installation.

The flaps fold tightly against


the ceiling when operation
stops so that the ceiling is
affected only slightly even if
air conditioning is installed.

MMU-AP***4MH-E

Available for ceilings up to 3.5 m in


height.

Condensate drain pump


included.

The drain-checking hole makes it


possible to check the drain pan
through the side case.

RBC-UM11PG(W)E
3.5m

Drain-checking hole
TCB-AX32E2

RBC-AMS41E

Maximum height

RBC-AMS51E

Technical specifications
Model name

MMU

AP0074MH-E

AP0094MH-E

AP0124MH-E

AP0154MH-E

AP0184MH-E

Cooling/Heating capacity*1

(kW)

2.2/2.5

2.8/3.2

3.6/4.0

4.5/5.0

5.6/6.3

Electrical
characteristics

Power consumption
50 Hz/60 Hz (kW)

Appearance (Ceiling panel)


Height

External
dimensions:
Width
Main unit
(Ceiling panel)*
Depth

Total weight: Main unit (Ceiling panel)*


Fan unit

Standard air flow


(High/Mid/Low)
Motor output
Gas side

Connecting
pipe

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

0.034/0.034

0.036/0.036

0.038/0.038

Model

RBC-UM11PG(W)-E

(mm)

268 (27)*

(mm)

575 (700)*

(mm)

575(700)*

552/462/378

570/468/378

(W)

594/504/402

762/642/522

9.5

12.7

(mm)

6.4

Drain port

(nominal
dia.)

25 (Polyvinyl chloride tube)

(dB(A))

660/552/468

60

(mm)

Liquid side

Sound pressure level*2 (High/Mid/Low)

0.052/0.052

17 (3)*

(kg)
(m3/h)

0.041/0.041

36/32/28

37/33/28

37/33/29

*Figures in parentheses are for ceiling panels.


*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

40/35/30

44/39/34

33
31

MMU-AP0074MH-E to MMU-AP0184MH-E

235
235

207
207

575
575

Ceilingopen
open dimension
dimension 595
Ceiling
595toto660
660

Indoor

Indoor
unit
unit

Bottom
of ceiling
Bottomface
face
of ceiling

Ceiling open
595595
to 660
Ceiling
opendimension
dimension
to 660
Panelexternal
external dimension
700700
Panel
dimension
Hanging bolt
or W3/8
procured
locallylocally
Hanging
boltM10
M10
or W3/8
procured

For
ductknockout
knockout
Forbranch
branch duct
square
150
square hole
hole 150

158
158

120
120
142
142

268
268

63
63
21
21

Bottom
of of
ceiling
Bottomface
face
ceiling
27
27

Wiring
port
Wiringconnection
connecting port

Drain pipe
pipe connecting
port
Drain
connecting
port

20.5
220.5

256
256
162
162

145.5
145.5

105
105
148
148

134
134

215
214
42
42

55
55

97.5
97.5
93 105
105 70
70
93

300
300

Ceilingopen
open dimension
dimension 595
Ceiling
595toto660
660

Hanging bolt
525
Hanging
boltpitch
pitch
525

Refrigerant pipe
Refrigerant
pipe
connecting port
connecting
port
(Liquid side)
(Liquid
side)

190.5
190.5

Checkport
port
Check
(( 450)
450)

64 142
142
64

177
177

Refrigerant
pipe
Refrigerant pipe
connecting port
connecting
port
(Gas side)
(Gas
side)

139.5
139.5

175
175
149
149

64
64

29
29

368.5
368.5

320.5
320.5

575
575

Hanging bolt
pitch
525 525
Hanging
bolt
pitch

Electric
boxbox
Electricparts
parts

Panel external
700 700
Panel
externaldimension
dimension

Bottom
of of
ceiling
Bottomface
face
ceiling

Ceiling open
595595
to 660
Ceiling
opendimension
dimension
to 660

Knockout for fresh


airintake
intake 100
100
air

Stand-up
Stand-up
629.5
629.5 or
or less
less

105
105

235
235

Stand-up 850
less
Stand-up
850oror
less

162
162

200
200

For
ductknockout
knockout
For branch
branch duct
square hole
square
hole150
150

145.5
145.5

70
105 93
93
70 105

Bottom
of ceiling
Bottomface
face
of ceiling

Ceiling panel
(sold separately)
Ceiling
panel(sold
separately)

(Unit:(Unit:
mm) mm)

Options

Auxiliary fresh air flange


TCB-FF101URE2

Ceiling panel
RBC-UM11PG(W)E

34
32

2-way Air Discharge Cassette Type


Slim and compact unit

Unified the width of ceiling panels, 680mm.


Available for ceilings up to 3.8m in height. (in case of 0.8HP to 3.2HP)
Easy installation and fine adjustment using the Adjust-Cover function.
Condensate drain pump included.

MMU-AP***2WH

REMOTE CONTROLS

RBC-AX23UW(W)-E

RBC-AMS41E

RBC-AMS51E

Technical specifications
Model name

MMU

Cooling/Heating capacity*1

(kW)

Electrical
characteristics

2.2/2.5

3.6/4.0

2.8/3.2

(kW)

0.029/0.029

Model

RBC-UW283PG(W)-E

Height
External
dimensions:
Width
Main unit
(Ceiling panel)*
Depth

(mm)

295 (20)

(mm)

815 (1050)

Fan unit

Standard air flow


(High/Mid/Low)
Motor output
Gas side

Connecting
pipe

7.1/8.0

8.0/9.0

9.0/10.0

11.2/12.5

14.0/16.0

16.0/18.0

(mm)

Drain port

(nominal
dia.)
(dB(A))

RBC-UW1403
345 (20)

1180 (1415)

19 (10)

1600 (1835)

20

30

9.5

36 (14)

26 (14)
600/534/450 900/750/618

558/498/450

(W)
(mm)

0.064/0.064 0.076/0.076 0.088/0.088 0.117/0.117

570 (680)

(kg)
(m3/h)

0.054/0.054
RBC-UW803PG(W)-E

(mm)

Liquid side

Sound pressure level*2 (High/Mid/Low)

5.6/6.3

0.030/0.030 0.044/0.044

Appearance (Ceiling panel)

Total weight: Main unit (Ceiling panel)*

4.5/5.0

1-phase 50Hz 230V (220-240V)/1-phase 60Hz 220V (Separate power supply for indoor units required)

Power requirements
Power consumption
50 Hz/60 Hz

AP0072WH AP0092WH AP0122WH AP0152WH AP0182WH AP0242WH AP0272WH AP0302WH AP0362WH AP0482WH AP0562WH

1050/840/738

1260/900/780 1740/1434/1182 1800/1482/1230 2040/1578/1320

40

50

12.7

70
15.9

6.4

9.5
25 (Polyvinyl chloride tube)

34/32/30

35/33/30

38/35/33

*Figures in parentheses are for ceiling panels.


*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

40/37/34

42/39/36

43/40/37

46/42/39

33

MMU-AP0072WH to AP0152WH
Hanging bolt 4-M10
procured locally

Adjust cover

Wireless sensor mounting section

295

151

20

77
Bottom face
Ceiling panel (sold separetely)
of ceiling

880
Hanging bolt pitch
1000~1010
Ceiling open dimension
1050
Panel external dimension

Refrigerant pipe
connecting port
(Liquid side)
Refrigerant pipe
connecting port
(Gas side)

185

570
137.5 147.5
95
190
80 20

189

850 or less

609 or less

300 or less

Drain pipe
connecting port
241

380
Hanging bolt
pitch

680
ceiling open
dimension

680
Panel external
dimension

815

103

Electric parts box

Power supply
Knockout hole for auxiliary connecting port
fresh air intake flange
(only at reverse side)

ceiling
Drain standing-up size

(Unit: mm)

MMU-AP0182WH to AP0302WH
Adjust cover

345

570
137.5 147.5
95 190
185 80 20

Refrigerant pipe
connecting port
(Liquid side)
Refrigerant pipe
connecting port
(Gas side)

Drain pipe
connecting port

242

850 or less

559 or less

300 or less

ceiling

Knockout hole for auxiliary


fresh air intake flange
(Only at reverse side)

Drain standing-up size

291

Ceiling panel (sold separetely)

103

Bottom face
of ceiling

20

151

77
1245
Hanging bolt pitch
1365~1357
Ceiling open dimension
1415
Panel external dimension

Wireless sensor mounting section

Hanging bolt 4-M10


procured locally

1180

380
Hanging bolt
pitch

620
Ceiling open
dimension

680
Panel external
dimension

Electric parts box

Power supply
connecting port

(Unit: mm)

MMU-AP0362WH to AP0562WH
Adjust cover

Wireless sensor mounting section

Electric parts box

20
ceiling
Drain standing-up size

570
137.5 147.5
95 190
185 80 20

Drain pipe
connecting port

Refrigerant pipe
connecting port
(Gas side)

Knockout hole for auxiliary


fresh air intake flange
(Only at reverse side)

291

Refrigerant pipe
connecting port
(Liquid side)

103

300 or less

242

Ceiling panel (sold separetely)

850 or less

Bottom face
of ceiling

559 or less

1835 Panel external dimension

255

151

77
1665 Hanging bolt pitch
1785~1795 Ceiling open dimension

345

Hanging bolt 4-M10


procured locally

120
120

380
Hanging bolt
pitch

620
Ceiling open
dimension

680
Panel external
dimension

1600

Power supply
connecting port

(Unit: mm)

Options

Ceiling panel
RBC-UW283PG(W)-E
RBC-UW803PG(W)-E
RBC-UW1403PG(W)-E

Filter chamber
TCB-FC283UW-E
TCB-FC803UW-E
TCB-FC1403UW-E
Super long life filter
TCB-LF283UW-E
TCB-LF803UW-E
TCB-LF1403UW-E

Auxiliary fresh air flange


TCB-FF151US-E

36
34

1-way Air Discharge Cassette Type


The perfect choice for hotels and
reception areas

Fresh air intake is possible

Silent sound design ensures the


quiet required for the office.

Preparations/connection possible
with a circle duct flange.

Ideal for smaller rooms where


one-way air distribution is required.
Able to blow air straight out.
MMU-AP***4YH-E
MMU-AP***4SH-E

Condensate drain pump included.


Long-life filters fitted as standard.

* The photo shows the MMU-AP***4SH-E Series.

REMOTE CONTROLS

RBC-AX32CE2

RBC-AMS41E

RBC-AMS51E
Technical specifications

Model name

MMU

AP0074YH-E

AP0094YH-E

AP0124YH-E

AP0154SH-E

AP0184SH-E

AP0244SH-E

Cooling/Heating capacity*1

(kW)

2.2/2.5

2.8/3.2

3.6/4.0

4.5/5.0

5.6/6.3

7.1/8.0

Electrical
characteristics

Power requirements
Power consumption
50 Hz/60 Hz

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)
0.042/0.041

5.6/6.3

(kW)

0.053/0.056

Appearance (Ceiling panel)

Model

RBC-UY136PG

Height
External
dimensions:
Width
Main unit
(Ceiling panel)*
Depth

(mm)

235 (18)*

200 (20)*

(mm)

850 (1050)*

1000 (1230)*

(mm)

850 (1050)*

710 (800)*

(kg)

22 (3.5)*

(m3/h)

540/480/420

(W)

22

Gas side

(mm)

9.5

Liquid side

(mm)

Drain port

(nominal
dia.)

Total weight: Main unit (Ceiling panel)*


Fan unit

Standard air flow


(High/Mid/Low)
Motor output

Connecting
pipe

Sound pressure level*2 (High/Mid/Low)

(dB(A))

7.1/8.0

RBC-US21PGE

21 (5.5)*
750/690/630

22 (5.5)*

780/720/660

1140/960/810

30
12.7

15.9

6.4

6.4

25 (Polyvinyl chloride tube)


42/39/34

37/35/32

*Figures in parentheses are for ceiling panels.


*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

38/36/34

45/41/37

35

MMU-AP0074YH-E to AP0124YH-E
Panel external dimension 1050
Ceiling open dimension 1010

20

455

Hanging bolt 4-M10


procured locally

140

120

Ceiling panel (Sold separately)

100 or less
Bottom face of ceiling

Air outlet

1050

Support metal

Stand-up
150 or less

Discharge louver

400

18

85

200

850

Refrigerant pipe
connecting port
(Gas side)

20

50

Center of panel

100

235

395

110

150
225

470

Refrigerant pipe
connecting port
(Liquid side)
Panel mounting hole 5 positions

Stand-up 350 or less

Drain pipe connecting port

Panel external
dimension 470

Power supply connecting port

400

Hanging bolt
pitch 330

20

Hanging bolt pitch 890

Ceiling open
dimension 430

20

Bottom face of ceiling


Air inlet

Drain standing-up size

(Unit: mm)

MMU-AP0154SH-E to AP0244SH-E
Wiring connection port
Drain pipe
connecting port

20

72

Refrigerant pipe connecting port (Gas side)

Ceiling panel (Sold separately)

800

60

43

1230

80

710

20

135

220

122

233

Hanging
bolt pitch 475 100

112

20

Hanging bolt pitch 1060

216

Ceiling open dimension 1190

Panel externaldimension 800

20

112

94

Wireless sensor mounting section

154
140 or less

1000

Hanging bolt M10 or W3/8 local arrange

73.4

93

20

200

76

706

Stand-up
696 or less

Refrigerant pipe connecting port (Liquid side)

Bottom face of ceiling

Stand-up 850 or less

Panel external dimension 1230

Ceiling open dimension 760

Fresh air intake (92 knockout hole)

Bottom face of ceiling

Knockout hole for front blow out

Drain standing-up size

(Unit: mm)

Options
AP0074YH-E/AP0094YH-E/AP0124YH-E

Front air discharge unit


TCB-BUS21HWE

Ceiling panel
RBC-UY136PG

Auxiliary fresh air flange


TCB-FF101URE2
Ceiling panel

AP0154SH-E/AP014SH-E/AP0244SH-E

RBC-US21PGE

38
36

Concealed Duct Type


Compact size, wider range of installation opportunities

275mm giving a wider range of installation opportunities


Especially in height as new model has a slimmer chassis
Improved external static pressure (max 120Pa)

With a new DC Fan Motor provides a wider range of installation


opportunities.
New Design for safety and easy maintenance

The new model has adopted new features for safety and easy
approach during installation
Pre-installed drain pump

Gives a wider scope for installation as it is able to pump


water 850mm up from the drain pan.

MMD-AP***6BHP-E

REMOTE CONTROLS

TCB-AX32E2

RBC-AMS41E

RBC-AMS51E

Technical specifications
Model name

MMD

Cooling/Heating capacity (Note 1)

(kW)

2.2/2.5

(A)

0.26 / 0.27

AP0076BHP-E AP0096BHP-E AP0126BHP-E AP0156BHP-E AP0186BHP-E AP0246BHP-E AP0276BHP-E AP0306BHP-E AP0366BHP-E AP0486BHP-E

2.8/3.2

4.5/5.0

Running current
Power consumption
Starting current

0.29/ 0.31

9.0/10.0

11.2/12.5

14.0/16.0

16.0/18.0

0.52 /0.55

0.61 / 0.64

1.07 / 1.12

1.23 / 1.29

0.038

0.043

0.062

0.077

0.094

0.172

0.198

(A)

0.45 /0.47

0.5 /0.54

0.73 / 0.76

0.9 /0.95

1.06 /1.11

1.85 / 1.94

2.13 / 2.23

Zinc hot dipping steel plate


(mm)

Width

(mm)

Depth

(mm)

275
700

1,000

1,400

30

40

750
23

(kg)

Heat exchanger

Finned tube

Soundproof / Heat-insulating meterial

Polyethlene foam

Fan
Standard air flow
(Mid/Low)

Centrifugal fan
(m3/h)

Motor output

540 (420/360*)

5 7 0 ( 4 5 0 /390*)

8 0 0 ( 6 3 0 /540*)

1 , 2 0 0 ( 9 3 0 /870*)

1,260 (960/930*) 1,920 (1,500/1380*)

150

(W)

External static pressure


(Pa)(factory setting)

2100 (1,650/1500*)

250

30

40

50

30 - 40 - 50 - 65 - 80 - 100 - 120 (7steps)

External static pressure (Pa)

Standard filter (Long life filter)

Air filter

Remote controller

Controller

Connecting pipe

8.0/9.0

(kW)

Height

Total weight

Fan unit

7.1/8.0

0.42 /0.44

Appearance

Dimension

5.6/6.3

1phase 50Hz 230V(220V-240V),1phase 60Hz 220V (Sepatate power supploy for indoor unit is required.)

Power supply
Electrical
characteristics
(50Hz / 60 Hz)

3.6/4.0

AP0566BHP-E

Gas side

(mm)

Liquid side

(mm)

Drain port

(mm)

Sound pressure level (Note 2) (Hi/Med./Low)

9.5

12.7

15.9

6.4

9.5
25 (Polyvinyl chloride tube)

29/26/23

30/26/23

33/29/25

36/31/27

40/36/33

Note 1: The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 base on the reference piping. The reference piping consists of 5 m of main piping and
2.5 m of branch piping connected with 0 meter height.
Note 2: The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values
due to the effects of external sound.
Note: Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB. Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB.

37

MMD-AP0076BHP-E to AP0566BHP-E
Flexible drain hose
(Accessory)

Hanging bolt pitch A

Space required for installation and servicing


5 or
more

Unit external dimension B

Refrigerant pipe
connecting port 6.4

25
700 or
more
Service door (Ceiling opening)
700 or
more

2500
or more

25
100 or
more

275

Air outlet

Ceiling

1/100 or more downward


At the time of natural drainage

750

Floor surface

(Liquid side)
Refrigerant pipe
connecting port 9.5

108

(Gas side)

650

Electrical control box


Air filter

(For air taking-in air)

20
37

233
232

20

345

50
125 knockout hole

18

136

233
117.5

570
355

Hanging bolt pitch 650

Drain pipe
connecting port

170

Unit external dimension 750

50

22

64 180 (Outside)

Unit external dimension


275

C (outside)

18

Wires
drawing-out port

229

Model MMD-

(Unit: mm)
D

Options

Spigot shaped flange


TCB-SF56C6BE
TCB-SF80C6BE
TCB-SF160C6BE

AP0076BH-E, AP0096BH-E, AP0126BH-E

765

700

640

654

AP0156BH-E, AP0186BH-E

765

700

640

654

1000

940

953.5

1500

1340

1349

1065
AP0246BH-E, AP0276BH-E, AP0306BH-E
Under air intake type
1465
AP0366BH-E, AP0486BH-E, AP0566BH-E
Model MMD- (Thailand)

AP0076BHP-E, AP0096BHP-E, AP0126BHP-E

765

700

640

654

AP0156BHP-E, AP0186BHP-E

765

700

640

654

AP0246BHP-E, AP0276BHP-E, AP0306BHP-E

1065

1000

940

953.5

AP0366BHP-E, AP0486BHP-E, AP0566BHP-E

1465

1500

1340

1349

42
38

Concealed Duct High Static Pressure type


Design flexibility

Construction characteristics

Satisfies all your design needs.

Three-phase-switchable static
pressure.

Compatible with external static


pressures up to 196 Pa.

The flexible duct is accessible.

Inspection inlet enables easy


access and maintenance.

Easy service and installation.

high-efficiency filter (65%, 90%


efficiency)
Filter/Drain pump optional

MMD-AP***4H-E

Inspection hole enables easy access


and maintenance.

REMOTE CONTROLS

RBC-AMS41E

RBC-AMS51E

Technical specifications
Model name

MMD

AP0184H-E

AP0244H-E

AP0274H-E

AP0364H-E

AP0484H-E

AP0724H-E

AP0964H-E

Cooling/Heating capacity*1

(kW)

5.6/6.3

7.1/8.0

8.0/9.0

11.2/12.5

14.0/16.0

22.4/25.0

28.0/31.5

Power consumption
50 Hz/60 Hz

(kW)

0.184/0.198

Height

(mm)

Width

(mm)

850

Depth

(mm)

660

Electrical
characteristics

External
dimensions

Total weight
Standard air flow
(High/Mid/Low)
Fan unit

Connecting
pipe

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

0.299/0.385

0.368/0.450

0.414/0.490

1.200/1.540

380

1.260/1.610
470

1,200

1,380
1,250

(kg)

50

52

56

67

150

(m3/h)

900

1,320

1,600

2,100

3,600

160

260

Motor output

(W)

External static pressure


(factory setting)

(Pa)

137

External static pressure

(Pa)

68.6 137 196

4,200
370x3

Gas side

(mm)

12.7

15.9

22.2

Liquid side

(mm)

6.4

9.5

12.7

Drain port

(nominal
dia.)

Sound pressure level*2 (High/Mid/Low)

(dB(A))

25 (male screw)
37

40

*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

49

50

39

MMD-AP0484H-E

MMD-AP0724H-E, AP0964H-E
70

70

MMD-AP0184H-E to AP0364H-E

Air inlet

Refrigerant pipe
connecting port
(Liquid side)

Refrigerant pipe
connecting port
(Liquid side)
1250

13

316

164

470
31

Drain pipe
connecting port
190

1200
(202)

624
698

250

250

250

250

316

348

(141) 226

13

348

77
Left side

(141) 226

406

850
Left side
AP0361H

Left side
Air outlet

Air outlet

275

275

(150)

150

300

300

300

250

(150)

250

250

250 190

Z view

(Unit: mm)

Screw hole for


duct mounting (8-M6)

(47)

Screw hole for


duct mounting (6-M6)

65

85

(47)

30

70

(Unit: mm)

Filter chamber
TCB-FCY21DE, TCB-FCY31DE
TCB-FCY51DE, TCB-FCY100DE

Long life prefilter


TCB-PF1D-1E
TCB-PF2D-1E
TCB-PF3DE

High-efficiency filter 65
TCB-UFM1D-1E, TCB-UFM2D-1E, TCB-UFM3DE
High-efficiency filter 90
TCB-UFH5D-1E, TCB-UFH6D-1E, TCB-UFM7DE

TCB-DP31DE
TCB-DP32DE

Screw hole for


duct mounting (10-M6)

(Unit: mm)

Options

Drain pump kit

370

Z view

35

Z view

316

316

17

150

Screw hole for


duct mounting (10-M6)

Screw hole for


duct mounting (8-M6)

Screw hole
for duct mounting (6-M6)
17

Air outlet

29

Air outlet

110

45

90
30

Drain pipe
connecting port

Screw hole
for duct mounting (4-M6)

200 150

40

60

35

(141)226

242

380

105

426

Refrigerant pipe
connecting port
(Gas side)

Electric parts box

660

35

(182)

100

70
Refrigerant pipe
connecting port
(Gas side)

850
13

Air inlet

1328
Hole for hanging bolt (4-12x92)

Hanging bolt pitch


700
740

35

30

35

60

110

Hanging bolt pitch 1288

35

660
105

Left side
AP0181H
to
AP0271H

Air outlet

70
Refrigerant pipe
connecting port
(Liquid side)

Power supply/communication
piping port (26) (bottom side
of electric parts box)

380

Refrigerant pipe
connecting port
(Gas side)

Drain pipe
connecting port

Air inlet

Electric parts box


Hanging bolt pitch
700
740

90 40

Power supply/communication
piping port (26) (bottom side
of electric parts box)

1060

Air outlet

Electric parts box

Z
1380

710

Air outlet

Hole for hanging bolt


(4-12x72)

Hanging bolt pitch 1260

44
40

Slim Duct Type


Slim & Quite

Functional design

Only 210 mm in height for greater


application flexibility.

Perfect comfort throughout the


room.

4 step static pressure setup.

Can be used with any style of air


diffuser.

Concealed installation within a


ceiling void.

Quiet, powerful operation.

Fresh air intake available.


MMD-AP***4SPH-E

Condensate drain pump included.

REMOTE CONTROLS

TCB-AX32E2

RBC-AMS41E

RBC-AMS51E

Technical specifications
Model name

MMD

AP0074SPH-E

AP0094SPH-E

AP0124SPH-E

AP0154SPH-E

AP0184SPH-E

AP0244SPH-E

AP0274SPH-E

Cooling/Heating capacity*1

(kW)

2.2/2.5

2.8/3.2

3.6/4.0

4.5/5.0

5.6/6.3

7.1/8.0

8.0/9.0

Electrical
characteristics
50 Hz/60 Hz

Power consumption

(kW)

Height

(mm)

210

210

Width

(mm)

845

1,140

Depth

(mm)

645

645

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

0.039

0.043

Appearance

0.045

(kg)

Total weight

22

23

Heat exchanger

Fan unit

Motor output
External static pressure
Gas side

Connecting
pipe
Sound pressure
level (note 2)
(Hi/Mi/Lo)
(dB(A)

Note:

29

Fined tube
Standard air flow
(Mid/Low)

Note 2:

0.105

Zinc hot dipping steel plate

External
dimensions

Note 1:

0.054

(m3/h)

540/470/400

600/520/450

(W)
(Pa)

06/16/31/46

(mm)

Liquid side

(mm)

Drain port

(nominal
dia.)

690/600/520

780/680/580

60

1,080/1,000/900
120

05/15/30/45

04/14/29/44

9.5

12.7

02/12/22/42
15.9

6.4

9.4

25 (polyvinyl chloride tube)

Under air inlet

36/33/30

38/35/32

39/36/33

40/38/36

49/47/44

Back air inlet

28/26/24

29/27/25

32/30/28

33/31/29

38/36/33

The cooling capacities and electrical characteristics and measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
The sound levels are measured in an anechoic chamber in accordance with JIS B 8615. Normally, the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.
Rated conditions cooling: Indoor air temperature 27C DB / 19C WB, Outdoor air temperature 35C DB.
Heating: Indoor air temperature 20C DB, outdoor air temperature 7C DB/6C WB.

41

MMD-AP0074SPH-E to AP0184SPH-E

210

Refrigerant pipe
connecting port
(Liquid side)

21

803 (inside)

21

Refrigerant pipe
connecting port
(Gas side)

103

Air filter

31
359
372
422
502

168

40

67

120

80

9
2

511
645

19

4-4

67

20 21

168 (Inside)

57

21

845

805
80

59

33
163

910

Fresh air intake


(knock-out hole)

Drain pipe
connecting port

Hanger plate

(Unit: mm)

MMD-AP0244SPH-E & AP0274SPH-E


Hanging bolt pitch 1205

Unit external
dimension 210
Hung-up
plate
103

Refrigerant pipe
connecting port 9.5
(Liquid side)
Refrigerant pipe
connecting port 15.9
(Gas side)

1100

98
92 knockout hole
(For air taking-in-air)

Air filter

Electrical control box

Unit external dimension 645


120
166

67

372
422
502

359

31

40

120

185

168

Hanging bolt pitch 511

67

20

21 168 (inside)

Unit external dimention 1140


1100 (inside)

15
33
163

Drain pipe connecting port


for vinyl chloride pipe
(Inner dia. 32. VP25)

(Unit: mm)

Options

Auxiliary fresh air flange


TCB-FF101URE2

48
42

Ceiling Type
Equipped with self-clean operation.
Improved air flow angel by new designed wide flap.
Reduces noise level to half that of conventional
The unit can be suspended from the ceiling with free access hangers:
Fix the hanging plate on the ceiling firstly.
Next, hang the indoor unit on that plate.
Drain pump kit (Optional)
To restrict the bacterial growth, anti-bacterial glass is built into new
drain pump kit.

MMC-AP***7HP-E

REMOTE CONTROLS

RBC-AX32CE2

RBC-AMS41E

RBC-AMS51E

Technical specifications
Model name

MMC

AP0157HP-E

AP0187HP-E

AP0247HP-E

AP0277HP-E

AP0367HP-E

AP0487HP-E

AP0567HP-E

Cooling/Heating capacity*1

(kW)

4.5/5.0

5.6/6.3

7.1/8.0

8.0/9.0

11.2/12.5

14.0/16.0

16.0/18.0

Power consumption
50 Hz/60 Hz

(kW)

0.033/0.033

Height

(mm)

Width

(mm)

Depth

(mm)

Electrical
characteristics

External
dimensions

Standard air flow


(High/Mid/Low)

0.830/0.830

1,270

23
840/690/540

0.111/0.111

1,586

29
900/720/540

(mm)

12.7

Liquid side

(mm)

6.4

Drain port

(nominal
dia.)
(dB(A))

0.083/0.083

690

30

Sound pressure level*2 (High/Mid/Low)

0.067/0.067
235

(W)

Motor output
Gas side

Connecting
pipe

(m3/h)

0.034/0.034

950

(kg)

Total weight
Fan unit

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

35

1410/1020/750

1860/1350/1020

2040/1650/1260

40

80

80

15.9
9.5
20 (Polyvinyl chloride tube)

36/34/28

37/35/28

41/36/29

0.083/0.083

*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

44/41/35

46/42/36

43

MMC-AP0157HP-E to AP0567HP-E

Upper piping drawing-out port (Knockout)

235

Piping drawing-out port


(Knockout)

176
205
244

145
Hanging position

98

690

320

Z
40

218
109 66

170

48

Power supply cable taking-in port (Knockout)


Drain left pipe
87
connecting port

158

102

Drain pipe
connection port

132
192

A (Hanging position)
Refrigerant pipe connecting port D
(Liquid side)
Refrigerant pipe connecting port C
(Gas side)

353
Wireless sensor mounting section

158

125

33

33
85

351
270

Remote controller cable taking-in port


Power supply taking-in port (Knocking)
Remote controller cable
taking-in port (Knockout)
87

Air taking-in port


(Duct sold separately)
(Knockout hole 92)
Z view

Drain left piping


drawing-out port
(Knockout)

Space requirement for installation and servicing

MMC-AP0157HP-E / 0187HP-E

906

950

12.7

6.4

MMC-AP0247HP-E / 0277HP-E

1223

1269

15.9

9.5

MMC-AP0367HP-E / 0487HP-E / 0567HP-E

1540

1586

15.9

9.5

Ceiling surface
Unit
250 or more

250 or more

500 or
more

MMC-

Within 50

Hanging bolt

Model

(Front side to be positioned horizontally)

(Unit:mm)

Options
TCB-KP13CE, TCB-KP23CE
Elbow piping
RBC-AX33CE
Wireless remote controller

TCB-DP31CE
Drain pump kit

TCB-PCUC1E
Optional connecting kit

50
44

High-wall Type (3 series)


Elegant and slim

This classic high wall is elegant and slim; it can easily blend in with any
room.
Total comfort is granted, thanks also to the 70directional auto swing
louver that provide uniform air distribution.

REMOTE CONTROLS

MMK-AP***3H

Standard

RBC-AMS41E

RBC-AMS51E

MMK-AP0073H to AP0243H
1050

Air Filter

228

50

Air outlet

Heat exchanger

50
Knockout

73.5

73.5

320

Air inlet

50

Knockout

72 78

Tab for installation plate


132

568

Tab for
installation plate

200

Drain
connecting
pipe

Refrigerant
connecting pipe
(Gas side)

150

Refrigerant
connecting pipe
(Liquid side)

(Unit: mm)

Technical specifications
Model name

MMK

AP0073H

AP0093H

AP0123H

AP0153H

AP0183H

AP0243H

Cooling/Heating capacity*1

(kW)

2.2/2.5

2.8/3.2

3.6/4.0

4.5/5.0

5.6/6.3

7.1/8.0

Power consumption
50 Hz/60 Hz

(kW)

0.018

Height

(mm)

320

Width

(mm)

1,050

Depth

(mm)

228

(kg)

15

Electrical
characteristics

External
dimensions

Total weight
Fan unit

Connecting
pipe

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

Standard air flow


(High/Mid/Low)
Motor output

(m3/h)

570/450/390

600/480/390

(mm)

Liquid side

(mm)

Drain port

(nominal
dia.)
(dB(A))

0.043

0.050

840/660/540

1,020/750/570

12.7

15.9

30

(W)

Gas side

Sound pressure level*2 (High/Mid/Low)

0.021

9.5

9.5

6.4
16 (Polyvinyl chloride tube)
35/31/28

37/32/28

*1 The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
*2 The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

41/36/33

46/39/34

51
45

Floor Standing Concealed Type


Cool air makes for a pleasant indoor
environment

Easy maintenance

Install it under a window and


aircondition any room effectively.

Simplified design of fan and


drainage pipe eases maintenance.

REMOTE CONTROLS

MML-AP***4BH-E

TCB-AX32E2

RBC-AMS41E

RBC-AMS51E

MML-AP0074BH-E to AP0244BH-E
Hole for floor mounting

(Air discharge port size in flange)


Ceiling board section

25

145

145

50

85

100

(Air discharge port size in flange)


10

123

2- 4.7 hole (left/right side each)

10

65

10

20

A
D X 100

135

Drain pipe
connecting port

AP0074BH-E to AP0124BH-E

610

580

550

AP0154BH-E to AP0244BH-E

910

880

850

104

274

140

80

129

Model MML-

Air filter

2-12 X 18 long hole


(Hole for floor
mounting)

224

315

Refrigerant
pipe connecting port
(Gas side)

436

Refrigerant
pipe connecting port
(Liquid side)

4-15 hole
(for mounting rear
side)

Electric parts box (earth terminal


is provided in inner side)

170

394

402

600

Expansion valve box


E -4.7 hole
(front side and
rear side)

110
85

55

155
220

(Unit: mm)

Technical specifications
Model name

MML

AP0074BH-E

AP0094BH-E

AP0124BH-E

AP0154BH-E

AP0184BH-E

AP0244BH-E

Cooling/Heating capacity*1

(kW)

2.2/2.5

2.8/3.2

3.6/4.0

4.5/5.0

5.6/6.3

7.1/8.0

Electrical
characteristics

External
dimensions

Power consumption
50 Hz/60 Hz

(kW)

Height

(mm)

Width

(mm)

Depth

(mm)

Total weight
Fan unit

Standard air flow


(High/Mid/Low)
Motor output
Gas side

Connecting
pipe

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

0.056/0.058

0.090/0.096

745

1,045
220

(kg)

21

(m3/h)

460/400/300

(W)

19

(mm)

9.5

29
740/600/490

Liquid side

(mm)

6.4

(nominal
dia.)

20 (Polyvinyl chloride tube)

(dB(A))

950/790/640
70

12.7

Drain port
Sound pressure level*2 (High/Mid/Low)

0.095/0.110

600

36/34/32

*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

15.9
9.5

42/37/33

52
46

Floor Standing Cabinet Type


Slim & compact design

Air exits from front or top

Under-window mounting does not


black lighting.

Distribution can be reversed to


suit occupant preference.

Indoor unit size of 2.2 kW to 7.1 kW


is the same.
Air blown from top
Air blown from front panel
(Factory default)

REMOTE CONTROLS

MML-AP***4H-E

TCB-AX32E2

RBC-AMS41E

RBC-AMS51E

150

Drain pipe connecting port

Hole for wall mounting


(Knockout hole)

230

(Drain)

138

(Liquid)

(Gas)

Piping positional drawing


133

Air outlet

130
5

177

35

Refrigerant pipe
connecting port
(Gas side)

(Gas)

120
130

400

106

Hole for floor


mounting (2-10)

Refrigerant pipe
connecting port
(Liquid side)

162

95
28
Lower refrigerant piping port
(Knockout hole 50x100)

(Liquid)

MML-AP0074H-E to AP0244H-E

97

70

50

35

Long hole for


wall mounting

430

630

Power supply cord hole


(26 knockout hole)

950

120

30

Refrigerant pipe port (both sides) (knockout hole 50x100)

Earth screw (M6)

130
(100 left side)

57

Air inlet

Refrigerant pipe port


(Knockout hole 130)

(Unit: mm)

Technical specifications
Model name

MML

AP0074H-E

AP0094H-E

AP0124H-E

AP0154H-E

AP0184H-E

AP0244H-E

Cooling/Heating capacity*1

(kW)

2.2/2.5

2.8/3.2

3.6/4.0

4.5/5.0

5.6/6.3

7.1/8.0

Electrical
characteristics

External
dimensions

Power consumption
50 Hz/60 Hz

(kW)

Height

(mm)

630

Width

(mm)

950

Depth

(mm)

Total weight
Fan unit

Connecting
pipe

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

0.056/0.053

230
37

(kg)
Standard air flow
(High/Mid/Low)
Motor output

(m3/h)

(mm)

Liquid side

(mm)

Drain port

(nominal
dia.)

Sound pressure level*2 (High/Mid/Low)

(dB(A))

40

480/420/360

900/780/650

1,080/930/780

45

(W)

Gas side

0.102/0.113

0.092/0.092

70

9.5

12.7

15.9

6.4

9.5

20 (Polyvinyl chloride tube)


39/37/35

45/41/38

*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

49/44/39

53
47

Bi-Flow Console Type


Compact and modern design in all three dimensions (60x70x22 cm).
Bi-flow. Two outlets for complete personalized flow: flow intensity and
air direction control.
Toshiba new IAQ Filtration : Having anti virus, Anti bacteria and the
deodorizing capabilities.
Smart user interface : Child lock function on the unit display panel.
Brightness level control of the display unit to reduce the LED light glow.
Automatic restart function in case of unexpected electricity supply line
power cuts.
Floor heating function.
REMOTE CONTROLS
MML-AP***4NH-E

TCB-AX32E2

RBC-AMS41E

RBC-AMS51E

MML-AP0074NH-E to MML-AP0184NH-E

(Wall installation)

230

15
288

Slit

6 screw
(M4 x 25L)

4 screw
(M4 x 25L)

670

15

1000 mm or less

Note

150

10

Installation on the wall


1) Fix the installation plate on the wall with 4 mounting screws.
2) Hook the indoor unit on the installation plate.
3) Fix the upper part of indoor unit on the wall with 4 mounting screws.

40

Mounting directly on the floor


1) Fix the leg of indoor unit on the floor with 2 mounting screws.
2) Fix the upper part of indoor unit on the wall with 4 mounting screws.

In case the plinth is fi xed to the wall, please make sure to cut out the
slit on the left and right side of the main part.
Cut dot-line area

4 screw
(M4 x 25L)

Technical specifications
Indoor unit

MML

Cooling capacity
Heating capacity
Power consumption
Running current
Starting current

AP0074NH-E

AP0094NH-E

AP0124NH-E

AP0154NH-E

AP0184NH-E

(kW)

2.2

(kW)

2.5

2.8

3.6

4.5

5.6

3.2

4.0

5.0

6.3

(kW)
(A)

0.021

0.021

0.025

0.034

0.052

0.20

0.20

0.23

0.29

0.42

(A)

0.26

0.26

0.30

0.38

0.55

Air flow

(m3/h)

510/282

510/282

552/324

624/384

726/426

Sound pressure level (h/l)

(dB(A))

38/26

38/26

40/29

43/31

47/34

Sound power level (h/l)

(dB(A))

53/41

53/41

55/44

58/46

62/49

Dimensions (H x W x D)

(mm)

600/700/220

600/700/220

600/700/220

600/700/220

600/700/220

Weight

(kg)

17

17

17

17

17

Connecting pipe (Gas)

(in)

3/8

3/8

3/8

1/2

1/2

Connecting pipe (liquid)

(in)

1/4

1/4

1/4

1/4

1/4

Drain port diameter


Power Supply

(mm)

16

16

16

16

16

V-ph-Hz

220/240-1-50

220/240-1-50

220/240-1-50

220/240-1-50

220/240-1-50

54
48

Floor Standing Type


Thin profile suits interior design

Wide outlet

Slender, space-saving
(1.7-6.0HP)

Corner location is also possible,


with right and left auto swing.

type

Auto
swing
REMOTE CONTROLS
MMF-AP***4H-E
TCB-AX32E2

RBC-AMS41E

RBC-AMS51E

MMF-AP0154H-E to AP0564H-E
Bracket for wall mounting
Pitch
30x3

Air outlet

20

80

Wall

Model MMD-

Pipe holes on side


(both sides)
(knockout hole)

50
Rear side pipe hole
(130 knockout hole)

120

180

132 157

210

50

AP0364H-E to AP0564H-E

380

120 160

390

40

Drain pipe
connecting port

125

MMF-AP0364H-E
Liquid
side

358

Liquid
side

155

D
204

120

MMF-AP0154H-E

165

631

Air inlet

164
C

Floor fixing bracket


Screw position 640

200 107

Drain pipe port


(both sides)
(knockout hole)

59
10

Bracket for
floor mounting
(both sides)

AP0154H-E to AP0274H-E

380

815

1750

210 25

40

600
Pitch
30x3

Gas
side

165

Refrigerant pipe connecting


port (Liquid side)

215
215

Gas side

Refrigerant pipe connecting port (Gas side)

Earth screw (M4)

Refrigerant piping position

(Unit: mm)

Technical specifications
Model name

MMF

AP0154H-E

AP0184H-E

AP0244H-E

AP0274H-E

AP0364H-E

AP0484H-E

AP0564H-E

Cooling/Heating capacity*1

(kW)

4.5/5.0

5.6/6.3

7.1/8.0

8.0/9.0

11.2/12.5

14.0/16.0

16.0/18.0

Electrical
characteristics

External
dimensions

Power consumption
50 Hz/60 Hz

(kW)

Height

(mm)

1,750

Width

(mm)

600

Depth

(mm)

0.067/0.067

0.830/0.830

210

390

(kg)

48

49

900/780/660

1,200/1,020/840

1,920/1,680/1,380

2,160/1,860/1,560

(W)

37

63

110

160

(mm)

12.7

Liquid side

(mm)

6.4

Drain port

(nominal
dia.)

Standard air flow


(High/Mid/Low)
Motor output
Gas side

Connecting
pipe

0.033/0.033

(m3/h)

Total weight
Fan unit

1-phase 50 Hz 230 V (220240 V)/1-phase 60 Hz 220 V (Separate power supply for indoor units required.)

Power requirements

Sound pressure level*2 (High/Mid/Low)

(dB(A))

65

15.9
9.5
20 (Polyvinyl chloride tube)

46/43/38

49/45/40

51/48/44

*1 This reference piping consists of 5 m of main piping and 2.5 m of branch piping connected at the same height level.
*2 The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient noise.

54/50/46

56

49

AHU DX Connectivity Kit - DX Controller


& DX Valve Kit
DX Coil Interface

Valve Kit

DX Coil interface enables the connection of Toshiba VRF Outdoor with


third party Air Handling Unit (AHU) for fresh air intake.
Control possible thru standard Toshiba Remote control (RBC-AMT32-E).
Compatible with Toshiba control accessories.
External on/off output.
Safety cut out input to detect fan failure.
Air temperature control using TA sensor positioned in supply air stream|
(set with remote controller).
Diversity Ratio maximum 110 % ( when a DX interface is connected )
Its composed of two parts : Controller & Valve Kit (3 sizes).
AHU DX Controller

Controller (Field supplied)

Controller

DX Controller-MM-DXC***
DX Valve Kit - MM-DXV***
Outdoor Unit
Air Handling Unit (Field Supplied)

Options :

Typical System Diagram

RBC-FDP3-PE Monitoring & Control Interface


TCB-TC21LE2 Remote Temperature Sensor

Technical specifications
Total Size (Individual)
MM-DXC010
MM-DXC012
MM-DXV080
MM-DXV140
MM-DXV280
Nominal Cooling Capacity (kW)
Nominal Heating Capacity (kW)
Minimum Air volume flow rate (m3/hr)
Standard Air volume flow rate (m3/hr)
Maximum Air volume flow rate (m3/hr)

HP
2
2.5
3
4
5
6
8
10

2.0
1
1

2.5
1
-

3.0
1
-

7.1
8.0
1060
1320
1580

5.6
6.3
720
900
1080

4.0
1
-

5.0
1
-

8.0
9.0
1060
1320
1580

6.0
1
-

11.2
12.5
1280
1600
1920

8.0
1
-

14.0
16.0
1680
2100
2520

16.0
18.0
1850
2800
3740

22.4
25.0
2880
3600
4320

10
1
-

1
28.0
31.5
3360
4200
5040

Technical specifications
Total Size (Individual)
MM-DXC010
MM-DXC012
MM-DXV080
MM-DXV140
MM-DXV280

HP
2
2.5
3
4
5
6
8
10

Nominal Cooling Capacity (kW)


Nominal Heating Capacity (kW)
Minimum Air volume flow rate (m3/hr)
Standard Air volume flow rate (m3/hr)
Maximum Air volume flow rate (m3/hr)
*In GROUP combination the Header Controller (MM-DXC010)

12.0
1
1

14.0
1
1

32.0
38.4
36.0
43.0
3700
4730
5600
6400
7480
8060
must be connected to

16.0
1
1

18.0
1
1

20.0
1
1

22.0
1
2

1*
2
44.8
50.4
56.0
50.0
56.5
63.0
5730
6240
6720
7200
7800
8400
8640
9360
10080
the largest DX Coil Valve Kit.

24.0
1
2

26.0
1
2

28.0
1
2

30.0
1
2

1
2*

60.8
68.0
7610
10000
12380

67.2
75.0
8640
10800
12960

2
1*
72.8
81.5
9120
11400
13680

1
2*
78.4
88.0
9600
12000
14400

3
84.0
94.5
10080
12600
15120

Technical specifications
Total Size (Individual)
MM-DXC010
MM-DXC012
MM-DXV280
Nominal Cooling Capacity (kW)
Nominal Heating Capacity (kW)
Minimum Air volume flow rate (m3/hr)
Standard Air volume flow rate (m3/hr)
Maximum Air volume flow rate (m3/hr)

HP
8
10

32.0
1
3
4
89.6
100.0
11520
14400
17280

34.0
1
3
3
1*
95.2
106.5
12000
15000
18000

36.0
1
3
2
2*
100.8
113.0
12480
15600
18720

38.0
1
3
1
3*
106.4
119.5
12960
16200
19440

40.0
1
3
112
126.0
13440
16800
20160

42.0
1
3
4
1*
117.6
131.5
14880
18600
22320

44.0
1
3
3
2*
123.2
138.0
15360
19200
23040

46.0
1
3
2
3*
128.8
144.5
15840
19800
23760

*In GROUP combination the Header Controller (MM-DXC010) must be connected to the largest DX Coil Valve Kit.
Cooling & Heating output figures are based on calculations and general test data. All figures are to ne taken as approximations.
The properties of the DX coils (by others) will have an effect on the performance of the outdoor units. All capacity data shown in this brochure is based on the following conditions.
Cooling: indoor air temperature 27C db/ 19C wb, outdoor air temperature 35C db
Heating: indoor air temperature 20C db, outdoor air temperature 7C db / 6C wb

The DX coil must be suitable for R410A.


The design should allow operation as both an Evaporator and a Condenser (Features: Multiple circuits/Liquid Capillary Distributor / Gas Header)
The counter flow principle must be observed.
Design target Evaporation temperature : 6.5C
Design target Condensation temperature: 52C
A Drain Pan must be fitted (even if only used in Heat mode) due to defrost cycles.
It is recommended to fit droplet eliminator plates in the discharge air stream if used in Cool mode.

48.0
1
3
1
4*
134.4
151.0
16320
20400
24480

50

Air to Air Heat Exchanger


9 models available with air flow ranges from 110 to 2000 m3/h.
Air conditioners and heat exchangers are controlled with same main bus.
(Fig.1)
Automatic changeover to efficient operation mode: Units automatically
switches to the heat exchange mode and normal ventilation based on
operating conditions.(Fig. 2)
Free cooling -Provides fresh outdoor cool air to reduce the indoor air
temperature,when the outdoor temperature is lower than the indoor air
conditioned temperature.
Air balance volume rate can be varied to suit the usage environment and
location .
VN-M***HE

REMOTE CONTROLLER

Main bus
(TCC-LINK)

1) ON/OFF

Main bus
(TCC-LINK)

COOLING or HEATING

Main bus
(TCC-LINK)

EXCEPT COOLING & HEATING


By-pass flow
Damper : Open

New Heat Exchange

2) Operating mode

RA

EA

Indoor

Outdoor

3) Setting temp

EA

OA

5) Ventilation mode

New Remote controller


for HEX (NRC-01HE)

NRC-01HE

SMMSi

New Remote controller


for HEX (NRC-01HE)

Remote controller
for SMMSi

Indoor
SA

OA

Central remote
controller

4) Air volume

RA

Outdoor

SA

Heat exchange element

Heat exchange element

Heat exchange mode

Normal ventilation mode

(Fig. 1)

(Fig. 2)

Technical specifications
VN-M150HE

VN-M250HE

VN-M350HE

VN-M500HE

VN-M650HE

VN-M800HE

VN-M1000HE

VN-M1500HE

VN-M2000HE

150/110

250/150

350/210

500/390

650/520

800/700

1,000/755

1,500/1,200

2,000/1,400

81.5/83

78/81.5

74.5/79.5

76.5/78

75/76.5

76.5/77

73.5/77

76.5/79

73.5/77.5

dB(A)

25.5/20

27/21

32/27

31/26

34/31

37/33.5

40.5/38.5

37.5/36

41/37

Model name
Air Flow (h/l)
Temperature exchange efficiency (h/l)
Sound pressure level (h/l)

m3/h

Power Input (h/l)


Enthalpy exchange efficiency

67/42

111/52

145/82

192/128

258/178

353/286

538/353

784/570

1,080/702

Heating (h/l)

74.5/76

70/74

65/71.5

72/73.5

69.5/71.5

71/71.5

68.5/71.5

71/73.5

68.5/72

Cooling (h/l)

69.5/71

65/69

60.5/67

64.5/66.5

61.5/64

64/65.5

60.5/64.5

64/67

60.5/65.5

Max. external static pressure(h/l)

Pa

8/47

65/28

83/65

99/62

82/61

132/76

122/84

124/112

116/110

Dimensions (HxWxD)
Weight
Duct diameter (Indoor side)

290x900x900

mm

350x1140x1140

400x1189x1189

810x1189x1189

kg

36

36

38

53

53

70

70

143

143

mm

100

150

150

200

200

250

250

250

250

49
51
MMD-VNM150HE to VNM350HE
25

1050

350

170

1140
EA(Exhaust Air)

454

RA(Return Air)

Outdoor side

Indoor side

80 Connecting Diagram

80

SA(Suppiy Air)

150~250 170

Power supply wire intake


25

200

600 or more

OA(Outdoor Air)

1197

800

1140

195
212

Earth Terminal

175
4-13 30 Oval hole(Hanging Bracket)
Inspection Opening 450 450 or more
Heat Exchange Element Filter Motor,Fans Maintenance Space

(Unit: mm)

Duct size (Nominal Diameter): 200

MMD-VNM500HE, VNM650HE
25

350
1140

EA(Exhaust Air)

454

RA(Return Air)

Earth Terminal

Outdoor side

Indoor side

80 Connecting Diagram

80

SA(Suppiy Air)

150~250 170

25

Power supply wire intake


200

600 or more

OA(Outdoor Air)

1197

800

1140

195
212

170

1050

175
4-13 30 Oval hole(Hanging Bracket)
Inspection Opening 450 450 or more

(Unit: mm)

Heat Exchange Element Filter Motor,Fans Maintenance Space


Duct size (Nominal Diameter): 200

MMD-VNM800HE, VNM1000HE
195

25

1099
EA(Exhaust Air)

400
1189
454

Earth Terminal

Outdoor side

Indoor side

1246

800

1189

245
262

RA(Return Air)

85

85

SA(Suppiy Air)

150~250 195

Power supply wire intake


25

200

600 or more

OA(Outdoor Air)

Connecting Diagram

200

4-13 30 Oval hole(Hanging Bracket)


Inspection Opening 450 450 or more

(Unit: mm)

Heat Exchange Element Filter Motor,Fans Maintenance Space


Duct size (Nominal Diameter):250

MMD-VNM1500HE, VNM2000HE

195

25

1099
EA(Exhaust Air)

810
50

1189
454
245
262
Connecting Diagram

410

85

Power supply wire intake

4-13 30 Oval hole(Hanging Bracket)


Inspection Opening 450 450 or more
Heat Exchange Element Filter Motor,Fans Maintenance Space

Duct size (Nominal Diameter): 250

245
262

SA(Suppiy Air)

200

150~250 195

600 or more

OA(Outdoor Air)

205

Indoor side

1246

Outdoor side

25

800

1189

730

RA(Return Air)

(Unit: mm)

52

Air to Air Heat Exchanger with DX-coil & Humidifier


Greater comfort and reduced load
Functionality built into the cooling system reduces load on cooling beyond that
of the heat exchanger itself. This improves air quality and ensures maximum
comfort throughout room being cooled.
Free cooling at night
When the air outdoors is cooler at night, the system expels warm air from the
room. This reduces the air conditioning load the next day for improved energy
efficiency.
Flexible control
Supply and exhaust fan speed ratios can be changed for improved air volume
control that best matches the needs of the environment and location.
*Limitations
The total capacity of indoor units combined should be within 80 - 135% of the capacity of the outdoor unit.
The capacity of the air to air heat exchanger should be no more than 30% of the capacity of the outdoor unit.

REMOTE CONTROLLER

Connectable with SMMSi


Outdoor, It is not possible to
connect SMMS/SHRM/MiniSMMS

(Fig.1)
NRC-01HE
Mo del name
Fresh air
conditioning load

VN(K )502HEXE

VN(K )802HEXE

VN(K )1002HEXE

Cooling (*1)

MMD (k W )

4.10 (1. 30)

6. 56 (2.06)

8. 25 (2. 32)

8. 25 (2. 32)

Heating (*1)

(k W )

5. 53 (2. 33)

8.61 (3.61)

10.92(4. 32)

10.92 (4. 32)

1-phase 50Hz 230V (220240V) / 1-phase 60Hz 220V


(Separate power supply for indoor units required.)

Power supply
Temperature
exchange
efficiency
50Hz / 60Hz

Enthalpy
exchange
efficiency
50Hz / 60Hz

(%)

70. 5/70. 5

70.0/70.0

65. 5

70. 5/70. 5

70.0/70.0

65. 5

Low
Cooling

Heating

High

D r ain p o r t

(%)

71. 5/72.0

72. 5/73.0

H i gh

(%)

56. 5/56. 5

56.0/56.0

Mid

(%)

56. 5/56. 5

56.0/56.0

L ow

(%)

57. 5/58.0

59.0/59. 5

High

(%)

68. 5/68. 5

70.0/70.0

M id

(%)

68. 5/68. 5

70.0/70.0

L ow

(%)

69.0/69.0

73.0/73. 5

High

(m3/h)

500/500

800/800

Mid

(m3/h)

500/500

800/800

Low

(m3/h)

4 40/410

6 40/600

820

High

(Pa)

120/200

120/190

135

195

Mid

(Pa)

105/170

100/155

120

160

L ow

67. 5

6 8 .0
52.0
52.0

54. 5

55.0
6 6.0
6 6 .0

68. 5

69.0
950
950
80 0

(Pa)

115/150

105/130

105

130

(dB)

37. 5/40.0

41.0/43.0

43.0

43. 5

Mid

(dB)

36. 5/38.0

40.0/42.0

42.0

L ow

(dB)

34. 5/36. 5

38.0/37.0

4 0. 0

H e i g ht

(mm)

W i d th

(mm)

1140

1189

D e p th

(mm)

1690

1739

G as si d e

(mm)

Total weight

(kg)
Liquid side

1-phase 60Hz 220V

(Separate power supply for indoor units is required.)

(%)

External static
pressure

Connecting
piping

(Separate power supply for indoor units is required.)

High

Fan unit
50Hz / 60Hz

External
Dimensions

1-phase 50Hz 230V (220V-240V)

Mid

Standard
air flow

Sound pressure
50Hz / 60Hz

VN(K )1002HEXE2

430

84

100

101

9. 5

(mm)
(Nominal dia .mm)

(*1) Cooling and heating capacities are based on the following conditions:
Cooling capacities are based on : indoor temperature :27 CDB/19CWB, Outdoor temperature : 35CDB
Heating capacities are based on : indoor temperature :20 CDB, Outdoor temperature : 7 CDB/6CWB
Fan is based on High and Middle
( ): The figures in ( ) indicate the heat reclaimed from the heat recovery ventilator.

12.7
6.4
25(Poly vinyl chloride tube)

103

47
53

MMD-VN(K)502HEXE
1690
1601
25

550

400

Outdoor
side

Indppr Side

250

1197
1140
800

173

RA
(Return Air)

EA
(Exhaust
Air)

SA
(Supply Air)

OA
(Outdoor Air)
200

152

Power supply wire intake

600

25

4-13 x 30 oval hole


(Hangling bracket)

Inspection opening 600 x 600

80
Duct size (Nominal Diameter): 200

26

46

476
350
175
195
212
430

350
175

343

454

Water inlet
connecting
port (R1/2)
194 53

Heat exchange element Filter Motors,


(Fans,
(
Maintenance space
Magnetic valve Decompression magnetic valve
(
(

496

Drain pipe connecting port


(VP25)

80
Refrigerant pipe connecting port (Liquid) 6.4
Refrigerant pipe connecting port (Gas) 9.5

(Unit: mm)

MMD-VN(K)802HEXE to VN(K)1002HEXE2

4-13 x 30 oval hole


(Hangling bracket)

550

RA
(Return Air)

400

EA
(Exhaust
Air)
Outdoor
side

Indppr Side

SA
(Supply Air)

200

Power supply wire intake

Inspection opening 600 x 600

600

25

OA
(Outdoor Air)

343
80

Duct size (Nominal Diameter): 250

Water inlet
connecting
port (R1/2)

46

476
350

496
Drain pipe connecting port
(VP25)

Options

Drain pump kit


TCB-DP31HEXE

200
245
262
430

454
400
200

26

Heat exchange element Filter Motors,


Fans, Maintenance space
Magnetic valve Decompression magnetic valve

194 53

250

800

1246
1189

25

1739
1650

85
Refrigerant pipe connecting port (Liquid) 6.4
Refrigerant pipe connecting port (Gas) 12.7

(Unit: mm)

57
5

54

Fresh Air Intake Indoor Unit Type


Air controller for fresh-air intake

Outside static pressure maximum 230Pa (In case of 50Hz of 5Hp).


Use of high-performance filter provides more comfortable room
enviroment.Introduces outdoor air at atemperature close to that of the
indoor air. Primary processing of fresh outdoor air.
Fresh Air-intake often influences the system, rendering normal control of
the air conditioner difficult or placing large loads on the system and its
cooling performance. Therefore it is frequently adopted to handle the
fresh air to a certain condition before the fresh air will enter in the main
air conditioner.
This device is known as a fresh air intake indoor unit.

MMD-AP****HFE

NOTE: The fresh air intake indoor unit is an air conditioner provided to handle the fresh air load and is not to control the
room temperature. For correspondence to the load of the indoor air controller, set an air conditioner separately.

Connectable outdoor unit


MMY-MAPXXXXHT8
MMY-MAPXXXXHT7

Fresh air intake indoor unit


SMMS-i outdoor unit
Indoor unit

Fresh air
Technical specifications
Model name

MMD

AP0481HFE

AP0721HFE

AP0961HFE

Cooling/Heating capacity (Note 1)

(kW)

14.0/8.9

22.4/13.9

28.0/17.4

Electrical
characteristics

External
dimensions:
Main unit

Power supply

(kW)

Power consumption

(kW)

Height

(mm)

Width

(mm)

Depth

(mm)
(kg)

Total weight
Standard air flow
Fan unit

Connecting
pipe

Motor output
External static pressure
50 Hz/60 Hz
Air ow limit Lower
limit/Upper limit

1-phase 50 Hz 230 V (220240 V)/60 Hz 220 V


0.28/0.34

0.45/0.55

0.52/0.65

492
892

1392
1262

93

(m3/h)

1080

(W)

0.160

144
1680

2100
0.1602

170-210-230 / 115-215-260

140-165-180 / 150-210-235

160-190-205 / 80-180-220

(m3/h)

756/1188

1176/1848

1470/2310

Gas side

(mm)

15.9

22.2

Liquid side

(mm)

9.5

12.7

Drain port

(nominal
dia.)

Sound pressure level (Note 2)


(High/Med./Low)

(dB(A))

R1
45/43/41

46/45/44

* The setting temperature is 16 27C (standard FCU18 29C).


* An optional humidi er is not available with fresh air intake indoor unit.
* Height di erence between fresh air intake indoor units must be within 0.5 m. Height di erence between fresh air intake indoor unit and standard FCU must be within 30 m.
NOTE 1:

NOTE 2:
NOTE 3:
NOTE 4:
NOTE 5:

Rated conditions

Cooling: Outdoor air temperature 33C DB/28C WB setting temperature 18C


Heating: Outdoor air temperature 0C DB/2.9C WB setting temperature 25C
Piping: Length 7.5 m / Height 0 m
Normally, the values measured in the actual operating environment become large than the indicated values due to the e ects of external sound
* When supply air temperature is setting temperature + 3C or less, fresh air intake indoor unit operates as FAN mode..
* When supply air temperature is 19C or less, Fresh Air Intake Indoor unit operates as FAN mode.
* When supply air temperature is setting temperature 3C or over, fresh air intake indoor unit operates as FAN mode.
* For more connectivity option please contact supplier.

55

MMD-AP0481HFE to AP0961HFE
Long hole for M10 hanging bolt
Type

Hole dia.-Width x Length

0481

4-12 x 40

0721, 0961

4-12 x 92

1328
Hanging bolt pitch 1288

100

Hanging bolt pitch B

1262

600

600

Refrigerative piping work


example at local site

Check port

Refrigerant pipe connecting port


(Gas pipe M)
Electric parts box (With cover)

145.5

492

370
Discharge port connecting flange (K)
(Accessory for main unit of product)

23
60

35

Suction port

Suction port connecting flange (L)


(Accessory for main unit of product)

1262
Drain pipe connecting port

Model MMD-

(Unit: mm)

704
850

47

81

Blow-off port
Discharge temp sensor

528.5

406

51

216 150

41

Refrigerant pipe
connecting port
(Liquid pipe N)

AP0961HFE

1392

1260

250

250

250

250

250

250

250

250

10-M6

10-M6

22.2 brazing

12.7 flare

AP0721HFE

1392

1260

250

250

250

250

250

250

250

250

10-M6

10-M6

22.2 brazing

12.7 flare

AP0481HFE

892

810

215

107.5

107.5

215

250

250

8-M6

6-M6

15.9 flare

9.5 flare

Options
Filter chamber
TCB-FCY51DFE
TCB-FCY100DE
Long life prefilter
TCB-PF3DE
TCB-PF4D-1E

High-efficiency filter 65
TCB-UFM3DE, TCB-UFM4D-1E
Drain pump kit
TCB-DP32DFE

High-efficiency filter 90
TCB-UFH7DE, TCB-UFH8D-1E

5
53

56

Mini-SMMS
Superior EER & COP (4.61 COP for 4HP).
Quiet Operation ( Noise level 49dB(A) for 4HP).
Upto 9 indoors may be connected ( 6HP Outdoor Model ).
DC Twin rotary compressor delivering higher efficiency.
Wide range of indoor units 15 types and different sizes.
Compact design ( approx 70% smaller than SMMS equal capacity
outdoor ).
MCY-MAP

1HT

Full range of SMMSi Controls available


.

Piping Diagram

Height between
indoor and outdoor
units ( Outdoor unit
higher than indoor
units)

When PMV Kit is not used


(Outdoor unit higher than indoor unit)

When PMV Kit is used


(Outdoor unit higher than indoor unit)

Not used

Piping length

Used

180

Maximum pipe extension (Liquid pipe, real length)


Piping section : L1+L2+a+b+c

150

125

Farthest piping length (Equivalent length)


Piping section : L1+L2+C

80

Height difference

(Outdoor unit lower than indoor units)

PMV Kit (Outdoor unit lower than indoor units)

30

Height between indoor and outdoor units


(Outdoor unit higher than indoor units)
Piping section : H

30

20

Height between indoor and outdoor units


(Outdoor unit lower than indoor units)
Piping section : H

20

54
57
Technical specifications
Outdoor Unit

MCY-MAP0401HT
4 HP

HP

Cooling capacity
EER
Heating capacity
COP

MCY-MAP0501HT
5 HP

MCY-MAP0601HT
6 HP

kW

12.1

14.0

15.5

W/W

4.29

4.03

3.35

kW

12.5

16.0

18.0

W/W

4.61

4.0

3.71

Air Flow

m3/h

5820

6120

6420

Sound pressure level

dB(A)

C/H

49/50

50/52

51/53

Sound power level

dB(A)

C/H

66/67

67/69

68/70

Dimensions (HxWxD)

mm

Weight

1340x900x320

kg

117

Compressor type

Twin Rotary

Refrigerant charge R410A

kg

Suction line type - diameter

In

Liquid line type - diameter

in

7.2

Flare - 5/8
Flare - 3/8

Brazing - 3/4
Flare - 3/8

Maximum equivalent length separation*

125

Maximum actual piping separation*

100

Maximum total pipe length*

180

Maximum lift (indoor unit above/below)

20/30

Operating range - db

CO

-5~43

Operating range - wb

HP

-15.0~15.5

Power supply

V-ph-Hz

230-1-50

* when PMV Kit is used: Maximum equivalent length separation (80 m); Maximum actual piping separation (65 m); Maximum total pipe length (150 m)

Indoor Connectivity Table


Model Name

Size

Cooling
Capacity

heating
Capacity

Number of
indoo units
Max

Total capacity on connectable indoor


units
Min
Max

MCY-MAP0401HT

4 HP

12.1kW

12.5kW

3.2HP

5.2HP

MCY-MAP0501HT

5 HP

14.0kW

16.0kW

4.0HP

6.5HP

MCY-MAP0601HT

6 HP

15.5kW

18.0kW

4.8HP

7.8HP

Single VRF indoor unit capacity of maximum 5HP can be connected.

PMV kit

The PMV kit is an option for super-silent operation, available for hotel rooms and residential
applications where noise levels are critical.
Ease of installation
ntegral condensate pump
PMV Kit Model Name

Indoor unit capacity code

RBM-PMV0361E

0.8 1 1.25 HP

RBM-PMV0362E

For new High wall MMK-AP***3H - 0.8 1 1.25 HP

RBM-PMV0901E

1.7 2 2.5 HP

RBM-PMV0902E

For new High Wall MMK-AP***3H - 1.7 2 2.5 HP

PMV Kit Compatibility Table


Model
Compact 4 Way Cassette

HP

0.8

1.0

1.3

1.7

2.0

2.5

kW

2.2

2.8

3.6

4.5

5.6

7.1

4-Way Cassette
2-Way Cassette
1-Way Cassette

Standard Ducted
Slim Ducted
High Static Duct
Ceiling
High Wall

Floor Cabinet

Floor Concealed
Floor Standing

3.0
8.0

3.2
9.0

4.0
11.2

5.0
14.0

55
5

58

SHRM-i - Super Heat Recovery Multi System-i


Multiple (Two/Three) Inverter Heat Recovery VRF.
The three-pipe VRF Super Heat Recovery Multi System (SHRM-i) delivers
simultaneously cooling and heating.
Exceptional energy efficiency COP of 4.4 for 22.4kW.
Compact ow selector unit: it automatically adjusts the temperature either
by unit or by area.

MMY-MAP

Installation Flexibility : Three Pipe connection allows installation height


variation of 40 meters ( Equivalent to 10 story building ).

4FT8-E

Active Oil Management system : As a system, it has more than 1 compressor.


This running compressor can get oil and refrigerant from other compressor or
modular quickly without any additional power consumption. Full range of SMMSi
17
Controls available. Upto 48 Indoor units may be connected of different types
( 42HP Size ).

Flow selectors
RBM-Y1123FE

RBM-Y1803FE

Connectable indoor
unit capacity (HP)

Below 4.0

4.0 to below 6.4

Connectable indoor
units*

RBM-Y2803FE

Appearance

6.4 to 10.0 or less

*Only group operation is possible with 1 (or 2) remote controller.


*Connecion cable kit : RBC-CBK15FE

Branching joints
Y-shap e branching joint

Branch headers

O utdo or unit connection piping kit

Appearance

(4-branch headers)

Model name

Usage (HP)

(Classification according to
)
indoor unit capacity code

RBMBY55FE

Total
below 6.4

RBMBY105FE

RBMBY205FE

Total
Total 6.4
14.2 or
or more
more and
and
below
below
25.2
14.2

RBMBY305FE

RBMHY1043FE

RBMHY2043FE

Max. 4 branches
Total 25.2
or more

RBMHY1083FE

RBMHY2083FE

RBM-BT14FE

RBM-BT24FE

Max. 8 branches

Total
Total 14.2
14.2 or
Total
or more
Total
more and
below 14.2 and below below 14.2
below
25.2
25.2

Total below 26.0

Total 26.0 or more

56
59

System Diagram
3 Pipe (discharge gas/suction gas/liquid)
Outdoor unit
FS unit

Cooling

Heating

Piping Layout

4 pipe connection
(Outdoor - Outdoor)
3 pipe

FS unit
(Flow Selector unit)

Simultaneous
operation

Cooling

Cooling

Heating

Heating

Heating

16
60

Outdoor units

Capacity
Model name (MMY-)

8H P

10HP

MAP0804FT8-E

12HP

MAP1004FT8-E

14HP

MAP1204FT8-E

MAP1404FT8-E

Co oling capacity (kW)

22.4

28.0

33.5

40.0

Heating cap acity (kW)

25.0

31.5

37.5

45.0

Maximum number
of indoor units

13

16

20

23

Capacity

16HP

18HP

20HP

Model name (MMY-)

AP1614FT8-E

AP1814FT8-E

AP2014FT8-E

Units in combination
(MMY-)

MAP0804FT8-E
MAP0804FT8-E

MAP1004FT8-E
MAP0804FT8-E

MAP1004FT8-E
MAP1004FT8-E

22HP
AP2214FT8-E
MAP1204FT8-E
MAP1004FT8-E

24HP
AP2414FT8-E
MAP1404FT8-E
MAP1004FT8-E

26HP
AP2614FT8-E
MAP1404FT8-E
MAP1204FT8-E

28HP
AP2814FT8-E
MAP1404FT8-E
MAP1404FT8-E

Cooling capacity (kW)

45.0

50.4

56.0

61.5

68.0

73.0

78.5

Heating capacity (kW)

50.0

56.5

63.0

69.0

76.5

81.5

88.0

Maximum number
of indoor units

27

Capacity

30

33

37

40

43

47

30HP

32HP

34HP

36HP

38HP

40HP

42HP

Model name (MMY-)

AP3014FT8-E

AP3214FT8-E

AP3414FT8-E

AP3614FT8-E

Units in combination
(MMY-)

MAP1004FT8-E
MAP1004FT8-E
MAP1004FT8-E

MAP1204FT8-E
MAP1004FT8-E
MAP1004FT8-E

MAP1404FT8-E
MAP1004FT8-E
MAP1004FT8-E

MAP1204FT8-E
MAP1204FT8-E
MAP1204FT8-E

AP3814FT8-E
MAP1404FT8-E
MAP1204FT8-E
MAP1204FT8-E

AP4014FT8-E
MAP1404FT8-E
MAP1404FT8-E
MAP1204FT8-E

AP4214FT8-E
MAP1404FT8-E
MAP1404FT8-E
MAP1404FT8-E

Cooling capacity (kW)

85.0

90.0

96.0

101.0

106.5

112.0

118.0

Heating capacity (kW)

95.0

100.0

108.0

113.0

119.5

127.0

132.0

Maximum number
of indoor units

48

48

48

* Power: 3-phase 50 Hz 400V (380 - 415V)


* The source voltage must not fluctuate more than 10%.
* Rated conditions
Cooling: Indoor air temperature 27C DB/19C WB, outdoor air temperature 35C DB
Heating: Indoor air temperature 20C DB, outdoor air temperature 7C DB/6C WB

48

48

48

48

18

61

Outdoor unit specifications


Single units

Technical specifications
Equivalent HP

M o del name
Outdoor unit type
1
Cooling capacity (*
)
1
Heating capacity (*
)
Power supply (*2)

(M M Y-)

8H P
MAP0804FT8-E

(kW)
(kW)

Power consumption
(kW)
Cooling
EER (Energ y Efficiency Ratio)
Electrical
characteristics
Power consumption
(kW)
Heating
(*1)
COP (Coefficient of Performance)
External dimensions (Heig ht / Width / D epth)
(mm)
Total weig ht
(kg )
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
A ir volume
(m3/h)
Suction gas side
(mm)
Connecting
Discharge gas side
(mm)
Refrigerant piping
port
Liquid side
(mm)
diameter
Balance pipe
(mm)
Sound pressure level (Co oling /Heating )
(dB(A))

22.4
25.0
5.17
4.33
5.68
4.40
1,830 / 990 / 780
259
2.3 x 2
1.0
8,700
22.2
19.1
12.7
9.5
55.0 / 57.0

10HP
MAP1004FT8-E

Inverter
28.0
33.5
31.5
37.5
3-phase 4 wires 50Hz 400V (380-415V)
7.28
8.38
3.85
4.00
7.50
9.05
4.20
4.14
1,830 / 990 / 780
1,830 / 1,210 / 780
259
334
3.1 x 2
2.6 x 3
1.0
1.0
9,400
12,000
22.2
28.6
19.1
19.1
12.7
12.7
9.5
9.5
57.0 / 59.0
60.0 / 62.0

Combinations
M o del name
Outdoor unit type
O utdoor unit mo del
1
Cooling capacity (*
)
1
Heating capacity (*
)
Power supply (*2)

M M Y-

16HP
AP1614FT8-E

M M Y-M A P 0804FT8-E 0804FT8-E


(kW)
45.0
(kW)
50.0

Power consumption
(kW)
EER (Energy Efficiency Ratio)
Power consumption
(kW)
Heating
COP (Coefficient of Performance)
Total weig ht
(kg )
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
A ir volume
(m3/h)
Suction gas side
(mm)
Connecting
Discharge gas side
(mm)
Refrigerant piping
port
Liquid side
(mm)
diameter
Balance pipe
(mm)
Sound pressure level (Co oling /Heating )
(dB(A))

10.42
4.32
11.36
4.40

Cooling

259
2.3 x 2
1.0
8,700

259
2.3 x 2
1.0
8,700
28.6
22.2
19.1
9.5
58.0 / 60.0

18HP
AP1814FT8-E

20HP
AP2014FT8-E

Inverter
1004FT8-E 0804FT8-E 1004FT8-E 1004FT8-E
50.4
56.0
56.5
63.0
3-phase 4 wires 50Hz 400V (380-415V)
12.45
14.56
4.05
3.85
13.18
15.00
4.29
4.20
259
259
259
259
3.1 x 2
2.3 x 2
3.1 x 2
3.1 x 2
1.0
1.0
1.0
1.0
9,400
8,700
9,400
9,400
28.6
28.6
22.2
22.2
19.1
19.1
9.5
9.5
59.5 / 61.5
60.0 / 62.0

Combinations

40.0
45.0
11.30
3.54
12.70
3.54
1,830 / 1,210 / 780
334
3.1 x 3
1.0
13,000
28.6
22.2
15.9
9.5
62.0 / 64.0

22HP
AP2214FT8-E
1204FT8-E 1004FT8-E
61.5
69.0
15.66
3.93
16.55
4.17
334
259
2.6 x 3
3.1 x 2
1.0
1.0
12,000
9,400
34.9
28.6
19.1
9.5
62.0 / 64.0

Technical specifications
Equivalent HP

M o del name
Outdoor unit type
Outdoor unit mo del
1
Cooling capacity (*
)
1
)
Heating capacity (*
Power supply (*2)

M M YM M Y-M A P
(kW)
(kW)

Power consumption
(kW)
EER (Energy Efficiency Ratio)
Power consumption
(kW)
Heating
COP (Coefficient of Performance)
Total weig ht
(kg )
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
A ir volume
(m3/h)
Suction g as side
(mm)
Connecting
Discharge gas side
(mm)
Refrigerant piping
port
Liquid side
(mm)
diameter
Balance pip e
(mm)
Sound pressure level (Co oling /Heating )
(dB(A))

Electrical
characteristics 1(*)

14HP
MAP1404FT8-E

Technical specifications
Equivalent HP

Electrical
characteristics 1(*)

12HP
MAP1204FT8-E

Cooling

24HP
AP2414FT8-E

26HP
AP2614FT8-E

28HP
30HP
AP2814FT8-E
AP3014FT8-E
Inverter
1404FT8-E 1004FT8-E 1404FT8-E 1204FT8-E 1404FT8-E 1404FT8-E 1004FT8-E 1004FT8-E 1004FT8-E
68.0
73.0
78.5
85.0
76.5
81.5
88.0
95.0
3-phase 4 wires 50Hz 400V (380-415V)
18.58
19.48
21.98
22.26
3.66
3.75
3.57
3.82
20.20
21.35
24.60
22.70
3.79
3.82
3.58
4.19
334
259
334
334
334
334
259
259
259
3.1 x 3
3.1 x 2
3.1 x 3
2.6 x 3
3.1 x 3
3.1 x 3
3.1 x 2
3.1 x 2
3.1 x 2
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
13,000
9,400
13,000
12,000
13,000
13,000
9,400
9,400
9,400
34.9
34.9
34.9
34.9
28.6
28.6
28.6
28.6
19.1
22.2
22.2
22.2
9.5
9.5
9.5
9.5
63.5 / 65.5
64.5 / 66.5
65.0 / 67.0
62.0 / 64.0

19
5

62

Combinations

Technical specifications
Equivalent HP

M o del name
Outdoor unit type
O utdoor unit mo del
1
Cooling capacity (*
)
Heating capacity (1*)
2
Power supply (* )

M M YM M Y-M A P 1204FT8-E
(kW)
(kW)

Power consumption
(kW)
EER (Energy Efficiency Ratio)
Power consumption
(kW)
Heating
COP (Coefficient of Performance)
Total weig ht
(kg )
Compressor
M otor output
(kW)
M otor output
(kW)
Fan unit
A ir volume
(m3/h)
Suction g as side
(mm)
Connecting
D ischarg e g as side
(mm)
Refrigerant piping
port
Liquid side
(mm)
diameter
Balance pip e
(mm)
Sound pressure level (Co oling /Heating )
(dB(A))

Electrical
characteristics 1(*)

32HP
AP3214FT8-E

Cooling

334
2.6 x 3
1.0
12,000

1004FT8-E
90.0
100.0
23.15
3.89
23.85
4.19
259
3.1 x 2
1.0
9,400
34.9
28.6
22.2
9.5
63.0 / 65.0

34H P
36HP
AP3414FT8-E
AP3614FT8-E
Inverter
1004FT8-E 1404FT8-E 1004FT8-E 1004FT8-E 1204FT8-E 1204FT8-E 1204FT8-E
96.0
101.0
108.0
113.0
3-phase 4 wires 50Hz 400V (380-415V)
25.86
25.35
3.71
3.98
27.70
27.35
3.90
4.13
259
334
259
259
334
334
334
3.1 x 2
3.1 x 3
3.1 x 2
3.1 x 2
2.6 x 3
2.6 x 3
2.6 x 3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
9,400
13,000
9,400
9,400
12,000
12,000
12,000
34.9
41.3
28.6
34.9
22.2
22.2
9.5
9.5
64.5 / 66.5
65.0 / 67.0

Combinations

Technical specifications
Equivalent HP

M o d e l nam e
Outdoor unit type
O u td o o r u n i t m o d e l
Cooling capacity (*1)
Heating capacity (*1)
Power supply (*2)

MMYMMY-MAP
(k W )
(k W )

Power consumption
(kW)
EER (Energy Efficiency Ratio)
Power consumption
(kW)
Heating
COP (Coefficient of Performance)
Total weight
(kg)
Compressor
Motor output
(kW)
Motor output
(kW)
Fan unit
Air volume
(m3/h)
Su c ti o n g as si d e
(mm)
Connecting Discharge gas side
(mm)
Refrigerant piping
port
(
mm)
L
i
q
u
i
d
s
i
d
e
diameter
B a l a n ce p i p e
(mm)
Sound pressure level (Cooling/Heating)
(dB(A))
Electrical
characteristics (*1)

38 H P
AP3814FT8-E
1404FT8-E

Cooling

334
3.1 x 3
1.0
13,000

1204FT8-E
106. 5
119. 5
27.85
3.82
30. 6 0
3.91
334
2.6 x 3
1.0
12,000
41. 3
34.9
22 . 2
9. 5
65. 5 / 67. 5

4 0 HP
42HP
AP4014T8-E
AP4214FT8 -E
Inverter
1204FT8-E 1404FT8-E 1404FT8-E 1204FT8-E 1404FT8-E 1404FT8-E 1404FT8-E
112.0
118.0
127.0
132.0
3-phase 4 wires 50Hz 400V (380-415V)
30. 4 0
33.10
3. 6 8
3. 56
3 4. 25
36.90
3.71
3. 58
334
334
334
334
334
334
334
2.6 x 3
3.1 x 3
3.1 x 3
2.6 x 3
3.1 x 3
3.1 x 3
3.1 x 3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
12,000
13,000
13,000
12,000
13,000
13,000
13,000
41. 3
41. 3
34.9
34.9
22 . 2
22 . 2
9. 5
9. 5
6 6. 5 / 68 . 5
67.0 / 69.0

*1 Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height.
*2 The source voltage must not fluctuate more than 10%.

Single unit (SHRM)

Technical specifications

Eq u i v a l e n t H P
M o d e l nam e
O u td o o r u n i t t y p e
Cooling capacity (*1)
Heating capacity (*1)
Power supply (*2)

(MMY-)
(k W )
(k W )

Power consumption
(kW)
Cooling
EER (Energy Ef f icienc y Ratio)
Electrical
characteristics
Power consumption
(kW)
Heating
(*1)
COP (Coefficient of Performance)
External dimensions (Height / Width / Depth)
(mm)
Total weight
(kg)
Co m p r e s s o r
M o to r o u t p u t
(k W )
M o to r o u t p u t
(k W )
Fan unit
A i r vo l u m e
(m3/h)
Suction gas side
(mm)
Connecting
Discharge gas side
(mm)
Refrigerant piping
port
Liquid side
(mm)
diameter
Balance pipe
(mm)
S o u n d p r e s s u r e l e ve l
(dB(A))

12HP
MAP1202FT8-E
Inver ter unit
33.5
35.5
3-phase 4 wires 50Hz 400V (380 - 415V )
12.90
2.6 0
9.65
3.68
1,800 / 990 / 750
263
4.2 x 2
0.60
10,500
28.6
19.1
12.7
9.5
59.0

Note: SHRM is for use as a standalone unit


and cannot be combined with SHRM-i.

20

63
Model: MMY-MAP0804FT8-E, MAP1004FT8-E
60

100

755
(Anchor bolt pitch)

670

610

790

(including steady leg)

Foundation

4-15x20
(Long hole)
100

990

60

700

(Anchor bolt hole pitch)

780

755
(anchor bolt pitch)

Mounting surface of bottom plate

Foundation

1595

1830

50

700
(Anchor bolt hole pitch)

500

85

2-60x200 square hole


(for freight handling)

(220)*1

213
219
257

687

(75)*1

L-shape pipe
Balance pipe connecting port
9.5

Refrigerant pipe connecting port


(Liquid side) 12.7

(Note)
1. If there is an obstacle at the upper side of the outdoor unit,
Refrigerant pipe connecting port
set the top end of the outdoor unit 2000mm apart from the obstacle.
(Discharge gas side) 19.1
2. Limit the height of the obstacle surrounding the outdoor unit to
800mm or less from the bottom end of the outdoor unit.
3. If a locally procured pipe is drawn horizontally from the front of the
outdoor unit to a traversing pipe, keep a minimum 500mm between the
outdoor unit and the traversing pipe.

Refrigerant pipe connecting port


(Suction gas side) 22.2

*1 Recommended cutting
position of L-shape pipe

(Unit: mm)

Model: MMY-MAP1204FT8-E, MAP1404FT8-E

755
(Anchor bolt pitch)

4-15x20 (Long hole)

60

22.2

670

19.1

15.9

100

12.7

610

MAP1204FT8-E
MAP1404FT8-E

Mounting surface of bottom plate


Foundation

B
780
790
(Including steady leg)

755
(Anchor bolt pitch)

Applied model (MMY-)

920 (Anchor bolt hole pitch)

60

100

1210
920

Foundation

1595

(75)*1

85

(220)*

687

1830

50

(Anchor bolt hole pitch)

620

2-60x200 square hole


(for freight handling)

Balance pipe connecting port


9.5

(Note)
1. If there is an obstacle at the upper side of the outdoor unit,
set the top end of the outdoor unit 2000mm apart from the obstacle.
2. Limit the height of the obstacle surrounding the outdoor unit to
800mm or less from the bottom end of the outdoor unit.
3. If a locally procured pipe is drawn horizontally from the front of the
outdoor unit to a traversing pipe, keep a minimum 500mm between the
outdoor unit and the traversing pipe.

L-shape pipe

Refrigerant pipe connecting port


(Liquid side) A

Refrigerant pipe connecting port


(Suction gas side) 28.6

Refrigerant pipe connecting port


(Discharge gas side) B
*1 Recommended cutting
position of L-shape pipe

(Unit: mm)

21
5

64
Model : MMY-MAP1202FT8-E (SHRM)

Foundation

Refrigerant pipe
connecting port
(Suction gas side) 28.6

500
2-60x150 square hole
(for freight handling)

(Note)
1. If there is an obstacle at the upper side of the outdoor unit,
set the top end of the outdoor unit 2000mm apart from the obstacle.
2. Limit the height of the obstacle surrounding the outdoor unit to
800mm or less from the bottom end of the outdoor unit.
3. If a locally procured pipe is drawn horizontally from the front of the
outdoor unit to a traversing pipe, keep a minimum 500mm between the
outdoor unit and the traversing pipe.

*1

88

201

700

1640

1800

165

700
(Anchor bolt hole pitch)

Foundation

755
(Anchor bolt pitch)

80
630

610

990

80

4-15x20
(Long hole)

100

700
(Anchor bolt hole pitch)

790
(Including steady leg)

750
755
(Anchor bolt pitch)

100

Mounting surface of bottom plate

Refrigerant pipe
connecting port
(Discharge gas side) 19.1

Refrigerant pipe
connecting port
(Liquid side) 12.7

*1 Recommended cutting
position of L-shape pipe

(Unit: mm)

65

Refrigerant piping design


Allowable Length of Refrigerant Pipes and Allowable Height Difference between Units

D
Follower unit

A
B
C
Header Follower Follower
unit
unit
unit

Height
difference
between
outdoor
units
H3 5 m

Ld
La

Lb

Height
difference
between
outdoor
and indoor
units:
H1 70 m

Main piping L1

LA

Lc

Outdoor unit connecting pipes

Outdoor unit

LB

Outdoor unit connection piping kit


(For linking of outdoor units)
The longest piping between outdoor units:
L0 25 m

Branching header
Indoor unit connecting
pipe
Indoor unit
a
b

First branching
section

L3

L7

Y-shaped branching
joint

The longest piping length: L 235 m


The longest piping length from the rst branch: Li 90 m
Y-shaped
branching joint
f

Height
difference
between
indoor units:
H2 40 m

L6

L5

L4

Indoor unit
(j)

66

System Restriction
Outdoor unit combination

Up to 4 units

Total capacity of outdoor units

Up to 48 HP

Indoor unit connection

Up to 48 units

Total capacity of indoor units


(varies depending on the height difference between indoor units.)

H2 15m

135% of outdoor units capacity

15m < H2

105% of outdoor units capacity

Cautions for Installation

Set the outdoor unit rst connected to the bridging pipe to the indoor units as the header unit.
Install the outdoor units in order of their capacity codes: A (header unit) B C D
When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit and
those to indoor units at a right angle as shown in gure 1 on INSTALLATION MANUAL (6. INSTALLATION OF
THE OUTDOOR UNIT). Do not connect them as in gure 2 on INSTALLATION MANUAL (6. INSTALLATION
OF THE OUTDOOR UNIT).

Allowable Length and Allowable Height Difference of Refrigerant Piping


Item
Total extension
of pipe (liquid
pipe, real length)

Less than 96kW


96kW or more

Farthest piping length L (1)

Pipe
length

Height
difference

Main piping length

Less than 34HP or less

Allowable
value

Pipes

300m

LA + LB + La + Lb + Lc + Ld + L1 +
L2 + L3 + L4 + L5 + L6 + L7 +
a+b+c+d+e+f+g+h+i+j

34HP or more

500m

Equivalent length

235m

Real length

190m

LA + LB + Ld + L1 +
L3 + L4 + L5 + L6 + j

Equivalent length

120m (2)

L1

Real length

100m (2)

Farthest equivalent piping length from the rst branch Li1)


(

90m (3)

L3 + L4 + L5 + L6 + j

Farthest equivalent piping length between outdoor units L01)


(

25m

LA + LB + Ld (LA + Lb, LA + LB + Lc)

Maximum equivalent piping length of pipes connected to


outdoor units

10m

Maximum real length of pipes connected to indoor units

30m

a, b, c, d, e, f, g, h, i, j

Maximum equivalent length between branching sections

50m

L2, L3, L4, L5, L6, L7

Upper outdoor units

70m (4)

Lower outdoor unit

40m (5)

Height between indoor units H2

40m

Height between indoor units H3

5m

Height between outdoor


and indoor units H1

La, Lb, Lc, Ld

1: Farthest outdoor unit from the rst branch: (D), farthest indoor unit: (j)
2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 70m (real length 50m) or less.
3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m.
4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m.
5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.

67

Selection of refrigerant piping


6 Header branching pipe

Branching piping
Follower
unit 3

Follower
unit 1 Header unit

Follower
unit 2

Outdoor
unit

1 Outdoor unit
connecting
piping

Balance pipe
9.5
1st branching
1
section

Indoor unit
branching
joint
4

7 Branching joint for

Main connecting
piping between
outdoor units

6 Y-shape

3 Main piping
2

Indoor unit connecting piping

outdoor unit

Indoor unit
connecting piping
Indoor unit

Pipe size of outdoor unit (Table 1)


Model name MMYMAP0804*
MAP1004*
MAP1204*
MAP1404*
MAP1604*

Gas side
22.2
22.2
28.6
28.6
28.6

Liquid side
12.7
12.7
12.7
15.9
15.9

Connecting pipe size between outdoor units (Table 2)

Total capacity code of outdoor units at


downstream side * 1
16 to below 22
22 to below 26
26 to below 36
36 or more
3

Gas side
28.6
34.9
34.9
41.3

Liquid
side
15.9
15.9
19.1
22.2

Balance
pipe
9.5

Y-shape branching
joint *2 *3 *8

Branching header
*2 *3 *6 *8

Pipe size between branching sections (Table 4)* 5

SMMS-i 8HP to 48HP


Total capacity code of indoor
units at downstream side * 1
2.4 or less
2.4 to below 6.4
6.4 to below 12.2
12.2 to below 20.2
20.2 to below 35.2
35.2 or more

Gas side
12.7
15.9
22.2
28.6
34.9
41.3

Liquid side
9.5
9.5
12.7
15.9
19.1
22.2

Total capacity code of indoor unit * 1


Below 6.4
6.4 to below 14.2
14.2 to below 25.2
25.2 or more
For 4
Below 14.2
14.2 to below 25.2
branching
For 8
Below 14.2
14.2 to below 25.2
branching

Total
capacity
code of
outdoor unit
Branching Below 26
joint for
outdoor
unit
26 or more

Model name
RBM-BY55E
RBM-BY105E
RBM-BY205E
RBM-BY305E
RBM-HY1043E
RBM-HY2043E
RBM-HY1083E
RBM-HY2083E

Selection of branching joint for outdoor unit (Table 7)

Size of main pipe (Table 3)

Total capacity code of all


Gas side
Liquid side
outdoor units * 1
B elow 6
15 .9
9 .5
6 to below 8
19.1
9.5
8 to below 12
22.2
12.7
12 to below 14
28.6
12.7
14 to below 22
28.6
15.9
22 to below 36
34.9
19.1
36 to below 46
41.3
22.2
41.3
22.2
46 or more *7
Determine thickness of the main pipe according to capacity of the outdoor units.
4

Selection of branching section (Table 6)

Joints
Gas
(Y-shape)
31.8

Liquid
(T-shape)

Balance
(T-shape)

19.1

9.5

28.6

25.4 19.1 19.1


38.1

38.1

9.5

22.2

9.5

9.5

28.6 22.2 22.2

9.5

9.5

Model
name
RBMBT14E
RBMBT24E

Minimum wall thickness for R410A application (Table 8)


Soft

OK
OK
OK
OK
No Good* 4
No Good* 4
No Good* 4
No Good* 4
No Good* 4

Half hard or hard OD (Inch) OD (mm)


OK
OK
OK
OK
OK
OK
OK
OK
OK

1/4''
3/8''
1/2''
5/8''
3/4''
7/8''
1.1/8''
1.3/8''
1.5/8''

6.35
9.52
12.70
15.88
19.05
22.20
28.58
34.92
41.28

Minimum wall
thickness (mm)
0.80
0.80
0.80
1.00
1.00
1.00
1.00
1.10
1.25

If the total capacity code value of indoor units exceeds that of the outdoor units,
apply the capacity code of outdoor units.
5

Piping of indoor unit (Table 5)

Capacity rank
005 type to Actual length 15 m or less
012 type Actual length exceeds 15 m
015 type to 018 type
024 type to 056 type
072 type to 096 type

*1
*2
*3
*4
*5
*6
*7
*8

Gas side
9.5
12.7
12.7
15.9
22.2

Liquid side
6.4
6.4
6.4
9.5
12.7

Code is determined according to the capacity rank.


When using a branching joint for the 1st branch, select according to capacity code of the outdoor unit.
For 1 line after branching header indoor units with a maximum capacity code of 6.0 in total can be connected.
If the pipe size is 19.0 or more, use a suitable material as detailed in the installation manual.
If the piping size becomes over main piping size, select the size same as main piping.
When the first branch is a header with the outdoor total capacity
codes of 12 to 26, apply the model RBM- HY2043E(4-branch) o r RBMHY2083E(8-branch) regardless of the total capacity codes of the down-stream indoor units.
The maximum equivalent length of main pipe should be 70m or shorter.
When the sum of capacity code of indoor units exceeds the capacity code of outdoor units, select according to capacity code of the outdoor units.

59
5

68
Indoor unit accessories
Indoor unit

Parts Name

Model Name

Applied Model

Notes

Remarks

RBC-U31PG(W)-E
Ceiling panel
4-way air discharge
cassette type

Compact 4-way
Cassette (600x600) type

TCB-GFC1602UE

For fresh air inlet box

Auxiliary fresh air flange


Spacer for height adjustment

TCB-FF101URE2

For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)

TCB-SP1602UE

Height=50 mm

Air discharge direction kit

TCB-BC1602UE

Ceiling panel

RBC-UM11PG(W)E

Auxiliary fresh air flange

TCB-FF101URE2

Super long life filter

Auxiliary fresh air flange


Ceiling panel

Drain pump kit


Slim duct type

Auxiliary fresh air flange


Drain pump kit

Ceiling Type
Elbow piping kit

Concealed duct type


6 Series

*European market only

Spigot Shaped Flange

For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)

MMU-AP0182 to 0302WH

RBC-UW1403PG(W)-E
TCB-LF283UW-E

MMU-AP0362/0482/0562WH
MMU-AP0072 to 0152WH

TCB-LF803UW-E

MMU-AP0182 to 0302WH

TCB-LF1403UW-E

MMU-AP0362/0482/0562WH

TCB-FC283UW-E
TCB-FC803UW-E

MMU-AP0072 to 0152WH

TCB-FC1403UW-E

MMU-AP0362/0482/0562WH

TCB-FF151US-E

MMU-AP***2WH

For fresh air intake by using the knockout hole of indoor unit. (dia.=150mm)

RBC-UY136PG

MMU-AP***4YH-E

Required accessory

MMU-AP0182 to 0302WH

Required accessory

Dust collecting effect: 50%


(Weight method)

Use with TCB-FC803UW-E


Use with TCB-FC1403UW-E

For super long life filter

MMU-AP***4SH-E
For easy fresh air intake by using the knockout hole of indoor unit. (dia.=100 mm)

TCB-UFM1D-1E

MMD-AP0184H-E

TCB-UFM2D-1E (2 pcs.)
TCB-UFM1D-1E (2 pcs.)

MMD-AP0244/0274/0364H-E

TCB-UFM3DE

MMD-AP0724/0964H-E

TCB-UFH5D-1E

MMD-AP0184H-E

TCB-UFH6D-1E (2 pcs.)

MMD-AP0244/0274/0364H-E

TCB-UFH5D-1E (2 pcs.)

MMD-AP0484H-E

TCB-UFH7DE

MMD-AP0724/0964H-E

TCB-PF1D-1E

MMD-AP0184H-E

TCB-PF2D-1E (2 pcs.)

MMD-AP0244/0274/0364H-E

TCB-PF1D-1E (2 pcs.)
TCB-PF3DE

MMD-AP0484H-E
MMD-AP0724/0964H-E

TCB-FCY21DE

MMD-AP0184H-E

TCB-FCY31DE

MMD-AP0244/0274/0364H-E

TCB-FCY51DE

MMD-AP0484H-E

TCB-FCY100DE
TCB-DP31DE

MMD-AP0724/0964H-E

TCB-DP32DE
TCB-FF101URE2

MMD-AP0724/0964H-E

Stand-up 330 or less


(from bottom face of ceiling)

MMD-AP***4SPH-E

For fresh air intake by using the knockout hole of indoor unit. (dia.=100mm)

MMC-AP0154/0184H-E

Stand-up 600 or less


(from bottom face of ceiling)

TCB-DP22CE2

Use with TCB-FC283UW-E

Required accessory

RBC-US21PGE
TCB-FF101URE2

Filter chamber

Required accessory

RBC-UW803PG(W)-E

Auxiliary fresh air flange

Long life prefilter

Air direction charge by cutting off air discharge port (3 pcs)


MMU-AP***4MH-E
MMU-AP0072 to 0152WH

TCB-BUS21HWE

High-efficiency filter 90

MMU-AP***2H

RBC-UW283PG(W)-E

Front air discharge unit

High-efficiency filter 65

Concealed duct high


static pressure type

For fresh air intake by using the knockout hole of fresh air filter chamber. (dia.=100 mm) Use with TCB-GFC1602UE

TCB-GB1602UE

Fresh air filter chamber

Filter chamber

1-way air discharge


cassette type

Required accessory

RBC-U31PGS(WS)-E*

Ceiling panel

2-way air discharge


cassette type

RBC-U31PGS(W)-E*

Fresh air inlet box

MMD-AP0484H-E

MMD-AP0481H-E to 0484H-E

MMC-AP0244 to 0484H-E

TCB-KP12CE2

MMC-AP0154/0184H-E

TCB-KP22CE2
TCB-SF56C6BE

MMC-AP0244 to 0484H-E
MMD-AP0076 to 0186BHP-E

TCB-SF80C6BE

MMD-AP0246 to 0306BHP-E

TCB-SF160C6BE

MMD-AP0366 to 0566BHP-E

Use with TCB-FCY21DE


Dust collecting effect: 65%
(NBS Colorimentric method)

Use with TCB-FCY31DE


Use with TCB-FCY51DE
Use with TCB-FCY100DE
Use with TCB-FCY21DE

Dust collecting effect: 90%


(NBS Colorimentric method)

Use with TCB-FCY31DE


Use with TCB-FCY51DE
Use with TCB-FCY100DE
Use with TCB-FCY21DE

Dust collecting effect: 50%


(Weight method)

Use with TCB-FCY31DE


Use with TCB-FCY51DE
Use with TCB-FCY100DE

For high efficiency filter or long life prefilter.

Needed when drain pump kit is used

For multi duct connection at unit outlet.

Use with TCB-KP12CE2


Use with TCB-KP22CE2

60

69
Indoor unit accessories
Indoor unit

High-efficiency filter 65

High-efficiency filter 90
Fresh air intake
indoor unit type

Model Name

Parts Name

Long life prefilter

Filter chamber
Drain pump kit

Applied Model

Notes

Remarks

TCB-UFM3DE

MMD-AP0721/0961HFE

TCB-UFM4D-1E

MMD-AP0481HFE

TCB-UFH7DE

MMD-AP0721/0961HFE

TCB-UFH8D-1E

MMD-AP0481HFE

TCB-PF3DE

MMD-AP0721/0961HFE

TCB-PF4D-1E

MMD-AP0481HFE

TCB-FCY51DFE

MMD-AP0481HFE

TCB-FCY100DE

MMD-AP0721/0961HFE

TCB-DP32DFE

MMD-AP0481/0721/0961HFE Stand-up 330 or less (from bottom face of ceiling)

Dust collecting e ect: 65%


(NBS Colorimentric method)

Use with TCB-PF3DE

Dust collecting e ect: 90%


(NBS Colorimentric method)

Use with TCB-PF3DE

Use with TCB-PF4D-1E

Use with TCB-PF4D-1E


Use with TCB-FCY100DE

Dust collecting e ect: 50%


(Weight method)

Use with TCB-FCY51DFE

For high-efficiency filter or long life prefilter

Combination Pattern
1) Accessory for 4-way air discharge cassette type:
combination pattern

Ceiling panel

Fresh air inlet box


+
Fresh air lter
chamber

Fresh air lter


chamber

Auxiliary fresh air


flange

Spacer for height


adjustment

Air discharge
direction kit

OK

OK

OK

OK

OK

Ceiling panel

Fresh air inlet box + Fresh airfilter chamber

OK

OK

OK

OK

Fresh airfilter chamber

OK

OK

OK

OK

Auxiliary fresh air flange

OK

OK

OK

OK

OK

Spacer for height adjustment

OK

OK

OK

OK

Air discharge direction kit

OK

OK

OK

OK

2) Accessory for concealed duct high static pressure


type/fresh air intake indoor unit type: combination
pattern

High-efficiency filter 65 High-efficiency filter 90


-

OK

Long life prefilter

Filter chamber

Drain pump kit

OK

OK

OK

OK

OK

OK

OK

OK

High-efficiency filter 65

High-efficiency filter 90

Long life pre filter

OK

OK

Filter chamber

OK

OK

OK

Drain pump kit

OK

OK

OK

OK

OK
OK

70

61
71

Remote Controller - Wireless Kit


Wireless Handset
Easy to use remote control with a compact button layout
and a fresh new design.
Setting operation mode: cool, heat, dry, fan.
Setting of temperature and fan speed
Swing louver or fix louver position.
Hi power function for an extra strong air flow.
Comfort sleep operation: to save energy the air flow is
controlled automatically; depending on timer the indoor
unit turns off automatically after 1,3 5 or 9 hrs.
Quiet Mode: the indoor unit operates at a super low fan
speed level for extra quiet operation.

Control by 2 remote controllers is available.


Check code display
* The wireless remote control cannot be connected to
Concealed duct high static pressure type or Fresh air
intake indoor unit type.

RBC-AX32U(W)-E/RBC-AX32U(WS)-E
Integral receiver
(For 4-way air discharge cassette)

RBC-AX23UW(W)-E
Integral receiver
(For 2-way air discharge cassette)

RBC-AX32CE2
Integral receiver (For Ceiling,
1-way air discharge cassette
(MMU-AP***4SH-E)

TCB-AX32E2
Stand alone receiver (For 4-way air discharge cassette,
Compact 4-way cassette, 2-way air discharge cassette,
Ceiling, Concealed duct standard, Slim duct, Floor standing
cabinet, Floor standing, 1-way discharge cassette
(MMU-AP***4YH-E)

Remote Controller - Wired


Remote controller with weekly timer (7-day timer function)
RBC-AMS41E
Clock display
Schedule timer:
Possible to program schedule timer (7-day timer) function
Possible to program 8 functions for each day of the week
* The following items can be set in program: Operation time, Operation start/stop, Operation mode,
Temperature setting, Restriction on button operation

Lite - Vision Plus Remote Controller


The RBC-AMS51E is the new local remote controller with a built in 7-Day Timer. It features a backlight
display with operation instructions shown in 11 languages.

RBC-AMS51E-ES : English, Spanish,


Portuguese, French, Dutch, German.
RBC-AMS51E-EN : English, Italian,
Polish, Greece, Russian, Turkish.
Function:
Operation On/Off
Operation Mode.
Set Temperature
Air Flow Control
Air Direction Control
Programmable Button Restrictions.
Error Code
Filter Sign

Features:
Possibility to set and display the room name to
easily set-up and monitor the working parameters.
New Modern and desirable controller design
with menu driven display.
Save mode by schedule timer to optimize
energy consumption.
Room temperature display always available.
Two Hot Keys (F1, F2) for easy operation
of air conditioner functions.
Easy to read layout including display of Indoor
Unit Model Name and serial number.
Built-in backup power. Settings are kept in
memories up to 48 hours in case of power failure
Remote TA sensor available in controller.
Can be connected to a single Indoor Unit
or a group of up to 8 Indoor Units.

Up to 8 indoor unit

Local control wiring diagram

62
72

Central Controller
ON-OFF controller
TCB-CC163TLE2

Individual control of up to 16 indoor units.


Connection by 2 remote controllers is available.
Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer.

Central remote controller


TCB-SC642TLE2

Individual control of up to 64 indoor units.


Individual control for max. 64 indoor units divided into 1 to 4 zone (Up to 16 indoor
units for each zone)
Up to 16 outdoor header units are connectable
4 types of central control settings to inhibit individual operation by remote
controller can be selected.
Setting for one of 1 to 4 zones is available.
Usable with other central control devices (Up to 10 central control devices in one
control circuit)
Two control mode selectivity (Central controller mode ) Remote controller mode
Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer.

Schedule Timer
TCB-EXS21TLE

Schedule timer mode


6 programmings per day
Enabling 8 groups to be programmed
A maximum of 64 indoor units can be controlled
A maximum of 100 hours back-up power supply
Weekly timer mode
7 types of weekly schedule and 3 programmings per day
Can program off mode by one-minute units.

Compliant Manager
The Compliant Manager Controller is an advanced Central Control device that is used
for VRF Equipment and can be connected to up to 128 Indoor Units.

BMS-CM1280TLE
Function
Operation On/Off.
Operation Mode
Set TemperatSet Temperature
Air Flow Control
Air Direction Control
Error Code
Filter Sign

Advanced Zone Configuration.


External Input for Simultaneous Indoor Unit ON/OFF Control and external Alarm Input.
External Output for Operation status and Alarm Status.
4-Pattern Permit/Prohibit Functions.
Return Back Function Available.

Central Control Device

63
73

Advance control systems


Smart Manager with Data Analyzer
The Smart Manager has the same hardware Control Function as the BMS-CM1280TLE Controller, but also
has the ability of control from a Local Area Network and , with the use of an additional Interface, is
capable of Energy Monitoring and Report Creation Functions. This controller is ideal where advanced
control, Energy Monitoring, advanced scheduling or access to individual Air Conditioners is required from
networked computer systems.
Web Browser Control Software Features
List View available -Displays all Indoor Units from one screen
Set View available Shows Basic Indoor Unit settings on main screen g
Advanced Operation and Master schedule functions available
Up to 4 Concurrent users can be connected
Up to 32 User accounts can be programmed with different levels of access
(at least 1 must be administrator level)

BMS-SM1280ETLE

Power Meter Pulse signal

BMS-IFWH5E

RS-485 Network

TCC-Link Line 1
Digital Input Output signal

TCC-Link Line 2
BMS-IFDD03E

TCB-EXS21TLE
Schedule Timer

Digital Inputs Digital Outputs

TCB-PCNT30TLE2*

NETWORK HUB

* TCC-Link Adaptor for Digital/Super Digital Indoor Units.

Up to 32 User accounts
Max. 4 Concurrent Users

Equipment List
Device

Number of pieces

Description

BMS-SM1280ETLE

Up to 128 indoor unit can be connected to Smart Manager

BMS-IFDD03E

Up to 4 Boards

Interface for Digital Input & Outputs. Can connect up to 8 Power Meters per Board (Optional )

BMS-IFWH5E

Up to 4 Boards

Interface for Power Meter (Energy Monitoring Option only)

Number of pieces

Energy consumption history (days)


Description

Locally Procured Item


Device

Energy consumption comparison

Alarm list

Energy consumption history (hours)

Power Meter

Digital Energy Meter with Pulse Output ( Energy Monitoring Option only)

PC

For Operation Monitoring

Network Hub

For LAN Connection.

Energy consumption history (days)

T_12_CT_GEN_EN__print.indd 165

Energy consumption comparison

Alarm list

TOSHIBA | 165

02/03/12 14.31

Energy consumption history (Hours)

62
64
74

Advance control systems


Touch-screen controller
Touch-screen controller
Using the touch-screen controller provides a clear display and enables easy operation.
A maximum of 512 units are controllable using the one-touch controller.
Function
Operation monitoring
Operation control
Operation Schedule
Error Code
Alarm List
Energy monitoring/Billing
Digital I/O Signal Control

Touch-screen Controller
BMS-CT5120E

Up to 12

Up to 8

Up to 8

Relay Interface BMS-IFLSV4E


For TCS-NET

Relay Interface BMS-IFWH5E


For Energy Monitoring
(Optional)

Relay Interface BMS-IFDD03E


For Digital I/O
(Optional)

CONTROL WIRING
RS-485 Network

TCS-Net Relay I/F


BMS-IFLSV4E
TCC-Link Network

Energy Monitoring I/F


BMS-IFWH5E

Digital Input/Output I/F


BMS-IFDD03E

Power Meter
(Local Supply)
1 kWh/pulse or 10 kWh/pulse
(Pulse duration 50 to 1000 ms)
(Maximum 8 power meter per interface)

Digital I/O
Digital Input 1

Digital Input 8

Digital Output 1
Power Meter 1

Digital Output 4
Network Hub

Power Meter 8

PC for Energy Monitoring

65
75

Advance control systems


WEB Based Controller

WEB Based Controller


BMS-WB2561PWE
(Web Server/Gateway Server)

WEB Based Controller


BMS-WE01GTE
(Master Server)

Up to 8
Relay Interface BMS-IFLSV4E
For TCS-NET

WEB Based Controller


Signals and provides the following functions :
Operation monitoring
Operation control
Operation Schedule
Error Code
Alarm List
Energy monitoring/Billing
Digital I/O Signal Control
Connect the WEB server for every 256 indoor units,
and connect a gateway server upstream from the server.

Up to 4

Up to 4

Relay Interface BMS-IFWH5E


For Energy Monitoring
(Optional)

Relay Interface BMS-IFDD03E


For Digital I/O
(Optional)

Web Based Controller (Web Server System)


System diagram for
connecting 256FCUs or less
TCS-NET Interface
BMS-IFLSV4E

WEB Server
BMS-WB2561PWE

TCS-NET Interface
BMS-IFLSV4E

Local Supply

Web Based Controller (Master Server System)


System diagram for
connecting upto 2048FCU
TCS-NET Interface
BMS-IFLSV4E

Master Server
BMS-WB01GTE

Gateway
BMS-WB2561PWE

TCS-NET Interface
BMS-IFLSV4E

Gateway
BMS-WB2561PWE

Local Supply

66
76

Open Network systems


BACnet system
BACnet

The BACnet system operates in conjunction with the BAC net server.
Server uses object signals to provide the following functions:
Object signals command
ON/OFF
Mode: cool/heat/fan
Temperature setting
Central/local
Fan speed
Monitoring
ON/OFF etc.

Intelligent Server
BMS-LSV9E

Mode
Cool/heat/fan/failure
Temperature setting
Room temperature
Central/local, etc.

Relay Interface BMS-IFLSV4E


For TCS-NET

BACnet Server Software


BMS-STBN10E

BACnet IP
BMS-STBN10E
Local supply

RS-485

TCS-NET
Relay Interface
BMS-IFLSV4E

Main bus

Intelligent server
(BACnet server software required)
BMS-LSV9E

KNX Interface
KNX
The KNX interface manages the SMMS-i air conditioning system as a KNX
device to communicate with the custormer s Home automation.
Accessible to 64 units per one ,
Signals and provides the following functions:
ON/OFF
Mode: cool/heat/fan
Air flow and fan speed
Temperature setting
Filter reset

TO-AC-KNX-64

KNX Control Panel

Main bus
KNX Network

KNX Interface
TO-AC-KNX-64
Lighting

Blind &
Shutter

Electrical
appliance

Audio &
Video

67
77

Open Network systems


BACnet system
LonWorks LN Interface
The LonWorks interface manages the SMMS-i air conditioning system as
a Lon device to communicate with the custormers Building Management
System and to monitor operational status.
A maximum of 64 units are controllable per interface.
SNVT signal
Signals and provides the following functions:
Object signals command
ON/OFF
Mode: cool/heat/fan
Temperature setting
Central/local

LN Interface
TCB-IFLN642TLE

Monitoring
ON/OFF
Mode
Cool/heat/fan/failure
Temperature setting
Room temperature
Central/local, etc.

Main Bus
Local supply

LN Interface
TCB-IFLN642TLE

Modbus
Modbus
The Modbus interface manages the SMMS-i air conditioning system as a Modbus device to
communicate with the custormers Building Management System.
Accessible to 64 units per one TCB-IFMB641TLE, 15 TCB-IFMB641TLEs on one
Modbus Master (prepared by user).

Modbus Interface
TCB-IFMB641TLE

Signals and provides the following functions:


ON/OFF
Mode: cool/heat/fan
Air flow/Louver setting
Temperature setting
Filter reset
Accumulated operation time, etc.

Local supply

Main Bus

RS-485

Modbus Interface
TCB-IFMB641TLE

1. LonWorks: Registered trademark Echelon corporation


2. BACnet: ANSI/ASHRAE 135-1995, A data Communication Protocol for Building Automation and Control Networks.
3. Modbus is a registered trademark of Schneider E.

68
78

Application Controls
TCB-PCDM4E

Power peak-cut Control


Feature

Size: 71 x 85 (mm)

The upper limit capacity of the outdoor unit is restricted based on the outdoor power
peck selected setting.
* Install the optional
P.C. board in the
inverter assembly of
the outdoor header
unit.

Function
Two control settings are selectable by setting SW07 on the interface P.C. board on the
header outdoor unit.

TCB-PCMO4E

Size: 55.5 x 60 (mm)

Snowfall fan control


Feature

The upper limit capacity of the outdoor unit is


restricted based on the outdoor power peck
selected setting.

* Install the optional


P.C. board in the
inverter assembly of
the outdoor header
unit.

External master ON/OFF control


Feature

The outdoor unit starts or stops the system.

Night operation (Sound reduction) control


Feature

Sound level can be reduced by restricting the


compressor and fan speeds.

Operation mode selection control


Feature

The control can restrict the selectable operation


mode.

TCB-IFCB5-PE
This is an application control PC Board that is capable of providing two different
control functions when connected to a Toshiba Indoor Unit, these are:

Window Switch Function


Remote Location On/Off Controller

TCB-IFCB5-PE

Each time the window is opened (contact open) the Indoor Unit operation is turned Off and will not
operate again until the window is closed.
There are two possible operation selections for when the window is closed again.

Standard Function Mode

Standard Function Mode


The Indoor Unit operation remains Off.

Return Function Mode

Return Function Mode


The Indoor Unit will revert to the last setting before the window was opened.

69
79
TCB-PCIN4E
Size: 73 79 (mm)

* Install the optional


P.C. board in the
inverter assembly of
the outdoor header
unit.

Error/Operation output control

Feature
Enables external output of error and operation signals.

Compressor operation output


Feature

L1 : Operation monitoring lamp


L2 : Error monitoring lamp
Operation monitoring: Display relay is ON with
more than one indoor unit operation.
EMG monitoring: Display relay is ON when the
system is in error status.

Enables external signal output for each compressor


that is in operation within any given outdoor unit. This
feature provides a practical method for calculating
total operating times for each compressor.

Operating rate output


Feature

External output of system operating rates enables


remote monitoring of operating conditions.

TCB-IFCB-4E2
Remote location ON/OFF control box
Size: 200 170 66 (mm)

Feature
Start and stop of the air conditioner is possible by an
external signal and indication of operation/alarm
externally.
Operation

Monitoring
ON/OFF status (for indoor unit)
Alarm status (system & indoor unit stop)
ON/OFF command
Air conditioner can be turned ON/OFF by the
external signals.
The external ON/OFF signals will initiate the
signals shown below.

ON/OFF

Interface
Display
Remote Controller

Non-voltage
ON/OFF continuous signal

COM

TCB-PCNT30TLE2

Network adapter

Size: 85 52 (mm)
Install optional P.C.
board in E-parts of
the indoor unit.

Feature
Link adapter for 1:1 model to enable connection
to VRF system network.
1:1 model: Super digital inverter
Digital inverter
Used only for light commercial products

ON-OFF
control

Central
control
devices

Indoor unitIndoor unit

Indoor
control
P.C.board

Adaptor

ON-OFF Controller
TCB-CC163TLE2

Indoor unit

U3 U4
Indoor
control
P.C.board

Indoor
control
P.C.board
A

Remote controller

Controller
TCB-SC642TLE2
Connecting
terminal block
BLU

U3 U4
BLU
1 2
SMMS-i control wiring

1 2
CN40 (BIU)
CN51 (RED)

1:1 model
connection
interface

adapter
Indoor units

Digital Inverter
Super Digital Inverter
Outdoor unit

1
2
3
4
5

1
2
3
4
5

WHI
RED
RED
RED
RED

1
2
3
4
5

1 CN50 (WHI)
2
Indoor control
3
P.C.board
4
5

66
70
80

5
General Purpose Interface
General purpose interface
TCB-IFCG1TLE

Concept

TCC-LINK

Controls the operation status of each indoor unit.


ON/OFF control of peripheral equipment via the
relay point of Toshiba's BMS. (1pt only)
Provides 4-channel relay control, 6-channel digital
input, 2-channel analog voltage input and output,
and 2-channel temperature measurement functions
via Modbus I/F.

Programmable conjunction function


(HA)
Daiseikai

Sensor

Switches

Pump/
motor

Operation of specified indoor units can interlock


with input signal.

Lights

GSM Phone Control Interface

Concept

GSM phone control interface


TCB-IFGSM1E

GSM modem

ON/OFF control and status monitoring of the


air-conditioner via the SMS system of GSM mobile
phones.
Up to 5 mobile phone numbers can be registered for
on/off control and status monitoring.
Auto alarm transfer function for SMMS-i, SDI, DI.
Up to 5 mobile phone numbers can be registered for an
alarm signal output.

RC-232C

AC Adapter
Not required when CN61 is used

Indoor units connectors


Toshiba Indoor Units have a number of Connectors built in to allow for connection and control of external equipment and control/monitoring of the Air Conditioner
Cable Model Name

Function

Connector

Outline

TCB-KBCN32VEE

Fan output

CN32.

External Ventilation fan control from Remote controller.

TCB-KBCN60OPE

Option output

CN60

Operation status signal output (cooling, heating, fan, defrost, thermo-ON)

TCB-KBCN61HAE

Operation Input /
Output

CN61

External ON/OFF control, operation ON/ OFF status output, alarm status output

TCB-KBCN70OAE

Option error input

CN70

Alarm display on Remote controller by this input

TCB-KBCN73DEE

Demand input

CN73

Forced thermo-o control by this input

TCB-KBCN80EXE

Outside error input

CN80

Generate check code L30 (for 1 minutes continuously) to stop forcedly the operation

71
81
Control Devices
Model Number

Reference

Description

Used with

RBC-AMT32E

Wired Remote Controller

Main wired remote controller

VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units

RBC-AS41E

Simplified Wired Remote


Controller

As above but designed for hotel and domestic


applications

VRF and VRF Air-to-air heat exchanges with (DX coil) indoor units

NRC-01HE

Wired Remote Controller

Wired remote controller for Air-to-air heat exchanger,


including with DX coil and humidifiers models

New Air-to-air heat exchangers and Air-to-air heat exchangers with DX coil

TCB-EXS21TLE

Schedule timer

Operating in weekly timer mode or schedule timer


mode

VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units

RBC-AMS41E

Remote controller with


schedule timer

Enables to control indoor unit operation with schedule


timer (7-days) allowing to program 8 functions/day
+ clock display

VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units

RBC-AMS51E-EN
RBC-AMS51E-ES

Lite-Vision plus Remote


Controller

Local Controller with Multi-Language LCD display,


a built-in 7-Day timer, Energy Saving options and
return back function. EN =English, Italian, Polish,
Greek, Russian, Turkish.
ES = English, Spanish, Portuguese, French, Dutch,
German

VRF and VRF Air-to-air heat exchangers with (DX coil) indoor units

RBC-AX32CE2

Infra-red Remote Kit

Wireless remote controller

All ceiling units and one-way cassettes (SH series)

TCB-AX32E2

Infra-red Remote Kit

Wireless remote controller

All other units (including compact 4-way cassette

RBC-AX23UW(W)-E

Wireless remote unit kit

Wireless remote unit kit for 2-way cassette

2-way-cassette MMU-AP***2WH

RBC-AX32U(W)-E

Wireless remote unit kit

Wireless remote unit kit for 4-way cassette

RBC-U31PG(W)-E & RBC-U31PGS(W)-E panels for 4-way cassette indoors.

RBC-AX32U(WS)-E

Wireless remote unit kit

Wireless remote unit kit for 4-way cassette

With RBC-U31PGS(WS)-E panels for 4-way cassette indoors.

TCB-TC21LE2

Remote temperature sensor

Remote temperature sensor for cassette & duct

All VRF

TCB-SC642TLE2

Central Remote Controller

Enables the control of up to 64 individual units

All VRF indoor units.

TCB-CC163TLE2

On / Off Controller

Enables On / Off control (Max. 16 units)

All VRF indoor units.

TCB-IFCB5-PE

Remote location On / Off


Control Box

Enables remote location On / Off control

All VRF indoor units.

BMS-WB2561PWE

Web Based Controller


( Web Gateway )

Gateway server. Network Intranet connection, yearly


schedule, error message history, up to 256 IDUs

All VRF indoor units.

BMS-WB01GTE

Web Based Controller


( Web Server )

Web server. Network Intranet connection, yearly


schedule, error message history,up to 2048 IDUs
All VRF indoor units.

All VRF indoor units.

BMS-CM1280TLE

Compliant Manager

Enables full control of up to 128 indoor units

All VRF indoor units.

BMS-SM1280ETLE

Smart Manager with Data


analyzer

Enables full control of up to 128 indoor units with


Energy Monitoring and Advanced Control Options

All VRF indoor units.

72
82
Control Devices
Model Number

Reference

Description

Used with

BMS-TP0641ACE

Touch Screen Controller

Enables full control of up to 64 indoor units, ML

All VRF

BMS-TP5121ACE

Touch Screen Controller

Enables full control of up to 512 indoor units, ML

All VRF

BMS TP0641PWE

Touch Screen Controller

Enables full control of up to 64 indoor units with


BMS-electric billing, ML

All VRF

BMS-TP5121PWE

Touch Screen Controller

Enables full control of up to 512 indoor units with


electric billing, ML

All VRF

BMS-IFLSV4E

TCS-Net Relay Interface

Relay for integration to TCS-Net

Bacnet gateway, Touch-screens & Web based controller

BMS-IFWH5E

Energy monitoring relay


interface

Energy monitoring relay interface

Touch screen controller, Compliant manager, Web based controller,


Smart Manager

BMS-IFDD03E

Digital I/O relay interface

Digital I/O relay interface

Touch screen controller, Compliant manager, Web based controller,


Smart Manager

BMS-LSV9E

Intelligent Server

Bacnet Gateway

Requires software BMS-STBN08E & Interface BMS-IFLSV3E

BMS-STBN10E

BACnet

Server Software

Enables integration with BACnet

BMS-STCC06E

Intelligent Server Software

Software package for the intelligent server

All VRF indoor units.

TCB-IFLN642TLE

Lonworks Gateway

Allows control of 64 indoor units from a Lonworks


based BMS

All VRF indoor units.

TCB-IFMB641TLE

Modbus Interface

Allows control of 64 indoor units from a Modbus


based BMS

All VRF indoor units.

TO-AC-KNX-64

KNX Interface

Allows control of 64 indoor units from a KNX based


BMS/Home Auto machine

All VRF indoor units.

TCB-IFCG1TLE

General purpose interface

Enables control of A/C by the DI/DO and AI/AO

All VRF indoor units.

TCB-IFGSM1E

GSM control interface

Allows ON/OFF control, operation status monitoring


& alarm monitoring of A/C

All VRF indoor units.

TCB-PX30MUE

Terminal box

Steel Terminal box to connect to

TCB-PCNT30TLE2 , TCB-IFCB5-PE

TCB-PX100PE

Terminal box

Plastic Terminal box to connect to

TCB-PCNT30TLE2 , TCB-IFCB5-PE

TCB-IFCB-4E2

Application Control PC Board

Remote On/Off Control

All VRF indoor units.

TCB-IFCB5-PE

Application Control PC Board

Window Switch Remote On/Off control

All VRF indoor units.

TCB-PCDM4E

Application Control PC Board

Power Peak Cut Control

SMMS, SMMS-i, SHRM and Mini-SMMS Outdoor Units

TCB-PCMO4E

Application Control PC Board

External Master ON/OFF Control Board

SMMS, SMMS-i, SHRM and Mini-SMMS Outdoor Units

TCB-PCIN4E

Connectors

Error/Individual compressor Operation Output


Control Board

SMMS SMMS i SHRM d Mi i SMMS O td U it

TCB-KBCN32VEE

For CN32

All VRF indoor units.

TCB-KBCN60OPE

For CN60

All VRF indoor units.

For CN61

All VRF indoor units.

TCB-KBCN70OAE

For CN70

All VRF indoor units.

TCB-KBCN73DEE

For CN73

All VRF indoor units.

TCB-KBCN80EXE

For CN80

All VRF indoor units.

TCB-KBCN61HAE

Application
Control PC Board

73
83

SMMS-i Selection Tools


Everything at the click of a button

Sophisticated system design software has been developed for the whole SMMS-i range and is a useful and irreplaceable
support tool for engineers, architects, installers and, in general, for anyone who wants to apply innovative Toshiba
solutions. With this software, the user can create a complete VRF system by simply clicking on the icons for the indoor
units and the other connection components. It is also possible to define, in advance, relevant parameters such as
outside and inside temperatures fan speed pipe system length and routing etc. The software automatically manages
all the parameters entered, and the actual system capacity for the conditions required can be quickly calculated and
simulated during the design stage. The software constantly monitors possible design errors and warns the user, when
it reaches the system limits.
Features

* Graphical representation of the required pipe connection system and pipe sizing.
* Specific details and data of the system selected: heating capacity, sensible and total cooling capacity, actual
cooling capacity, additional refrigerant charge and pricing indications.

* Multiple system management as a single project


* Export function to transfer the project report using standard Microsoft Word and Adobe Acrobat (PDF). The
images can also be exported to an AutoCAD (DXF) file.

* Automatic regeneration when adding or amending an existing project selection.


* Indoor unit fan speed indication (high /medium/low) on the system Report

Indoor Unit Selection

Refrigerant Line Diagram

Diagnostic software -DynaDoctor

( TCB-DK01SSE )

The correct operation of sophisticated systems such as VRF is important to the


long-term reliability of the system. In order to assist with the correct commissioning
of SMMS-i, Toshiba has developed a diagnostic software programme a valuable tool for
the commissioning and service engineer. The engineer can connect to the VRF system
using a dedicated interface enabling the download of all operating parameters and
providing the engineer with detailed information for instant analysis or record.

Description of DynaDoctor Parts


Dyna Doctor Hardware for SMMS-i
Software for SMMS-i

Running Parameter views

74
84

Sharjah

About :

AHI Carrier Toshiba Solution Center is a world class training center, to cater product training and troubleshooting
requirements of AHI Carriers Customer, Channel technicians & sales staff.
This is to achieve greater customer satisfaction by :
Responding to their technical requirements quickly.
Identifying scope of product improvements by observing the products in running conditions.

Facilities :

Product Display : Showcasing Toshiba Range of


products for Residential, Small Offices & Large Buildings.
Product trainings : Hands-on product trainings.
VRF Live demonstration
Control Training : Hands-on training for VRF control
system.
Troubleshooting

85

Conversion Table

86