Академический Документы
Профессиональный Документы
Культура Документы
CHAPTER 2
INVESTIGATIONS OF TRANSFORMER OIL
CHARACTERISTICS
2.1
INTRODUCTION
Power transformers are the most significant components of power
22
2.2
Dia =19.8 mm
2.5mm
23
Samples
Conditions of sample
BDV (kV)
[Mean SD]
26 0.63
300.77
240.63
210.74
180.63
170.93
190.74
160.63
220.74
Each sample was subjected to five times of BDV test and their
average is taken as final value. The Standard Deviation (SD) of each test
samples is included along with final BDV value. Based on BDV value the
samples are further classified as very low, moderate and high with respect to
the gradient. From the test results it shall be identified that highly burned oil
shows very lower BDV.
2.3
ACIDITY
It is a measure of free organic and inorganic acid present in the oil
24
The acidity of the samples for titration method is calculated using formula
Total Acidity = A N 56.1 / W
mgKOH/g
(1.1)
2.4
Samples
Titration Value
(mgKOH/g)
PH meter
0.2243
5.70
0.2467
5.50
0.1802
6.10
0.3590
5.46
0.3300
5.67
0.3123
5.65
0.3256
5.70
0.2854
5.25
0.0900
6.53
25
Flash and fire point test is carried out in Pensky-Martens closed cup
apparatus as per ASTM D3828. Total amount of transformer oil used for
analysis in the test apparatus is of 60 ml. The various combinations of
samples (Ideal sample along with natural dust and saw dust) are evaluated for
flash point and fire point values in the closed cup are shown in Table 2.3.
26
27
28
29
2.5
FURAN ANALYSIS
Cellulose is a natural polymer of glucose and it degrades slowly as
30
Samples
2FFD
2AF
5MFFD
5HMFFD
49
24
20
32
125
70
33
30
59
268
100
30
65
82
283
121
42
57
90
320
123
40
57
100
330
500
10
150
265
1034
120
43
60
127
354
4900
35
120
287
5482
100
40
67
98
305
FFD
- Furfural dehyde,
AF
- Acetyl furan,
MFFD
(ppb)
31
Acidity (mgKOH/g)
Acidity (mgKOH/g)
32
Acidity (mgKOH/g)
Description
Coefficient of
determination
r2
0.2759
-133.24
176.510
0.1158
-59.36
192.63
Acidity vs BDV
0.5670
38.94
-38.94
Acidity vs Furan
0.0222
2980.69
165.102
BDV vs Furan
0.643
-0.0023
23.418
Figures 2.2, 2.3, 2.4, 2.5 and 2.6 illustrates the correlation between
critical parameters Acidity, BDV, Flash point, Fire point and Furan contents.
Regression analysis of the Flash and Fire point implies that the Flash and Fire
point moderately linear with the acidity value as observed from Figures 2.2
and 2.3. Regression analysis of the Acidity and Breakdown voltage strongly
implies the linearity between them as observed from Figure 2.4. Results of
correlation coefficients from the Figures.2.2, 2.3, 2.4, 2.5 and 2.6 are listed in
Table 2.6.
33
Acidity (mgKOH/g)
Furan (ppb)
Figure 2.6 Correlation of Furan with Break down voltage
34
2.7
oil immersed transformers and test is carried for regular periodic intervals. It
mainly involves the following steps,
1.
2.
3.
4.
CH4
Samples
ppm
ppm
650
C2H6
C2H4
C 2 H2
CO2
ppm
ppm
ppm
ppm
116
43
528
528
19
12
0.3
0.3
910
17
39
0.7
160
305
112
163
359
11998
2212
0.1
0.02
269
14
0.1
0.1
0.1
0.1
436
23
0.4
0.4
38
3986
21
26
14
0.5
0.5
857
35
PROPOSED X METHOD
Traditional methods for determining the faults using dissolved
gases are of Rogers 3 ratio method as shown in Table 2.8 and Dorenburg 4
ratio method as shown in Table 2.9. The drawback of these methodologies is
some code of range of ratios does not harmonize with the Rogers method and
others with the Doernenburgs method.
The characteristics of the fault are not the same in both methods.
Besides the faults in the Rogers table are not present in the Doernenburgs
table and those in Doernenburgs table are not in the Rogers table.
36
Sl. No.
R2
R3
0.1-1
1-3
Greater than 3
Characteristic Fault
No fault
1-2
1-2
R1 = C2H2/ C2H4
R2 = CH4/ H2
R3 = C2H4/ C2H6,
R4=C2H6/ CH4
In this Proposed X method, the two ratio methods are merged and
include all types of characteristics faults that are present in both the ratio
methods. The role of intertwined Fuzzy with basic software like visual basic,
37
38
R4
R3
R1
Evolution
39
2.8.1
visual basic in order to estimate the fault present in Proposed X method and
the conditions of transformer oil insulation by correlating all the parameters.
Based on recommendations suggested by the IS, IEC, ASTM, BS standards
and also on dexterity of engineers. The adequate limits are fixed for BDV,
acidity, flash, fire point and furan compounds for determining the insulation
condition of transformer.
The minimum and maximum limits to ensure the performance of
transformer oil insulation efficiency are given by Table 2.10. The results to be
exhibited based on conditions satisfaction are given in Table 2.11; it was
framed by means of Expert knowledge in the corresponding field.
Fuzzy strategy entwined with basic software is adopted to ensure
the new merged X conditions for Rogers and Dorenburgs methods. Analysis
of dissolved gas with their corresponding fault is carried out by means of
Fuzzy logic entwined with basic software (Visual Basic), since fuzzy strategy
is used to cover wide range of datas shown in Rogers and Dorenburgs
method. A typical solution is the application of a fuzzy inference system to
approximate the relationship between the measured values and the faults
causing the different gas combinations. It is important to remark, that setting
the crossing of membership functions the degree of uncertainty can be taken
into consideration. The second difference, that by the use of these functions,
an upper and a lower limit are calculated for the specific faults.
An index model of display system used in the expert system (X
method) with their appropriate faults is given in the Table 2.12. In the model
40
of expert system, on entering the data of gas concentrations in ppm and rating
of transformer it will display the fault respective to the ppm concentration of
gases. The details given in the Table 2.12 are of example datas given as input
(transformer rating and ppm concentration of gas) to the system and their
corresponding faults are displayed automatically by expert system. Screen
shots of transformer oil insulation efficiency system and panel view of input,
output panel formed are illustrated in the Figures 2.7, 2.8 and 2.9 respectively.
Table 2.10 Limits for analysis of transformer oil efficiency
S.No
Tests conducted on
transformer oil
Min.
Limit
Max. Limit
Furan Analysis(ppb)
Above 2500
Acidity content(mgKOH/g)
0.35
25
50
120
180
150
220
S. No
Total number of
conditions to be
satisfied
Results to be exhibited
" Satisfactory"
<3
41
H2
CH4
C2 H6
C2 H4
C2H2
ppm
ppm
ppm
ppm
ppm
16
650
116
43
528
Discharge of Low
Energy
0.3
Sight Over
heating below150
C)
50
3.15
10
23
19
0.4
12
0.4
0.3
38
Fault type
General
conductor over
heating
Thermal fault of
low temperature
150 to 300 ( C)
25
19
0.1
General over
Heating
42
Figure 2.8 Screen shot of input panel developed using Fuzzy logic
strategy - X method
Figure 2.9 Screen shot of output panel developed using Fuzzy logic
strategy - X method
43
2.9
DISCUSSION
Tests were carried out on nine samples to investigate various
critical characteristics.
It is inferred on adding saw dust to samples it permits to act as
insulating medium and increases flash point.
It is inferred that on adding dust with humidity contents reduces
the flash and fire point.
Furan analysis of test samples reveals that highly burned oil
shows higher production of furanic compounds. More over the
time duration and cost wise approach for determining furanic
derivatives was very high by HPLC process.
Regression analysis implies that breakdown voltage shows
stronger linearity for furan and acidity.
DGA analysis of test samples reveals that sample four
containing transformer was subjected to very high partial
discharge problems.
The expert system developed for analyzing insulation efficiency
and DGA methods using fuzzy helps the operator to have an
easy solution about the dielectric strength of his transformer.
44
2.10
CONCLUSION
The experimentation on various transformer oil samples has been
carried out and the results are interpreted. The methodology has been found to
formulate measures through which effective monitoring of the power
transformer can pave way to determine the life time of insulation. The
strategy has been coined to incorporate measures for evaluating unpredictable
failures and unnatural outages. It can be concluded that predictive monitoring
strategies will enable an extension in life and facilitate proper asset
management. The next chapter deals with investigations of thermal
degradation and spectral response of transformer oil.