Title:
Prep.:

Compliance statement DC_DEP_33.65.50.31-Gen. Sept 2013


MBO

Appr.:

DEP SECT.

INTRODUCTION
1
1.1
1.2
1.3
1.3.1
1.3.2
1.4
1.5
1.6

MDR

COMPLY

Date:

DEVIATE

07.02.2014

ALTERNATIVE

Document No.
Ref. No.

A3.01.01_Thyristor_Sept2013
113528

COMMENT

x
x
x
x
x
x
x
x

GENERAL REQUIREMENTS
2
2.1
x

2.2

2.3
2.4
2.5
2.6

x
x
x
x

- 4-6 years replacement interval for fans depending on


environmental conditions
- 8-10 years replacement interval for electrolytic capacitors
- 6 years maintenance interval for overall system

2.7

- N+1 Parallel connected systems with off-load boost


charge functionality (interlocked with output switch)
- Passive Load-Sharing for >= 2 units in parallel with inclined
output characteristic
- More accurate Load-Sharing is possible with CAN-Bus
communication between 2 units

2.8

- The country of brand of the main parts/components of the


DC UPS system is Western Europe (Switzerland, Germany,
Italy, France etc.), Japan and North America.

PERFORMANCE REQUIREMENT
3
3.1
3.1.1
x

3.1.2

3.2
3.3

x
x

3.4

3.6

Page 1 of 2

- Battery sizing parameters: (fdv=final discharge voltage)


For VRLA Batteries:
Temperature: 20C, Ageing Factor: 1.25, fdv: 1.80Vpc
For Vented Lead Acid Batteries:
Temperature: 20C, Ageing Factor: 1.10, fdv: 1.70Vpc
For NiCd Batteries:
Temperature: 20C, Ageing Factor: 1.10, fdv: 1.10Vpc
- Stated VRLA battery classification BS 6290-4 Category 1H23
is no longer valid and has been superseded by IEC 6089621, -22.
- To allow practical battery sizing voltage variation
tolerances of -11.5% / +12.5% are used.

3.5

3.7
3.8
3.9

-For batteries with gas recombination charging currents are


limited. It is not possible to meet recharge times and
capacity restoration for applications having 60minute or
longer support duration .
The recharge time to 85 - 90% nominal capacity of a fully
discharged (100% DOD) VRLA battery is < 12hours.

- Standard units will comply with harmonic limits for supply


capacities greater than 250 times the kVA rating of the DC
UPS (IEC 61000-3-12, Table 2 or 3). For supplies with limited
power capacities additional filter networks can be fitted.

x
x
x

DEP compliance statement DC_DEP_33.65.50.31_Sept_2013_20140207_Thyristor.xls

Shell - UPS Enterprise Framework Agreement RFP


Title:
Prep.:

Compliance statement DC_DEP_33.65.50.31-Gen. Sept 2013


MBO

DEP SECT.

Appr.:

MDR

COMPLY

Date:

DEVIATE

07.02.2014

ALTERNATIVE

CONSTRUCTIONAL REQUIREMENT
4
4.1
4.1.1
x
4.1.2
x
4.1.3
x
4.1.4
x
4.2
x
4.3

4.4
4.5
4.6
4.7

x
x
x
x

Document No.
Ref. No.

A3.01.01_Thyristor_Sept2013
113528

COMMENT

- natural cooling or N+1 fans with fan monitoring

- Double insulated wires allow direct fixation to conductive


surfaces as an alternative to additonal insulating means.

MEASUREMENT, PROTECTION AND CONTROL EQUIPMENT


5.
5.1
x
5.2

- Mimic diagram only available on 3-phase input DC UPS


- LED indications provided for Mains Failure, Battery
Operation and DC Output Switch Open

5.3

- Battery autonomy time displayed in minutes or capacity


(Ah)

5.4
x

5.4.1
5.4.2
5.5

- "First failure feature" is not supported by alarm indicators


but every event / alarm is logged with a time stamp.

x
x
x

5.6
5.7

- event / alarm is
logged with a time
stamp

- Automated On-line Battery Monitoring is not supported but


a battery availability test can be initiated manually or
automatically. Midpoint voltage battery monitoring is
available as an option.

INSPECTION AND TEST


6.
6.1
x
6.2
x
6.2.1
x
6.2.2
x
6.2.3
x
6.2.4
6.2.4.1
x
6.2.4.2
x
6.2.4.3
x
6.2.4.4
x
6.2.4.5
x
DOCUMENTS
7.

REFERENCE
8.

- Stated VRLA battery classification BS 6290-4 is no longer


valid and has been superseded by IEC 60896-21, -22

APPENDIX 1
x
APPENDIX 2
x

- Thyristor design is not intended for telecom use

APPENDIX 3
x

Page 2 of 2

DEP compliance statement DC_DEP_33.65.50.31_Sept_2013_20140207_Thyristor.xls