THERMAL CHARACTERISTICS
Continuous Current Carrying Capacity
The continuous current carrying capacity of a conductor depends on the permissible conductor temperature rise above
ambient air temperature. For the calculation of current ratings of bare overhead conductors, ambient air temperatures
between 20C and 40C are usually considered.
The maximum permissible continuous operating temperature of an overhead conductor is limited by the permanent effects
of high temperatures on the strength of the conductor material. Aluminium wire may be operated indefinitely at
temperatures of up to 75C without significant annealing occurring. Therefore, this temperature is taken as the continuous
operating temperature for bare aluminium and aluminium alloy conductors.
For aluminium and aluminium alloy conductors, a maximum operating temperature limit of 100C is recommended,
resulting in approximately 3% loss of strength after 1000 hours of operation. Under emergency operating conditions with
higher temperatures, the effect of annealing should be considered. The loss of strength for an AAC or AAAC/1120
conductor operated at 150C for 10 hours is equivalent to the loss of strength for the same conductor operated at 100C
for 7000 hours. The effect is less significant with steel-reinforced conductors, where the steel provides most of the strength
of the conductor and is essentially unaffected by temperature. However, to allow for the effects on grease and fittings, a
maximum operating temperature limit of 120C is recommended in this case.
The maximum load capacity of a long line is usually dictated by consideration of system stability, permissible voltage
regulation, or the cost of energy losses. However, the maximum load capacity of a short line may be determined by the
maximum permissible operating temperature of the conductor. The maximum permissible operating temperature is that
which results in the greatest permissible sag (allowing for creep) or that which results in the maximum allowable permanent
loss of tensile strength due to annealing.
The conductor temperature depends on the current load, the electrical characteristics of the conductor, and the
atmospheric parameters such as wind and sun. Assuming these factors to be fairly constant, the conductor temperature
does not change significantly. In this situation, the heat supplied to the conductor is balanced by the heat dissipated and
the thermal condition of the conductor is then defined as steady state. At such a steady state, with the conductor at
maximum permissible temperature, a heat balance equation can be used to calculate the continuous current carrying
capacity of a conductor.