Вы находитесь на странице: 1из 7

SG - 4 - 56

B R I TA L

4 Sided Structurally Glazed Curtain Walling System


Typical Elevation & Vertical Section

ALUMINIUM FACADE DESIGNS

Top
Hung
Vent

Fixed
Light

4
1

Spandrel
Panel

Spandrel
Panel

Top
Hung
Vent

Top
Hung
Vent

Fixed
Light

Fixed
Light
4
6

4
2

4
5

Spandrel
Panel

Spandrel
Panel

Spandrel
Panel

Spandrel
Panel

Transom centres.

Spandrel
Panel

Storey height

Spandrel
Panel

4 Sided Structural Glazed


Curtain Walling System

Transom centres.

Typical Elevation
Scale 1:40

Back-up wall
Height.

4
3

See full size details shown on


Assembly drawings of Mullions & Transoms
in section 4 of this manual

* : For typical Smokestop details at floor slab


see manual pages 4/20, 4/21, 4/49, 4/50, 4/51,
4/52, 4/58, and 4/59.

Typical Vertical Section


Scale 1:20

Copyright Brital 2003 R6

4/0

SG - 4 - 56

B R I TA L

4 Sided Structurally Glazed Curtain Walling System


Mullion, Fixed & Fixed

ALUMINIUM FACADE DESIGNS

56
35.5

For mullion and joint


sleeve options
see sheet 3/1

profile
BR-25011A

70

Fixing lug
BR-15007A
at max 300mm
centres

profile
BR-25011A

10

Mullion
gasket
BR-04

Silicone
Weather Sealant

No 10 x 19mm long
Cap Head (DIN 912)
Stainless Steel Self
Tapping Screws
(Point Type AB)

13

Closed cell,
non-gassing,
Polyethylene
foam backer rod

Copyright Brital 2003 R6

4/2

SG - 4 - 56

B R I TA L

4 Sided Structurally Glazed Curtain Walling System


Mullion, Spandrel Panel & Spandrel Panel

ALUMINIUM FACADE DESIGNS

56
35.5

No 10 x 19mm long
Cap Head (DIN 912)
Stainless Steel Self
Tapping Screws
(Point Type AB)

70

profile
BR-25010A

Fixing lug
BR-15007A
at max 300mm
centres

profile
BR-25010A

Mullion
gasket
BR-04

10

For mullion and joint


sleeve options
see sheet 3/1

Silicone
Weather Sealant

13

Closed cell,
non-gassing,
Polyethylene
foam backer rod

Copyright Brital 2003 R6

4/3

B R I TA L
ALUMINIUM FACADE DESIGNS

SG - 4 - 56
4 Sided Structurally Glazed Curtain Walling System
Transom, Fixed & Non Thermally Broken Vent

* : For details of Glazing Support


see sheet 6/2

70
24

Weatherseal
BR-01
4

*
Seal
BR-07

Heads of all screws


to be sealed

profile BR-25012A

Fixing lug BR-15007A


at max 300mm
centres

6.5

35.5

13

11

47.5

56.5

profile BR-VF1

profile BR-25011A
For transom
back options
see sheet 3/2

Transom
gasket
BR-05

Thermal
break
BR-03
No 10 x 25.4mm long
Cap Head (DIN 912)
Stainless Steel Self
Tapping Screws
(Point Type AB)

Copyright Brital 2003 R8

4/6

B R I TA L
ALUMINIUM FACADE DESIGNS

SG - 4 - 56
4 Sided Structurally Glazed Curtain Walling System
Typical Mullion Joint Detail

Structural fixings
to suit site
conditions
For mullion and
joint sleeve options
see sheet 3/1

Extruded Mullion
Bracket BR-MB2

Bond breaker tape


to be applied
to joint sleeve at joint
position to prevent
Silicone bonding to
sleeve
Extruded Mullion
Bracket BR-MB2

Mullion joint sleeve


(length of sleeve is
subject to structural
design)

EQ
EQ

M12

10

Low modulus, neutral


cure, Silicone joint
sealant between
mullions

Mullion Joint Sleeve


10mm
Mullion Joint

26

30

Copyright Brital 2003 R7

4/11

SG - 4 - 56

B R I TA L

4 Sided Structurally Glazed Curtain Walling System


Typical Head & Cill Details

ALUMINIUM FACADE DESIGNS

Sealant & closed


cell, non-gassing
polyethylene foam
backer rod

20 10

Structural fixings
to suit site
conditions

60

Pressed metal 2mm


thick ( profile to suit site
conditions).

13

Ceiling
Board

Subframe
profile BR - SF1

Sliding
head joint

10
Mullion

70

Dead load of D G Units to be


mechanically supported
( see details on sheet 6/2 & 6/3 )

24

Subframe
profile BR - SF1

Pressed metal cill 2mm


thick ( profile to suit site
conditions) screwed to
hollow section after
sealant is applied.
( cill optional )

13

FFL

EPDM perimeter
membrane bond to
structure (minimum
75mm contact)

53.5

Dead Load
Cill fixing

20 10

Floor
Finish

Minimum Edge Distance


Subject to Anchor Size

Copyright Brital 2003 R6

4/13

B R I TA L
ALUMINIUM FACADE DESIGNS

SG - 4 - 56
4 Sided Structurally Glazed Curtain Walling System
Typical Transom Details (at ceiling & back-up wall)

28

For typical details of


mullion joint and tie
back details
see sheet 4/11

Ceiling
Finish

Mullion

Dead load of D G units and panels


are to be mechanically supported
(see details on sheets 6/2 & 6/3)

28

Cill Board

No 10 x 25.4mm long
Cap Head (DIN 912)
Stainless Steel Self
Tapping Screws
(Point Type AB)

Plaster
Finish
Back up wall

6mm Spandrel panel

Copyright Brital 2003 R5

4/16

Вам также может понравиться