INFORME ESTRUCTURAL DE LA
DESINFECCIN FINAL

Guayaquil,Juniode2015

NDICEDELCONTENIDO
Pgina

GENERALIDADES..............................................................................................................1

ALCANCE..........................................................................................................................1

CARGASCONSIDERADAS..................................................................................................2

3.1

CargasMuertas.................................................................................................................2

3.2

CargasVivas......................................................................................................................3

3.3

CargasAccidentales(Ssmicas).........................................................................................3

3.3.1

ZONASSSMICAS(MapaparaDiseoSsmico)..........................................................4

3.3.2

TABLAPARAFACTOR:Z.............................................................................................4

CARACTERSTICASDERESISTENCIADELOSMATERIALES.................................................5
4.1

ResistenciadelConcreto...................................................................................................5

4.2

ResistenciadelAcerodeRefuerzo....................................................................................5

MDULODEELASTICIDAD...............................................................................................5
5.1

Concreto:...........................................................................................................................5

5.2

Acero:................................................................................................................................6

NORMASYCDIGOSDEDISEO.....................................................................................6

CONCEPCINDELMODELOESTRUCTURAL......................................................................6

DIMENSIONESGENERALESDELANLISIS.........................................................................6

ESTADOSDECARGACONSIDERADOS...............................................................................7

10 CARGASDEPRESINLATERAL.........................................................................................7
10.1

PresinLateraldelAgua(PAGUA):...............................................................................7

10.2

PresinLateraldelSuelo(PTIERRA):.............................................................................8

11 ANLISISSSMICO(DINMICO).....................................................................................10
12 ANLISISESTRUCTURAL.................................................................................................12
13 CONSIDERACIONESDEDISEODELOSELEMENTOS......................................................13
14 RECOMENDACIONES......................................................................................................14

INFORMEESTRUCTURAL

GENERALIDADES

La presente memoria tcnica contempla el diseo de los elementos y unidades estructurales


queformanpartedelaDesinfeccinfinal.

LaestructuraestimplantadaenMuchoLote.

ALCANCE

Elpresenteinformedescribelametodologadeanlisisydiseoestructuraldelacimentacin,
murosylosas.

Paraelcometidosehanconsideradovariosfactoresfundamentales:
Larevisingeolgicadelazonayestudiodesuelos.
Elanlisisydiseodelacimentacin.
Diseo de los diferentes elementos, de acuerdo a las condiciones de carga descritas en el
numeral3.

FiguraN1:PerfilHidrulicoDesinfeccinFinal

INFORMEESTRUCTURAL

ndepgina1/15

CARGASCONSIDERADAS

3.1

CargasMuertas

Definicin:Seconsideracomocargasmuertaslasqueactanpermanentemente,talescomoel
pesopropiodelaestructura,muros,maquinariasdeinstalacionesdiversas,empujesdetierrae
hidrosttica,reaccindelsueloetc.

Setienenlossiguientespesosunitarios:

a) Hormignestructural

Resistenciamnimaalacompresinsimplealos28das:

HormignEstructural:fc=350kg/cm2.(Paracontactoconelagua)

Replantillo:

fc=140kg/cm2.

Pesoespecfico=2400kg/m3.

b) Aceroderefuerzoenvarillacorrugadas

Lmitedefluenciafy=4200kg/cm2.

Pesoespecfico=7850kg/m3.

c) Materialdesitio:

Pesoespecficoaprox.=1700kg/m3

Cohesin=10Kpa

ngulodeFriccin=26

Permeabilidad<1x108m/s

INFORMEESTRUCTURAL

ndepgina2/15

3.2

CargasVivas

Definicin:Sonlasprovisionalesyquenotienencarcterdepermanente.
reasdestinadasa:
Losasaccesibles....................................500Kg/m2
Losasinaccesibles.........100kg/m2

ParaelDiseossmicoseconsiderlacargamuertaycargasderellenocircundante.

3.3

CargasAccidentales(Ssmicas)

LascargasssmicasseobtuvieronmedianteelespectrodediseodelaNormaEcuatorianadela
Construccin(NEC11).

De acuerdo al mapa ssmico, los parmetros donde se implantar la estructura son los
siguientes:
ZonaSsmicaV,TipodeperfilC(360m/s>Vs>360m/s).
Z=0.4:
Fa=1.2:
Fd=1.3:
Fs=1.3:
=1.8,
(secontemplaunacapade10cmdereplantillo)

INFORMEESTRUCTURAL

ndepgina3/15

3.3.1 ZONASSSMICAS(MapaparaDiseoSsmico)

FiguraN2:Zonasssmicasparapropsitosdediseo(Figura2.1,NEC11:2011,Captulo2)

3.3.2 TABLAPARAFACTOR:Z

TablaN1:TabladePoblacionesyfactorZ(Fuente:NEC11Captulo2)

FiguraN3:Espectrossmicoelsticodeaceleraciones(Figura2.1,NEC11,Captulo2)

INFORMEESTRUCTURAL

ndepgina4/15

4.1

CARACTERSTICASDERESISTENCIADELOSMATERIALES

ResistenciadelConcreto

Paraestaestructurahidrulicaseconsiderar:fc=350Kg/cm2nominalalacompresinalos
28das,lomnimoindicadoenelACI350es:

4000psi=280kg/cm2

La capacidad terica de los elementos estructurales se ajusta por un factor de reduccin de


resistencia (). Este coeficiente prev la posibilidad de variacin de la resistencia del material
(fc)enlamanodeobradentrodeloslmitesaceptables(ACI31811)Cap.9.

4.2

ResistenciadelAcerodeRefuerzo

fy=4200Kg./cm2(lmitedefluencia).Paravarillasdedimetronominal10mmymayores.
(Varillasmenoresa10mmnoseconsiderarnparaestaestructura.

Paraefectosdedeterminacinderesistencia,seutilizelesfuerzodefluencia.

5
5.1

MDULODEELASTICIDAD
Concreto:

Paraelconcretosetom:Ec=15000fcKg/cm2

INFORMEESTRUCTURAL

ndepgina5/15

5.2

Acero:

Paraelacerosetom:Es=2100000Kg/cm2

NORMASYCDIGOSDEDISEO

Lasnormasquesehanaplicadoeneldiseodeesteproyectoestructuralsonlasqueseindican
acontinuacin:

ACI31811(AmericanConcreteInstitute)
ACI35006(AmericanConcreteInstitute),(estructurashidrulicas)
NEC11CAP.2PELIGROSISMICOYREQUISITOSDEDISEOSISMORESISTENTE

A continuacin se presenta en forma detallada el procedimiento que se sigui para la


modelacindelaestructura.

CONCEPCINDELMODELOESTRUCTURAL

LaEstructuraestasoportadaporunsistemadecimentacinconformadoporunalosa.
LasestructurassemodelaronconelementosfinitostipoShell(placas)yelementostipoFrame
(vigasycolumnas),loscualesseunenentrespormediodenudosparaformarasuvezlaslosas
ymuros.

DIMENSIONESGENERALESDELANLISIS

Lasdimensionesyespesoresdeloselementosseleccionadosenelprediseoydiseofinalson
lossiguientes:

Losasdefondoh=250y300mm

Muroe=200y250mm

INFORMEESTRUCTURAL

ndepgina6/15

ESTADOSDECARGACONSIDERADOS

De acuerdo a las caractersticas del proyecto se han propuestos los siguientes estados de
anlisisdecarga:

Descarga vaca, en este caso solo acta la presin del terreno. A este estado se lo llama
(DESCARGAVACIO).

Descarga llena, es decir, cuando la estructura est llena. Se ha considerado este estado de
cargasuponiendoquenoseharellenadolaestructura,aestoselellama(DESCARGALLENO).

Descarga cimentacin, se han modelado las losas de cimentacin por la reaccin del suelo
causada por los pesos de los muros y losas cuando este vaco la reserva. A esto se le llama
(DESCARGACIMENTACION)

10 CARGASDEPRESINLATERAL

10.1 PresinLateraldelAgua(PAGUA):

Lapresinlateraldeaguaconsideradaparaelanlisisydiseodelaestructuraseconsidera
partirdelniveldellenadodelaestructura,incrementndosesuvalorsegnlaprofundidad.Se
ha usado un patrn de carga joint patterns La presin ejercida por el agua a cualquier
profundidades.

P=.H
Donde:
P=Presindeagua

INFORMEESTRUCTURAL

ndepgina7/15

=Densidaddelagua
H=Profundidadconsiderada,variable(m).

Debidoalascargasypresincircundantes(terreno),setieneelsiguienteesquema:

FiguraN4:Esquemadecargasdebidoalascargas(q1)ypresionescircundantes

10.2 PresinLateraldelSuelo(PTIERRA):

Se considera el empuje proporcionado por la Teora de Rankine. Las ecuaciones


correspondientesson:

Presinactiva:P=K.W.H(paramurosinternos).
PresinlateralenReposo=Pr=Ko.W.H(paramurosperimetralesdelaEstructura).
K=(1Sen)/(1+Sen):Ko=1Sen

Donde:

INFORMEESTRUCTURAL

ndepgina8/15

W=PesodelsueloKg/m3
H=Profundidadconsideradaenmetros
=Angulodefriccininternadesuelo

Elrelleno,quesevacolocarsegnelestudiogeotcnicotienelassiguientescaractersticas:

SehausadounpatrndecargaJointpatternsparadefinirunacargatriangularrealsobrelas
paredesdecadaestructuraencontactoconelsuelo.

La carga horizontal sobre los muros se ha considerado trapezoidal o triangular segn el caso
sobrelasparedes.

Segn la Norma AASHTO, nos indica que si hay acceso vehicular se considerar una altura
adicionalde60cmderelleno,dndonoselsiguienteesquemadecarga:

INFORMEESTRUCTURAL

ndepgina9/15

h1=0.60m

h2

q3

q4

FiguraN5:Esquemadecargaconaccesovehiculardebidoalapresindelsuelo

11 ANLISISSSMICO(DINMICO)

Para analizar el comportamiento de la estructura sometido a solicitaciones ssmicas, se


considerel espectro de aceleracin dado en la norma del NEC11. (Norma Ecuatoriana de la
Construccin,CapitulodeDiseoSismoResistente)segneltipodesueloydentrodelazona
ssmicaqueseencuentra.

Tipodesuelo:
Zonassmica:V
Z=0.4;Factordezonaparalaregindondevaaserconstruidolaestructura(Tabla2.2dela
NormaNEC2011,Captulo2)

Fa = 1.2; Coeficiente que amplifica las ordenadas del espectro de respuesta elstico de
aceleraciones para diseo en roca, tomando en cuenta los efectos de sitio. (Tabla 2.5 de la
NormaNEC11,Captulo2)

Fd = 1.3; Coeficiente que amplifica las ordenadas del espectro elstico de respuesta de
desplazamientosparadiseoenroca,considerandolosefectosdesitio.(Tabla2.6delaNorma
NEC11,Captulo2)

INFORMEESTRUCTURAL

ndepgina10/15

Factordeimportancia:I=1.5
Factorderespuesta:R=2.0(Paralaestructura)

(NormasutilizadasestnsealadasdentrodelNEC11)

Aceleracin(g)

EspectroparaelAnlisisSsmico(Estegraficoescualitativo.)
1.000
0.900
0.800
0.700
0.600
0.500
0.400
0.300
0.200
0.100
0.000
0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

PeriodoT(s)

Losvaloresdiscretizadossepresentanacontinuacin:
T(s)

Sa(g)

T(s)

Sa(g)

T(s)

Sa(g)

0.10

0.864

1.00

0.669

3.25

0.206

0.20

0.864

1.25

0.535

3.50

0.191

0.30

0.864

1.50

0.446

3.75

0.178

0.40

0.864

1.75

0.382

4.00

0.167

0.50

0.864

2.00

0.335

4.50

0.149

0.60

0.864

2.25

0.297

5.00

0.134

0.70

0.864

2.50

0.268

7.50

0.089

0.80

0.837

2.75

0.243

10.00

0.067

0.90

0.744

3.00

0.223

TablaN2:TabladeValoresdiscretizadosparagrficadeEspectroSsmico

INFORMEESTRUCTURAL

ndepgina11/15

12 ANLISISESTRUCTURAL

Elanlisisestructuralsebasaenunmodelotridimensional,elmismoqueconstade:columnas,
vigas, losas y muros formados por placas macizas de hormign armado. El anlisis de las
estructurasserealizconlaayudadeunprogramadeelementosfinitos(SAP2000)yconhojas
declculoenExcel,conlaopcindemodeladomedianteelelementoFRAMEparalascolumnas
yvigas;ymedianteelelementoSHELLparalaslosasymuros.Semodelaronlasestructurascon
los mencionados elementos para los diferentes niveles y secciones, segn las medidas
geomtricasproporcionadasporelproyectohidrulicoylascondicionesdecargadescritasenel
numeral3y9.

LasfuerzasinternasdecadaelementoFRAMEson:
P:Fuerzaaxial
V22:Fuerzacortanteenelplano12
V33:Fuerzacortanteenelplano13
T:Fuerzadetorsin
M22:MomentodeFlexinenelplano13(alrededordeleje2)
M33:MomentodeFlexinenelplano12(alrededordeleje3)

LasfuerzasinternasdecadaelementoSHELLson:
F11:Fuerzadirectademembranaeneleje1
F22:Fuerzadirectademembranaeneleje2
V13:Fuerzadecortetransversaldeplacaenelplano13
V23:Fuerzadecortetransversaldeplacaenelplano23
M11:MomentodeFlexindeplaca(alrededordeleje1)
M22:MomentodeFlexindeplaca(alrededordeleje2)
M12:Momentotorsor

INFORMEESTRUCTURAL

ndepgina12/15

13 CONSIDERACIONESDEDISEODELOSELEMENTOS

Elcriteriodediseoparalaestructuradehormigneseldediseopararesistenciaultimade
loselementossometidosacargasmayoradas,paralocualseutilizanlasnormasdediseodel
cdigodelaACI35006.

Paraeldiseodelaestructuraseconsideranlosvaloresdelosresultados(output)delanlisis,
basndose en los valores crticos tanto para flexin, como para cortante y fuerza axial y se
comparan los esfuerzos actuantes respecto a los resistentes para el diseo final de los
elementos.

Lascombinacionesdecargasparalaestructurason:

DEAD=Cargamuerta(pesopropiodeloselementos)
VIVA=Cargaviva
PAGUA=Presindeagua
PTIERRA=Presindetierra
Ex/Ey=Fuerzasssmicas.

COMBINACIONESDECARGA:SegnACI35006:
COMB1=1.4(DEAD+PAGUA)
COMB2=1.2(DEAD+PAGUA)+1.6(LIVE+PTIERRA)+0.5Lr
COMB3=1.2DEAD+1.6Lr+1.0L
COMB5=1.2(DEAD+PAGUA)+/1.0(ExEy)+1.6PTIERRA+1.0LIVE
COMB7=0.9DEAD+1.2PAGUA+/1.0(ExEy)+1.6PTIERRA
COMB(DESCARGALLENO)=1.6PTIERRA

INFORMEESTRUCTURAL

ndepgina13/15

Adicionalmenteseaplicaatodoslosresultadosuncoeficiente1.3dedurabilidad,prescritopor
elACI350.

ENVOLVENTE=1.3(COMB1COMB2COMB3.)

Para la realizacin del diseo se escogieron los elementos con mayores esfuerzos descritos
anteriormente.Porlafacilidaddelprogramaparaverlosresultadossehaceunvisualencada
sector ms esforzado y se puntualiza el sitio que convenga analizar (o cualquier elemento
especifico).

Entrminosgeneralesseaplicalateoradediseoalarotura,teniendoencuentalashiptesis
fundamentalesdelamisma.SeapliclaEc.dediseoporflexinMn=0.9.b.d^2.fc.w.(10.59w),
para obtener las reas de acero y se calcularon estas para los diferentes momentos;
considerando, los recubrimientos establecidos r=5.00 contacto con agua, r=>4.00 para aire y
r=7.5 para suelo. Las resistencia de los materiales fc=350 y fy=4200 Kg/cm2, descritos
anteriormente.

Alfinalsepresentanvariosgrficosdecadaestructuradelosdiferentesestadosdecargadonde
se muestran los momentos a los que estn sometidos las paredes, muros y las losas de la
estructura.

14 RECOMENDACIONES

Cualquier cambio en las condiciones previstas que se determine al momento de la ejecucin,


deberserconsideradoporlaFiscalizacin,lacualjuzgarlanecesidaddenotificaralaempresa
ejecutoradelosestudiosparalasmodificacionescorrespondientes.

Cambiosmenorespuedenserresueltosenobraconlajustificacintcnicaadecuada.

INFORMEESTRUCTURAL

ndepgina14/15

No se deberealizar cambios que alterenel concepto del diseo o introduzcan modificaciones


mayoresaestosestudiossinelconocimientoyaprobacindelIngenieroqueharealizadoestos
estudios y diseos. Todos los procedimientos constructivos, deben ser aprobados por la
fiscalizacin.

Sobre la construccin de estas estructuras los procesos de curado son muy importantes para
alcanzarlasresistenciassolicitadas.

INFORMEESTRUCTURAL

ndepgina15/15

ANEXO 1
REPORTES SAP2000
ESTRUCTURAL DESINFECCIN FINAL

ANEXO 1
REPORTES SAP2000
ESTRUCTURAL DESINFECCIN FINAL

Contenido
1. MODELO 3D ......................................................................................................................... 1
2. CARGAS EN LAS PAREDES ........................................................................................... 2
3. CARGA EN LOSA INFERIOR ........................................................................................... 2
4. DEFORMACIN EN ESTRUCTURA ............................................................................... 3
5. MOMENTO M11 ................................................................................................................... 3
6. MOMENTO M22 ................................................................................................................... 4
7. ESFUERZO F11 ................................................................................................................... 4
8. ESFUERZO F22 ................................................................................................................... 5
9. SECCIN TRANSVERSAL Y LONGITUDINAL ............................................................ 5

ANEXO 1
REPORTES SAP2000
ESTRUCTURAL DESINFECCIN FINAL

1. MODELO 3D

Estudio Estructural

2. CARGAS EN LAS PAREDES

3. CARGA EN LOSA INFERIOR

Estudio Estructural

4. DEFORMACIN EN ESTRUCTURA

5. MOMENTO M11

Estudio Estructural

6. MOMENTO M22

7. ESFUERZO F11

Estudio Estructural

8. ESFUERZO F22

9. SECCIN TRANSVERSAL Y LONGITUDINAL

Estudio Estructural

ANEXO 2
DISEOS

ClculodelCoeficientedeBalastoDesinfeccin

L=
b=
h=
K30x30 =

Ks, Cuad =
Ks, Rect =

90
8.85
0.3
0.5
4.91
0.5
4905

k s,
k s,
k s,

m
m
m
kp/cm3
N/cm3
kg/cm3
kN/m3
2
cuadrado arenoso = ks,30 [(b+0,30)/(2b)]
cuadrado cohesivo = ks,30 [0,30/b]
rectangular = (2/3) k s, cuadrado [ 1+ b/(2l) ]

rea Tributaria Externos =


rea Tributaria internos =

0.8 m2
0.8 m2

=
=

1310.79

KN/m3

166.27
116.30

KN/m3
KN/m3

8000 cm2
8000 cm2

26

Externo

Interno

Unidad

Kz = Kb * rea tributaria
Kx=ky = Kb (1-sen) rea tributaria

136
76

136
76

kg/cm
kg/cm

Traslacin 3
Traslacin 1

Kz = Kb * rea tributaria
Kx=ky = Kb (1-sen) rea tributaria

13573
7623

13573
7623

kg/m
kg/m

Traslacin 3
Traslacin 1

Con=

Valores para Sap2000

Suelo Cohesivo: Cuadrado


Externo
Interno
Unidad
13600
13600
kg/m
7600
7600
kg/m

Traslacion 3
Traslacion 1

0.134
0.017
0.012

kg/*cm3
kg/*cm3
kg/*cm3

COMPROBACIN DE LA FLOTACIN MUCHO LOTE


ESTRUCTURA: DESINFECCIN
Para el chequeo de la flotacin se revisa que el peso de la Estructura vaca sea suficiente para resistir la presin
del agua a nivel del fondo de la base
DATOS:
Peso Especfico =
Volumen de Hormign =
Peso Especfico Replantillo =
Volumen de Replantillo =
Peso Esp. Suelo (Piedra Filtro) =
Altura de Relleno =
Volumen de Suelo =
Fuerza Resistente =
F (flotacin) =

2400
823.31
2200
92.56
2200
1.85
217.01
2656982

kg/m3
m3
kg/m3
m3
kg/m3
m
m3
kg

Presin *rea de la Base

Nivel Fretico =
Peso Especfico del Agua =
Presin =

2.85
1000
2850

m
kg/m3
kg/m2

Ancho =
Largo =
Alas =
rea de la Base =
F (flotacin) =

8.85
88.9
0.6
906
2580689

m
m
m
m2
Kg

Presin - Flotacin =

76292

kg

Coeficiente de Seguridad =
Cs =

Fuerza Resistente / F (flotacin)


1.030

Cumple

DETERMINACIN DEL ASENTAMIENTO MUCHO LOTE


Caractersticas del Suelo:
Peso Especfico del Suelo =
Peso Especfico Saturado =
ngulo de Friccin =
Cohesin =
Df =

17.00
18.00
26.00
10
3.20

KN/m3 =
KN/m3 =

1700
1800

Kg/m3
Kg/m3

Kpa
m

De acuerdo a Harr (1966) el asentamiento se expresa como:

L = Longitud de Cimentacin =
B = ancho de la Cimentacin =
qo = Carga Admisible =
Es = Mdulo de Elasticidad =
s = Coeficiente de Poisson =

90
9.95
0.04
30
0.25

m=

9.05

(1+m )^0.5 =
=
Se =

9.10
2.48
0.0275

m
m
Mpa
Mpa

=
=

0.36
300

kg/cm2
kg/cm2

27.51

mm

DISEO DE PAREDES, REFUERZO HORIZONTAL MUCHO LOTE


ELEMENTO:
L (m):

3.5

Q (kg/m)
MAXIMOS

Q
Kg/m
1426

Combinaciones de Carga
V izq (kg)
V der (kg)
M izq (kg-m)
4368

Esfuerzos de Diseo
MOM DER
MOM IZQ
Kg - m
Kg - m
4368
2351

M der (kg-m) M pos (kg-m)


2351
2184

MOM POS
Kg - m
2184

Caractersticas de la Viga
Parmetro
Dimensin
Peralte
H
0.25 m
Base
B
1.00 m
Recubrimiento
r
0.05 m
Peralte Efect.
d
0.20 m
Longitud Libre
L
3.20 m
Resistencia
f'c
350 Kg/cm2
Resistencia
fy
4200 Kg/cm2

As Negativo

As Positivo

L=1m
SECCION TRANSVERSAL

Comprobacin de la luz libre del elemento. Artculo 21.5.1.2 ACI - 318


L/H >4
12.80
OK
Comprobacin del ancho del elemento. Artculo 21.5.1.3 y 4 ACI - 318
0,75>B/H>0,4
4.00
revisar
B>0,25
ARMADURA LONGITUDINAL
As neg Izq

As neg der

As pos

Requerimientos maximos y minimos de armadura longitudinal Artculo 21.5.2.1 ACI - 318


6.60 cm2
As min = 0.0033BD

14 =
7.7
As mx = 0,025BD
50.00 cm2

12 =
0
Hierros a alargar de losa
Requerimientos de armadura longitudinal

12 =
0
Adiconales
As en el Apoyo Izquierdo (Negativo)
Ru = Mu (izq)/(BD^2)
12.13
6.60 cm2
- Amin = -1.10
As calculado:
Colocar: 5 14 + alargar hierros de Losa Inferior mnimo H/4
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.00296
As izq = D
5.92 cm2
As colocado:
7.70 cm2
As en el Apoyo Derecho (Negativo)
Ru = Mu (der)/(BD^2)
6.53
6.60 cm2
- Amin = -1.10
As calculado:
Colocar: 5 14 + alargar hierros de Losa Inferior mnimo H/4
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.0016
As der = BD
3.15 cm2
As colocado:
7.70 cm2
As en el Centro de la Luz (Positivo)
As pos min ( con Mom apoyo/2)
Ru = Mu (apoyo/2)/(BD^2)
6.07
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.001464
As pos min ( con Mom Apoyo/2)
2.93 cm2
As pos calculado
Ru = Mu (positivo)/(BD^2)
6.07
6.60 cm2
- Amin = -1.10
As calculado
Colocar: 5 14
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.001464
As pos calculado
2.93 cm2
As colocado:
7.70 cm2

DISEO DE PAREDES REFUERZO VERTICAL MUCHO LOTE


ELEMENTO:
L (m):

3.2

Q (kg/m)
MAXIMOS

Q
Kg/m
3279

Combinaciones de Carga
V izq (kg)
V der (kg)
M izq (kg-m)
8394

Esfuerzos de Diseo
MOM DER
MOM IZQ
Kg - m
Kg - m
8394
4710

M der (kg-m) M pos (kg-m)


4710
4197

MOM POS
Kg - m
4197

Caractersticas de la Viga
Parmetro
Dimensin
Peralte
H
0.25 m
Base
B
1.00 m
Recubrimiento
r
0.05 m
Peralte Efect.
d
0.20 m
Longitud Libre
L
2.90 m
Resistencia
f'c
350 Kg/cm2
Resistencia
fy
4200 Kg/cm2

As Negativo

As Positivo

L=1m
SECCION TRANSVERSAL

Comprobacin de la luz libre del elemento. Artculo 21.5.1.2 ACI - 318


L/H >4
11.60
OK
Comprobacin del ancho del elemento. Artculo 21.5.1.3 y 4 ACI - 318
0,75>B/H>0,4
4.00
revisar
B>0,25
ARMADURA LONGITUDINAL
As neg Izq

As neg der

As pos

Requerimientos maximos y minimos de armadura longitudinal Artculo 21.5.2.1 ACI - 318


6.60 cm2
As min = 0.0033BD

14 =
7.7
As mx = 0,025BD
50.00 cm2

14 =
6.16
Hierros a alargar de losa
Requerimientos de armadura longitudinal

14 =
0
Adiconales
As en el Apoyo Izquierdo (Negativo)
Ru = Mu (izq)/(BD^2)
23.32
11.61 cm2
- Amin = 3.91
As calculado:
Colocar: 9 14 + alargar hierros de Losa Inferior mnimo H/4
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.00581
As izq = D
11.61 cm2
As colocado:
13.86 cm2
As en el Apoyo Derecho (Negativo)
Ru = Mu (der)/(BD^2)
13.08
6.60 cm2
- Amin = -1.10
As calculado:
Colocar: 9 14 + alargar hierros de Losa Inferior mnimo H/4
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.0032
As der = BD
6.39 cm2
As colocado:
13.86 cm2
As en el Centro de la Luz (Positivo)
As pos min ( con Mom apoyo/2)
Ru = Mu (apoyo/2)/(BD^2)
11.66
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.002841
As pos min ( con Mom Apoyo/2)
5.68 cm2
As pos calculado
Ru = Mu (positivo)/(BD^2)
11.66
6.60 cm2
- Amin = -1.10
As calculado
Colocar: 5 14
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.002841
As pos calculado
5.68 cm2
As colocado:
7.70 cm2

DISEO DE LOSA INFERIOR, REFUERZO TRANSVERSAL MUCHO LOTE


ELEMENTO:
L (m):

8.25

Q (kg/m)
MAXIMOS

Q
Kg/m
195

Combinaciones de Carga
V izq (kg)
V der (kg)
M izq (kg-m)
3322

Esfuerzos de Diseo
MOM DER
MOM IZQ
Kg - m
Kg - m
3322
3322

M der (kg-m) M pos (kg-m)


3322
1661

MOM POS
Kg - m
1661

Caractersticas de la Viga
Parmetro
Dimensin
Peralte
H
0.30 m
Base
B
1.00 m
Recubrimiento
r
0.05 m
Peralte Efect.
d
0.25 m
Longitud Libre
L
7.95 m
Resistencia
f'c
350 Kg/cm2
Resistencia
fy
4200 Kg/cm2

As Negativo

As Positivo

L=1m
SECCION TRANSVERSAL

Comprobacin de la luz libre del elemento. Artculo 21.5.1.2 ACI - 318


L/H >4
26.50
OK
Comprobacin del ancho del elemento. Artculo 21.5.1.3 y 4 ACI - 318
0,75>B/H>0,4
3.33
revisar
B>0,25
ARMADURA LONGITUDINAL
As neg Izq

As neg der

As pos

Requerimientos maximos y minimos de armadura longitudinal Artculo 21.5.2.1 ACI - 318


8.25 cm2
As min = 0.0033BD

14 =
7.7
As mx = 0,025BD
62.50 cm2

14 =
1.54
Hierros verticales a alargar
Requerimientos de armadura longitudinal

14 =
1.54
Adiconales
As en el Apoyo Izquierdo (Negativo)
Ru = Mu (izq)/(BD^2)
5.91
8.25 cm2
- Amin = 0.55
As calculado:
Colocar: 5 14 + alargar 1 14 hierros de pared mnimo 50 cm
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.00142
As izq = D
3.56 cm2
As colocado:
9.24 cm2
As en el Apoyo Derecho (Negativo)
Ru = Mu (der)/(BD^2)
5.91
8.25 cm2
- Amin = 0.55
As calculado:
Colocar: 5 14 + alargar 1 14 hierros de pared mnimo 50 cm
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.0014
As der = BD
3.56 cm2
As colocado:
9.24 cm2
As en el Centro de la Luz (Positivo)
As pos min ( con Mom apoyo/2)
Ru = Mu (apoyo/2)/(BD^2)
2.95
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.000709
As pos min ( con Mom Apoyo/2)
1.77 cm2
As pos calculado
Ru = Mu (positivo)/(BD^2)
2.95
8.25 cm2
- Amin = 0.55
As calculado
Colocar: 6 14
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.000709
As pos calculado
1.77 cm2
As colocado:
9.24 cm2

DISEO DE VIGA LOSA DESMONTABLE MUCHO LOTE


ELEMENTO:
L (m):
q=

1
349.6

Q (kg/m)
MAXIMOS

Q
Kg/m
699

Combinaciones de Carga
V izq (kg)
V der (kg)
M izq (kg-m)
175

Esfuerzos de Diseo
MOM DER
MOM IZQ
Kg - m
Kg - m
175
0

M der (kg-m) M pos (kg-m)


0

MOM POS
Kg - m
0

Caractersticas de la Viga
Parmetro
Dimensin
Peralte
H
0.15 m
Base
B
0.20 m
Recubrimiento
r
0.05 m
Peralte Efect.
d
0.10 m
Longitud Libre
L
0.80 m
Resistencia
f'c
350 Kg/cm2
Resistencia
fy
4200 Kg/cm2
Comprobacin de la luz libre del elemento. Artculo 21.5.1.2 ACI - 318
L/H >4
5.33
OK
Comprobacin del ancho del elemento. Artculo 21.5.1.3 y 4 ACI - 318
0,75>B/H>0,4
1.33
revisar
B>0,25

ARMADURA LONGITUDINAL
As neg Izq

As neg der

As pos

Requerimientos maximos y minimos de armadura longitudinal Artculo 21.5.2.1 ACI - 318

12 =
2.26

10 =
0
0.67 cm2
As min = 14BD/fy

10 =
0
Hierros verticales a alargar
5.00 cm2
As mx = 0,025BD
Requerimientos de armadura longitudinal
As en el Apoyo Izquierdo (Negativo)
Ru = Mu (izq)/(BD^2)
9.71
0.67 cm2
- Amin =
-1.59
As calculado:
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.00236
Colocar: 2 12 + alargar hierros de pared
As izq = D
0.47 cm2
As colocado:
2.26 cm2
As en el Apoyo Derecho (Negativo)
Ru = Mu (der)/(BD^2)
0.00
0.67 cm2
- Amin =
-1.59
As calculado:
Colocar: 2 12 + alargar hierros de pared
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.0000
As der = BD
0.00 cm2
As colocado:
2.26 cm2
As en el Centro de la Luz (Positivo)
As pos min ( con Mom apoyo/2)
Ru = Mu (apoyo/2)/(BD^2)
4.86
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.001169
As pos min ( con Mom Apoyo/2)
0.23 cm2
As pos calculado
Ru = Mu (positivo)/(BD^2)
0.00
0.67 cm2
- Amin =
-1.59
As calculado
Colocar: 2 12
0,85*f'c/fy(1-Raiz(1-(2,36*Ru/f'c)))
0.000000
As pos calculado
0.00 cm2
As colocado:
2.26 cm2

ARMADURA TRANSVERSAL
Resistencia Probable. Artculo 21.5.3 ACI - 318
Mp = 1,25As fy (D - 1,25As fy/(2*0,85 f'c B)
Mp1
1068.2 Kg-m
Mp2
1068.2 Kg-m
Mp'1
1068.2 Kg-m
Mp'2
1068.2 Kg-m
Q
699.2 Kg/m
Cortante R21.5.4.2 ACI - 318
V1
2950.2 Kg
V2
2390.8 Kg
V'1
2390.8 Kg
V'2
2950.2 Kg
Mximo
2950.2 Kg
Separacin Mxima. Artculo 21.5.3.2 ACI - 318
Diametro del estribo
0.80 cm
Dimetro de la varilla longitudinal
1.20 cm
D/4
2.50 cm
8 Dimetros Longitudinales
9.60 cm
24 Dimetros Varilla Transversal
19.20 cm
s calculado 2.50cm
s colocado= 10.00cm
Requerimiento de Armadura Transversal
7857.5 Kg
0.19
0.02
0.08
2280.6 Kg
1685.6 Kg
1590.2 Kg
0.21 cm2

Vsmax = 2.1*f'c^0.5*B*D (11.5.7.9)


Avmax/Separacin Mxima = Vsmax/(fy*D) (11.5.7.2)
Avmin/Separacin Mxima = 3.5*B/fy (11.5.6.3)
Av/Separacin Mxima = (Vu-fVc)/(0.85*fy*D) (R11.5.7)

Vu = 3.5*B*D*+Vc
Vc = 0.53*0.85*B*D*f'c^0.5
Vc = 0.85(0.5*f'c^0.5+175(As/BD)*(Vu*D/Mu))*B*D
Av requerido
Av colocado
8 mm
2.01 cm2
COLOCAR 1 estribo 8mm@ 10 cm
REPARTICION DE ESTRIBOS
Longitud libre
Espaciam. entre estribos Laterales
Espaciam. entre estribos Centrales
Longitud Lateral para estribos
# de Vigas iguales
# de estribos
# Total de Est.

80
6.5
15
200
1
40
40

cm
cm
cm
cm
u.
u.
u.

ANEXO 3
CANTIDADES DE OBRA

ANEXO 3
CANTIDADES DE OBRA
ESTRUCTURADEDESINFECCIN
Marca
Dimetro
Cantidad
Tipo
(Mc)
(mm)
1
450
G
14
2
450
C
14
3
102
L
14
4
306
I
14
5
1561
Z
14
6
128
L
14
7
384
I
14
8
2847
Z
12
9
220
L
10
10
660
I
10
11
96
C
10
12
86
Z
12
13
172
Z
12
14
44
C
10
15
46
C
10
16
46
C
10
17
780
L
14
COLUMNAS
50
480
Z
16
51
1440
O
10
52
1440
O
8
VIGAS
60
96
C
14
61
144
I
10
62
1032
O
10
63
1656
O
10
64
12
C
12
65
12
C
12
66
190
O
8
67
35
Z
12
LOSASUPERIOR
70
46
C
12
71
14
C
10
72
78
C
10
73
12
C
10
74
12
C
10
75
58
G
18
LOSASPREFABRICADAS
100
1152
C
12
101
2304
C
12
102
3168
I
12
103
1296
I
10
104
11520
O
8
105
576
U
12

Dimetro
(mm)
8
10
12
14
16
18

a
9.8
8.60
11
12
0.2
11
12
0.10
11
12
8.60
0.4
0.1
2.4
3.2
4.7
1.3

Dimensiones(m)
b
c
d
0.2
0.65
1
1

Longitud
(m)
11.50
10.60
12.00
12.00
4.10
12.00
12.00
4.00
12.00
12.00
10.60
3.00
3.00
3.00
4.00
5.50
1.80

Long.Total
(m)
5175.00
4770.00
1224.00
3672.00
6400.10
1536.00
4608.00
11388.00
2640.00
7920.00
1017.60
258.00
516.00
132.00
184.00
253.00
1404.00

4.20
1.40
0.90

2016.00
2016.00
1296.00

Columnasde50x35cm
EstribosColumnas50x35cm
EstribosColumnas50x35cm

0.05
0.075

9.00
8.65
0.90
0.90
8.95
2.45
0.80
0.45

864.00
1245.60
928.80
1490.40
107.40
29.40
152.00
15.75

VigasV1
VigasV1
SoporteV1deLosasPrefabricadas
EstribosVigasV1
VigasV2
VigasV3
EstribosVigasV2,V3
SoporteTapassobreVigasV2yV3

0.2

2.80
3.50
5.00
8.80
6.20
1.50

128.80
49.00
390.00
105.60
74.40
87.00

LosaCmaradeEntradaySalida
LosaCmaradeEntrada
LosaCmaradeSalida
LosaCmaradeSalida
LosaCmaradeSalida
HierrosparaEscalera

0.05
0.1

3.45
1.55
1.30
3.20
0.60
0.50

3974.40
3571.20
4118.40
4147.20
6912.00
288.00

Vigas20x15cm,Longitudinales
Vigas20x15cm,Transversales
RefuerzoCorto
RefuerzoLargo
EstribosparaVigas
EstribosparaVigas

3.3
1

0.6

3.3
1

0.6

1
2.3
2.3
0.3
0.4
0.4
0.5

0.2
0.40
0.15

3.5
0.25
0.25

8.65
8.65
0.30
0.15
8.65
2.15
0.20
0.075

0.175

2.50
3.20
4.70
8.60
6.00
0.40

0.15
0.15
0.15
0.10
0.10
0.35

3.15
1.25
1.30
3.20
0.15
0.13

0.15
0.15

0.1
0.25
0.15
0.15
0.15
0.30

0.10
0.08

0.3
0.6

0.5
0.05
0.05

0.05
0.05

RESUMENPLANILLADEESTRUCTURADEDESINFECCIN
Cantidad
Peso/m
10%adicional
(m)
(kg/m)
desperdicio
8360.00
0.39
9196.00
22593.60
0.62
24852.96
24395.35
0.89
26834.89
29653.10
1.21
32618.41
2016.00
1.58
2217.60
87.00
2.00
95.70
TOTALPESO(kg)
VolumendeHormign(f'c=350kg/cm2)

Observaciones
LosaInf.Transversal
LosaInf.Transversal
LosaInf.RefuerzoLongitudinal
LosaInf.RefuerzoLongitudinal
ParedesExt.HierrosVerticales
ParedesExt.HierrosHorizontales
ParedesExt.HierrosHorizontales
ParedesInt.HierrosVerticales
ParedesInt.HierrosHorizontales
ParedesInt.HierrosHorizontales
ParedesPerim.yCentral,HierrosHoriz.
ParedesCmaradeIngresoySalida
ParedesCmaradeIngresoySalida
ParedesCmaradeIngresoySalida
ParedesCmaradeIngreso
ParedesCmaradeSalida
ParedesExt.HierrosVert.Adicionales

Pesototal
(kg)
3628.59
15322.78
23824.39
39416.53
3500.12
191.17
85883.58
823.31

PLANILLADEPERFILERIAPARAESTRUCTURADEDESINFECCIN
DESCRIPCION
Perfil
Cantidad Longitud(m) Peso(Kg/m) PesoTotal(kg)
PERFILERIADECUBIERTA
L50x50x5mm
6
2.80
3.6
60.48
ngulosInferior
L50x50x5mm
6
3.20
3.6
69.12
ngulosSuperior
129.60
TOTAL:
kg

CANTIDADESDEHORMIGN
DatosEspecficos:
PesoEspH=
fy=
f'c=

2400
4200
350

kg/m3
kg/cm2
kg/cm2

ESTRUCTURADEDESINFECCIN
Nmero
Long./Esp. rea
#
m
m
1
0.30
895.50
1
195.10
1.02
1
8.75
1.02
1
427.00
0.49
1
0.150
7.43
1
7.30
0.65
1
0.150
10.80
1
8.80
0.65
1
0.150
35.48
24
8.650
0.0825
2
8.650
0.05
3
2.150
0.05
48
3.400
0.18
144
0.110
4.62
TOTAL:

Volumen
Peso
Observaciones
m3
kg
268.65
644760 LosadeCimentacin
199.0
477604.8 ParedesExternas
8.925
21420 ParedIntermedia
208.1625 499590 ParedesInternas
1.11375
2673 LosaC.Ingreso
4.745
11388 ParedesC.Ingreso
1.62
3888 LosaC.Salida
5.72
13728 ParedesC.Salida
5.321
12771 LosaSuperior
17.127
41104.8 VigasV1
0.865
2076 VigasV2
0.3225
774
VigasV3
28.56
68544 Columnas
73.1808 175633.92 LosasDesmontables
823.31

1975956

RESUMENDEMATERIALESDEESTRUCTURADEDESINFECCIN
Materiales
Unidad
MaterialdeMejoramiento(e=20cm)
m3
Hormignf'c=140kg/cm2(Replantillo)
m3
EncofradoparaLosa
m2
EncofradoparaMurosyParedes
m2
Hormignf'c=350kg/cm2
m3
AcerodeRefuerzocorrugadofy=4200kg/cm2
kg
PerfileraMetlica
kg

Cantidad
187.10
93.55
53.70
2150.66
823.31
85883.58
129.60