BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

Dead Load Calculation (roof slab):


Self Weight of Slab
6mm ceiling Plastering
Foam concrete
Top plastering
Roof built up weight
Concrete Tiles

=
=
=
=
=
=

0.15
0.006
0.075
0.015

x
x
x
x

25.00
20.40
10.00
20.40

0.02

25.00

=
=
=
=
=
=

3.75
0.1224
0.75
0.306
0.1
0.5

5.53 kN/m2
5.55 kN/m2

Say
Wall Load Calculation (230 mm thk wall):
Unit weight of Brick
=
20.00
Thickness of wall
=
0.23
Unit weight of Plastering
=
20.40
Outside plastering thicknes =
0.018
Inside plastering thickness =
0.012
Intensity of wall load

S.No.

=
=

kN/m3
m
kN/m3
m
m

20 X 0.23 + (0.018 + 0.012)*20.4


5.21 kN/m2

Description

Wall Intensity of
Height wall load
1 Above Plinth Beam 2.6
5.21

UDL in
kN/m
13.55

2 Beam @ 3.0 Lvl


1.7
5.21
(bot of roof beam to top of lintel beam )
Wall Load Calculation (345 mm thk wall):
Unit weight of Brick
=
20.00
Thickness of wall
=
0.345
Unit weight of Plastering
=
20.40
Outside plastering thicknes =
0.018
Inside plastering thickness =
0.012
Intensity of wall load

S.No.

=
=

kN/m2
kN/m2
kN/m2
kN/m2
kN/m2
kN/m2

8.9

Remarks
Grid (A1 -H1, A1A2, H1H2,G1G2
E2H2,F3G3,F2F3,G2G3)
Grid (A1 -H1, A1A2, H1H2,E2H2)

kN/m3
m
kN/m3
m
m

20 X 0.345 + (0.018 + 0.012)*20.4


7.51 kN/m2

Description

Wall Intensity of
Height wall load
1 Above Plinth Beam 2.6
7.51
2 Beam @ 3.0 Lvl
1.7
7.51
3 Above Plinth Beam 3.2
7.51
(bot of roof beam to top of lintel beam

UDL in
kN/m
19.53
12.8
24.0

Remarks
Grid (A2 -E2)
Grid (A2 -E2)
Grid (D2D4,C2C4,B2B4)

Wall Load Calculation - RC Parapet Wall (150 mm thk wall):


Unit weight of concrete
=
25.00 kN/m3
Thickness of wall
=
0.15 m
Unit weight of Plastering
=
20.40 kN/m3
Outside plastering thicknes =
0.018 m
Inside plastering thickness =
0.012 m

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
Dead Load

C.1-1

PE-DC-239-653-C001
PART 1
R0

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

Intensity of wall load

S.No.

Description

=
=

25 X 0.15 + (0.018 + 0.012)*20.4


4.36 kN/m2

Wall Intensity of
Height wall load
1.4
4.36

UDL in
kN/m
6.1

1 RC Parapet Wall
2
Moment & Shear Calculation for sunshade
For Sunshade of Rolling Shutter
Unit weight of Concrete
Thickness of sunshade
Self weight of sunshade
Floor finish
Live load
Intensity of load on sunshade
Thickness of facia on
sunshade
Height of facia on
sunshade
Load due to facia work

=
=
=
=
=
=

=
=

Remarks
A1H1, A1A2,A2H2,H1H2

Grid - A1 A2

25.00
0.10
2.50
1.00
0.75
4.25

kN/m3
m
kN/m2
kN/m2
kN/m2
kN/m

0.075
0.16 m

=
=

0.075 x 0.16 x 25 x 1
0.3
KN
4.25

0.3

0.3
4.25
1.00
0.16 m
0.10 m
1.00
Moment

=
(4.25 x 1 x 1 / 2) + (0.3 x ( 1 - 0.075/2))
=
2.41
KNm
2.41 Knm/m is applied as uniform moment for a length of 3.6m

Shear force

=
(4.25 x 1 ) + 0.3
=
4.55
KN
4.55 KN/m is applied as uniform load for a length of 3.6m

For Sunshade of SW 1
For Window
Unit weight of Concrete
Thickness of sunshade
Self weight of sunshade
Floor finish

Grid - A1A2,A1B1,B1C1,C1D1,D1E1,E1F1,G1H1,F1G1,H1H2,
H1H2, H2G2, E2F2
=
=
=
=

25.00
0.100
2.50
1.00

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
Dead Load

kN/m3
m
kN/m2
kN/m2

C.1-2

PE-DC-239-653-C001
PART 1
R0

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

Live load
=
Intensity of load on sunshade =
Thickness of facia on
sunshade
Height of facia on
sunshade
Load due to facia work

=
=
=
=

0.75 kN/m2
4.25 kN/m

0.075
0.13 m
0.075 x 0.16 x 25 x 1
0.24
KN
4.25

0.24

0.24
4.25
0.60
0.13 m
0.10 m
0.60
Moment

=
(4.25 x 0.6 x 0.6 / 2) + (0.24 x ( 0.6 - 0.075/2))
=
0.900
KNm
0.9 Knm/m is applied as uniform moment for a length of 2.4m

Shear force

=
(4.25 x 0.6 ) + 0.24
=
2.79
KN
2.79 KN/m is applied as uniform load for a length of 2.4m

For Sunshade of SD1


For Door
Unit weight of Concrete
=
Thickness of sunshade
=
Self weight of sunshade
=
Floor finish
=
Live load
=
Intensity of load on sunshade =
Thickness of facia on
sunshade
Height of facia on
sunshade

Load due to facia work

=
=

=
=

Grid - H1H2
25.00
0.075
1.88
1.00
0.75
3.63

kN/m3
m
kN/m2
kN/m2
kN/m2
kN/m

0.075
0.16 m

0.075 x 0.16 x 25 x 1
0.29
KN
3.63

0.29

0.29
3.63
0.75

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
Dead Load

C.1-3

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

PE-DC-239-653-C001
PART 1
R0

0.16 m
0.08 m
0.75
Moment

=
(3.625 x 0.75 x 0.75 / 2) + (0.29 x ( 0.75 - 0.075/2))
=
1.226
KNm
1.23 Knm/m is applied as uniform moment for a length of 2.4m

Shear force

=
(3.625 x 0.75 ) + 0.29
=
3.00875
KN
3.01 KN/m is applied as uniform load for a length of 2.4m

For Sunshade of SD2


For Door
Unit weight of Concrete
=
Thickness of sunshade
=
Self weight of sunshade
=
Floor finish
=
Live load
=
Intensity of load on sunshade =
Thickness of facia on
sunshade
Height of facia on
sunshade
Load due to facia work

=
=
=
=

Grid - A1A2, F1G1


25.00
0.075
1.88
1.00
0.75
3.63

kN/m3
m
kN/m2
kN/m2
kN/m2
kN/m

0.075
0.16 m
0.075 x 0.16 x 25 x 1
0.29
KN
3.63

0.29

0.29
3.63
0.75
0.16 m
0.08 m
0.75
Moment

=
(3.625 x 0.75 x 0.75 / 2) + (0.29 x ( 0.75 - 0.075/2))
=
1.226
KNm
1.23 Knm/m is applied as uniform moment for a length of 1.3m

Shear force

=
(3.625 x 0.75 ) + 0.29
=
3.009
KN
3.01 KN/m is applied as uniform load for a length of 1.3m

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
Dead Load

C.1-4

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
Dead Load

PE-DC-239-653-C001
PART 1
R0

C.1-5

PE-DC-239-653-C001
PART 1
R0

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

DETERMINATION OF THICKNESS OF FLOOR SLAB (For STAAD input)


SWITCH GEAR ROOM (+5.0m LVL)
SLAB @ 5.0 LVL.
Grid G - H & 1 - 2
Design of Roof slab for Switch Gear Room
Length of the slab ,Ly
=
6
Breadth of the slab, Lx
=
5
Ratio Ly/Lx
=
1.2
DESIGN AS TWOWAY SLAB
Assume slab thickness
=
150
DEAD LOAD
Self Weight of Slab
=
0.15
x
25.00
6mm ceiling Plasterin
=
0.006
x
20.40
Foam concrete
=
0.065
x
10.00
Top plastering
=
0.015
x
20.40
Roof built up weight
=
Concrete Tiles
=
0.02
x
25.00

m
m
<2
mm
=
=
=
=
=
=

3.75
0.122
0.65
0.306
0.1
0.5

LIVE LOAD
=
1.50
TOTAL LOAD
=
6.93
Factored load
=
10.39
TWO ADJACENT EDGES DISCONTINUOUS
IS 456 Table 26
Slab Moment as per boundary condition
=
0.052 * 10.39 * 5 * 5
Slab Moment as per boundary condition
=
15.59
fck
=
30
N/mm^2
fy
=
415
N/mm^2
b
=
1000
mm
Mulimit
=
0.138*fck*b*d*d
After Substituting we get
d
=
61.37
Overall Depth
=
61.37+25+6
d
=
92.37
Let us consider 150 mm THK Slab
SWITCH GEAR ROOM (+5.0m LVL)
SLAB @ 5m LVL.
Grid F - G & 1 - 2
Design of Roof slab for Switch Gear Room
Length of the slab ,Ly
=
6 m
Breadth of the slab, Lx
=
5 m
Ratio Ly/Lx
=
1.2 < 2
DESIGN AS TWOWAY SLAB
Assume slab thickness
=
150 mm
DEAD LOAD
Self Weight of Slab
=
0.15
x
25.00
=
3.75
6mm ceiling Plasterin
=
0.006
x
20.40
=
0.122
Foam concrete
=
0.075
x
10.00
=
0.75
Top plastering
=
0.015
x
20.40
=
0.306
Roof built up weight
=
=
0.1
Concrete Tiles
=
0.02
x
25.00
=
0.5
LIVE LOAD
=
1.50
TOTAL LOAD
=
7.03
Factored load
=
10.54
ONE LONG EDGE DISCONTINUOUS
IS 456 Table 26
Slab Moment as per boundary condition
=
0.052 * 10.39 * 5 * 5
Slab Moment as per boundary condition
=
13.71

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
SLAB

kN/m2
kN/m2
kN/m2
kN/m2
kN/m2
kN/m2
Kn/m^2
Kn/m^2
Kn/m^2

Knm

mm
mm

kN/m2
kN/m2
kN/m2
kN/m2
kN/m2
kN/m2
Kn/m^2
Kn/m^2
Kn/m^2

Knm

C.2-1

PE-DC-239-653-C001
PART 1
R0

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

fck
fy
b
Mulimit
After Substituting we get
Overall Depth
=

=
=
=
=

30
N/mm^2
415
N/mm^2
1000
mm
0.138*fck*b*d*d
57.55+25+6

d
d

=
=

57.55
88.55

mm
mm

Let us consider 150 mm THK Slab

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
SLAB

C.2-2

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
SLAB

PE-DC-239-653-C001
PART 1
R0

C.2-3

BHEL - 1500MW CCPP PRAGATI - III


CHEMICAL LABORATORY BUILDING - ANALYSIS AND DESIGN

PE-DC-314-646-C003

Design calculation for Aircompressor & workshop


1

DEAD LOAD

Load on roof :
1. Load on Roof :
Wt. of Sheeting = 10 kg/sq.m
Wt. of Purlin & Rafter Bracing = 20 kg/sq.m
Hence, DL on roof = 30 kg/sq.m

LIVE LOAD
1. Load on Roof :
Roof Slope = 1:3
= 18.43
LL = (18.43 - 10) X 2 = 58.14 kg/sq.m
Dust Load = 20 kg/sq.m

[Ref. IS : 875 (Part - 2)]

Hence, LL = (58.14 + 20) = 78.14 kg/sq.m

WIND LOAD

Here, Basic wind speed, Vb = 44

m/Sec
As per Cl. 5.3 - IS:875 - Part 3

Now, Design Wind Speed Vz = k1.k2.k3.Vb


Where, k1 =
1 = Risk Coefficient (from Table - 1 IS:875 - Part 3)
k2 =
Terrain, height & structure size factor. Considering terrain category
2, class C structure and 6 m (max) height (From Table - 2 IS:875 - Part 3)
k2 =
1 for up to 10.0 m height

Now, Design Wind pressure, Pz = 0.6 X Vz2 (as per Cl. 5.4 - IS:875 - Part 3)
Hence, Pz (for up to 10.0 m height) =
1161.6 N/m2
118.5 Kg/m2

1. Wind Load on Bldg. :


[Ref. Table - 4 of IS 875 (Part - 3)]
Specification w = 10m, l =18m & h = 6m
Hence, h/w = 6/10 = 0.6;
l/w = 18/10 = 1.8 ;
x
C

z

(p) (s)
(s)
(p)

(p) = Internal pressure (away from the structure)


(s) = Internal suction (towards the structure)
B

(p)
(s)
(s) (p)

Openings are considered in between 5% to 20%


Hence, Cpi = [Cl. 6.2.3.2 of IS 875 (Part- 3)]

When wind blows along (+X) direction


on A = 0.7 - 0.5(p) = 0.2 ()

When wind blows along (-X) direction


on A = -0.3 - 0.5(p) = -0.8 ()

= 0.7 + 0.5 (s) = 1.2 ()


on B = -0.3 - 0.5(p) = -0.8 ()

= -0.3 + 0.5 (s) = 0.2 ()


on B = 0.7 - 0.5(p) = 0.2 ()

= -0.3 + 0.5 (s) = 0.2 ()


on C = -0.7 - 0.5(p) = -1.2 (())

= 0.7 + 0.5 (s) = 1.2 ()


on C = -0.7 - 0.5(p) = -1.2 (())

= -0.7 + 0.5 (s) = -0.2 (())


on D = -0.7 - 0.5(p) = -1.2 (())

= -0.7 + 0.5 (s) = -0.2 (())


on D = -0.7 - 0.5(p) = -1.2 (())

= -0.7 + 0.5 (s) = -0.2 (())

= -0.7 + 0.5 (s) = -0.2 (())

When wind blows along (+Z) direction


on A = -0.5 - 0.5(p) = -1 ()

When wind blows along (-Z) direction


on A = -0.5 - 0.5(p) = -1 ()

= -0.5 + 0.5 (s) = 0 ()


on B = -0.5 - 0.5(p) = -1 ()

= -0.5 + 0.5 (s) = 0 ()


on B = -0.5 - 0.5(p) = -1 ()

= -0.5 + 0.5 (s) = 0 ()


on C = 0.7 - 0.5(p) = 0.2 (())

= -0.5 + 0.5 (s) = 0 ()


on C = -0.1 - 0.5(p) = -0.6 (())

= 0.7 + 0.5 (s) = 1.2 (())


on D = -0.1 - 0.5(p) = -0.6 (())

= -0.1 + 0.5 (s) = 0.4 (())


on D = 0.7 - 0.5(p) = 0.2 (())

= -0.1 + 0.5 (s) = 0.4 (())

2. Wind Load on Roof :

= 0.7 + 0.5 (s) = 1.2 (())

[Ref. Table - 5 of IS 875 (Part - 3)]

Hence, h/w = 6/10 = 0.6;


When wind blows along (X) direction

[When = 0]

Windward side
For Pre.= 1.04 - 0.5 = 0.54 Pz ()
For Suc. = 1.04 + 0.5 = 1.54 Pz ()

0.585

Leeward side
For Pre.= 0.585 - 0.5 = 0.085 Pz ()

1.04

For Suc. = 0.585 + 0.5 = 1.085 Pz ()

When wind blows along (Z) direction


0.6
0.8

[When =90]
Windward side
For Pre.= 0.8 - 0.5 = 0.3 Pz ()

For Suc. =0.8 + 0.5 = 1.3 Pz ()


Leeward side
For Pre.= 0.6 - 0.5 = 0.1 Pz ()
For Suc. = 0.6 + 0.5 = 1.1 Pz ()

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
306691107.xls

4
SEIEMIC LOAD
Reference code

Considered data's:
Seismic zone

0.16

Importance factor
Response reduction factor

=
=

1.75
4

IS - 1893-2002/05

SVP

03/01/2016

REV.NO. R0
PE-DC-297-646-C001

BHEL - 345.4 MW NAGOTHANE CCPP


STRUCTURAL ANALYSIS AND DESIGN REPORT FOR CHEMICAL LAB BUILDING

7.1

DEAD LOAD

7.1.1 Dead Load of Roof slab:


Self Weight of Slab

0.150

25.00

3.75 kN/m2

6 mm ceiling plastering

0.006

20.40

0.12 kN/m2

Screed Concrete

0.0425

24.00

1.02 kN/m2

Foam concrete

0.075

10.00

0.75 kN/m2

Top plastering

0.015

20.40

0.31 kN/m2

0.10 kN/m2

0.50 kN/m2

6.55 kN/m2

Roof Water proofing membrane


Concrete tiles

0.020

25.00

Sl.
No.

Elevation (m)

Load intensity

Remarks

(+) 4.00m

6.55

Members at (+) 4.00m

Projection of the roof slab from the outer beam

Load on the outer beam due to the slab projection

=
=

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls

1 m
6.55 x 1

kN/m
6.55 kN/m

03/01/2016

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR CHLORINATION PLANT

7.3

PE-DC-239-637-C001

Mono-Rail Load
Capacity of the Mono-Rail

=
=
=

Weight of the Hoist


(As per monorail vendor REVA Industries ltd)
Impact Factor
Total Imposed load on the beam

Self weight of Monorail

(ISMB 300)

3.00 T
30.00 kN
2.80 kN

1.25

=
=

30 x 1.25 kN
37.50 kN

0.45 kN/m

Dead Load calculation :


Dead load calculation
Sl.
No.

Memb. No.

1
2
3
4
5

401
402
403
404
405

Dead Load
Contributory
from Rail
width (m)
(kN/m)
0.45
0.45
0.45
0.45
0.45

1.60
3.15
3.25
3.38
3.19

Load
(kN)
0.72
1.42
1.46
1.52
1.44

Total Dead
load
Location of
including
load from
starting node Wt of hoist
3.385
3.385
3.385
3.385
3.385

3.52
4.22
4.26
4.32
4.24

Live Load calculation :


Live load calculation
Sl.
No.

Memb. No.

Live load
on crane

Location of
Total Load
load from
(kN)
starting node

Load Type

1
2

Load Position for Design of Foundation


37.50
3.385
37.50
401 405
37.50
3.385
37.50
403

CON GY
CON GY

3
4

Load Position for Design of Roof Beams


37.50
3.385
37.50
401 403 405
37.50
3.385
37.50
402 404

CON GY
CON GY

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls

KHM

03/01/2016

BHEL - 345.4 MW NAGOTHANE CCPP


STRUCTURAL ANALYSIS AND DESIGN REPORT FOR CHEMICAL LAB BUILDING

7.1.2

Wall Load Calculation :

REV.NO. R0
PE-DC-297-646-C001

( 230 mm thick Wall )

Unit weight of Brick

18.85

kN/m3

Thickness of wall

0.23

Unit weight of Plastering

20.40

kN/m3

Outside plastering thickness

0.018

Inside plastering thickness

0.012

Intensity of wall load

=
=

As per Table-1,
(item 36), IS-875 (Part 1)

As per Table-1,
(item 40), IS-875 (Part 1)

S.No

2
3
4
5
6
7
8
9

Member
EL (-) 0.50 (Plinth level)
1024 to 1027 1029
1020 to 1023 1028
1016 to 1019
1012 to 1015
1000 to 1002
1003 1004
1005 1006
1007 1008
1009 to 1011

8
9
10
11
12
13
14
15
16

EL (+) 2.10 (Lintel level)


2023 to 2026
2019 to 2022
2015 to 2018
2011to 2014
2000 to 2002
2003 2004
2005 2006
2007 2029
2008 to 2010

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls

18.85 x 0.23+ (0.018+0.012) x 20.4


4.95 kN/m
Height of
wall (m)

Location /
GRID

UDL in
kN/m

2.60

Grid 1
Grid 2
Grid 3

12.86
12.86
12.86
12.86
12.86
12.86
12.86
12.86
12.86

9.40
9.40
9.40
9.40
9.40
9.40
9.40
9.40
9.40

2.60
2.60
2.60
2.60
2.60
2.60
2.60
2.60

1.90
1.90
1.90
1.90
1.90
1.90
1.90
1.90
1.90

Grid 4
Grid A
Grid B
Grid C
Grid D
Grid E

Grid 1
Grid 2
Grid 3
Grid 4
Grid A
Grid B
Grid C
Grid D
Grid E

Eccentricity

03/01/2016

BHEL - 345.4 MW NAGOTHANE CCPP


STRUCTURAL ANALYSIS AND DESIGN REPORT FOR CHEMICAL LAB BUILDING

Moment
-

REV.NO. R0
PE-DC-297-646-C001

Remarks
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC
EL (-) 0.50 TOC

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls

EL (+) 2.1 TOC


EL (+) 2.1 TOC
EL (+) 2.1 TOC
EL (+) 2.1 TOC
EL (+) 2.1 TOC
EL (+) 2.1 TOC
EL (+) 2.1 TOC
EL (+) 2.1 TOC
EL (+) 2.1 TOC

03/01/2016

BHEL - 345.4 MW NAGOTHANE CCPP


STRUCTURAL ANALYSIS AND DESIGN REPORT FOR CHEMICAL LAB BUILDING

REV.NO. R0
PE-DC-297-646-C001

7.1.3 Wall Load Calculation - RC Parapet Wall (150 mm thk wall):


Unit weight of Concrete

25.00

kN/m3

Thickness of wall

0.125

Unit weight of Plastering

20.40

kN/m3

Outside plastering thickness

0.012

Inside plastering thickness

0.018

Intensity of wall load

=
=

25 x 0.125+ (0.012+0.018) x 20.4


3.74 kN/m

Sl.
No.

Parapet wall height (m)

Load intensity (kN/m)

Remarks

0.90

3.36

Members at (+) 4.00m

Moment due to Parapet wall on the Roof beams:


Total Load of parapet wall

3.36 kN/m

Parapet Eccentricity from the centre of beam

1 m

Moment due to eccentric parapet on the roof beam

3.36 kN.m/m

Total Load of parapet wall

3.36 kN/m

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls

03/01/2016

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR CHLORINATION PLANT

PE-DC-239-637-C001

DESIGN OF SAG ROD

Maximum pull on sag rod

Dia of rod provided

Stress on the rod

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls

5.00 kN
12 mm
= 5.00 / (pi) x 12^2 / 4 =
<150 N/mm2
44.2 N/mm2

KHM

03/01/2016

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
ISOMETRIC VIEW

PE-DC-239-653-C001
PART 1
R0

D.1-1

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
ISOMETRIC VIEW

PE-DC-239-653-C001
PART 1
R0

D.1-2

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
ISOMETRIC VIEW

PE-DC-239-653-C001
PART 1
R0

D.1-3

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-1

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-2

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-3

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-4

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-5

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-6

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-7

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-8

BHEL - 2 X 250MW BHILAI TPS


DESIGN CALCULATION FOR SWITCH GEAR ROOM BUILDING - SUB-STRUCTURE

file:///var/www/apps/conversion/tmp/scratch_4/306691107.xls
FRAMING ELEVATIONS

PE-DC-239-653-C001
PART 1
R0

D.2-9