Академический Документы
Профессиональный Документы
Культура Документы
N
PA
R T ME
MECHANIC
AL
MET
LOGY
HNO
EC
I NEER I NG
ENG
T
MET 412
2/25
Chapter 1
Psychrometric Properties of Moist Air and Conditioning processes.
1.1- Introduction
Air Conditioning can be defined as the process of treating air in an internal
environment to establish and maintain required standards of temperature, humidity,
cleanliness, and motion.
There are numerous applications for Air Conditioning in which human comfort is the
prime consideration such as, shops, offices, factories, transport, --------etc, but there
are also many applications human comfort is not the prime consideration. These
include textile and printing industries, mainframe, servers, computers -----------etc.
Therefore understanding of the properties of moist air and the ability to analyze the
various processes involving air and water vapour is basic to the refrigeration and
HVAC (Heating Ventilation and Air Conditioning) Engineers.
1.2- Composition of Air
The ASHRAE handbook of fundamentals gives the following approximate
composition of dry air by volume fraction.
Constituent
Molecular weight
kg/kmol
Volume fraction
Nitrogen
Oxygen
Argon
Carbon Dioxide
28
32
39.94
44
0.7809
0.2095
0.0093
0.0003
Table (1)
Based on the composition of dry air in Table (1), the molecular weight M a of dry air is
28.965, then the gas constant Ra is
Ra
R
8.3145
0.287 ( kJ/ kg K )
M a 28.965
The basic medium in air conditioning practice is a mixture of dry air and water vapor.
The water vapor constant Rv is
Rv
R
8.3145
0.462 ( kJ/ kg K )
Mv
18
3/25
MET 412
P
i 1
where:
Because the various constituents of the dry air may be considered to one gas. Then
the total pressure of moist air is,
P = Pa + Pv
where Pa
Pv
Tdb
MET 412
4/25
MET 412
5/25
The temperature at which the water vapour in the air is saturated or the minimum
temperature any surface exposed to airflow can have without visible condensation
occurring on it. Obviously then the DP temperature of the air is always the saturation
temperature corresponding to partial pressure exerting by the water vapour.
Consequently when the partial pressure exerted by the water vapour is known, the
DP temperature of the air can be determined from the saturated water tables.
Likewise when DP temperature of the air is known, the partial pressure exerted by the
water vapour can be determined from the saturated water tables.
Example 1.1
Air has a temperature of 26 oC and partial pressure exerted by water vapour in the air
is 1.227 kPa. Determine the DP temperature of the air.
Solution
From the saturated water tables at P =1.227 kPa. DP = 10 oC.
Example 1.2
Air has a temperature of 26 oC and has a DP temperature of 16 oC. Determine the
partial pressure exerted by the water vapour.
Solution
From saturated water tables at T=16 oC. Partial pressure of water vapour = 1.8168
kPa.
Relative humidity can be defined as, the ratio of the actual partial pressure exerted
by the water vapour in any volume of the air to the partial pressure that would be
exerted by the water vapour if the water vapour in the air is saturated at the
temperature of that air,
RH
Example 1.3
Air has a temperature of 26 oC and DP temperature of 10 oC. Determine the RH.
MET 412
6/25
Solution
RH
Pv
Ps
at 10 oC 1.227
x 100 36.5%
at 26 oC
3.36
Sometimes called specific humidity, is the ratio of the mass of the water vapour mv
to the mass of dry air ma.
mv
ma
kg
kg of dry air
Using the ideal gas law we can drive a relation between the humidity ratio and
relative humidity.
mv
Pv V
Rv T
ma
Pa V
Ra T
Then
Ra Pv
P
0.287 Pv
0.622 v
Rv Pa
0.462 Pa
Pa
Pa Patm Pv ,
W
0.622
and
RH
W Pa
0.622 Ps
Pv
Patm Pv
MET 412
7/25
Example 1.4
Determine the W and RH for air at saturated atmosphere having a temperature of 26
o
C and DP temperature of 10 oC.
Solution
0.622
0.622
Pv
Patm Pv
1.227
0.00762 kg/kg dry air
101.325 1.227
Is the ratio of the mass of water vapour in the air per unit mass of dry air to the
mass of water vapour required for saturation of the same air sample.
W
x 100
Ws
Example 1.5
Air at normal atmosphere pressure has a temperature of 26 oC and DP temperature of
10 oC. Determine the saturation ratio of the air.
Solution
W
x 100
Ws
W 0.622
Pv
1.227 (at T 10 o C)
0.622
0.00762 kg/kg dry air
Patm - Pv
101.325 1.227
Ws 0.622
Ps
3.36 (at T 26 o C)
0.622
0.02133 kg/kg dry air
Patm - Ps
101.325 3.36
Then
0.00762
x 100 35.7 %
0.02133
MET 412
8/25
Enthalpy Deviation
Is the difference between the actual or true specific enthalpy of the air at any given
condition and the specific enthalpy of saturated air at the same WB temperature.
1.7- The Heat Content of Enthalpy of Air
Air has both sensible heat and latent heat. The total heat of the air at any condition is
the sum of sensible heat and latent heat.
Sensible heat of the air is a function of the DB temperature.
Latent heat of the air is a function of the DP temperature.
Total heat of the air is a function of the WB temperature
The enthalpy of a mixture of perfect gases is equal to the sum of the enthalpies of
each constituent and is usually referenced to a unit mass of one constituent. For the
air-water vapour mixture dry air is used as the reference because the amount of water
vapour may vary during some processes
h = ha +W x hw,v
ha =Cpa x t, hw,v = hg +Cpv x t , and hg =2501.3 at zero oC
h = t + W (2501.3 +1.88t)
(kJ/kga)
Sensible Heat ( Q s )
For any given DB temperature, the sensible heat of air is taken as the enthalpy of dry
air at that temperature as calculated from 0 oC and can be computed from
a C p,a T m
C p,a T m
a ha
Q s m
Example 1.6
The temperature of 10 kg of air is increased from 30 oC to 50 oC by addition of heat.
Determine the quantity of sensible heat supplied.
Solution
MET 412
9/25
hw,v
is the specific enthalpy of the water vapour in the air, usually taken as
the enthalpy of saturated water vapour at the saturation temperature
equal to the air DP temperature
= hg + Cpv (DB-DP), Cpv = 1.88 kJ/kg
Convenient empirical equation for determining the enthalpy of low pressure, low
temperature steam (such as that found in the air) is,
hw,v = hg + Cpv DB, hg = 2501.3 kJ/kg
Example 1.7
Fourty five kg/min of air having DB and DP temperature of 35 oC and 20 oC
respectively are passed across a cooling coil and cooled to a final DB temperature of
12 oC. Assuming that the air leaving the cooling coil is saturated (DB, WB, and DP
temperatures are the same). Calculate
a-
b-
Solution
MET 412
10/25
Q t = m a [ ht,2- ht,1]
1.9- Standard Air
Is defined as air having a density of 1.2kg/m3 or a specific volume of (1/1.2) = 0.833
m3/kg.
Q s = m a Cp,a T
= 1.2 Va T
11/25
MET 412
Figure 1.1 shows a schematic of heating or cooling device and Figure 1.2 shows the
process on the Psychrometric chart.
Energy Balance between 1 and 2
h2
h1
h1
h2
m a h1 = Q t + m a h2
Q t = m a (h1 h2)
h1 = ha,1 + W 1 hw,1
MET 412
12/25
h2 = ha,2 + W2 hw,2
2 kg/s of air having initial dry bulb temperature and wet bulb temperature of 21 oC and
16 oC are passed across a heating coil and dry bulb temperature is raised to 33 oC.
Plot the process on a Psychrometric chart and determine:
a-The final WB temperature of the air.
b-The sensible heat transferred in kW.
c-The total heat transferred in kW.
Solution
13/25
MET 412
When moist air is cooled to a temperature below its dew point temperature some of
the water vapour will condense and leave the stream. Figure 1.3 shows a schematic
of cooling and dehumidifying device and Figure 1.4 shows the process on the
psychrometric chart.
h2
h1
hw
h1
ha
h2
m a h1 = Q t + m a h2 + m w hw
Q t = m a (h1 h2) - m w hw
(1.1)
m a W1 = mw + m a W2
m w = m a (W1 W2)
(1.2)
14/25
MET 412
(1.3)
Q s = m a Cp,a
(1.4)
db
By referring to psychrometric chart, we may also express the latent heat transfer as
Q l = m a ( h1-ha)
(1.5)
Q s = m a ( ha-h2)
(1.6)
Q t = Q s + Q l
(1.7)
The sensible heat factor SHF is defined as Q s / Q t . This parameter is shown on the
semicircular.
MET 412
15/25
Example 1.9
Conditioned air is supplied to a space at 15 oC DB temperature and 14 oC WB
temperature at the rate of 0.5 m3/s. The sensible heat factor for the space is 0.7 and
the space is to be maintained at 24 oC DB temperature. Determine the sensible and
latent cooling loads for the space.
Solution
MET 412
16/25
Example 1.10
4 kg/s of air, having initial DB and WB temperatures of 30 oC and 21 oC respectively,
are passed across a cooling coil whose mean effective surface temperature is 10 oC.
Assuming that all parts of the air contact the cooling surface so that the air leaves the
coil saturated at the temperature of the coil surface. Plot the process on the
psychrometric chart and determine
abcdeSolution
17/25
MET 412
Air conditioning which human comfort is the prime consideration may be described as
the control of temperature and humidity. The process of heating and humidifying of
moist air is generally required during cold months of the year. Figure 1.5 shows a
schematic of heating and humidifying device and Figure 1.6 shows the process on the
psychrometric chart.
h1
h2
h2
h1
m a h1 + Q t + m w hw = m w h2
Q t = m a (h2 h1) - m w hw
(1.8)
18/25
MET 412
m a W1 + mw = m w W2
m w = m a (W2 W1)
(1.9)
(1.10)
where hw is the water vapour enthalpy at inlet temperature which is normally 100 oC
(2676 kJ/kg).
Dividing by m a (W2 W1)
Q t
h h1
2
hw
m a (W2 W1 ) W2 W1
(1.11)
Q
h2 h1
t hw
W2 W1 m w
(1.12)
h2 h1
hw
W2 W1
Protractor
hw>hg
hw<hg
hw=hg
SHF=0
hw=hg
h
W
SHF
17 oC
hw<hg
hw>hg
Tw=Twb
SHF=1
24 oC
Tdb
MET 412
19/25
Example 1.11
Moist air at 16 oC DB temp. and 20% relative humidity flows through a heater and
humidifier at the rate of 0.75 m3/s. Heat is transferred to the air at the rate of 30 kW.
Saturated water vapour at 100 oC is injected at the rate of 0.00625 kg/s. Determine
the final state of the moist air if the process occurs at 100 kPa.
Solution
20/25
MET 412
h1
h3
h2
h3
h1
Figure 1.8
a3 m
a1 m
a2
m
(1.13)
a3W3 m
a1W1 m
a 2W2
m
W3
m a1W1 m a 2W2
m a 3
(1.14)
(1.15)
Since the mixing of the airstreams occurs adiabatically (without gain or loss of heat)
and without gain or loss of moisture, it follows that the enthalpy of the mixture is the
sum of the enthalpies of the components, that is
(1.16)
21/25
MET 412
(1.17)
(1.18)
3h 3 m
1h1 m
2h2
m
(1.19)
T3
m a1T1 m a 2T2
m a 3
(1.20)
(1.21)
By combining equations (1.19), (1.15) and (1.13) and eliminating m a , we obtain the
following result.
h2 h3 W2 W3
m
a1
h3 h1 W3 W1 m a 2
(1.22)
Example 1.12
0.575 kg/s of air at 38 oC DB temperature and 24 oC WB temperature are mixed with
1.15 kg/s of air at 15 oC DB temperature and 10 oC WB temperature. The process is
adiabatic, at a steady state steady flow rate and standard sea level pressure. Find
the condition of the mixed stream.
Solution
22/25
MET 412
BPF
T2 Td
T1 Td
(1.23)
and
1 BPF
T1 T2
T1 Td
(1.24)
Where BPF is the fraction of air bypassed, or coil bypass factor, expressed as a
decimal, and where the temperatures are dry bulb values. Now
Q s = m 1 cpa (T1-T2)
(1.25)
(1.26)
or
Example 1.15
Find the bypass factor for the coil of example 1.13 and compute the sensible and
latent heat transfer rates.
Solution
23/25
MET 412
CF
t1 t 2
t1 t d
(1.27)
2-
Calculate (i)- RH, (ii)- W, (iii)- dew point temperature, (iv)- density and (v)- enthalpy of
atmospheric air when the DBT is 35 oC and WBT is 23 oC.
3- A certain quantity of air has a temperature of 25 oC and that the water vapor in the air
exerts a partial pressure of 1.7051kPa. Determine the DP temperature and RH
4- Determine the humidity ratio, enthalpy, and specific volume for saturated air at 101.325
kPa using perfect gas relations and Thermodynamic Tables for temperatures of,
a- 25 oC
b-
-5 oC
5- The temperature of a certain room is 20oC and the relative humidity is 50%.
barometric pressure is 100kPa. Find,
abc-
The
6- 40 m3/min of a mixture of recirculated room air and outdoor air inter a cooling coil at 31
o
C DB and 18.5 oC WB temperatures. The effective surface temperature of the coil is 4.4
o
C. The surface area of the coil is such as would give 12.5 kW of refrigeration with the
given entering air state. Determine the dry and wet bulb temperatures of the air leaving
the coil and the coil bypass factor.
7- Moist air enters a chamber at 10 oC DBT and 5 oC WBT at a rate of 1.5 m3/s. The
barometric pressure is 101.325 kPa. While passing through the chamber, the air absorbs
sensible heat at a rate of 40 kW and picks up 40 kg/h of saturated steam at 100 oC.
Determine the dry and wet temperatures of the leaving air.
MET 412
24/25
MET 412
25/25