1. General
This document is a Specification and Drawing of Coal Bunker Microcell (Load Cell) (Coal
Bunker Weighing System) for COCHRANE THERMOELECTRIC POWER PLANT, PULVERIZED
COAL FIRED BOILER project.

2. System Overview
Each Coal Bunker is supported on 4 legs (box shape of 400mm x 400mm x t32mm). Two Strain
Gauge Sensors per leg will be supplied. Each of the pair of sensors will be connected to one (1)
Junction Box by means of a cable supplied by Kistler-Morse. Wire from each Junction Box to a
Stahl Barrier Assembly. Stahl Barrier Assembly to be located within approximately 10 feet
distance from Weight Indicator, Model SVS2000. Interconnecting cable from Junction Box to
Stahl Barrier Assembly and from Stahl Barrier Assembly to Weight Indicator to be supplied by
Kistler- Morse.

Each Coal Bunker requires:


8 pcs.

P/N MC-3-X-X-F-065 Microcell Bolt-On Sensor Assembly, w/65 feet cable

1 pc.

P/N MC-13 Installation Kit

4 pcs.

P/N JB-S-S1 Stainless Steel Junction Box

400 ft.

P/N 33-1008-01 Reel of Interconnect Cable

1 pc.

P/N SBMVS -S4-1 Stahl Barrier Assembly, Single Vessel. Stainless Steel Enclosure,

1 pc.

P/N SVS2000-A-S-A-N Weight Indicator. Stainless Steel Enclosure

For the detailed system overview, please refer to


Microcell (Load Cell) (for 1Set of Boiler).

(Fig.1) Typical Overview of Coal Bunker

JOB NO.

CODE NO.

5411-C46

F734A01

Cable length : approx. 20 m (65ft)

Connected wth DCS

(Microcell)

Weight of Bunker with Coal : Maximum 500 ton


(Divide live load by 4 sets of support legs is 125 ton)

Strain Gauge Sensor will be putted on


here.

Dimension of Leg is Box,

400mm x 400m, t 32mm.

(Fig.2) Overview of Coal Bunker

(quoted from 0-WD132-EM300-00002)

JOB NO.

CODE NO.

5411-C46

F734A01

Microcell
Bolt-on, strain gauge, sensor technology for measuring
inventory weights on vessels with support structures.

TECHNICAL SPECIFICATIONS

When you need weight inventory you want to use a weighing system. The Microcell is a highly
sensitive and thermally stable semiconductor strain gauge sensor, Kistler-Morse pioneered bolt-on
technology for measuring the contents of a wide range of bulk storage vessels. This sensor is still
the standard way to measure the weight-induced strain in a vessel with a leg support structure.
When Microcells are bolted on the vertical legs of a vessel, it converts the vessel into a weighing
system. Adding weight to a vessel compresses the gauge, changing the Microcells resistance which
produces an electrical output proportional to the material weight change.
The Microcell is quickly and easily installed while the vessel is still in productive use. An empty vessel
is not required for installation or calibration. For use on existing vessels with legs, the Microcell is a
cost-effective weighing solution compared to having to modify vessels for other types of weighing
sensors.
In combination with your existing vessels, the versatility of the Microcell can supply a cost effective,
easy to install, easy to maintain, highly reliable industrial strength weighing system. For cost and
performance, nothing can compare with the Microcell when weight is needed and weight is wanted.

FEATURES
AnD BEnEFITS
Bolt-on Technology
Creates a weighing system
by mounting Microcells to the
vessels support structure.
Simple Mounting
no specialized tools for
installation.
Uses Existing Vessel
Structure
no need to empty vessel or
take out of production to
install or service.
75 years MTBF
Unprecedented long-term
reliability.
Unique Design
Continuous weighing that
is immune to material
characteristics.

HOW TO ORDER
MC

(Notes 1, 2)

CABLE
015 = 15 ft. (4.6m) of Cable (note 3)
___ = Custom Length (in feet)
COVER SHAPE
n = no Cover
F = Flat Cover
S = Small Diameter Curved Cover (3 to 6)
L = Large Diameter Curved Cover (6 to 8 or larger)
VESSEL MATERIAL
X = Carbon Steel
A = Aluminum
S = Stainless Steel
SENSOR TYPE
S = Standardized, Light Blue Cover (note 5)
n = non-Standardized, Dark Blue Cover
A = Standardized, Light Blue Cover (note 5) with ATEX Approval (notes 4, 5)
X = non-Standardized, Dark Blue Cover with ATEX Approval (note 4)
SENSOR SIZE
3 = 3 inch
2 = 2 inch (note 5)
MICROCELL BOLT-ON SENSOR ASSEMBLY
note 1.
note 2.
note 3.
note 4.
note 5.

new installations require an installation kit.


Replacement installations require Sikaflex sealant, silicone grease and cover.
Lengths available from 5 ft (1.52 m) to 500 ft (152.4 m).
ATEX approved Microcell sensors must be ordered with ATEX approved SS junction boxes.
The 2 inch Sensor Size is not available with Sensor Type S or A.

Specifications
FUNCTIONAL
Excitation Voltage
Excitation Current
Insulation Resistance
Strain Gage to Sensor Frame
Breakdown Voltage
Red to White & Black to
White Resistance

Stress Level
Fatigue Life

12 VDC, 5%; maximum 30 VDC


12 V: 4.0 mA at 0 F (-18 C) to 2.7 mA to 100 F (30 C)
2 vM ohms
>500 VDC
3 Microcell: Standardized: 8.50 K 200 ohms at 70 F (21 C)
Non-Standardized: 2.0 K 200 ohms at 70 F (21 C)
2 Microcell: 2.0 K 200 ohms at 70 F (21 C)
3 Microcell: Maximum: 10,000 psi (7.0 kg/mm)
Recommended: 5,000 2,500 psi (3.5 1.5 kg/mm)
2 Microcell: Maximum: 15,000 psi (10.5 kg/mm)
Recommended: 7,500 3,750 psi (5.3 2.6 kg/mm)
>20 million cycles; load & unload at 0 to 5,000 psi (0 to 3.5 kg/mm)

PERFORMANCE

Output for 12 V Excitation

Output Impedance and


Temperature Effects

Sensitivity - Carbon Steel 3 Microcell: 70 mV 1%/1,000 psi


(70 mV 1%/0.7 kg/mm)
Sensitivity - Carbon Steel 2 Microcell: 56 mV 1%/1,000 psi
(56 mV 1%/0.7 kg/mm)
Zero Strain Output: 0 mV 25 mV
3 Microcell: Standardized: 7.50K 75 ohms at 70 F (21 C)
Non-Standardized: 1000K 100 ohms at 70 F (21 C)
2 Microcell: 1000 100 ohms at 70 F (21 C)
Sensitivity Change: 0.02% per degree F (0.036% per degree C)
over the compensated range
Zero Shift: 5 mV/100 F ( 5 mV/56 C) in compensated
temperature range

PHYSICAL
Rating

Temperature Range
Weight
Steel Base
Cable
Cable Length

Designed for rugged, outdoor applications, not for high pressure


washdown
Operational: -30 to 150 F (34 to 66 C)
Storage:-30 to 150 F (34 to 66 C)
Compensated: Standard 0 to 100 F (-18 to 38 C).
Mid +50 to +150 F (+10 to 66 C)
3 ounces (90 grams)
AISI 1018 carbon steel matched to vessel leg material A36
(Consult factory for aluminum or stainless steel vessel leg support)
3-conductor, 22 gage, unshielded
15' (4.6 meters)

OPTIONS
3" Microcells
Junction Box
Test Meter
Aluminum Base
Stainless Steel Base
Installation Hardware

Standardized or non standardized version; temperature


compensated for standard or mid-temperature ranges
Plastic or stainless steel version
To simplify sensor installation
For aluminum support legs, consult factory
For stainless steel support legs, consult factory

APPROVALS
ATEX, CE

150 Venture Boulevard, Spartanburg, SC 29306


Tel: 800-426-9010 864.574.2763
Fax: 864.574.8063
www.kistlermorse.com

97-7026-01 Rev. G

2013 All rights reserved.


All data subject to change without notice.

SVS2000TM
A full-featured, high performance weight indicator for
in-process weighing and batching or inventory weighing
applications.

TECHNICAL SPECIFICATIONS

The SVS2000TM accepts input signals from half- or full-bridge strain


gage load cells through a high resolution (up to 21-bit) analog-todigital converter. Resolution and gain are adjustable for optimal system
performance. Weight is displayed at the indicator and the data can be
serially polled from a master device. Analog and digital outputs can be
generated from the inputs to the SVS2000 to provide auxiliary controls.

FEATURES
AND BENEFITS
Quick Config
Adjusts system parameters and
precalibrates unit without special load
cells.
SentryTM DSP Filter
Separates mixer and plant vibrations
from weight changes. This provides
accurate and reliable weight readings.
High-speed, High-resolution Weight
Conversion
Performance for demanding
applications with up to 21-bit resolution.
Alphanumeric Backlit LCD Display
Simple, understandable operator
messages eliminates special coding/
decoding, cryptic setup and diagnostic
messages.
Displays the weight as a bar graph or
digital readout.
NEMA-4X Enclosure
ABS or optional stainless steel offers the
right protection for your environment.

The SVS2000 includes setpoint preact, digital interfaces and Kistler-Morses


SentryTM DSP filter which provides stable, accurate readings under a variety
of mixing conditions or plant vibrations. Sentry digitally separates the
vessel weight changes from the vibrations and dynamic conditions often
experienced on vessels with mixers. This provides stable and accurate
weight readings. Its flexibility allows you to optimize system performance so
it wont be fooled by sudden weight changes like other filter systems.
Using Quick Config, the SVS2000 is easy to setup and calibrate without test
weights or special load cells. Responses to simple Quick Config questions
provides the SVS2000 with the information needed to set up and calibrate
the system for your application. Within minutes, the SVS2000 provides
usable weight information. Later, when convenient, a more accurate
calibration is easily obtained by moving a known quantity of material.
The SVS2000 provides easy system configuration and expansion to meet
future requirements. Optional digital interfaces include Ethernet/IP, Profibus
DP, DeviceNet and RS422 serial.

HOW TO ORDER
SVS2000A

SLOT 1
A = Isolated 4-20 mA Output Card
B = Isolated Serial Card, RS232/RS422
N = None
SLOT 2
A = 0 mA Output Card
B = Isolated Serial Card, RS-232/RS-422
E = EtherNet/IP Card
F = DeviceNet Card
G = Profibus DP Card
N = None
ENCLOSURE TYPE
A = NEMA 4X, Plastic
B = NEMA 4X, Plastic with Bezel for Panel Mounting
S = NEMA 4X, SS
OPERATING VOLTAGE
A = AC Voltage (100 VAC to 120/230 VAC, 50/60 Hz)
SVS2000 WEIGHT INDICATOR

10

Specifications
FUNCTIONAL
Voltage - Operating Range

AC Power: 115 VAC 10%, 50/60 Hz; 230 VAC 10%, 50/60 Hz 30 VA

Operating Temperature

-4 to 122 F (-20 to 50 C)

PERFORMANCE
Transducer/Sensor Input

All Kistler-Morse half-bridge sensors, full-bridge foil gage

Excitation

Programmable between 5 and 13 volts @ 400 mA

Resolution

Selectable 16 bits (1 part in 65,536) to 21 bits (1 part in 2,097,152) in 1 bit increments

Conversion Speed

16 bits = 17 ms, 17 bits = 20 ms, 18 bits = 25 ms, 19 bits = 34 ms,


20 bits = 50 ms, 21 bits = 100 ms

Span

Programmable between 3.0 V @ 12 V excitation, Gain = 1 19.5 mV @ 10 V excitation,


Gain = 128

Temperature Stability

Zero 1 ppm/ C; Span 5 ppm/ C

Common Mode Rejection

92 db min @ DC; 150 db min @ 60 Hz

Normal Mode Rejection

100 db min @ 60 Hz

Multi-Vessel Remote Tare


Relay Output

2 relay outputs; Form "C" SPDT, programmable, 10 A 110 VAC, 8 A 230 VAC non-inductive;
for motors and other large inductive loads, contractors rated for the load are required.

PHYSICAL
Display

Back lit alphanumeric liquid crystal, one line of 16 characters, selectable bar graph or engineering
units format

Programming/
Parameter Entry

Integral 19-key sealed membrane tactile keypad

Setup

Menu-driven prompts

Memory

Non-volatile RAM

Enclosure

Designed to meet NEMA 4X ABS or NEMA 4X 304L SS

Humidity

1% to 95% (non-condensing)

Storage

-4 to 140 F (-20 to 60 C)

Dimensions

ABS version: 6.375" x 11" x 5.68" (161.91 mm x 279.4 mm x 144.27 mm)


SS version: 7.87 x 9.84 x 5.91 (199.9 mm x 249.94 mm x 150.11 mm)

Mounting Hole Pattern

ABS version: 2.5" x 10.4" (63.5 mm x 264.16 mm).


SS version: 5.31 x 9.13 (134.87 mm x 231.90 mm)

Shipping Weight

ABS version: 6 lbs (2.6 kg). SS version: 11.3 lbs (5.1 kg)

OPTIONS

PCBs

RS-422, RS-485: (optical isolation standard), baud rate 1200, 2400, 4800, 9600 or 19.2K.
PLC interfaces: DeviceNet (polled slave), Profibus DP, Ethernet I/P.
Analog Output: 0-20 or 4-20 mA, 14 bit resolution, 500 VAC isolation, maximum load 600
ohms with internal loop supply

APPROVALS
CE, UL (US and Canada): General Purpose

150 Venture Boulevard, Spartanburg, SC 29306


Tel: 800-426-9010 864.574.2763
Fax: 864.574.8063
www.kistlermorse.com

97-7052 Rev. F

2013 All rights reserved.


All data subject to change without notice.

11

12

13

14

15

16

Single-Channel Safety Barriers


Series 9001

A2

> Broad product range for all


standard applications in the
world of automation

A2

> Flexible and space saving single


and dual channel versions
available
> Time saving installation due to
simple snap on DIN-Rail and
connection to PE and ground
at the same time

A2

> Reduced inventory due to


uniform exchangeable fuse

A2

www.stahl.de

A2
A2
Series 9001 A2

09965E00

A2
R.STAHL safety barriers INTRINSPAK series 9001 are used for
various applications in the arena of automation. Based on the broad
range of versions and the possibility of various interconnections it
offers for almost all tasks.
The safety barriers enable the intrinsic safe operation of HART
transmitter, proximity switches, potential-free contacts and
temperature sensors, strain gauge, solenoid valves, indicators e.t.c.
The compact design allows a space saving and flexible installation
in the cabinet. The mounting is very comfortable and easy due to
the fact that installation on the DIN-rail and the contact to the
potential equalization is made in one step.

A2
A2
A2

ATEX / IECEX /

NEC 505 NEC 506

NEC 500

GOST

Class I

Class I Class II Class III

Zone

0 1 2 20 21 22

Zone

Ex i interfaces

x x x x

Ex i interfaces

Installation in
*)

x
x

Installation in

0 1

20 21 22

Division

Ex i interfaces

Installation in

x*)

A2

x*)

Restrictions see table explosion protection

A2
A2
WebCode
2013-03-12AK00IIIen

9001A

A2
Safety Barriers

A2/1

17

Single-Channel Safety Barriers


Series 9001
Explosion Protection
Global (IECEx)
Gas and dust

Europe (ATEX)
Gas and dust

USA (NEC)
Gas and dust

Russia (GOST-R)
Gas
Certificates and approvals
Certificates
Further parameters
Installation
Further information
Technical data
Electrical data
Transmission
characteristic
Leakage current at UN
Temperature effect
Transmission
frequency
At resistive current
limitation
Im ( 50 mA
Im ) 50 mA
At electronic current
limitation
Ambient conditions
Ambient temperature
Storage temperature
Maximum relative
humidity
Mechanical data
Ingress protection
terminal enclosure
Casing
Enclosure material
Connection
Weight

A2/2

Safety Barriers

IECEx PTB 09.0001X


Ex nA [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
PTB 01 ATEX 2088 X
E II 3 (1) G Ex nA [ia Ga] IIC/IIB T4 Gc
E II (1) D [Ex ia Da] IIIC
3011002 (FM)
CL. I, DIV.2, GP. A,B,C,D, T4 AND CL. I, ZONE 2, GP. IIC/IIB T4,
INTRINSICALLY SAFE CONNECTIONS FOR
CL. I,II,III, DIV. 1, GP. A,B,C,D,E,F,G AND CL. I, ZONE 0, GP. IIC/IIB
E81680 (UL)
CLASS I, DIV. 2, GROUPS A,B,C,D
CLASS II, DIV. 2, GROUPS F,G
CLASS III
[Exia Ga] IIC/IIB/IIA
ExnA [iaGa] IIC/IIB/IIA T4 Gc
IECEx, ATEX, Canada (CSA), Kazakhstan (GOST-K), Russia (GOST-R), Serbia (SRPS),
Ukraine (GOST-U), USA (FM, UL), Belarus (GOST-B)
in Zone 2, Division 2 and in safe area
see respective certifcate and operating instructions

( 2 mA (if not stated otherwise)


( 0.25 % / 10 K

( 50 kHz
( 100 kHz
( 10 kHz

-20 ... +60 C / -4 ... +140 F


-20 ... +75 C / -4 ... +167 F
95 % mean, no dewing

according to IEC 60529


IP20
IP40
Polyamide 6 GF
4 cage terminals, each maximum 1.5 mm2 flexible / solid
2 PA-terminals, each maximum 4 mm2 flexible / solid
approx. 0.115 kg

2013-03-12AK00IIIen

18

Single-Channel Safety Barriers


Series 9001

A2
Selection Table
Version

Description

Type

Page

Single-channel
barriers

Earthed electric circuit


Current limiting to < 100 mA

9001/01

Earthed electric circuit


Connection to regulated power supply UN

9001/01

Application for floating contacts


Nominal current limited to < 40 mA
Earthed electric circuit
Connection to unregulated power supply UN between + 20 and 35 V DC

9001/01

Application for floating contacts


Nominal current limited to < 40 mA
Earthed field device
Connection to unregulated power supply UN between + 20 and 35 V DC

9001/01

Application for solenoid valves, LEDs or audible signals


Earthed electric circuit
Connection to unregulated power supply UN between + 20 and 35 V DC

9001/01

Earthed electric circuit


Connection to regulated power supply UN

9001/00

10

Earthed electric circuit


Suitable for alternating current and direct current

9001/02

11

Earthed electric circuit


Suitable for alternating current and direct current
Current limiting to < Imax

9001/02

13

Earthed electric circuit


For the evaluation of direct current signals
Current limiting to < Imax

9001/03

14

Application for HART transmitters


Earthed field device
Connection to unregulated power supply UN between + 20 and 35 V DC

9001/51

15

Application for transmitters


Earthed field device
Connection to unregulated power supply UN between + 20 and 35 V DC

9001/51

17

A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/3

19

Single-Channel Safety Barriers for Positive Potential


Series 9001/01
Series 9001/01

Single-Channel Safety Barriers for Positive Potential


Hazardous area

Earthed electric circuit


Installation possible in Division 2 and Zone 2
Can be used as intrinsically safe supply

Safe area

-Ue

+Ue

Intrinsically safe
field device

Control room
equipment

UN

0V

+Ue / 0V

0V

/ PA
05495E01

Selection Table
UN

Rmin

Rmax

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

12

64

73

< 100

< 1.4

15.8

270

1067

0.23

0.478

2.2

2.88

9001/01-158-270-101

46

53

< 100

< 1.4

15.8

390

1541

0.16

0.478

0.89

2.88

9001/01-158-390-101

16

57

66

< 100

< 1.4

19.9

390

1940

0.89

1.42

9001/01-199-390-101

24

111

124

< 100

< 1.4

28

280

1960

0.6

0.65

9001/01-280-280-101

*) Ambient

Lo

Co

*)

temperature - 20 ... + 50 C

Functional Data and Safety-Relevant Maximum Values

A2/4

UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

IN

Nominal current
UN - U
IN =
Rmax + RL

Additional voltage drop across


the safety barrier

Lo

max. permissible external


inductance

Rmin

Minimum resistance of
the safety barriers

Uo

Maximum voltage

Co

max. permissible external capacity

Rmax

Maximum resistance of
the safety barriers

Io

Maximum current

RL

max. resistance of the field device

Safety Barriers

2013-03-12AK00IIIen

20

Single-Channel Safety Barriers for Positive Potential


Series 9001/01

A2
Single-Channel Safety Barriers for Positive Polarity
Hazardous area

Grounded cicuit
Allows the connection of regulated power
supplies, UN
Approved for installation in Division 2 and
Zone 2

Safe area

+Ue

+Ue
Intrinsically safe
field device

UN

-Ue / 0V

Control room
equipment

A2

0V

A2

0V

/ PA
05438E02

Selection Table
UN
Rmin
Rmax

V
1 ... 3
6

10
12

16

20
24

42
24
864
452
195
129
64
39
27
681
178
93
215
120
872
377
235
2096
1052
539
415
282
149
378
1435
599
415
340
286
263
177

49
27
963
501
218
144
73
44
32
698
199
106
240
135
965
420
262
2321
1165
598
462
241
168
421
1590
666
462
375
319
294
198

A2
Imax

mA
61
222
6
11
27
41
82
136
187
11
40
75
41
88
12
28
45
6
13
26
34
66
95
47
15
36
51
64
75
81
121

Safety values
Uo
Io
V
5
8.3
8.6
8.6
8.6
8.6
8.6
8.6
8.6
12.6
12.6
12.6
13.7
15.8
16.8
16.8
16.8
19.9
19.9
19.9
19.9
19.9
19.9
25.2
28
28
28
28
28
28
28

mA
150
442
10
20
50
75
150
270
390
20
75
150
65
150
20
50
75
10
20
38
50
100
150
70
20
50
75
85
100
110
165

Order number
Po
mW
187.5
917.2
21.5
43
107.5
161.3
322.5
580.5
839
63
236
473
222.6
593
84
210
315
50
100
189
249
498
746
441
140
350
525
595
700
770
1155

IIC
Lo
mH
1.3
0.1
300
90
15
6.7
1.3
0.23
0.16
90
6.7
1.3
8.8
1
90
15
6.7
330
90
26
15
4
1.3
4.5
50
8.5
3.3
2.4
1.6
1.2

Co
mF
100
7.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
1.15
1.15
1.15
0.79
0.478
0.39
0.39
0.39
0.223
0.223
0.223
0.223
0.223
0.223
0.107
0.083
0.083
0.083
0.083
0.083
0.083

IIB
Lo
mH
7
0.5
1000
330
56
25
7
2.2
1
330
25
7
34
7
330
56
25
1000
330
95
56
15
7
25
50
25
21
16
11
9
3.5

Co
mF
1000
73
55
55
55
55
55
55
55
7.4
7.4
7.4
5
2.88
2.29
2.29
2.29
1.42
1.42
1.42
1.42
1.42
1.42
0.82
0.65
0.65
0.65
0.65
0.65
0.65
0.65

A2

9001/01-050-150-101
9001/01-083-442-101
9001/01-086-010-101
9001/01-086-020-101
9001/01-086-050-101
9001/01-086-075-101
9001/01-086-150-101
9001/01-086-270-101
9001/01-086-390-101
9001/01-126-020-101
9001/01-126-075-101
9001/01-126-150-101
9001/01-137-065-101
9001/01-158-150-101
9001/01-168-020-101
9001/01-168-050-101
9001/01-168-075-101
9001/01-199-010-101
9001/01-199-020-101
9001/01-199-038-101
9001/01-199-050-101
9001/01-199-100-101
9001/01-199-150-101
9001/01-252-070-101
9001/01-280-020-101
9001/01-280-050-101
9001/01-280-075-101
9001/01-280-085-101
9001/01-280-100-101
9001/01-280-110-101
9001/01-280-165-101

A2
A2
A2
A2
A2
A2
A2

Functional and Maximum Safety Values


UN

Nominal voltage

Imax

Maximum current
through the safety barrier

Po

Maximum power

Rmin

Minimum resistance
of the safety barrier

Uo

Maximum voltage

Lo

Maximum permissible
external inductance

Rmax

Maximum resistance
of the safety barrier

Io

Maximum current

Co

Maximum permissible
external capacity

A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/5

21

Single-Channel Safety Barriers for Positive Potential


Series 9001/01
Application 9001/01-280-110-101
Analog output (current source) with I/P converter etc. Field circuit earthed
Schematic

Safe area

Hazardous area

4 ... 20 mA

9001/01-280-110-101

11331E01

Operating data
Operating voltage

UN = + 24 V

Operating current

IN = 0 ... 22 mA

Maximum voltage drop


at the safety barrier

Umax (6.5 V

Safety data
Maximum voltage

Uo = 28 V

Maximum current

Io = 110 mA

Maximum permissible
external inductance

Lo

IIC
2.2 mH

IIB
9 mH

Maximum permissible
external capacity

Co

IIC
0.08 F

IIB
0.65 F

Maximum power

Po = 770 mW

2-wire 4/20 mA transmitter - Standard


Schematic

Hazardous area

4 ... 20 mA

Safe area

+24 V DC
9001/01-280-110-101

09952E01

Application note

This safety barrier is used if the control system measures the current in the supply line.
The transmitter and the control system are earthed, regulated power supply must be used.

Discrete 2-wire output for magnet reed switches, LEDs and audible alarm indicators
Schematic

Hazardous area

Safe area

+24 V DC
9001/01-280-110-101

06603E01

Application note

A2/6

Safety Barriers

This barrier is suitable for use with regulated power supplies and earthed return circuits.
The rated voltage is 24 V. 9001/01-280-165-101 and 9001/01-280-280-101 should be used for
applications which require higher power and for use exclusively in gas groups IIB and IIA.

2013-03-12AK00IIIen

22

Single-Channel Safety Barriers for Positive Potential


Series 9001/01

A2

Single-Channel Safety Barriers for Positive Polarity


Hazardous area

Application specific for the connection of volt


free contacts
Operational current limited to < 40 mA
Grounded circuit
Allows the connection of unregulated power
supplies, UN between + 20 to 35 V DC
Approved for installation in Division 2 and
Zone 2

Safe area

-Ue

+Ue

Intrinsically safe
field device

UN

Control room
equipment

+Ue

-Ue / 0V

A2

0V

A2
/ PA
05494E02

Selection Table
UN

Rmin

Rmax

Imax

Uo

Io

Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

20 ... 35

454

505

40

25.2

57

359

6.3

0.107

25

0.82

* ) Maximum

A2

Order number

Safety values
Lo

Co

9001/01-252-057-141

A2

*)

leakage (terminal 1 -> PA/) Ileak 100 A

A2

Functional Data and Safety-Relevant Maximum Values


UN

Nominal voltage

Additional voltage drop across


the safety barrier

Lo

max. permissible external


inductance

Rmin

Minimum resistance of
the safety barriers

Uo

Maximum voltage

Co

max. permissible external capacity

Rmax

Maximum resistance of
the safety barriers

Io

Maximum current

RL

max. resistance of the field device

Imax

Maximum output current

Po

Maximum power

A2
A2

Application
Binary input with switch (load to +) Field circuit earthed
Schematic

Hazardous area

Safe area
Supply Voltage

A2

+20 ... 35 V DC
9001/01-252-057-141

RL

A2

01721E01

Operating data
Operating voltage
Open-circuit output voltage
(3 -> 4, In = 0)
Operating current

UN = + 20 ... 35 V
UL )

UN (24 V

UN > 24 V

UN - 3 V

21 V

A2

IN = UL / 505 + RL

Safety data
Maximum voltage

Uo = 25.2 V

Maximum current

Io = 57 mA

A2

Maximum permissible
external inductance

Lo

IIC
6.3 mH

IIB
25 mH

Maximum permissible
external capacity

Co

IIC
0.107 F

IIB
0.82 F

Maximum power

Po = 359 mW

Application note

This safety barrier is particularly suitable for relay control.


A binary input (optocoupler) of an automation device can be used as load.

A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/7

23

Single-Channel Safety Barriers for Positive Potential


Series 9001/01
Single-Channel Safety Barriers for Positive Polarity
Hazardous area

Application specific for the connection of volt


free contacts
Operational current limited < 40 mA
Grounded field device
Allows the connection of unregulated power
supplies, UN between + 20 to 35 V DC
Approved for installation in Division 2 and
Zone 2

Safe area

-Ue

+Ue

Intrinsically safe
field device

UN

Control room
equipment

+Ue

-Ue / 0V

0V

/ PA
05440E02

Selection Table
UN

Rmin

Rmax

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

20 ... 35

454

505

40

25.2

60

378

6.2

0.107

25

0.82

* ) Maximum

Lo

Co

9001/01-252-060-141

*)

leakage (terminal 1 -> PA/) Ileak 100 A

Functional Data and Safety-Relevant Maximum Values


UN

Nominal voltage

Additional voltage drop across


the safety barrier

Lo

max. permissible external


inductance

Rmin

Minimum resistance of
the safety barriers

Uo

Maximum voltage

Co

max. permissible external capacity

Rmax

Maximum resistance of
the safety barriers

Io

Maximum current

RL

max. resistance of the field device

Imax

Maximum output current

Po

Maximum power

Application
Binary input with switch (load on ground) Field circuit earthed
Schematic
Hazardous Location

Nonhazardous Location
Supply Voltage
+20 ... 35 V DC
9001/01-252-060-141
RL

09955E01

Operating data
Operating voltage
Open-circuit output voltage
(3 -> 4, In = 0)
Operating current
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note

A2/8

Safety Barriers

UN = + 20 ... 35 V
UL )

UN (24 V

UN > 24 V

UN - 3 V

21 V

IN = UL / 505 + RL
Uo = 25.2 V
Io = 60 mA
Lo

IIC
6.2 mH
IIC
0.107 F

IIB
25 mH
IIB
0.82 F

Co
Po = 378 mW
This safety barrier is particularly suitable for relay control.
A binary input (optocoupler) of an automation device can be used as load.

2013-03-12AK00IIIen

24

Single-Channel Safety Barriers for Positive Potential


Series 9001/01

A2
Single-Channel Safety Barriers for Positive Polarity
Hazardous area

Application specific for the connection of solenoid valves, LEDs or audible alarms
Grounded circuit
Allows the connection of unregulated power
supplies, UN between + 20 to 35 V DC
Approved for installation in Division 2 and
Zone 2

Safe area

+Ue

+Ue
Intrinsically safe
field device

Control room
equipment

UN

0V

-Ue / 0V

A2
A2

0V

/ PA
05501E02

A2

Selection Table
UN

Rmin

Rmax

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

20 ... 35

259

268

78

25.2

100

630

0.107

11

0.82

*)

Lo

Co

A2
9001/01-252-100-141

*)

Maximum leakage (terminal 1 -> PA/) at 24 V / 35 V Ileak 1 mA / 10 mA

A2

Functional and Maximum Safety Values


UN

Nominal voltage

Imax

Maximum current
through the safety barrier

Po

Maximum power

Rmin

Minimum resistance
of the safety barrier

Uo

Maximum voltage

Lo

Maximum permissible
external inductance

Rmax

Maximum resistance
of the safety barrier

Io

Maximum current

Co

Maximum permissible
external capacity

A2
A2

Application
Binary output (current source) for valves, LEDs etc. Field circuit earthed
Schematic
Nonhazardous Location
Hazardous Location

A2
+20 ... 35 V DC
9001/01-252-100-141

A2
06602E01

Operating data
Operating voltage
Open-circuit output voltage
(3 -> 4, In = 0)
Operating current
Safety data
Maximum voltage
Maximum current
Maximum permissible external inductance
Maximum permissible external capacity
Maximum power

UN = + 20 ... 35 V
UL )

UN (24 V

UN > 24 V

UN - 3 V

21 V

A2

IN = UL / 268 + RL
Uo = 25.2 V
Io = 100 mA
Lo
Co
Po = 630 mW

A2
IIC
2 mH
IIC
0.107 F

IIB
11 mH
IIB
0.82 F

A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/9

25

Single-Channel Safety Barriers for Negative Polarity


Series 9001/00
Series 9001/00

Single-Channel Safety Barriers for Negative Polarity


Hazardous area

Grounded cicuit
Allows the connection of regulated power
supplies, UN
Approved for installation in Division 2 and
Zone 2

Safe area

-Ue

-Ue

Intrinsically safe
field device

Control room
equipment

UN

+Ue / 0V

0V
0V

/ PA
05428E02

Selection Table
UN

Rmin

Rmax

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

1 ... 3

42

49

61

150

187.5

1.3

100

1000

9001/00-050-150-101

24

28

214

8.3

442

917.2

0.1

7.2

0.5

73

9001/00-083-442-101

864

963

8.6

10

21.5

300

6.2

1000

55

9001/00-086-010-101

452

501

11

8.6

20

43

90

6.2

330

55

9001/00-086-020-101

195

218

27

8.6

50

107.5

15

6.2

56

55

9001/00-086-050-101

92

103

58

8.6

100

215

6.2

15

55

9001/00-086-100-101

64

73

82

8.6

150

322.5

1.3

6.2

55

9001/00-086-150-101

39

45

136

8.6

270

580.5

0.23

6.2

2.2

55

9001/00-086-270-101

27

32

187

8.6

390

839

0.16

6.2

55

9001/00-086-390-101

12

120

135

88

15.8

150

593

0.478

2.88

9001/00-158-150-101

16

1052

1165

13

19.9

20

100

90

0.223

330

1.42

9001/00-199-020-101

539

598

26

19.9

38

189

26

0.223

95

1.42

9001/00-199-038-101

415

462

34

19.9

50

248.8

15

0.223

56

1.42

9001/00-199-050-101

149

168

95

19.9

150

746

1.3

0.223

1.42

9001/00-199-150-101

1435

1590

15

28

20

140

50

0.083

50

0.65

9001/00-280-020-101

599

666

36

28

50

350

8.5

0.083

25

0.65

9001/00-280-050-101

340

375

64

28

85

595

2.4

0.083

16

0.65

9001/00-280-085-101

286

319

75

28

100

700

1.6

0.083

11

0.65

9001/00-280-100-101

263

294

81

28

110

770

1.2

0.083

0.65

9001/00-280-110-101

177

198

121

28

165

1155

3.5

0.65

9001/00-280-165-101

24

Functional and Maximum Safety Values

A2/10

UN

Nominal voltage

Imax

Maximum current
through the safety barrier

Po

Maximum power

Rmin

Minimum resistance
of the safety barrier

Uo

Maximum voltage

Lo

Maximum permissible
external inductance

Rmax

Maximum resistance
of the safety barrier

Io

Maximum current

Co

Maximum permissible
external capacity

Safety Barriers

2013-03-12AK00IIIen

26

Single-Channel Safety Barriers for Alternating Polarity


Series 9001/02

A2

Series 9001/02

Single-Channel Safety Barriers for Alternating Polarity


Hazardous area

Grounded circuit
Suitable for AC and DC circuits
Approved for installation in Division 2 and
Zone 2

Safe area

+/-Ue

+/-Ue
Intrinsically safe
field device

UN

A2

Control room
equipment

+/-Ue/0V

+/-Ue/0V

A2

0V

/ PA
05502E02

A2

Selection Table
UN

Rmin

Rmax

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

0.7

119

134

1.6

15

160

100

560

1000

9001/02-016-015-101

*)

38

43

16

1.6

50

20

15

100

56

1000

9001/02-016-050-101

*)

39

40

17

1.6

50

20

15

100

56

1000

9001/02-016-050-111

*)

20

35

1.6

150

60

1.3

100

1000

9001/02-016-150-101

*)

19.9

20.1

35

1.6

150

60

1.3

100

1000

9001/02-016-150-111

*)

11

14

50

1.6

320

128

0.19

100

1.6

1000

9001/02-016-320-101

*)

3141

3472

1.7

9.3

6.975

1000

4.1

1000

31

9001/02-093-003-101

319

354

16

9.3

30

69.8

40

4.1

150

31

9001/02-093-030-101

195

218

27

9.3

50

116.3

15

4.1

56

31

9001/02-093-050-101

148

165

36

9.3

75

174.4

6.7

4.1

25

31

9001/02-093-075-101

70

79

75

9.3

150

348.8

1.3

4.1

31

9001/02-093-150-101

36

166

9.3

390

906.8

0.16

4.1

0.89

31

9001/02-093-390-101

10

102

115

86

13.3

150

498.8

1.3

0.91

5.6

9001/02-133-150-101

12

378

421

28

17.5

50

219

15

0.339

56

1.97

9001/02-175-050-101

197

222

54

17.5

100

437.5

0.339

15

1.97

9001/02-175-100-101

101

114

105

17.5

200

875

0.5

0.339

1.97

9001/02-175-200-101

16

148

167

95

19.6

150

735

1.3

0.235

1.47

9001/02-196-150-101

24

320

357

67

28

90

630

2.2

0.083

14

0.65

9001/02-280-090-101

36

456

509

70

41.2

95

979

0.287

9001/02-412-095-101

*)

Maximum leakage
Tolerance

Lo

Co

A2
A2
A2
A2
A2
A2

Ileak ( 10 mA
0.5 %

A2

Functional and Maximum Safety Values


UN

Nominal voltage

Imax

Maximum current
through the safety barrier

Po

Maximum power

Rmin

Minimum resistance
of the safety barrier

Uo

Maximum voltage

Lo

Maximum permissible
external inductance

Rmax

Maximum resistance
of the safety barrier

Io

Maximum current

Co

Maximum permissible
external capacity

A2
A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/11

27

Single-Channel Safety Barriers for Alternating Polarity


Series 9001/02
Application
Pt100, 3-wire circuit Field circuit unearthed
Schematic

Hazardous area

Safe area
RTD
Input

9002/22-032-300-111

9001/02-016-150-111

Supply
Voltage

09960E01

Operating data
Operating voltage

UN ( 1.4 V

Series resistance of
the safety barriers

R = 3 x (20 0.1 )

Measuring range

( 400 C (IN ( 5 mA)


( 850 C (IN ( 3 mA)

Safety data

A2/12

Maximum voltage

Uo = 3.2 V

Maximum current

Io = 450 mA

Maximum permissible
external inductance

Lo

IIC
0.12 mH

IIB
0.5 mH

Maximum permissible
external capacity

Co

IIC
0.10 F

IIB
1000 F

Safety Barriers

2013-03-12AK00IIIen

28

Single-Channel Safety Barriers for Alternating Polarity


Series 9001/02

A2
Single-Channel Safety Barriers for Alternating Polarity
Hazardous area

Safe area

+/-Ue

+/-Ue
Intrinsically safe
field device

UN

Control room
equipment

Grounded circuit
Suitable for AC and DC circuits
Current limitation to < Imax
Approved for installation in Division 2 and
Zone 2

A2

+/-Ue/0V

+/-Ue/0V

A2

0V

/ PA
05526E02

A2

Selection Table
UN

Rmin

Rmax

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

16

63

72

< 80

< 1.4

21.7

390

2116

0.89

1.17

9001/02-217-390-101

24

143

162

< 65

< 1.4

30.8

230

1771

0.7

0.524

9001/02-308-230-101

A2
A2

Functional data and safety-relevant maximum values


UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

IN

Nominal current
UN - U
IN =
Rmax + RL

Additional voltage drop across


the safety barrier

Lo

max. permissible external


inductance

Rmin

Minimum resistance of
the safety barriers

Uo

Maximum voltage

Co

Rmax

Maximum resistance of
the safety barriers

Io

Maximum current

A2

max. permissible external capacity

A2
A2
A2
A2
A2
A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/13

29

Single-Channel Diode Return Barriers for Positive Polarity


Series 9001/03
Series 9001/03

Single-Channel Diode Return Barriers for Positive Polarity


Hazardous area

+Ue
Intrinsically safe
field device

Grounded circuit
For DC current signal returns
Approved for installation in Division 2 and
Zone 2

Safe area

+Ue
Control room
equipment

UN

0V

-Ue / 0V

0V

/ PA
05541E02

Selection Table
UN

Imax

Order number

Safety values
Uo

Io

Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

< 150

3.5

8.6

1000

6.2

1000

55

9001/03-086-000-101

*)

12

< 100

3.5

16.8

1000

0.39

1000

2.29

9001/03-168-000-101

*)

16

< 100

3.5

19.9

1000

0.223

1000

1.42

9001/03-199-000-101

*)

9001/03-280-000-101

*) **)

24

< 100

3.5

28

*)

Short circuit rating

not short circuit proof

**)

Ambient temperature

- 20 C ... + 50 C

Lo

Co

50

0.083

50

0.65

Functional data and safety-relevant maximum values


UN

Nominal voltage

Additional voltage drop across


the safety barrier

Po

Maximum power

IN

Nominal current
UN - U
IN =
Rmax + RL

Uo

Maximum voltage

Lo

max. permissible external


inductance

Imax

Maximum output current

Io

Maximum current

Co

max. permissible external capacity

Application
3-wire 4 ... 20 mA transmitter
Schematic

Hazardous area

Safe area

9001/01-280-100-101
4 ... 20 mA

+24 V DC
Signal

9001/03-280-000-101

15294E01

A2/14

Safety Barriers

2013-03-12AK00IIIen

30

Single-Channel Safety Barriers for Transmitters


Series 9001/51

A2

Series 9001/51

Single-Channel Safety Barriers for Transmitters


Hazardous area

Application for HART transmitters


Earthed electric circuit
Connection to unregulated power supply UN
between + 20 and 35 V DC
Installation possible in Division 2 and Zone 2
The PA and OV should have equal potentials
in the control system

Safe area
Power supply
+20 V ... 35 V
0V

Is

+Ue

Intrinsically safe
field device

UN

Control room
+Ue equipment

-Ue / 0V

A2
A2

RL

0V
/ PA
05561E01

A2

Selection Table
UN

Safety values
Uo

Io

Order number
Po

IIC

IIB
Lo

Co

mA

mW

mH

mF

mH

mF

20 ... 35

28

91

637

2.2

0.083

14

0.65

9001/51-280-091-141

20 ... 35

28

110

770

1.2

0.083

0.65

9001/51-280-110-141

Technical data
Version
Supply current
Accuracy
Temperature influence
Longterm drift
Rated operational current
Load
Transmitter supply voltage

Lo

Co

A2
A2

9001/51-280-091-141
Is ( 50 mA
0.05 %
0.1 % / 10 K
0.05 %
IN = 3.6 mA ... 22 mA
RL ( 350
Umin (IN = 20 mA)
UN - 9.5 V
14 V

9001/51-280-110-141
Is ( 50 mA
0.05 %
0.1 % / 10 K
0.05 %
IN = 3.6 mA ... 22 mA
RL ( 500 (UN ( 23.5 V)
RL ( 750 (UN > 23.5 V)
UN
( 23.5 V
> 23.5 V

Umin (IN = 20 mA)


UN - 8.5 V
15 V

UN
( 23.5 V
> 23.5 V

A2
A2

Functional and Maximum Safety Values


UN

Nominal voltage

Po

Maximum power

Uo

Maximum voltage

Lo

Maximum permissible
external inductance

Io

Maximum current

Co

Maximum permissible
external capacity

A2
A2
A2
A2
A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/15

31

Single-Channel Safety Barriers for Transmitters


Series 9001/51
Application
Analog input with standard transmitter Field circuit earthed
Schematic

Safe area

Hazardous area

+20 ... 35 V DC

4 ... 20 mA

9001/51-280-110-141

09950E01

Operating data
Operating voltage

UN = + 20 ... 35 V

Load

RL ( 500 (UN ( 23.5 V)


RL ( 750 (UN > 23.5 V)

Operating voltage of
the transmitter

Umin (IN = 20 mA)

UN

UN - 8.5 V

( 23.5 V

15 V

> 23.5 V

Safety data

A2/16

Maximum voltage

Uo = 28 V

Maximum current

Io = 110 mA

Maximum permissible
external inductance

Lo

IIC
1.2 mH

IIB
9 mH

Maximum permissible
external capacity

Co

IIC
0.083 F

IIB
0.65 F

Maximum power

Po = 770 mW

Application note

The safety barriers 9002/13-280-110-001 can be used with stabilised voltages UN ( 26 V.


In this case the operating voltage of the transmitter is Umin ) 12.1 V
(with UN = 24 V; IN = 20 mA; RL = 250 )

Safety Barriers

2013-03-12AK00IIIen

32

Single-Channel Safety Barriers


Series 9001

A2

Series 9001

Accessories and Spare Parts


Designation

Figure

Description

Art. no.

Weight

for all safety barriers Series 9001, 9002 and 9004


unit: 5 pcs.

158964

0.008 /
0.018

158977

0.002 /
0.004

158973

0.005 /
0.011

158826

0.006 /
0.013

165283

0.004 /
0.009

NS 35 / 15 (meter length)

103714

1.410 /
3.109

USLKG 5 (wire range( 4 mm2)

112760

0.012 /
0.026

kg / lbs
Back-up fuse
09919E00

Holder for labels

09920E00

Labelling paper

perforated, for typing


Format: DIN A4

A2
A2

09921E00

Adaptor

A2

09922E00

Mounting attachment
moulded plastic
09924E00

DIN rail

03856E00

Earth terminal

A2
A2

09926E00

USLKG 6 N (wire range( 6 mm2)

Earth terminal

A2

112599

0.030 /
0.066

A2
09926E00

Fuse holder

158834

0.020 /
0.044

158828

0.023 /
0.051

A2

09927E00

Insulating stand off

for rail NS 35/15

09928E00

A2
A2
A2
A2
A2

2013-03-12AK00IIIen

Safety Barriers

A2/17

33

Single-Channel Safety Barriers


Series 9001

103 mm / 4.06 "

12 mm / 0.47 "

72 mm / 2.83 "

Dimensional Drawings (All Dimensions in mm / inches) - Subject to Alterations

09929E00

76 mm / 3.00 "

95 mm / 3.74 "

80 mm / 3.15 "

Safety barriers 9001, 9002, 9004

09930E00

66 mm
2.60 "

66 mm
2.60 "

38 mm
1.50 "
09933E00

38 mm
1.50 "
09932E00

Safety barriers 9001, 9002, 9004


mounting on
DIN rail NS 35/15 (acc. to EN 50 022)

Safety barriers 9001, 9002, 9004


mounting on
DIN rail NS 32 (acc. to EN 50 035)
by means of adaptor and
mounting attachment, moulded plastic

Safety barriers 9001, 9002, 9004


mounting on
mounting plate by means of adaptor

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice.
The illustrations cannot be considered binding.

A2/18

Safety Barriers

2013-03-12AK00IIIen

34

Two-channel safety barriers


Series 9002

A2

> Wide product range for all


standard applications of the
automation

A2

> Flexible and space-saving


available in single and double
channel versions
> Time-saving installation thanks
to simultaneous
snap-on mounting on rails
and
connection to PE and earth

A2
A2

> Reduced stock-keeping thanks


to a uniform back-up fuse

www.stahl.de

A2
A2
Series 9002 A2

04101E00

A2
The R. STAHL INTRINSPAK safety barriers of Series 9002 can be
used for various tasks in the field of automation. The wide product
range and scope of different combinations offer you a large field of
applications.
The safety barriers allow the intrinsically safe operation of HART
transmitters, proximity sensors, potential-free contacts,
temperature sensors, DMS, solenoid valves, indicators and others.
Due to the compact width, space-saving and flexible installation in
the switch cabinet is possible. Thanks to DIN-rail mounting and
simultaneous connection of the equipotential bonding, the
installation can be performed very easily.
ATEX / IECEX

Zone

0 1 2 20 21 22

Zone

Ex i interface

x x x x

Ex i interface

Installation in
*) For

x
x

Installation in

A2
A2
A2

NEC 505 NEC 506

NEC 500

Class I

Class I Class II Class III

0 1

20 21 22

Division

Ex i interface

Installation in

x*)

A2

x*)

restrictions, see Explosion protection table

A2
A2
WebCode
2013-05-24AK00IIIen

9002A

A2
Safety barriers

A2/1

35

Two-channel safety barriers


Series 9002

Explosion Protection
Global (IECEx)
Gas and dust

Europe (ATEX)
Gas and dust

Certificates
Certificates
Further parameters
Installation
Further information

IECEx PTB 08.0057X


Ex nA [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
PTB 01 ATEX 2053 X
E II 3 (1) G Ex nA [ia Ga] IIC/IIB T4 Gc
E II (1) D [Ex ia Da] IIIC
IECEx, ATEX, Canada (CSA), Kazakhstan (operating licence), Russia (GOST R), Serbia (SRPS),
Ukraine (TR), USA (FM, UL), Belarus (operating licence)
in Zone 2, Division 2 and in safe area
see respective certificate and operating instructions

Technical Data
Electrical data
Transmission
characteristic
Leakage current at UN
Temperature influence

( 0.25 % / 10 K

Transmission
frequency
In case of resistive
current limiting
Im ( 50 mA

( 50 kHz

Im ) 50 mA
In case of electronic
current limiting
Ambient conditions
Ambient temperature
Storage temperature
Maximum relative
humidity
Mechanical data
Degree of protection
Terminal support
Enclosure
Enclosure material
Connection type
Weight

A2/2

( 2 mA (unless specified otherwise)

Safety barriers

( 100 kHz
( 10 kHz

-20 ... +60 C


-20 ... +75 C
95 % on average, no condensation

according to IEC 60529


IP20
IP40
polyamide 6GF
4 connection terminals (cage terminals), each maximum 1.5 mm2 finely stranded / solid wire
2 PA-terminals, each maximum 4 mm2 finely stranded / solid
approx 0.115 kg

2013-05-24AK00IIIen

36

Two-channel safety barriers


Series 9002

A2
Selection table
Version

Description

Type series

Page

Dual-channel barriers

Connection to regulated power supply UN

9002/11

A2/4

Application for 3-wire NPN, sensors with voltage output


Low nominal current

9002/11

A2/6

Application for 4/20 mA transmitters with 1-5 V input in the wiper


Incl. precision resistance of 250

9002/11

A2/7

Connection to regulated power supply UN

9002/00

A2/8

Application for load cells


Channel for positive and negative potential in one module

9002/10

A2/9

9002/22

A2/11

Connection of a resistance teletransmitter is possible


High precision resistance of each channel, 20 0.1
Low temperature influence of < 50 ppm/K
Connection to regulated power supply UN

A2
A2
A2

Connection to regulated power supply UN

9002/22

A2/13

Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to unregulated power supply on UN to channel 1
Nominal current limited to 35 mA

9002/13

A2/14

Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to regulated power supply UN

9002/13

A2/16

Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Nominal current limited to 40 mA at 250 load
Connection to unregulated power supply on UN to channel 1

9002/13

A2/18

Evaluation barrier for direct current signals with max. output current Io
Suitable for potential-free contacts and floating 4/20 mA signals
Positive potential of both channels

9002/33

A2/19

Evaluation barrier for direct current signals with max. output current Io
Application for passive signals of 4/20 mA (transmitter with 4 conductors
or more) with insulated analog input on the control system
Channel for positive and negative potential in one module

9002/34

A2/20

Connection to regulated power supply UN


Suitable for voltage signals

9002/77

A2/21

A2
A2
A2
A2
A2
A2
A2
A2
A2
A2

2013-05-24AK00IIIen

Safety barriers

A2/3

37

Two-channel safety barriers, potential: + / +


Series 9002/11

Series 9002/11

Two-channel safety barriers, potential: + / +


Hazardous area

Connection to regulated power supply UN


Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

Control room
equipment

UN

+ve

+ve
0V

/ PA
05820E01

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data

Order number

Uo

Io

Po

IIC

mA

mA

mW

mH

mF

mH

mF

1
2
1+2

9
9
--

1043
1043
--

1156
1156
--

7.7
7.7
--

12
12
12

12
12
24

40
40
70

240
240
63

1.41
1.41
1.1

850
850
230

9
9
7.1

9002/11-120-024-001

1
2
1+2

10
1
--

45
45
--

52
52
--

100
19
--

13
1.6
13

321
39
360

1040
16
1170

0.19
24
0.17

1
100
0.79

1.6
91
1.3

6
100
5

9002/11-130-360-001

1
2
1+2

10
10
--

953
953
--

978
978
--

10
10
--

13.7
13.7
13.7

14.5
14.5
29

50
50
100

160
160
43

0.79
0.79
0.67

560
560
160

5
5
4.18

9002/11-137-029-001

1
2
1+2

16
16
--

1423
1423
--

1576
1576
--

10
10
--

19.9
19.9
19.9

15
15
30

75
75
150

160
160
40

0.223
0.223
0.223

560
560
150

1.42
1.42
1.42

9002/11-199-030-001

1
2
1+2

22.5
17.5
--

321
416
--

358
463
--

62
37
--

26
20
26

87
51
138

570
260
850

2.7
14
0.81

0.099
0.22
0.087

15.4
54
5.1

0.77
1.41
0.67

9002/11-260-138-001

1
2
1+2

25
25
--

321
321
--

358
358
--

69
69
--

28
28
28

93
93
186

650
650
1300

2
2
--

0.083
0.083
--

13
13
2.8

0.65
0.65
0.551

9002/11-280-186-001

1
2
1+2

25
6
--

321
59
--

358
68
--

69
88
--

28
9.6
28

89
180
269

630
430
1050

2.2
0.6
--

0.083
3.6
--

14
5
0.56

0.65
26
0.62

9002/11-280-293-001

IIB

*)

*) max. leakage current Ileak ( 10 mA


Functional data and safety-relevant maximum values

A2/4

UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

Safety barriers

2013-05-24AK00IIIen

38

Two-channel safety barriers, potential: + / +


Series 9002/11

A2
Application case
Load cell (DMS) 350 or 700
6 conductors + 16 V, field circuit unearthed
Schematic
Hazardous area

A2

Safe area

+16 V

9002/13-199-225-001

A2

0V

9002/11-199-030-001

9002/11-199-030-001

A2
09963E01

Operating data
Operating voltage
Voltage for load cell and
electric line
Current for load cell

IL (at UN = + 16 V)
Number of the load cells
connected in parallel
1
2
3
4

Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note

A2

UN ( + 16 V
UL (at UN = + 16 V)

Uo = 19.9 V
Io = 285 mA
Lo

IIC
0.2 mH
IIC
0.223 F

350
UL (V)
10.4
8.3
6.9
5.9

ImA (V)
30
47
60
67

700
UL (V)
12.1
10.4
9.5
8.3

A2

ImA (V)
17
30
41
47

A2

IIB
1.8 mH
IIB
1.42 F

A2

Co
Po = 1.42 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 255 mA, the
maximum power to Po = 1.3 W.
3-wire NPN inputs (negative switching) of proximity switches, photocells and encoders
Schematic
Hazardous area
Safe area

A2
A2

+24 V DC

Supply

9002/11-280-186-001
+0 V
NPN

A2

06601E01

Discrete 2-wire output for solenoid valves, LEDs and signalling devices
Schematic
Safe area
Hazardous area

A2
9002/11-280-186-001

+24 V DC
+24 V DC

A2
06606E01

2013-05-24AK00IIIen

Safety barriers

A2
A2/5

39

Two-channel safety barriers, potential: + / +


Series 9002/11

Two-channel safety barriers, potential: + / +


Hazardous area

Application for 3-wire NPN, sensors with voltage output


Low nominal current
Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

Control room
equipment

UN
RL

+ve

+ve
0V

/ PA
05823E01

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

1
2
1+2

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

24
24
--

264
11979
--

296
12221
--

91
2
--

28
28
28

109
3
112

760
20
780

1.3
50
0.76

0.083
0.083
0.065

9
150
84

0.65
0.65
0.551

9002/11-280-112-001

Functional data and safety-relevant maximum values


UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

Application case
3-wire NPN inputs (negative switching) of proximity switches, photocells and encoders
Schematic

Hazardous area

Safe area
+24 V DC

Supply

9002/11-280-112-001
0V
NPN
06597E01

Application note

A2/6

Safety barriers

With this barrier all loop voltages must be checked to ensure correct function.

2013-05-24AK00IIIen

40

Two-channel safety barriers, potential: + / +


Series 9002/11

A2
Two-channel safety barriers, potential: + / +
Hazardous area

Application for 4/20 mA transmitter with 1-5 V


input in the wiper
Incl. precision resistance of 250
Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

A2

Control room
equipment

UN

+ve

+ve

A2

0V

/ PA
05824E01

A2

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

1
2
1+2

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

25
6
--

321
59
--

358
68
--

69
88
--

28
9.6
28

89
180
269

630
430
1050

2.2
0.6
--

0.083
3.6
--

14
5
0.56

0.65
26
0.62

A2
9002/11-280-293-021

A2

Functional data and safety-relevant maximum values


UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

A2

Application case

A2

2-wire, 4/20 mA transmitters - standard and HART


Schematic

Hazardous area

4 ... 20 mA

Safe area

9002/11-280-293-021

A2

+24 V DC
+1 ... 5 V
Input

A2

11332E01

Application note

This safety barrier is used if the automation system only accepts signals from 1 to 5 V.
This barrier contains a 250 resistor to convert the signal 1 ... 5 V.

A2
A2
A2
A2
2013-05-24AK00IIIen

Safety barriers

A2/7

41

Two-channel safety barriers, potential: - / Series 9002/00

Series 9002/00

Two-channel safety barriers, potential: - / Hazardous area

Connection to regulated power supply UN


Installation permitted in Division 2 and Zone 2

Safe area

-ve

-ve
Intrinsically safe
field device(s)

Control room
equipment

UN

-ve

-ve
0V

/ PA
05822E01

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

1
2
1+2

9
9
--

1043
1043
--

1156
1156
--

7.7
7.7
--

12
12
12

12
12
24

40
40
70

240
240
63

1.41
1.41
1.1

850
850
230

9
9
7.1

9002/00-120-024-001

1
2
1+2

22.5
17.5
--

321
416
--

358
463
--

62
37
--

26
20
26

87
51
138

540
245
785

2.7
14
0.81

0.099
0.22
0.087

15.4
54
5.1

0.77
1.41
0.67

9002/00-260-138-001

1
2
1+2

25
25
--

321
321
--

358
358
--

69
69
--

28
28
28

93
93
186

650
650
1300

2
2
--

0.083
0.083
--

13
13
2.8

0.65
0.65
0.551

9002/00-280-186-001

Functional data and safety-relevant maximum values


UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

Application case
Vibration sensor
Schematic

Hazardous area

Safe area

-24 V DC max.

Sensor

9002/00-260-138-001

Transducer

Input
0V

06615E01

Operating data
Operating voltage
Series resistance of the
safety barrier
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note

A2/8

Safety barriers

UN = - 24V
R = 358
Uo = 26 V
Io = 138 mA
Lo

IIC
0.81 mH
IIC
0.087 F

IIB
5.1 mH
IIB
0.67 F

Co
Po = 850 mW
Application of the barrier for Bentley Nevada and Metrix position transducer. This barrier has negative
potential; for a positive potential, use the barrier 9002/11-260-138-001.

2013-05-24AK00IIIen

42

Two-channel safety barriers, potential: + / Series 9002/10

A2

Series 9002/10

Two-channel safety barriers, potential: + / Hazardous area

Application for load cells


Channel for positive and negative potential in
one module
Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

A2

Control room
equipment

UN

-ve

-ve

A2

0V

/ PA
05821E01

A2

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

1
2
1+2

6
6
--

490
490
--

543
543
--

11
11
--

9.33
9.33
18.7

20
20
20

50
50
90

90
90
90

3.9
3.9
0.27

330
330
330

29
29
1.64

9002/10-187-020-001

1
2
1+2

6
6
--

42
42
--

49
49
--

122
122
--

9.33
9.33
18.7

270
270
270

630
630
1260

0.23
0.23
0.23

3.9
3.9
0.27

2.2
2.2
2.2

29
29
1.64

9002/10-187-270-001

A2
A2

Functional data and safety-relevant maximum values


UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

A2
A2
A2
A2
A2
A2
A2
A2

2013-05-24AK00IIIen

Safety barriers

A2/9

43

Two-channel safety barriers, potential: + / Series 9002/10

Application case
Load cell (DMS) 350 or 700
6 conductors +/- 7.5 V (15 V), field circuit unearthed
Schematic
Hazardous area

Safe area

+7,5 V

9002/10-187-270-001

-7,5 V

9002/10-187-020-001

9002/77-093-040-001

09962E01

Operating data
Operating voltage
Voltage for load cell and
electric line
Current for load cell

Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note

A2/10

Safety barriers

UN ( +/- 7.5 V (15 V)


UL (at UN ( +/- 7.5 V)
IL (at UN ( +/- 7.5 V)
Number of the load cells
connected in parallel

350
UL (V)

ImA (V)

UL (V)

ImA (V)

11.6

35

13.2

19

9.6

55

11.6

35

70

10.6

45

80

9.6

55

Uo = 18.7 V
Io = 330 mA
Lo

IIC
0.18 mH
IIC
0.27 F

700

IIB
1.45 mH
IIB
1.64 F

Co
Po = 1.45 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 310 mA,
the maximum power to Po = 1.36 W.

2013-05-24AK00IIIen

44

Two-channel safety barriers, potential: ~ / ~


Series 9002/22

A2

Series 9002/22

Two-channel safety barriers, potential: ~ / ~


Hazardous area

Connection of a resistance teletransmitter is


possible
High precision resistance of each channel,
20 0.1
Low temperature influence of < 50 ppm/K
Connection to regulated power supply UN
Installation permitted in Division 2 and Zone 2

Safe area

+/-ve

+/-ve
Intrinsically safe
field device(s)

Control room
equipment

UN

+/-ve

+/-ve

A2
A2

0V

/ PA
05835E01

A2

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

1
2
1+2

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

0.7
0.7
1.4

19.9
19.9
--

20.1
20.1
--

33
33
--

1.6
1.6
3.2

150
150
300

60
60
120

1.3
1.3
0.2

100
100
100

7
7
1.8

1000
1000
1000

A2
9002/22-032-300-111

*)

A2

*) max. leakage current Ileak ( 10 mA


Functional data and safety-relevant maximum values
UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

A2
A2
A2
A2
A2
A2
A2
A2

2013-05-24AK00IIIen

Safety barriers

A2/11

45

Two-channel safety barriers, potential: ~ / ~


Series 9002/22

Application case
Pt100, 2-wire circuit, field circuit unearthed
Schematic

Hazardous area

Safe area
RTD
Input

9002/22-032-300-111

09959E01

Operating data
Operating voltage

UN ( 1.4 V

Series resistance of the


safety barrier

R = 2 x (20 +/- 0.1 )

Measuring range

( 400 C (IN ( 5 mA)


( 850 C (IN ( 3 mA)

Safety data
Maximum voltage

Uo = 3.2 V

Maximum current

Io = 300 mA

Maximum permissible
external inductance

Lo

IIC
0.2 mH

IIB
1.8 mH

Maximum permissible
external capacity

Co

IIC
100 F

IIB
1000 F

Pt100, 3-wire circuit, field circuit unearthed


Schematic

Hazardous area

Safe area
RTD
Input

9002/22-032-300-111

9001/02-016-150-111

Supply
Voltage

09960E01

Operating data
Operating voltage

UN ( 1.4 V

Series resistance of the


safety barrier

R = 2 x (20 +/- 0.1 )

Measuring range

( 400 C (IN ( 5 mA)


( 850 C (IN ( 3 mA)

Safety data

A2/12

Maximum voltage

Uo = 3.2 V

Maximum current

Io = 450 mA

Maximum permissible
external inductance

Lo

IIC
0.12 mH

IIB
0.5 mH

Maximum permissible
external capacity

Co

IIC
100 F

IIB
1000 F

Safety barriers

2013-05-24AK00IIIen

46

Two-channel safety barriers, potential: ~ / ~


Series 9002/22

A2
Two-channel safety barriers, potential: ~ / ~
Hazardous area

Connection to regulated power supply UN


Installation permitted in Division 2 and Zone 2

Safe area

A2

+/-ve

+/-ve
Intrinsically safe
field device(s)

Control room
equipment

UN

+/-ve

+/-ve

A2

0V

/ PA
05845E01

A2

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

1
2
1+2

5.5
5.5
11

84
84
--

95
95
--

57
57
--

7.9
7.9
15.8

100
100
200

198
198
395

4
4
0.5

8.8
8.8
0.478

15
15
4

115
115
2.88

9002/22-158-200-001

1
2
1+2

9
9
18

1043
1043
--

1156
1156
--

7.7
7.7
--

12
12
24

12
12
24

40
40
80

240
240
41

1.41
1.41
0.125

850
850
145

9
9
0.93

9002/22-240-024-001

1
2
1+2

9
9
18

158
158
--

177
177
--

50
50
--

12
12
24

80
80
160

240
240
480

6
6
0.7

1.41
1.41
0.125

22
22
4

9
9
0.93

9002/22-240-160-001

A2
A2
A2

Functional data and safety-relevant maximum values


UN

Nominal voltage

Imax

Maximum output current

Po

Maximum power

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

A2
A2

Application case
with RS 232
Schematic

Safe area

Hazardous area

A2

RS-232
Tx / Rx
Intrinsically Safe GND
Field Device

Tx / Rx

9002/22-240-160-001

GND

Interface
Module

A2
06624E01

A2
A2
A2
2013-05-24AK00IIIen

Safety barriers

A2/13

47

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Series 9002/13

Series 9002/13

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Hazardous area

Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for
channel 2
Nominal current limited to 40 mA at 250
load
Connection to unregulated power supply on
UN to channel 1
Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

Control room
equipment

UN

+ve

+ve

0V

/ PA
05439E01

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

1
2
1+2
*)

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

20 - 35
22
--

216
---

243
---

86
---

-3.5
--

25.2
25.2
25.2

118
0
121

740
20
760

1.3
50
1.25

0.107
0.107
0.104

7.4
150
7.35

0.82
0.82
0.8

9002/13-252-121-041

*)

only for channel 1: leakage current at 24 V / 35 V Ileak ( 1 mA / 10 mA

Functional data and safety-relevant maximum values

A2/14

UN

Nominal voltage

Additional voltage drop across the Lo


safety barrier

max. permissible external


inductance

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

max. permissible external capacity

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Imax

Maximum output current

Po

Maximum power

Safety barriers

Co

2013-05-24AK00IIIen

48

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Series 9002/13

A2
Application case
Analog output (current source) for I/P converter etc., field circuit unearthed
Schematic

Hazardous area

A2

Safe area

+20 ... 35 V DC

4 ... 20 mA

9002/13-252-121-041

A2
09953E01

A2

Operating data
Operating voltage

UN = + 20 ... 35 V

Operating current

IN = 0 ... 22 mA

Maximum voltage drop at


the safety barrier

Umax ( 8.9 V

A2

Safety data
Maximum voltage

Uo = 25.2 V

Maximum current

Io = 121 mA

Maximum permissible
external inductance

Lo

IIC
1.25 mH

IIB
7.35 mH

Maximum permissible
external capacity

Co

IIC
0.104 F

IIB
0.8 F

Maximum power

Po = 763 mW

A2
A2

Analog output (current source) for I/P converter etc., field circuit unearthed
Schematic

Safe area

Hazardous area

A2
+20 ... 35 V DC
9002/13-252-121-041

A2
06604E01

Operating data
Operating voltage

UN = + 20 ... 35 V

Open-circuit output voltage


(terminal 3 4, In = 0)

UL)

Operating current

IN = UL / 243 + RL

UN ( 24 V
UN - 3.5 V

A2

UN > 24 V
21 V

Safety data

A2

Maximum voltage

Uo = 25.2 V

Maximum current

Io = 121 mA

Maximum permissible
external inductance

Lo

IIC
1.25 mH

IIB
7.35 mH

Maximum permissible
external capacity

Co

IIC
0.104 F

IIB
0.8 F

Maximum power

Po = 760 mW

Application note

This safety barrier is used if the automation system activates the analog output signal in the return
(negative) line. The field device and automation system are not earthed and unregulated power supply
can be used.

A2
A2
A2

2013-05-24AK00IIIen

Safety barriers

A2/15

49

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Series 9002/13

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Hazardous area

Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to regulated power supply UN
Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

Control room
equipment

UN

+ve

+ve
0V

/ PA
05826E01

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

Io

Order number
Po

IIC

IIB
Lo

Co

mA

mA

mW

mH

mF

mH

mF

1
2
1+2

16
16
--

95
---

108
---

148
---

-2
--

19.9
19.9
19.9

222
3
225

1100
15
1120

0.39
1000
0.37

0.223
0.223
0.213

3.18
1000
3.15

1.42
1.42
1.38

9002/13-199-225-001

1
2
1+2

24
24
--

321
---

358
---

67
---

-2
--

28
28
28

90
3
93

630
21
651

2.2
50
2

0.083
0.083
0.08

14
150
13

0.65
0.65
0.636

9002/13-280-093-001

1
2
1+2

24
24
--

269
---

290
---

82
---

-2
--

28
28
28

107
3
110

749
21
770

1.35
50
1.25

0.083
0.083
0.08

9.6
150
9

0.65
0.65
0.635

9002/13-280-110-001

*)

Lo

Co

*)

only for channel 2: max. leakage current Ileak ( 10 mA

Functional data and safety-relevant maximum values

A2/16

UN

Nominal voltage

Additional voltage drop across the Lo


safety barrier

max. permissible external


inductance

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

max. permissible external capacity

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Imax

Maximum output current

Po

Maximum power

Safety barriers

Co

2013-05-24AK00IIIen

50

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Series 9002/13

A2
Application case
Load cell (DMS) 350 or 700
6 conductors + 16 V, field circuit unearthed
Schematic

Hazardous area

A2

Safe area

+16 V

9002/13-199-225-001

A2

0V

9002/11-199-030-001

9002/11-199-030-001

A2
09963E01

Operating data
Operating voltage
Voltage for load cell and electric
line
Current for load cell

UN ( + 16 V
UL (at UN = + 16 V)

A2

IL (at UN = + 16 V)
Number of the load cells
connected in parallel
1
2
3
4

Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note

350
UL (V)
10.4
8.3
6.9
5.9

ImA (V)
30
47
60
67

700
UL (V)
12.1
10.4
9.5
8.3

ImA (V)
17
30
41
47

A2

Uo = 19.9 V
Io = 285 mA

A2
IIC
0.2 mH
IIC
0.223 F

Lo

IIB
1.8 mH
IIB
1.42 F

Co
Po = 1.42 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating data remains
unchanged. The safety-relevant maximum current is reduced to Io = 255 mA, the maximum power to Po = 1.3 W.
Discrete 2-wire output for solenoid valves, LEDs and signalling devices
Schematic

Hazardous area

A2

Safe area

A2
+24 V DC
9002/13-280-110-001

A2
06605E01

Application note
This barrier is suitable for use with regulated power supplies and earthed return circuits. The nominal voltage is 24 V.
2-wire 4/20 mA I/P converters and control valves - standard and HART, 4/20 mA indicators
Schematic

Hazardous area

4 ... 20 mA

Safe area

+24 V DC
9002/13-280-110-001

A2

11334E01

Application note

A2

This safety barrier is used if the automation system activates the analog output signal in the return (negative) line.
The field device and automation system are not earthed and a regulated power supply must be used. At an operating
current of 0 ... 22 mA, the maximum voltage drop across the barrier will be 8.4 V.

A2
A2

2013-05-24AK00IIIen

Safety barriers

A2/17

51

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Series 9002/13

Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +


Hazardous area

Function:
Channel 1 current supply
Channel 2 evaluation barrier
No safety-relevant output current Io for channel 2
Connection to unregulated power supply on
UN to channel 1
Nominal current limited to 35 mA
Installation permitted in Division 2 and Zone 2

Safe area

+ve

+ve
Intrinsically safe
field device(s)

Control room
equipment

UN

+ve

+ve

0V

/ PA
05827E01

Selection table
Channel

UN

Rmin

Rmax

Imax

Safety data
Uo

1
2
1+2
*)

Io

Order number
Po

IIC

IIB

Lo

Co

Lo

Co

mA

mA

mW

mH

mF

mH

mF

20 - 35
26
--

292
---

327
---

52
---

-3.5
--

28
28
28

97
0
100

679
21
700

1.8
50
1.55

0.083
0.083
0.08

12
150
11

0.65
0.65
0.635

9002/13-280-100-041

*)

only for channel 1: leakage current < 26 V / > 26 V Ileak ( 1 mA / 35 mA

Functional data and safety-relevant maximum values


UN

Nominal voltage

Additional voltage drop across the Lo


safety barrier

max. permissible externa


l inductance

Rmin

Minimum resistance of the safety


barrier

Uo

Maximum voltage

max. permissible external capacity

Rmax

Maximum resistance of the safety


barrier

Io

Maximum current

Imax

Maximum output current

Po

Maximum power

Co

Application case
3-wire PNP inputs (positive switching) of proximity switches, photocells and encoders
Schematic

Hazardous area

Safe area

Supply

+20 ... 35 V DC
9002/13-280-100-041
V

+0 V
PNP
06595E01

A2/18

Safety barriers

2013-05-24AK00IIIen

52

Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: +


Series 9002/33

A2

Series 9002/33

Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: +

+ve
Intrinsically safe
field device(s)

Evaluation barrier for direct current signals


with max. output current Io
Suitable for potential-free contacts and
floating 4/20 mA signals
Positive potential of both channels
Installation permitted in Division 2 and Zone 2

Safe area

Hazardous area

+ve
Control room
equipment

UN

A2

+ve

+ve

A2

0V

/ PA
05829E01

A2

Selection table
Channel

UN

Imax

Safety data
Uo

1
2
1+2
*)

Io

Order number
IIC

IIB

Lo

Co

Lo

Co

mA

mA

mH

mF

mH

mF

25.5
25.5
--

60
60
--

3.5 *)
3.5 *)
--

28
28
28

0
0
0

1000
1000
1000

0.083
0.083
0.083

1000
1000
1000

0.65
0.65
0.65

A2
9002/33-280-000-001

A2

2.5 V to 20 mA

Functional data and safety-relevant maximum values


UN

Nominal voltage

Uo

Maximum voltage

Imax

Maximum output current

Io

Maximum current

Additional voltage drop across the Lo


safety barrier

Co

max. permissible external capacity

A2

max. permissible external


inductance

A2
A2
A2
A2
A2
A2
A2
2013-05-24AK00IIIen

Safety barriers

A2/19

53

Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: Series 9002/34

Series 9002/34

Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: Hazardous area

+ve

Intrinsically safe
field device(s)

Evaluation barrier for direct current signals


with max. output current Io
Application for passive signals of 4/20 mA
(transmitter with 4 conductors or more) with
insulated analog input on the control system
Channel for positive and negative potential in
one module
Installation permitted in Division 2 and Zone 2

Safe area

+ve
UN

RL

Control room
equipment
-ve

-ve

0V

/ PA
05828E01

Selection table
Channel

UN

Imax

Safety data
Uo

1
2
1+2
*)

mA

+ 16
-5
21

100
100
--

3.5
3.5
--

*)
*)

Io

Order number
IIC

IIB

Lo

Co

Lo

Co

mA

mH

mF

mH

mF

28
8
28

0
0
0

1000
1000
1000

0.22
8.4
0.083

1000
1000
1000

1.14
100
0.65

9002/34-280-000-001

2.5 V to 20 mA

Functional data and safety-relevant maximum values


UN

Nominal voltage

Uo

Maximum voltage

Imax

Maximum output current

Io

Maximum current

Additional voltage drop across the Lo


safety barrier

Co

max. permissible external capacity

max. permissible external


inductance

Application case
Vibration sensor
Schematic

Safe area

Hazardous area

4 ... 20 mA

9002/34-280-000-001

09951E011

Operating data
Operating current

IN = 0 ... 22 mA

Load

RL (750

Maximum voltage drop at


the safety barrier

Umax ( 3.5 V

Safety data

A2/20

Maximum voltage

Uo = 28 V

Maximum current

Io = 0 mA

Maximum permissible
external inductance

The inductance is determined depending on the maximum current of the transmitter

Maximum permissible
external capacity

Co

Maximum power

Po = 0 mW

Application note

A potential-free input is required for the circuit.


If the input is earthed, (RL to /PA), the safety barrier 9001/03-280-000-001 can be used.

Safety barriers

IIC
0.083 F

IIB
0.65 F

2013-05-24AK00IIIen

54

Two-channel safety barriers, star barrier / star barrier


Series 9002/77

A2

Series 9002/77

Two-channel safety barriers, star barrier / star barrier


Hazardous area

Safe area

+ve/-ve

+ve/-ve

Intrinsically safe
field device(s)

UN

+ve/-ve

Connection to regulated power supply UN


Suitable for voltage signals
Installation permitted in Division 2 and Zone 2
AC version

A2

Control room
equipment
+ve/-ve

A2

0V

/ PA
05836E01

A2

Selection table
Channel

UN

Rmin

Rmax

Safety data
Uo

1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
1
2
1+2
*)

Order number

Io

Po

IIC

IIB

Lo

Co

Lo

Co

mA

mW

mH

mF

mH

mF

545
545
--

9.3
9.3
9.3

20
20
40

50
50
90

90
90
23

4.1
4.1
4.1

330
330
87

31
31
31

9002/77-093-040-001

492
492
--

82.1
82.1
--

9.3
9.3
9.3

150
150
300

350
350
700

1.3
1.3
0.2

4.1
4.1
4.1

7
7
1.8

31
31
31

9002/77-093-300-001

71
71
--

69.2
69.2
--

10
10
10

200
200
400

500
500
1000

0.5
0.5
0.15

3
3
3

4
4
0.8

20.2
20.2
20.2

9002/77-100-400-001

60
60
--

126
126
--

15
15
15

150
150
300

560
560
1130

1.3
1.3
0.2

0.58
0.58
0.58

7
7
1.8

3.55
3.55
3.55

9002/77-150-300-001

12

111
111
--

358
358
--

22
22
22

73
73
146

400
400
800

7
7
1.4

0.165
0.165
0.165

26
26
7.4

1.14
1.14
1.14

9002/77-220-146-001

*)

18

321
321
--

180
180
--

22
22
22

148
148
296

810
810
1630

1.35
1.35
0.24

0.165
0.165
0.165

7.2
7.2
1.84

1.14
1.14
1.14

9002/77-220-296-001

18

159
159
--

*)

730
730
--

28
28
28

47
47
94

330
330
660

10.1
10.1
1.96

0.083
0.083
0.083

30
30
12.5

0.65
0.65
0.65

9002/77-280-094-001

24

657
657
--

A2
A2
A2
A2
A2

Ambient temperature - 20 ... + 50 C

A2

Functional data and safety-relevant maximum values


UN

Nominal voltage

Uo

Maximum voltage

Lo

max. permissible external


inductance

Rmin

Minimum resistance of the safety


barrier

Io

Maximum current

Co

max. permissible external capacity

Rmax

Maximum resistance of the safety


barrier

Po

Maximum power

A2
A2
A2
A2

2013-05-24AK00IIIen

Safety barriers

A2/21

55

Two-channel safety barriers, star barrier / star barrier


Series 9002/77

Application case
Load cell (DMS) 350 or 700
6 conductors +/- 7.5 V (15 V), field circuit unearthed
Schematic
Hazardous area

Safe area

+7,5 V

9002/10-187-270-001

-7,5 V

9002/10-187-020-001

9002/77-093-040-001

09962E01

Operating data
Operating voltage
Voltage for load cell and
electric line
Current for load cell

Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity
Maximum power
Application note
Vibration sensor
Schematic

UN ( +/- 7.5 V (15 V)


UL (at UN ( +/- 7.5 V)
IL (at UN ( +/- 7.5 V)
Number of the load cells
connected in parallel

350
UL (V)

ImA (V)

UL (V)

ImA (V)

11.6

35

13.2

19

9.6

55

11.6

35

70

10.6

45

80

9.6

55

Uo = 18.7 V
Io = 330 mA
Lo

IIC
0.18 mH
IIC
0.27 F

700

IIB
1.45 mH
IIB
1.64 F

Co
Po = 1.42 W
For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 310 mA, the
maximum power to Po = 1.36 W.

Hazardous area

Safe area
Voltage
Input

9002/77-093-300-001

09958E01

Operating data
Maximum series resistance
of the safety barrier
Sensor voltage
Safety data
Maximum voltage
Maximum current
Maximum permissible
external inductance
Maximum permissible
external capacity

A2/22

Safety barriers

Rmax = 2 x 82.1
U ( +/- 4 Veff / 6 Vpp
Uo = 9.3 V
Io = 300 mA
Lo
Co

IIC
0.2 mH
IIC
4.1 F

IIB
1.8 mH
IIB
31 F

2013-05-24AK00IIIen

56

Two-channel safety barriers


Series 9002

A2

Series 9002

Accessories and Spare Parts


Designation

Figure

Description

Art. no.

Weight

for all safety barriers of Series 9001, 9002 and 9004


Packaging unit: 5 pieces

158964

0.008

158977

0.002

158973

0.005

158826

0.006

165283

0.004

NS 35 / 15 (available by the metre)

103714

1.410

USLKG 5 (clamping range ( 4 mm2)

112760

0.012

kg
Back-up fuse
09919E00

Label carrier
09920E00

Labelling sheet

perforated, for automatic inscription


Format: DIN A4

A2
A2

09921E00

Adapter

A2

09922E00

Clamping base,
moulded material
09924E00

DIN rail

03856E00

Protective conductor
terminal

A2
A2

09926E00

Earthing terminal

A2

USLKG 6 N (clamping range ( 6 mm2)

112599

0.030

A2
09926E00

Fuse holder

158834

0.020

158828

0.023

09927E00

Insulation and
fastening material

for mounting rail NS 35/15

A2

09928E00

A2
A2
A2
A2
A2
2013-05-24AK00IIIen

Safety barriers

A2/23

57

Two-channel safety barriers


Series 9002

103 mm / 4.06 "

12 mm / 0.47 "

72 mm / 2.83 "

Dimensional drawings (all dimensions in mm / inches) - subject to modifications

09929E00

76 mm / 3.00 "

95 mm / 3.74 "

80 mm / 3.15 "

Safety barrier 9001, 9002, 9004

09930E00

66 mm
2.60 "

66 mm
2.60 "

38 mm
1.50 "
09933E00

38 mm
1.50 "
09932E00

Safety barrier 9001, 9002, 9004


mounted on the mounting rail LV 35/15
EN 50 022

Safety barrier 9001, 9002, 9004


mounted on the mounting rail LV 32
EN 50 035 with adaptor and clamping
base made of moulded material

Safety barrier 9001, 9002, 9004


mounted on
mounting plate with adaptor

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice.
The illustrations cannot be considered binding.

A2/24

Safety barriers

2013-05-24AK00IIIen

58
/E

Attachment 1: Location of barriers and indicators

Added

Barriers and Indicators are mounted on the stanchions.


Stanchions are located here.
(
: Stanchion)