Materials Code
N A N CY P EA RCE CI H
S E NI OR F I R E P ROT ECTI ON E N G INEER
N AT IONA L F I R E P ROT EC TION A S S OCIATION
(2)
(3)
Flammable solids
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Flammable solids
Organic peroxide formulations
Solid and liquid oxidizers
Pyrophoric materials
LP Gases
NFPA 58
NFPA 59
Chapter 2 References
Chapter 12 Corrosives
Chapter 3 Definitions
Chapter 4 Classification
Chapter 16 Reserved
Chapter 7- Emergency
Chapter 17 Pyrophorics
Chapter 8-Reserved
Chapter 18 Toxics
Chapter 9-Security
NFPA 400
Classifies the hazardous material
Provides you with the maximum amount (MAQ) that should be stored in a
particular occupancy before requiring special construction requirements.
Provides methods for increasing amounts by using special protections
such as sprinklers or special storage requirements.
Provides storage use and handling requirements for all covered materials.
YES
Quantity exceeds
MAQ?
NO
Or
gate
Apply provisions
for protection
levels
Apply provisions
for multiple
control areas
No special
construction
features
required
12
3.3.61.10.1* Class 1 Unstable (Reactive). Materials that in themselves are normally stable, but that can
become unstable at elevated temperatures and pressures.
3.3.61.10.2* Class 2 Unstable (Reactive). Materials that readily undergo violent chemical change at
elevated temperatures and pressures.
3.3.61.10.3* Class 3 Unstable (Reactive). Materials that in themselves are capable of detonation or
explosive decomposition or explosive reaction, but that require a strong initiating source or that must be
heated under confinement before initiation.
3.3.61.10.4* Class 4 Unstable (Reactive). Materials that in themselves are readily capable of detonation
or explosive decomposition or explosive reaction at normal temperatures and pressures.
YES
Quantity exceeds
MAQ?
NO
Or
gate
Apply provisions
for protection
levels
Apply provisions
for multiple
control areas
No special
construction
features
required
15
YES
Quantity exceeds
MAQ?
NO
Or
gate
Apply provisions
for protection
levels
Apply provisions
for multiple
control areas
No special
construction
features
required
19
Control Area
A building or portion of a building or outdoor area within which hazardous materials
are allowed to be stored, dispensed, used, or handled in quantities not exceeding
the maximum allowable quantities (MAQ).
Can have multiple control areas up to a maximum depending on the floor level
and fire resistance
Control Areas are separated by particular fire resistance-1-2 hours (includes floors,
walls to completely separate from other areas)
Control Areas
Flammable
Solid Storage =
MAQ is 125 lb.
Sprinkler
Protection
Provided =
Footnote D
allows a 100%
increase
YES
Quantity exceeds
MAQ?
NO
Or
gate
Apply provisions
for protection
levels
Apply provisions
for multiple
control areas
No special
construction
features
required
25
Protection Level
Protection Level describes a tier of building safety that exceeds the
construction requirements for control areas
The MAQ is able to be exceeded due to the increased protective
measures associated with the Protection Level provisions imposed
The Protection Level required is dependent on the Hazard Level of
the contents
Protection Level construction allows you to exceed the MAQ
NFPA 400
Classifies the hazardous material
Provides you with the maximum amount (MAQ) that should be stored in a
particular occupancy before requiring special construction requirements.
Provides methods for increasing amounts by using special protections
such as sprinklers or special storage requirements.
Provides storage use and handling requirements for all covered materials.
Haz-Mat releases
Personnel training
Ignition source controls
Equipment and processes, tanks etc
Shelf construction
Separation of incompatibles
Closure plan
Other plans as required may include Incident Investigation Plan, Security Plan
Emergency Action Plan-always required. Unauthorized releases activate the plan
Example
31
Calcium Hypochlorite
Industrial Occupancy
Ammonium dichromate
(2)
(3)
(4)
YES
Quantity exceeds
MAQ?
NO
Or
gate
Apply provisions
for protection
levels
Apply provisions
for multiple
control areas
No special
construction
features
required
36
37
38
Separation of combustibles by a
1 hour fire barrier wall
Pre-incident planning
Notification and Alert System
48