GE Industrial Systems
EX2100
Static Excitation System
These instructions do not purport to cover all details or variations in equipment, nor
to provide for every possible contingency to be met during installation, operation,
and maintenance. If further information is desired or if particular problems arise
that are not covered sufficiently for the purchaser’s purpose, the matter should be
referred to GE Industrial Systems.
This document contains proprietary information of General Electric Company, USA,
and is furnished to its customer solely to assist that customer in the installation,
testing, operation, and/or maintenance of the equipment described. This document
shall not be reproduced in whole or in part, nor shall its contents be disclosed to any
third party without the written approval of GE Industrial Systems.
Section Page
Introduction..................................................................................................................3
Hardware......................................................................................................................3
Digital Controller (Thyristor-Based Controls)......................................................6
Application Control Layer Board (ACLA)...........................................................7
Digital Signal Processor Control Board (DSPX)..................................................8
Exciter ISBus Board (EISB) .................................................................................8
Exciter Selector Board (ESEL).............................................................................8
Exciter PT/CT Board (EPCT)...............................................................................8
Exciter Contact Terminal Board (ECTB) .............................................................9
Exciter Terminal Board (EXTB) ..........................................................................9
Excitation Power Supply Module (EPSM and EPBP)..........................................9
Exciter Power Distribution Module (EPDM) .....................................................10
Gate Pulse Amplifier Board (EGPA)..................................................................10
Exciter DC Feedback Board (EDCF) .................................................................11
Exciter AC Feedback Board (EACF) .................................................................11
Exciter De-Excitation Module (EDEX)..............................................................11
Power Control Module (Thyristor – SCR)..........................................................13
DC Interrupting Device ......................................................................................13
AC Isolation Device ...........................................................................................13
Shaft Voltage Suppressor....................................................................................14
Crowbar Module.................................................................................................14
Field Flashing Module ........................................................................................14
Field Ground Detector (EGDM).........................................................................14
Redundancy (Power Bridge – Warm Back-Up) .................................................15
Operator Console (Remote/Local)......................................................................15
Diagnostic Interface (Keyboard) ........................................................................16
Cabinet................................................................................................................16
Standards Supported ...........................................................................................17
________
Ethernet is a trademark of Xerox Corporation.
SPEEDTRONIC is a trademark of General Electric Company, USA
VersaMax is a trademark of GE Fanuc Automation North America, Inc.
Software .................................................................................................................... 18
Overview............................................................................................................ 18
Software Transducers......................................................................................... 18
Auto Regulator Reference (AUTO REF)........................................................... 19
Manual Regulator Reference (MANUAL REF) ................................................ 19
Automatic and Manual Reference Follower (Tracking) ................................... 20
Exciter AVR Setpoint (EXASP) ........................................................................ 21
Under Excitation Limiter (UEL)........................................................................ 21
Reactive Current Compensation (RCC/ARCC)................................................. 21
Volts per Hertz Limiter (V/Hz Lim) .................................................................. 21
Automatic Voltage Regulator (AVR) ................................................................ 21
Power System Stabilizer (PSS) .......................................................................... 22
Stator Current Limit (SCL) ................................................................................ 22
Manual Regulator (FVR or FCR) ...................................................................... 22
Over-excitation Limiter (OEL) .......................................................................... 23
Hydrogen Pressure / Temperature Limiter Compensation................................ 23
Manual Restrictive Limiter ................................................................................ 23
VAR/PF Control ................................................................................................ 23
Generator Simulator (GEN SIM)....................................................................... 24
Unit Data Highway Interface (UDH)................................................................. 24
DCS Interface (ModBus) ................................................................................... 24
Volts per Hertz Protection (24G) ....................................................................... 24
Over-Excitation Protection (OET) ..................................................................... 24
Generator Overvoltage Trip (59G) .................................................................... 24
Potential Transformer Fuse Failure Detection (PTFD)...................................... 25
Transfer to Manual Regulator upon Loss of PT................................................. 25
Loss of Excitation Protection (40) ..................................................................... 25
Exciter Phase Unbalance (EUT) ........................................................................ 25
OffLine Over Excitation Protection (OLOT)..................................................... 25
Generator Field Temperature Calculation.......................................................... 25
Testing ...................................................................................................................... 26
Routine Factory Tests ........................................................................................ 26
Customer Witness Testing ................................................................................. 26
Option A – Customer Witness ........................................................................... 27
Option B - Customer Witness ............................................................................ 27
Hardware
The EX2100 is available in several configurations to provide flexibility for full static
excitation systems. These systems can support potential (voltage only) or compound
(voltage and current) source.
The architecture is one control rack, the customer interface sub-system, operator in-
terface device, control power input module and the power module. The power mod-
ule consists of a bridge interface sub-system, power bridge, ac and dc filter networks,
and ac and/or dc isolation devices.
The EX2100 supports Ethernetä local area network (LAN) communication to:
• Control System Toolbox (toolbox)
• Mark VI turbine control system and HMI using the Ethernet Global Data (EGD)
protocol
• Static Starter
• OnSite center
It can also support a RS-232 ModBus interface to a customer Distributed Control
System (DCS).
The EX2100 incorporates a powerful diagnostic system and a control simulator to
support fast installation, tuning of control constants, and training.
The following two figures include a one-line diagram overview of the EX2100 sys-
tem, and all the printed wiring boards (PWBs) in the EX2100, along with major in-
terconnections.
Customer I/O
CT Current
PT Voltage I/O
Bridge I/O
AC AC CB
Generator Aux
Source
Control Control Control
M1 M2 C
PPT
Gating Selector
(Bridge 1 or 2)
AC CB or
Disconnect
Line Filter
To Bridge
Power Power #1 only
Conversion Conversion To Bridge
Modules Modules #2 only
(Bridge #2) (Bridge #1)
AC
Flashing
DC
Control
DC CB or
Contactor
Keypad Keypad
EBKP
Backplane
PT PT M1 M2 C
EXTB
PT PT To Flashing
panel
ACLA
DSPX
DSPX
DSPX
ACLA
53A 41
pilot close
ESEL
ESEL
53A 41 De-
CT pilot close excitation
53B 41
EPCT 53B 41
EISB
EISB
EISB
De-ex
pilot trip pilot
70V
53B 41 -125Vdc
70V pilot trip
Bridge 1
Bridge 2
TRIP
86
Tool Gate Pulse Amplifiers
Bridge 3
Bridge 4
2nd
TRIP
EGPA
EETB
Bridge 5
Bridge 6
125Vdc
EGPA
125Vdc
EDCF
EDEX
De-excitation
EPBP 125 Vdc
EPDM Coil Power
back EXAM
plane Attenuator
GPA power
Field
Ground 125 V dc Option: Optional:
Detector Battery DACA Crowbar
EGDM Rectified ac
Communication
with Mark VI, HMI, Ethernet Data Highway (EGD, Modbus)
and LCI Static Starter
Serial Serial
Modb us Modb us
ACLA DSPX DSPX ACLA DSPX
M1 M1 M2 M2 C
g
Status Lights:
GE Industrial Systems
2
ENET
Discrete Hall
Effect Sensors
1 3 5
4 6 2
1 4 3 6 5 2
DC Power Source
130 V dc (nominal)
80 - 140 V dc
Line Filter Sensor
Single cable
5 feedbacks to control
(redundantfeedbacks to M1 and M2)
- 3 cond sensors
- 1 ALAR M
- 1 Temp/FAULT(VCO)
To Bridge 2
41A + - 2
Gen. Fld +
1 BK WH
Au xiliary Encl.
HS +
De-Excit.
FDI-1
SCR1 SCR2 SCR3 53B (W) Field
L1 53B (Y) Flash
L2
L3 TB1-1 Shaft
TB1-2 Voltage
SCR4 SCR5 SCR6
41B
J1 J4 J2 J5 J3 J6 Gen. Field -
Control
Enclosure To Bridge 2
J2/3M
EXTB 4
K41_M1 K41_M2
1 41A 41B
J6 FI 3 3
K41_M2 K41_C 4 LT
4 4
K41_C K41_M1 1 1 2
J505 J505 5 5
EMIO M1
J508 J508
70V Ret Control Encl.
EMIO M2 Feedback
J515 PDM
J515 + -
1 2
EMIO C J7A
125VDC
DC Interrupting Device
For most applications a field interrupting dc contactor in the rectifier bridge dc-
positive output is used to connect the exciter to the generator field leads. The dc
contactor and the de-excitation module (SCR or diode-based) together form the in-
ternal field breaker function found in previous excitation systems used to remove
stored energy in the generator field during shutdown or trip events. Often, two dc
contactors are provided to interrupt both the positive and negative field leads.
For some applications, an external exciter field breaker is offered. DC field breakers
interrupt the output of the exciter and use a shorting contact to de-excite the genera-
tor field through a discharge resistor. Some dc field breakers may use a static de-
excitation device in place of the shorting contractor, which is functionally the same
as the combination of a dc contactor and static de-excitation module.
AC Isolation Device
An internal manual ac disconnect switch is offered for small to medium size systems,
below 600 V ac. This switch serves as a disconnect device between the secondary of
the power potential transformer and the power bridge in the static exciter. In most
cases, it is a molded case, 3-phase, non-automatic, panel-mounted switch, which is
manually operated. This switch permits the customer to close and open the ac-input
supply.
An external ac disconnect breaker can be offered for larger systems. This breaker
serves as a disconnect device between the secondary of the power potential trans-
former and the static exciter. It may be a molded-case or a vacuum breaker support-
ing remote control. This breaker permits the customer to close and open the ac-input
supply.
Crowbar Module
A crowbar circuit is applied for most hydro applications (salient pole generators) and
some steam or gas applications (wound rotor generators). During a pole slip event
(when the generator loses synchronism with the power grid), high voltages can be
induced from the generator stator back on the generator field. This high voltage can
damage the excitation system and/or the generator field if the induced voltage rises
above destructive levels. The crowbar safely limits the induced voltage below the de-
structive level for the excitation system and the generator field.
The hardware used to implement the crowbar function is the de-excitation module
with the thyristor direction changed. The load for the crowbar must be a resistor, but
the resistor can be shared with the de-excitation function. The functionality of the
crowbar, thyristor with snubber, and conduction sensor, are the same as for the de-
excitation module. The crowbar’s thyristor is turned on when the anode to cathode
voltage of the SCR exceeds a certain value. Once the crowbar conducts, the reverse
current induced by the pole slip event has a conduction path thus limiting the voltage
on the generator field and exciter output.
g EX2100 Excitation
C t l
Exciter Health
FVR Feedback
& State Icons
0.0 Volts -30% 0% 100% 150%
FldCurrAmps
0.00 Amps -30% 0% 100% 150%
Exciter Control
On
Navigation
Run (Green)
Reset
Status Auto
Faults
Stop (Red)
Menu Command Man
Menu
Voltage Level
Off
Escape Enter
Display: Pushbuttons:
Status screens provide analog and digital Organized into functional groups:
representation of exciter functions and values. Navigation buttons for using the menu
Menu screens provide text-based access to Exciter Control buttons
parameters, wiz ards, and faults. Run and Stop buttons
Cabinet
The exciter lineup is supplied in a NEMA 1 / IP20 freestanding, indoor-type metal
cabinet for floor mounting installation. The lineup consists of several cabinets bolted
together, with cable entry through the top or bottom. The equipment is designed to
operate in an ambient temperature range of 0° C to 40° C, but custom applications
may support up to 50° C.
Each cabinet consists of a rigid, self-supporting, enclosed panel with a full-length
door to provide easy access to the equipment. The panel back serves as the rear of
the cabinet. Each door is equipped with a suitable handle, three-point latch, and pro-
visions for locking. The power bridge doors do not have handles, but are bolted
closed to support code requirements. The standard cabinet color is ANSI-70 (light
gray) on both exterior and interior surfaces.
Overview
The EX2100 software is designed to support high performance and structured to help
the customer and field engineers to understand, install, commission, tune, and main-
tain the excitation system. The following sections define major software functions
shown in the software overview block diagram below.
Voltage/Current
Sensing
DC
Regulator
DC Voltage
adjust Exciter
Generator
Bridge
AC
Regulator
AC
Voltage
adjust Exciter System
Stabilizer Circuits
Over-e xcitation
Limiter
Under-excitation
Limiter
Power System
Stabilizer
Software Transducers
Integral to the high performance of the EX2100 is the sophisticated software trans-
ducering system. The generator Potential Transformers (PTs) and Current Trans-
formers (CTs) are the source of the control signals needed by the automatic
(generator terminal voltage) regulator, most limiters, and protection functions. The
system simultaneously samples the ac waveform at high speed and in software uses
advanced mathematical algorithms to digitally generate the variables needed.
EXASP
Setpoint
Exciter AVR
Setpoint.
Watts
PSS V/Hz Limit;
Reactive AVR
Power Current Setpoint
Slip System Compen- and
Stabilizer sation. Tracking
Frequency
Watts
UEL VMAG AVR
VARs
Automatic
Under Voltage FVR
Generator
Excitation VMAG Regulator Track
Terminal
Limit Value
Voltage
(VMAG) Setpoint
FVR
Field Voltage Regulator Setpoint
External Field
Raise/ MANUAL Voltage
Lower REF Regulator Firing
Commd
to
Bridge
Min.
FCR Setpoint
Field Volts from Bridge Output (User Input) FCR
Field
Field Current from Bridge DC Shunt Current
Regulator
VAR/PF Control
This function is accomplished by slow ramping of the AVR reference setpoint. The
VAR/PF is selected by operator command and the var/pf value is controlled using
the raise/lower pushbuttons. When the exciter interfaces with a Mark VI turbine
control system, this function is typically included in the Mark VI system.
The transformer tests are in general accordance with ANSI Std. C57.91 for dry type
transformers and ANSI Std. C57.90 for liquid filled transformers. The tests include:
• Resistance measurements by any of the methods described in the applicable
ANSI standard
• No-load loss and excitation test
• Applied potential test
• Induced potential test
• Losses and impedance tests
• Ratio tests
• Phase relation test
g
GE Industrial Systems
Issue date: 2000-12-04 General Electric Company
2000 by General Electric Company, USA.
All rights • EX2100 Static Excitation
28reserved. System 1501 Roanoke Blvd. GEH-100488EX2100
+ 1 540 387 7000 Salem, VA 24153-6492 USA