PEMEX Refinacin

Aprovechamiento de Residuales Ref. Miguel Hgo.


No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1
Job Bulletin
JB ART 115 Rev. 1
Oct 19, 15

Cables of Control and Instrumentation General Specification ART-02-120-P-ESP-5025 (Extract)

1. Objective: Provide the most significant issues of the document ART-02-120-P-ESP-5025 for the
understanding of Fluor ND Engineering about the Cables of Control and Instrumentation

2. Scope: This bulletin applies for HDGO unit.

3. Annexes: N/A

4. Formats: N/A

By Abel Ruiz Nicolas at 11:04 am, Oct 20, 2015

Abel Ruz Nicols


Control Systems Lead

Pag. 1 de 15

By Ciro Jardn Castrejn at 10:06 am, Oct 20, 2015

Ciro Jardn Castrejn


Control Systems Coordinator

By Enrique Gutirrez at 6:56 am, Oct 21, 2015

By Silvia Alfaro at 6:30 pm, Oct 20, 2015

Silvia G. Alfaro Hernndez


Project Engineer

Enrique N. Gutirrez Garca


Project Manager

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

5. Proceso:
1.0 ALCANCE
Esta especificacin establece los requerimientos mnimos con que debe cumplir el diseo, ingeniera,
documentacin, fabricacin, inspeccin, pruebas, empaque y embarque de los cables de instrumentacin
y control a ser suministrados en las plantas nuevas, de servicios auxiliares e integracin del proyecto
APROVECHAMIENTO DE RESIDUALES REF. MIGUEL HGO.
1.0 SCOPE
This specification establishes the minimum requirements that must comply the following: design,
engineering, manufacturing, tests, package and shipment of cables for instrumentation and control to be
supplied in new units, utility units and integration units of the project Aprovechamiento de Residuales Ref.
Miguel Hgo.
2.0 CODIGOS Y NORMAS APLICABLES
El diseo, fabricacin y pruebas de este tipo de instrumento, debern estar de acuerdo a los
requerimientos de las normas y cdigos aplicables de las siguientes instituciones:
ASTM (American Society for Testing and Materials)
ASTM-B-3-2007 Standard Specification for Soft or annealed Copper wire
ICEA (Insulated Cable Engineers Associaton)
ICEA-S-73-532-2004 Standard for Control, Thermocouple Extension and instrumentation cables
ANSI (American National Standards Institute)
ANSI/NEMA WC 57/ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation
Cables
ANSI/ISA 50.02 PART 2 Fieldbus Standard for use in industrial control systems Part 2 Physical layer
specification and service definition
IEC (International Electrotechnical Commission)
IEC-61515 Mineral Insulated Thermocouples Cables and Thermocouples
IEC-61158-2009 Industrial communication networks - Fieldbus specifications
UL (Under writers Laboratories)
UL-1581-2001 Standard for safety reference for electrical wires, cables and flexible cords.
UL-2250 Standard for instrumentation tray cable
NFPA (National Fire ProtecctionProtection Association)
NFPA-70-2008 National Electrical Code
NOM (Normas Oficiales Mexicanas)
NOM-001-SEDE-2012 Instalaciones Elctricas
2.0 CODIGOS Y NORMAS APLICABLES
The design, manufacturing and tests of this type of instrument, must be according to the requirements of
the applicable regulations and codes from the following institutions:
ASTM (American Society for Testing and Materials)
ASTM-B-3-2007 Standard Specification for Soft or annealed Copper wire
ICEA (Insulated Cable Engineers Associaton)

Pag. 2 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

ICEA-S-73-532-2004 Standard for Control, Thermocouple Extension and instrumentation cables


ANSI (American National Standards Institute)
ANSI/NEMA WC 57/ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation
Cables
ANSI/ISA 50.02 PART 2 Fieldbus Standard for use in industrial control systems Part 2 Physical layer
specification and service definition
IEC (International Electrotechnical Commission)
IEC-61515 Mineral Insulated Thermocouples Cables and Thermocouples
IEC-61158-2009 Industrial communication networks - Fieldbus specifications
UL (Under writers Laboratories)
UL-1581-2001 Standard for safety reference for electrical wires, cables and flexible cords.
UL-2250 Standard for instrumentation tray cable
NFPA (National Fire ProtecctionProtection Association)
NFPA-70-2008 National Electrical Code
NOM (Normas Oficiales Mexicanas)
NOM-001-SEDE-2012 Instalaciones Elctricas
2.1 Guas de aplicacin Foundation Fieldbus
AG (Foundation Fieldbus application guide )
AG 163 Rev 2.0
31,25 Kbit/s Intrinsically safe systems
AG 181 Rev 2.0
System engineering guidelines
AG 140 Rev 1.0
31.25 Kbit/s Wiring and installation
Si un cdigo o norma emitida por las instituciones anteriormente mencionadas hacen referencia o
promueven otros cdigos o normas, stas ltimas deben de ser consideradas como incluidas en las
instituciones anteriormente listadas.
Los cables deben cumplir con Underwriters Laboratories (UL) o deben estar aprobados por un laboratorio
nacional de pruebas de reconocido prestigio del pas o ciudad donde sean fabricados.
En el caso de presentarse discrepancias entre los documentos de la solicitud de cotizacin, esta
especificacin y cualquier otro documento, el Proveedor debe hacerlo del conocimiento de ICA Fluor e
indicarlo por escrito para obtener a su vez, una resolucin por escrito
2.1 Guides for Foundation Fieldbus application.
AG (Foundation Fieldbus application guide)
AG 163 Rev. 2.0
31,25 Kbit/s Intrinsically safe systems
AG 181 Rev. 2.0
System engineering guidelines
AG 140 Rev. 1.0
31,25 Kbits/s Wiring and installation
If a code or regulation issued by the institutions above mentioned makes reference or promotes another
regulations or codes, these last must be considered as included in the institutions above mentioned.
The cables must comply with Underwrites Laboratories (UL) or must be approved by a national tests
laboratory with recognized prestige of the country or city where are manufactured from.

Pag. 3 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

In the case to present discrepancies between documents of the Request for Quotation, this specification
and any other document, provider must announce to ICA Fluor and indicate it written to obtain a written
resolution.
3.0 REQUERIMIENTOS GENERALES DE DISEO
3.1 La configuracin de los cables de instrumentacin deben ser de dos conductores, multiconductor, par
simple, multipar, trada simple o multi-trada dependiendo de la aplicacin.
3.0 GENERAL REQUIREMENTS OF DESIGN
3.1 The configuration of the instrumentation cables must be of 2-wire, multi conductor, single pair, multipair, simple triad or multi-triad. Depending the application.
3.2 Cable de instrumentos multipar (4, 8, 12, 24 y 36 pares 18 AWG) debe ser de tipo PLTC/ITC-ER,
300 V, 105C, PVC aislante primario, par trenzado, para referencia del cdigo de color, ver "Insulated
Cable Engineers Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57) tabla E5, para
identificacin del (+) y (-), con pantalla protectora de aluminio mylar por par individual y general, alambre
de drenado por par individual y general, cubierta protectora del Cable de PVC de color; negro para
seales sin seguridad intrnseca y de color azul claro para las seales con seguridad intrnseca resistente
a la propagacin de incendios y a la luz solar, con cuerda nylon de desgarre.
3.2 Instrumentation Cable (Multi-Pair): (4, 8, 12, 24 and 36 pairs of 18 AWG Gauge) must be of
"PLTC/ITC-ER" type, 300 Volt, 105C, Primary PVC Insulator, Twisted-Pair, for the reference of the color
code, must see "Insulated Cable Engineers Association" (ICEA) S-73-532 Standard for control Cables
(NEMA WC57) table N E5, for the identification of Positive (+) and Negative (-), with a protective shield
made in mylar aluminum for single pair and general, drainage cable for each single pair and general,
protective cover of PVC cable in Black color for non-intrinsically safe signals and the Blue color for
intrinsically safe signals with fire resistance and sunlight, with a nylon rope for tearing.
3.3 Cable de instrumentos par simple (1 par 16 AWG) debe ser de tipo PLTC/ITC -ER, 300 V 105C,
PVC aislante primario, par trenzado, para referencia del cdigo de color, ver "Insulated Cable Engineers
Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57) tabla E5, para identificacin del
(+) y (-), con pantalla protectora de aluminio mylar individual , alambre de drenado y cubierta protectora
del Cable de PVC de color; negro para seales sin seguridad intrnseca y de color azul claro para las
seales con seguridad intrnseca resistente a la propagacin de incendios y a la luz solar, con cuerda
nylon de desgarre.
3.3 Instrumentation Cable (Simple-Pair): (1 pair of 16 AWG Gauge) must be of "PLTC/ITC-ER" type,
300 Volt, 105C, Primary PVC Insulator, Twisted-Pair, for the reference of the color code, must see
"Insulated Cable Engineers Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57)
table N E5, for the identification of Positive (+) and Negative (-), with a protective shield made in single
mylar aluminum, drainage cable and protective cover of PVC cable in Black color for non-intrinsically safe
signals and the Blue color for intrinsically safe signals with fire resistance and sunlight, with a nylon rope
for tearing.
3.4 Cable para seales con protocolo Foundation Fieldbus para 31.25 Kbps, tipo A , par trenzado,
simple (1 par 18 AWG) debe ser de tipo PLTC/ITC-ER, CMX-Outdoor, 300 V, 105 C, par trenzado,
aislante primario de PVC, para referencia de cdigo de color, ver Industrial communication networks
Fieldbus specifications Part 2: Physical layer specification and service definition IEC 61158-2, para
identificacin del (+) y (-), con pantalla protectora de aluminio mylar total, alambre de drenado y cubierta
protectora del Cable de PVC de color: azul claro para seal foundation fielbus (FISCO) para los spurs y de

Pag. 4 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

color naranja seal foundation fieldbus (Ex) para el trunk resistente a la propagacin de incendios y a la
luz solar, con cuerda nylon de desgarre.
3.4 Signals Cable with Foundation Fieldbus Protocol: For 31.25 Kbps, "A" Type, Twisted Pair, simple
(1 pair of 18 AWG Gauge), must be of "PLTC/ITC-ER" type, 300 Volt, 105C, Primary PVC Insulator, for
the reference of the color code, must see Industrial Communication Networks - Fieldbus Specificatios Part 2: Physical layer specification and service definition IEC 61158-2, for the identification of Positive (+)
and Negative (-), with a protective shield made in total mylar aluminum, drainage cable and protective
cover of PVC cable in Light Blue color for Foundation Fieldbus (FISCO) and the spurs. And the Orange
color for Foundation Fieldbus (Ex) for the "trunk", with fire resistance and sunlight, with a nylon rope for
tearing.
3.5 Cable de instrumentacin multitrada (4, 8 y 12 tradas 18 AWG) debe ser de tipo PLTC/ITC-ER,
300 V, 105 C, aislante primario de PVC, para referencia del cdigo de color, ver "Insulated Cable
Engineers Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57) tabla E5, para
identificacin del (+), (-), y (c), tradas torcidas con pantalla protectora de aluminio mylar individual y
general, alambre de drenado individual por triada y cubierta protectora del cable de PVC, resistente a la
propagacin de incendios y a la luz solar con cuerda nylon de desgarre.
3.5 Instrumentation Cable (Multi-Triad): (4, 8 and 12 pairs of 18 AWG Gauge) must be of "PLTC/ITCER" type, 300 Volt, 105C, Primary PVC Insulator, for the reference of the color code, must see "Insulated
Cable Engineers Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57) table N E5,
for the identification of Positive (+) and Negative (-) and (c), twisted triads with a protective shield made in
single and general mylar aluminum, single drainage for each triad and protective cover of PVC cable with
fire resistance and sunlight, with a nylon rope for tearing.
3.6 Cable de instrumentacin trada simple (1 trada 16 AWG) debe ser de tipo PLTC/ITC-ER, 300 V,
105 C, aislamiento primario de PVC, para referencia del cdigo de color, ver "Insulated Cable Engineers
Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57) tabla E5, para identificacin del
(+), (-), y (c), trada torcidas con pantalla protectora de aluminio mylar total, alambre de drenado y cubierta
protectora del cable de PVC de color; negro para seales sin seguridad intrnseca y de color azul claro
para las seales con seguridad intrnseca resistente a la propagacin de incendios y a la luz solar, con
cuerda nylon de desgarre.
3.6 Instrumentation Cable (Simple-Triad): (1 triad of Gauge 16 AWG) must be of "PLTC/ITC-ER" type,
300 Volt, 105C, Primary PVC Insulator, for the reference of the color code, must see "Insulated Cable
Engineers Association" (ICEA) S-73-532 Standard for control Cables (NEMA WC57) table N E5, for the
identification of Positive (+) and Negative (-) and (c), twisted triad with a protective shield made in total
mylar aluminum, drainage cable and protective cover of PVC cable in Black color for non-intrinsically safe
signals and the Light blue color for intrinsically safe signals, with fire resistance and sunlight, with a nylon
rope for tearing.
3.7 Cable de 2 conductores para instrumentos con seal de entrada discretas de 24 VCD cal. 16
AWG debe ser tipo TC, 600 V, 75 C en ambiente mojado y 90C en ambiente seco, aislamiento primario
de PVC nylon, para referencia del cdigo de color ver Insulated Cable Engineers Association (ICEA) S-73532 Standard for Control Cables (NEMA WCST) tabla E2 para identificacin del (+) y (-), sin pantalla
protectora y cubierta protectora, del cable de PVC de color; negro para seales sin seguridad intrnseca y
de color azul claro para las seales con seguridad intrnseca resistente a la propagacin de incendios y a
la luz solar, con cuerda de nylon de desgarre.
3.7 2-Wire Cable for instruments with discrete input signal of 24VDC: (16 AWG Gauge) must be of
"CT" type, 600 Volt, 75C in wet environment and 90C in Dry environment, Primary PVC Nylon Insulator,

Pag. 5 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

for the reference of the color code, must see "Insulated Cable Engineers Association" (ICEA) S-73-532
Standard for control Cables (NEMA WCST) table N E2, for the identification of Positive (+) and Negative () and (c), without a protective shield and protective cover of PVC cable in Black color for non-intrinsically
safe signals and the Light blue color for intrinsically safe signals, with fire resistance and sunlight, with a
nylon rope for tearing.
3.8 Cable de 2 conductores para instrumentos con seal de salida discretas de 24 VCD cal. 14 AWG
debe ser tipo TC, 600 V, 75 C en ambiente mojado y 90C en ambiente seco aislamiento primario de
PVC nylon, para referencia del cdigo de color ver Insulated Cable Engineers Association (ICEA) S-73532 Estndar for Control Cables (NEMA WCST) tabla E2 para identificacin del (+) y (-), sin pantalla
protectora y cubierta protectora, del cable de PVC de color; negro para seales sin seguridad intrnseca y
de color azul claro para las seales con seguridad intrnseca resistente a la propagacin de incendios y a
la luz solar, con cuerda de nylon de desgarre.
3.8 2-Wire Cable for instruments with discrete output signal of 24VDC: (Gauge 14 AWG) must be of
"CT" type, 600 Volt, 75C in wet environment and 90C in Dry environment, Primary PVC-Nylon Insulator,
for the reference of the color code, must see "Insulated Cable Engineers Association" (ICEA) S-73-532
Standard for control Cables (NEMA WCST) table N E2, for the identification of Positive (+) and Negative () and (c), without a protective shield and protective cover of PVC cable in Black color for non-intrinsically
safe signals and the Light blue color for intrinsically safe signals, with fire resistance and sunlight, with a
nylon rope for tearing.
3.9 Cable de (4, 8, 12 y 24 conductores) cal. 16 AWG debe ser tipo TC, 600 V, 75 C en ambiente
mojado y 90C en ambiente seco, aislamiento primario de PVC -nylon, para referencia del cdigo de color
ver Insulated Cable Engineers Association (ICEA) S-73-532 Estndar for Control Cables (NEMA WCST)
tabla E para identificacin del (+) y (-),, sin pantalla protectora y cubierta protectora, del cable de PVC de
color; negro para seales sin seguridad intrnseca y de color azul claro para las seales con seguridad
intrnseca resistente a la propagacin de incendios y a la luz solar, con cuerda de nylon de desgarre
3.9 Cable: (with 4, 8, 12 and 24 wires of 16 AWG Gauge) must be of "CT" type, 600 Volt, 75C in wet
environment and 90C in Dry environment, Primary PVC-Nylon Insulator, for the reference of the color
code, must see "Insulated Cable Engineers Association" (ICEA) S-73-532 Standard for control Cables
(NEMA WCST) table E, for the identification of Positive (+) and Negative (-) and (c), without a protective
shield and protective cover of PVC cable in Black color for non-intrinsically safe signals and the Light blue
color for intrinsically safe signals, with fire resistance and sunlight, with a nylon rope for tearing.
3.10 Alambre de extensin para termopar tipo K calibre 16 AWG tipo PLTC/ITC +con aislamiento de
PVC, un par trenzado, debe ser con pantalla de aluminio y cable de dren de cobre, con blindaje de malla
metlica trenzada para proteccin contra campos electromagnticos, con cubierta de PVC de color
amarillo resistente a la propagacin de incendios, temperatura de operacin 105 C, con cuerda nylon de
desgarre.
3.10 Extension wire for "K" Type Thermocouple: (16 AWG Gauge) must be of "PLTC/ITC" type with
Primary PVC Insulator, 105C, Twisted-Pair, with a protective shield made in aluminum, drainage copper
cable, with shielded metal mesh, twisted for protection against electromagnetic fields, protective cover of
PVC cable in Yellow color, with fire resistance and sunlight, with a nylon rope for tearing.
3.11 Cable para Alimentacin elctrica a Equipos de Sistemas Control
Para la alimentacin elctrica a equipos de 127 VCA se debe seguir lo indicado en la norma de referencia
NRF-048-PEMEX-2014 Diseo de instalaciones elctricas en plantas industriales. Cable monopolar
calibre 12 AWG ser tipo THWN, 600 V, 75C, aislamiento PVC, de color Negro (Fase), Blanco (Neutro) y
Verde (Tierra).

Pag. 6 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

3.11 Cable for electrical supply of Control Systems Equipments


For the power supply to equipments at 127 VAC must follow the indicated in the reference norm NRF-048PEMEX-2015 Diseo de Instalaciones elctricas en plantas industrials (Design of electrical installation in
Industrial Plants). Monopolar Cable schedule 12 AWG shall be THWN type, 600V, 75 C, with PVC
insulation in black color (phase), white (neutral) and green (ground).
3.12 Cable para Seales Discretas (120 VCA) de Arranque-Paro de Bombas.
Para conducir seales discretas (120 VCA), usar multiconductor de 2 hilos de cobre suave calibre 12
AWG, con aislamiento de PVC y cubierta de nylon, tipo THWN, 600 V y 75 C.
3.12 Cable for discrete signals (120 VAC) for start-stop of pumps.
To conduce discrete signals (120 VAC), use multi-conductor two soft copper wired schedule 12 AWG, with
PVC insulation and nylon cover, THWN type, 600 V and 75 C.
3.13 Cable para seal audio formado por un par trenzado de conductores de cobre estaado tipo
PLTC/ITC calibre 18 AWG con aislamiento de PVC de 300 V, 105 C en color blanco y negro con
pantalla metlica con hilo de dren de cobre estaado y cordn de desgarre, cubierta exterior de PVC
resistente a la humedad, a la luz del sol y a la propagacin del fuego.
3.13 Cable for audio signal formed by a twisted pair of stained copper conductors PLTC/ITC type,
schedule 18 AWG with PVC insulation of 300 V, 105 C in black and white color with metallic shield, drain
wire of stained copper and rope for tearing, exterior cover of PVC Moisture proof, sunlight proof and
against fire propagation.
3.14 Cable multiconductor de 2 conductores son pantalla aislamiento ignifugo 30 min cal 14 y 16 para
vlvulas VAAR.
3.14 Multi-conductor of two conductors Are a fireproof insulation by 30 min, schedule 14 and 16 for
VAAR valves.
3.15 Cable de comunicacin serial (RS-485) 2 pares trenzados, calibre 22 AWG, rgimen 300 V, 60C,
aislamiento primario de Polietileno con pantalla protectora de aluminio mylar total trenzado y pantalla de
cobre estaado cobertura parcial , alambre de dren y cubierta protectora del cable de PVC y cuerda de
Nylon de desgarre.
3.15 Serial Communication Cable (RS-485): (22 AWG Gauge) 2 Twisted Pairs, 300 Volt, 60 C,
Polyethylene Insulation with a protective twisted shield made in aluminum total mylar and a partial cover of
a Tinned copper shield, drainage cable, protective PVC cover and a nylon rope for tearing.
3.16 Cable de comunicacin Ethernet cable tipo 5e o 6 4 pares trenzados (8 conductores sin pantalla)
calibre , 24 AWG, rgimen 300 V, 105C, aislamiento primario de PVC y cubierta protectora del cable de
PVC y cuerda de Nylon de desgarre.
3.16 Ethernet Communication Cable: "5e or 6" Type, 4 Twisted pairs (8 wires non-shielded), 24 AWG
Cable, 300 Volt, 105 C, Primary PVC Insulator and protective PVC cable cover and a nylon rope for
tearing.
3.17 El cable de instrumentacin debe ser diseado para operar satisfactoriamente en lugares hmedos y
secos.
3.17 The instrumentation cable must be designed to operate satisfactorily in wet and dry locations.

Pag. 7 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

3.18 El cable de instrumentacin debe ser adecuado para instalaciones internas o externas sobre
charolas, bancos de ductos subterrneos y tubo conduit. Cuando se instale en exteriores, el cable de
instrumentacin podra ser expuesto a la luz solar, lluvia y polvo, por lo que debe ser resistente a la
humedad, abrasin, rayos UV y retardante a la flama.
3.18 The instrumentation cable must be the suitable for internal and external facilities in wire trays,
underground ducts and conduit pipe. When installed outdoors, the instrumentation cable might be exposed
to sunlight, rain and dust, and have to be resistant to moisture, abrasion and fire retardant.
3.19 Tamaos y longitudes y otros requerimientos especficos de los cables deben indicarse en la solicitud
de compra y/u orden de pedido.
3.19 Size, Length and other specific requirements of the cable must be indicated in the purchase request
or the purchase order.
3.20 Los cables de instrumentacin deben cumplir con UL Subject 1581 "Standard For Safety Reference
For Electrical Wires, Cables and Flexibles Cords.
3.20 The instrumentation cable must comply with UL Subject 1581 "Standard For Safety Reference For
Electrical Wires, Cables and Flexible Cords".
3.21 El conductor de alambre ser de aleacin de cobre desnudo, 7 hilos concntricos de acuerdo a
ASTM B-3 "Standard Specification For Soft or Annealed Copper Wire", calibre 16 AWG, para pares /
tradas simples. Para Cables multipares / multitradas.se requiere de calibre 18AWG:
3.21 The wire conductor must be of bare copper alloy, 7-wire, concentrics in accordance with ASTM B-3
"Standard Specification for Soft or Annealed Copper wire", 16 AWG, for pairs or simple triads. For multipair cables or multi-triads it is required in Gauge 18 AWG.
3.22 En la orden de compra debe especificarse que los conductores sern continuos en toda la longitud de
un carrete o bobina. Las bobinas que presenten cualquier empalme en los conductores sern totalmente
rechazadas.
3.22 In the purchase order must specify that the conductors will be continous in all the length of the reel or
coil. The coils that have splices in the conductors will be completely rejected.
3.23 El aislante debe ser de PVC (Polyvinyl chloride) retardante a la flama.
3.23 The insulator must be of PVC (Polyvinyl Chloride) and flame retardant.
3.24 Las capas de trenzado para los Cables par simple y Cables multipar deben ser escalonadas cada 2
pulgadas mximo.
3.24 The twisted layers for simple pair cables and multi-pair cables must be staggered each 2 inches
maximum.
3.25 El cable de drenado para Pares / Tradas multipares y multitriadas debe ser calibre 22 AWG, 7 hilos
en conductor de cobre.
3.25 The drainage cable for pairs, triads or multi-pair and multi-triads cables must be of Gauge 22 AWG
and 7-wires in copper conductors.

Pag. 8 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

3.26 En las intercapas de los cables multipares deben usarse rellenos de material retardador de fuego y
material resistente a la humedad cuando sea necesario para dar al cable completo una seccin
transversal totalmente circular.
3.26 In the interlayers of the multi-pair cables must use fillings of fire retardant material and moisture
resistant when it is necessary, with the purpose to give to the cable a complete circular cross section.
3.27 Una cinta de polmero no higroscpico debe servir como un blindaje con una cinta de pantalla de
aluminio aplicada sobre el blindaje. La cinta de polmero y la cinta de pantalla de aluminio deben ser
aplicadas elpticamente con al menos 25 por ciento de traslape sobre el cable multipar completo. La cinta
de polmero debe servir para conservar los rellenos en su sitio. La pantalla general de aluminio debe estar
en contacto continuo con el alambre general de drenado
3.27 A polymer tape non-hygroscopic must work as shielding with an aluminum shield tape applied on the
shield. The polymer tape and the aluminum shield must be applied elliptically with at least 25% of overlap
in all the multi-pair cable. The polymer tape must work to keep the fills in its place. The aluminum general
sshield must be in continuous contact with the general drainage wire.
3.28 El cable de instrumentacin debe tener un forro de polivinilo (PVC), retardador de fuego resistente a
la humedad y a la luz solar incluye cuerda nylon de desgarre.
3.28 The instrumentation cable must have a PVC cover, fire retardant and resistant to moisture, sunlight
and with a nylon rope for tearing.
3.29 Cada multipar/multitriada debe ser numerado secuencialmente, para el caso de los multiconductores
es por codificacin de colores en base a la ICEA.
3.29 Each multi-pair or multi-triad must be sequentially numbered, in case of the multi-conductors is by
colors code based on the ICEA.
3.30 Para referencias al cdigo de color, ver "Insulated Cable Engineers Association" (ICEA) S-73-532
Standard for control Cables (NEMA WC57) tabla E5).
3.30 For the color code references, must see "Insulated Cable Engineers Association" (ICEA) S-73-532
Standard for control cables (NEMA WC57) Table E5.
3.31 La siguiente informacin como mnimo debe ser impresa de manera clara y permanente, en la
superficie del forro a intervalos regulares sin exceder 24 pulgadas sobre toda la longitud del cable:
a) Tamao del conductor
b) Numero de parte
c) Numero de pares /triadas
d) Clase de voltaje
e) Tipo de aislamiento
f) Rango de temperatura
g) Nombre del fabricante
h) Marcado que indique la clase UL
i) Marcas secuenciales de la cantidad de cable instalada o restante footage
3.31 The following information at minimum must be printed in a permanent and clear way in the surface of
the cover, in regular spaces without exceed 24 inches of all the cable length:
a)Wire size.

Pag. 9 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

b)Part Number.
c)Number of pairs or triads.
d)Voltage Class.
e)Insulation Type.
f)Temperature Range.
g)Name of the manufacturer.
h)Marking that indicates the UL class.
i)Sequential marks of the installed quantity of cable or remaining. "footage".
4.0 REQUERIMIENTOS DE EMPAQUE Y EMBARQUE
4.0 REQUIREMENTS OF PACKAGE AND SHIPPING
4.1 Todos los cables de instrumentos incluidos en esta especificacin deben ser empacados y rgidamente
reforzados para protegerlos de la intemperie y de daos durante su manejo y almacenamiento exterior.
4.1 All instrument cables included in this specification must be packed and reinforced for their protection
from weather and damages during its handling and storage.
4.2 Cada extremo del cable debe ser suministrado con un sello ajustado de agua para prevenir la entrada
de humedad durante el trnsito o almacenaje en exteriores. El extremo interno del cable debe ser
proyectado a travs del carrete para que el cable pueda ser probado en el carrete en el sitio de trabajo.
4.2 Each ending must be supplied with adjusted water seal to prevent the moisture during the transit or
exterior storage. The inner end of the cable must me projected trough the reel with the purpose of the
cable testing on site.
4.3 Una placa de metal resistente al ambiente debe estar firmemente colocada a cada extremo del carrete,
conteniendo la siguiente informacin:
a) Nmero de orden
b) Nmero de carrete asignado
c) Nombre del fabricante
d) Clase de voltaje
e) Tipo de aislamiento
f) Rango de temperatura
g) Tamao del conductor
h) Nmero de pares en el cable
i) Longitud de cable en el carrete
4.3 A metal nameplate, resistant to the weather must be attached firmly to each end of the reel, with the
following information:
a) Order No.
b) Assigned Reel No.
c) Manufacturers name
d) Voltage class
e) Insulation type
f) Temperature range
g) Conductor size
h) Pairs no.
i) Cable length in the reel

Pag. 10 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

4.4 Todos los carretes debern resistir su manejo y transporte a la planta de forma que lleguen en perfecto
estado para operar. (Deber considerarse que el periodo de embarque y transporte ser durante la poca
de lluvia por lo que los empaques debern resistir la humedad y el agua de lluvia.
4.4 All reels must resist its handling and transport to the plant, in that way to be delivered in perfect
conditions to operate. (must consider that the shipping time and transportation shall be during rainy
season, that is the reason of the package must resist moisture and water).
4.5 En proveedor deber notificar a ICA Fluor, por escrito con 30 das de anticipacin la llegada de los
carretes de los cables al sitio de instalacin.
4.5 Vendor must notify to ICA Fluor, written with 30 day of anticipation the arrive of the cable reels to the
installation place.
5.0 INFORMACIN DEL FABRICANTE
El fabricante debe entregar con los cables:
a) El proveedor debe garantizar por escrito que los cables amparados por la presente especificacin son
nuevos y estn libres de defectos de fabricacin
b) Certificados de Calidad de los cables.
c) Dossier de calidad.
d) Especificacin completa del cable.
e) Rango de temperatura.
f) Dimetro del cable con su forro.
g) Espesor del forro general.
h) Peso por unidad de longitud del cable.
i) Mxima longitud de empaque en el mayor carrete estndar.
j) Literatura tcnica de descripcin del cable.
k) Mxima tensin permitida de estiramiento tanto para el accesorio para jalar el cable con ojillopulling
eye como mtodo de fijacin del cable.
l) Mximo radio de curvatura permitido para el cable completo.
m) Copia de los reportes de prueba certificadas para cada carrete de cable que deben ser enviadas a ICA
Fluor, quien las entregar a PEMEX REFINACION.
n) Instrucciones de terminacin y empalme.
o) Lista de recomendaciones de lubricantes para el jalado de cables a travs de tubera.
p) Hoja de especificaciones de cada tipo de cable suministrado con cumplimiento normativos (UL, IEC,
etc.) y caractersticas fsicas y elctricas.
5.0 INFORMATION BY PROVIDES
Provider must deliver with the cables:
a) Provider must guarantee written that the cables covered by this specification are new and free of defects
b) Quality certificates of the cables
c) Quality Dossier
d) Complete specification of the cable
e) Temperature range
f) Diameter of the cable with its coating
g) General coating Thickness
h) Weight by unit of length of the cable
i) Maximum length of packing in the bigger standard reel
j) Technical literature of cable description

Pag. 11 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

k) Maximum allowed stress for both, the accesorie to pull the cable (pulling eye) and the method of cable
fastening.
l) Maximum curvature ratio allowed for the complete cable
m) Copy of the certified test reports for each cable reel that must be sent to ICA Fluor, who is delivering to
PEMEX Refinacin.
n) Instructions for termination and coupling.
o) Recommendation list of lubricants for the cable pulling trough the pipe.
p) Data sheets of each supplied cable type with regulations compliance (UL, IEC etc.) and physical and
electrical characteristics.
6.0 INSPECCIN Y PRUEBAS
6.0 INSPECTIONS AND TESTS
6.1. El fabricante debe contar con personal calificado para la inspeccin. Todos los cables sern probados
en fbrica por el fabricante para asegurar que han sido fabricados de acuerdo con esta especificacin y
los estndares aplicables.
6.1. The manufacturer should have qualified personnel for inspection. All cables will be tested at the factory
by the manufacturer to ensure that products are manufactured in accordance with this specification and
applicable standards.
6.2. Todos los cables sern suministrados estrictamente con los materiales mencionados.
6.2. All cables will be supplied strictly with these materials
6.3. La informacin suministrada al proveedor en esta especificacin, no lo releva de la responsabilidad de
suministrar el cable que satisfaga las condiciones de operacin mencionada en dicha especificacin.
6.3. The information provided to the supplier in this specification does not relieve you of the responsibility
to provide the cable that meets the operating conditions mentioned in the specification.
6.4. El cable de instrumentos estar garantizado por el proveedor contra cualquier defecto de fabricacin
en sus materiales, componentes y/o mano de obra por un periodo de 24 meses despus de la fecha de
embarque, o 12 meses despus de la puesta en operacin, lo que ocurra primero. Cualquier problema
operativo y/o dao causado al suministro, originado por deficiencias en materiales, y/o mano de obra
deber ser inmediatamente reparado por el proveedor sin costo alguno para el comprador y/o usuario
final.
6.4. The instrument cable will be guaranteed by the supplier against manufacturing defects in materials,
components and / or workmanship for a period of 24 months after the date of shipment, or 12 months after
start-up, which whichever comes first. Any operating problems and / or damage to the supply, caused by
deficiencies in materials and / or workmanship will be repaired immediately by the supplier at no cost to the
purchaser and / or end user.
6.5. Todos los cables sern probados de acuerdo a los estndares ICEA con certificaciones UL, se deber
entregar documentos de las pruebas efectuadas en fbrica.
6.5. All cables will be tested according to UL standards ICEA certifications, documents must be delivered
testing in the factory.

Pag. 12 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

6.6. El proveedor deber suministrar los certificados de calidad que garanticen la fabricacin,
componentes y materiales de acuerdo a esta especificacin.
6.6. The supplier must provide certificates guaranteeing quality manufacturing, components and materials
according to this specification.
6.7. PEMEX Refinacin se reserva el derecho de participar en las actividades de verificacin y / o
atestiguamiento de inspeccin en cualquier etapa de fabricacin y no debe ser obstculo para continuar
con los programas de manufactura, ni relevar sus responsabilidades a ICA Fluor o al fabricante, con
relacin a los eventos de calidad durante la manufactura.
6.7. PEMEX Refinacin reserves the right to participate in verification activities and / or witnessing
inspection at all stages of production and should not be an obstacle to continue manufacturing programs,
nor relieve their responsibilities or manufacturer ICA Fluor, relative to quality events during manufacture.

Pag. 13 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

7.0 TABLAS DE POLARIDAD

Pag. 14 de 15

AQ1ART01F02 Rev. 1
Cdigo de Distribucin: O002

PEMEX Refinacin
Aprovechamiento de Residuales Ref. Miguel Hgo.
No. Proyecto 7414
No. Boletn de trabajo JB ART 115

Revision 1

7.0 POLARITY CHART


No

Signal type

Cable type

Conductors type

4-20 mA,
4-20 mA+hart

1 Twisted Pair, 16
AWG

2 conductors +
shield

4-20 mA

1 Twisted Triad, 16
AWG

3 conductors +shield

4-20 mA,
4-20 mA+HART

Multipair of
4/8/12/24/36 twisted
pair, 18 AWG

Each pair contains 2


conductors +
individual shield and
+ general shield

4-20 mA,
4-20 mA+HART

Multitriad of 4/8/12
Twisted triad, 18
AWG

Each triad contains


3 conductors +
individual shield +
general shield

Foundation
Fieldbus

1 Pair, 18 AWG

2 conductors +
shield

Discrete (24
VDC)

Multiconductor of 2
conductors, 16 AWG

2 conductors

Discrete (24
VDC)

Multiconductor of 2
conductors, 14 AWG

2 conductors

Discrete (24
VDC)

Multiconductor of
4/8/12/24
conductors, 16 AWG

4/8/12/24
conductors

Multiconductor of 2
conductors, 12 AWG

2 conductors

Multiconductor of 3
conductors, 12 AWG

3 conductors

9
10
Notes:
1.
2.

Discrete (120
VAC)
Power supply to
Control Systems
(120 VAC)

Base color of
conductor
Black
White
Black
White
Red
(Note 2)
Black
White
Black
White
Black
White
(Note 2)
Black
White
Red
Black
White
Red
(Note 2)
Orange
Blue
Black
Red
(Note 1)
Black
Red
(Note 1)
Black
Red
Blue
Orange
(Note 1)
Black
Red
Black
White
Green

Exterior cover
color

Polarity

Black PVC

Black (+)
White (-)

Black PVC

Black (+) Triad 1


White (-) Triad 1
Red (S) Triad 1

Black PVC

Black PVC

Orange PVC

Black (+) Pair 1


White (-) Pair 1
Black (+) Pair 2
White (-) Pair 2
Black (+) Pair 3
White (-) Pair 3
Etc.
Black (+) Triad 1
White (-) Triad 1
Red (S) Triad 1
Black (+) Triad 2
White (-) Triad 2
Red (S) Triad 2
Etc.
Oranje (+)
Blue (-)

Black PVC

Black (+)
Red (-)

Black PVC

Black (+)
Red (-)

Black PVC

Black PVC
Black PVC

Black (+) c1
Red (-) c2
Blue (+) c3
Orange (-) c4
Black
Red
Black (Phase)
White (Neutral)
Green (Ground)

Colors according to chart E-2 from NEMA WC 57


Colors according to chart E-1 from NEMA WC 57
Chart 1. Polarity and Colors for Cable of Instruments

END OF DOCUMENT