2 Installation
The sensor tip must be completely immersed in the medium.
In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).
- When the unit is to be mounted at the bottom of the pipe, it should be free
from deposits.
- When the unit is to be mounted at the top of the pipe, it should be completely
filled with the medium to be monitored.
In the case of vertical pipes mount the unit in a place where the medium flows
upwards (fig. 2).
fig. 1
A
B
A = 15 mm for units with M12 x 1 and 1/4" thread
A = 23 mm for units with 1/2" thread.
B = packing washer
fig. 2
A
fig. 3
B
min.
3xD
min.
5xD
UK
A
3 Electrical connection
The unit must only be mounted by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply for units up to 60 V to EN50178, SELV, PELV.
Disconnect power.
Connect the unit (wiring: see type label).
4 Adjustment
1 setting potentiometer
sensitivity
2 chain of LEDs
Apply the operating voltage. Switch on the flow (preset value) and keep it
constant.
> The yellow LED lights; the output is switched for about 20 s (power-on delay
time).
Turn the pot until one green LED comes on. The farther the green LED is
away from the yellow LED, the safer is the adjustment (excess gain for flow or
temperature fluctuations).
Conceal the pot after adjustment by the label provided to protect it against
unauthorised tampering.
5 Operation
After mounting, wiring and setting check whether the unit operates correctly.
Recommended maintenance
Check the sensor tip for build-up from time to time. Clean it with a soft cloth. If
necessary, build-up which adheres firmly (e.g. lime) can be removed with a common vinegar cleansing agent.
The units are suitable for use in moderate electromagnetic fields (see table).
When operating ISM equipment or powerful walkie-talkies in the vicinity of the
units additional measures to avoid malfunction can be required.
Noise immunity
ESD
HF radiated
Burst
HF conducted
Standard
IEC 1000-4-2 /
EN 61000-4-2
IEC 1000-4-3 /
EN 61000-4-3
IEC 1000-4-4 /
EN 61000-4-4
IEC 1000-4-6 /
EN 61000-4-6
Severity level
4 kV CD / 8 kV AD
3 V/m; 80 ... 1000 MHz
2 kV coupling pliers