Академический Документы
Профессиональный Документы
Культура Документы
MT3250E rev.0
14/06/2012
pag. 1 of 93
Technical Manual
MULTISCAN++PK
Warning
THIS MANUAL MUST BE CAREFULLY READ BY ALL PERSONS WHO HAVE OR
WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS
PRODUCT.
Like any equipment, this product will perform as designed only if installed, used and
serviced in accordance with the manufacturers instructions. OTHERWISE, IT COULD
FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT
FOR THEIR SAFETY COULD SUFFER SEVERE PERSONAL INJURY OR DEATH.
The warranties made by Sensitron s.r.l. with respect to this product are voided if the
product is not installed, used and serviced in accordance with the instructions in this
user guide. Please protect yourself and others by following them.
We recommend our customers to write or call regarding this equipment prior to use or
for any additional information relative to use or repair.
MT3250E rev.0
14/06/2012
pag. 2 of 93
Technical Manual
MULTISCAN++PK
INDEX
1)
INTRODUCTION................................................................................................................................... 5
1.1)
2)
3)
4)
14/06/2012
pag. 3 of 93
5)
MT3250E rev.0
14/06/2012
pag. 4 of 93
1)
INTRODUCTION
The gas detection system for car parks SPS consists of MULTISCAN++Park control
panels and SMART-P gas detectors, purposely designed to satisfy the European norm
EN50545-1
The MULTISCAN++Park control panels can manage and monitor up to 256 gas detectors
These can either be addressable detectors (Smart P), daisy chained on the available
loops, or analog type with 4-20mA transmission, connected via remote 8 input cards
STG/IN8-PK.
Three alarm thresholds can be set for each gas detector being connected and the panels
allow alarms to be time averaged in a period adjustable from 5 to 60 minutes for
thresholds 1 and 2; for the third threshold, alarm is to be triggered when the concentration
is exceeded for a time longer than1 minute (adjustable up to >5 minutes).
The panels come complete with 8 preset relays onboard the units. The system architecture
also allows having outputs extended up to 256 via remote 16 output cards STG/OUT16-S
and 8-relays boards. The panels are available in 19 3U rack (24Vdc power supply) or in a
metal box complete with power supply.
1.1)
16 O/C
(3)
LOOP 1
(5)
(2)
LOOP 2
LOOP 3
(4)
(4)
(1)
OPZIONALI
(OPTIONAL)
LOOP 4
CONTROL PANEL
(MULTISCAN ++ PK)
(6)
(1) RILEVATORI GAS ANALOGICI 4-20 mA / 4-20 mA ANALOG GAS DETECTORS
(2) MODULO 8 INGRESSI ANALOGICI ST.G/IN8PK / ANALOG 8 INPUT MODULE
ST.G/IN8PK
(3) CAVO 2 FILI TWISTATI PER Rs485 + 2 FILI PER ALIMENTAZIONE (12-24 Vdc) /
2 TWISTED WIRES FOR THE Rs485 BUS + 2 WIRES FOR THE POWER SUPPLY (12-24 Vdc)
(4) RILEVATORI GAS CON USCITA SERIALE Rs485 / GAS DETECTORS WITH Rs485 OUTPUTS
(5) MODULO 16 USCITE O/C ST.G/OUT16PK / 16 O/C OUTPUTS MODULE ST.G/OUT16PK
(6) MODULO 8 RELE ST.G/8REL / 8 RELE ST
.G/8REL MODULE
2)
SMART P are available in the following versions, according to the gas to be detected:
CO, range 0-300 ppm, industrial grade 3-pin cell.
NO2, range 0-30 ppm, industrial grade 3-pin cell
To optimize the installation costs, double sensor detectors have been developed,. These
consist of a CO and NO2 sensors combined in the same housing.
The first sensor detecting gas, will provide the corresponding signal to the control panel.
SMART P employ high performance sensors and provide a periodic check to verify all
functions correctness as well as dedicate self test of the CO cell accuracy.
SMART P detectors are to be connected via a 4-core wire: 2 wires for power supply and 2
for RS485 data communication to the MULTISCAN++PARK.
MT3250E rev.0
14/06/2012
pag. 5 of 93
SMART P allow a rapid and safe installation along with an easy maintenance and field
calibration via the calibration keypad STS/CKD-PK.
Detectors require a 12-24 Vdc power supply and are delivered in a metal box rated to
IP55.
SMART P-1 detectors for Carbon Monoxide or Nitrogen Dioxide
CODICE
DESCRIZIONE
S2398CO
S2399ND
IMMAGINE
DESCRIZIONE
S2400CO-ND
2.1)
IMMAGINE
Typical use
Detectable gases
Sensor employed
Power supply
Proportional output
Consumption at 12-24Vdc
Repeatability
Storage temp.
Operating temp.
Relative humidity
IP rating
Weight
Dimensions
Sensor expected lifetime
Approvals
MT3250E rev.0
pag. 6 of 93
2.2)
At the mounting and installation phase be sure all safety precautions have been
considered.
Always consider how important it is the correct positioning of gas detectors to get the
optimum response. Be careful never to install gas detectors close to air intakes or fans
causing strong air currents.
Be sure the detectors are attached to a firm base to prevent vibration that can damage
them, producing unreliable results.
Although the electronics comply with the electromagnetic compatibility rules, it is advised
to keep the detectors at a distance from any radio frequency senders (such as radio links
or similar).
Please be also sure that detectors are placed in a convenient location for future
maintenance and calibration requirements.
Carbon monoxide and Nitrogen Dioxide, having a specific weight approximately equal
to air's should be detected at breathing level, and the detector should be at approximately
1.50m above the floor to get a reliable protection.
The gas detector is always to be mounted with the sensing element placed downward.
For no reasons at all the enclosure can be drilled.
Wall mount the detectors by employing the existing holes
Al rilevatore successivo
to the next detector
Fixing
hole
11
4
MT3250E rev.0
14/06/2012
pag. 7 of 93
MT3250E rev.0
14/06/2012
Testa sensore 1 (E.C. Cella Elettrochimica)
S1
A
B
S2
+
-
Jp7 collegamento
tastiera calibrazione
Morsettiera collegamento
2.3)
Smart P gas detector circuit layout
pag. 8 of 93
2.4)
Electric wiring
The connection of SMART3G to RS485 bus lines should be performed by using a 4-wire
cable, 1 pair for the RS485 bus and 1 for the power supply.
Wiring between the detectors and the control panel should be made by using connection
cable EIA RS485: 2 core wires with section 0.22 / 0.35 mm2 and shield (twisted pair).
Nominal capacity between the wires <50pF/m, nominal impedance 120 ohm.
These features can be found in BELDEN cable 9842 or similar (data transmission cable in
EIA RS485).
Using this wiring, the total length of the line should not exceed m 1000.
Detectors and output modules are to be wired in daisy chain mode. We recommend
avoiding star or tree mode connection as interference immunity would be reduced.
Make sure that a 120 Ohm end line resistor is placed at the beginning and at the end (on
the last detector or output module) of the bus line.
For the detectors' power supply connection we recommend to use a 2-wire cable with
suitable section according to the distance and number of detectors.
Once the installation has been completed, verify that each detector reaches at least 12
Vdc.
B
A
Dalla centrale
From the control panel
A
-
S1
+
-
Detector
A
B
S2
S1
A
B
S2
+
-
Detector
B
A
+AB -
S1
+
-
A
B
S2
ST.G/OUT16 module
Detector
MT3250E rev.0
14/06/2012
pag. 9 of 93
2.5)
Detector power ON
When the detector is powered on, the green LED DL1 on the motherboard starts blinking
at slow intermittence.
After nearly two minutes, the red LED flash rate is equivalent to the detector working
status (see table below).
Once the warm-up phase is over, the detector can work correctly, although the optimal
performances will be achieved after two hours.
2.6)
LED DL1 (green) shows the detector's operative status (mS= milliseconds)
Warm-Up
Fault low
Lit fixed
Allarm 1
Allarm 2
Allarm 3
Fault high
Normal status
2.7)
Smart P gas detectors offer a field adjustment for the Zero, Span (response to gas) and
the serial address (for the RS485 loop).
By operating with the handheld calibration keypad, pressing ENTER, ESC, Arrow UP and
Arrow DOWN, the Zero, Span and serial Address shall be accomplished.
The keypad can be connected when the detector is powered ON and operating. Before
opening the detector enclosure, be sure all safety precautions have been considered.
Insert the female connector of the keypad at the edge of the flat cable into the male
connector on the Smart P main board.
Once connected, the keypad will display the gas concentration being measured.
Adjustments are required whenever either Fault or unjustified Alarms due to environmental
conditions occur (Zero adjustment) or detectors need modifying their response to gas
(Span adjustment).
Span adjustment requires a calibrated gas cylinder, either filled with the same gas the
detector has been calibrated for or a reference gas advised by the manufacturer
For the Zero adjustment, gas detectors are to be in fresh air (without any gas or interfering
compounds) and powered on since 8 hours at least.
Once the routine is over a test with gas is to be made to verify the right working condition.
MT3250E rev.0
14/06/2012
pag. 10 of 93
S1
A
B
S2
+
-
KEYPAD
MT3250E rev.0
14/06/2012
pag. 11 of 93
ESC
0,0
ENT
ZERO
SPAN
ENT
ENT
0,0
0,0
rES
ENT
WAIT
VER
ENT
0,12
ADR
ENT
001
MT3250E rev.0
14/06/2012
pag. 12 of 93
cap can be fitted on all of Sensitron sensing heads by employing, when necessary, the
endowed adaptors.
Both gaskets and screw threads inside the cap allow an optimum tightness between the
sensing head and the cap. The analysis chamber inside the calibration cap has been
designed and realized to obtain a test method identical to that adopted in our laboratory for
the initial factory calibration.
The valve complete with flow meter is to be mounted on the gas can to allow a gas outlet
at a controlled velocity to obtain accurate data to verify the sensing element status.
rES Reset
Reset of Fault status
VER Version
Detector firmware version
ADR Address
Address of detector for communicating to RS485 bus. Ex. 004
MT3250E rev.0
14/06/2012
pag. 13 of 93
0,0
ENT
SPAN
ZERO
rES
VER
ENT
ENT
ENT
WAIT
ZGL
ENT
000,0
0.0.12
ENT
DONE
SGL
200,0
FACT
YES
0,0
004
ENT
0,0
ADR
ENT
195,0
200,0
DONE
Fig. 2.7 c) Handheld keypad operation flow chart
MT3250E rev.0
14/06/2012
pag. 14 of 93
3)
This manual details the procedures required to install, program, operate, test and maintain
the MULTISCAN++PK gas detection unit.
3.1) Unit features
The MULTISCAN++PK is a gas detection control unit designed to meet the widest range of
flexibility required by the market.
The control panel is based on a powerful microprocessor which provides a wide range of selfdiagnostic procedures to detect and locate possible faults.
Extremely flexible and reliable, it can manage up to 256 gas detectors simultaneously. These can
be either of addressable type (Smart P), directly connected on buses, or 4-20mA analogical types
connected via 8-input STG/IN8-PK remote modules.
System architecture includes up to 256 Open Collector outputs, fully programmable, equipped with
STG/OUT16-S modules connected on RS485 buses. Up to 4 serial buses can be connected to the
unit.
Other MULTISCAN++PK panel features:
Event log can be displayed on the screen or downloaded to a PC.
RS232 serial port for PC connection for programming and control via specific software.
Parallel port for printer connection.
The control panels are sold in 2 different versions: housed in Metal cabinet or in a 19 3 units rack
(for the 19 rack version, the power supply has to be ordered separately).
(1)
16 O/C
(3)
LOOP 1
(5)
(2)
LOOP 2
LOOP 3
LOOP 4
(4)
(4)
(1)
OPZIONALI
(OPTIONAL)
CONTROL PANEL
(MULTISCAN ++ PK)
(6)
(1) RILEVATORI GAS ANALOGICI 4-20 mA / 4-20 mA ANALOG GAS DETECTORS
(2) MODULO 8 INGRESSI ANALOGICI ST.G/IN8 PK / ANALOG 8 INPUT MODULE
ST.G/IN8 PK
(3) CAVO 2 FILI TWISTATI PER Rs485 + 2 FILI PER ALIMENTAZIONE (12-24 Vdc) /
2 TWISTED WIRES FOR THE Rs485 BUS + 2 WIRES FOR THE POWER SUPPLY (12-24 Vdc)
(4) RILEVATORI GAS SMART P / SMART P GAS DETECTORS
(5) MODULO 16 USCITE O/C ST.G/OUT16 S / 16 O/C OUTPUTS MODULE ST.G/OUT16 S
(6) MODULO 8 RELE ST.G/8REL / 8 RELE ST.G/8REL MODULE
MT3250E rev.0
14/06/2012
pag. 15 of 93
3.3)
Technical Specifications
Specifiche tecniche
Housing:
Inputs:
Outputs:
Contacts rating at
control panel and
optional ST.G/8REL
Serial Ports:
Network connection
Power Supply:
Consumption:
warm-up time
Display:
Visual indications:
Operating Temp.:
Storage Temp.:
Operating RH:
Storage RH:
Max 10 VA
To be set between 2 to 10 min. (default 3 min.)
Graphic Liquid Crystal Display (LCD)
Double 9 LED raw
0-55C
-20 +60 C
15-85%
5-85% (non condensing)
3.4)
Installation
For the box version, mount the panel using the four fastening holes on the back of the box.
MT3250E rev.0
14/06/2012
pag. 16 of 93
Connect the three-pole mains cable to the power supply board (minimum 1.5mm2 for each
pole) and secure using the wire clamps.
Power the system and then connect the power supply wires with red and black faston
crimps to the 2 x 12V 7Ah back up batteries, housing them in the panel near the power
supply.
CONTROL PANEL
INTERNAL VIEW
1234-
789101112-
MT3250E rev.0
14/06/2012
pag. 17 of 93
3.4.2)
JP33
JP35
D
D24
Jp51
D
D19
Jp48
Earth
F2
F1
Back panel
JP37
JP39
JP34
JP36
P2
JP38
JP40
P1
JP7
JP11
JP15
JP19
JP41
JP42
Jp41
Jp42
P1
P2
Jp19
D33
Earth
D30-33
C
NO
Jp37
NC
NC
C
NO
Jp35
Jp39
C
NO
Dl2
Dl4
Jp40
Dl7
Jp38
NC
NC
C
NO
Jp33
DL 1-8
Dl8
AB
AB
D31
Jp11
AB
A B
Jp15
Jp7
D30
Dl6
NO
Jp36
Jp34
F2
NO
NC
NC
C
NO
Dl1
JP51
Dl5
F1
NC
D32
JP48
D19
NC
C
NO
D24
MT3250E rev.0
14/06/2012
Legenda
Rel 1 per Fault di sistema / Relay
1 System Fault
Rel 2 programmabile /
programmable Relay 2
Rel 3 programmabile /
programmable Relay 3
Rel 4 programmabile /
programmable Relay 4
Rel 5 programmabile /
programmable Relay 5
Rel 6 programmabile /
programmable Relay 6
Rel 7 programmabile /
programmable Relay 7
Rel 8 programmabile /
programmable Relay 8
Bus RS485 connection 1
Bus RS485 connection 2
Bus RS485 connection 3
Bus RS485 connection 4
Ingressi digitali / Digital Inputs
Ingressi digitali / Digital Inputs
Porta parallela stampante
Printer parallel port
Porta seriale RS232 per PC
RS232 PC serial port
Connessione alimentazione (24Vcc)
Power supply connection (24 Vdc)
Fusibile alimentazione 1 (3,15A F)
Fuse first power supply (3,15A F)
Connessione di terra
Earth connection
LED indicazione attivazione rel
LED indicating relay activation
LED lampeggianti indicazione
comunicazione bus RS485
Flashing LED indicating the RS485
bus communication
LED indicazione alimentazione a
JP48
LED indicating the power supply at
JP48
LED indicazione alimentazione a
JP51
LED indicating the power supply at
JP48
pag. 18 of 93
3.4.3)
Power connections
Jp48
F1
D
D19
3,15 A
Jp51
F2
D
D24
3,15 A
27,4 Vdc
Earth
to JP41/JP42 circuit
P2
P1
Earth
select the
input voltage
110
220
100-120 Vac
200-240 Vac
3.4.4)
Jp41
- Jp48
F1
D2 D1
Jp42
Jp51
F2
D4 D3
P1
P2
Earth
Control unit back panel
Dallalimentatore
From the Power Supply
Al
To circ
th uit
ec o
on di c
tro on
l c tro
irc llo
uit
4 opto-isolated digital inputs are available on the back panel to be used as indicated in the
diagram below.
14/06/2012
pag. 19 of 93
3.4.5)
DIP-Switch setting for the communication bus, PC serial port and control
panel language
Communication (baud rate and protocol) for unit compatibility with various gas
detector versions and IN / OUT modules.
Communication (baud rate) of the RS232 serial port for the communication with the
PC
The D3 dip switch series is for set the language text of the control panel display.
Note: the dip switch state is acquired at the control panel switch ON
D2=switches
(see table below)
D3 switches: Control panel language
Sw4
ON
ON
ON
ON
Sw3
OFF
ON
ON
ON
Sw2
OFF
ON
OFF
OFF
Sw1
OFF
OFF
ON
OFF
Not use
d
(not to m
odify)
Language
English
Italian
Spanish
Portoguese
ON
ON
115.200
OFF
9.600
MT3250E rev.0
14/06/2012
pag. 20 of 93
Sw 3
Protocol
ON
ON
Galileo
OFF
ON
OFF
ON
OFF
OFF
Not to be used
Not to be used
Not to be used
Notes
Dip-switch 4 e 5: Communication (baud rate) of the RS232 serial port for the
communication with the PC
Sw 4
Sw 5
Baud Rate
ON
ON
9600 Bit/sec.
OFF
ON
19200 Bit/sec.
ON
OFF
38400 Bit/sec.
OFF
OFF
Function
ON
OFF
Normal position
14/06/2012
pag. 21 of 93
-) Detector power supply (and IN and OUT modules on the bus) must be connected with a
2-core wire with adequate section based on the number of connected devices, their
distance from the power supply and each devices consumption (please see the technical
manual enclosed with gas detectors for this purpose).
MULTISCAN++PK can support a maximum of 256 gas detectors. Gas detectors can be
divided on the bus lines provided that the maximum number of 128 detectors is not
exceeded on each bus line.
Each device connected to the RS485 buses must have a univocal address. See the table
on page 28 for STG/IN8-PK and STG/OUT16-S modules address setting. For gas
detectors, see the technical manuals for address setting.
Module/Sensor
ST.G/IN8-PK
ST.G/OUT16-S
SMART P
detectors
(directly
connected on
RS485 bus)
Bus 1
Bus 2
Bus 3
Bus 4
(optional)
(optional)
Address
1-255
Address
1-255
Address
1-255
Address
1-255
(247)
(247)
(247)
(247)
Address
1-255
Address
1-255
Address
1-255
Address
1-255
(247)
(247)
(247)
(247)
Address
1-256
Address
1-256
Address
1-256
Address
1-256
Note
Up to a maximum of 16 modules
per line and up to 32 maximum in
the system.
Up to a maximum of 8 modules
per line and up to 16 maximum in
the system.
Up to a maximum of 128 detectors
per line and up to 256 maximum in
the system.
NB.: STG/IN8 PK modules and SMART P detectors can be simultaneously connected on buses
but the total number of points must not exceed 256.
MT3250E rev.0
14/06/2012
pag. 22 of 93
Fig. 3.5.1 a
4-20 mA
analog
gas
detector
Negative
-V
B
A
+V
-V
I8
I7
I6
I5
+V
-V
I4
I3
I2
I1
+V
4-20 mA
signal
MODULO INGR.
4-20 mA ST/G.IN8
Positive
REMOTE INPUT
MODULE ST/G.IN8
Rilevatore
analogico
4-20 mA
The following diagram illustrates the connection on the loop of gas detectors and remote
IN/8 or OUT/16 modules to the control panel.
MT3250E rev.0
14/06/2012
pag. 23 of 93
MT3250E rev.0
14/06/2012
pag. 24 of 93
Jp7
Back panel
Loop4
Loop2
Jp19
Jp15
A B
Loop3
A B
A B
Jp11
Loop1
A B
Earth
Shield
Loop (Bus) 4
Loop (Bus) 2
Loop (Bus) 3
AB
Come Bus 1
As Bus 1
AB
IN/8 or OUT/16
module
AB
AB
AB
Al rilevatore o modulo
successivo
To the next detector
or module
Morsettiera rilevatori
(gas detector connections)
C hann e ls 5-8
-V
Chann e ls 1 -4
+V
+V -V
Jp1
Open
Jp 9
Open
Jp2
Open
Jp11
Open
Open
Jp3
O pen
Jp 12
Jp 4
Closed
Led
Commutatori rotativi
per lindirizzo del modulo
Rotary switches for
the module address)
B
A
MT3250E rev.0
14/06/2012
pag. 25 of 93
+V
Outputs 9-1 6
-V
+V -V
+V
Jp9
Open
Jp6
Open
Jp11
Closed
Jp7
Open
Jp1 2
Open
Jp 8
Open
Morsettiera alimentazione
e linea seriale
(Power supply and serial line)
Led
Jp5
MT3250E rev.0
14/06/2012
pag. 26 of 93
B
A
3.7.1)
The STG/8REL 8-relay expansion board converts STG/OUT16-S O/C outputs into voltage free
changeover contact. Up to two relay boards can be connected to each output module. A relay
board is directly connected to the output module (J1 connector) and a second relay board is
connected to the first.
Esempio collegamento
/ Connection example
3.7.2)
STG/IN8-PK and STG/OUT16-S modules are addressed using the two rotary switches in
RSW 1 and 2 hexadecimals (fig. 2.5). Rotary switches permit hexadecimal settings (base
16). Each switch as 16 positions (0-F) and the pointer is positioned on the number chosen
using a screwdriver to create a decimal value between 1 and 255 (see table 1). The
maximum number of modules that can be connected to the unit is:
Each module must have univocal address in the system. Dual addresses are not permitted
even if modules are on different serial buses.
MT3250E rev.0
14/06/2012
pag. 27 of 93
Esempio:
HEX
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
DEC
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
HEX
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
DEC
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
HEX
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
59
5A
5B
5C
5D
5E
5F
60
61
62
63
64
65
66
67
68
69
6A
DEC
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
HEX
70
71
72
73
74
75
76
77
78
79
7A
7B
7C
7D
7E
7F
80
81
82
83
84
85
86
87
88
89
8A
8B
8C
8D
8E
8F
DEC
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
HEX
95
96
97
98
99
9A
9B
9C
9D
9E
9F
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
AC
AD
AE
AF
B0
B1
B2
B3
B4
DEC
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
HEX
BA
BB
BC
BD
BE
BF
C0
C1
C2
C3
C4
C5
C6
C7
C8
C9
CA
CB
CC
CD
CE
CF
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
33
21
70
46
107
6B
144
90
181
B5
218
DA
34
35
36
37
22
23
24
25
71
72
73
74
47
48
49
4A
108
109
110
111
6C
6D
6E
6F
145
146
147
148
91
92
93
94
182
183
184
185
B6
B7
B8
B9
219
220
221
222
DB
DC
DD
DE
DEC
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248 (*)
249 (*)
250 (*)
251 (*)
252 (*)
253 (*)
254 (*)
255
(**)
(*) Indirizzi non disponibili con protocollo Modbus / not available addresses for the Modbus protocol
(**)Indirizzo non disponibile con protocollo Galileo / not available addresse for the Galileo protocol
MT3250E rev.0
14/06/2012
pag. 28 of 93
HEX
DF
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
EF
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
FE
FF
CHN 02001
Indirizzo modulo IN/8 o rilevatore gas
(Module IN/8 or detector address)
da 0 a 255 (from 0 to 255)
Posizione rilevatore da 01 a 08 se modulo
IN/8 oppure 00 se rilevatore collegato su bus
(detector position from 01 to 08 if IN/8
module or 00 is detector on the bus
Programming by PC
Fig. 3.8
MT3250E rev.0
PC Connection cable
14/06/2012
pag. 29 of 93
3.9)
Via an optional interface, to be connected to the RS232 port, it is possible to connect the
panel on a LAN/WAN network with TCP/IP protocol. By this type of connection, the
following features are possible:
Remote management of the control panel, via third parties supervising software, by
using the Modbus protocol
For technical features and use of TCP/IP module, please consult the product
documentation.
4)
The chapter explains the procedures for the operation, the commissioning and the
maintenance of the control unit MULTISCAN++PK
For the programming of the MULTISCAN++PK control panel the PC software is required.
Numerical
keypad
Display
Arrow
Keypad
Status
Led
MT3250E rev.0
14/06/2012
pag. 30 of 93
4.1)
Power ON
After ensuring correct installation of the MULTISCAN++PK, the unit can be switched on.
When first switched on, after the Warm Up time (3 minutes by default), the display will
show an empty picture without any indication because, at the first switch ON, the control
panel needs programming.
14/06/2012
pag. 31 of 93
4.2)
The LCD display provides the user with details about the various system states.
A few general rules apply at any level as follows:
Should there be a list displayed, the page scrolling can be done using the UP/DOWN arrow
keys. Once a selection is made by pressing the ENTER key the display will show a more
detailed view of that particular selection.
All the arrow keys, UP/DOWN, LEFT/RIGHT are being used also to move through the
parameter under change fields.
At any display level, the ESC key will switch back to the previous view. Pressing twice the
ESC key, you will go back to the main screen.
The same, at any display level, should no keys be pressed for more that 3 minutes, the
view will automatically switch back to the main window of the Normal mode.
14/06/2012
pag. 32 of 93
ALARM
The alarm condition will be activated according to the settings for each and every input:
The activation conditions can be user programmable, although for each detector type (in
effect each gas detected) a standard configuration is defined and loaded, when making the
settings of a stated input through the PC software.
Note on operations according to E50545 standard
Alarm 1 & 2 thresholds are activated if the gas value measured by the detector exceeds
an average concentration in the set time (Average Alarm Time).
Threshold 3 is immediately activated if the concentration value measured by the detector
exceeds the set alarm 3 value for a certain amount of time (Alarm 3 Persistence).
The system usually displays the average measured by the detector (except in Graph
mode where the real time value is displayed).
In the alarm window the following info is available:
MT3250E rev.0
14/06/2012
pag. 33 of 93
MT3250E rev.0
14/06/2012
pag. 34 of 93
under
The signals from channels under TEST will be displayed but will not be considered, in the
way that no alarm will be triggered even though the alarm thresholds are being exceeded.
In the same way, the relays under TEST will not be activated, even if an alarm event
associated is taking place while the relay is in TEST/MAINTENANCE mode.
EXCEPTION: In case the system just includes one channel only, it will be possible to put
that channel under test.
The same principle applies in the case when just one single output is defined. That output
can be put under test.
UNSET
The state is useful for virtually excluding single detectors or parts of the system, without
physically interrupting the connection.
The UNSET condition may be activated for each channel or part of the system.
In the same way as for TEST/MAINTENANCE mode, a user with OPERATOR or
MAINTENANCE level cannot UNSET more than 50% of the systems channels and relays.
The only exception is the ENGINEER level, which may UNSET the whole system if
necessary.
MT3250E rev.0
14/06/2012
pag. 35 of 93
EMERGENCY MODE
This is a special defined state into which the systems switches for the following two
situations:
1.malfunctioning of the control panel power supply
2. AC Fail (230 Vac or 110 Vac missed)
4.3)
User levels
The system offers three user levels and, depending on these, various options are
available. The three levels are as follows:
1. OPERATOR level (O)
2. MAINTENANCE level (M)
3. ENGINEER level (E)
Once logged in with a certain level, a letter in the top right side of the screen will inform
about the level chosen, as follows: O for Operator. M for Maintenance and E for
Engineer.
If the user is not logged in, the allowed operations are as per Operator level, without
permitting to do the ACK of the events.
The user passwords can be created and/modified just by the PC configuration software.
MT3250E rev.0
14/06/2012
pag. 36 of 93
MENU
2
4
5
LOGOUT
LOGIN
SYSTEM
gets the user into a sub menu (just for the Event Log, the
printer options and the System info)
logs out the active user
opens the login dialogue window
gets the user into a sub menu (just for a general viewing of
the system through the Zone, the Module and Detectors).
MT3250E rev.0
14/06/2012
pag. 37 of 93
MENU DETAILS
MENU
LOGOUT
LOGIN
SYSTEM
4.5)
gets the user into a sub menu (see the next chapter)
logs out the active user
opens the login dialogue window
gets the user into a sub menu (the available operations
depend on the User level).
1- MENU
In the main window in normal mode (without any user login), one may view the systems
configuration details, pressing the key 1 (MENU).
ACTIVE EVENTS (available just if some active event is present)
EVENT LOG
SYSTEM INFO
MT3250E rev.0
14/06/2012
pag. 38 of 93
Other sub-menus may be available, depending on the user login level, see the table below
Operator level (O)
EVENT LOG
EVENT LOG
EVENT LOG
ABORT PRINT
SYSTEM INFO
ABORT PRINT
ABORT PRINT
SYSTEM INFO
(*) available just if some active event is present
SYSTEM INFO
MT3250E rev.0
14/06/2012
pag. 39 of 93
14/06/2012
pag. 40 of 93
In this case by pressing 1 ACK the screen image will simply refresh and an X mark
will appear on the A column (the Acknowledged column)
2. the user is not yet logged in.
In this case the LOGIN dialogue window pops up and the user should key in the
password. After which the X mark will be shown under the A column of the related
active event.
Practically this is the only situation when the login of an Operator level user is
required so that a trace is being kept about the person who acknowledged the active
event.
RESET
Pressing 2 RESET with the cursor on the active event previously acknowledged (the one
marked with "X"), this will get reset and the event will disappear from the active events list.
As described above, there are two situations:
1. the user is already logged in for a previous operation that requires login.
In this case pressing 2 RESET the screen image will simply refresh and delete the
event line from the list
2. the user is not yet logged in.
In this case the LOGIN dialogue window pops up and the user should key in the password.
After which the screen will be refreshed and the event deleted.
NOTE: A user with Operator level is NOT allowed to reset active events. He can only
acknowledge them so that the display image may be switched back to the main screen.
The reset may only be done by Maintenance or Engineer level users.
PRINT
Pressing 4 PRINT, if a Printer is connected to the system (and if the Printer Mode is not
Real Time, see chapter 3.5.5) the event details will be printed out.
4.5.2) EVENT LOG
The EVENT LOG is one of the main menu options (available on any user level). Use the
UP/DOWN keys to move to the EVENT LOG icon and press ENT.
This opens a screen that displays events in chronological order from the most recent
event.
14/06/2012
pag. 41 of 93
- Using the up/down arrow keys one may scroll through the list.
- Using the keys 2 and 4, one may refine the search
- Pressing the ESCAPE key instead will switch back to the main window.
Should 3 minutes pass without any key pressed, the view switches to the Operator main
window.
Select Period
This opens a query asking to select the period to be observed by entering the start and the
end date.
MT3250E rev.0
14/06/2012
pag. 42 of 93
4.5.3) PRINT
If a Printer is connected to the control panel and in the Set Printer Mode the On Request
parameter is selected (see next paragraph 4.5.5), by selecting PRINT and pressing ENT
one starts the printout of the system detector list with all the programming data (Zone,
detector description, Alarm levels etc.).
4.5.4) ABORT PRINT
To stop and cancel the printout
4.5.5) SET PRINTER MODE (Users level M and E)
This parameter is used to select the print mode.
ON REQUEST
MT3250E rev.0
14/06/2012
pag. 43 of 93
In this case, the control panel only prints specific details (Event Log, detector list etc.) at
the users request, in the different menu. The printer can be connected and disconnected
at any time as required.
REAL TIME
This option switches the printer to on-line mode and requires that a printer be continuously
connected to the system. Events are printed as and when they occur.
NOTE: If Real Time is enabled, the event log and other options will not be printed at the
users request. The Real Time parameter must be disabled to permit all other print option
to operate.
MT3250E rev.0
14/06/2012
pag. 44 of 93
4.6)
2-LOGOUT
From the normal mode screen, pressing 2-LOGOUT key, the actual user will logout.
4.7)
4-LOGIN
Pressing 4-LOGIN key a login window will ask for the user password, to allow entering one
of the three user levels: OPERATOR, MAINTENANCE or ENGINEER level (see the
related chapter 4.3 User levels).
Fig. 4.7 b) NORMAL state screen with the E in the right and upper corner
MT3250E rev.0
14/06/2012
pag. 45 of 93
4.8)
3-SYSTEM
In the main window in Normal mode, at any user level, one may view the systems
configuration details, by pressing 3-System. The Zones screen will appear. The Zones
screen shows the list of the defined zones. One may move the cursor up and down by
using the up/down arrow keys. In the bottom side, the available function buttons depend
on the user level.
4.8.1) Zones
In the zones screen, moving up and down with the arrow keys through the zones list and
pressing ENTER one gets into the modules screen.
In the modules screen, moving up and down with the arrow keys through the modules list
and pressing ENTER one gets into the detectors or outputs screens
In the bottom side, the available function buttons depend on the user level.
In the Maintenance or the Engineer level it is possible to Set or Unset and put in
TEST/Maintenance parts of the system.
In the Operator level, the SET/Unset and Test/Maintenance options are not active. The
user should be in Maintenance or Engineer level to use the options.
SET / UNSET
Pressing 3-Zone in the Maintenance or the Engineer level it is possible to Set or Unset
parts of the system.
The number of channels that may be Unset will never exceed 50% of the total
channels/relays number or 32 channels/relays, whatever happens first.
NOTE:
The Engineer level is allowed to Unset the WHOLE system, for the complete system
maintenance period. Trying to Unset the zone, a message will come out warning the exact
number of channels and relays that are about to be unset. If confirmed by pressing Enter
key (OK), then the zones window will show the unset status of the zone:
TEST / EXIT TEST
MT3250E rev.0
14/06/2012
pag. 46 of 93
This will put to TEST mode or take out of the TEST mode the selected zone. It is possible
to put in TEST mode just parts of the system at user level Maintenance or Engineer.
If more than half of the system selected, a warning screen as below will pop-up. A screen
message came out trying to put in Test/Maintenance mode the only zone defined.
Until the number of zones to put in Test/Maintenance mode does not exceed the defined
limits (50%), the selected items will change the status into TEST.
Only the ENGINEER user is authorized to set under Test Mode the whole system. By
pressing ENT on the Test command, a new window will appear showing the number of
channels (detectors or output) that you are going to set under Test mode. To confirm press
ENT (OK). A new window will appear to show the list of systems zone marked with TST.
NOTE: The Zone TEST function is aimed at helping the Engineer during the Start Up. Indeed, after the
system has been switched on and the Control panel programmed, some communication faults may
arise from the remote Input modules or detectors connected on the RS485 buses. This situation would
generate a large amount of Faults (FLT) that could hardly be managed and would require all Faults to
be acknowledged before starting an adequate troubleshooting routine.
The Zone TEST mode allows to overcome this situation the following way: select the Test Mode, the
system zones and automatically all detectors belonging to these zone are set in test mode.
In the main window, close to each channel (detector) its status will appear: TST (under TEST) or FLT
(fault). Now it will be easy to verify, directly in field, which modules or detectors are not communicating
on the RS485 bus and so fix the issues.
When these fault are fixed, the channels status in the main window will change from FLT to TEST.
4.8.2) Modules
Nella videata delle Zone, spostandosi con i tasti freccia su e gi, una volta selezionata la
Zona di interesse e premendo ENT, si entra nella videata dei moduli In ed Out.
Press 3-Module for the SET / UNSET and TEST / EXIT TEST operation, see 4.8.1 and
4.8.2 chapters.
MT3250E rev.0
14/06/2012
pag. 47 of 93
4.8.3) Relays
In the modules screen, moving up and down with the arrow keys through the modules list,
choosing RIO OUTP and pressing ENTER one gets into the Relays screens.
Using the up/down arrow keys one may scroll through the list choosing one of the channel
and press 3-Relay for the SET / UNSET and TEST / EXIT TEST operations.
By the options of the relative screen, unlike the Operator level, the Maintenance level
and the Engineer level may:
- Put in Set or Unset the selected relay
- Put in Test/Maintenance and take out of Test/Maintenance the selected relay
SET / UNSET
Pressing 3-Relay in the Maintenance or the Engineer level it is possible to Set or Unset
parts of the system.
An user with the MAINTENANCE level cannot UNSET more than 50% of the systems
channels and relays.
The only exception is the ENGINEER level, which may UNSET the whole system if
necessary. It is required to do so for maintenance operations in the installation where the
gas detection system is installed.
TEST / EXIT TEST
Will put to TEST mode or take out of the TEST (EXIT TEST) mode the selected relay. It is
possible to put in TEST mode just parts of the system at user level Maintenance or
Engineer. If more than half of the system selected, a warning screen will pop-up.
Until the number of relays to put in Test/Maintenance mode does not exceed the defined
limits, the selected items will change the status into TEST.
The relay remains in TEST until the Channel Maintenance Time set for the control panel
by the Configuration software (10-60 minutes) is expired.
MT3250E rev.0
14/06/2012
pag. 48 of 93
MT3250E rev.0
14/06/2012
pag. 49 of 93
Using the up/down arrow keys one may scroll through the list choosing one of the channel
and press 3-Channel for the SET / UNSET and TEST / EXIT TEST operations.
In the Operator level, the options 3-CHANNEL, is not present. The user should be in
Maintenance or Engineer level to see and to use these options.
By the options of this screen, unlike the Operator level, the Maintenance level and the
Engineer level may:
- Put in Set or Unset the selected channel
- Put in Test/Maintenance and take out of Test/Maintenance the selected
channel
SET / UNSET
Pressing 3-Channel in the Maintenance or the Engineer level it is possible to Set or Unset
parts of the system.
An user with the MAINTENANCE level cannot UNSET more than 50% of the systems
channels and relays.
The only exception is the ENGINEER level, which may UNSET the whole system if
necessary. It is required to do so for maintenance operations in the installation where the
gas detection systems is installed.
TEST / EXIT TEST
This will put to TEST mode or take out of the TEST (EXIT TEST) mode the selected
channel. It is possible to put in TEST mode just parts of the system when user level is
Maintenance or Engineer. If more than half of the system is selected, a warning screen
will pop-up.
As far as the number of channels to put in Test/Maintenance mode does not exceed the
defined limits, the selected items will change the status into TEST, as in the screen below:
MT3250E rev.0
14/06/2012
pag. 50 of 93
MT3250E rev.0
14/06/2012
pag. 51 of 93
5)
PC CONFIGURATION SOFTWARE
5.1)
Introduction
The Configuration Software is an easy to handle user interface for each kind of
communication with the MULTISCAN++PK . The software is designed
to upload the actual configuration data of the system or the events log
to simplify each type of parameter change (e.g. alarm levels)
to download modifications to the MULTISCAN++PK
for maintenance
for the initial configuration of the MULTISCAN++PK at Sensitron or by the installer
5.1.1)
5.2)
Installation
Launch the program from the Windows program bar by clicking on MULTISCAN++PK
14/06/2012
pag. 52 of 93
Serial port
Test
pag. 53 of 93
Logout
Access Log
Info
Help
Exit
5.4)
Program menu
The various program functions are only visible if the user who logged in has the
permissions to use them.
Configuration software includes plausibility checks on edited and new parameters.
The following chapters list program menus and describe their functions.
5.4.1) File
MT3250E rev.0
14/06/2012
pag. 54 of 93
14/06/2012
pag. 55 of 93
MT3250E rev.0
14/06/2012
pag. 56 of 93
MT3250E rev.0
14/06/2012
pag. 57 of 93
MT3250E rev.0
14/06/2012
pag. 58 of 93
5.4.2) Settings
5.4.3) Users
MT3250E rev.0
14/06/2012
pag. 59 of 93
Contact Info can be changed for the Sensitron user but not the username (sensitron) and
level (Administrator).
An unlimited number of users can be created, each with his own name and surname,
password, category, contact info and permissions.
User identification
Password
Category
Contact Info
Permissions
MT3250E rev.0
14/06/2012
pag. 60 of 93
14/06/2012
pag. 61 of 93
Up to 64 users can be set for the MULTISCAN++PK control panel, 32 on the Operator
level, 16 on the Maintenance level and 16 on the Engineer level. For user level functions,
see chapter 3.3, User Levels.
Passwords must be 4 numeric digits long.
Click Logout to log the user out of the program. The Login window reappears where a
new user can login. See chapter 4.3 and Fig. 4.3.b.
Access Log displays the program Login and Logout log as well as operations
conducted.
MT3250E rev.0
14/06/2012
pag. 62 of 93
5.4.4) Communication
Rs232 serial
connection
14/06/2012
pag. 63 of 93
must be entered to establish the connection (Serial Password). The entered password is
compared with the one that resides on the control panel and the connection is established.
MT3250E rev.0
14/06/2012
pag. 64 of 93
MT3250E rev.0
14/06/2012
pag. 65 of 93
After entering the password, the event log file starts uploading and this operation may take
up to one minute. When uploaded, in addition to being automatically saved in the PC
default folder: c:\Documents and settings \ user \ Documents \ MULTISCAN++PK \ Logs,
events are also displayed in the specific window.
Description
Acknowledge
Acknowledge/mute an event
Reset
Reset an event
Info
Config
Settings
Alarm
Alarm event
Fault
Fault event
Emergency
Serial Trace
Event concerning data transfer on the serial port (data upload and
download from PC)
Event
Value
Unit
14/06/2012
pag. 66 of 93
User
Device
Hardware device that generated the event (input module, Gas detector,
Output module, etc.).
Area
System area
Channel
Search criteria can also be entered in the window to optimize the underlying event list
display. Criteria can be by event type and/or date and time. If a printer is connected to the
PC, click Print Event Log to print the event list.
Change Control Unit Password see explanation at the beginning of chapter
Communication.
5.4.5) Reports
Via the Open command in the File menu existing configuration files will be indicated
and may be chosen and opened. If some parameters at the MULTISCAN++PK shall be
modified, this has to be carried out as described in the following chapters.
MT3250E rev.0
14/06/2012
pag. 67 of 93
MT3250E rev.0
14/06/2012
pag. 68 of 93
the warm-up time for the system after which it passes over to
measuring mode (from 2 to 10 minutes; default 3 minutes)
BUS Architecture
Slave Address
Maintenance Time
Buzzer Reactivation Time reactivation time for buzzer after which the acoustic
alarm is reactivated if the alarm conditions are still valid
(from 20 to 120 minutes; default 60 minutes)
MT3250E rev.0
14/06/2012
pag. 69 of 93
5.5.3) Zones
Modules Overview
IN/OUT modules and system detectors are set in Modules Overview. The system
layout must be known to correctly set the various field devices. What you need to know:
Detectors and IN and OUT modules (relays) installed in the system.
The Zones they are in
The Loops (RS485 bus) they are connected to and their addresses
For information on Multisystem++S1 installation, please see chapter 2Installing in this
manual.
MT3250E rev.0
14/06/2012
pag. 70 of 93
Input Modules
STG/IN8-PK analog input modules installed in the system are set in Add RIO Input
Modules.
Click Add RIO Input Module to open the window shown in Fig. 5.5.4 b.
Sensors
Gas Detectors installed in the system and directly connected on the CPU loop RS485
(Smart P) are set in Sensors. Refer to chapter 2-Installation for further information.
Click Sensors to open the window shown in Fig. 5.5.4 c.
MT3250E rev.0
14/06/2012
pag. 71 of 93
Zone
Loop
Output Modules
STG/OUT16 output modules installed in the system are set in RIO Output Module.
Click Add RIO Output Module to open the window shown in Fig. 5.5.4 d.
MT3250E rev.0
14/06/2012
pag. 72 of 93
MT3250E rev.0
14/06/2012
pag. 73 of 93
5.5.5) Channels
Use the Input Modules menu to enable and program single gas Detector settings in the
system.
Channel Map
MT3250E rev.0
14/06/2012
pag. 74 of 93
MT3250E rev.0
14/06/2012
pag. 75 of 93
Channel Manage
The Gas Type represents the list of gases belonging to the related Profile.
MT3250E rev.0
14/06/2012
pag. 76 of 93
Choose the right gas as for the gas detector connected to the input. e.g. choose CO
(Carbon Monoxide) if a Carbon Monoxide gas detector is connected to the input or choose
NO2 (Nitrogen Dioxide) if a Nitrogen Dioxide detector is connected to the input. And so on.
3)
The Detector Model lists the available detectors for the chosen gas.
Choose the right part number as for the gas detector connected to the input. e.g. choose
S2398CO for a Smart P CO gas detector (see the labels stuck on the gas detector case)
or choose S2399NO2 if a Smart P for NO2 detector model is connected to the input.
The Channel Description is not mandatory for the reliable function of the gas detection
system. It is an aid for the user to indicate useful additional information in the case of
alarms.
In the case of alarms all information related to the detector(s) in alarm condition will be
indicated at the display on request.
The Channel Description may be additional to the zone description and may include
data according redundancy to another channel or describe the measurement task in detail.
In Alarm settings, set the levels and operations of the three system alarm thresholds
according to European EN50545 standards.
The three alarm threshold values can be edited within a specific range, indicated by the
horizontal red bars.
Note on operations according to EN50545 standards
Alarm 1 & 2 thresholds are activated if the gas value measured by the detector exceeds an
average concentration in the set time (Average Alarm Time).
Threshold 3 is immediately activated if the concentration value measured by the detector
exceeds the set alarm 3 value for a certain amount of time (Alarm 3 Persistence).
The system usually displays the average measured by the detector (except in Graph mode
where the real time value is displayed).
MT3250E rev.0
14/06/2012
pag. 77 of 93
14/06/2012
pag. 78 of 93
MT3250E rev.0
14/06/2012
pag. 79 of 93
Channels Redundancy
If the system requires a very high security level, two detectors are to be placed at each
measuring point. Profile and Gas Type have to be identical. The two detectors
may be of the same type.
Profile
Gas Type
Measuring range
Alarm set point for each alarm level
MT3250E rev.0
14/06/2012
pag. 80 of 93
Fig. 5.5.5 g) Typical warning when choosing as redundant an already defined channel,
with different parameters
MT3250E rev.0
14/06/2012
pag. 81 of 93
Output Map
MT3250E rev.0
14/06/2012
pag. 82 of 93
MT3250E rev.0
14/06/2012
pag. 83 of 93
Output Manage
Redundancy
Operation Mode
Relay Type
Event Type
OR
Voting
Associated Sensors /Modules it is the window where the events associated to the
output can be chosen (with the Add/Remove key) and
shown.
Add / Remove
MT3250E rev.0
14/06/2012
pag. 84 of 93
14/06/2012
pag. 85 of 93
It is not possible to select different types of events associated to just one output. An
output set for the Alarm 1 cannot be set for the Alarm 2 or 3 as well.
Module event: Select Event Module to associate an output to a Fault or an Off Line
mode.
MT3250E rev.0
14/06/2012
pag. 86 of 93
Voting Function
MT3250E rev.0
14/06/2012
pag. 87 of 93
Outputs Redundancy
If the system requires a very high security level, two outputs could be programmed for
the same activation.
MT3250E rev.0
14/06/2012
pag. 88 of 93
Fig. 5.5.6 o) Typical warning when choosing as redundant a non defined output
MT3250E rev.0
14/06/2012
pag. 89 of 93
The Redundant Output will appear in the Output Relay programming screen (fig.
5.5.5.p)
Fig. 5.5.6 p) Outputs details screen showing a defined relay with redundancy
MT3250E rev.0
14/06/2012
pag. 90 of 93
Steady
On
activated until the
channel restore +
the Deactivation Delay
Off
Activation
Delay
Output
status
Pulsed
On
Off
T1
T1
T2
Timed
T2
On
Off
0
MT3250E rev.0
T1
T2
14/06/2012
t
pag. 91 of 93
The Normally Energized option defines if the output is normally activated or not, in
normal operation.
MT3250E rev.0
14/06/2012
pag. 92 of 93
The above information does not make the manufacturer liable, and the manufacturer
reserves the right to make any changes that it retains will be useful to improve the
product.
Sensitron S.r.l.
MT3250E rev.0
14/06/2012
pag. 93 of 93