Level of Development (LOD) Specification Introduction .............................................................................................. 7
A SUBSTRUCTURE ................................................................................................................................................... 12
A10 Foundations ..................................................................................................................................................... 12
A1010 Standard Foundations ............................................................................................................................... 12
A1020 Special Foundations .................................................................................................................................. 14
A20 Subgrade Enclosures ....................................................................................................................................... 15
A2010 Walls for Subgrade Enclosures ................................................................................................................. 16
A40 Slabs-on-Grade ................................................................................................................................................ 16
A4010 Standard Slabs-on-Grade.......................................................................................................................... 17
A4020 Structural Slabs-on-Grade ......................................................................................................................... 17
B SHELL .................................................................................................................................................................... 18
B10 Superstructure .................................................................................................................................................. 18
B1010 Floor Construction ..................................................................................................................................... 18
B20 Exterior Vertical Enclosures .............................................................................................................................. 30
B2010 Exterior Walls ............................................................................................................................................ 30
B2020 Exterior Windows ...................................................................................................................................... 33
B2050 Exterior Doors and Grilles ......................................................................................................................... 34
B2070 - Exterior Louvers and Vents ........................................................................................................................ 36
B2080 - Exterior Wall Appurtenances ...................................................................................................................... 36
B2090 Exterior Wall Specialties ............................................................................................................................ 37
B30 Exterior Horizontal Enclosures .......................................................................................................................... 37
B3010 Roofing ..................................................................................................................................................... 37
B3020 Roof Appurtenances.................................................................................................................................. 38
B3040 Traffic Bearing Horizontal Enclosures ........................................................................................................ 39
B3060 Horizontal Openings .................................................................................................................................. 39
B3080 Overhead Exterior Enclosures ................................................................................................................... 40
C INTERIORS ............................................................................................................................................................. 41
C10 Interior Construction ......................................................................................................................................... 41
C1010 Interior Partitions ....................................................................................................................................... 41
C1020 Interior Windows ....................................................................................................................................... 44
C1030 Interior Doors ............................................................................................................................................ 45
C1040 Interior Grilles and Gates .......................................................................................................................... 48
C1060 Raised Floor Construction ......................................................................................................................... 49
C1070 Suspended Ceiling Construction ............................................................................................................... 49
C1090 Interior Specialties .................................................................................................................................... 51
C20 Interior Finishes ................................................................................................................................................ 55
C2010 Wall Finishes ............................................................................................................................................ 56
C2020 Interior Fabrications .................................................................................................................................. 57
2

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C2030 Flooring .................................................................................................................................................... 57


C2040 Stair Finishes ............................................................................................................................................ 59
C2050 Ceiling Finishes ........................................................................................................................................ 60
C2090 Interior Finish Schedules ........................................................................................................................... 61
D SERVICES .............................................................................................................................................................. 62
D10 Conveying ........................................................................................................................................................ 62
D1010 Vertical Conveying Systems ...................................................................................................................... 62
D1030 Horizontal Conveying ................................................................................................................................ 63
D1050 Material Handling ...................................................................................................................................... 63
D1080 Operable Access Systems ........................................................................................................................ 65
D20 Plumbing .......................................................................................................................................................... 66
D2010 Domestic Water Distribution ...................................................................................................................... 66
D2020 Sanitary Drainage ..................................................................................................................................... 70
D2030 Building Support Plumbing Systems .......................................................................................................... 74
D2050 General Service Compressed-Air .............................................................................................................. 78
D2060 Process Support Plumbing Systems.......................................................................................................... 78
D30 HVAC ............................................................................................................................................................... 81
D3010 Facility Fuel Systems ................................................................................................................................ 81
D3020 Heating Systems ....................................................................................................................................... 85
D3030 Cooling Systems ....................................................................................................................................... 88
D3050 Facility HVAC Distribution Systems ........................................................................................................... 92
D3060 Ventilation ................................................................................................................................................. 95
D3070 Special Purpose HVAC Systems ............................................................................................................... 99
D40 Fire Protection .................................................................................................................................................100
D4010 Fire Suppression ......................................................................................................................................100
D4030 Fire Protection Specialties ........................................................................................................................102
D50 Electrical .........................................................................................................................................................104
D5020 Electrical Service and Distribution ............................................................................................................109
D5030 General Purpose Electrical Power ............................................................................................................114
D5040 Lighting ....................................................................................................................................................115
D5080 Miscellaneous Electrical Systems .............................................................................................................118
D60 Communications .............................................................................................................................................121
D6010 Data Communications ..............................................................................................................................121
D6020 Voice Communications ............................................................................................................................121
D6030 Audio-Video Communication ....................................................................................................................121
D6060 Distributed Communications and Monitoring .............................................................................................121
D6090 Communications Supplementary Components .........................................................................................121
D70 Electronic Safety and Security .........................................................................................................................121
D7010 Access Control and Intrusion Detection ....................................................................................................121
D7030 Electronic Surveillance .............................................................................................................................121

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D7050 Detection and Alarm.................................................................................................................................121


D7070 Electronic Monitoring and Control .............................................................................................................121
D7090 Electronic Safety and Security Supplementary Components .....................................................................121
D80 Integrated Automation .....................................................................................................................................121
D8010 Integrated Automation Facility Controls ....................................................................................................121
E EQUIPMENT & FURNISHINGS ..............................................................................................................................122
E10 Equipment .......................................................................................................................................................122
E1010 Vehicle and Pedestrian Equipment ...........................................................................................................122
E1030 Commercial Equipment ............................................................................................................................122
E1040 Institutional Equipment .............................................................................................................................124
E1060 Residential Equipment .............................................................................................................................125
E1070 Entertainment and Recreational Equipment ..............................................................................................125
E1090 Other Equipment ......................................................................................................................................126
E20 Furnishings ......................................................................................................................................................127
E2010 Fixed Furnishings .....................................................................................................................................127
E2050 Movable Furnishings ................................................................................................................................128
F SPECIAL CONSTRUCTION & DEMOLITION .........................................................................................................129
F10 Special Construction ........................................................................................................................................129
F1010 Integrated Construction ............................................................................................................................129
F1020 Special Structures ....................................................................................................................................129
F1030 Special Function Construction ..................................................................................................................129
F1050 Special Facility Components.....................................................................................................................129
F1060 Athletic and Recreational Special Construction .........................................................................................129
F1080 Special Instrumentation ............................................................................................................................129
F20 Facility Remediation ........................................................................................................................................129
F2010 Hazardous Materials Remediation ............................................................................................................129
F30 Demolition .......................................................................................................................................................129
F3010 Structure Demolition .................................................................................................................................129
F3030 Selective Demolition .................................................................................................................................129
F3050 Structure Moving ......................................................................................................................................129
G BUILDING SITEWORK ..........................................................................................................................................130
G10 Site Preparation ..............................................................................................................................................130
G1010 Site Clearing ...............................................................................................................................................130
G1020 Site Elements Demolition .........................................................................................................................130
G1030 Site Element Relocations .........................................................................................................................130
G1050 Site Remediation .....................................................................................................................................130
G1070 Site Earthwork .........................................................................................................................................130
G20 Site Improvements ..........................................................................................................................................131
G2010 Roadways ................................................................................................................................................131
4

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

G2020 Parking Lots ............................................................................................................................................131


G2030 Pedestrian Plazas and Walkways ............................................................................................................131
G2040 Airfields ...................................................................................................................................................131
G2050 Athletic, Recreational, and Playfield Areas ...............................................................................................131
G2060 Site Development ....................................................................................................................................131
G2080 Landscaping ............................................................................................................................................131
G30 Liquid and Gas Site Utilities .............................................................................................................................131
G3010 Water Utilities ..........................................................................................................................................131
G3020 Sanitary Sewerage Utilities ......................................................................................................................131
G3030 Storm Drainage Utilities ...........................................................................................................................131
G3050 Site Energy Distribution ...........................................................................................................................131
G3060 Site Fuel Distribution ................................................................................................................................131
G3090 Liquid and Gas Site Utilities Supplementary Components ........................................................................131
G40 Electrical Site Improvements ...........................................................................................................................132
G4010 Site Electric Distribution Systems .............................................................................................................133
G4050 Site Lighting .............................................................................................................................................134
G5010 Site Communications Systems .................................................................................................................135
G9010 Tunnels ...................................................................................................................................................136
APPENDIX ...................................................................................................................................................................137

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Acknowledgements
Thanks to all individuals and organizations who reviewed and contributed to this work, and to the following industry
association representatives and co-chairs of the major discipline subgroups who made this document possible:

Overall co-chairs
Jan Reinhardt, AIA, PE, Adept Project Delivery
Jim Bedrick, FAIA, AEC Process Engineering

Domain-Specific Content
Design

Construction

Structures

Will Ikerd, Ikerd Consulting

David Merrifield, Alpha Steel

Exterior Skin

James Vandezande, HOK

Walt Cichonski, L F Driscoll

Interior Construction

Ron Dellaria, RA, CSI, Astorino

Brian Filkins, Mortenson

Building Services

Murat Karakas, Arup

David Francis, Southland


Aaron Lawson, Gould Electric

Industry association representatives


Dmitri Alferieff, Associated General Contractors
Michael Bomba, Esq., American Institute of Architects

Overall editing
Marisa Gerdano, Associated General Contractors

Nothing contained in this work shall be considered to be the rendering of legal advice for specific cases, and readers are
responsible for obtaining such advice from their own legal counsel. This work and any forms herein are intended solely for
educational and informational purposes.
Qualifications Based Selection of Contractors 2013 by BIMForum.
No portions of this work may be reproduced or displayed without the express written permission of the copyright holders. All
rights reserved.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Level of Development (LOD) Specification Introduction


1

Overview
1

The Level of Development (LOD) Specification is a reference that enables practitioners in the AEC Industry to specify
and articulate with a high level of clarity the content and reliability of Building Information Models (BIMs) at various stages
in the design and construction process. The LOD Specification utilizes the basic LOD definitions developed by the AIA for
2
3
the AIA G202-2013 Building Information Modeling Protocol Form and is organized by CSI Uniformat 2010 . It defines
and illustrates characteristics of model elements of different building systems at different Levels of Development. This
clear articulation allows model authors to define what their models can be relied on for, and allows downstream users to
clearly understand the usability and the limitations of models they are receiving.
The intent of the Specification is to help explain the LOD framework and standardize its use so that it becomes more
useful as a communication tool. It does not prescribe what Levels of Development are to be reached at what point in a
project but leaves the specification of the model progression to the user of this document. To accomplish the documents
intent, its primary objectives are:

To help teams, including owners, to specify BIM deliverables and to get a clear picture of what will be included in
a BIM deliverable

To help design managers explain to their teams the information and detail that needs to be provided at various
points in the design process

To provide a standard that can be referenced by contracts and BIM execution plans.

Background

The BIMForum initiated the development of this LOD Specification and formed a working group comprising contributors
from both the design and construction sides of the major disciplines. The working group first interpreted the AIAs basic
LOD definitions for each building system, and then compiled examples to illustrate the interpretations. Because BIM is
being put to an ever increasing number of uses, the group decided that it was beyond the initial scope to address all of
them. Instead, the specifications were developed to address model element geometry, with three of the most common
uses in mind quantity take-off, 3D coordination and 3D control and planning. The group felt that in taking this approach
the interpretations would be complete enough to support other uses.

Levels of Development

AIA Contract Document G202-2013, Building Information Modeling Protocol Form is part of a new series of
digital practice documents the AIA will be publishing in in conjunction with the AIA National Convention in June
2013. For general information on the documents and downloadable drafts that were published in August 2012 as
part of a public comment period see www.aia.org/digitaldocs. Once the final documents are released, samples
will be available for download through the same site.
3
TM
UniFormatTM Numbers and Titles used in this publication are from UniFormat , published by CSI and
Construction Specifications Canada (CSC), and are used with permission from CSI. For a more in-depth
TM
explanation of UniFormat and its use in the construction industry visit www.csinet.org or contact CSI,110 South
Union Street, Suite 100, Alexandria, VA 22314. (800)-689-2900.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

The Level of Development (LOD) framework addresses several issues that arise when a BIM is used as a communication
or collaboration tool, i.e., when someone other than the author extracts information from it:

During the design process, building systems and components progress from a vague conceptual idea to a precise
description. In the past there has been no simple way to designate where a model element is along this path.
The author knows, but others often dont.

Its easy to misinterpret the precision at which an element is modeled. Hand drawings range from pen strokes on
a napkin to hard lines with dimensions called out, and its easy to infer the precision of the drawing from its
appearance. In a model though, a generic component placed approximately can look exactly the same as a
specific component located precisely, so we need something besides appearance to tell the difference.

It is possible to infer information from a BIM that the author doesnt intend unstated dimensions can be
measured with precision, assembly information often exists before its been finalized, etc. In the past, this issue
has been sidestepped with all-encompassing disclaimers that basically say, Since some of the information in the
model is unreliable, you may not rely on any of it. The LOD framework allows the author to clearly state the
reliability of given model elements, so the concept becomes Since some of the information in the model is
unreliable, you may only rely on it for what I specifically say you can.

In a collaborative environment, where people other than the model author are depending on information from the
model in order to move their own work forward, the design work plan takes on high importance it is necessary
for the model users to know when information will be available in order to plan their work. The LOD framework
facilitates this.

The LOD Framework addresses these issues by providing an industry-developed standard to describe the state of
development of various systems within a BIM. This standard enables consistency in communication and execution by
facilitating the detailed definition of BIM milestones and deliverables.

3.1 Level of Development vs. Level of Detail


This Specification uses the concept of Levels of Development rather than Levels of Detail. There are important
differences.
Level of Detail is essentially how much detail is included in the model element. Level of Development is the degree to
which the elements geometry and attached information has been thought through the degree to which project team
members may rely on the information when using the model. In essence, Level of Detail can be thought of as input to the
element, while Level of Development is reliable output.

LOD Definitions

In 2008, the AIA developed its first set of Level of Development definitions in AIA Document E202 -2008 Building
Information Modeling Protocol. Due to the rapidly evolving nature of the use of BIM, the AIA evaluated the AIA E202
2008, including the LOD definitions. The result is the updated and reconfigured Digital Practice documents, AIA E203
2013, Building Information Modeling and Digital Data Exhibit, AIA G2012013, Project Digital Data Protocol Form, and
AIA G2022013, Project Building Information Modeling Protocol Form, which are accompanied by a detailed guide
document entitled Guide and Instructions to the AIA Digital Practice Documents. The AIAs updated Digital Practice
documents include revised LOD definitions.
To help further the standardization and consistent use of the LOD concept, and to increase its usefulness as a foundation
for collaboration, the AIA agreed to allow the BIMForum to utilize its latest LOD definitions in this Specification. The LOD
definitions that are used in this catalog are identical to those to be published in the AIAs updated Digital Practice
Documents, with two exceptions.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

First, the working group identified the need for an LOD that would define model elements sufficiently developed to
facilitate coordination between disciplines e.g. clash detection/avoidance, layout, etc. The requirements for this level
are higher than those for 300, but not as high as those for 400. Thus it was designated LOD 350. The AIA documents do
not include LOD 350, but the associated Guide and Instructions references it.
Second, while LOD 500 is included in the AIAs LOD definitions, the working group did not feel it was necessary to further
define and illustrate LOD 500 in this Specification because it relates to field verification. Accordingly the expanded
descriptions and graphical illustrations in this Specification are limited to LOD 100-400.
Fundamental LOD Definitions

LOD 100
The Model Element may be graphically represented in the Model with a symbol or other generic
representation, but does not satisfy the requirements for LOD 200. Information related to the Model Element (i.e.
cost per square foot, tonnage of HVAC, etc.) can be derived from other Model Elements.

LOD 200
The Model Element is graphically represented within the Model as a generic system, object, or
assembly with approximate quantities, size, shape, location, and orientation. Non-graphic information may also be
attached to the Model Element.

LOD 300
The Model Element is graphically represented within the Model as a specific system, object or
assembly in terms of quantity, size, shape, location, and orientation. Non-graphic information may also be
attached to the Model Element.

LOD 350
The Model Element is graphically represented within the Model as a specific system, object, or
assembly in terms of quantity, size, shape, orientation, and interfaces with other building systems. Non-graphic
information may also be attached to the Model Element.

LOD 400
The Model Element is graphically represented within the Model as a specific system, object or
assembly in terms of size, shape, location, quantity, and orientation with detailing, fabrication, assembly, and
installation information. Non-graphic information may also be attached to the Model Element.

LOD 500
The Model Element is a field verified representation in terms of size, shape, location, quantity,
and orientation. Non-graphic information may also be attached to the Model Elements. 4

Example light fixture:

100
200
300
350
400

cost/sf attached to floor slabs


light fixture, generic/approximate size/shape/location
2x4 troffer, specific size/shape/location
Lightolier DPA2G12LS232, specific size/shape/location
As 350, plus special mounting details, as in a decorative soffit

Glossary
The expanded definitions use the following interpretations of these terms:

Specific: The quantity, size, shape, location, and orientation of the element as designed can be measured directly
from the model without referring to non-modeled information such as notes or dimension call-outs.
Actual: The model element includes all the qualities of a specific element and is representative of the
manufacturer-specific model to be installed or the construction intent of an assembly.

Order of Precedence
4

The definitions for LOD 100, 200, 300, 400, and 500 included in this Specification represent the updated
language that appears in the AIAs most recent BIM protocol document, G2022013, Building Information
Modeling Protocol Form. The LOD 100, 200, 300, 400 and 500 definitions are produced by the AIA and have
been used by permission. Copyright 2013. The American Institute of Architects. All rights reserved. LOD 350
was developed by the BIMForum working group. Copyright 2013. The BIMForum and the American Institute of
Architects. All rights reserved.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

The body of this Specification expands on these fundamental definitions as they apply to specific building systems and
sub-systems. In the event of any conflict, more specific expansions take precedence over less specific expansions and
fundamental definitions, e.g. the expanded definitions for C1010 take precedence over those for C10, which in turn take
precedence over the fundamental definitions.
Model Element Author
This document does not prescribe who the author of a particular component at a certain LOD should be the sequence of
responsibility for modeling various systems will vary from one project to another. To accommodate for this variation this
document defers to the concept of Model Element Author (MEA) as defined in the AIA E203-2013: The Model Element
Author is the entity (or individual) responsible for managing and coordinating the development of a specific Model Element
to the LOD required for an identified Project milestone, regardless of who is responsible for providing the content in the
5
Model Element."

4.1 LOD Definitions Explained


LOD 100, then, corresponds to a conceptual level. For example, in a massing model the interior walls may not yet be
modeled, but we can use the approximate floor area to generate an area-based interior construction cost. Thus the walls
are at LOD 100 theyre not modeled, but information about them can be obtained from elements that are modeled (the
floors) coupled with other information (area-based cost tables).
To continue with the wall example, a floor plan is often first laid out using generic walls. The walls can now be measured
directly, but the specific wall assemblies arent known and the quantity, thickness, and location measurements are
approximate. The walls are now at LOD 200. To step back to the massing model, if generic exterior walls are modeled
and can be measured directly, they are actually at LOD 200, even though there is little detail.
At LOD 300 the wall element is modeled as a specific composite assembly, with information about its framing, wallboard,
insulation if any, etc. The element is modeled at the thickness of the specified assembly, and is located accurately within
the model. Non-geometric information such as fire rating may also be attached as well. This means that its not
necessary to model every component of the wall assembly a solid model element with accurate thickness and location
and with the information usually included in a wall type definition satisfies the requirements of LOD 300.
At LOD 350 enough detail for installation and cross-trade coordination is included. For the wall example, this would
include such things as blocking, king studs, seismic bracing, etc.
LOD 400 can be thought of as similar to the kind of information usually found in shop drawings.

4.1 Caveats
There is no strict correspondence between LODs and design phases. Building systems are developed at different
rates through the design process for example, design of the structural system is usually well ahead of the design of
interior construction. At an early design phase milestone, the model will include many elements at LOD 200, but will also
include many at LOD 100, as well as some at 300, and possibly even 400.
Similarly, there is no such thing as an LOD ___ model. As previously stated, project models at any stage of delivery
will invariably contain elements and assemblies at various levels of development.

Updates of This Document

While this document is intended as a reference that can be cited in agreements such as contract and BIM execution
plans, it is recognized that the use of BIM in design and construction is evolving. To accommodate this evolution this
document will be updated periodically in clearly identifiable versions. Initially the target frequency is annually, but that
may change in the future. In addition, interim updates may be issued if needed.
5

AIA Document E203-2013 Building Information Modeling and Digital Data Exhibit. Copyright American
Institute of Architects 2013. All rights reserved. Definition quoted here by permission.
10

Level of Development
Specification
Version: DRAFT 2013
Revision History

4/24/13
__/__/__

Initial draft for public review


Draft Level of Development Specification 2013

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

A SUBSTRUCTURE
A10 Foundations
100

A written structural narrative is provided without structural elements


modeled. This narrative may reference an architectural mass model
that shows generic building scale and proportion of the foundation.

200

Generic element modeling to include:

300

Approximate size/shape of foundation element


Structural grids defined in model

This LOD includes but is not limited to design level information such
as the engineered size/shape of the foundation.
Specific element modeling to include:

Overall size and geometry of the foundation element


Sloping surfaces or floor depressions
Out to out dimensions of the members
Material strength

Element information defined with notes or 2D details may include:


350

Rebar
Actual element modeling to include but not limited to information
needed for cross trade collaboration such as:

400

Chamfers
Rebar and any embedded elements modeled at congested
areas where specified by project BIM manager which is
typically with in a set distance from the area of congestion
Anchor rods
Any permanent shoring or forming structures such as
caissons or void boxes.

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

A1010 Standard Foundations


See A10 Foundations

12

Level of Development
Specification
Version: DRAFT 2013

A1010.10 Wall Foundations (Shallow Foundations)


See A10 Foundations and A1010 Standard Foundations
100

See A10

200

See A10

300

See A10

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

Location of sleeve penetrations


Pour joints
Moisture retarder
Dowels
All elements needed for cross-trade collaboration are to be
modeled.

Additional element modeling for unit masonry foundations include


but are not limited to:

400

Actual location and shape of structural element


All exposed embeds or reinforcement such as lintels
All penetrations detailed and modeled
Expansion joints

Fabrication element modeling to include but not limited to:

Rebar detailing including hooks and lap splices


Dowels
Chamfer
Finish
Coursing for unit masonry defined
Waterproofing

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

A1010.30 Column Foundations (Deep Foundations)


See A10 Foundations and A1010 Standard Foundations
100

See A10

200

See A1010

300

Specific element modeling to include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Approximate bearing depth noted with site and soil


contingencies expected
Top of Pier
Size of Pier

Actual Top of Pier (TOP) and expected Bottom of Pier


(BOT) modeled per engineers review of site conditions
All elements needed for cross-trade collaboration are to be
modeled

Fabrication element modeling to include but not limited to:

Depth to bearing stratum


Penetration into bearing stratum
Locations of lap splices

A1020 Special Foundations


See A10 Foundations

A1020.80 Grade Beams


See A10 Foundations and A1020 Special Foundations
100

See A10

200

See A1010

300

See A1010

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Water Stops
Pour joints and sequences required to identify reinforcing
lap spice, scheduling, etc.
Post-tension profile and strands called out with a narrative
or modeled if required by the BIM manager

Fabrication element modeling to include but not limited to:

Detailed Post-tensioned components

14

Level of Development
Specification
Version: DRAFT 2013

A20 Subgrade Enclosures


100

A written structural narrative is provided without structural objects


modeled. This narrative may reference an architectural mass model
that shows generic building scale and proportion of the foundation.

200

Generic element modeling to include:

300

Approximate size/shape of the subgrade enclosure element


Structural grids defined in model

This LOD included but is not limited to design intent level information
such as the engineered size/shape of the subgrade enclosure.
Specific element modeling to include:

Overall size and geometry of the subgrade element


Sloping surfaces
Out to out dimensions of the element
Material strength

Element information defined with notes or 2D details may include:

350

Rebar
Chamfers
Finishes

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

Chamfers
Sleeve penetrations
Pour joints
Rebar and any embedded elements modeled at congested
areas where specified by project BIM manager which is
typically with in a set distance from the area of congestion.
Any permanent shoring or forming structures such as void
boxes
Interior finish and/or insulation
Expansion Joints
All elements needed for cross-trade collaboration are to be
modeled
Moisture retarder

Additional element modeling for unit masonry enclosures include but


are not limited to:

400

Actual location and shape of structural masonry element


All exposed embeds or reinforcement such as lintels
All penetrations detailed and modeled
Expansion joints

This element level modeling shall include all information needed to


Fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.
Fabrication element modeling to include but not limited to:

Rebar detailing including hooks and lap splices


Dowels
Chamfer
Finish

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Coursing for unit masonry defined


Waterproofing

A2010 Walls for Subgrade Enclosures


See A20 Subgrade Enclosures

A40 Slabs-on-Grade
100

A written structural narrative is provided without structural objects


modeled. This narrative may reference an architectural mass model
that shows generic building scale and proportion of the slab.

200

Generic element modeling to include:

300

Generic slab with approximate thickness


Structural grids defined in model

This LOD included but is not limited to design intent level information
such as the engineered size/shape of the subgrade enclosure.
Specific element modeling to include:

Overall size, thickness and geometry of the slab-on-grade


Slab Depressions
Edge turn downs
Material strength

Element information defined with notes or 2D details may include:

350

Rebar
Moisture Retarder
Slab penetrations

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Sleeve penetrations
Pour joints
Control joints
Expansion joints
Water Stops
Rebar and any embedded elements modeled at congested
areas where specified by project BIM manager which is
typically with in a set distance from the area of congestion.
Void boxes
Anchor rods
Moisture retarder
Dowels
Post-tension profile and strands called out with a narrative or
modeled if required by the BIM manager
This element level modeling shall include all information needed to
fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.
Fabrication element modeling to include but not limited to:

Actual slab dimensions and profiles with fully modeled rebar


Post tensioning components
16

Level of Development
Specification
Version: DRAFT 2013

All joints
Water proofing
Finish

A4010 Standard Slabs-on-Grade


See A40 Slabs-on-Grade

A4020 Structural Slabs-on-Grade


See A40 Slabs-on-Grade

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B SHELL
B10 Superstructure
100

A written structural narrative is provided without structural objects


modeled. This narrative may reference an architectural mass model
that shows generic building scale and proportion of the foundation.

200

A written structural narrative is provided without structural objects


modeled. This narrative may reference an architectural mass model
that shows generic building scale and proportion of the foundation.

B1010 Floor Construction


100

See B10

200

Generic floor model to include

Floor with approximate dimensions


Approximate supporting framing members
Structural grids defined in model

B1010.10 Floor Structural Frame


Masonry
100

See B10

200

Generic Masonry superstructure to have:

300

Specific element modeling to include:

350

Specific sizes of main structural elements modeled per


defined structural grid with correct dimensions.
Rough openings with reinforcement and steel lintels called
out in typical details
Reinforcement and fill called out in 2D
Typical details for small penetrations

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Type of structural masonry system


Defined structural grid
Rough order of magnitude estimate of masonry structure

Actual location and shape of structural masonry element


All exposed embeds or reinforcement such as lintels
All penetrations detailed and modeled
Expansion joints

Fabrication element modeling to include but not limited to:

Waterproofing
Coursing

This element level modeling shall include all information needed to


18

Level of Development
Specification
Version: DRAFT 2013
fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

Steel
100
200

See B10
Generic steel superstructure to have:

Type of structural system


Defined structural grid
Rough order of magnitude estimate of steel structure

Steel Framing Columns


100

See B10

200

See B1010 (00)

300

Specific element modeling to include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Specific sizes of main vertical structural members modeled


per defined structural grid with correct orientation.
Structural steel materials defined in specifications.
Typical connection details in 2D

Actual elevations and location of member connections


Large elements of typical connections applied to all structural
steel connections such as base plates, gusset plates, anchor
rods, ect.
Any miscellaneous steel members with correct orientation
Any steel structure reinforcement such as web stiffeners,
sleeve penetrations, ect.

Fabrication element modeling to include but not limited to:

Welds
Coping of members
Cap pates
Washers, nuts, etc.
All assembly elements

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Steel Framing Beams


100

See B10

200

See B1010 (00)

300

Specific element modeling


deling to include:

Specific sizes of main horizontal structural members modeled per


defined structural grid with correct orientation, slope and elevation

Element information defined with notes or 2D details may include:

350

Actual element modeling to include but not limited to information needed


for cross trade collaboration such as:

400

Connection details
Structural steel materials defined
Finishes, i.e. painted, galvanized, etc

Large elements of typical connections applied to all structural steel


connections
ons such as base plates, gusset plates, anchor rods, etc.
Any miscellaneous steel members with correct orientation
Any steel structure reinforcement such as web stiffeners, sleeve
penetrations, etc.

Fabrication element modeling to include but not limited to:

Welds
Coping of members
Bent plates, Cap pates, ect.
Bolts, Washers, nuts, etc.
All assembly elements

This element level modeling shall include all information needed to fully
define the fabrication and installation of the element. Additional nonmodeled information may be included into the element.

20

Level of Development
Specification
Version: DRAFT 2013

Steel Framing Miscellaneous Members


100

See B10

200

See B1010 (00)

300

Specific element modeling to include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Specific sizes of main structural members modeled per


defined structural grid with correct orientation.
Structural steel materials defined in specifications.
Typical connection details in 2D

Actual elevations and location of member connections


Large elements of typical connections applied to all structural
steel connections such as base plates, gusset plates, anchor
rods, etc.
Any miscellaneous steel members with correct orientation
Any steel structure reinforcement such as web stiffeners,
sleeve penetrations, etc.

Fabrication element modeling to include but not limited to:

Welds
Coping of members
Cap pates
Washers, nuts, etc.
All assembly elements

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Steel Framing Bracing Rods


100

See B10

200

See B1010 (00)

300

Specific element modeling to include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Specific sizes of main structural braces modeled per defined


structural grid
Structural steel materials defined in specifications.
Typical connection details in 2D

Actual elevations and location of member connections


Large elements of typical connections applied to all structural
steel connections such as base plates, gusset plates, anchor
rods, etc.
Any miscellaneous steel members with correct orientation
Any steel structure reinforcement such as web stiffeners,
sleeve penetrations, etc.

Fabrication element modeling to include but not limited to:

Welds
Coping of members
Cap pates
Clevis
Bolts, Washers, Nuts, etc.
All assembly elements

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

22

Level of Development
Specification
Version: DRAFT 2013

Steel Joist
100

200

Generic element modeling to include:

300

See B10 for additional information


Basic floor loading criteria and geometry would be defined
with a narrative and would include but is not limited to:
o Live
o Dead
o Wind
o Vibration
o Expected depth

Expected depth

Specific element modeling to include:

Joist size, depth, and material with sloping geometry


Spacing and end elevations
Joist seat depth

Element information defined with notes or 2D details may include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Non-standard joist seat depths and\or sloping joist seat


Member designation, load capacity and deflection criteria
Design loads

Actual final joist profile locations with panel points


Joist bridging and lateral braces.
Fire protection coating
Any miscellaneous steel pertaining to the joist
Joist seat width
Erection details for installation
Chord and web member section profiles are actually defined
Joist layout in coordination with metal deck fasteners would
be confirmed
Non-standard joist seat depths and\or sloping joist seat

Fabrication element modeling to include but not limited to:

Welds
Connection plates
Member fabrication part number

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Cold-Formed Metal Framing


100

See B10

200

Generic element modeling to include:

300

Rough architectural masses


Desired member depth
Desired member spacing

Specific element modeling to include:

model with specific locations and geometries

Element information defined with notes or 2D details may include:

350

Member size, depth, and material with sloping geometry


Spacing and end elevations
Design Loads
Deflection Criteria

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Members modeled at any interface with wall edges (top,


bottom, sides) or opening through wall
Members coming out of the plan of walls which includes but
is not limited to kickers, diagonal bracing, etc.
Bridging or straps
Fabrication element modeling to include but not limited to:

Welds
Connections
Member fabrication part number
Any part required for complete installation

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

24

Level of Development
Specification
Version: DRAFT 2013

Wood Floor Truss


100

See B10

200

Generic element modeling to include:

300

Basic floor loading criteria and


geometry would be defined with a
narrative and would include but is
not limited to:
o Live
o Dead
o Wind
o Vibration
o Expected depth

Expected depth
Top chord or bottom chord bearing
Truss Orientation

Specific element modeling to include:

Truss size, depth, and material


with sloping geometry
Spacing and end elevations
Support locations

Element information defined with notes or


2D details may include:

350

400

Member designation, load


capacity and deflection criteria
Design loads

Actual element modeling to include but not


limited to information needed for cross
trade collaboration such as:

Actual final truss profile with panel


points.

Bridging and lateral braces.

Fire protection coating

Any miscellaneous framing


pertaining the truss

Erection details for installation

Chord and web member section


profiles are actually defined

Truss layout in coordination with


deck fasteners would be
confirmed

Hold down locations for large


bolts.

Fabrication element modeling to include


but not limited to:

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

Truss Capacity

Connection plates

Member fabrication part number

www.bimforum.org/lod

This element level modeling shall include


all information needed to fully define the
fabrication and installation of the element.
Additional non-modeled information may
be included into the element. All
connection plates modeled

B1010.20 Floor Decks, Slabs, and Toppings


Wood Floor Deck
100

See B10

200

See B1010

300

Specific element modeling to include:

Diaphragm load and deflection criteria


Deck orientation
Deck material and thickness
Applicable slopes
Expected Framing member profiles, spacing, and material

Element information defined with notes or 2D details may include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Deck fasteners
Typical framing details

Deck edge location


Actual framing member and location per manufacture
All miscellaneous framing including braces, kickers, etc.
Deck openings modeled with support framing around
openings
Point load locations
Actual opening locations and sizes defined

Fabrication element modeling to include but not limited to:

All framing accessory and fasteners modeled per expected


installation
Waterproofing

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

26

Level of Development
Specification
Version: DRAFT 2013

Metal Floor Deck


100

See B10

200

See B1010

300

Specific element modeling to include:

Diaphragm load and deflection criteria


Deck material and thickness
Expected Framing member profiles, spacing, and material
Opening locations are prescriptively defined with notes for
additional misc. framing
Point load locations

Element information defined with notes or 2D details may include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Deck fasteners
Typical framing details
Typical weld specifications
Reinforcing

Deck edge location


Deck splice and end lap locations
Actual deck profile and flute locations per manufacture
All miscellaneous framing including braces, kickers, etc.
Deck openings modeled with support framing

Fabrication element modeling to include but not limited to:

All framing accessory and fasteners modeled per expected


installation
Welds
Waterproofing

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

Composite Floor Deck


100

See B10

200

See B1010

300

Specific element modeling to include:

Diaphragm load and deflection criteria


Expected deck material and thickness
Expected Framing member profiles, spacing, material
Opening locations are prescriptively defined with notes for
additional misc. framing

Element information defined with notes or 2D details may include:

350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Deck fasteners
Typical framing details
Typical weld specifications
Camber
Shear studs
Toppings

Deck edge location


Deck profile and flute locations per manufacture
Deck splice and end lap locations
Actual framing member and location per manufacture
All miscellaneous framing including deck support, deck
closure, shear studs, etc.
Slab openings modeled with support framing around
openings
Point load locations
Slab reinforcing may need to modeled per BIM mangers
request

Fabrication element modeling to include but not limited to:

All framing accessory and fasteners modeled per expected


installation
All slab reinforcing
Welds
Waterproofing

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

28

Level of Development
Specification
Version: DRAFT 2013

Concrete
100

See B10

200

Generic concrete superstructure to have:

300

Type of structural concrete system


Defined structural grid
Approximate geometry (e.g. depth) of structural elements

Specific element modeling to include:

Specific sizes and locations of main concrete structural


members modeled per defined structural grid with correct
orientation.
Concrete defined per spec (strength, air entrainment,
aggregate size, etc.).

Element information defined with notes or 2D details may include:


Reinforcing
Post-tension profiles and strand locations
Penetrations for items such as MEP.
Finishes, camber, chamfers, ect.
Typical details
All embeds and anchor rods identified in 2D
350

Actual element modeling to include but not limited to information


needed for cross trade collaboration such as:

400

Reinforcement called out, modeled if required by BIM


manager, typically only in congested areas.
Pour joints and sequences to help in identifying, reinforcing
lap spice, scheduling, ect.
Expansion Joints
Anchor rods
Post-tension profile and strands called out with a narrative or
modeled if required by the BIM manager.
All embed elements
Elevations and location of elements
Penetrations for items such as MEP
Any permanent forming or shoring components

Fabrication element modeling to include but not limited to:

All reinforcement including post tension elements detailed


and modeled
Finishes, camber, chamfer, etc.

This element level modeling shall include all information needed to


fully define the fabrication and installation of the element. Additional
non-modeled information may be included into the element.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B20 Exterior Vertical Enclosures


100

Narrative containing percentage of materials (e.g. solid vs.


glazed); or solid mass model representing overall building
volume.

B2010 Exterior Walls


100

See B20

200

Generic wall objects separated by type of material (e.g. brick wall vs.
curtain wall); wall thicknesses and detailed locations still flexible;
mullion spacing may be included as a single-line grid pattern.

300

Composite model assembly with overall thickness that accounts for


veneer, structure, insulation, air space, and interior skin specified for
the wall system. (Refer to LOD350 and LOD400 for individually
modeled elements)
Specification of assembly materials shall be attached to the model
elements as non-graphical information.Penetrations are modeled to
nominal dimensions for major wall openings such as windows, doors,
and large mechanical elements.

350

Dependent on 350 being provided by host objects such as windows,


doors, etc. Headers and jambs must be modeled.

30

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B2010.10 Exterior Wall Veneer


Description: Nonstructural outside face elements of exterior walls. Includes precast concrete, unit masonry,
EIFS, manufactured siding, and stucco.
100

See B20

200

See B2010

300

See B2010

350

Exterior wall veneer modeled as a separate element.


All openings modeled to actual rough dimensions.
Precast concrete panels are individually modeled. Connection
points are specified.

400

All assembly components modeled including, but not limited to


masonry units, reinforcing, flashing, sealants, anchors, and
embeds.

B2010.20 Exterior Wall Construction


Description: Exterior wall construction including backup systems for wall veneer. May be vertical load bearing.
Includes cast-in-place concrete walls, precast concrete walls, unit masonry walls, metal framed wall systems,
and wood framed wall systems.
100

See B20

200

See B2010

300

See B2010

350

Exterior wall construction modeled as a separate element.


All openings modeled to actual rough dimensions. Headers
and jamb framing are modeled.
Framing, unit masonry, or reinforcement specification included
as non-graphical information.

400

All assembly components modeled including, but not limited to


studs, tracks, masonry units, reinforcing, sheathing, and
insulation.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B2010.30 Exterior Wall Interior Skin


Description: Materials to provide finish or protective covering on inside of face of exterior walls. May include
insulation and vapor retarder.
100

See B20

200

See B2010

300

See B2010

350

Exterior wall interior skin modeled as a separate element.


All openings modeled to actual rough dimensions.
Framing, unit masonry, or reinforcement specification included
as non-graphical information.

400

All assembly components modeled including, but not limited to


studs, tracks, masonry units, reinforcing, sheathing, and
insulation.

B2010.50 Parapets
Exterior wall construction above plane of roof.
< Use specifications for B2010, B2010.10, B2010.20, and B2010.30. >

B2010.60 Equipment Screens


Exterior wall construction to screen equipment from public view.
100

See B20

200

See B2010

300

Overall assembly modeled to actual thickness with surface


representation of fenestration condition.

350

Framing member sizing represented in quantity, size, shape,


location and orientation.
Surface area, joint sizing, framing member sizing represented
in quantity, size, shape, location and orientation.

400

Connections are modeled (anchors, embeds, etc.)

32

Level of Development
Specification
Version: DRAFT 2013

B2020 Exterior Windows


100

See B20

200

Windows approximate in terms of location, size, count and type.


Units can be modeled as a simple, monolithic component; or
represented with simple frame and glazing.
Nominal unit size is provided.

B2020.10 Exterior Operating Windows


Also includes: B2020.20 - Exterior Fixed Windows; B2020.50 - Special Function Windows
300

Units are modeled based on specified location and nominal size.


Outer geometry of window frame elements and glazing modeled to
within 1/8 [1 mm] precision.
Operation is indicated
Non-graphic information associated with model element:

350

Modeled units will meet the minimum requirements of LOD 300, in


addition to the following:

400

Aesthetic characteristics (finishes, glass types)


Performance characteristics in narrative, but associated
with element in model (i.e. U-value, wind loading, blast
resistance, structural, air, thermal, water, sound)
Attachment method of window to structure

Rough opening dimensions


Embed geometry
All connection attachment details

Modeled units will meet the minimum requirements up to and


including LOD 350, in addition to the following:

Frame profiles
Glazing sub-components (gaskets)
Attachment components

B2020.20 Exterior Fixed Windows


[See B2020.10]

B2020.30 Exterior Window Wall


[See B2020.10]

B2020.50 Exterior Special Function Windows


[See B2020.10]

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B2050 Exterior Doors and Grilles


100

Simple representation of a door unit. Size, count, and location are


approximate.

200
Units can be modeled as a simple, monolithic component; or
represented with simple frame and glazing.
Nominal unit size is provided.

B2050.10 Exterior Entrance Doors


Exterior personnel door assemblies at main entrances. Includes automatic, revolving, balanced, and other
special operating entrance doors, and sliding storefront wall systems.
100

See B20

200

See B2050

300

Doors and door frames defined by type, hardware; narrative


associated with specific model elements; envelope and space
requirements are represented in model element.
Specific doors, frames and hardware. Hardware set functionality and
types are specified.

350

Modeled units will meet the minimum requirements of LOD 300, in


addition to the following:

400

Rough opening is modeled (if applicable)


Major framing elements are modeled at jambs and head

Modeled units will meet the minimum requirements of LOD 350, in


addition to the following:

B2050.20 Exterior Utility Doors


Exterior personnel door assemblies other than at main entrances.
100

See B20

200

See B2050

300

Doors and door frames defined by type, hardware; narrative


associated with specific model elements; envelope and space
requirements are represented in model element.
Specific doors, frames and hardware. Hardware set functionality and
types are specified.

350

Modeled units will meet the minimum requirements of LOD 300, in


addition to the following:

400

Rough opening is modeled


Major framing elements are modeled at jambs and head

Modeled units will meet the minimum requirements of LOD 350, in


addition to the following:

34

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B2050.30 Exterior Oversize Doors


Large exterior door assemblies to allow for passage of large objects involving various operating methods.
100

See B20

200

See B2050

300

Doors and door frames defined by type, hardware; narrative


associated with specific model elements; envelope and space
requirements are represented in model element.
Specific doors, frames and hardware. Hardware set functionality and
types are specified.

350

Modeled units will meet the minimum requirements of LOD 300, in


addition to the following:

400

Clearance zones are modeled for operation of overhead doors


Enclosures and motor housings are modeled with overall
nominal dimensions

Rough opening is modeled (if applicable)


Major framing elements are modeled at jambs and head

Modeled units will meet the minimum requirements of LOD 350, in


addition to the following:

B2050.40 Exterior Special Function Doors


[See B2050.20 Exterior Utility Doors]

B2050.60 Exterior Grilles


Exterior devices of open construction to provide moveable barrier to provide access through wall or other
divider.
100

See B20

200

See B2050

300

See B2050

350

Modeled units will meet the minimum requirements of LOD 300, in


addition to the following:

400

Rough opening is modeled (if applicable)


Major framing elements are modeled at jambs and head

Modeled units will meet the minimum requirements of LOD 350, in


addition to the following:

B2050.70 Exterior Gates


Exterior devices of solid or open construction to provide moveable barrier to provide access through wall or
other divider.
[See B2050.60 Exterior Grilles]

B2050.90 Exterior Door Supplementary Components


Includes frames, hardware, glazing and louvers that are part of door to be included with exterior door elements
above as appropriate.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B2070 - Exterior Louvers and Vents


100

Represented as a calculated value, usually derived as a percentage of


exterior vertical surface area; or, as a ratio to overall habitable space.

200

Generic model element that is indicative of approximate area and


location of intended louver/vent.

B2070.10 Exterior Louvers


100

See B20

200

See B2070

300

Specific model element, indicative of specific area and location of


intended louver/vent.

350

Modeled units will meet the minimum requirements of LOD 300, in


addition to the following:

400

Includes specific frame (boundary dimensions) and blades.


Opening for louver is cut from host wall

Rough opening is modeled (if applicable)


Major framing elements are modeled at jambs and head

Modeled units will meet the minimum requirements of LOD 350, in


addition to the following:

B2070.50 Exterior Vents


[See B2070.10 Exterior Louvers]

B2080 - Exterior Wall Appurtenances


B2080.10 Exterior Fixed Grilles and Screens
Exterior enclosures, grilles and screens of wood, metal, plastic, and other materials for a variety of purposes
including screening of equipment.

B2080.30 Exterior Opening Protection Devices


Manufactured items such as louvers, fins, shutters, demountable panels, awnings, and sun screens to provide
sun control, privacy, security, insulation, and storm protection on exterior of windows, skylights, and entrances.
Includes fixed and moveable, manually and electrically operated, and automatically controlled devices.

B2080.50 Exterior Balcony Walls and Railings


Manufactured items such as louvers, fins, shutters, demountable panels, awnings, and sun screens to provide
sun control, privacy, security, insulation, and storm protection on exterior of windows, skylights, and entrances.
Includes fixed and moveable, manually and electrically operated, and automatically controlled devices.

B2080.70 Exterior Fabrications


[See general LOD definitions.]

B2080.80 Bird Control Devices


[See general LOD definitions.]
36

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B2090 Exterior Wall Specialties


Complete fabrication of metal, wood, and fiberglass, including accessories and appurtenances. For example,
clocks, below-grade egress assemblies, and window wells.
See general LOD definitions.

B30 Exterior Horizontal Enclosures


100

Narrative, information attached to other model elements.

B3010 Roofing
100

Narrative, information attached to other model elements.

200

Generic assembly that may contain spatial (layer) allowance for


structural slab/deck and/or framing system.

300

Individual substrate layers may not be separately modeled, but


they are specified and their extents are shown precisely.

Roof structure is modeled separately.

B3010.10 Steep Slope Roofing


Lapped roofing shingles, shakes and roofing tiles, including fastening and flashing products and methods.
[See B1020 - Roof Construction. Steep slope roofing material is often modeled as a layer within the overall roof
structure assembly.]

B3010.50 Low Slope Roofing


Includes membrane roofing of various types and protected membrane roofing, including fastening and flashing
products.
100

See B30

200

See B3010

300

Specific material thickness, openings are subtracted from solid.


Framing is a separate assembly, see SUPERSTRUCTURE.
Drainage pitches are modeled.

350
400

B3010.70 Canopy Roofing

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B3010.90 Roofing Supplementary Components


Includes substrate boards, vapor retarder, air barriers, deck insulation, flashing and sheet metal, and
expansion joints to be included with roofing elements above as appropriate.
100

See B30

200

See B3010

300
350
400

B3020 Roof Appurtenances


100

See B30

200

Not modeled

300

B3020.10 Roof Accessories


Includes ladders, curbs, vents, walkways, and snow guards.
[See also: B1080.80 - Ladders]
100

See B30

200

Not modeled

300

Ladders: Specific assemblies indicating length, width and


connection method.

350
400

B3020.30 Roof Specialties


Includes cupolas, spires, steeples, and weathervanes.
See general LOD definitions.

B3020.70 Rainwater Management


Includes conductor heads, gutters, downspouts, scuppers, and splash blocks.
100

See B30

200

Generic assemblies.
[See also D2030.20 Stormwater Drainage Equipment]

300

Mfr. Specific drains, all connected drainage (?). Locations


specific.

350
400

38

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B3040 Traffic Bearing Horizontal Enclosures


100

See B30

200

Not modeled.

300

B3040.10 Traffic Bearing Coatings


Includes surface applied waterproofing exposed to weather and suitable for pedestrian or vehicular traffic.
[Not Modeled]

B3040.30 Horizontal Waterproofing Membrane


Includes substrate board, deck insulation, vapor retarder, sheet metal flashing and trim, flexible flashing, and
expansion joints.
100

See B30

200

Not modeled

300

Specific material thickness, manufacturer, finish, color

350
400

B3040.50 Wear Surfaces


Wearing surfaces on top of horizontal waterproofing membrane that are suitable for pedestrian or vehicular
traffic.
100

Not modeled

200

Not modeled

300

Specific material thickness, manufacturer, finish, color

350
400

Placement of pedestals?

B3040.90 Horizontal Enclosure Supplementary Components


Includes substrate board, deck insulation, vapor retarder, sheet metal flashing and trim, flexible flashing, and
expansion joints to be included with horizontal enclosure elements above as appropriate.
[Supplementary components may be modeled with other assemblies as listed in the tables above.]

B3060 Horizontal Openings


100

Not modeled.

200

Not modeled.

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

B3060.10 Roof Windows and Skylights


Wearing surfaces on top of horizontal waterproofing membrane that are suitable for pedestrian or vehicular
traffic.
100

Not modeled.

200

Not modeled.

300

Specific material thickness, manufacturer, finish, color.

350
400

Placement of pedestals?

B3060.50 Vents and Hatches


Other roof openings such as roof hatches, smoke vents, and gravity roof ventilators.

B3060.90 Horizontal Opening Supplementary Components


Includes: Frames, hardware, glazing, flashing, and joint sealants to be included with horizontal opening
elements above as appropriate.
[Supplementary components may be modeled with other assemblies as listed in the tables above.]

B3080 Overhead Exterior Enclosures


B3080.10 Exterior Ceilings
100

Not modeled.

150

Not modeled

200

Generic assemblies

300

Specific assemblies in specific locations

B3080.20 Exterior Soffits


100

Not modeled.

150

Not modeled

200

Generic assemblies

300

Specific assemblies in specific locations

B3080.30 Exterior Bulkheads


100

Not modeled.

150

Not modeled

200

Generic assemblies

300

Specific assemblies in specific locations

40

Level of Development
Specification
Version: DRAFT 2013

C INTERIORS
C10 Interior Construction
100

Interior construction model elements can be placed as a


generic representation with their default parameters, used as
placeholders for assurance of program, code, zoning
compliance and visualization of the conceptual design.

200

Interior construction model elements are graphically


represented as generic systems, objects or assemblies with
approximate location and orientation, including height. Nongraphic data may be attached to elements.

300

Interior construction model elements are graphically


represented as specific systems, objects or assemblies with
specific location and orientation. Non-graphic data should be
fully populated, including specific type, life safety, finish and
similar parameters.

350

Interior construction model elements are graphically


represented with additional detail not normally shown in the
design intent documentation necessary for cross trade
interference check.

400

Interior construction model elements are graphically


represented as detailed elements, and may include
manufacturer specific non-graphic data.

500

Interior construction model elements are graphically


represented as detailed elements actual in the as built
condition and should include all pertinent manufacturer specific
non-graphic data.

C1010 Interior Partitions


100

Generic representation or massing of core elements (shafts,


corridors, separation walls, etc.) necessary for assurance of
program, code, zoning compliance and visualization of the
conceptual design.

200

Generic objects with approximate location, orientation and


height necessary for other system definitions, including all
required parametric data.

300

Specific and accurate assemblies with all hardware and


accessories tagged and scheduled. Non-graphical data should
be fully populated for each separate assembly, including all
required parametric data.

350

Inclusion of any accessory backing and structural bracing that


may affect/conflict with other scopes of work.

400

Fabrication details including blocking/backing and any


necessary structural supports, actual manufacturer's details,
identity and parametric data.

500

Installation details that reflect actual as built conditions and


corresponding manufacturers identity and parametric data.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1010.10 Interior Fixed Partitions


100

Shafts, corridors & separation walls for intended use.

200

Graphical representation with required parametric data.

300

Specific partition types with accurate assemblies, dimensions,


locations and heights, containing all required tagging,
scheduling and parametric data.

350

Detailed blocking, kickers, cross bracing, etc.

400

All assembly components including studs, tracks, bracing,


insulation, sheathing and openings ready for fabrication.
Include specific identity and related parametric data

500

See C1010

C1010.20 Interior Glazed Partitions


100

Not modeled, info attached to other elements, if required.

200

See C1010.10

300

See C1010.10

350

See C1010.10

400

See C1010.10

500

See C1010

C1010.40 Interior Demountable Partitions


100

See C1010

200

See C1010

300

See C1010.10

350

See C1010.10

400

All assembly components specific to manufacturer's product.


Include all identity and related parametric data

500

See C1010

42

Level of Development
Specification
Version: DRAFT 2013

C1010.50 Interior Operable Partitions


100

See C1010.20

200

See C1010.10

300

Specific partition types with accurate dimensions, locations and


heights, containing all required hardware and accessories,
support structure, tagging, scheduling and parametric data and
any necessary connection points to other scopes of work.

350

Detailed blocking, kickers, cross bracing, detailed overhead


supports and mechanical connections.

400

All assembly components including tracks, panels, hardware


and supports ready for fabrication. Include specific identity and
related parametric data

500

See C1010

C1010.70 Interior Screens


100

See C1010.20

200

See C1010.10

300

Graphical representation with required parametric data.

350

See C1010

400

Graphical representation with specific identity and parametric


data.

500

See C1010

C1010.90 Interior Partitions Supplementary Components


100

See C1010.20

200

See C1010.10

300

See C1010.70

350

See C1010

400

See C1010.70

500

See C1010

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1020 Interior Windows


100

See C1010

200

Generic windows with approximate size, location and


orientation.

300

Specific and accurate assemblies with all hardware and


accessories tagged and scheduled. Non-graphical data should
be fully populated for each separate assembly, including all
required parametric data.

350

Inclusion of any accessory backing and structural bracing that


may affect/conflict with other scopes of work.

400

Fabrication details including blocking/backing and any


necessary structural supports, actual manufacturer's details,
profiles, hardware, identity and parametric data.

500

Installation details that reflect actual as built conditions and


corresponding manufacturer's identity and parametric data.

C1020.10 Interior Operating Windows


100

Not modeled, info attached to other elements, if required.

200

Graphical representation with required parametric data.

300

Specific window types with specific dimensions, locations &


heights, properly tagged & scheduled.

350

Supplemental rigid bracing

400

All assembly components including profiles, hardware, glazing,


attachments and supports ready for fab.

500

See C1020

C1020.20 Interior Fixed Windows


100

See C1020.10

200

See C1020.10

300

See C1020.10

350

See C1020.10

400

See C1020.10

500

See C1020

44

Level of Development
Specification
Version: DRAFT 2013

C1020.50 Interior Special Function Windows


100

See C1020.10

200

See C1020.10

300

See C1020.10

350

See C1020.10

400

See C1020.10

500

See C1020

C1020.90 Interior Window Supplementary Components


100

See C1020.10

200

See C1020.10

300

See C1020.10

350

See C1020.10

400

See C1020.10

500

See C1020

C1030 Interior Doors


100

See C1010

200

Generic doors with approximate size, location and orientation


and required parametric data.

300

Specific and accurate assemblies with all hardware and


accessories tagged and scheduled, and inclusion of any
necessary connection points to other scopes of work. Include
all required parametric data for each separate assembly.

350

See C1010

400

Fabrication details including blocking/backing, king-stud


placement, structural supports and actual manufacturer details,
profiles, hardware, identity and parametric data

500

Installation details that reflect actual as built conditions and


corresponding manufacturer's identity and parametric data.

C1030.10 Interior Swinging Doors


100

Corridors & separation walls for intended use.

200

Graphical representation with required parametric data.

300

Specific door types with specific dimensions, locations &


heights, properly tagged & scheduled.

350

Supplemental rigid bracing

400

All assembly components including profiles, hardware,


attachments and supports ready for fabrication.

500

See C1030

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1030.20 Interior Entrance Doors


100

Not modeled, info attached to other elements, if required.

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.10

500

See C1030

C1030.25 Interior Sliding Doors


100

See C1030.20

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.10

500

See C1030

C1030.30 Interior Folding Doors


100

See C1030.20

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.25

500

See C1030

C1030.40 Interior Coiling Doors


100

See C1030.20

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.25

500

See C1030

46

Level of Development
Specification
Version: DRAFT 2013

C1030.50 Interior Panel Doors


100

See C1030.20

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.10

500

See C1030

C1030.70 Interior Special Function Doors


100

See C1030.20

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.10

500

See C1030

C1030.80 Interior Access Doors and Panels


100

See C1030.20

200

See C1030.10

300

See C1030.10

350

See C1030.10

400

See C1030.10

500

See C1030

C1030.90 Interior Door Supplementary Components


100

See C1030.20

200

See C1030.10

300

See C1030.10

400

Graphical representation with specific identity and parametric


data.

500

See C1030

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1040 Interior Grilles and Gates


100

May be graphically represented or verbally described.

200

Generic objects with approximate size and placement, and


required parametric data.

300

Specific and accurate assemblies with all hardware and


accessories tagged and scheduled, and inclusion of any
necessary connection points to other scopes of work. Include
all required parametric data for each separate assembly.

350

Inclusion of any accessory backing and structural bracing that


may affect/conflict with other scopes of work.

400

Fabrication details including blocking/backing, structural


supports and actual manufacturer details, profiles, hardware,
identity and parametric data.

500

Installation details that reflect actual as built conditions and


corresponding manufacturer's identity and parametric data.

C1040.10 Interior Grilles and Gates


100

Not modeled, info attached to other elements, if required.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

400

See C1030.10

500

See C1040

C1040.50 Interior Gates


100

See C1040.10

200

See C1040.10

300

See C1040.10

350

See C1040.10

400

See C1030.10

500

See C1040

48

Level of Development
Specification
Version: DRAFT 2013

C1060 Raised Floor Construction


100

See C1040

200

Generic objects with approximate size and placement, and


required parametric data.

300

Specific and accurate assemblies, including grid spacing, with


all hardware and accessories tagged and scheduled. Include all
required parametric data for each separate assembly.

350

See C1010

400

Fabrication details including blocking/backing, structural


supports and actual manufacturer details, profiles, hardware,
identity and parametric data.

500

Installation details that reflect actual as built conditions and


corresponding manufacturer's identity and parametric data.

C1060.10 Access Flooring


100

Not modeled, info attached to other elements, if required

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

350

Accurate floor grid layout and pedestal placement

400

All assembly components including frame, floor tiles, pedestals


and cross bracing ready for fabrication.

500

See C1060

C1060.30 Platform/Stage Floors


100

See C1060.10

200

See C1060.10

300

See C1060.10

350

Accurate sub-structure assemblies.

400

All assembly components including fixed construction of raised


floors ready for fabrication.

500

See C1060

C1070 Suspended Ceiling Construction


100

See C1040

200

See C1040

300

See C1060

350

See C1010

400

See C1020

500

See C1010

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1070.10 Acoustical Suspended Ceilings


100

Not modeled, info attached to other elements, if required.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

350

Extruded grid placement and any accessory back-up


components.

400

All assembly components including tees, hangers and tiles


ready for fabrication.

500

See C1070

C1070.20 Suspended Plaster and Gypsum Board Ceilings


100

See C1070.10

200

See C1070.10

300

See C1070.10

350

Incorporation of all accessory back-up components.

400

All assembly components including furring chanels, hangers,


lath, plaster coats and gypsum boards ready for fabrication.

500

See C1070

C1070.50 Specialty Suspended Ceilings


100

See C1070.10

200

See C1070.10

300

See C1070.10

350

See C1070.20

400

All assembly components including framing, hangers and tiles


ready for fabrication.

500

See C1070

50

Level of Development
Specification
Version: DRAFT 2013

C1070.70 Special Function Suspended Ceilings


100

See C1070.10

200

See C1070.10

300

See C1070.10

350

See C1070.20

400

See C1070.50

500

See C1070

C1070.90 Ceiling Suspension Components


100

See C1070.10

200

See C1070.10

300

See C1070.10

350

See C1070.20

400

Graphical representation with specific identity and parametric


data.

500

See C1070

C1090 Interior Specialties


100

See C1040

200

See C1040

300

See C1060

350

See C1010

400

Fabrication details including blocking/backing, structural


supports and actual manufacturer details, profiles, hardware,
identity and parametric data.

500

Installation details that reflect actual as built conditions and


corresponding manufacturer's identity and parametric data.

C1090.10 Interior Railings and Handrails


100

Not modeled, info attached to other elements, if required.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

350

Backing & imbedded inserts.

400

All assembly components including rails, pickets, infill panels,


fasteners and supports ready for fabrication.

500

See C1090

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1090.15 Interior Louvers


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

Supplemental rigid bracing.

400

See C1090.10

500

See C1090

C1090.20 Information Specialties


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

C1090.25 Compartments and Cubicles


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

C1090.30 Service Walls


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

52

Level of Development
Specification
Version: DRAFT 2013

C1090.35 Wall and Door Protection


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

C1090.40 Toilet, Bath and Laundry Accessories


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

C1090.45 Interior Gas Lighting


100

See C1090.10

200

See C1090.10

300

Specific types with specific dimensions, locations, properly


tagged & scheduled, including any necessary connection points
to other scopes of work.

350

See C1090.10

400

See C1090.10

500

See C1090

C1090.50 Fireplaces and Stoves


100

See C1090.10

200

See C1090.10

300

See C1090.45

350

See C1090.10

400

See C1090.10

500

See C1090

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C1090.60 Safety Specialties


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

54

Level of Development
Specification
Version: DRAFT 2013

C1090.70 Storage Specialties


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

C1090.90 Other Interior Specialties


100

See C1090.10

200

See C1090.10

300

See C1090.10

350

See C1090.10

400

See C1090.10

500

See C1090

C20 Interior Finishes


100

Not represented in the model, unless necessary to establish


visualization of the conceptual design, and does not satisfy the
requirements for LOD 200.

200

Interior finish model elements may be graphically represented


as generic materials or as non-graphic data attached to Interior
construction elements where needed to support other systems.

300

Interior finish model elements are graphically represented as


specific systems, objects or assemblies with specific location,
orientation and thickness. Non-graphic data should be fully
populated, and may be attached to other Interior Construction
elements

350

Interior construction model elements are graphically


represented with additional detail and information not normally
shown in the design intent documentation necessary for cross
trade interference check.

400

Interior finish model elements are graphically represented as


detailed assemblies or non-graphic data attached to other
Interior construction elements

500

Interior finish model elements are graphically represented as


detailed as built assemblies and should include all pertinent
manufacturer specific non-graphic data.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C2010 Wall Finishes


100

No info.

200

Generic materials, approximate dimensions, thickness and


elevations.

300

Finishes may not be actually modeled, but they are specified


and their extents are shown precisely.

350

Finishes are actually modeled for visual cross trade


coordination.

400

Detailed assemblies or materials that may be attached to other


interior construction elements.

500

Detailed as built assemblies and specific corresponding


manufacturer's non graphic data.

C2010.10 Tile Wall Finish


100

No info.

200

Graphical representation with required parametric data or info


attached to other elements properly scheduled.

300

Objects modeled to depict thickness (may be attached to other


objects/assemblies) where it may affect other scopes of work.

C2010.20 Wall Paneling


100

No info.

200

See C2010.10

300

See C2010.10

C2010.30 Wall Coverings


100

No info.

200

See C2010.10

300

See C2010.10

C2010.35 Wall Carpeting


100

No info.

200

See C2010.10

300

See C2010.10

C2010.50 Stone Facing


100

No info.

200

See C2010.10

300

See C2010.10

56

Level of Development
Specification
Version: DRAFT 2013

C2010.60 Special Wall Surfacing


100

No info.

200

See C2010.10

300

See C2010.10

C2010.70 Wall Painting and Coating


100

No info.

200

See C2010.10

300

See C2010.10

C2010.80 Acoustical Wall Treatment


100

No info.

200

See C2010.10

300

See C2010.10

C2010.90 Wall Finish Supplementary Components


100

No info.

200

See C2010.10

300

See C2010.10

C2020 Interior Fabrications


100

No info.

200

See C2010

300

See C2010

400

See C2010

500

See C2010

C2030 Flooring
100

No info.

200

Finishes may be generically modeled with approximate


dimensions, or attached to other model elements.

300

Modeled with specific thickness and grid layout where finishes


affect details. All finishes are specified and their extents are
shown precisely.

350

Finishes are actually modeled for visual cross trade


coordination.

400

See C2010

500

See C2010

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C2030.10 Flooring Treatment


100

No info.

200

Graphical representation with required parametric data or info


attached to other elements properly scheduled.

300

Objects modeled to depict thickness (may be attached to other


objects/assemblies) where it may affect other scopes of work.

C2030.20 Tile Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.30 Specialty Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.40 Masonry Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.45 Wood Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.50 Resilient Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.60 Terrazzo Flooring


100

No info.

200

See C2030.10

300

See C2030.10

58

Level of Development
Specification
Version: DRAFT 2013

C2030.70 Fluid-Applied Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.75 Carpeting
100

No info.

200

See C2030.10

300

See C2030.10

C2030.80 Athletic Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.85 Entrance Flooring


100

No info.

200

See C2030.10

300

See C2030.10

C2030.90 Flooring Supplementary Components


100

No info.

200

See C2030.10

300

See C2030.10

C2040 Stair Finishes


100

No info.

200

See C2030

300

Modeled specifically where finishes affect details. All finishes


are specified and their extents are shown precisely.

400

See C2010

500

See C2010

C2040.20 Tile Stair Finish


100

No info.

200

Graphical representation with required parametric data or info


attached to other elements properly scheduled.

300

Objects modeled to depict thickness (may be attached to other


objects/assemblies) where it may affect other scopes of work.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

C2040.40 Masonry Stair Finish


100

No info.

200

See C2040.20

300

See C2040.20

C2040.45 Wood Stair Finish


100

No info.

200

See C2040.20

300

See C2040.20

C2040.50 Resilient Stair Finish


100

No info.

200

See C2040.20

300

See C2040.20

C2040.60 Terrazzo Stair Finish


100

No info.

200

See C2040.20

300

See C2040.20

C2040.75 Carpeted Stair Finish


100

No info.

200

See C2040.20

300

See C2040.20

C2050 Ceiling Finishes


100

No info.

200

See C2030

300

See C2040

350

See C2010

400

See C2010

500

See C2010

C2050.10 Plaster and Gypsum Board Finish


100

No info.

200

Graphical representation with required parametric data or info


attached to other elements properly scheduled.

60

Level of Development
Specification
Version: DRAFT 2013

C2050.20 Ceiling Paneling


100

No info.

200

See C2050.10

C2050.70 Ceiling Painting and Coating


100

No info.

200

See C2050.10

C2050.80 Acoustical Ceiling Treatment


100

No info.

200

See C2050.10

C2050.90 Ceiling Finish Supplementary Components


100

No info.

200

See C2050.10

C2090 Interior Finish Schedules


100

No info.

200

See C2010

300

Specific materials. Precise heights, locations of ceiling


devices.

400

Detailed non-graphic data attached to other interior


construction elements.

500

Detailed as built conditions and specific corresponding


manufacturer's non graphic data.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D SERVICES
D10 Conveying
100
200

Generic representations of the envelope of the system in terms


of size and location.

300

Specific representations of the envelope of the system in terms


of size and location.

400

Actual representations of the envelope of the system in terms


of size and location plus connection points.

D1010 Vertical Conveying Systems


100

Narrative, info attached to other elements or quantitative call


outs.

200

Approximate size/shape/location (1).

300

Specific models, precise size, shape & location.

400

Any necessary fabrication details.

500

Detailed as built conditions and specific corresponding


manufacturer's non graphic data.

D1010.10 Elevators
100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

D1010.20 Lifts
100

See D1010.10

200

See D1010.10

300

See D1010.10

D1010.30 Escalators
100

See D1010.10

200

See D1010.10

300

See D1010.10

D1010.50 Dumbwaiters
100

See D1010.10

200

See D1010.10

300

See D1010.10
62

Level of Development
Specification
Version: DRAFT 2013

D1010.60 Moving Ramps


100

See D1010.10

200

See D1010.10

300

See D1010.10

D1030 Horizontal Conveying


100

See D1010

200

See D1010

300

See D1010

400

See D1010

500

See D1010

D1030.10 Moving Walks


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

D1030.30 Turntables
100

See D1030.10

200

See D1030.10

300

See D1030.10

D1030.50 Passenger Loading Bridges


100

See D1030.10

200

See D1030.10

300

See D1030.10

D1030.70 People Movers


100

See D1030.10

200

See D1030.10

300

See D1030.10

D1050 Material Handling


100

See D1010

200

See D1010

300

See D1010

400

See D1010

500

See D1010

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D1050.10 Cranes
100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

D1050.20 Hoists
100

See D1050.10

200

See D1050.10

300

See D1050.10

D1050.30 Derrecks
100

See D1050.10

200

See D1050.10

300

See D1050.10

D1050.40 Conveyors
100

See D1050.10

200

See D1050.10

300

See D1050.10

D1050.50 Baggage Handling Equipment


100

See D1050.10

200

See D1050.10

300

See D1050.10

D1050.60 Chutes
100

See D1050.10

200

See D1050.10

300

See D1050.10

D1050.70 Pneumatic Tube Systems


100

See D1050.10

200

See D1050.10

300

See D1050.10

64

Level of Development
Specification
Version: DRAFT 2013

D1080 Operable Access Systems


100

See D1010

200

See D1010

300

See D1010

400

See D1010

500

See D1010

D1080.10 Suspended Scaffolding


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly


tagged & scheduled.

D1080.20 Robe Climbers


100

See D1080.10

200

See D1080.10

300

See D1080.10

D1080.30 Elevating Platforms


100

See D1080.10

200

See D1080.10

300

See D1080.10

D1080.40 Powered Scaffolding


100

See D1080.10

200

See D1080.10

300

See D1080.10

D1080.50 Building Envelope Access


100

See D1080.10

200

See D1080.10

300

See D1080.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D20 Plumbing
100

Generic elements or quantitative call outs;


conceptual and/or schematic layout/flow diagram;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
element(s);
design performance Information;
approximate access/code clearance requirements represented
in the model
shaft requirements represented in the model

D2010 Domestic Water Distribution


D2010.10 Facility Potable-Water Storage Tanks
100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
tank(s);
design performance Information;
approximate access/code clearance requirements represented
in the model

300

Specific elements;
modeled as design specified size/shape/spacing/location of
tank(s);
approximate allowances for spacing and clearances required
for all specified anchors, supports, vibration and seismic control
that are utilized in the layout of tanks(s);
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of tank(s)
actual size/shape/spacing/clearances required for all specified
anchors, supports, vibration and seismic control that are
utilized in the layout of tanks(s);

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

66

Level of Development
Specification
Version: DRAFT 2013

D2010.20 Domestic Water Equipment


100

See D2010.10

200

Generic elements;
schematic layout with approximate size/shape/location of
equipment;
design performance Information;
approximate access/code clearance requirements represented
in the model

300

Specific elements;
modeled as design specified size/shape/spacing/location of
equipment;
approximate allowances for spacing and clearances required
for all specified anchors, supports, vibration and seismic control
that are utilized in the layout of equipment;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of equipment,
actual size/shape/spacing/clearances required for all specified
anchors, supports, vibration and seismic control that are
utilized in the layout of equipment;

400

See D2010.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D2010.40 Domestic Water Piping


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location
of mains and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location of
pipe/valves/fittings/insulation for risers/mains/branches;
approximate allowances for spacing and clearances
required for all specified hangers, supports, vibration
and seismic control that are to be utilized in the layout
of all risers/mains/branches;
actual access/code clearance requirements represented
in the model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections of
pipe/valves/fittings/insulation for risers/mains/branches;
actual size/shape/spacing/clearances required for all
hangers, supports, vibration and seismic control that are
utilized in the layout of all risers/mains/branches;
actual floor and wall penetrations required represented
in the model

68

Level of Development
Specification
Version: DRAFT 2013
400

See D2010.10

D2010.60 Plumbing Fixtures


100

See D2010.10

200

Generic elements;
schematic layout with approximate size/shape/location
of fixtures;
design performance Information;
carrier and wall width requirements represented in the
model

300

Specific elements;
modeled as design specified
size/shape/spacing/location of fixtures;
approximate allowances for spacing and clearances
required for all specified supports that are to be utilized
in the layout of all fixtures;
actual access/code clearance requirements represented
in the model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of
fixtures/carriers
actual size/shape/spacing/clearances required for all
supports that are utilized in the layout of all fixtures;

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013
400

www.bimforum.org/lod

See D2010.10

D2010.90 Domestic Water Distribution Supplementary Components


100

See D2010.40

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D2010.10

D2020 Sanitary Drainage

70

Level of Development
Specification
Version: DRAFT 2013

D2020.10 Sanitary Sewerage Equipment


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location
of equipment;
design performance Information;
approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified
size/shape/spacing/location of equipment;
approximate allowances for spacing and clearances
required for all specified anchors, supports, vibration
and seismic control that are utilized in the layout of
equipment;
actual access/code clearance requirements represented
in the model

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013
350

www.bimforum.org/lod

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of equipment,
actual size/shape/spacing/clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment;

400

Manufacturer or Contractor elements added to the


model required for fabrication and field installation

72

Level of Development
Specification
Version: DRAFT 2013

D2020.30 Sanitary Sewerage Piping


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location/slope of
pipe/valves/fittings/insulation for risers/mains/branches;
approximate allowances for spacing and clearances
required for all specified hangers, supports, vibration
and seismic control that are to be utilized in the layout
of all risers/mains/branches;
actual access/code clearance requirements represented
in the model

300

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/slope of
pipe/valves/fittings/insulation for risers/mains/branches;
actual size/shape/spacing/clearances required for all
hangers, supports, vibration and seismic control that are
utilized in the layout of all risers/mains/branches;
actual floor and wall penetrations required represented
in the model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of
risers/mains/branches/valves;
actual insulation/floor and wall penetrations represented
in the model

400

See D2020.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D2020.90 Sanitary Drainage Supplementary Components


100

See D2020.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D2020.10

D2030 Building Support Plumbing Systems

74

Level of Development
Specification
Version: DRAFT 2013

D2030.10 Stormwater Drainage Equipment


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
equipment;
design performance Information;
approximate access/code clearance requirements represented
in the model

300

Specific elements;
modeled as design specified size/shape/spacing/location of
equipment;
approximate allowances for spacing and clearances required
for all specified anchors, supports, vibration and seismic control
that are utilized in the layout of equipment;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of equipment,
actual size/shape/spacing/clearances required for all specified
anchors, supports, vibration and seismic control that are
utilized in the layout of equipment;

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D2030.20 Stormwater Drainage Piping


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of mains
and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location/slope of
pipe/valves/fittings/insulation for risers/mains/branches;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all risers/mains/branches;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections/slope of
pipe/valves/fittings/insulation for risers/mains/branches;
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all risers/mains/branches;
actual floor and wall penetrations required represented in the
model

400

See D2030.10

76

Level of Development
Specification
Version: DRAFT 2013

D2030.30 Facility Stormwater Drains


100

See D2030.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all components

400

See D2030.10

D2030.60 Gray Water Systems


100

See D2030.20

200

See D2030.20

300

See D2030.20

350

See D2030.20

400

See D2030.20

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D2030.90 Building Support Plumbing System Supplementary Components


100

See D2030.10

200

See D2030.30

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D2030.20

D2050 General Service Compressed-Air


See D2060.10 Compressed-Air Systems

D2060 Process Support Plumbing Systems

78

Level of Development
Specification
Version: DRAFT 2013

D2060.10 Compressed-Air Systems


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
mains and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location/slope of
equipment/pipe/valves/fittings/insulation for
risers/mains/branches;
approximate allowances for spacing and clearances
required for all specified hangers, supports, vibration and
seismic control that are to be utilized in the layout of all
risers/mains/branches;
actual access/code clearance requirements represented
in the model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections/slope of
equipment/pipe/valves/fittings/insulation for
risers/mains/branches;
actual size/shape/spacing/clearances required for all
hangers, supports, vibration and seismic control that are
utilized in the layout of all risers/mains/branches;
actual floor and wall penetrations required represented
in the model

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D2060.20 Vacuum Systems


100

See D2060.10

200

See D2060.10

300

See D2060.10

350

See D2060.10

400

See D2060.10

D2060.30 Gas Systems


100

See D2060.10

200

See D2060.10

300

See D2060.10

350

See D2060.10

400

See D2060.10

D2060.40 Chemical-Waste Systems


100

See D2060.10

200

See D2060.10

300

See D2060.10

350

See D2060.10

400

See D2060.10

D2060.50 Processed Water Systems


100

See D2060.10

200

See D2060.10

300

See D2060.10

350

See D2060.10

400

See D2060.10

80

Level of Development
Specification
Version: DRAFT 2013

D2060.90 Process Support Plumbing System Supplementary Components


100

See D2060.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D2060.10

D30 HVAC
100

Generic elements or quantitative call outs;


conceptual and/or schematic layout/flow diagram;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
element(s);
design performance Information;
approximate access/code clearance requirements represented
in the model
shaft requirements represented in the model

D3010 Facility Fuel Systems

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3010.10 Fuel Piping


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of mains
and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location of
pipe/valves/fittings/insulation for risers/mains/branches;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all risers/mains/branches;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections of
pipe/valves/fittings/insulation for risers/mains/branches;
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all risers/mains/branches;
actual floor and wall penetrations required represented in the
model

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

82

Level of Development
Specification
Version: DRAFT 2013

D3010.30 Fuel Pumps


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
equipment;
design performance Information;
approximate access/code clearance requirements represented
in the model

300

Specific elements;
modeled as design specified size/shape/spacing/location of
equipment;
approximate allowances for spacing and clearances required
for all specified anchors, supports, vibration and seismic control
that are utilized in the layout of equipment;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of equipment,
actual size/shape/spacing/clearances required for all specified
anchors, supports, vibration and seismic control that are
utilized in the layout of equipment;

400

See D3010.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3010.50 Fuel Storage Tanks


100

See D3010.30

200

Generic elements;
schematic layout with approximate size/shape/location
of tank(s);
design performance Information;
approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified
size/shape/spacing/location of tank(s);
approximate allowances for spacing and clearances
required for all specified anchors, supports, vibration
and seismic control that are utilized in the layout of
tanks(s);
actual access/code clearance requirements represented
in the model

84

Level of Development
Specification
Version: DRAFT 2013
350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of tank(s)
actual size/shape/spacing/clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of tanks(s);

400

See D3010.10

D3020 Heating Systems

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3020.10 Heat Generation


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location
of equipment;
design performance Information;
approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified
size/shape/spacing/location of equipment;
approximate allowances for spacing and clearances
required for all specified anchors, supports, vibration
and seismic control that are utilized in the layout of
equipment;
actual access/code clearance requirements represented
in the model

86

Level of Development
Specification
Version: DRAFT 2013
350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of equipment,
actual size/shape/spacing/clearances required for all
specified anchors, supports, vibration and seismic
control that are utilized in the layout of equipment;

400

Manufacturer or Contractor elements added to the


model required for fabrication and field installation

D3020.30 Thermal Heat Storage


100

See D3020.10

200

See D3020.10

300

See D3020.10

350

See D3020.10

400

See D3020.10

D3020.70 Decentralized Heating Equipment


100

See D3020.10

200

See D3020.10

300

See D3020.10

350

See D3020.10

400

See D3020.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3020.90 Heating System Supplementary Components


100

See D3020.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D3020.10

D3030 Cooling Systems

88

Level of Development
Specification
Version: DRAFT 2013

D3030.10 Central Cooling


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
equipment;
design performance Information;
approximate access/code clearance requirements represented
in the model

300

Specific elements;
modeled as design specified size/shape/spacing/location of
equipment;
approximate allowances for spacing and clearances required
for all specified anchors, supports, vibration and seismic control
that are utilized in the layout of equipment;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual
size/shape/spacing/location/connections of equipment,
actual size/shape/spacing/clearances required for all specified
anchors, supports, vibration and seismic control that are
utilized in the layout of equipment;

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3030.30 Evaporative Air-Cooling


100

See D3030.10

200

See D3030.10

300

See D3030.10

90

Level of Development
Specification
Version: DRAFT 2013
350

See D3030.10

400

See D3030.10

D3030.50 Thermal Cooling Storage


100

See D3030.10

200

See D3030.10

300

See D3030.10

350

See D3030.10

400

See D3030.10

D3030.70 Decentralized Cooling


100

See D3030.10

200

See D3030.10

300

See D3030.10

350

See D3030.10

400

See D3030.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3030.90 Cooling System Supplementary Components


100

See D3030.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D3030.10

D3050 Facility HVAC Distribution Systems

92

Level of Development
Specification
Version: DRAFT 2013

D3050.10 Facility Hydronic Distribution


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location
of mains and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location of
pipe/valves/fittings/insulation for risers/mains/branches;
approximate allowances for spacing and clearances
required for all specified hangers, supports, vibration
and seismic control that are to be utilized in the layout
of all risers/mains/branches;
actual access/code clearance requirements represented
in the model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections of
pipe/valves/fittings/insulation for risers/mains/branches;
actual size/shape/spacing/clearances required for all
hangers, supports, vibration and seismic control that are
utilized in the layout of all risers/mains/branches;
actual floor and wall penetrations required represented
in the model

400

Manufacturer or Contractor elements added to the


model required for fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3050.30 Facility Steam Distribution


100

See D3050.10

200

See D3050.10

300

See D3050.10

350

See D3050.10

400

See D3050.10

D3050.50 HVAC Air Distribution


100

See D3050.10

200

See D3050.10

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location of
duct/dampers/fittings/insulation for risers/mains/branches;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all risers/mains/branches;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections of
duct/dampers/fittings/insulation for risers/mains/branches;
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all risers/mains/branches;
actual floor and wall penetrations required represented in the
model

400

See D3050.10

94

Level of Development
Specification
Version: DRAFT 2013

D3050.90 Facility Distribution Systems Supplementary Components


100

See D3050.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D3050.10

D3060 Ventilation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3060.10 Supply Air


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location
of mains and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location of
duct/dampers/fittings/insulation for
risers/mains/branches;
approximate specified allowances for spacing and
clearances required for all hangers, supports, vibration
and seismic control that are to be utilized in the layout
of all risers/mains/branches;
actual access/code clearance requirements represented
in the model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections of
duct/dampers/fittings/insulation for
risers/mains/branches;
actual size/shape/spacing/clearances required for all
hangers, supports, vibration and seismic control that are
utilized in the layout of all risers/mains/branches;
actual floor and wall penetrations required represented
in the model

96

Level of Development
Specification
Version: DRAFT 2013
400

Manufacturer or Contractor elements added to the


model required for fabrication and field installation.

D3060.20 Return Air


100

See D3060.10

200

See D3060.10

300

See D3060.10

350

See D3060.10

400

See D3060.10

D3060.30 Exhaust Air


100

See D3060.10

200

See D3060.10

300

See D3060.10

350

See D3060.10

400

See D3060.10

D3060.40 Outside Air


100

See D3060.10

200

See D3060.10

300

See D3060.10

350

See D3060.10

400

See D3060.10

D3060.60 Air-to-Air Energy Recovery


100

See D3060.10

200

See D3060.10

300

See D3060.10

350

See D3060.10

400

See D3060.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3060.70 HVAC Air Cleaning


100

See D3060.10

200

See D3060.10

300

See D3060.10

350

See D3060.10

400

See D3060.10

98

Level of Development
Specification
Version: DRAFT 2013

D3060.90 Ventilation Supplementary Components


100

See D3060.1100

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D3060.10

D3070 Special Purpose HVAC Systems

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D3070.10 Snow Melting


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation.

D40 Fire Protection


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout/flow diagram;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
element(s);
design performance Information;
approximate access/code clearance requirements represented
in the model
shaft requirements represented in the model

D4010 Fire Suppression


100

Level of Development
Specification
Version: DRAFT 2013

D4010.10 Water-Based Fire-Suppression


100

Generic elements or quantitative call outs;


conceptual and/or schematic flow diagrams;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of mains
and risers;
design performance Information;
shaft requirements represented in the model

300

Specific elements;
modeled as design specified elements
specified size/shape/spacing/location of
pipe/valves/fittings/insulation for
risers/mains/branches/standpipes;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all
risers/mains/branches/standpipes;
actual access/code clearance requirements represented in the
model

350

Detailed elements;
modeled as contractor submitted actual elements
actual size/shape/spacing/location/connections of
pipe/valves/fittings/insulation for
risers/mains/branches/standpipes;
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all risers/mains/branches/standpipes;
actual floor and wall penetrations required represented in the
model

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

D4010.50 Fire-Extinguishing
100

See D4010.10

200

See D4010.10

300

See D4010.10

350

See D4010.10

400

See D4010.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D4010.90 Fire Suppression Supplementary Components


100

See D4010.10

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
supplementary components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all supplementary
components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of supplementary
components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all supplementary components

400

See D4010.10

D4030 Fire Protection Specialties

102

Level of Development
Specification
Version: DRAFT 2013

D4030.10 Fire Protection Cabinets


100

Generic elements or quantitative call outs;


conceptual and/or schematic layout;
minimal design performance information.

200

Generic elements;
schematic layout with approximate size/shape/location of
components;
design performance Information where applicable

300

Specific elements and assemblies;


modeled as design specified size/shape/spacing/location of
components;
approximate allowances for spacing and clearances required
for all specified hangers, supports, vibration and seismic control
that are to be utilized in the layout of all components;
actual access/code clearance requirements represented in the
model

350

Detailed elements and assemblies;


modeled as contractor submitted actual
size/shape/spacing/location/connections of components
actual size/shape/spacing/clearances required for all hangers,
supports, vibration and seismic control that are utilized in the
layout of all components

400

Manufacturer or Contractor elements added to the model


required for fabrication and field installation

D4030.30 Fire Extinguishers


100

See D4030.10

200

See D4030.10

300

See D4030.10

350

See D4030.10

400

See D4030.10

D4030.50 Breathing Air Replenishment Systems


100

See D4030.10

200

See D4030.10

300

See D4030.10

350

See D4030.10

400

See D4030.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D4030.70 Fire Extinguisher Accessories


100

See D4030.10

200

See D4030.10

300

See D4030.10

350

See D4030.10

400

See D4030.10

D50 Electrical
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information

- Approximate access/code clearance requirements


represented in the model

104

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5010.10 Packaged Generator Assemblies


Description: Generator, frequency changers, and rotary converters and uninterruptible power units.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of equipment and
associated components
- Approximate allowances for spacing and clearances required
for all specified supports and seismic control that are utilized
- Actual access/code clearance requirements represented in
the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of equipment and
associated components
- Actual size/shape/spacing/location for supports and seismic
control that are utilized
-Actual size/shape/location/connections of equipment and
support structure/pads

400

Contractor elements added to the model required for fabrication


and field installation

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5010.20 Battery Equipment


Description: Batteries, battery racks, battery chargers, static power converters, uninterruptible power supplies,
and accessories. To include Uninterruptable Power Supplies, and Lighting Inverters.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified supports and seismic control
that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of equipment and
associated components
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads

400

Contractor elements added to the model required for


fabrication and field installation

106

Level of Development
Specification
Version: DRAFT 2013

D5010.30 Photovoltaic Collectors


Description: Solar cells to convert sunlight to electricity.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified supports and seismic control
that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of equipment and
associated components
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads

400

Contractor elements added to the model required for


fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5010.40 Fuel Cells


Description: Fuel cell electricity generating equipment.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified supports and seismic control
that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of equipment and
associated components
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads

400

Contractor elements added to the model required for


fabrication and field installation

108

Level of Development
Specification
Version: DRAFT 2013

D5010.70 Transfer Switches


Description: Switches that transfer from one source of electricity to another.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified supports and seismic control
that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of equipment and
associated components
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads

400

Contractor elements added to the model required for


fabrication and field installation

D5020 Electrical Service and Distribution

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5020.10 Electrical Service Entrance


Description: Meters, substations, transformers, switchgear, switchboards, and protective devices where
electrical power enters structure.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified supports and seismic control
that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of equipment and
associated components
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads

110

Level of Development
Specification
Version: DRAFT 2013
400

Contractor elements added to the model required for


fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5020.30 Power Distribution


Description: Bus assemblies, distribution equipment, and electrical wiring system to distribute electrical power
to switchboards, panelboards, and motor control centers.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes/enclosures in the Power Distribution System
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures in the Power Distribution System
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads
-Actual floor and wall penetrations required are
represented in the model

112

Level of Development
Specification
Version: DRAFT 2013
400

www.bimforum.org/lod

Contractor elements added to the model required for


fabrication and field installation

D5020.70 Facility Grounding


Description: Raceways, wiring and devices for grounding and bonding an electrical distribution system.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes/enclosures and the electrical equipment and
end-devices served
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual
elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures and the electrical equipment and
end-devices served
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual floor and wall penetrations required are
represented in the model

400

Contractor elements added to the model required for

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

fabrication and field installation

D5030 General Purpose Electrical Power


D5030.10 Branch Wiring System
Description: Raceways, ducts, cable trays, and wiring to deliver power from branch panelboards to the point of
use.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes and enclosures in the branch wiring system
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual
elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures in the branch wiring system
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual floor and wall penetrations required are
represented in the model

400

Contractor elements added to the model required for


fabrication and field installation

114

Level of Development
Specification
Version: DRAFT 2013

D5030.50 Wiring Devices


Description: Electrical devices at point of use including electrical outlets and switches.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of outlet boxes
and devices.
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual
elements:
- Actual size/shape/spacing/location of outlet boxes
and devices

400

Contractor elements added to the model required for


fabrication and field installation

D5040 Lighting

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5040.10 Lighting Control


Description: Clock and calendar, photoelectric switches, occupancy sensors, and light-leveling control devices.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of enclosures ,
equipment and devices
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual
elements:
- Actual size/shape/spacing/location of enclosures,
equipment, and control devices
-Actual size/shape/location/connections of equipment
and control devices

400

Contractor elements added to the model required for


fabrication and field installation

116

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5040.20 Branch Wiring for Lighting


Description: Raceways, ducts, trays, and wiring beyond branch circuit panelboards to lighting fixtures.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes/enclosures to fixture locations
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures to fixture locations
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual floor and wall penetrations required are
represented in the model

400

Contractor elements added to the model required for


fabrication and field installation

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5040.50 Lighting Fixtures


Description: Luminaires, lighting equipment, ballasts, and accessories. Includes fluorescent, high intensity
discharge, incandescent, mercury vapor, neon, and sodium vapor lighting.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of lighting
fixtures
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of lighting fixtures.
- Actual size/shape/spacing/location for supports and
seismic control that are utilized

400

Contractor elements added to the model required for


fabrication and field installation

D5080 Miscellaneous Electrical Systems

118

Level of Development
Specification
Version: DRAFT 2013

D5080.10 Lightning Protection


Description: Wiring and equipment for lightning protection.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes/enclosures and the electrical equipment, and
end-devices served
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual
elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures and the electrical equipment, fixtures
and end-devices served
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads
-Actual floor and wall penetrations required are
represented in the model

400

Contractor elements added to the model required for


fabrication and field installation

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

D5080.70 Transient Voltage Suppression


Description: Devices to protect against voltage surges on electrical distribution systems.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of the
equipment
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of the equipment
- Actual size/shape/spacing/location for supports and
seismic control that are utilized

400

Contractor elements added to the model required for


fabrication and field installation

120

Level of Development
Specification
Version: DRAFT 2013

D60 Communications
D6010 Data Communications
D6020 Voice Communications
D6030 Audio-Video Communication
D6060 Distributed Communications and Monitoring
D6090 Communications Supplementary Components

D70 Electronic Safety and Security


D7010 Access Control and Intrusion Detection
D7030 Electronic Surveillance
D7050 Detection and Alarm
D7070 Electronic Monitoring and Control
D7090 Electronic Safety and Security Supplementary Components

D80 Integrated Automation


D8010 Integrated Automation Facility Controls

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

E EQUIPMENT & FURNISHINGS


E10 Equipment
E1010 Vehicle and Pedestrian Equipment
100

See D1010

200

See D1010

E1010.10 Vehicle Servicing Equipment


100

Info or call outs.

200

Graphical representation with required parametric data

300

Specific types with specific dimensions, locations, properly tagged


& scheduled.

E1010.30 Interior Parking Control Equipment


100

See E1010.10

200

See E1010.10

300

See E1010.10

E1010.50 Loading Dock Equipment


100

See E1010.10

200

See E1010.10

300

See E1010.10

E1010.70 Interior Pedestrian Control Equipment


100

See E1010.10

200

See E1010.10

300

See E1010.10

E1030 Commercial Equipment


100

See D1010

200

See D1010

400

Detailed non-graphic data attached to other interior construction


elements.

500

Detailed as built conditions and specific corresponding


manufacturer's non graphic data.

122

Level of Development
Specification
Version: DRAFT 2013

E1030.10 Mercantile and Service Equipment


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly tagged


& scheduled.

E1030.20 Vault Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.25 Teller and Service Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.30 Refrigerated Display Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.35 Commercial Laundry and Dry Cleaning Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.40 Maintenance Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.50 Hospitality Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.55 Unit Kitchens


100

See E1030.10

200

See E1030.10

300

See E1030.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

E1030.60 Photographic Processing Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.70 Postal, Packaging and Shipping Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.75 Office Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1030.80 Foodservice Equipment


100

See E1030.10

200

See E1030.10

300

See E1030.10

E1040 Institutional Equipment


100

See D1010

200

See D1010

E1040.10 Educational and Scientific Equipment


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly tagged


& scheduled.

E1040.20 Healthcare Equipment


100

See E1040.10

200

See E1040.10

300

See E1040.10

E1040.40 Religious Equipment


100

See E1040.10

200

See E1040.10

300

See E1040.10

124

Level of Development
Specification
Version: DRAFT 2013

E1040.60 Security Equipment


100

See E1040.10

200

See E1040.10

300

See E1040.10

E1040.70 Detention Equipment


100

See E1040.10

200

See E1040.10

300

See E1040.10

E1060 Residential Equipment


100

See D1010

200

See D1010

E1060.10 Residential Appliances


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly tagged


& scheduled.

E1060.50 Residential Stairs


100

See E1060.10

200

See E1060.10

300

See E1060.10

E1060.70 Residential Ceiling Fans


100

See E1060.10

200

See E1060.10

300

See E1060.10

E1070 Entertainment and Recreational Equipment


100

See D1010

200

See D1010

300

See D1010

E1070.10 Theater and Stage Equipment


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly tagged


& scheduled.

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

E1070.20 Musical Equipment


100

See E1070.10

200

See E1070.10

300

See E1070.10

E1070.50 Athletic Equipment


100

See E1070.10.

200

See E1070.10

300

See E1070.10

E1070.60 Recreational Equipment


100

See E1070.10

200

See E1070.10

300

See E1070.10

E1090 Other Equipment


100

See D1010

200

See D1010

E1090.10 Solid Waste Handling Equipment


100

Info or call outs.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly tagged


& scheduled

E1090.30 Agricultural Equipment


100

See E1090.10

200

See E1090.10

300

See E1090.10

E1090.40 Horticultural Equipment


100

See E1090.10

200

See E1090.10

300

See E1090.10

E1090.60 Decontamination Equipment


100

See E1090.10

200

See E1090.10

300

See E1090.10

126

Level of Development
Specification
Version: DRAFT 2013

E20 Furnishings
E2010 Fixed Furnishings
100

Not Modeled.

200

See D1010

300

See D1010

400

See D1010

500

See D1010

E2010.10 Fixed Art


100

Not Modeled.

200

Graphical representation with required parametric data.

300

Specific types with specific dimensions, locations, properly tagged


& scheduled.

E2010.20 Window Treatments


100

See E2010.10

200

See E2010.10

300

See E2010.10

E2010.30 Casework
100

See E2010.10

200

See E2010.10

300

See E2010.10

E2010.70 Fixed Multiple Seating


100

See E2010.10

200

See E2010.10

300

See E2010.10

E2010.90 Other Fixed Furnishings


100

See E2010.10

200

See E2010.10

300

See E2010.10

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

E2050 Movable Furnishings


E2050.10 Movable Art
E2050.30 Furniture
E2050.40 Accessories
E2050.60 Movable Multiple Seating
E2050.90 Other Movable Furnishings

128

Level of Development
Specification
Version: DRAFT 2013

F SPECIAL CONSTRUCTION & DEMOLITION


F10 Special Construction
F1010 Integrated Construction
F1020 Special Structures
F1030 Special Function Construction
F1050 Special Facility Components
F1060 Athletic and Recreational Special Construction
F1080 Special Instrumentation

F20 Facility Remediation


F2010 Hazardous Materials Remediation

F30 Demolition
F3010 Structure Demolition
F3030 Selective Demolition
F3050 Structure Moving

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

G BUILDING SITEWORK
G10 Site Preparation
100

A written civil, site, and landscape architecture narrative is provided


without site elements modeled. This narrative may reference an
architectural mass model that shows generic building and site scale
and
d proportion of the project. It may also reference a topographic
surface that is available.

200

Generic element modeling to include:

Approximate
mate size/shape of foundation element
Approximate size/location of utilities and structures
Approximate code and clearance requirements
Approximate pipe material
Rough modeling of site grading
Local structural building grids defined in model and
coordinated
ed with global state plane coordinate system for
site model.

G1010 Site Clearing


G1020 Site Elements Demolition
G1030 Site Element Relocations
G1050 Site Remediation
G1070 Site Earthwork

130

Level of Development
Specification
Version: DRAFT 2013

G20 Site Improvements


100

A written civil, site, and landscape architecture narrative is provided


without site elements modeled. This narrative may reference an
architectural mass model that shows generic building and site scale
and
d proportion of the project. It may also reference a topographic
surface that is available.

200

Generic element modeling to include:

Approximate size/shape of foundation element


Approximate size/location of utilities and structures
Approximate code and clearance requirements
Approximate pipe material
Rough modeling of site grad
grading
Local structural building grids defined in model and
coordinated with global state plane coordinate system for
site model.

G2010 Roadways
G2020 Parking Lots
G2030 Pedestrian Plazas and Walkways
G2040 Airfields
G2050 Athletic, Recreational,, and Playfield Areas
G2060 Site Development
G2080 Landscaping

G30 Liquid and Gas Site Utilities


G3010 Water Utilities
G3020 Sanitary Sewerage Utilities
G3030 Storm Drainage Utilities
G3050 Site Energy Distribution
G3060 Site Fuel Distribution
G3090 Liquid and Gas Site Utilities Supplementary Components

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

G40 Electrical Site Improvements


100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information

- Approximate access/code clearance requirements


represented in the model

132

Level of Development
Specification
Version: DRAFT 2013

www.bimforum.org/lod

G4010 Site Electric Distribution Systems


Description: Electrical wiring systems to distribute electrical power to on the Site. Includes Duct Banks,
Pullboxes, vaults and transformers from the utility point of connection, to the buildings main electric room.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes/enclosures in the Power Distribution System
- Specified size/shape/spacing/location of equipment
and associated components
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements
represented in the model

350

Detailed elements:
- Manufacturer or contractor submitted actual
elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures in the Power Distribution System
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment
and support structure/pads
-Actual floor and wall penetrations required are
represented in the model

Level of Development
Specification
Version: DRAFT 2013
400

www.bimforum.org/lod

Contractor elements added to the model required for


fabrication and field installation

G4050 Site Lighting


Description: Luminaires, lighting equipment, ballasts, and accessories. Includes fluorescent, high intensity
discharge, incandescent, mercury vapor, neon, and sodium vapor lighting. Includes Pole Mount, Building
Mount and on-grade fixtures for exterior lighting.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of lighting fixtures
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized. Includes required pole bases and
footing elements.
- Actual access/code clearance requirements represented in
the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of lighting fixtures.
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment and
support structure/pads

400

Contractor elements added to the model required for


fabrication and field installation
134

Level of Development
Specification
Version: DRAFT 2013

G50 Site Communications


100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information

- Approximate access/code clearance requirements


represented in the model

G5010 Site Communications Systems


Description: Conduit Systems for routing of Communication trunk systems.
100

Generic elements or quantitative call outs:


-Conceptual and/or schematic layout
-Minimal design performance information

200

Generic elements schematic layout with:


- Approximate size/shape/location of equipment
- Design performance Information
- Approximate access/code clearance requirements
represented in the model

300

Specific elements;
modeled as design specified elements:
- Specified size/shape/spacing/location of raceways/
boxes/enclosures in the Power Distribution System
- Specified size/shape/spacing/location of equipment and
associated components
- Approximate allowances for spacing and clearances
required for all specified hangers, supports and seismic
control that are utilized
- Actual access/code clearance requirements represented in
the model

350

Detailed elements:
- Manufacturer or contractor submitted actual elements:
- Actual size/shape/spacing/location of raceways/
boxes/enclosures in the Power Distribution System
- Actual size/shape/spacing/location for supports and
seismic control that are utilized
-Actual size/shape/location/connections of equipment and
support structure/pads
-Actual floor and wall penetrations required are represented
in the model

www.bimforum.org/lod

Level of Development
Specification
Version: DRAFT 2013
400

www.bimforum.org/lod

Contractor elements added to the model required for


fabrication and field installation

G90 Miscellaneous Site Construction


G9010 Tunnels

136

Level of Development
Specification
Version: DRAFT 2013

APPENDIX