1. SPECIFICATION
Sensing Input
Voltage
Frequency
Voltage Regulation
< 1% ( with 4% engine governing )
Voltage Build-up
Residual voltage at AVR terminal > 5 VAC
Thermal Drift
5 VDC
1V for 5% generator volt
1K ohm
Droop Input
Burden
Max. sensitivity
Max. input
10 ohm
0.07 A for 5% droop (PF=0)
0.33 A
Environmental
100Hz ~ 2K Hz 3.3g
0.5 ~ 1A
2. GENERAL DESCRIPTION
AVR341
FUNCTION
To adjust generator output voltage
To prevent voltage hunting
To set the UFRO knee point
To set the generator droop to 5% at 0pf
To optimize analogue input sensitivity
To set the over excitation cut off level
To set the frequency related voltage dip
DIRECTION
Clockwise increases output voltage
Clockwise increase the damping effect
Clockwise reduces the knee point frequency
Clockwise increases the droop
Clockwise increases the gain or sensitivity
Clockwise increase the cut off level
Clockwise increases the voltage dip
WARNING
Do not increase the voltage above the rated
generator voltage. If in doubt, refer to the
rating plate mounted on the generator case.
Do not ground any of the hand trimmer
terminals, as these could be above earth
potential. Failure to observe this could
cause equipment damage.
______________________________________________________________________________________
AVR341
4.3 Under
Frequency
Roll
Off
(UFRO)
Adjustment
The AVR incorporates an under-speed protection
circuit which gives a VOLT / Hz characteristic when
the generator speed falls below a presentable
threshold known as the knee point. The red Light
Emitting Diode (LED) gives indication that the
UFRO circuit is operating.
______________________________________________________________________________________
AVR341
TRIM
DROOP
VOLT
EXC. TRIP
DIP
C-A < 90KW
C-B 90-550KW
B-A > 550KW
UFRO
STABILITY
C B A
LED
UNIT : mm
ATTENTION
1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will
not affects operation. For dimension reference, please see Figure 1.
2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AVR.
______________________________________________________________________________________
AVR341
K2
K1
P2 P3 P4 XX
X3
2 2 1
TRIM
A1
A2
S1
S2
DROOP
Temperatu
re
SENSING SELECTION
Hi
gh
1
2
3
4
5
6
7
VOLT
AVR341
EXC. TRIP
DIP
FREQUENCY
SELECTION
SELECTION
UFRO
STABILITY
3 2 1
INDICATOR
LED
CBA
3-1 4P/60HZ
3-2 4P/50HZ
2-1 6P/50HZ
NO LINK 6P/50HZ
C-B 90KW~550KW
B-A OVER 550KW
PMG
Exciter
3 Bridge
220V
Generator
G
~
S
C.T
T
1K
For external adjusted
P2 P3 P4
XX X
S1
S2
AVR341
Use only original supplied spare protection fuse for fuse replacement.
Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.
______________________________________________________________________________________
AVR341