Вы находитесь на странице: 1из 128

10/5/2015 10:10 AM

Jeff Stein, PE, Principal

Revisiting Variable Air


Volume Reheat
Systems

Taylor Engineering, LLC


jstein@taylor-engineering.com
http://www.taylor-engineering.com

66%

Site 1 Monitored CFM vs DP from 12/20/01 to 9/16/02


(with perfect system curve and likely actual system curve)

Actual Data

52%

Perfect System Curve (i.e. SP reset)

Pressure Drop Across Fan (" H2O)

3.5
37%

23%

9%

Design Point (145,000 CFM at 4.0")


3

Likely Actual System Curve (No SP Reset)

2.5
2
1.5
1
0.5
0
0

20,000

40,000

60,000

80,000

100,000

120,000

140,000

Total CFM (SF-1 + SF-2)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

Logistics
Safety
Restrooms
Recycling
Cell phone etiquette
Lunch
Review forms
Webinar etiquette
PG&E Resources
Rebates
Tool Lending Library
Marlene Vogelsang (mxv6@pge.com)
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

10/5/2015 10:10 AM

Agenda
Welcome and Overview
System Selection
Zone Controls
VAV Box Control
DCV & Occupancy Sensors
Special case zones: conf rooms, computer rooms, toilet rooms
Min OSA
Air Economizers
Supply Pressure Reset
VAV Reheat vs DOAS
Field Research Energy and Occupant Comfort
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

Handouts
You can get a copy of the handouts in PDF format as
follows:
Type the following link into your web browser:
o

http://www.taylorengineering.com/ftp/PECClassHandouts.html

Click on the link for Revisiting VAV to download the


Acrobat file of the presentation.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

10/5/2015 10:10 AM

Audience & Objectives


To promote efficient practical designs that advance
standard practice
Focus on California climate
Focus on air side of VAV systems
Based on the NBI PIER Project that produced the EDR
VAV Design Guide (2007): http://tinyurl.com/3dw6vlx

For wet side see CoolTools Chilled Water Plant Design and
Specification Guide (2009): http://tinyurl.com/ye385nv

Provide updates based on recent research by ASHRAE,


CBE, Iowa Energy Center, LBNL, PG&E, Taylor
Engineering and the Title 24 Codes and Standards team.
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

HVAC System Selection

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

10/5/2015 10:10 AM

HVAC System Options


Single zone versus multiple zone
Mechanical cooling and/or:
Direct evaporative cooling
Direct + indirect evaporative cooling
Heat and vent only

Mechanical cooling
Packaged DX
Chilled Water

Multiple zone air systems


VAV reheat
Dual duct

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

77

Title 24 Baseline Mapping

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

88

10/5/2015 10:10 AM

Evaporative Cooling Climate Analysis

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

99

Evaporative Cooling Climate Analysis

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

1010

10/5/2015 10:10 AM

Evaporative Cooling Climate Analysis

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

1111

HVAC System Selection Matrix


Each attribute gets a weight.
Each system gets a rank for each attribute.
Attributes
First Costs
o

HVAC First Cost

Impact on Other Trades: General Contractor

Impact on Other Trades: Electrical Contractor

Floor Space Requirements


Ceiling Space Requirements
Energy Efficiency - Normal Operation (requires parametric simulation analysis)
Energy Efficiency - Off-hour Operation
Smoke Control (7 story buildings)
Acoustical Impact
Indoor Air Quality
Comfort
Maintenance Costs and Reliability
PG&E
Flexibility
PACIFIC ENERGY CENTER

OCTOBER 2015

12

10/5/2015 10:10 AM

Performanc
e Attribute

Weig
ht

VAV Reheat System

Ran
k

Dual Fan Dual Duct System

Ran
k

HVAC20 System
Selection
Low shell & core
costs. Highest zoneMatrix
8
Low zone costs usually offset higher shell &

HVAC First
Costs

costs.

Impact GC.

10

Impact Elec.

core cost resulting in slightly lower overall


costs compared to VAV reheat
10

Larger penthouse space required for heating


fans.

Smallest equipment rooms or wells


and shafts. Furred columns required
for hot water piping.
Fewer units to wire mechanically.

Floor Space
Requirements

Smallest shafts required.

10

Slightly higher cost compared to reheat due to


added heating fan, often offset by eliminating
boiler.
Somewhat larger shafts required for
additional heating duct.

Ceiling Space
Requirements

Usually extra heating duct can fit into same


space as cooling duct (with cross-overs
between beams) but will not work well with
flat slab structure.

Efficiency
Normal Oper.

10

Reheat system causes higher heating


costs.

Maintenance
Costs and
Reliability

10

Only rooftop equipment requires


frequent maintenance; VAV boxes
occasional maintenance. Risk of
water damage due to piping above
ceiling.

Reduced reheat and heat recovery from


recessed lights reduces overall energy costs
compared to reheat system
No water above ceiling reduces risk of water
damage. Dual duct boxes require slightly less
maintenance than reheat boxes.

Flexibility

Any number of zones may be used, but


at high cost per zone.

Total

PG&E
PACIFIC ENERGY CENTER
100

Any number of zones may be used and zone


costs are less than for reheat

OCTOBER
2015
810

13

10

815

HVAC System Selection Matrix


It can combine quantitative (e.g. first cost) and qualitative
(e.g. impact on other trades) assessments
Each performance attribute needs a weight
Constrain the weights to sum to 100
Ranks are on the basis 10 for the best with other ranks
assessed relative to the best
Total scores are the sum of the ranks times the weights
for each alternate system. The highest score wins.
This inherently documents and communicates the design
intent.
It has more rigor than simply choosing a system based
on experience.
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

14

10/5/2015 10:10 AM

Variable Air Volume with Reheat

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

15

Zone Controls
Zonal System Type
Single duct reheat
Cooling only
Fan powered box
Parallel
Series

Zone Controls
CO2 Demand Control Ventilation
Occupant Sensing
Window Switches

Control Sequences
Single vs Dual Maximum
Controllable minimum airflow setpoint
Time Averaged Ventilation (TAV)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

16

10/5/2015 10:10 AM

Demand Control Ventilation

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

17

Title 24 DCV Requirements


Required for each densely occupied space (<40 ft2/person) if:
AHU has an outdoor air economizer
Single zone system or multiple zone with DDC to the zone
Exemptions: classrooms, healthcare, < 10 people, etc.
Minimum rate = Table 120.1A cfm/ft2 * area
CO2 Setpoint = ambient + 600 ppm
Ambient can be either
400 ppm assumed
Ambient CO2 sensor
Sensor
Located in the space between 3 ft and 6 ft above the floor
75 ppm accuracy at 1000 ppm
Factory or field calibrated
Require recalibration no more frequently than every 5 years
Continuous display and recorded on DDC systems
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

18

10/5/2015 10:10 AM

DCV Multiple Zone Control Sequence


P-only
0% at 800 ppm CO2
100% at 1,000 ppm
Output mapped:
0-50%: reset zone minimum first from Table 120.1A (0.15
cfm/ft2) to max under control

50%-100%: reset AHU OSA minimum position from Table


120.1A up to 15 cfm per person based on most demanding
zone

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

19

CO2 Control at Zone (Multizone)

Maximum
Cooling Vcoolmax
Airflow
Zone level reset
Minimum
Air Flow
Setpoint

Minimum
Ventilation
Airflow

Largest zone demand


used at AHU for reset
of minimum OSA
Min OSA

Design
OSA

Vmin

0%

PG&E PACIFIC ENERGY CENTER

50%
PID Loop Output

OCTOBER 2015

100%

20

10

10/5/2015 10:10 AM

CO2 Sensors

Solid State

Infrared

Gas Molecules

Custom Designed
Infrared Filters
Reference Target GasDual Beam

Diffusion Membranes

Interactive
Sensor Element

Oxidation

Incandescent
Infrared Source

Reduction
Resistance Change Light Emission (Voltage Output)
Quenching
(Color Change)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

Micro-Machined
Thermopile Detector

1.25"
Patented Waveguide

Microprocessor

21

Carbon Dioxide Transmitters


NDIR Photometric Principle

Problem: Ageing of light


source causes drift

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

22

11

10/5/2015 10:10 AM

CO2 Transmitters
Referencing/Calibrating Technology
Automatic Background Calibration: Periodically selfcalibrate using lowest reading over a period of time
assumed to be ~400 ppm

Dual wavelength: Measure light transmission at second


wavelength where CO2 and other common components of
air do not absorb light

Dual beam: Second light source used to assess ageing of


primary light source

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

23

CO2 Transmitters

Single Beam Dual Wavelength, 2 Detectors

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

24

12

10/5/2015 10:10 AM

CO2 Transmitters

Single Beam Dual Wavelength w/FPI


Courtesy Vaisala

CO2
IR detector

Light source Sample cell


with reflector

FPI chip
Air gap
Upper mirror
Lower mirror
Silicon substrate

Applying different voltages tunes


filter to different wavelengths

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

25

CO2 Transmitters

Dual Beam Single Wavelength


Second light source pulsed infrequently to slow its ageing

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

26

13

10/5/2015 10:10 AM

CO2 Recommendations
For 24/7 occupancies use only:
Single Beam with Dual Wavelength
For non-24/7 occupancies:
Single Beam, Single Wavelength with ABC

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

27

Return Sensors Dont Work for Multi-Zone Units!

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

28

14

10/5/2015 10:10 AM

Occupancy Sensors

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

29

Occupancy Sensors and Code


Can reset minimum ventilation from occupant-based
level to area-based level if zone is unoccupied
Title 24 2013 will reduce this to 25% of area-based
minimum when unoccupied.

Can set back/up setpoints (required in Title 24 2013)


Can also use occupant sensors to eliminate zone signal
where multiple sensors are used on a zone

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

30

15

10/5/2015 10:10 AM

New Title 24-2013 Occupant Sensor Requirements


Multipurpose room < 1000 ft2, classrooms > 750 ft2 and
conference, convention, auditorium rooms > 750 ft2
Wshall be equipped with occupant sensor(s) to
accomplish the following during unoccupied periods:
Automatically setup the operating cooling temperature set
point by 2F or more and setback the operating heating
temperature set point by 2F or more; and
Within 30 minutes after being vacant W then no outside air
is required and supply air shall be zero.
Wthen the system or zone controls shall cycle or operate to
maintain the average outdoor air rate over an averaging
period of 120 minutes equal to 0.04 cfm/ft2.

EXCEPTION: If DCV is used


PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

31

Window Switches

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

32

16

10/5/2015 10:10 AM

Window/Door Switches in next Title 24 version


Title 24 2016 prescriptively requires HVAC interlock if
windows are operable that disable mechanical heating
and cooling when any such opening is open. Mechanical
cooling may remain enabled when an opening is open if
outside air temperature is below space temperature.
Exceptions:
Exits with automatic closers
Any space without a thermostat
Existing buildings
T24 modeling rules do not have operable windows in
basecase. Proposed gets a bonus if it has operable
windows with switches and a penalty if no switches.
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

33

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

34

17

10/5/2015 10:10 AM

Window Switches Advice / Indicator Displays


Advice Indicator Light:
Green = zone is in cooling and the outside air temperature
is less than the space temperature, opening the window
now will save cooling energy

Red = bad to open the window, opening the window now


will turn off the heating/cooling

Mode Indicator Light


Green = heating/cooling not disabled
Red = heating/cooling is disabled because a window is
open

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

35

Conference Rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

36

18

10/5/2015 10:10 AM

Challenges

High ventilation requirement


(e.g. 70% of design flow)
Variable and intermittent
occupancy
Minimum ventilation required
at all normally occupied
times

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

37

Conference Room Strategies


1. Standard VAV Box
2. Standard VAV Box with Occupancy Sensor
3. Standard VAV Box with DCV
4. Series Style VAV Box
5. Standard VAV Box with Occupancy Sensor and DCV
NOTE: Occupancy sensors or DCV are required in T-242013 for most conference rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

38

19

10/5/2015 10:10 AM

Strategy 1: Standard VAV Box


Wastes fan energy, cooling energy and reheat due to
high minimum ventilation requirements
Not recommended if minimum ventilation exceeds 30%
of box flow.
With operable windows this could work if zone meets the
natural ventilation exception and box minimum is 0 cfm.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

39

Strategy 2: Add an Occupancy Sensor


In Title 24 2013 (120.1(c)5) you can cycle the VAV box to
achieve an average airflow of 25% of the Table 120.1A
values (0.15 cfm/ft2) when unoccupied.
You need to setup/setback by +/-2F when unoccupied
(120.2(e)3)
You can use the same occupancy sensor(s) for the
ventilation, lights and setup/setback
Better than Strategy 1 but not perfect

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

40

20

10/5/2015 10:10 AM

Strategy 3: Add DCV


Can reduce ventilation to Table 120.1A values (0.15
cfm/ft2)
Does not make sense for naturally ventilated spaces
May be better than Strategy 2 (Occupancy Sensors)
since it also works to reduce energy when the space is
lightly loaded
However CO2 sensors do drift and should use Automatic
Background Calibration (ABC). See research from LBNL
and Iowa State Energy Center:
http://tinyurl.com/3lw6b42.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

41

Strategy 4: Use a Series Fan-Powered Box with 0


Minimum
The box fan meets the ventilation requirements with
return air.
No central air or reheat necessary during unoccupied
times
Simple controls
Potentially best energy savings

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

42

21

10/5/2015 10:10 AM

VAV Minimum Volume with Series Fan-Powered Boxes


Total Supply Air
Flow Rate

Supply
Volume
IDEAL FOR
INTERIOR
CONFERENCE
ROOMS!

Cooling Supply
Air Flow Rate

Shut-off Valve No Minimum Required!


Space Temperature
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

43

Toilet Rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

44

22

10/5/2015 10:10 AM

Toilet Rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

45

OCTOBER 2015

46

Toilet Rooms

PG&E PACIFIC ENERGY CENTER

23

10/5/2015 10:10 AM

Toilet Rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

47

VAV Reheat Boxes

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

48

24

10/5/2015 10:10 AM

VAV Boxes Main Points


Size VAV reheat boxes for 0.5 total pressure drop
All boxes should be at 0.5 as critical path varies over the year
Use Dual Maximum control sequence
Min = max(box min, ventilation min)
Fan boxes generally only make sense for very high ventilation
or very high heating loads
References:
Steve Taylor, Jeff Stein, Sizing VAV Boxes, ASHRAE Journal,
March 2004 (http://tinyurl.com/af35vfu_

Jeff Stein, Specifying VAV Boxes, HPAC Magazine, November


2005 (http://tinyurl.com/art8t6x)
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

49

VAV Box Sizing


Oversized box
Less pressure drop
Less noise
Cost more
Higher box min more reheat (only on perimeter zones)
o

Consider oversizing interior zone boxes

Undersized box
More pressure drop
More noise
Lower box min less reheat

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

50

25

10/5/2015 10:10 AM

VAV Box Sizing: Simulation Results


Compared TP from 0.3 to 0.8
office building
Sensitivity Analysis

Climate
Loads (internal, envelope)
operating schedules
Load calc (aggressive, conservative)
Utility rates
8 bit versus 10 bit A/D converter
SAT (50F-60F), SAT reset, SP reset

RESULT: Size VAV Boxes for ~0.5 TP

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

51

VAV Box Sizing: Calculating TP


Manufacturers list SP not TP

TP = SP + VP
v 2 v 2
= SP + in out
4005 4005
Need to know Outlet Area

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

52

26

10/5/2015 10:10 AM

VAV Box Sizing: Sample Calc.

Nominal
size

Inlet
Outlet Outlet
SP
VP
TP
Max Radiated
dia.
width height
(in.
(in.
(in.
CFM
NC*
(in.)
(in.)
(in.)
w.g.)*
w.g.)
w.g.)
4
4
12
8
0.08
0.42
0.50
230
21
5
5
12
8
0.15
0.35
0.50
333
20
6
6
12
8
0.24
0.25
0.49
425
21
7
7
12
10
0.25
0.25
0.50
580
20
8
8
12
10
0.33
0.17
0.50
675
22
9
9
14
13
0.27
0.23
0.50
930
17
10
10
14
13
0.32
0.18
0.50
1100
19
12
12
16
15
0.32
0.17
0.49
1560
19
14
14
20
18
0.31
0.19
0.50
2130
18
16
16
24
18
0.32
0.18
0.50
2730
22
*From selection software using ARI 885-95 and assuming inlet SP = 1.5 and outlet
SP = 0.25

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

53

VAV Box Sizing: Noise

Manufacturers required to use ARI 885-98


attenuation factors

ARI 885-98 assumptions


Type 2 mineral fiber ceiling
3 deep plenum
Plenum >= 30 wide or lined with insulation
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

54

27

10/5/2015 10:10 AM

VAV Box Sizing: Noise


Noise decreases at part load
Noise decreases with static pressure reset
Noise can be mitigated with insulation, gypsum board,
and clever box location

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

55

OCTOBER 2015

56

VAV Box Inlet Duct

PG&E PACIFIC ENERGY CENTER

28

10/5/2015 10:10 AM

VAV Box Discharge Ducts (based on 8 inlet box)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

57

VAV Box Control: Single Maximum


Maximum
Airflow Setpoint
Reheat Valve Position

Airflow Setpoint
Minimum
Airflow Setpoint

(shaded area = reheat)

Heating Loop

PG&E PACIFIC ENERGY CENTER

Dead
Band

OCTOBER 2015

Cooling Loop

58

29

10/5/2015 10:10 AM

VAV Box Control: Dual Maximum


Maximum
Supply Air
Temperature

Max Cooling
Airflow Setpoint
Supply Air Temperature Setpoint
(requires discharge temp. sensor)

Maximum
Heating
Airflow
Setpoint

Airflow Setpoint

Minimum
Airflow
Setpoint
(shaded area = reheat)
Heating Loop

PG&E PACIFIC ENERGY CENTER

Cooling Loop

Dead
Band

OCTOBER 2015

59

Dual Max/Constant Volume Heat Prohibited


Maximum
Airflow
Setpoint
Reheat Valve Position

Once in heating mode, the cooling load


must exceed 50% of design cooling load to
unstick the zone from heating mode
50%

Airflow
Setpoint

20%

(shaded area = reheat)

Heating Loop

PG&E PACIFIC ENERGY CENTER

Dead
Band

OCTOBER 2015

Cooling Loop

60

30

10/5/2015 10:10 AM

Dual Max / Simultaneous - Prohibited in T24-2013


Max Cooling

100%

[Summarize what we believe typical practice


is.
Airflow Setpoint
Ask for feedback on whether this is correct.]
Reheat Valve
50% or vent.

Airflow Setpoint

20%, or vent.
(shaded area = reheat)
Heating Loop

PG&E PACIFIC ENERGY CENTER

Dead
Band

OCTOBER 2015

Cooling Loop

61

VAV Box Min Flow


For Single Max Must be high enough to meet peak
heating load without short-circuiting (at supply
temperature < 90F)
Often requires 50% or higher minimum flows
For Dual Max (or interior zones) Meet the ventilation
and be above box controllable minimum flow
Often 10% or less of design flow
To meet Std. 62.1 efficiently the zone minimum should be
above the zone minimum outside air

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

62

31

10/5/2015 10:10 AM

Dual Max: Arguments and Rebuttals


Against Dual Max

For Dual Max

Stuffiness

ASHRAE 55: no min air speed


necessary for comfort. Complaints
are usually related to temperature.

Poor air change effectiveness

Dual maximum is better: air change


effectiveness is only an issue when
SAT > 85F (ASHRAE 62, Persily, etc)

Short-circuiting

Dual maximum is better: controlling


SAT minimizes short circuiting

Dumping

Good ADPI and comfort at 18% flow


(Fisk, Bauman, etc.)

Does not work for all box types (i.e.,


pneumatic, electronic or
preprogrammed digital).

Specify fully programmable DDC


controllers

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

63

Box Controllability: How Low Can You Go?


Stability is important but not accuracy
Manufacturers recommended minimums are related to
accuracy, not stability
Calculate the controllable minimum from:
Amplification of the flow probe
Actual controller

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

64

32

10/5/2015 10:10 AM

VAV Box Flow Sensing

Amplifying Probe

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

65

Flow Probes

Krueger

PG&E PACIFIC ENERGY CENTER

Enviro-tec

OCTOBER 2015

66

33

10/5/2015 10:10 AM

How a VAV Box Works


Zone Controller

Amplified
velocity
pressure
signal
Air
Flow

Flow
Probe

vm = 4005

VPm
F

Vm = vm A

Transducer

Analog
electronic
(4-20mA)
A/D
Conv.

Digital
Input

Contr AO Actuator
oller

10 bit
A/D

0.004

VPm = Minimum Velocity Pressure Signal (in. w.g.)


F = Amplification Factor
vm = Minimum Velocity (FPM)
Vm = Minimum Airflow (CFM)
A = area (ft2)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

67

Why Not Just Look in the VAV Box Catalog?


Titus

About 30% of design CFM for typical box selections


PG&E PACIFIC ENERGY CENTER OCTOBER 2015

68

34

10/5/2015 10:10 AM

Why Not Just Look in the VAV Box Catalog?


0.004 is possible

Envirotech

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

69

Flow Probe Amplification


10000
7000

3665
2806
2062
1432
1160
916

22 inch
1000

I
n
l
e
t

C
F
M

100

S
i
z
e

702

16 inch
14 inch

515

12 inch

358

10 inch
9 inch
8 inch

229

7 inch
6 inch
5 inch
4 inch

10
0.01

0.1

C
F
M
@
O
n
e
I
n
c
h
S
i
g
n
a
l

4005 A
F =

F = amplification factor
K = actual flow in CFM at flow probe
output of 1.0 w.c.
A = is the nominal inlet area in ft2

Flow Probe Velocity Pressure Signal (Inches W.G.)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

70

35

10/5/2015 10:10 AM

Taylor Engineering/Dickerhoff Research: Titus Probe


Measured Points
Measured Calibration

Titus Nominal Calibration

2000
Titu s K fa c to r= 9 0 4
M e a s . D a ta : K = 8 6 9

V e lo c ity [fp m ]

1000
500

200
100
50
.001

.005 .01
.05
Flow Grid Pressure [iwc]

.1

.5

All measured Data Points


Recall that Amplification (F)
corresponds to

4005 A
F =
= 2 .6
K

K-Factor (CFM at 1.0 signal)


PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

71

Taylor Engineering/Dickerhoff: Nailor Results

Measured Points
Nailor Nominal Calibration

Measured Calibration

N a ilo r N o m in a l K = 1 0 0 7
M e a s u re d K = 9 9 5

2000

V e lo c ity [fp m ]

1000
500

200

F = 2.3

100
50
.001

.005 .01
.05
Flow Grid Pressure [iwc]

.1

.5

All measured Data Points


PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

72

36

10/5/2015 10:10 AM

TE/Dickerhoff Box Only Conclusions


Amplification is stable and constant down to very low
flows
Not affected by damper position

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

73

Why is Accuracy at Low Flow So Difficult?

Velocity Pressure (inches w.c.)

V e lo city P re s su re (in c h e s w .c.)


0 .8 5
0 .8 0
0 .7 5
0 .7 0
0 .6 5
0 .6 0
0 .5 5
0 .5 0
0 .4 5
0 .4 0
0 .3 5
0 .3 0
0 .2 5
0 .2 0
0 .1 5
0 .1 0
0 .0 5
0 .0 0

A m p lifie d V e lo c ity P res su re

Actual flow +/0.003 at 500


CFM setpoint
Actual flow +/0.003 at 50
CFM setpoint

5 0 1 0 0 1 5 0 2 0 0 25 0 3 0 0 3 5 0 4 0 0 45 0 5 0 0 5 5 0 6 0 0 6 50 7 0 0 75 0 8 0 0 8 5 0
A irflo w (C F M )

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

74

37

10/5/2015 10:10 AM

TE/Dickerhoff Controller Results Summary


Controller

Calibration Errors

Zero Drift

Deadband

Software Issues

Siemens
(pressure-based)

Inaccurate below 0.001;


highly accurate above 0.001

Significant tempcorrelated drift


(can be eliminated
with optional
bypass kit)

None-results in
many
damper
movements

None

Johnson (pressurebased)

Inaccurate below 0.001;


highly accurate above 0.001

Minimal drift

varies
depending
on signal
noise (~15
CFM)

Incorrectly re-zeroed
the damper resulting
in offset error (can be
eliminated with
optional bypass kit)

Alerton (hot-wire)

Highly accurate at calibration


points (no flow and design
flow), underestimates actual
flow at other values

No noticeable drift

3% of range
(~15 CFM)

None

ALC (hot-wire)

Highly accurate at four


calibration points with small
deviations between these
points

No noticeable drift

1 second of
damper
movement
(~5 CFM)

None

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

75

Sample Calculation of Box Minimum Flow Setpoint

Nominal Inlet
Diameter, in.

Area,
ft2

CFM @
1
sensor
readin
g

Amplification
factor

Min VP sensor reading


= 0.004 w.g.

Min VP sensor reading


= 0.01 w.g.

Minimum
Velocity,
FPM

Minimum
Flow,
CFM

Minimum
Velocity,
FPM

Minimum
Flow,
CFM

vm

Vm

vm

Vm

0.087

229

2.33

166

14

263

23

0.136

358

2.33

166

23

263

36

0.196

515

2.33

166

33

263

52

0.267

702

2.33

166

44

263

70

0.349

916

2.33

166

58

263

92

0.442

1,160

2.33

166

73

263

116

10

0.545

1,432

2.33

166

91

263

143

12

0.785

2,062

2.33

166

130

263

206

14

1.069

2,806

2.33

166

177

263

281

16

1.396

3,665

2.33

166

232

263

367

22

2.64

7000

2.28

168

443

265

700

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

76

38

10/5/2015 10:10 AM

ASHRAE RP-1353: Flow Probe Results

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

77

ASHRAE RP-1353: Conclusions


Accuracy within 10% of reading can generally be
achieved at 140 fpm (0.003 VP signal) if:
Hard duct at inlet
No elbows at inlet if using Ebtron sensor
inlet pressure is below 1.4 accuracy degrades when
damper is nearly closed

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

78

39

10/5/2015 10:10 AM

Dual Duct: Snap Acting Controls with a Single Sensor on


the Outlet

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

79

Dual Duct Box Sizing: Beware of Odd Sizes!

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

80

40

10/5/2015 10:10 AM

Cooling Only Boxes: Zero Minimum


Applications:
No ventilation requirements e.g. telecom closet
In combination with heating boxes in large zones e.g.
open office with cooling-only, zero-stop boxes in the interior
and reheat boxes at the perimeter.

Oversize no reheat penalty

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

81

OCTOBER 2015

82

81

Box Type Example

PG&E PACIFIC ENERGY CENTER

41

10/5/2015 10:10 AM

Auxiliary Loads

IDF Closets
Electrical Rooms
Security Rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

83

Auxiliary Load Strategies


1.

Chilled Water Fan Coils

2.

Water-Cooled AC Units

3.

Air-Cooled Split Systems

4.

Serve from Central AHUs

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

84

42

10/5/2015 10:10 AM

Strategy 1: Chilled Water Fan Coils


Must design CHW plant to unload efficiently
Could integrate heat recovery or water-side economizer
Generally expensive
Very inflexible to changes
Must be VAV Title 24 2013 [(140.4(c)4, 140.4(m) and
Table 140.4-D)]

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

85

Strategy 2: Dedicated Water Cooled AC Units


Should have head pressure control for AC units
Design tower for flow turndown
Can have economizer pre-cooling coil or heat recovery
Very flexible design
Potential for heat recovery if spaces have WLHPs
Specify with 2-position isolation valves interlocked to the
compressors. This is a Title 24 requirement.
It is recommended to separate WCAC/HP units with a
plate and frame HX to prevent fouling of condensers.
Expensive but costs can be deferred to tenants in
speculative buildings
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

86

43

10/5/2015 10:10 AM

Strategy 3: Air-Cooled Split Systems


Usually least efficient
Can be low cost for small distributed systems
Loads must be close to outdoor units for split systems
Reliability and maintenance concerns
Could also use VRF which provides some heat recovery

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

87

Strategy 4:VAV Boxes From Central System


Can be very efficient due to economizer and with good
fan turndown
Must have zone isolation controls as required by code
Fans must be able to turn down to ~10%
Chilled water plant must be designed for turndown as
well
Pretty flexible design
Inexpensive, high reliability, low maintenance
Required in Title 24 2013 for computer rooms (any room
with more than 20 W/ft2 of plug loads)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

88

44

10/5/2015 10:10 AM

Title 24 Economizer Exception (sort of) for Small


Computer Rooms

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

89

Fan Powered VAV Boxes and Applications

Series Fan

PG&E PACIFIC ENERGY CENTER

Parallel Fan

OCTOBER 2015

90

45

10/5/2015 10:10 AM

Parallel-Style Fan-Powered VAV Box

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

91

Parallel-Style Fan-Powered VAV Box


Schematic

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

92

46

10/5/2015 10:10 AM

Sequence of control
Cooling Maximum

Supply Air Temperature Setpoint

Optional if
Min<minOA flow
Parallel fan

Minimum Airflow setpoint

Heating PID Signal

PG&E PACIFIC ENERGY CENTER

Cooling PID Signal

OCTOBER 2015

93

Series-Style Fan-Powered VAV Box

Series Fan

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

94

47

10/5/2015 10:10 AM

Series-Style Fan-Powered VAV Box


Schematic

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

9595

Sequence of control
Series fan
Cooling Maximum

Supply Air Temperature Setpoint

Heating PID Signal

PG&E PACIFIC ENERGY CENTER

Cooling PID Signal

OCTOBER 2015

96

48

10/5/2015 10:10 AM

Fan Powered Box Issues and Applications


Fan powered boxes are noisy, expensive, inefficient and
high maintenance
Consider series boxes for high minimums
Interior conference rooms
spaces open to above
Consider parallel boxes for
Max heating flow > 50% of design flow
o

e.g. north facing, perimeter zones

If using electric heat


Consider zero minimums on primary air for fan boxes if
interior zone cooling loads can be counted on to provide
enough primary flow to achieve min OA for the building
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

97

Typical Title 24 DDC Zone

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

98

49

10/5/2015 10:10 AM

Should T24 Adopt ASHRAE 189.1 Reheat Exception?


ASHRAE Standard 189.1 Reheat Exception:
Zones for which the volume of air that is reheated,
recooled, or mixed is no greater than the larger of the
following:
o

(1) the design outdoor airflow rate for the zone, or

(2) 15% of the zone design peak supply rate.

This effectively prohibits VAV reheat boxes and requires


parallel fan boxes or something similar.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

99

Parallel Fan-Powered Boxes

Energy Saved with FPB

- Less hot water required


less boiler and less
pump energy

- Less primary air

less
central supply fan energy

- HW coils not in primary


air stream
lower
central supply fan energy

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

100

50

10/5/2015 10:10 AM

Cost Data (per zone)


Includes contractor markup
Source: Communications with HVAC and controls
contractors

VAV reheat

Fan powered VAV

$210

$798

Installation

$1,765

$2,132

Controls

$1,086

$1,217

Electrical

$634

$3,061

$4,781

$70

Box

Total first cost


Filter replacement/yr

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

101

Energy Model Assumptions

Zone properties:

Box minimum = MAX (0.15


cfm/sqft, 15 cfm/person, 20%)

Fan kW taken from Titus and


Price data

PG&E PACIFIC ENERGY CENTER

10,000 sqft, single story


4 15 deep perimeter zones, 1 interior
zone
WWR: 38%
LPD: 0.9 W/sqft
Equipment load: 2.0 W/sqft
Occupants: 100 sqft/person
7am 7pm, M-F
Load schedules vary randomly (average
53% of peak)
VAV packaged unit with air-cooled DX. Hot
water for reheat at zone.
Supply fan static: 3.5 Reheat case, 3.25
FPB case
Max reheat delta T: 35F
Climate Zone 3 (Oakland)

OCTOBER 2015

102

51

10/5/2015 10:10 AM

Energy Model Results


Boxes at minimum majority of time (no energy savings
for fan-powered boxes)
Few hours above 50% (which does not meet T24 or 90.1)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

103

Energy Model Results


Annual Energy Use

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

104

52

10/5/2015 10:10 AM

Energy Model Results (Assumes 500 ft2/zone, excludes


filter maintenance)
Savings
($/sqft)

Years to
payback

$0.06

56.1

Lighting: 0.3 W/sqft


Plug loads: 0.7 W/sqft
Occupancy: 286 sqft/person

$0.12

28.7

$0.10

34.3

$0.05

67.0

Baseline value

Variation

Baseline

Low lighting, low plug


loads, and low
occupancy levels

Lighting: 0.9 W/sqft


Plug loads: 2.0 W/sqft
Occupancy: 100 sqft/person

Oversized system

Average 0.94 cfm/sqft supply air Average 1.4 cfm/sqft supply air

Supply air temperature


control
Hours of operation

55F constant supply air


temperature in cooling
7am - 8pm, Monday through
Friday

24 hours/day, 7 days/week

$0.05

69.9

High zone minimum

20% box minimum

30% box minimum

$0.06

56.6

Low zone minimum

20% box minimum

10% box minimum

$0.07

50.3

Zero minimum

20% box minimum

0% box minimum for fan


powered box

$0.19

19.2

Fan motor

Standard motor

ECM on fan powered box fans

$0.07

50.7

Reheat box control

Dual maximum sequence

Single maximum sequence with


30% minimums

$0.09

40.1

Dual maximum sequence

Single maximum sequence with


50% minimums

$0.41

8.8

Reheat box control

PG&E PACIFIC ENERGY CENTER

Supply air temperature resets


from 55F to 59F

OCTOBER 2015

105

Conclusion
Parallel fan powered boxes are not cost-effective and are
not required in Title 24 2013

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

106

53

10/5/2015 10:10 AM

Future Zone Controls: Time Average Ventilation (TAV)


Ignore the controllable minimum when calculating the desired
airflow setpoint
e.g. in deadband desired setpoint = ventilation minimum
When desired airflow setpoint is below the controllable
minimum then cycle the actual flow setpoint between 0 CFM
and the controllable minimum such that the time averaged
flow = desired setpoint.
Example:
Controllable minimum = 100 cfm
Ventilation minimum = 25 cfm
Setpoint in deadband = 100 cfm for 3 minutes, then 0 cfm for 9
minutes, then 100 cfm for 3 minutes, etc.
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

107

Future Zone Controls: Time Average Ventilation (TAV)


Applicable to dual maximum and single maximum sequences
Pilot projects at UC Berkeley and San Mateo County
One discovery: Zone cycle start/stops need to be
staggered/randomized to mitigate large swings in AHU CFM.
If successful we will propose removing the 20% from Title 24
deadband maximum.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

108

54

10/5/2015 10:10 AM

Dedicated Interior AHU Study from Title 24 2013

Require interior and perimeter zones to be served by


separate air handlers
This would reduce reheat by allowing the perimeter unit
to have colder (summer) and hotter (winter) SAT than the
interior unit.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

109

Typical Practice for Multiple Zone AHUs


Small buildings: one main air handler
Larger buildings:
One AHU/quadrant
One AHU/floor
Separate perimeter/interior AHUs (not common)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

110

55

10/5/2015 10:10 AM

Energy Model Assumptions


10,000 sqft, single story
4 15 deep perimeter zones, 1 interior zone
WWR: 38%
LPD: 0.9 W/sqft
Equipment load: 2.0 W/sqft
Occupants: 100 sqft/person
7am 7pm, M-F
Load schedules vary randomly (average 53% of
peak)
VAV packaged unit with air-cooled DX. Hot
water for reheat at zone.
Max reheat delta T: 35F
Climate Zone 3 (Oakland)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

111

Energy Model Assumptions

Baseline
Single AHU
Zone cooling setpoint

74F
61F Interior zones,
57F Perimeter
Size zones according to supply
zones
air temperature
Supply air temperature

Supply air temperature reset

Proposed
Interior Zones AHU

Perimeter Zones
AHU

74F

74F

62F

57F

57F
62F
57F
Based on zone
loads, temperature
Based on zone
Based on zone
first, from 57F to loads, temperature loads, temperature
65F
first, up to 65F
first, up to 70F

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

112

56

10/5/2015 10:10 AM

0.0800

0.900

0.0700

0.800

0.0600

0.700
0.600

0.0500

kWh/sqft

therm/sqft

Annual Energy Use

0.0400
0.0300

0.500

Baseline
0.400

Baseline

Proposed
0.300

Proposed

0.0200

0.200

0.0100

0.100

0.0000

0.000
Space heating
energy

Fan energy

Cooling
energy

Pump energy

Annual Electricity Savings: $0.0054/sqft


Annual Gas Savings: $0.0057/sqft
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

113

Conclusions
Energy savings is small compared to expected cost of
measure.
Discontinue analysis for this measure.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

114

57

10/5/2015 10:10 AM

Ducted vs Unducted Return Air

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

115

Unducted (Plenum) Return


Advantages of Unducted:
Reduced HVAC cost (~15% of total HVAC cost)
Reduced cost to other trades (e.g. lower floor/floor height)
~25% fan energy savings
No balancing
Less crosstalk
Disadvantages of Unducted:
Potential for mildew in humid climates if building pressure
is allowed to go negative.

Not a real issue with Unducted:


Partially ducted
Unbalanced return / dead spots
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

116

58

10/5/2015 10:10 AM

Supply Air Temperature Control

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

117

OCTOBER 2015

118

SAT Setpoint Reset


Cooler temperature
Decreases fan energy

Warmer temperature
Extends economizer
operation (more hours
with cooling system off)
Reduces reheat at zone
level

What is the best control?

PG&E PACIFIC ENERGY CENTER

59

10/5/2015 10:10 AM

SAT Setpoint Reset


Simulated Control Options
1.

Constant 55F

2.

Reset by zone demand within range (55F to 65F)

3.

Switch to 55F when chiller runs

4.

Switch to 55F when OAT > 70F

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

119

SAT Setpoint Reset


Simulation Results

Sacramento

0.40

0.40

0.35

0.35
Dollars per sq. ft.

Dollars per sq. ft.

San Francisco

0.30
0.25

0.30

0.25
Gas
0.20
Elec.
0.15

0.20
0.15
0.10
0.05

Gas
Elec.

0.10
0.05

0.00

0.00
Constant
55

Reset by Switch to Switch to


zone
T-min
T-min
demand
when
when OAT
chiller runs
> 70

PG&E PACIFIC ENERGY CENTER

Constant
55

OCTOBER 2015

Reset by
zone
demand

Switch to Switch to
T-min
T-min
when
when OAT
chiller runs
> 70

120

60

10/5/2015 10:10 AM

Recommended SAT Reset Logic

Reheat

Economizer

None

None

Medium
to High
(e.g. VAVRH)

Constant SAT at design (~55F)

Yes

Constant SAT at design. Allow to float


up by locking out cooling until zone
request indicates need for CHW

Yes

Reset by zone cooling demand during


cool weather (<55F to 60F OSA), then
ramp down to design SAT in warm
weather (>60F to 70F OSA)

Low
(e.g. DFDD,
fan-powered
VAV)

SAT Logic

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

121

Recommended Sequence of Operations VAV-Reheat

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

122

61

10/5/2015 10:10 AM

(continued)
Where:
Tmin

A constant (e.g. 53 F )

Tmax

Ranges from 55F to 65F based on


zone demand (cooling loop values)
(Exact sequence discussed below)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

123

VAV Reheat System


SAT Reset Logic
During occupied mode, the setpoint is reset from T-min (53F) when the
outdoor air temperature is 70F and above, proportionally up to T-max when
the outdoor air temperature is 60F and below. T-max shall be reset using
trim and respond logic within the range 55F to 65F. When fan is off, freeze
T-max at the maximum value (65F). While fan is proven on, every 2
minutes, increase the setpoint by 0.2F if there are two (adjustable) or fewer
zone cooling requests. If there are more than two (adjustable) cooling
requests, decrease the setpoint by 0.3F. A cooling request is generated
when the cooling loop of any zone served by the system is >99%.

Adjustable to limit
dominance of
rogue zones
PG&E PACIFIC ENERGY CENTER

Lower if reheat reduced


using dual maximum
logic and central plant
OCTOBER 2015

124

62

10/5/2015 10:10 AM

Performance Oversized Zones

62

60

58

56

54

52
52

54

56

58

60

62

64

Outdoor Air Temperature (oF)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

125

Performance Rogue Zones


64
Supply Air Temperature Setpoint (oF)

Supply Air Temperature Setpoint (oF)

64

62
60
58
56
54
52
52

54

56

58

60

62

64

66

68

Outdoor Air Temperature (oF)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

126

63

10/5/2015 10:10 AM

The Future of SAT Reset: Model Predictive Control


At each time step, compare the estimated HVAC energy cost at the
current SAT with the estimated energy cost at alternative SATs (e.g.
one degree warmer and one degree cooler) and adjust the set-point
in the direction of the lower cost.
Zone requests for colder SAT takes priority over the energy cost
signals.
Requires detailed models for fans, chiller plant, boiler plant, DX
compressors, etc.
Inputs each time step could include:
Measured load and reheat at each zone (based on DAT and CFM)
OADB/OAWB
Fan speed, P
Chiller plant load
Boiler plant load
Utility rates

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

127

Outside Air Control

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

128

64

10/5/2015 10:10 AM

Outside Air
Control of Minimum outdoor air for VAV Systems
Design of Airside Economizer Systems
Economizer Temperature Control
Economizer High-Limit Switches

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

129

Lab and Field Tests


Fisk et al (LBNL 2004, 2005)
Measured performance of 5 measurement technologies in
lab and a few in the field

Unfortunately only tested a few products many more


available but untested

ASHRAE RP-980
Theoretical review and lab tests of several common airflow
measurement concepts

May be the only two unbiased tests (not performed by


manufacturers)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

130

65

10/5/2015 10:10 AM

Fixed Minimum OA Damper Position


Not Recommended &
Prohibited in T24 2013

Does NOT WORK for VAV since mixed air plenum


pressure varies!! Outdoor air flow will vary
proportional to supply air flow.

Outdoor Air

Minimum
Signal Pot.

Return Air
Signal from SAT
Controller
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

131

RP980 Lab Results


Fixed Minimum OA Damper
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

110%

S u p p l y A ir % of D e si g n

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

132

66

10/5/2015 10:10 AM

Dual Minimum Mitigation


Minimum damper position is set proportionally based on
fan speed between setpoints determined when the fan is
at full speed and minimum speed
Low cost
Affected by wind, stack effective, filter loading
Prohibited in T24 2013

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

133

Energy Balance
Not Recommended

Does NOT WORK when OAT ~ RAT (which it is when high limit is reached)

Outdoor Air

MAT

OAT

RAT

Return Air
DDC
%OA = (MAT - RAT) / (OAT - RAT)
CFM-OA = %OA * CFM-SA
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

134

67

10/5/2015 10:10 AM

Return Fan Tracking


OA CFM = Supply CFM Return CFM
May not work if pressurization CFM is different from OA CFM (e.g. operable windows)

Outdoor Air

VSD

Exhaust Air
Return Air
DDC
Signal from SAT
Controller
PG&E PACIFIC ENERGY CENTER

VSD

OCTOBER 2015

135

Air Flow Measurement of 100% OA


Not Recommended

Outdoor Air

AFMS

Will only work if AFMS is very accurate at low flow (i.e. at min OSA)!

Return Air
DDC
Signal From SAT Controller
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

136

68

10/5/2015 10:10 AM

Injection Fan w/AFMS


This works if controlled
using a damper and fan
airflow measurement as
shown.

AFMS

Outdoor Air

It will not work with a


variable speed fan alone as
the DP will vary across the
fan.

Injection Fan w/ Discharge


Damper

Return Air
Signal from SAT Controller
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

137

Dedicated Minimum Outdoor Air Section with AFMS


Recommended
Works! But space needed for AMS

Outdoor Air

DDC

Return Air
Signal from SAT Controller

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

138

69

10/5/2015 10:10 AM

Fixed Minimum OA Damper w/ Plenum Pressure Control


This works, and is generally the lowest cost solution. However, the
control sequence can be complex and/or fan energy increased
slightly. Not accurate when the min. OSA airflow setpoint is reset
(e.g. for DCV).

Recommended!

Outdoor Air

DDC

Return Air
Signal from SAT Controller

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

139

Fixed Minimum OA Damper w/ Plenum Pressure


Control
Open minimum outdoor air damper when the supply air
fan is proven on and the system is not in warm-up, cooldown, setup, or setback mode. Damper shall be closed
otherwise.
The minimum differential pressure setpoint across the
mixed air plenum (MinDP) is determined by the air
balancer as that required to maintain design minimum
outdoor air flow rate across the minimum outdoor air
damper with the supply air fan at design airflow.
When the economizer is locked out due to warm weather,
the RA damper signal is modulated to maintain
differential pressure across the outdoor air damper at
setpoint, MinDPsp, determined above.
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

140

70

10/5/2015 10:10 AM

Summary of OSA Control Methods


METHOD
Fixed Minimum
Dual Minimum
Energy Balance
Return Fan Tracking
100% AFMS
Injection Fan
Dedicated Min AFMS
P Across OA Damper
PG&E PACIFIC ENERGY CENTER

ACCURACY
Very poor
Fair
Very Poor
Fair to Good
Poor to Good
Good to Excellent
Good to Excellent
Good

OCTOBER 2015

141

Comparison of the Options that Work


Option
Minimum position
reset by fan speed

Advantages

Disadvantages

Least expensive
Available on some packaged
VAV systems as standard
No additional AHU length
required

Inaccurate
No compensation for wind and other effects
Field calibration required
Does not work well with CO2 DCV
Prohibited in Title 24 2013

Total outdoor airflow rate


always known
Can be used for CO2 DCV
Does not require return air
damper pressure control

Questionable accuracy of anemometer


Expensive
Requires extra AHU length

100% Outdoor Air


AFMS with thermal
anemometer

Injection Fan and


dedicated minimum
AFMS

Does not require return air


damper control

Most expensive
Requires extra AHU length

Dedicated minimum
AFMS

Can be used for CO2 DCV

Requires extra AHU length


Requires return air damper control

Plenum pressure
control

Very inexpensive
No additional AHU length
required

Field calibration required


Does not work well with CO2 DCV
Requires return air damper control for best
efficiency

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

142

71

10/5/2015 10:10 AM

Title 24 2013 and OSA


Minimum OSA tested at design and minimum
flows
30% design or
All boxes at minimum position

Measured OSA airflow must be within 10% of


design at both conditions
Failing the test jeopardizes the certificate of
occupancy

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

143

Design of Economizer
Systems

144

72

10/5/2015 10:10 AM

Air Economizers

100%

% Open

Economizer
OA damper

Min OA

Return air
damper

CHW valve

0%

No
Cooling

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

Control Loop Control

Maximum
Cooling

145

Economizer Design Issues


Damper types and sizing
(see Guideline 16)
Damper configuration
Building pressure control
Sequencing of fans and dampers
High limit switches

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

146

73

10/5/2015 10:10 AM

Building Pressure Control


1.

Barometric

2.

Relief Fans

3.

Return Fans

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

147

Barometric Relief (with 100% OA Flow Measure)


Lowest energy
Requires low return pressures
Relief can be put anywhere
Relief openings can be prohibitively large

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

Design for < 0.08 P


in Relief Path

148

74

10/5/2015 10:10 AM

Relief Fan with Direct Pressure Control


Stage relief damper before staging on relief fans
P-2 setpoint = 0.05
Rolling average building pressure signal
Do not locate sensor in the lobby!

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

149

Return Fan with Direct Pressure Control


Control return fan to maintain return plenum pressure (P-3) at setpoint

P-3 Max Setpoint = P needed to maintain P-2 at 0.05 at 100% OA

Bldg pressure loop first opens relief damper then resets the P-3 setpt from 0 to
Max
Same pressure issues as relief fan
Bldg pressure loop must be slower than return fan loop to prevent instability

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

150

75

10/5/2015 10:10 AM

Return Fan with Tracking Control


Return fan speed maintains return flow = supply flow minus fixed
offset for pressurization
Not vulnerable to building pressure sensor or bldg pressure loop vs
return fan loop instability

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

151

Economizer Damper Control


(Most Common)

100%

% Open

Economizer
OA damper

Min OA

Return air
damper

CHW valve

0%

No
Cooling

Control Loop Control

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

Maximum
Cooling

152

76

10/5/2015 10:10 AM

Economizer Damper Control


(More Efficient)

Return
Air Damper
Outdoor Air Damper

ciO
m
n
o
zA
rE
e
p
a
d

O
n
e
p
%

Damper/Valve Position, % Open

100%

iM
O
n
A

rd
e
p
R
m
a
itu
n

C
H
W
v

%
0
C
o

o
trn
C
N
lig

lo
trn
C
p
L

lve
a

CHW Valve
Minimum Position
(MinOA)

0%

Supply Air Temperature Control


Loop Output Signal

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

153

OBD vs. PBD when Mixing

O
n
e
p

ciO
m
n
o
zA
rE
e
p
a
d

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

iM
O
n
A

rd
e
p
R
m
a
itu
n

C
H
W
v

%
0
C
o

C
N
o
trlig
n

lL
C
p
o
tr
n

lve
a

154

77

10/5/2015 10:10 AM

Air Economizer Control


MINIMUM OA
DAMPER

ECONOMIZER OA
DAMPER

SUPPLY FAN

OUTDOOR
AIR
SUPPLY AIR
TEMP SENSOR
CHW VALVE

RA
DAMPER
HIGH LIMIT
SWITCH

SUPPLY AIR TEMP


CONTROLLER

RETURN
AIR
100% OPEN

CHW VALVE

0% OPEN
SUPPLY AIR TEMP CONTROL LOOP

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

155

170

45

Optimum Lockout
Wet Cooling Coil

160
150
40

140
130
120

35

Outdoor Air

30

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

90
80

25

Return Air

15

NO

Supply Air

5
0

50
40

Outdoor Air

30

10

70
60

20

-10 -5

100

Humidity Ratio, grains/lb of dry air

110

20

YES

10

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

156

78

10/5/2015 10:10 AM

170

45

160

Optimum Lockout
Dry Cooling Coil

150
40

140
130
120

35

100

30

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

90
80

25

Return Air

60

20

50

Supply Air
15

Outdoor Air

10

40
30
20

NO

YES

-10 -5

70

10

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

157

170

45

Optimum Lockout
Wet or Dry
Cooling Coil

160
150
40

140
130
120

35

100

30

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

90
80

25

Return Air

70
60

20

50
15
10

Supply Air

Humidity Ratio, grains/lb of dry air

110

40
30

YES

NO

20
10

-10 -5

Humidity Ratio, grains/lb of dry air

110

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

158

79

10/5/2015 10:10 AM

High Limit Devices


Fixed Drybulb Temperature
Compares outdoor air drybulb to a fixed setpoint
Differential Drybulb Temperature
Compares outdoor air drybulb to return air drybulb
Fixed Enthalpy
Compares outdoor air enthalpy to a fixed setpoint
Differential Enthalpy
Compares outdoor air enthalpy to return air enthalpy
Electronic Enthalpy
Compares outdoor air temperature and humidity to a
setpoint that is a curve on the psychrometric chart
PG&E PACIFIC ENERGY CENTER

Where
Fixed Drybulb
Switches Fail
(72F Setpoint)

OCTOBER 2015

170

45

160
150
40

140
130
120

35

110
100

30

90
25

80

Return Air

70
60

20

50
15

Supply Air

10
5

40
30
20
10

-10 -5

Too hot

Humidity Ratio, grains/lb of dry air

NO

YES

Too moist

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

159

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

160

80

10/5/2015 10:10 AM

Where
Fixed Drybulb
Switches Fail
(65F Setpoint)

170

45

160
150
40

140
130
120

35

110
100

30

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

90
80

25

Return Air

70
60

20

50

Supply Air

15

40
30

10

20

10

-10 -5

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

161

170

45

Where
Differential Drybulb
Switches Fail

160
150
40

140
130
120

35

NO

100

30

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

110

90
25

20

Return Air

80
70
60
50

15
10
5

Humidity Ratio, grains/lb of dry air

YES

40
30
20
10

-10 -5

Humidity Ratio, grains/lb of dry air

NO

YES

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

162

81

10/5/2015 10:10 AM

170

45

160

Where
Differential Drybulb
Switches Fail

150
40

140
130
120

35

NO

100

30

Weather Hours
117 to 105
104 to 92
91 to 79
78 to 66
65 to 53
52 to 40
39 to 27
26 to 14
13 to 1

110

90
25

Return Air

80
70
60

20

50
15

40
30

10

20

10

-10 -5

Humidity Ratio, grains/lb of dry air

YES

San Francisco Weather

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-Bulb Temperature,
F 2015
PG&E PACIFIC ENERGY CENTER
OCTOBER

163

Where
Differential Drybulb
Switches Fail

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

164

82

10/5/2015 10:10 AM

170

45

Where
Fixed Enthalpy
Switches Fail

160
150
40

140
130
120

35

Humidity Ratio, grains/lb of dry air

110

NO

30

Weather Hours
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1

100
90
80

25

Return Air

YES

70
60

20

50

Supply Air

15

40
30

Too dry

10

20

10

-10 -5

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Dry-BulbO
Temperature,
PG&E PACIFIC ENERGY CENTER
CTOBER F2015

165

15oC
25oC
o

35 C

6
3
0
-3
-6
-9
-12
0

10

20

30

40

50

60

70

80

90

35 C

3
0
-3
-6
-9
-12

100

25 C
o

35 C

3
0
-3
-6
-9
-12
0

10

Deviation from Actual Relative Humidity (%)

Deviation from Actual Relative Humidity (%)

15oC

10

20

30

40

50

60

70

80

90

12

15oC

25oC
o

35 C

6
3
0
-3
-6
-9
-12
0

100

10

20

15oC

25 C
o

35 C

6
3
0
-3
-6
-9
-12

30 40 P
50 ACIFIC
60 70 80ENERGY
90 100
10 20 30 40OCTOBER
50 60 70 802015
90 100
PG&E
C0 ENTER
Actual Relative Humidity (%)

30

40

50

60

70

80

90

100

Actual Relative Humidity (%)

Model E

20

Actual Relative Humidity (%)

Model C

12

Actual Relative Humidity (%)

Model D

25oC

Actual Relative Humidity (%)

12

15oC

Deviation from Actual Relative Humidity (%)

Model B

12

Deviation from Actual Relative Humidity (%)

Model A

12

Deviation from Actual Relative Humidity (%)

Deviation from Actual Relative Humidity (%)

Measured Accuracy of New Sensors


Iowa Energy Center

Model F
12
15oC

25oC
o

35 C

6
3
0
-3
-6
-9
-12
0

10

20

30

40

50

60

80 90
166

70

100

Actual Relative Humidity (%)

83

10/5/2015 10:10 AM

Accuracy at 77F After 1 Year Aging


Iowa Energy Center

6
3
0
-3
-6

6
3
0
-3
-6

6
3
0
-3
-6

-9

-9

-12

-12

-12

20

30

40

50

60

70

80

90

100

10

20

Model D
New
4 months
8 months
12 months

6
3
0
-3
-6

60

70

90

100

10

20

30

80

90

50

60

70

80

90

100

80

90

100

Model F

12
9

-24
New
4 months
8 months
12 months

-30

6
3
0
-3
-6

New
4 months
8 months

-9
-12

100

40

Actual Relative Humidity (%)

-18

-12
50

80

-12

-42

40

70

-36

30

60

-6

-9

20

50

6
Deviation from
Actual Relative Humidity (%)

Deviation from
Actual Relative Hum idity (%)

10

40

Model E

12

12

30

Actual Relative Humidity (%)

Actual Relative Humidity (%)

Deviation from
Actual Relative Hum idity (%)

10

New
4 months
8 months
12 months

-9

Model C

12
New
4 months
8 months

9
Deviation from
Actual Relative Hum idity (%)

Deviation from
Actual Relative Humidity (%)

Model B

12
New
4 months
8 months
12 months

Deviation from
Actual Relative Hum idity (%)

Model A

12

10

20

PG&E
PACIFIC
Actual Relative
Humidity (%) ENERGY CENTER

30

40

50

60

70

80

90

OCTOBER 2015

100

10

20

30

Actual Relative Humidity (%)

40

50

60

70

167

Actual Relative Humidity (%)

Aging / Drift Testing Results


Model E

standard
mean
deviation
(% RH)
(% RH)

transmitter
symbol

-2.9
-3.0

10

Deviation from
Actual Relative Humidity (%)

Deviation from
Actual Relative Humidity (%)

Model C
24
21
18
15
12
9
6
3
0
-3
-6
-9
-12
-15
-18
-21
-24

20

30

1.2
1.1

40

50

60

70

80

90

100

24
21
18
15
12
9
6
3
0
-3
-6
-9
-12
-15
-18
-21
-24

transmitter
symbol

standard
mean
deviation
(% RH)
(% RH)
-1.0
2.0

10

Actual Relative Humidity (%)

20

30

10.2
9.3

40

50

60

70

80

90

100

Actual Relative Humidity (%)

One year of data collected at 15 minute intervals


Reference: Precision Grade 1% RH in-situ reference sensor
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

168

84

10/5/2015 10:10 AM

Aging / Drift Testing Results


Model B

Model D

Variation of performance between two sensors of the same Model


Precision Grade 1% RH in-situ reference sensor
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

169

Electronic Enthalpy Control

Manufacturer:
The A setting provides the greatest
energy
savings.

ASHRAE 90.1 and Title 24:


The A setting is required in all
climate zones

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

170

85

10/5/2015 10:10 AM

Performance Solid State Enthalpy Switch


Actual Test Data

Enthalpy Switch #2 Published vs Actual Data

Enthalpy switch action curve

100

90

80
Setting A

Relative Humidity, %RH

70

Setting D

60

50

Setting D

~ 4 BTU/lb
Hysteresis

Setting A

~ 20% RH @
same temp

40

30
30 Btu/Lb
Setting D
20

Setting A
25 Btu/Lb

Economizer Disable

10

Economizer Enable

A
20 Btu/Lb

0
40

45

50

55

60

65

70

75

80

85

90

95

100

Chamber Temperature, Deg F

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

171

Economizer High Limit Switch

Sensor Error Bars


Title 24-2013 Requirements

Fixed drybulb is best!

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

172

86

10/5/2015 10:10 AM

Reference
Economizer High-Limit Controls and Why Enthalpy
Economizers Dont Work
By Steve Taylor and Hwakong Cheng
ASHRAE Journal November 2010
Available at http://tinyurl.com/23xegku.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

173

Supply Static Pressure Control

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

174

87

10/5/2015 10:10 AM

Fan Energy at Varying SP Setpoints


120%

100%

Percent Fan kW

80%
SP setpoint = TSP
SP setpoint = TSP*.75
SP setpoint = TSP/2
SP setpoint = TSP/3

60%

Surge Region

SP setpoint = 0

40%

20%

0%
0

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Percent Fan CFM

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

175

Real Fan Systems


Many Hours At Low Loads
4

Actual Data
Perfect System Curve (i.e. SP reset)

Pressure Drop Across Fan (" H2O)

3.5

Design Point (145,000 CFM at 4.0")


3

Likely Actual System Curve (No SP Reset)

2.5
2
1.5
1
0.5
0
0

20,000

40,000

60,000

80,000

100,000

120,000

140,000

Total CFM (SF-1 + SF-2)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

176

88

10/5/2015 10:10 AM

Static Pressure Reset Controls PIER Research


No Static Pressure Reset

Annual Fan Energy Cost (at $0.12/kwh)

Perfect Static Pressure Reset


$4,000

$3,602

$3,500

$3,555

~20% (type of fan)


$3,057

$3,246

$3,171

$3,000

$2,998

$2,500
$2,000
$1,500

~66% (SP reset by zone demand)


$1,254

$1,266

$1,231

$1,232

$1,250

$1,248

$1,000
$500
$60" Plenum
Fan (3.5"
Design SP)
(62.4%)

60" BI
(71.2%)

PG&E PACIFIC ENERGY CENTER

66" BI
(75.5%)

49" AF
(75.4%)

44.5" AF
(73.0%)

54" Mixed
Flow
(73.4%)

OCTOBER 2015

177

Static Pressure Setpoint Reset Control Logic Options


Option 1: Reset static pressure setpoint based on PID
Loop on VAV damper position
Option 2: Reset static pressure setpoint using Trim &
Respond based VAV damper position or airflow demand

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

178

89

10/5/2015 10:10 AM

Best Choice: Trim and Respond


Advantages
Easier to tune
Can respond more quickly than trim
Does not require knowledge of damper position
Easier to ignore the first few requests
Easier to track rogue zones (e.g. runtime counter on
requests, cumulative percent request hrs)

Easier to lock out rogue zones


Easier to assign importance multipliers
Can escalate requests (e.g. 1 request if zone is 1F above
setpoint, 3 requests if 3F above setpoint)
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

179

Trim & Respond SP Setpoint Reset Logic


Static pressure setpoint shall be reset using trim and respond logic
within the range 0.15 inches to 1.5 inches. When fan is off, freeze
setpoint at the minimum value (0.15 inches). While fan is proven on,
every 2 minutes, decrease the setpoint by 0.04 inches if there two
(adjustable) or fewer pressure requests. If there are more than two
(adjustable) pressure requests, increase the setpoint by 0.04.
Where VAV zone damper position is known, a pressure request is
generated when any VAV or underfloor damper served by the system
is wide open. Where VAV zone damper position is unknown, a
pressure request is made when the ratio of the zones actual supply
airflow to supply airflow setpoint is less than 90%.

Adjustable to limit dominance


Set by TAB Contractor of rogue zones
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

180

90

10/5/2015 10:10 AM

Variations on this Sequence


A damper position (valve position, loop output, etc.) of
80% counts as one request, while a position of 95%
counts as two requests.
The response rate is a function of the number of
requests, e.g. response = 0.04 times the number of
requests.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

181

Tuning Unstable Control


1.4

Static Pressure Setpoint

1.2

y = 0.6709x + 0.2656
2

R = 0.5971

1
0.8
0.6
0.4
0.2
0
0

0.2

0.4

0.6

0.8

1.2

1.4

Actual Static Pressure

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

182

91

10/5/2015 10:10 AM

Tuning Stable Control

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

183

Trim & Respond Example


Static Pressure Reset by Demand

Trim

Respond

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

184

92

10/5/2015 10:10 AM

Demand Based Reset Rogue Zones


VAV2-9 is likely undersized!

VAV2-20

VAV2-21

VAV2-11

VAV2-22

VAV2-23

VAV2-24

VAV2-25

VAV2-27

VAV2-30

VAV2-31

VAV2-6

VAV2-7

VAV2-28

VAV2-9

Cooling Loop Output (%)

100
80
60
40
20
0
6/27/06 3:00

6/27/06 6:00

6/27/06 9:00 6/27/06 12:00 6/27/06 15:00 6/27/06 18:00 6/27/06 21:00

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

185

Fan Summary
SP reset is FANtastic!
50% energy savings
Keeps fan out of surge
Airfoil fans are more efficient, cheaper, and stay out of
surge longer than plenum fans but are noisier and
require more space
Set VFD minimum speed to 10% (6 Hz) or less

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

186

93

10/5/2015 10:10 AM

Filters
Avoid pre-filters
Adds pressure drop
Does not catch anything that final filter will not catch
Does not extend final filter life final filters should be
replaced regularly due to VOCs emitted from dirt in the filter

Use 15 MERV 13 bag filters


lasts 12 months versus 4 months for a 4 MERV 13
Beware 2 MERV 13 can loose effectiveness

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

187

VAV vs. DOAS with Chilled Beams

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

188

94

10/5/2015 10:10 AM

Overview
ASHRAE GGC Seminar with support from CBE
Three HVAC systems were compared on one building:
VAV reheat
DOAS w/ active chilled beams
A hybrid of the two
Construction costs were estimated by contractors using
SD documents from each team
Annual energy was compared using EnergyPlus

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

189

DOAS with Flat Panel Radiant

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

190
190

95

10/5/2015 10:10 AM

DOAS with Chilled Beams

Active Chilled Beams


(OA is supplied through beam to
improve capacity through induction)

PG&E PACIFIC ENERGY CENTER

Passive chilled beam


(Radiation and
convection only)

OCTOBER 2015

191

Potential Advantages of DOAS vs. VAV


Assures design outdoor air rates delivered to space
No multiple spaces issues per Standard 62.1
No concerns about minimum airflow setpoints and controls
No complex outdoor airflow measurement/control devices
See previous slides
No economizer and mixing plenum
No dampers to freeze up, maintain
No coil freeze problems from imperfect mixing in cold climates
No RH/enthalpy sensors to maintain
If zonal system is passive (radiant, chilled beams)
May reduce fan energy
Allows warmer CHW source (possibly even cooling tower if dry
climate)
Should be quieter
Less ceiling space required for duct mains
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

192

96

10/5/2015 10:10 AM

Potential Disadvantages of DOAS vs. VAV


Reduced annual outdoor air supply compared to systems with economizers
Fisk study shows significant indoor air quality and associated health benefits
from economizers
High maintenance costs of zonal fan-coils or heat pumps
Filters, coils, fans, pans, etc.
Slow response and low capacity if passive radiant system
Higher first costs depending on design details
Need OA duct, CHW, and HW to each zone
4-pipe fan-coils and heat pumps are typically twice as expensive as VAV
zones
Radiant panels or chilled beams 5 times as expensive as VAV zone
Lack of economizer usually causes cooling energy usage to be higher than
a well designed VAV system in mild climates
Fan energy may be higher!
Potential for mold and mildew growth due to condensation on chilled beam
cooling coils
Do not work well with operable windows because of the risk of humid
outside air condensing on the chilled beams.
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

193

ASHRAE Seminar Presentations


The following slides are just summary excerpts
The full presentations are posted here:
http://www.ggashrae.org/seminar
ASHRAE Journal Article: http://www.taylorengineering.com/downloads/articles/ASHRAE%20Journa
l%20-%20VAVR%20vs%20ACB+DOAS.pdf

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

194

97

10/5/2015 10:10 AM

Actual UC Davis GSB Design


Taylor Engineering
The Floor/Floor Height is the same for all 3 systems
VAV System

ACB System

Hybrid System

One shaft:

Two shafts:

Two shafts:

12 Duct

16 Duct

18 Duct

Mechanical Space Requirements


Taylor Engineering
HVAC MECHANICAL ROOM AREA (ft2)
CHILLED
FLOOR
VAV
HYBRID
BEAMS
1ST Pump/HX
2nd Shafts
3rd Shafts
Penthouse
Total

1st Floor Chilled Beam

460
144
144
4220
4968

0
113
113
2270
2496

327
154
154
4660
5295

1st Floor Hybrid

98

10/5/2015 10:10 AM

Title 24-2008 Rules & EnergyPro Bugs Favor Chilled Beams!


Taylor Engineering
Active Chilled Beams (using Induction Unit system)

Baseline: constant volume


packaged DX with 100%
outdoor air

VAV system

VAV worse than


ACB vs. Title 24

But absolute energy use


is 40% lower!

Baseline: Variable volume


packaged DX w/outdoor air
economizer

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

197

EnergyPro Title 24-2008 Simulation Results for GSB


This is the baseline for all
systems in T24-2013

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

198

99

10/5/2015 10:10 AM

Energy Plus Energy Model Result


SOM

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

199

VAV Reheat has lower total fan energy

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

200
200

100

10/5/2015 10:10 AM

VAV Reheat provides more outside air

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

201
201

Comparative Cost Study by Southland Industries


Cost comparative Study of Mechanical system.
SYSTEM
DESCRIPTIONS
Overall Cost
cost/SF
PARAMETER
COMPARISON
Material Cost
Labor Cost
Equipment Cost
Sub-contractors
lbs of ductwork
linear feet of
chilled water
linear feet of
Heating hot water
AHU CFM

Overhead VAV system.


$1,371,000
$25.39

Hybrid VAV with Chilled Beam


$1,980,000
$36.67

Chilled Beam
$3,341,000
$61.87

$215,179
$584,058
$319,695
$252,067
38,000 lbs

$279,703
$877,138
$380,297
$442,862
33,224 lbs.

$576,496
$1,509,349
$608,118
$647,037
28,612 lbs.

310 feet

5,963 feet

10,244 feet

2,085 feet
50,000 CFM

2,330 feet
38,000 CFM

9,630 feet
36,000 CFM

Chilled Beam System would take 80 years to pay back if it used zero energy!
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

202

101

10/5/2015 10:10 AM

Field Research

Significance
Reduce energy use of VAV systems

zone for
1 year

Frequency

Energy code adoption of


low minimum VAV control
Title 24-2008
ASHRAE 90.1-2013

Existing buildings retrofit opportunity


with less than 1 year payback

MIN

MAX

Cooling airflow

Barriers to market acceptance

VAV controller stability


Resolved (PG&E, ASHRAE RP 1353)

Potential occupant comfort issues?


Dumping diffusers
Poor room air mixing
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

204

102

10/5/2015 10:10 AM

Objective and method


Objectives
Measure energy savings & validate simulations
Identify comfort issues that may occur at low flow
Funding
California Energy Commssion - PIER
ASHRAE
UC Berkeley - Center for the Built Environment
Method
Field Study in 7 buildings
Background survey
Right now survey matched to zone trends
Energy monitoring
Laboratory Study
Air distribution for various diffuser types
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

205

Variable air volume (VAV) controls overview


AIRFLOW (CFM)

Typical
VAV box airflow control
2000

30%

Heating

Deadband

Cooling

1000

Low minimum
VAV box airflow control
(dual-maximum)

0
6 AM

12 PM

6 PM

10-20%
Heating Deadband Cooling
Diagrams exclude heating control for clarity

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

206

103

10/5/2015 10:10 AM

Yahoo! Sunnyvale Campus

B
C
A
D
Energy Meter

A,B,E,G

F
G

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

207

Yahoo! Sunnyvale Campus

1073 Zones
3700 Occupants
Plaque face diffusers
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

208

104

10/5/2015 10:10 AM

800 Ferry Building

22 Zones
Perforated Diffuser
with blades in face

PG&E PACIFIC ENERGY CENTER

5-15%

OCTOBER 2015

209

30% +

35-50%

PG&E PACIFIC ENERGY CENTER

5-15%

OCTOBER 2015

210

105

10/5/2015 10:10 AM

Example trend: perimeter zone facing east

AIRFLOW
(CFM)

2000

Cooling maximum

VAV reheat
zone
1000

Cooling minimum

0
6 AM

PG&E PACIFIC ENERGY CENTER

12 PM

6 PM

OCTOBER 2015

211

Example trend: interior


Cooling maximum
1000

AIRFLOW
(CFM)

VAV cooling
only zone

500

Cooling minimum

0
6 AM

PG&E PACIFIC ENERGY CENTER

12 PM

OCTOBER 2015

6 PM

212

106

10/5/2015 10:10 AM

Energy Results

213

Measured flow fractions: Yahoo campus


(all 1000 zones for the entire study period)

0.15

Cool Season All Occupied Hours


Low Minimum
30% Minimum

Density
0.05
0.00

0.00

0.05

Density

0.10

Low Minimum
30% Minimum

0.10

0.15

Warm Season All Occupied Hours

20

40

60

80

100

Flow Fraction [%]

PG&E PACIFIC ENERGY CENTER

20

40

60

80

100

Flow Fraction [%]

OCTOBER 2015

214

107

10/5/2015 10:10 AM

(high ~30%)
(low ~10-15%)

8%

20%

17%

9%

22% <---Savings

(high ~30%)
(low ~10-15%)

16%

19%

9%

PG&E PACIFIC ENERGY CENTER

4%

6% <---Savings

OCTOBER 2015

215

Loads are surprisingly low


0.2 0.5

CFM/FT2 at 20F T

140 Zones, 2 buildings, 1 warm month (Sept)


PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

216

108

10/5/2015 10:10 AM

What happens when load is less than design minimum?

Cooling
Setpoint
Heating
Setpoint

110% Design Load


(VAV box size)

100% MAX load

COOLING
LOAD
30% MIN capacity

over
cooling

(VAV box minimum flow)

10% Typical load


PG&E PACIFIC ENERGY CENTER

reheat

OCTOBER 2015

217

Average of 3F more reheat during high min flows


High operation: Tdischarge = 63.5F, SD=14F Low operation: Tdischarge = 60.7F, SD=8.7F
Yahoo! Building Warm season - Discharge air temperature
HIGH minimum flow rate
LOW minimum flow rate

120

100

80

55

68

52

43

43

11

43

27

58

27

34

20

57

67

26

24

17

45

16

32

61

61

72

68

64

69

62

60

61

59

61

62

69

59

59

61

60

65

61

59

61

58

8.3 9.9

16

8.6 8.5

22

18

15

15

10

4.6

7.6 8.8

10

13

7.5

6.2

7.2 3.8

12

10

7.6

10

4.1

10/02

10/05

10/06

10/07

10/09

10/10

10/10 low

10/11

10/13

10/14

10/16

10/17

10/18

10/19

10/21

10/23

10/25

10/26

sd 2.2 2.1

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

10/27

10
70

10/20

34
60

10/12

26
60

10/04

20
58

10/03

Mean 58

09/30

20

09/28

40

09/29

60

09/27

discharge air temperature [F]

140

218

109

10/5/2015 10:10 AM

What about your building: Savings?

0.55

$ .

= $0.066/ft2

Total gas + elec savings


$0.10

0.025

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

$ .

= $0.025/ft2

219

What about your building: Costs?


New construction
Minimal - Requires VAV discharge air temp sensor that is
often desired for other reasons.

Existing buildings
Engineering calculations of zone minimums
o

Requires collection of zone data:


ft2
Occupant density
VAV box size & controllable minimum

Operator time to enter new setpoints


Estimate < $0.10/ft2 cost for ~ 1 year payback
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

220

110

10/5/2015 10:10 AM

Conclusions
Conclusions
Energy savings is significant and similar to simulation
predictions
Validates Title 24 & 90.1 energy code requirement
Significant retrofit opportunity for existing building with DDC
controls. Less than 1 year payback.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

221

Thermal Comfort
Results

222

111

10/5/2015 10:10 AM

Occupant comfort study


Questions
When the minimum flow rate is reduced from high to low:
Did occupants become less comfortable?
Was their sense of air movement stronger due to dumping?
Approach
Surveyed 6 Yahoo! buildings and a county legal office (800 Ferry building)
3 surveys: Yahoo warm and cool seasons, 800 Ferry building warm
season
3 4 weeks of surveying each season
Switched between high and low minimum operation in the middle of
each survey period (unknown to occupants)
Surveys administered 3 times/day
About 10,000 responses received

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

223

Thermal comfort questions

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

224

112

10/5/2015 10:10 AM

Air movement questions

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

225

Perceived air quality question

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

226

113

10/5/2015 10:10 AM

Temperature satisfaction survey results (an example:


Yahoo! warm season)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

227

"How satisfied are you with the temperature in your workspace?


HIGH min flow rate

% dissatisfied of people

30.0%

LOW min flow rate

249

25.0%
681
20.0%
15.0%

463
1408

10.0%

1793

766

5.0%
0.0%
800 Ferry
Warm
800Building
Ferry Building

season Yahoo! Cool season

Yahoo! Warm season

114

10/5/2015 10:10 AM

Thermal sensations (Yahoo! warm season, 1865 votes)


HIGH min flow rate

LOW min flow rate

37.4%

60%

55.9%

50%
41.6%

40%

24.2%

30%
21.5%

20%

16.7% 16.8%

16.1%
10.4%

10%

5.5%

4.8%

3.3%

4.3%

2.9%

0.1% 0.2%

0%

Cold (-3)

Cool (-2)

Slightly cool (- Neutral (0) Slightly warm


1)
(1)

PG&E PACIFIC ENERGY CENTER

Warm (2)

Hot (3)

OCTOBER 2015

229

Air temperature under high and low minimum flows


(800 Ferry building)
High flow: average Tair = 71.2F
85

Low flow: average Tair = 73.3F

HIGH minimum flow rate


LOW minimum flow rate

75

70

N
14
Mean 72
sd
1.4

27
72
2

23
71
1.8

35
71
1.5

45
72
1.6

36
71
1.5

35
71
1.4

41
71
1.8

47
70
1.6

34
71
1.5

65
71
2

23
72
0.89

30
73
1.6

51
74
1.5

45
74
1.1

64
73
1.9

25
74
1.1

37
74
1.4

67
75
1.3

27
75
1.2

48
73
2.1

09/26

09/27

09/28

09/29

09/30

10/03

10/04

10/05

10/06

10/07

10/10

10/11

10/12

10/13

10/14

10/17

10/18

10/19

10/20

60

09/23

65

09/22

zone temperature [F]

80

Dates

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

230

115

10/5/2015 10:10 AM

Occupant comments about summer over-cooling (800 Ferry


building, high minimum operation)
Sept. 24 4 PM

Just cold! I have to out on a heater.

Sept. 24 2 PM

I often come into my office and immediately put on a sweater because it is too cold for me. I dont have the sweater
right now which is why I feel cold.

Sept. 24 2 PM

I find that as the day progresses, my floor (the third of three floors) gets colder due to the air conditioner.

Sept. 24 2 PM
Sept. 27 11 AM

I noticed right after lunch, I was extremely cold, but maybe because I had just eaten.
Its cold! Ill turn on my heater...

Sept. 27 3 PM

In the morning the office temp is good, but by 2:30 it starts to cool down when the sun moves away from the window.

Sept. 28 7:30 AM

I dont feel the direct air flow but it is for sure cold in here always.
Now that this survey requires me to focus attention on my work environment several times a day, it is clear to me that
my environment starts out in the morning just right. It gets progressively colder and less comfortable during the course
of the day.

Sept. 28 10 AM
Sept. 28 10:10 AM

Very cold Im moving around the office more and I feel more air movement then I felt just sitting down.

Sept. 28 11:40 AM
Sept. 28 3 PM
Sept. 29 11:30 AM
Sept. 29 12:45 PM
Oct. 3 10 AM
Oct. 3 12:15 PM
Oct. 3 1:30 PM
Oct. 4 8:40 AM
Oct. 4 10 AM
Oct. 4 11:50 AM
Oct. 4 11:54 AM
Oct. 4, 12:10 PM
Oct. 4 3:30 PM

Very cold!
LITTLE MORE AIR CONDITIONED.
Its just cold all the time!
You should send this survey on Monday when its going to be freezing in this building.
Please help my office because it is always cold....
Cold in here.
Cold, Cold, Cold!!!!!
its cold in here. They need to turn on the heat.
cold in here. Turn on some heat.
cold.
cold. Need heat.
warmer on cold days, cooler on hot days.
my arms are cold too, but there wasnt a check for that.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

231

Occupant comments about summer over-cooling (800 Ferry


building, low minimum operation)

Oct. 6 10:30 AM

I have my protable heater on and its still cold in here....

Oct. 6 4 PM

cold

Oct. 6 4 PM

Very cold today!

Oct. 10 1:10 PM

Its freezing!!!

Oct. 12 11:40 AM

It got cool in here!

Oct. 14 2:45 PM

The a/c is blasting in my office right now. I am cold and it is noisy.

Oct. 17 3:12 PM

I have my space heater on and its still cold in my office.

Oct. 17 3:30 PM

My office just went from uncomfortably warm to uncomfortably cool when the air conditioning turned on
in the span of 20 mins.

Oct 18 8:32 AM

I had to turn my heater on!!!!!

Oct 18 9:04 AM

Its cold in here!

Still cold complaints but less than half as many complaints as high min
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

232

116

10/5/2015 10:10 AM

Occupant comments about summer over-cooling (800 Ferry


building, low minimum operation)
Oct .7 3 :00PM

There is less background noise in my office this afternoon. It is great! (noise complaints were often
referred to as HVAC noise)

Oct. 10 11:32 AM

feels good today. They County must have turned on the heat.

Oct. 10 3:30 PM

I definitely notice a difference in the noise level in my office. I hardly hear it all. Thank you if you have had
anything changed!!

Oct. 11 2:30 PM

Office is just right today!

Oct. 12 10:20AM

the temperature and noise control is perfect.

Oct. 12 5:20 PM

I love the air temp. It is warm and not cold (AC on in the winter) like it normally is..

Oct. 13 11:00 AM

Warm in here today. its nice outside so it is nice inside.

Oct. 13 2:26 PM

nice day. wish they were all like this.

Oct. 14 2:44 PM

The temp is perfect!

Oct .19 4:40 PM

Just right!

Oct. 19 4:50 PM

Great!

Oct. 20 12:33 PM

nice day today, which makes it warm in the building.

Oct. 20 2:30 PM

Kinda cool outside now, but the office feels really good. Thank you!

Oct. 20 2:30 PM

Thanks for your involvement. I have definitely noticed an improvement in my office environment.

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

233

Sense of air movement


Have you noticed any air movement in your workspace?
No air movement
A moderate amount

A little
Strong air movement

Moderate and strong votes (% of total votes)


VAV flow rate

Yahoo! warm season


Yahoo! cool season
800 Ferry building

PG&E PACIFIC ENERGY CENTER

< 30%
11
7
9

30% - 40%
11
4
16

OCTOBER 2015

>90%
20
13

234

117

10/5/2015 10:10 AM

Sense of air movement (800 Ferry building)


70

Percentage of People

60
50

No
Little

40

Moderate
Strong

30

obs_No
obs_Little

20

obs_Moderate
obs_Strong

10
0
0

20

40

60

80

100

Flow rate (%)


PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

235

Perceived air quality


"How satisfied are you with the air quality in your workplace right now ? "

HIGH min flowrate

% of Dissatisfied people

25%

LOW min flowrate


263

20%

15%
N=763

10%

1072

1508

1397

512

5%

0%

Yahoo! warm season

PG&E PACIFIC ENERGY CENTER

Yahoo! cool season

OCTOBER 2015

800 Ferry Building

236

118

10/5/2015 10:10 AM

Low Minimum buildings compared to CBE database

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

237

Comparison with CBE database

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

238

119

10/5/2015 10:10 AM

Comparison with CBE database

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

239

Conclusions and acknowledgment


Conclusions
Counter to received wisdom, comfort improves rather than gets
worse with low flow operation
Dumping & draft are not found to be an issue at low flow
Acknowledgment
To ASHRAE for funding RP 1515
To California Energy Commission PIER program, Price
Industries, and CBE for co-funding.
To Yahoo!, Contra Costa County, and UC Merced for allowing
us to study their buildings

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

240

120

10/5/2015 10:10 AM

Laboratory Test
Results

Laboratory Testing Summary


Price Industries laboratory
6 diffuser types
SPD Square plaque
PDF perorated with controller in face
PDN perforated with controller in neck
SDB linear slot with plenum
RCD round cone
520 high sidewall
Measure temperature & air speed, and calculate ADPI
Flowrates: 18%, 26%, 33%, 49%, 80%
Measure air change effectiveness (ACE)
Flowrates 10%, 18%, 26%
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

242

121

10/5/2015 10:10 AM

Terminology
ASHRAE Standard 55 Thermal Environmental Conditions for
Human Occupancy
Air Speed average air speed at three heights over 1-3 minutes
Still air below 40 ft/min
Draft limit below 72.5F the air speed limit is 30 ft/min
Air speed limit above 72.5F & no occupant control, 160 ft/min
Vertical temperature limit 5.4F from head to ankle

ADPI Air Diffusion Performance Index. Measure of mixing.


Well mixed ADPI > 80% ensures ASHRAE 55 vertical air
temperature limit per ASHRAE Fundamentals Ch. 20

Air Change Effectiveness (ACE) Measure of age of air.


Perfectly mixed ACE = 1
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

243

Laboratory tests

8x6 520 Grille Smoke Pattern

Testing Chamber
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

244

122

10/5/2015 10:10 AM

Test setup
Simulated loads
Measure temperature and
air speed at 4 heights
4
24
42
66

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

245

OCTOBER 2015

246

Video

PG&E PACIFIC ENERGY CENTER

123

10/5/2015 10:10 AM

Slot diffuser results

< 30,40 ft/min


> 80% ADPI

< 30,40 ft/min


> 80% ADPI

Similar results for all other ceiling mounted diffusers


PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

247

Sidewall diffuser results

< 30,40 ft/min


> 80% ADPI

< 30,40 ft/min


> 80% ADPI
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

248

124

10/5/2015 10:10 AM

Round Cone Duct Mounted Diffuser Results

< 30,40 ft/min


> 80% ADPI

< 30,40 ft/min


> 80% ADPI
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

249

Temperature & Air Speed distribution


Price PDN perforated face diffuser

Temperature is more even at lower flow


Air speeds decrease at lower flow
Air speeds below 30 fpm draft limit
Similar results for all other ceiling mounted diffusers

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

250

125

10/5/2015 10:10 AM

Air Diffusion Results Summary


Diffusers Flush with Ceiling (PDF, PDN, SDB, SPD)
98-100% ADPI regardless of flow or temperature
Lower air speeds at lower flow
Average air speed below ASHRAE 55 draft limit
Lower air speed at 65F discharge temp compared to
55F
No Ceiling (RCD, 520 grille)
87-100% ADPI at 65F
Lower air speeds at low flow
Average air speed below ASHRAE 55 still air limit
Sidewalls can dump at 55F and low flow

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

251

Cooling Mode Air Change Effectiveness (ACE)


PDN 24X24
55 CFM @55F EAT

CO2 Concentration (PPM)

4500
4000
3500
3000

Supply Air

2500

4" height

2000

24" height

1500

43" height

1000

67" height

500

Exhaust

0
0

5000

10000

15000

20000

25000

Time (s)

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

252

126

10/5/2015 10:10 AM

Cooling Mode Air Change Effectiveness (ACE)


Linear slot

Full mixing down


to 10% flow
Previous
research showed
good ACE down
to 25%

Perforated

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

253

Overall Conclusions and acknowledgment


Conclusions
Counter to the original hypothesis, comfort improves rather
than gets worse
Dumping & draft do not occur at low flow
Ventilation is maintained
Energy savings is significant and similar to simulation
predictions
Significant retrofit opportunity for existing building with DDC
controls. Less than 1 year payback.
Acknowledgment
CEC/PIER, ASHRAE, and CBE for the funding
Yahoo! for allowing to do the study in their buildings
PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

254

127

10/5/2015 10:10 AM

Questions

PG&E PACIFIC ENERGY CENTER

OCTOBER 2015

255

128

Вам также может понравиться