PROFIS Anchor 2.3.

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Gutmann for AMG


Amro A.
-|-

Page:
Project:
Sub-Project I Pos. No.:
Date:

1
Damac Twin Towers
5/4/2014

Specifier's comments:

1. Input data

Anchor type and diameter:


Effective embedment depth:
Material:
Evaluation Service Report::
Issued I Valid:
Proof:
Stand-off installation:
Anchor plate:
Profile
Base material:
Reinforcement:

HSA-R, M16 hnom1


h ef = 65 mm, h nom = 77 mm
A4
ETA 11/0374
7/19/2012 | 7/19/2017
SOFA design method + fib (07/2011) - after ETAG testing
e b = 0 mm (no stand-off); t = 16 mm
lx x l y x t = 200 x 225 x 16 mm (Recommended plate thickness: not calculated)
no profile
uncracked concrete , C40/50, fc = 40.00 N/mm; h = 260 mm
no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
no longitudinal edge reinforcement

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.3.5

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

Gutmann for AMG


Amro A.
-|-

2
Damac Twin Towers
5/4/2014

2. Load case/Resulting anchor forces


Load case (Design loads):
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor

Tension force

Shear force

Shear force x

Shear force y

7.999

7.800

7.800

0.000

7.999

7.800

7.800

0.000

max. concrete compressive strain []: 0.10


max. concrete compressive stress [N/mm]: 2.86
resulting tension force in (x/y)=(-48/0) [kN]: 16.000
resulting compression force in (x/y)=(89/0) [kN]: 10.200

Tension

Compression
x

3. Tension load SOFA (fib (07/2011), section 10.1)


Proof
Steel Strength*
Pullout Strength*
Concrete Breakout Strength**
Splitting failure**
* anchor having the highest loading

Load [kN]

Capacity [kN]

Utilization bN [%]

Status

7.999

62.643

13

OK

N/A

N/A

N/A

N/A

15.997

44.871

36

OK

N/A

N/A

N/A

N/A

**anchor group (anchors in tension)

Steel Strength
NRk,s [kN]

g M,s

NRd,s [kN]

NSd [kN]

87.700

1.400

62.643

7.999

Concrete Breakout Strength


2

Ac,N [mm ]

Ac,N [mm ]

y A,N

c cr,N [mm]

s cr,N [mm]

70200

38025

1.846

98

195

e c1,N [mm]

y ec1,N

e c2,N [mm]

y ec2,N

y s,N

y re,N

k1

1.000

1.000

1.000

1.000

11.000

NRk,c [kN]

g M,c

NRd,c [kN]

NSd [kN]

36.458

1.500

44.871

15.997

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.3.5

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

Gutmann for AMG


Amro A.
-|-

3
Damac Twin Towers
5/4/2014

4. Shear load SOFA (fib (07/2011), section 10.2)


Proof

Utilization bV [%]

Load [kN]

Capacity [kN]

7.800

45.200

17

OK

N/A

N/A

N/A

N/A

Pryout Strength**

15.600

130.127

12

OK

Concrete edge failure in direction

15.600

39.819

39

OK

Steel Strength (without lever arm)*


Steel failure (with lever arm)*

Status

x+**
* anchor having the highest loading

**anchor group (relevant anchors)

Steel Strength (without lever arm)


VRk,s [kN]

g M,s

V Rd,s [kN]

VSd [kN]

56.500

1.250

45.200

7.800

Pryout Strength
0

Ac,N [mm ]

Ac,N [mm ]

y A,N

c cr,N [mm]

s cr,N [mm]

k4

70200

38025

1.846

98

195

2.900

e c1,V [mm]

y ec1,N

e c2,V [mm]

y ec2,N

y s,N

y re,N

1.000

1.000

1.000

1.000

NRk,c [kN]

g M,c,p

VRd,c1 [kN]

VSd [kN]

36.458

1.500

130.127

15.600

Concrete edge failure in direction x+


lf [mm]

d nom [mm]

kv

65

16

2.400

0.066

0.064

c 1 [mm]

Ac,V [mm ]

A c,V [mm ]

y A,V

150

138375

101250

1.367

y s,V

y h,V

y a,V

e c,V [mm]

y ec,V

y re,V

y 90,V

1.000

1.000

1.000

1.000

1.000

VRk,c [kN]

g M,c

V Rd,c [kN]

VSd [kN]

43.703

1.500

39.819

15.600

5. Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
steel
concrete
a

bN

bV

Utilization bN,V [%]

Status

0.128

0.173

2.0

OK

0.357

0.392

1.5

46

OK

bN + bV <= 1

6. Displacements
The displacement of the highest loaded anchor should be calculated according to the relevant approval. The displacement due to hole
tolerances can be neglected, because this method assumes that no hole clearance between anchors and fixture is present. The characteristic
loads of the highest loaded anchor are
NSk

5.920 [kN]

VSk

5.780 [kN]

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.3.5

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Gutmann for AMG


Amro A.
-|-

Page:
Project:
Sub-Project I Pos. No.:
Date:

4
Damac Twin Towers
5/4/2014

7. Warnings
The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient sompressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means.
The compliance with current standards (e.g. EC3) is the responsibility of the user
Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to
elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed
when subjected to the loading!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.3.5

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

Gutmann for AMG


Amro A.
-|-

5
Damac Twin Towers
5/4/2014

8. Installation data
Anchor plate, steel: Anchor type and diameter: HSA-R, M16 hnom1
Profile: no profile
Installation torque: 0.080 kNm
Hole diameter in the fixture: df = 18 mm
Hole diameter in the base material: 16 mm
Plate thickness (input): 16 mm
Hole depth in the base material: 85 mm
Recommended plate thickness: not calculated
Minimum thickness of the base material: 140 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Annular gap must be removed by e.g. filling the holes with mortar of sufficient compressive strength.
8.1. Required accessories
Cleaning
Manual blow-out pump

Drilling
Suitable Rotary Hammer
Properly sized drill bit

Setting
Dynamic set
Installation torque control bar with suitable
screw driver or torque wrench
Hammer

30.0

112.5

30.0

112.5

1
52.0

148.0
100.0

Coordinates Anchor [mm]


Anchor
x
y
1
-48
-83
2
-48
83

c -x
-

c +x
150
150

c -y
-

100.0

c +y
-

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.3.5

www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Gutmann for AMG


Amro A.
-|-

Page:
Project:
Sub-Project I Pos. No.:
Date:

6
Damac Twin Towers
5/4/2014

9. Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard
to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret
norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a
specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not
use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in
each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan