Purpose
This application notes will guide you through step-by-step instruction on how to
configure the Hitachi L300P Series Inverter to communicate with IDEC MicroSmart PLC
using Modbus RTU RS485 protocol.
Parts
1 FC5A MicroSmart Pentra CPU
1 FC4A-PC3 RS485 adapter (All-in-One CPU) or FC4A-HPC3 module (Slim CPU)
1 - Hitachi L300P Series Inverter
1 Hitachi SJ-MB (Modbus/RTU RS485 Interface)
Application Notes
Step 1: Wiring
1. Take off the front covers and connect SJ-MB to L300P series inverter as follows.
Connect
SJ-MB
Application Notes
Step 2: Configure L300P
1. Set the L300P parameter of table 1 by following front panel
pad.
key
Function Code
Name
Description
02
C071
05
C072
Node Allocation
01
C073
08
C070
C074
C075
A001
A002
01
01
02
02
Application Notes
The setting method of C070 is show to follows as example.
Key operation
Indication
Press the
Description
C Group is selected.
or
key
until right indicate is displayed
Press the FUNC key
C----
C0001
First C parameter.
C0070
Press the
1
Key
03
02
Press the
1
Key
C0070
Application Notes
6. Under Master Allocation No. , enter M0000 (Internal relay M0000 will be used to
store the operation command value of the Hitachi L300P series inverter)
7. Enter 1 for Slave Number
8. Under Slave address, enter 000002 which is the operation command coil number in
Modbus addressing
a. Note that in the Hitachi SJ-MB users manual, the Modbus address is
expressed in hexadecimal (example 0002h). Since IDEC WindLDR uses decimal Modbus
addressing, an
conversion between decimal and hexadecimal is needed.
9. Under next Function Code, click and select 16 Preset Multiple Registers
10. Under Master Allocation No. , enter D0000 (Data register D0000 will be used to
store the 1st setting Multispeed frequency value of the Hitachi L300P series inverter)
5
Application Notes
11. Enter 1 for Slave Number
12. Under Slave address, enter 4631 which is the 1st setting Multispeed frequency value
register number in Modbus addressing
13. Click OK button. Note that the Comm.Param.settings automatically changed to
9600-8-Even-1.
14. Click OK button.
15. Click Online, Download to download this setting into MicroSmart Pentra PLC.
16. Hitachi L300P series inverter is running when turn on M0000. And Hitachi L300P
series inverter is stop when turn off M0000.
17. Output frequency is changed according to the value of D0000. When value of D0000
is 1000, the output frequency is 10.00 Hz.