Training Guide
Advanced lighting controls made easy
Version 1.1
Background
Philips Dynalite is a highly specialized company whose principal occupation is to provide cutting
edge solutions for lighting control. Our achievements have been recognized worldwide and
Philips Dynalite is generally the system of choice for projects involving integration with thirdparty vendors equipment and for large-scale applications.
Philips Dynalites philosophy is to provide the best solution possible for each and every project.
This is the key to our success. Our considerable investment in Research & Development ensures
that we remain at the forefront of our industry. Our position as a world leader in lighting
management systems for the future is sustained through our total commitment to innovation.
We are represented around the world by distributors and dealers who are handpicked for their
ability to provide the highest possible level of service.
Topic 1: Infrastructure
Contents
Topic 1: Infrastructure .......................................................................................................................... 9
Overview............................................................................................................................................................................... 9
Learning outcomes ......................................................................................................................................................... 9
Cabling ................................................................................................................................................................................... 9
Networking requirements ............................................................................................................................................ 9
CAT 5 cable limits ........................................................................................................................................................ 10
CAT 5 wiring diagram .................................................................................................................................................. 11
Recommended DyNet color coding for CAT5 cable .......................................................................................... 11
Recommended DyNet CAT 5 data cable types .................................................................................................... 12
Belden wiring diagram .................................................................................................................................................. 12
Recommended DyNet color coding for Belden cable ......................................................................................... 13
S-Flat 6 cable limits ....................................................................................................................................................... 13
Recommended DyNet color coding for S-Flat 6 cable ........................................................................................ 14
Pin out conversion for RJ45 cable testers............................................................................................................... 14
RJ12 socket connections ............................................................................................................................................. 14
Termination ........................................................................................................................................................................ 15
CAT5 Instructions ........................................................................................................................................................ 15
Flat cable instructions .................................................................................................................................................. 22
DyNet voltages .................................................................................................................................................................. 22
Network architecture ...................................................................................................................................................... 23
The DyNet Network ................................................................................................................................................... 23
The Physical Layer ........................................................................................................................................................ 23
Trunk & spur network ..................................................................................................................................................... 24
Implementing trunk & spur topology ....................................................................................................................... 24
Trunk & spur network ................................................................................................................................................. 25
DLight III trunk &spur network ................................................................................................................................. 26
Ethernet networks ............................................................................................................................................................ 27
Multi trunk networks ................................................................................................................................................... 28
Network cable current limits and voltage drop ........................................................................................................ 29
HF Ballast installation ....................................................................................................................................................... 30
Installation instructions ................................................................................................................................................ 30
DyNet 1 & 2 networks .................................................................................................................................................... 31
Operational differences ............................................................................................................................................... 31
Network addressing ......................................................................................................................................................... 31
DALI network wiring ....................................................................................................................................................... 32
Device compatibility ..................................................................................................................................................... 32
Normal DALI ................................................................................................................................................................. 34
DALI Multi Master ........................................................................................................................................................ 34
Enumeration ................................................................................................................................................................... 35
Emergency lighting ............................................................................................................................................................ 35
Self contained luminaries ............................................................................................................................................. 36
Testing emergency lighting.......................................................................................................................................... 38
Essential supply load shedding.................................................................................................................................... 38
Maintaining circuits by bypassing load controllers ................................................................................................ 40
Error! No text of specified style in document.
DMX..................................................................................................................................................................................... 40
End of line resistors ...................................................................................................................................................... 40
Topic 1: Infrastructure
Topic 1: Infrastructure
Topic 1: Infrastructure
Topic 1: Infrastructure
Overview
In this topic we investigate network architecture of Philips Dynalite networks, cabling
requirements and terminations of different cabling types.
Learning outcomes
The approach to programming a Philips Dynalite system can be broadly categorized as follows:
Cabling
Networking requirements
Here are some important points to understand about cabling requirements:
The system communicates over screened, stranded RS485 data cable (such as Cat5) and
requires a minimum of three twisted pairs.
It is recommended that the data cable is connected between devices in a daisy chain
arrangement. Start at the first device then loop in then out of devices, with a single cable
terminating at the last device.
If it is necessary to wire the system in a star configuration the system will still operate
normally but diagnosing installation network faults should this be necessary will be more
difficult.
Topic 1: Infrastructure
Figure 1 Cabling
A 5-way pressure pad terminal strip is provided on devices for each data cable
termination. Some devices also have an RJ12 connector for temporary connection of
portable programming devices.
DR2P/E panels are available with 2x RJ12 connectors instead of a pressure pad terminal
strip for data connection. These panels use Philips Dynalite flat network cable. Using RJ
connectors speeds up the instillation time and helps to eliminate cabling errors. The flat
cable supports up to 10 panels on one cable run and its maximum cable run for a single
cable is limited to 100m before a network bridge is required.
Note: That any data cable that is connected to an energized device is live. Data cable should
not be cut or terminated while live!
10
Topic 1: Infrastructure
Figure 2 CAT5
SIGNAL
Blue Mate
Blue
DataData+
Orange Mate
Orange
Green Mate
Green
Brown Mate
Brown
Topic 1: Infrastructure
11
PART NUMBER
Philips Dynalite
DyNet STP-Cable
Belden
9503
Garland
MCP3S
Garland
STPL5e
Hartland
HCK603
M & M Cable
B2003CS
M & M Cable
B9503CS
Multicables
RS Components
368-687
12
Topic 1: Infrastructure
SIGNAL
Black
Ground
Blue
Data+
White
Data-
Red
+12Volts/+24 Volts
#1502R
#1502P
Topic 1: Infrastructure
13
SIGNAL
Silver
Not connected
White
Ground
Red
Data +
Green
Data -
Yellow
+12 Volts
Brown
Not connected
RJ45
CABLE COLOR
Silver drain
White
Red
Green
Yellow
Orange
14
Topic 1: Infrastructure
Termination
CAT5 Instructions
Follow instructions below for CAT5 cable termination on a Philips Dynalite network.
1. Using side-cutters cut a slit at the end of the cable. Use care to ensure only the out
plastic sheath is cut, avoiding the inner cores and shielding sheath.
Figure 7
2. Locate the draw string between the outer sheath and the foil shield wrapper and using
pliers pull downwards to cut a 90mm slit in the outer sheath shown in figure 8.
Figure 8
Topic 1: Infrastructure
15
Figure 9
3. Using side-cutters carefully trim away the outer plastic sheath, again ensuring not to cut
the inner cores.
Figure 10
16
Topic 1: Infrastructure
4. Locate the shield drain wire and separate from the shields foil sheath. Once separated
carefully trim away the foil shield and plastic wrap.
Figure 11
5. Bend the Brown/Brown-White pairs back towards the outer sheath to be kept as spares.
Figure 12
Topic 1: Infrastructure
17
Figure 13
Figure 14
18
Topic 1: Infrastructure
Figure 15
Figure 16
Topic 1: Infrastructure
19
14. Strip 10mm of sheath from each of the wires and twist together.
Figure 17
15. Fold this back on itself to improve contact with the screw terminal, this should then be
5mm in length.
16. Over the shield wire slide a piece of sheathing. This is to help prevent the shield being
inadvertently shorted.
Figure 18
20
Topic 1: Infrastructure
Shield - Shield
Ground - Green/Green-White
Data + - Blue
Data - - Blue-White
+12V Orange/Orange-White.
Figure 19
17. Ensure the conductors are fully inserted into the terminals with no loose strands
escaping.
Figure 20
21
Figure 21
Figure 22
Figure 23
DyNet voltages
Below are voltage values for proper operation of a DyNet network:
22
Max voltage range for Data+ and Data : -6.5V - +6.5V (Data+ must be greater)
Min voltage difference between Data + and Data-: 500mV recommended, 200mV is
absolute minimum
Topic 1: Infrastructure
Network architecture
The concept of a centralized controller and the complicated task of binding individual slave
devices to the central controller in a DyNet network is completely eliminated. Each individual
device will inherently know what they are and simply listen to and broadcast onto the network.
This means that in most cases, particular devices on the network do not know or care about
other devices. They simply respond to network messages, to which they are inherently sensitive,
and broadcast their own class of messages with no particular destination in mind.
A key principle of the DyNet network is that all of the functions associated with a particular
device are located within that device. For example, all scene preset information is stored within
the actual controllers. This means that if any device should fail, only the functions associated with
that device are lost, other devices on the network are not affected. From a maintenance point of
view, this concept of distributed control (self-contained) units both speeds up fault-finding, and
allows a high level of fault tolerance in large systems.
This Broadcast Network operating principle provides the necessary flexibility to ensure that the
system can be easily (and at low cost) altered or added to after installation. It is possible to add
extra equipment at any time without the need to re-configure or rewire the entire system.
Topic 1: Infrastructure
23
24
Topic 1: Infrastructure
Figure 24
Topic 1: Infrastructure
25
Figure 25
26
Topic 1: Infrastructure
Ethernet networks
It is possible to use an Ethernet network to work as a trunk with DyNet spurs.
The figure below shows an Ethernet trunk connected to DyNet spurs with the DNG100BT
Ethernet interface.
Figure 26
Topic 1: Infrastructure
27
Figure 27
28
Topic 1: Infrastructure
Topic 1: Infrastructure
29
Power Supply
Leading edge
Trailing edge
0-10V
Power only
connection
Touch screen
DyNet network
Data only
connection
Standard
connection
Figure 30
HF Ballast installation
Installation instructions
1. Calculate loads to ensure any channels are not overloaded, then connect loads to the
output channels. The maximum loading of this device is as follows:
2. *DALI broadcast mode: 80 ballasts per channel, do not exceed 500 ballasts in total
3. *1-10V mode: 100mA, 50mA source
4. *DSI Mode: 100 ballasts per channel, do not exceed 1200 ballasts
5. Remember that most 1-10V cabling scenarios are polarity conscious. DALI and DSI cables
are not polarity conscious.
6. Connect a single phase 0.5A feed to the supply terminals. This device must be earthed.
7. Connect data cables to the device as per diagram in instruction manual for the controller.
30
Topic 1: Infrastructure
8. If the Auxiliary input is to be used, connect a dry contact device in between the AUX and
GND terminals. Keep cable runs between the controller and the dry contacts under 2
meters. The function of the Auxiliary input will need to be programmed at the time of
commissioning.
Note: The correct operation of DALI broadcast mode relies on the ballasts being set to
their factory defaults. If problems are encountered, press the service switch 3 times, this will
reset all ballasts connected and energized to their default settings.
Network addressing
A DyNet network has two different addressing modes:
Physical addressing is used primarily during the testing and commissioning stage to configure
DyNet Devices. It is also used for physical, location specific parameters such as circuit breaker
trip signaling. A Device Type, Box Number and Physical channel number are used to identify each
individual lighting circuit.
Logical addressing is used in the day-to-day operation of the lighting system. Lighting circuits
and control panels are configured to Areas; independent of the physical device they are
connected to. An Area Number and Logical channel number are used to identify single or groups
of Physical Channels.
Areas are used to group related lighting points by the area/room they are in. Consider the
example of a load controller that supplies lighting circuits to 2 rooms, with a control panel in
each room. The controllers lighting circuits and the control panel in Room 1 could be configured
as Area 2, and the controllers lighting circuits and the control panel in Room 2 could be
configured as Area 3.
The end result would be that the control panel configured to Area 2 would only control circuits
designated Area 2. The control panel configured to Area 3 would only control circuits designated
Area 3. This allows the two rooms to operate independently of one another.
Topic 1: Infrastructure
31
Logical 1
Logical 2
Logical 1
Office 1
Area 2
Logical 2
Office 2
CP 1
Area 3
CP 2
Figure 31
DALI Ballasts and transformers: 5, 0-10V: 10mA source or 20mA sink DSI Ballasts
and transformers: 15.
Diagnostics include; Lamp failure reporting, Ballast failure reporting, Ballast run time
tracking for each ballast, Device Online/Offline status.
32
3 DALI control outputs, each supporting a full DALI universe of 64 channels (192
total), including backward channel.
3 DALI control outputs, each supporting a full DALI universe of 64 channels (192
total), including backward channel
3 x 20A feed through switched circuits for DALI ballast mains supply.
Topic 1: Infrastructure
Output capacity - DALI mode: 80 DALI ballasts per channel, 500 total, 0-10V mode:
100mA sink, 50mA source per channel, DSI: 100 DSI ballasts per channel, 1200 total.
DDBM100 1 channel ballast module, suitable for controlling DALI (Broadcast mode
only), DSI & 1-10V ballasts and transformers (a relay module must be paired with a
HF ballast module when controlling 1-10V ballasts).
Topic 1: Infrastructure
33
Normal DALI
Figure 32
Figure 33
34
Topic 1: Infrastructure
Enumeration
DALI ballast enumeration can cause some trouble shooting confusion, below is a list of points to
keep in mind when addressing DALI issues:
Hit the service switch 4 times to start the test sequence. (wait for the time out or reset
device)
Check that the number of ballasts does not exceed 64 per universe
Split the universe and then enumerate.- this will narrow down the search area for the
defective ballast.
Check for miss wired ballasts miss wired ballasts will cause a variety of dimming issues
Check ballasts are wired correctly make sure that the long and short wires are
connected correctly, to check remove the lamp and short the 2 wires together, this
should cause the universe to alternate between 0% and 100%.
Figure 34
Emergency lighting
There is a common requirement for emergency lighting to be used alongside general lighting
connected to a control system. There are a few ways of achieving this, the most appropriate
method is dependent on the type of emergency lighting fixture and control equipment used.
Following is a description of several different
techniques and their respective deployment methods. Sometimes it will be necessary to combine
two or more techniques to achieve the desired outcome.
Topic 1: Infrastructure
35
Figure 35
Non-maintained luminaires - This is an exit or emergency luminaire, where the lamps used
for emergency lighting only operate when the normal supply fails. The lamps used in these
luminaires are often incandescent such as the small Spitfire halogen lamp and the larger, sealed
beam flood lamp units.
Non-Maintained Luminaires are connected to the load side of the load controllers circuit
breaker, which supplies power to charge the internal battery and to use as a signal to turn the
lamp on in the event of a power failure. This connection method allows full control of the
normal lighting while providing for emergency lighting in the event of a circuit breaker trip or
power supply failure.
36
Topic 1: Infrastructure
Figure 36
Sustained luminaires - This is an exit or emergency luminaire with two or more lamps where
at least one lamp operates in non-maintained mode and is only illuminated when normal supply
fails. The other lamp operates on the normal supply only. This is identical in functionality to
having a Non-Maintained Luminaire and a Normal Luminaire both in the same housing. charge
the internal battery and to use as a signal to turn the lamp on in the event of a power failure. In
this example the normal half of the Sustained Luminaire is used for Normal Lighting, its ballast is
dimmable so two ballast control lines are shown, common protocols are DALI, DSI and 1-10V.
Sustained Luminaires have two line inputs. One is connected to the Normal lighting output of
the load controller. The Sustained input is connected to the load side of the load controllers
circuit breaker, which supplies power to charge the internal battery and to use as a signal to turn
the lamp on in the event of a power failure. In this example the normal half of the Sustained
Luminaire is used for Normal Lighting, its ballast is dimmable so two ballast control lines are
shown, common protocols are DALI, DSI and 1-10V.
Figure 37
Topic 1: Infrastructure
37
Figure 38
38
Topic 1: Infrastructure
The site should not be occupied while normal power is not available. In this case it is desirable to
place the lighting system into an egress mode.
To change the operating mode, the lighting system must be made aware that the generator is
online. This is typically carried out via a relay that actuates when the generator is online, (or
sometimes via a relay that actuates when the normal supply fails) providing a dry contact signal to
an input unit on the lighting control network, such as a DDMIDC8 Multifunction Input Interface.
1 Phase
40 AMP
Figure 39
In egress mode The DDMIDC8 locks out all control devices such as wall mounted
Control panels, touch screens, motion detectors etc, and selects a global egress preset, which is
pre-defined to illuminate egress paths and reduce lighting in workspaces to assist in alerting
occupants that something is amiss. When normal power is restored the DDMIDC8 restores
normal control functionality.
Load shed mode The DDMIDC8 instructs all load controllers to use a different set of presets
than the normal ones. Consider the example of a room with two channels of lighting and a
control panel that recalls four presets:
During normal operation, presets 1-4 are recalled from the control panel. In load shed mode the
DDMIDC8 uses a part of the DyNet feature set called Preset Offset, which instructs the load
controllers to recall presets 5-8. This function can target a single or group of rooms, or more
commonly, the whole site. If it is desirable that no lighting is on at all in particular rooms in load
shed mode, then all load shed presets are set to 0%. This method has the advantage of minimal
impact on the site, as lighting levels in particular rooms are not disturbed if they are already off or
at low levels.
Topic 1: Infrastructure
39
Figure 40
In this scenario the non-essential supply is used to hold a contactor closed, connecting the lamp
to the load controller. When the non-essential supply fails the load controller will be deenergized as will the contactor, which will connect the lamp to the essential supply.
DMX
End of line resistors
At 9600 Baud the distortion of the original signal is usually within limits and so EOL
resistors are not recommended on a standard DyNet system.
Baud rates greater than 9600 Baud must be terminated using a 120 resistor across D+
and D-.
Usually fitted into network connector strip for 1st and last devices.
For DMX integration network must be daisy chained with end of line resistors.
D+
D--
120R
120R
D+
D-Figure 41
40
Topic 1: Infrastructure
Learning outcomes
By the end of this topic youll be able to detail the installation steps for the following devices:
Mounting panels
Mounting sensors
Hardware controls
Service LED and switch
The Service LED has 3 signaling modes, which are useful for troubleshooting:
On = Fault.
41
The Service Switch, when pressed, causes a sign-on message to be transmitted onto the
network. If the transmission is successful, the Service LED will indicate network activity
detected. The Sign-on message contains information about the device, such as: box number,
device type and embedded software version. This information is captured by DLight
configuration software to speed up commissioning of large systems.
The Service Switch three states are:
AUX input
This is a dry contact interface that is active low. The dry contact is connected between the AUX
and GND terminals on the DyNet connector strip. The function of the AUX input is
programmable. Ensure that the cable length between the dry contact and terminal strip is no
longer than 2 meters.
Top set
This adjusts the maximum output that all other control sources can select, i.e. if the Top Set is
fully clockwise, 100% selected by a control source will give 100% output. If it is fully anticlockwise, 100% selected by a control source will give 50% output. This control is useful for
extending lamp life and can be operated without any form of network control, effectively turning
the device into a stand-alone power conditioner and lamp protector.
Load controllers
Network Bridges.
Wall mounted devices are designed for indoor use only. If installing in an external location, the
device must be housed in a suitable well-ventilated enclosure. Choose a dry location that will be
accessible after the installation is complete.
To ensure the cooling system functions correctly, the load controller should only be mounted
vertically, the right way up.
42
The load controller will generate heat when operating, approximately 2 Watts per Amp of load,
and requires an air gap of 200mm on each side and at the top and bottom of the device.
This air gap is also required to ensure serviceability of the load controller without complete
removal from the mounting surface.
This device may emit some mechanical noise. Take this into account when deciding the mounting
location.
Figure 42
Figure 43
Figure 44
43
44
Operating environments
This device is designed for indoor use only. If installing in an external location, the
DLE1205 must be housed in a suitable well ventilated enclosure. Choose a dry location that will
be accessible after the installation is complete.
In addition the load controller must not be in a location that exceed the following limits for
temperature and humidity:
0 to 40C ambient temperature
0% to 95% RH non condensing.
Load controllers
Time clocks
Power supplies
Network gateways
45
Follow the points below to ensure correct installation of DIN rail mounted devices:
Calculate loads to ensure any channels are not overloaded, then connect loads to the
output channels.
Connect data cables to the device as per diagrams in the previous topic.
If the Auxiliary input is to be used, connect a dry contact device in between the AUX and
GND terminals. Keep cable runs between the device and the dry contacts under two
meters. The function of the Auxiliary input will need to be programmed at the time of
commissioning.
Figure 45
46
Figure 46
Circuit breakers
Required by each device, consult the product data sheet or instruction manual for details.
Multi controllers
When installing Multi Controllers there are some additional considerations to take into account
regarding the controller modules.
Verify that the Output Cards supplied are suitable for your intended loads. Pay attention to any
Output Card specific documentation that may be packed with Output Cards. When dimming
electronic transformers, ensure that the intended transformer is included in Dynalites
Compatible Electronic Transformer List, the latest revision is available at dynalite-online.com
1. Snap the cover off the base unit. Plug each Output Card into the slots provided on the
main circuit board. Replace the base units cover. If using different types of Output Cards,
remember which type is associated with each set of output terminals.
2. Mount the device on a DIN rail inside an approved enclosure.
3. Calculate loads to ensure any channels are not overloaded, then connect loads to the
output terminals. The maximum loading of this device is 16A. A de-rating factor may
need to be applied if installed in a smaller sealed switchboard when using Leading or
Trailing edge dimmers, contact your dealer for details.
47
WARNING : Ballast controller output is referenced to mains neutral and is live. Only mains
rated cables and control ports should be connected.
Ensure that lamp holders are marked with the maximum permissible lamp size that will not
overload a channel. This is to protect the end user from inadvertently overloading a channel by
replacing lamps with higher wattage types.
1. Every time the front cover is removed, ensure that all modules are correctly seated and
locked into sockets before the cover is replaced.
2. Ensure that lamp holders are marked with the maximum permissible lamp size that will
not overload a channel. This is to protect the end user from inadvertently overloading a
channel by replacing lamps with higher wattage types.
3. Connect a single phase 16A feed to the supply terminals, via a 16A circuit breaker or
HRC fuse. This device must be earthed.
4. Connect data cables to the device as per diagrams below.
5. The Auxiliary input is connected via a dry contact device in between the AUX and GND
terminals. Keep cable runs between the device and the dry contacts under two metres.
The function of the Auxiliary input will need to be programmed at the time of
commissioning.
48
Figure 47
49
Wiring terminations
Removable connectors are utilized for all wiring terminations to simplify maintenance, installation
and replacement. Note that controllers are supplied without connectors. Please order
connectors separately as required.
Figure 48
Figure 49
Figure 50
Figure 51
50
Figure 52
Figure 53
Network connections
Serial ports are used to interconnect other dimmers, smart control panels, sensors and AV
controllers.
The DBC905 circuit design incorporates multiple layers of isolation to deliver robust fault
tolerance and uncompromising safety. It should be noted that most structured wiring solutions
for upstream supply circuitry which include both network and power (i.e. 5 pole systems) only
provide functional isolation between the data and mains circuits. Where such wiring systems are
used, the floor network must be considered at mains potential not SELV and all floor network
wiring should include the appropriate provision for prevention of access to live parts.
The main floor network port on the DBC905 is isolated for this reason. The isolation will
tolerate a fault which raises the floor network to mains potential.
Note that this does not include mains potential applied across D+ and D- which would of course
result in destruction of circuit components. Isolation is also separately provided to the local
DyNet ports and switch inputs. This ensures that all switch inputs and local network circuits are
SELV and prevents propagation of faults from these circuits across the floor network.
Where an upstream structured wiring solution is used, care should be made when terminating
network spur wiring at floor bridges (area controllers), to again prevent access to parts and
wiring considered potentially live. In this case only DBC905 controllers should be connected to
the floor network as they incorporate the isolated port. Under no circumstances should a
51
standard user interface be connected directly to the floor network as this may permit user access
to potentially live parts.
All user interfaces such as sensors and panels should be connected to the local network ports on
the DBC905 which provide SELV isolation from mains and the floor network. Where it is
necessary to connect user interfaces to a floor network of this type, a bridge should be always
used to provide effective isolation.
52
Learning outcomes
By the end of this topic youll be able to:
Instructions
Follow the points below to ensure correct installation:
To comply with local electrical standards, some products may be required to be installed
into a metal wall box (not supplied).
Follow the points below when connecting data cables to ensure correct installation:
Use screened, stranded RS485 data cable with three twisted pairs.
Connect data cable to devices in a daisy chain whenever possible. Start at the first
device, then loop in then out of devices, with a single cable terminating at the last device.
Physical constraints may dictate that data cable spurs are necessary. In these cases,
Network Bridges may be needed.
The Data Cable should be segregated from any Mains Cables by a minimum of 300mm. If
the Data Cable has to cross over any Mains Cables, it should do so at a 90 angle.
A data cable that is connected to an energized dimmer is live. Do not cut or terminate
live data cables.
53
Factory presets
Default preset levels are factory preprogrammed into give basic level of functionality.
These can be customized to specifically suit each room or area.
Figure 54
Figure 55
LIGHT LEVEL
P1
100%
P2
70%
P3
40%
P4
0%
P5
80%
P6
60%
P7
50%
P8
20%
54
Back of device
Button switch
Network LED
Light level
sensor
plug
Rim finish
Button guides
Tempreature sensor
Button clip
Network LED
Pin header
Communications module
Terminal connection
DyNet
connection
plug
Pin connectors
Function DIP
switches
Location
socket
Network LED
Labeling space
Network sign
on
plug
Connection header
55
Installation steps
56
Figure 56
Figure 57
DR2P
DR2P panel buttons are changed individually, see figure 47 below:
57
Figure 58
DPN
Buttons for DPN panels can be replaced without the need for any tools or extra wiring. By
pinching the button cap on the sides and pulling gently the cap can be removed. The fascia of the
DPN panel doesnt need to be removed for button maintenance.
Figure 59
Figure 60
In addition to the dingus, the LSP-PRO and FFC-LSP can be used to connect to the DyNet
network via DL2P and DR2P panels.
58
LSP-PRO
Remove the panels fascia to access the connector shown in figure 61 below:
Figure 61
Figure 62
FFC-LSP
A third type of connector can be used to connect to the DyNet network via a DR2P panel
Remove the panels fascia to access the connector shown in figure 48 below:
Figure 63
Figure 64
59
60
Learning outcomes
By the end of this topic youll be able to:
Installation instructions
Follow the points below to ensure correct installation:
WARNING * Do not touch the Pyro Sensor with your fingers. For indoor use only.
Remove the cover from the base unit by turning the cover in an anti clockwise direction.
Screw the base unit to the ceiling, passing the data cable through the cable entry hole.
Use silicon sealant to seal any cable entry and screw holes to prevent air draughts, dust
and insects from entering the enclosure.
Replace the cover onto the base unit by turning the cover in a clockwise direction.
61
Position the sensor so it is between 2.1 and 4.0 meters from the floor. Optimum height
for the sensor is 2.4 meters
Position the sensor so it is at least 1 meter away from electrical lighting such as neon and
fluorescent lights
Position the sensor as to avoid exposing it to direct sunlight and heating/cooling sources
Position the sensor where pedestrian traffic is more likely to walk across the detection
fingers rather than parallel with them (see Lens pattern diagram).
Note: That the coverage area for our sensors differ from model to model (see Motion
Detector Coverage diagram on the following pages).
62
Sensor must be mounted in a dry location on a rigid, vibration free surface. Ideal location
for PIR should have a clear view of all workspaces in coverage area. The ultrasonic
sensors field of view is less directional.
Avoid placing sensor where it may face doorways etc which could cause false triggering.
Sensor should be located at a distance of at least 7ft from horizontal or vertical air ducts.
Adjacent sensors with ultrasonic detector enabled should be installed with a minimum of
60ft spacing between. Sensor should be placed such that the PE cells field of view is
unobstructed, and does not have an artificial light source or natural light directly incident
on it.
For flush mount drill a 2.5 inch hole in ceiling, noting the ceiling void should be at least 2
inches deep. If surface mounting option is used, use provided mud ring mounting adaptor.
For this option removal of the spring clips from the sensors rear housing is required.
Wire the sensor following the recommendations. See data cable permanent connections.
Insert the sensor into the ceiling using spring clips or attach it to the mud ring mounting
adaptor provided, and rotate to secure.
Rotate the sensor in the direction of desired Ultrasonic coverage. If required pull-down
the PIR masking bezel to stop the PIR sensing in unwanted areas (e.g. movement past
doorways).
9m x 6m
At a height of 2.5m
Figure 65
5.6m x 7.4m
5.0 m circular
At a height of 2.5m
At a height of 2.5m
Figure 66
Figure 67
63
Figure 68
Figure 69
64
Figure 70
DUS704W Curtain Creates a solid, thin barrier which is useful for monitoring a
perimeter in an open space.
DUS704W Long Range Useful for monitoring a long thin space such as a corridor.
Contact your local supplier for more details.
Figure 71
Figure 72
65
Figure 73
Figure 74
Figure 75
Figure 76
It is possible to reduce the field of view of the DUS804C and DUS804C-SM from their normal
3600 by use of the in-built rotating pull out shield.
The shield blocks 1200 of the field of view, reducing the motion detection field area to 2400.
The shield can also be rotated to block any 1200 area once the sensor has been installed.
66
By suing the mask installation errors like in figure 55 can be corrected without the need to remount the sensor.
Position the sensor so it sees a combination of artificial light and natural light.
Figure 78
67
Position the sensor so it is within 6 meters of the intended operating position of the
infrared transmitter
Position the sensor so it is not directly exposed to light, especially incandescent and
sunlight, both of which can substantially reduce IR range
Figure 79
68
Position the sensor so it is between 1.1 and 3.1 meters from the floor. Optimum height
for the sensor is 2.1meters.
Slide the circuit board up or down so the marker on the housing matches up with the
installed height on the scale provided on the right hand side of the circuit board.
Position the sensor so it is at least 2 meters away from electrical lighting such as neon
and fluorescent lights.
Position the sensor as to avoid exposing it to direct sunlight and heating / cooling
sources.
Select a location where persons are more likely to walk across the detection fingers
rather than into them (see Figure 63).
Figure 80
69
Learning outcomes
By the end of this topic youll be able to:
70
Figure 81
Figure 82
If using a wall box, separate the wall box from the Touch Screen and make sure no dust
or debris enters the Touch Screen during installation.
The wall box can then be fixed in place using an appropriate method.
71
Programming port
Type B USB socket
Keyboard/Mouse port
Type B USB socket
DyNet port
Ethernet RJ45
network socket
Figure 83
72
Power supply
The DTP100 Touchscreen Panel is powered from the DyNet network and does not require
mains voltage supply.
73
DDNG485 gateway
Learning outcomes
By the end of this topic youll be able to
Install a DDMIDC8
74
Powerful Internal PLC - Custom scripts can be written to provide process control based on
conditional logic.
Simple Installation - DIN Rail mount facilitates installation. Fixing points are provided for
installation without the use of DIN rail.
Figure 85
Installation notes
Read Instructions We recommend that you read this Instruction Manual prior to
commencement of installation.
Special Programming This device will only operate in basic modes unless programmed via a
computer. If programming is required, contact your local agent for details. Once the data cable is
connected to the devices, the factory default settings will allow any control panel or input to operate
all channels in all controllers.
Mounting Location Install in a dry, well-ventilated location. Controllers may emit some
mechanical noise. Take this into account when deciding the mounting location.
Data Cable Use screened, stranded RS485 data cable with three twisted pairs. Segregate from
mains cables by 300mm minimum. Connect devices in a daisy chain. A data cable that is connected
to an energized device is live. Do not cut or terminate live data cables.
D-
+5V
0V
AN4
0V
0-5V/0-10V
Analogue
Inputs
AN3
0V
A/D
+15V
D+
DyNet
RS485
GND
SHIELD
A/D
A/D
AN2
0V
AN1
A/D
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
Opto Isolated
Dry Contact/0-24V
AC/DC
Digital Inputs
Electrical diagram
Figure 86
75
Analogue fader
AN1
Dynalite 0V
DDMIDC8
AN2
Input
Interface 0V
AN3
0-5V / 0-10V
Analogue 0V
Inputs
AN4
0V
+5V
Figure 87
Installation steps
1. Mount the device on a DIN rail inside an approved enclosure. The device can also be
installed without the use of DIN rail by removing the cover to access two mounting
screw holes.
2. Connect RS485 data cable to the serial port as per the connection diagram overleaf.
3. If used, connect volt free contacts or 0-24V AC/DC inputs to any of the 8 opto-isolated
inputs. Remove the lid and ensure that the jumpers for each input are set to the
appropriate 0-24V or volt free setting, depending on the input type.
4. If any opto-isolated inputs are of the Dry Contact type, ensure that the power supply
jumper is fitted in the volt free position. Note that this will increase the current
consumption of the device from 15mA to 40mA, which may require consideration of
voltage drop on long runs of DyNet data cable.
5. If used, connect 0-5V or 0-10V inputs to the analogue ports. Ensure the input voltage is
DC and a maximum of 10 Volts. Note that bare faders can also be connected to the
analogue inputs by using the adjacent +5V terminal as a supply. Suggested fader value is
10K ohm. Do not attempt to draw more than 25mA from the +5V terminal.
Installing DDNG485
76
1. Mount the device on a DIN rail inside an appropriate enclosure. Alternatively there are 2
holes provided to fix the device to a surface without the use of DIN rail. Remove the
front cover to access these holes.
2. Connect data cables to the device as per diagrams. Note that the device is powered from
the DyNet network segment that is connected to Port 1. When implementing Repeaters,
connect the link to Port 2 of both Gateways. Shielded cable must be used for long runs.
When implementing Trunk / Spur topology, connect the Trunk to Port 2 and the Spur to
Port 1. Note that up to 150mA of power from the DyNet network on Port 1 is fed to
Port 2, so providing there is surplus power available on the Spurs it is normally not
necessary to provide a network power supply for the Trunk.
3. If using the device as a DMX receiver, ensure DMX termination rules are obeyed, use a
120 Ohm terminating resistor across D+ and D- at the end of line. Note that Port 2
should be used for DMX Reception.
Figure 88
Figure 89
DPMI940
Topic 6: Installing integration devices
77
Figure 90
Installation steps
1. Mount the device on a DIN rail inside an approved enclosure. The device can also be
installed without the use of DIN rail by removing the cover to access two mounting
screw holes.
2. Connect RS485 data cable to the serial port as per the connection diagram overleaf.
3. If used, connect volt free contacts or 0-24V AC/DC inputs to any of the 8 opto -isolated
inputs. Remove the lid and ensure that the jumpers for each input are set to the
appropriate 0-24V or volt free setting, depending on the input type.
4. If any opto-isolated inputs are of the Dry Contact type, ensure that the power supply
jumper is fitted in the volt free position. Note that this will increase the current
consumption of the device from 37mA to 68mA, which may require consideration of
voltage drop on long runs of DyNet data cable.
5. If used, connect 0-5V or 0-10V inputs to the analogue ports. Ensure the input voltage is
DC and a maximum of 10 Volts. Note that bare faders can also be connected to the
analogue inputs by using the adjacent +5V terminal as a supply. Suggested fader value is
10K ohm. Do not attempt to draw more than 25mA from the +5V terminal.
78
Electrical diagram
Figure 92
19 mm
Mounting details
Ribbon Cable
19 mm
40 mm
side view
top view
Figure 93
79
Connect Ground and +12V leads to the motion detectors 0V & +12V terminals.
Connect Ground and Switch 1 leads to the motion detectors Alarm terminals.
Connect Ground and Switch 4 leads to the motion detectors Tamper terminals.
PIN
FUNCTION
COLOR
+12 Volts
Ground
Gray
Ground
Gray
Switch 1
Gray
Switch 2
Gray
Switch 3
Gray
Switch 4
Gray
To trigger a preset place a short between SW 1, 2, 3 or 4 to the Ground. The +12V terminal is
provided to power 3rd party devices such as motion detectors, ensure that it does not touch any
other terminal of the device.
Figure 94
80
Figure 95
81
Learning outcomes
By the end of this topic youll be able to:
LED tracking
To check the LED tracking on panels simply hit the buttons on a panel and the indicator LED
should illuminate on the button you pressed.
Check that other panels buttons also change accordingly to track the button pushes throughout
the network.
Luminaires
Hit buttons 1 and 4 on a panel to confirm that the luminaires are responding to Area Preset
messages for 100% and 0%.
Sensors
Check that sensors are working correctly by sending an Area 1 message on the network by
hitting button 1 on any panel in the network.
82
Touch screens
Use the sliders on the page to control channels to confirm that it is communicating on
the network
Troubleshooting
Network Fault finding
Once your network is complete, as described earlier. All devices should react to a single push
button message. If this is not the case the simplest way to diagnosis the problem is to:
Break the network into two halves. As you have kept a record of how the network was
installed, to find the mid way point should be simple.
Try pushing a button again in each half of the network, this will identify which half has the
problem.
Continue to break this half into quarters and repeat the push button press.
Overview
Select the panel in Physical view and press the R key on your PC keyboard. A red reset
message should appear in the monitor window if the device is online
Check that the LEDs are working on the front of the panel and are following the button
presses. No LEDs would indicate a possible panel failure or power loss
Remove the panel and check the data cable connection for broken wiring. Repair as
necessary.
83
Use a voltmeter to check the feed voltage. There should be at least 10v DC between the
12v and gnd terminals. If not, an additional network power supply may be required to
boost the voltage up to a stable level
Factory default the panel in EnvisionProject and reconfigure the device to ensure it is
configured correctly.
Common problems
Check the following list. If you are still unable to rectify the situation, contact Dynalite. Please
ensure that you have completed the following prior to calling our technical support department.
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system.
SYMPTOM
PROBABLE CAUSE
SOLUTION
84
DDMIDC8 Troubleshooting
SYMPTOM
PROBABLE CAUSE
SOLUTION
Overview
In the event of transformer failure, only the single lamp is extinguished. The transformer
is also readily accessible as it will be near the extinguished lamp.
If larger capacity transformers are used to control multiple lamps, any variances in cable
length will be manifested in different luminous outputs; the longer the cable, the less light
will be observed coming from the source.
85
Some transformers can be noisy when dimmed. This is often the case for larger
transformers (especially 'E' and 'I' types), some electronic transformers and toroidal
transformers that are potted in a fixture.
Large transformers are prone to nuisance tripping with MCB's at switch on, although the
soft start features of Dynalite controllers will minimise this risk. The problem is due to
the highly inductive nature of the transformer coupled with the high inrush current of the
lamps. Sometimes large transformers cannot be avoided for stretched-wire or parallel
rod distribution systems. These transformers are usually a component part of the system
and should have an integral provision for fast protection against overload or short circuit
of the conductors.
Large wire-wound transformers have high energy losses and poor output voltage
regulation.
Some transformers are not suitable for dimming. Please refer to the Dynalite
Transformer Compatibility Guide for further information.
For effective phase control dimming, minimum loads may apply, depending on the
transformer type or load characteristic of the connected lighting fixtures. Lighting
circuits comprising a single low voltage fitting of 20W or less may exhibit some instability
for this reason. Please refer to controller data sheets or consult a Dynalite
representative for advice on minimum loads.
Four-wire transformers (DALI, DSI, 1-10V) require a pair of cables for the control signal, in
addition to the mains feed. Local supply regulations must be observed when wiring mains and
control cables, as the control terminals on the transformers or controllers are not rated as SELV.
Mains voltage must never be applied to the control signal terminals or cables.
86
Overview