Control Units
2015

The art of handling air

TOC

Control Units
2015

The Control Units catalogue corresponds to sections 5.1,


5.2 and 5.4 of the previously used KLIMA 2 catalogue.
The TROX catalogues have been completely revised
and now oer several new features:

Hardcover editions
Simplified navigation
List of advantages of each product at a glance
Dierent chapters for principal products,
additional components and attachments

The following documentation is available to help you select


and size TROX components and systems:

Technical product documentation (catalogues)


Design manuals
Easy Product Finder design programme
Compendium CD
Website www.troxtechnik.com

This catalogue is a carbon neutral product.

The art of handling air


TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Phone +49(0)28 45 202-0


Fax
+49(0)28 45 202-265
E-Mail trox@trox.de
www.troxtechnik.com

TOC

Catalogue structure

Diusers

Air-Water Systems/Decentralised Ventilation

Multileaf Dampers Attenuators/


External Weather Louvres

Fire and Smoke Protection Systems

Control Units

The Control Units catalogue corresponds to sections 5.1, 5.2 and 5.4 of
the previously used KLIMA 2 catalogue.

Control Systems

Filter Units/Filter Elements

X-CUBE Air Handling Units

05/2015 DE/en

K5 0.0 5

TOC

Documentation Page numbering


Technical product documentation
comprise:
Product descriptions
Information on the materials used
Aerodynamic and acoustic data
Dimensions
Details on product characteristics
Specification texts
Technical document, or leaflet

Design manuals
comprise:
Basic information and technical concepts
Step-by-step product design
Overview and explanation on how to select the ideal system
components

Design manual

Easy Product Finder design programme


comprises everything to select and size our products:
Technical data
Diagrams, photos
Order codes that can be edited
CAD drawings(3D model; export function for DXF and other
standard formats)
Specification texts for each product and variant
Design programme

Website www.troxtechnik.com

The entire documentation is available on the internet.


Catalogue download center
Individual product leaflets
Installation examples
References

Internet

Page numbering
K5 0.0 6

05/2015 DE/en
Continuing page numbers
Chapter
Product segment

K5 0.0 6

Edition
Country
Language

05/2015 DE/en

Control units

TOC

Table of contents
1 Variable volume flow control VARYCONTROL
1.1 VAV terminal units
1.2 Secondary silencers for VAV terminal units
1.3 Control components for VAV terminal units
1.4 Adjustment devices for VAV terminal units
1.5 Basic information and nomenclature

2 Constant volume flow control CONSTANTFLOW


2.1 CAV controllers
2.2 Actuators for CAV controllers
2.3 Basic information and nomenclature

3 Shut-o and flow adjustment


3.1 Shut-o dampers
3.2 Flow adjustment dampers
3.3 Actuators for shut-o dampers
3.4 Basic information and nomenclature

4 Volume flow rate measurement


4.1 Volume flow rate measuring units
4.2 Dierential pressure transducers for volume flow rate measuring units
4.3 Basic information and nomenclature

5 Heat transfer
5.1 Heat exchangers and air heaters
5.2 Basic information and nomenclature

Additional information
Z 1 Product index
Z 2 Disclaimer
Z 3 TROX contact information

05/2015 DE/en

K5 0.0 7

Variable volume flow control VARYCONTROL

TOC

Table of contents
1

Variable volume flow control VARYCONTROL


VARYCONTROL VAV terminal units are air terminal units for supply air and extract air
systems. They work with an external power supply and can be used for controlling,
flow adjustment, or shutting off the airflow in room air conditioning systems.
Depending on their construction the units can meet the most demanding acoustic
requirements; different materials and surface finishes are also available.

1.1 VAV terminal units

Type

Page

For low airflow velocities and low duct


pressures

LVC

1.1 1

For the most diverse applications


regarding standard volume flow rate
ranges

TVR

1.1 11

For normal and high volume flow rate


ranges

TVJ

1.1 32

For normal and high volume flow rate


ranges and low-leakage shut-off

TVT

1.1 56

For supply air systems with demanding


acoustic requirements and low airflow
velocities

TZ-Silenzio

1.1 79

For extract air systems with demanding


acoustic requirements and low airflow
velocities

TA-Silenzio

1.1 96

For supply air systems with demanding


acoustic requirements

TVZ

1.1 113

For extract air systems with demanding


acoustic requirements

TVA

1.1 131

For dual duct systems

TVM

1.1 149

Circular

Rectangular

Acoustically optimised

K5 0.0 8

05/2015 DE/en

Header volume flow control VARYCONTROL


Variable

TOC

Subheader
Table
of contents

1.1 VAV terminal units

Type

Page

For contaminated air

TVRK

1.1 164

Optimised for use in laboratories and on


fume cupboards

TVLK

1.1 184

For the control of variable air volume


flows in potentially explosive
atmospheres (ATEX)

TVR-Ex

1.1 202

For the reduction of noise in circular


ducts, suitable for all circular VAV
terminal units and CAV controllers,
galvanised sheet steel construction

CA

1.2 1

For the reduction of noise in circular


ducts, suitable for all circular VAV
terminal units and CAV controllers,
aluminium construction

CS

1.2 8

For the reduction of noise in circular


ducts, suitable for all circular VAV
terminal units and CAV controllers,
flexible aluminium construction

CF

1.2 15

For the reduction of air-regenerated


noise of air terminal units Type TVZ, TVA, TS
TZ-Silenzio, TA-Silenzio or TVM

1.2 22

For the reduction of air-regenerated


noise of air terminal units Type TVJ, TVT
or EN

1.2 25

Optimum resistance

For use in potentially


explosive atmospheres

1.2 Secondary silencers for VAV terminal units


Circular

Rectangular

Optimum resistance

05/2015 DE/en

TX

For the reduction of noise in plastic


circular ducts, suitable for all circular VAV
CAK
terminal units and CAV controllers,
plastic construction for contaminated air

1.2 30

K5 0.0 9

Variable
Header volume flow control VARYCONTROL

TOC

Subheader
Table
of contents

1.3 Control components for VAV terminal units

Quick and easy handling

Type

Page

Easy

1.3 1

With service interface and bus communiCompact


cation facility

1.3 9

For different actuators

Universal,
dynamic

1.3 30

For contaminated extract air or for


pressure control

Universal,
static

1.3 43

Rapid replacement without interruption


of system operation

RETROFIT

1.3 80

For the individual temperature control in


rooms

RC

1.3 89

Adjustment
devices

1.4 1

1.4 Adjustment devices for VAV terminal units

For service and commissioning

1.5 Basic information and nomenclature


Variable volume flow control VARYCONTROL

K5 0.0 10

1.5 1

05/2015 DE/en

LVC

TOC

1.1

X X LVC testregistrierung

VAV terminal units

Type LVC
Compact controller

Easy controller

For low airflow velocities and low duct pressures


Nozzle for differential
pressure measurement

Circular VAV terminal units for supply air and extract air systems
with variable volume flows, low airflow velocities and low duct pressures
New measurement principle, optimised for airflow velocities from 0.6 to 6 m/s
High control accuracy even in case of unfavourable upstream conditions
Electronic control components for different applications (Easy, Compact)
Easy handling due to innovative control technique
Casing length of only 310 mm for all nominal sizes
Any installation orientation

Closed blade air leakage to EN 1751, up to class 2


Casing air leakage to EN 1751, class C

For all upstream conditions

H GE

TE

ET

HY

ISC

ST

EN

VD

Optional equipment and accessories


Secondary silencer Type CA, CS or CF
for the reduction of air-regenerated noise
Hot water heat exchanger Type WL and electric air heater Type EL
for reheating the airflow

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 1

VAV terminal units

TOC

General information

LVC

Type

Page

LVC

The Easy principle

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight
Installation details
Specification text

1.1 2
1.1 5
1.1 6
1.1 7
1.1 8
1.1 9
1.1 10

Basic information and nomenclature

1.5 1

Select nominal size

Set flow rates

Green light: Ready!

K5 1.1 2

05/2015 DE/en

VAV terminal units

TOC

General information
Description

VAV terminal unit


Type LVC
For detailed information
on control components
see Chapter K5 1.3.

Application
Circular VAV terminal units of Type LVC
for the precise supply air or extract air flow
control in variable air volume systems
with low airflow velocities
Closed-loop volume flow control
using an external power supply
For low airflow velocities
and low duct pressures
Effective pressure (differential pressure)
as the result of two measurements,
one upstream and one downstream
of the damper blade
The relation between damper blade position
and differential pressure is stored
as a characteristic relationship in the controller
Shut-off by means of switching
(equipment supplied by others)
Nominal sizes
125, 160, 200, 250
Attachments
Easy controller: Compact unit consisting
of controller with potentiometers,
differential pressure transducer and actuator
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Useful additions
Secondary silencer Type CA, CS or CF
for demanding acoustic requirements
Special features
Optimised for low airflow velocities
from 0.6 to 6 m/s
High control accuracy even in case
of unfavourable upstream conditions
Any installation orientation
Volume flow rate control
with Easy or Compact controller
Casing length of only 310 mm
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components.
Plastic nozzle with integral damper blade
to measure the volume flow rate
Easy controller with potentiometers,
indicator light, terminals, damper blade
position indicator, and protective cover
Wire clamping bracket
Double lip seal
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy even in case
of unfavourable upstream conditions

05/2015 DE/en

LVC
Construction features
Circular casing
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180
Position of the damper blade indicated
externally at shaft extension
Easy controller
Screw terminals for the electrical connection
Double terminals for looping the supply
voltage, i.e. for the simple connection
of voltage transmission
Wire clamping bracket fixed to the casing
Compact controller
Cable for the electrical connection
Materials and surfaces
Casing made of galvanised sheet steel
Nozzle, damper blade, and plain bearings
made of ABS plastic, UL 94,
flame retardant (V-0)
Damper blade seal made of TPV (plastic)
Installation and commissioning
Any installation orientation
Selection based on nominal size determination
Damper blade is factory set to open position
which allows ventilation airflow
even without control
Can be installed at a junction
Standards and guidelines
Hygiene conforms to VDI 6022
Closed blade air leakage to EN 1751,
class 2 (nominal sizes 160 250, class 1)
Nominal size 125 meets the general
requirements of DIN 1946, part 4,
with regard to the acceptable
closed blade air leakage
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear

K5 1.1 3

VAV terminal units

TOC

General information

LVC

Attachments: VARYCONTROL control components for Type LVC


Order code detail

Control function

Controller

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo

Dynamic, integral

Integral

Easy controller
Easy
Compact controller
BC0

Technical data

Nominal sizes
Volume flow rate range
Volume flow rate control range
Minimum differential pressure
Maximum differential pressure
Operating temperature

Function

Functional description
A new measurement principle makes it possible
to measure low volume flow rates. The pressure
is measured by means of a nozzle with tappings
before (upstream) and after (downstream)
the damper blade. The Easy controller
or the Compact controller of the LVC
determines the resulting differential pressure
(effective pressure) and compares
it to the stored characteristic.
This measurement principle is characterised
by small measuring tolerances,
and the upstream conditions do not have to meet
any special requirements.

Differential pressure transducer Actuator

125 250 mm
8 300 l/s or 30 1080 m/h
Approx. 10 to 100 % of the nominal volume flow rate
5 30 Pa
600 Pa
10 50 C

Schematic illustration of the LVC

Plastic nozzle
Damper blade
Lip seal

K5 1.1 4

Easy controller
Volume flow rate scale
Wire clamping bracket

05/2015 DE/en

VAV terminal units

TOC

Order code

Order code

LVC

LVC

VARYCONTROL

LVC / 160 / BC0 / E 0 / 80 400

LVC / 160 / Easy

Type
LVC VAV terminal unit
Nominal size [mm]
125
160
200
250
Attachments (control component)
Easy Easy controller
BC0 Compact controller

Order examples

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m3/h or l/s]
min max for factory setting

LVC/160/Easy
Nominal size
Attachment

160 mm
Easy controller

LVC/250/BC0/E2/200800 m/h
Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rates

K5 1.1 5

250 mm
Compact controller
Single
2 10 V DC
200 800 m/h

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured
for all operating
conditions and
for all control units.
The measurement points
for fan speed control must
be selected accordingly.

LVC

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

Nominal size

m/h
8
30
55
75
12
50
85
120
20
75
135
190
30
120
210
300

29
108
198
270
43
180
306
432
72
270
486
684
108
432
756
1080

Pa

5
5
16
30
5
5
15
30
5
5
15
30
5
5
15
30

5
5
17
32
5
5
16
32
5
5
16
31
5
5
15
31

pst min

%
5
5
18
34
5
6
16
33
5
5
16
32
5
5
15
32

5
6
19
35
5
6
17
34
5
5
16
33
5
5
16
32

15
12
8
5
15
12
8
5
15
12
8
5
15
12
8
5

LVC
LVC with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
LVC with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
LVC with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 6

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

LVC

Quick sizing: Sound pressure level at differential pressure 50 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values
and spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

K5 1.1 7

Nominal size
l/s
125

160

200

250

8
30
55
75
12
50
85
120
20
75
135
190
30
120
210
300

m/h
29
108
198
270
43
180
306
432
72
270
486
684
108
432
756
1080

LPA1

LPA
27
35
39
42
29
34
36
38
31
35
36
36
31
36
36
36

<15
24
30
34
19
26
28
31
21
26
28
28
24
28
28
29

Case-radiated noise

LPA2

dB(A)

<15
17
24
28
<15
23
23
26
<15
19
22
23
18
22
22
23

<15
<15
21
25
<15
19
20
23
<15
17
20
21
16
19
20
21

<15
17
21
23
<15
19
22
24
<15
19
22
24
17
25
28
31

LVC
LVC with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
LVC with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
LVC with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight


Dimensions

LVC

LVC

20

310

~80

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250

05/2015 DE/en

mm

kg
124
159
199
249

1.5
1.9
2.1
2.7

K5 1.1 8

VAV terminal units

TOC

Installation details

Space requirement
for commissioning
and maintenance

Junction

D
D

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply with
EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

LVC

p
p

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed in a branch just off the main duct.

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Space required
Attachments

VARYCONTROL
Easy controller
370
Compact controller
370

K5 1.1 9

mm
200
200

300
200

05/2015 DE/en

VAV terminal units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular VAV terminal units for variable air


volume systems with low airflow velocities,
suitable for supply or extract air,
available in four nominal sizes.
Measurement and control of low volume
flow rates based on a new measurement principle.
Plastic nozzle with damper blade for measuring
the differential pressure upstream
and downstream of the damper blade
(effective pressure). The relation between damper
blade position and differential pressure is stored
as a characteristic relationship in the Easy
or Compact controller. This results in high
control accuracy even in case of unfavourable
upstream conditions.
Selection based on nominal size determination.
Ready-to-commission unit which consists
of the mechanical parts and the electronic
control components. Units are equipped
with a plastic nozzle with integral damper blade.
The averaging differential pressure sensor
is resistant to dust and pollution.
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180.
Position of the damper blade indicated externally
at shaft extension. Damper blade is factory set
to open position which allows ventilation airflow
even without control.
Closed blade air leakage to EN 1751,
at least class 1.
Casing air leakage to EN 1751, class C.
Special features
Optimised for low airflow velocities
from 0.6 to 6 m/s
High control accuracy even in case
of unfavourable upstream conditions
Any installation orientation
Volume flow rate control
with Easy or Compact controller
Casing length of only 310 mm

LVC
Technical data
Nominal sizes: 125 to 250 mm
Volume flow rate range:
8 to 300 l/s or 30 to 1080 m/h
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 30 Pa
Maximum differential pressure: 600 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Clearly visible external indicator light
for signalling the functions:
Set, not set, and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Materials and surfaces


Casing made of galvanised sheet steel
Nozzle, damper blade, and plain bearings
made of ABS plastic, UL 94,
flame retardant (V-0)
Damper blade seal made of TPV (plastic)

Order options
VARYCONTROL

Type
LVC
VAV terminal unit
Nominal size [mm]
125
160
200
250
Attachments (control component)
Easy Easy controller
BC0 Compact controller

05/2015 DE/en

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m3/h or l/s]
min max for factory setting

K5 1.1 10

TVR

TOC

1.1

X X TVRtestregistrierung

VAV terminal units

Type TVR

Universal controller

For the most diverse applications regarding


standard volume flow rate ranges
Circular VAV terminal units for standard applications regarding the supply air
or extract air control in variable air volume systems
Suitable for the control of volume flow rate, room pressure or duct pressure

Compact controller

Electronic control components for different applications


(Easy, Compact, Universal, and LABCONTROL)
High control accuracy even with upstream bend (R = 1D)
Suitable for airflow velocities up to 13 m/s
Closed blade air leakage to EN 1751, up to class 4
Casing air leakage to EN 1751, class C
Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise

Easy controller

Secondary silencer Type CA, CS or CF for the reduction


of air-regenerated noise
Hot water heat exchanger Type WL and electric air heater Type EL
for reheating the airflow
ET

HY

SCH GET
E

ST

I
EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 11

VAV terminal units

TOC

General information

TVR

Type

TVR

Variants

Page
General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVR
Dimensions and weight TVR-D
Dimensions and weight TVR-FL
Dimensions and weight TVR-D-FL
Installation details
Specification text

1.1 12
1.1 16
1.1 20
1.1 21
1.1 22
1.1 23
1.1 24
1.1 25
1.1 26
1.1 27

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVR

VAV terminal unit, variant TVR-D

Application
Circular VARYCONTROL VAV terminal units
of Type TVR for the precise supply air or extract
air flow control in variable air volume systems
Closed-loop volume flow control
using an external power supply
For controlling, restricting, or shutting off
the airflow in air conditioning systems
Shut-off by means of switching
(equipment supplied by others)

Attachments
Easy controller: Compact unit consisting
of controller with potentiometers,
differential pressure transducer and actuator
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller:
Controller, differential pressure transducer
and actuators for special applications
LABCONTROL: Control components
for air management systems

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
TVR: VAV terminal unit
TVR-D: VAV terminal unit
with acoustic cladding
TVR-FL: VAV terminal unit
with flanges on both ends
TVR-D-FL: VAV terminal unit
with acoustic cladding
and flanges on both ends
Units with acoustic cladding
and/or a secondary silencer Type CA,
CS or CF for demanding acoustic requirements
Acoustic cladding cannot be retrofitted
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Nominal sizes
100, 125, 160, 200, 250, 315, 400

K5 1.1 12

Accessories
G2: Matching flanges for both ends
D2: Lip seals on both ends (factory fitted)
Useful additions
Secondary silencer Type CA,
CS or CF for demanding acoustic requirements
Heat exchanger Type WL
Electric air heater Type EL
Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary

05/2015 DE/en

VAV terminal units

TOC

General information
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blade
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy
(even with upstream bend R = 1D)
Construction features
Circular casing
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
Position of the damper blade indicated
externally at shaft extension
TVR-FL: Flanges to EN 12220
Materials and surfaces
Galvanised sheet steel construction
Casing and damper blade
made of galvanised sheet steel
Damper blade seal made of TPE plastic
Aluminium sensor tubes
Plastic bearings

TVR
Installation and commissioning
Any installation orientation
(except units
with static differential pressure transducer)
TVR-D: For constructions
with acoustic cladding, ducts on the room
side should have cladding up to the acoustic
cladding of the controller
Standards and guidelines
Hygiene conforms to VDI 6022
Closed blade air leakage to EN 1751, class 4
(nominal size 100, class 2;
nominal sizes 125 and 160, class 3)
Nominal sizes 100, 125, and 160 meet
the general requirements, nominal sizes
200 400 meet the increased requirements
of DIN 1946, part 4, with regard
to the acceptable closed blade air leakage
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Powder-coated construction (P1)


Casing made of galvanised sheet steel,
powder-coated
Damper blade and shaft
made of stainless steel 1.4301
Sensor tubes made of aluminium,
powder-coated
Stainless steel construction (A2)
Casing, damper blade
and shaft made of stainless steel 1.4301
Sensor tubes made of aluminium,
powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

05/2015 DE/en

K5 1.1 13

VAV terminal units

TOC

General information

TVR

Attachments: VARYCONTROL control components for Type TVR


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B13
B1B
XC3

Volume flow rate

Actuator
Spring return actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BRG
BS3
BSB
BSG
BG3
BGB
BH3
BHB
XE1
XE3
XF1
XF3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Static

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Static, integral
Static, integral 100 Pa

Universal controller with MP bus interface


TROX/Belimo
Static, integral 600 Pa
Differential pressure

Static, integral 100 Pa

Differential pressure controller


TROX/Belimo

Static, integral 600 Pa


Static, integral 100 Pa

Differential pressure controller


TROX/Gruner

Static, integral 600 Pa

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TVR


Order code detail
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Technical data

K5 1.1 14

Control function

Controller

Differential pressure transducer

Actuator

Room supply air


Room extract air
Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room supply air


Room extract air
Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Static, integral

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

Fast-running actuator
Fast-running actuator
(brushless motor)

100 400 mm
10 1680 l/s or 36 6048 m/h
Approx. 10 to 100 % of the nominal volume flow rate
5 90 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information

Function

TVR

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring
the volume flow rate.
The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator; the control functions
can be achieved with an Easy controller,
with a Compact controller, or with individual
components (Universal or LABCONTROL).
For most applications, the setpoint value
comes from a room temperature controller.
The controller compares the actual value
with the setpoint value and alters the control
signal of the actuator if there is a difference
between the two values.
Schematic illustration of the TVR

Differential pressure sensor


Damper blade

K5 1.1 15

Lip seal
Control components, e.g. an Easy controller

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
VARYCONTROL

TVR

TVR, TVR/.../Easy

TVR D ... FL / 160 / G2 / B1B / E 0 / 200 900 / NO

TVR D / 200 / D2 / Easy

Type
TVR VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
A2
Stainless steel
Flange
No entry: none
FL
Both ends (not for TVR-D-P1)
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends

Order example

TVR/200/D2/BC0/E0/5001200 m/h

VARYCONTROL

Acoustic cladding
Material
Flange
Nominal size
Accessories
Attachment
Operating mode
Signal voltage range
Volume flow rate

05/2015 DE/en

Attachments (control component)


Example
Easy Compact controller
BC0 Compact controller
B13 Universal controller
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)
Damper blade position
Only with spring return actuators
NO
Power off to open
NC
Power off to close

Without
Galvanised sheet steel
Without
200 mm
Lip seals on both ends
Compact controller
Single
0 10 V DC
500 1200 m/h

K5 1.1 16

VAV terminal units

TOC

Order code

Order code

TVR

TVR with EASYLAB for room control and single operation

LABCONTROL

TVR D ... FL / 160 / G2 / ELAB / RS / ULZ / LAB / ...

EASYLAB

TVR D ... FL / 160 / G2 / ELAB / EC E0 / ULZ / ...

Type
TVR VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated RAL 7001;
silver grey
A2
Stainless steel construction
Flange
No entry: none
FL
Both ends (not for TVR-D-P1)
Nominal size [mm]
DN
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
SC
EC

Single operation
Supply air controller
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC,
provides uninterruptible
power supply (UPS

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correctionh

Additional functions
Only for room control (equipment function)
Raum management function has been
deactivated
LAB Extract air led system for laboratories
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system
Operating values [m3/h oder l/s, Pa]
For equipment function room control
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For single operation (equipment function)
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

K5 1.1 17

05/2015 DE/en

VAV terminal units

TOC

Order code

Order code
LABCONTROL
EASYLAB

TVR

TVR with EASYLAB for fume cupboard control

TVR D ... FL / 160 / G2 / ELAB / FH VS / ULZS / 200 900

Type
TVR VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Both ends (not for TVR-D-P1)
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB EASYLAB controller TCU3
with fast-running actuator
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value
Order example

TVR/200/D2/ELAB/FH-2P/200-700

LABCONTROL

Acoustic cladding
Nominal size
Accessories
Attachments
Equipment function

EASYLAB

K5 1.1 18

Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket for the connection
of lighting and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-SEG-** OLED display
BE-LCD-01 40-character display

Without
200 mm
Lip seals on both ends
EASYLAB controller TCU3 with fast-running actuator
Two switching steps

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
LABCONTROL
TCU-LON-II

TVR

TVR with TCU-LON-II

TVR D ... FL / 160 / G2 / TMA / RE / 1500 / 750 / 100

Type
TVR VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
G2
Matching flanges for both ends
D2
Lip seals on both ends

Order example

TVR/200/D2/TMB/FH/200700

LABCONTROL

Acoustic cladding
Nominal size
Accessories
Attachment
Equipment function

TCU-LON-II

05/2015 DE/en

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
FH
Fume cupboard
RS
Room supply air
RE
Room extract air
PS
Differential pressure control supply air
(Pressure Supply)
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
FH: min max
RS: / constant
RE: Tag / night / constant
PS: / constant / psetpoint
PE: day / night / constant / psetpoint
The room control volume flow rates
(RS, RE, PS, PE) are related to the total
extract air volume flow rate for the room
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-TCU-LON-II Control panel

Without
200 mm
Lip seals on both ends
TCU-LON-II with fast-running actuator (brushless motor)
Fume cupboard (Fume Hood)

K5 1.1 19

VAV terminal units

TOC

Aerodynamic data

Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVR

Volume flow rate ranges and minimum differential pressure values

l/s
100

125

160

200

250

315

400

Nominal size

m/h
10
40
65
95
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
100
410
720
1030
170
670
1175
1680

36
144
234
342
54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
360
1476
2592
3708
612
2412
4230
6048

pst min
Pa

5
15
35
70
5
15
45
90
5
15
35
70
5
15
35
65
5
10
25
45
5
5
15
30
5
5
15
25

5
15
40
85
5
20
50
100
5
15
40
80
5
15
35
70
5
10
25
50
5
10
20
35
5
5
15
30

%
5
20
45
95
5
20
55
110
5
15
45
85
5
15
40
75
5
10
30
55
5
10
20
40
5
5
15
30

5
20
50
105
5
20
60
115
5
15
45
95
5
15
40
80
5
15
35
65
5
10
20
40
5
5
15
35

15
8
7
5
15
7
6
5
15
8
7
5
15
7
5
5
15
7
5
5
15
7
6
5
15
7
6
5

TVR
TVR with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
TVR with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
TVR with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 20

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TVR

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values
can be interpolated.
Precise intermediate
values and spectral data
can be calculated with
our Easy Product Finder
design programme.
The first selection criteria
for the nominal size
are the actual volume
flow rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
100

125

160

200

250

315

400

10
40
65
95
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
105
410
720
1030
170
670
1175
1680

m/h
36
144
234
342
54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
378
1476
2592
3708
612
2412
4230
6048

LPA1

LPA
32
45
51
54
33
45
49
52
40
47
50
53
40
47
50
54
37
47
48
52
42
47
49
53
43
44
47
50

20
36
41
42
22
36
40
41
28
39
42
44
31
40
44
45
28
40
42
44
35
42
44
48
36
38
42
44

Case-radiated noise

dB (A)
<15
28
33
33
<15
30
34
34
20
34
37
39
23
34
40
39
22
34
38
38
28
35
39
42
30
32
36
38

<15
26
31
31
<15
28
32
32
16
31
34
36
20
33
38
38
20
33
37
37
25
34
38
41
26
30
35
37

LPA2

LPA3
<15
25
31
36
<15
25
31
35
20
28
32
37
20
29
32
38
20
35
37
42
28
39
42
46
30
37
41
46

<15
18
24
27
<15
17
21
24
<15
19
23
28
<15
15
21
25
<15
18
25
29
<15
21
28
35
<15
21
29
33

TVR
TVR with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
TVR with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
TVR with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm

05/2015 DE/en

K5 1.1 21

VAV terminal units

TOC

Dimensions and weight TVR


VAV terminal unit for the control
of variable air volume flow rates
Spigot to make connections to the ducting

VAV terminal unit,


variant TVR
Dimensions

TVR
L

~80

50

Description

TVR

Dimensions [mm] and weight [kg]


Nominal size

Easy
Compact

Universal
LABCONTROL

mm
100
125
160
200
250
315
400

K5 1.1 22

310
310
400
400
400
500
500

kg
600
600
600
600
600
600
600

99
124
159
199
249
314
399

3.3
3.6
4.2
5.1
6.1
7.2
9.4

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVR-D


Description

TVR

VAV terminal unit with acoustic cladding


for the control of variable air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted

VAV terminal unit,


variant TVR-D
Dimensions

TVR-D

L
~80

Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

05/2015 DE/en

Easy
Compact
L

Universal
LABCONTROL
L1

310
310
400
400
400
500
500

L
mm
232
232
312
312
312
417
417

600
600
600
600
600
600
600

L1

D3

m
kg

517
517
517
517
517
517
517

99
124
159
199
249
314
399

198
223
258
298
348
413
498

7.2
8.5
11.0
13.9
15.9
18.0
22.6

K5 1.1 23

VAV terminal units

TOC

Dimensions and weight TVR-FL


Description

VAV terminal unit for the control


of variable air volume flow rates
With flanges on both ends to make detachable
connections to the ducting

Dimensions

TVR-FL


~ 80

TVR

n x 9.5
T

Dimensions [mm] and weight [kg]

Nominal size

Universal
LABCONT
ROL

Easy
Compact

D1

D2

L
mm

100
125
160
200
250
315
400

K5 1.1 24

290
290
380
380
380
480
480

580
580
580
580
580
580
580

mm
99
124
159
199
249
314
399

132
157
192
233
283
352
438

152
177
212
253
303
378
464

4
4
6
6
6
8
8

kg
4
4
4
4
4
4
4

3.9
4.2
5.3
6.5
7.8
10.3
13.3

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVR-D-FL

TVR

Description

VAV terminal unit with acoustic cladding


for the control of variable air volume flows
With flanges on both ends to make detachable
connections to the ducting
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted
Powder-coated surface (P1)
or stainless steel construction (A2) not possible

Dimensions

TVR-D-FL


~ 80

n x 9.5
T

Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

05/2015 DE/en

Easy
Compact
L
290
290
380
380
380
480
480

Universal
LABCONTROL

L1
232
232
312
312
312
417
417

L
580
580
580
580
580
580
580

L1

D1

D2

D3

mm

517
517
517
517
517
517
517

mm
99
124
159
199
249
314
399

132
157
192
233
283
352
438

152
177
212
253
303
378
464

198
223
258
298
348
413
498

4
4
6
6
6
8
8

kg
4
4
4
4
4
4
4

7.8
9.1
12.1
14.3
17.6
21.2
26.5

K5 1.1 25

VAV terminal units

TOC

Installation details

Space requirement
for commissioning
and maintenance

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Junction

Bend

1D

5D

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the VAV terminal unit. If there is no straight
upstream section at all, the control will not be
stable, even with a perforated plate.

Access to attachments

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Space required

Space required

Attachments

mm

Attachments

VARYCONTROL
Easy controller

250

200

300

Compact controller

250

200

250

Universal controller, dynamic

520

250

250

LABCONTROL
EASYLAB

550

350

400

TCU-LON-II

550

250

300

250

150

250

mm
VARYCONTROL

Universal
controller,
static

520

250

250

Access to attachments

150

Upstream conditions

TVR

25
0

250

Separate space for fixing and accessing


the battery pack (LABCONTROL EASYLAB accessory)

K5 1.1 26

05/2015 DE/en

VAV terminal units

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular VAV terminal units for variable


and constant air volume systems,
suitable for supply or extract air,
available in seven nominal sizes.
High control accuracy
(even with upstream bend R = 1D).
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement and a damper blade.
Factory assembled control components
complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Spigot with groove for lip seal,
suitable for connecting ducts
according to EN 1506 or EN 13180.
Position of the damper blade indicated
externally at shaft extension.
Closed blade air leakage to EN 1751, class 4
(nominal size 100, class 2;
nominal sizes 125 and 160, class 3).
Casing air leakage to EN 1751, class C.

TOC

TVR
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Technical data
Nominal sizes: 100 to 400 mm
Volume flow rate range:
10 to 1680 l/s or 36 to 6048 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 10 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 90 Pa
Maximum differential pressure: 1000 Pa

Powder-coated construction (P1)


Casing made of galvanised sheet steel,
powder-coated
Damper blade and shaft
made of stainless steel 1.4301
Sensor tubes made of aluminium,
powder-coated

Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Clearly visible external indicator light
for signalling the functions: Set, not set,
and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.

Stainless steel construction (A2)


Casing, damper blade
and shaft made of stainless steel 1.4301
Sensor tubes made of aluminium,
powder-coated

Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary
Materials and surfaces
Galvanised sheet steel construction
Casing and damper blade
made of galvanised sheet steel
Damper blade seal made of TPE plastic
Aluminium sensor tubes
Plastic bearings

Variant with acoustic cladding (-D)


Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool

K5 1.1 27

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
VARYCONTROL

Type
TVR
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Both ends (not for TVR-D-P1)
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends

05/2015 DE/en

TVR
Attachments (control component)
Example
Easy Compact controller
BC0 Compact controller
B13 Universal controller
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)
Damper blade position
Only with spring return actuators
NO
Power off to open
NC
Power off to close

K5 1.1 28

VAV terminal units

TOC

Specification text

Order options
LABCONTROL
EASYLAB

TVR

Type
TVR
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Both ends (not for TVR-D-P1)

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Nominal size [mm]


DN
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
SC
EC

Single operation
Supply air controller
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa]
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

K5 1.1 29

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
TVR
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Both ends (not for TVR-D-P1)
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

05/2015 DE/en

TVR
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket
for the connection of lighting
and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-SEG-** OLED display
BE-LCD-01 40-character display

K5 1.1 30

VAV terminal units

Specification text

Order options
LABCONTROL
TCU-LON-II

Type
TVR
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
G2
Matching flanges for both ends
D2
Lip seals on both ends

K5 1.1 31

TOC

TVR
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
FH
Fume cupboard
RS
Room supply air
RE
Room extract air
PS
Differential pressure control supply air
(Pressure Supply)
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
FH: min max
RS: / constant
RE: Tag / night / constant
PS: / constant / psetpoint
PE: day / night / constant / psetpoint
The room control volume flow rates
(RS, RE, PS, PE) are related to the total
extract air volume flow rate for the room
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-TCU-LON-II Control panel

05/2015 DE/en

TVJ

TOC

1.1

X X TVJ testregistrierung

VAV terminal units

Type TVJ

For normal and high volume flow rate ranges


Universal controller

Rectangular VAV terminal units for standard applications regarding the supply air
or extract air control in variable air volume systems
For volume flow rate ranges up to 36,000 m/h or 10,000 l/s
Suitable for the control of volume flow rate, room pressure or duct pressure
Electronic control components for different applications
(Easy, Compact, Universal, and LABCONTROL)
High control accuracy
Suitable for airflow velocities up to 10 m/s
Casing air leakage to EN 1751, class B

Compact controller

Optional equipment and accessories


Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TX for the reduction of air-regenerated noise
Hot water heat exchanger of Type WT for reheating the airflow

Easy controller

05/2015 DE/en

K5 1.1 32

VAV terminal units

TOC

General information

TVJ
Page

Type

TVJ

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVJ
Dimensions and weight TVJ-D
Installation details
Specification text

1.1 33
1.1 37
1.1 40
1.1 42
1.1 46
1.1 48
1.1 50
1.1 52

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVJ

VAV terminal unit, variant TVJ-D

Application
Rectangular VARYCONTROL VAV terminal
units of Type TVJ for the precise supply air
or extract air flow control in variable
air volume systems
Closed-loop volume flow control
using an external power supply
For controlling, restricting, or shutting off
the airflow in air conditioning systems

Useful additions
Secondary silencer Type TX
for demanding acoustic requirements
Heat exchanger Type WT

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
TVJ: VAV terminal unit
TVJ-D: VAV terminal unit with acoustic cladding
Units with acoustic cladding and/or secondary
silencer Type TX for demanding
acoustic requirements
Acoustic cladding cannot be retrofitted
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Nominal sizes
39 nominal sizes from
200 100 to 1000 1000
Attachments
Easy controller: Compact unit consisting
of controller with potentiometers,
differential pressure transducer and actuator
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems

K5 1.1 33

Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blades
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special
test rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High volume flow rate control accuracy
Construction features
Rectangular casing
Flanges on both sides,
suitable for duct connection
Opposed blade action, blades connected
by internal gears at both ends
Position of the damper blade
indicated externally at shaft extension
Bearings with ring seals

05/2015 DE/en

VAV terminal units

TOC

General information
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Shafts made of galvanised steel
Damper blades and differential pressure
sensor made of aluminium
Gears made of anti-static plastic (ABS),
heat resistant to 50 C
Plastic bearings

TVJ
Standards and guidelines
Casing air leakage to EN 1751, class B
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Powder-coated construction (P1)


Casing made of galvanised sheet steel,
powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Installation and commissioning
Any installation orientation (except units
with static differential pressure transducer)
With flanges on both ends
to make connections to the ducting
TVJ-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic
cladding of the controller

05/2015 DE/en

K5 1.1 34

VAV terminal units

TOC

General information

TVJ

Attachments: VARYCONTROL control components for Type TVJ


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B13
B1B

Volume flow rate

XC3

Actuator
Spring return actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BS3
BSB
BSG
BG3
BGB
BH3
BHB
XE1
XE3
XF1
XF3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Static

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Static, integral
Static, integral 100 Pa

Universal controller with MP bus interface


TROX/Belimo

Differential pressure

Static, integral 600 Pa


Static, integral 100 Pa

Differential pressure controller


TROX/Belimo

Static, integral 600 Pa


Static, integral 100 Pa

Differential pressure controller


TROX/Gruner

Static, integral 600 Pa

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TVJ


Order code detail Control function
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Controller

Differential pressure transducer

Actuator

Room supply air


Room extract air
Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room supply air


Room extract air
Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Technical data

K5 1.1 35

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

Fast-running actuator
Static, integral

Fast-running actuator
(brushless motor)

200 100 to 1000 1000 mm


45 10100 l/s or 162 36360 m/h
Approx. 20 to 100 % of the nominal volume flow rate
5 40 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information

Function

TVJ

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow rate.
The control components (attachments) include
a differential pressure transducer that transforms
the differential pressure (effective pressure)
into an electric signal, a controller, and an actuator;
the control functions can be achieved
with an Easy controller, with a Compact controller,
or with individual components
(Universal or LABCONTROL).
For most applications, the setpoint value
comes from a room temperature controller.
The controller compares the actual value
with the setpoint value and alters the control signal
of the actuator if there is a difference between
the two values.

Schematic illustration of the TVJ

Differential pressure sensor


Damper blade

K5 1.1 36

Gears
Control components, e.g. an Easy controller

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
VARYCONTROL

TVJ

TVJ, TVJ/.../Easy

TVJ D P1 / 600400 / B1B / E 0 / 200 900 / NO

TVJ D / 900300 / Easy

Type
TVJ VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
Nominal size [mm]
BH
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

Order example

TVJ/400200/B13/M0/8002000 m/h

VARYCONTROL

Acoustic cladding
Material
Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rate

05/2015 DE/en

Without
Galvanised sheet steel
400 200 mm
Universal controller
Master
0 10 V DC
800 2000 m/h

K5 1.1 37

VAV terminal units

TOC

Order code

Order code

TVJ

TVJ with EASYLAB for room control and single operation

LABCONTROL

TVJ D P1 / 600400 / ELAB / RS / ULZ / LAB / ...

EASYLAB

TVJ D / P1 / 600400 / ELAB / EC E0 / ULZ / ...

Type
TVJ VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
Nominal size [mm]
BH

L
B
M
I
R

Equipment function
Room control
RS
Supply air control (Room Supply)
RE
Extract air control (Room Exhaust)
PC
Differential pressure control

Single operation
Supply air controller
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
EM-TRF for 230 V AC
T
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Attachments (control component)


ELAB EASYLAB controller TCU3
with fast-running actuator

SC
EC

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

K5 1.1 38

05/2015 DE/en

VAV terminal units

TOC

Order code

TVJ

Order example

TVJ/900300/ELAB/RS/Z/LAB

LABCONTROL

Acoustic cladding

EASYLAB

Nominal size

900 300 mm

Attachments

EASYLAB controller TCU3 with fast-running actuator

Without

Equipment function

Supply air control (Room Supply)

Module expansions

EM-AUTOZERO Solenoid valve for automatic zero point correction

Additional functions

Order code

Extract air led system for laboratories

TVJ with TCU-LON-II

LABCONTROL

TVJ D P1 / 600400 / TMA / RE / 1500 / 750 / 100

TCU-LON-II

Types
TVJ VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
Nominal size [mm]
BH
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

Order example

TVJ-D/900300/TMA/RS/100/300

LABCONTROL

Acoustic cladding

TCU-LON-II

Nominal size
Attachment
Equipment function
Operating values

05/2015 DE/en

Equipment function
Room supply air
RS
RE
Room extract air
PS
Differential pressure control supply air
(Pressure Supply)
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
RE: day / night / constant
PS: / constant / psetpoint
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

With
900 300 mm
TCU-LON-II with fast-running actuator
Supply air control (Room Supply)
Volume flow rate difference 100 m/h, constant volume flow rates 300 m/h

K5 1.1 39

VAV terminal units

TOC

Aerodynamic data

Volume flow rate ranges

TVJ

Volume flow rate ranges and minimum differential pressure values

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for all
operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

Nominal size

200 100

300 100

400 100

500 100

600 100

200 200

300 200

400 200

500 200

600 200

700 200

800 200

l/s

m/h

45
85
150
215
65
120
210
320
85
170
300
425
105
200
350
535
130
260
450
650
85
160
280
415
125
240
420
620
165
330
580
825
205
400
700
1035
250
500
870
1250
290
560
980
1450
330
660
1160
1650

162
306
540
774
234
432
756
1152
306
612
1080
1530
378
720
1260
1926
468
936
1620
2340
306
576
1008
1494
450
864
1512
2232
594
1188
2088
2970
738
1440
2520
3726
900
1800
3132
4500
1044
2016
3528
5220
1188
2376
4176
5940

pst min
Pa

5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40

10
25
80
155
10
25
70
155
10
25
80
155
10
25
70
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
80
155
10
25
75
155
10
25
80
155
10
25
75
155
10
25
80
155

%
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

l/s
300 300

400 300

500 300

600 300

700 300

800 300

900 300

1000 300

400 400

500 400

600 400

700 400

Nominal size

m/h

185
666
360 1296
630 2268
920 3312
245
882
480 1728
840 3024
1230 4428
305 1098
600 2160
1050 3780
1535 5526
370 1332
740 2664
1290 4644
1850 6660
430 1548
840 3024
1470 5292
2150 7740
490 1764
980 3528
1720 6192
2450 8820
555 1998
1080 3888
1890 6804
2770 9972
620 2232
1240 4464
2150 7740
3100 11160
325 1170
640 2304
1120 4032
1630 5868
410 1476
800 2880
1400 5040
2040 7344
490 1764
980 3528
1720 6192
2450 8820
570 2052
1120 4032
1960 7056
2850 10260

pst min
Pa

5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35

10
25
75
150
10
25
70
150
10
25
70
150
10
25
75
150
10
25
70
150
10
25
75
150
10
25
70
150
10
25
75
150
10
25
75
150
10
25
75
150
10
25
75
150
10
25
75
150

14
8
5
5
14
8
8
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

TVJ
TVJ with secondary silencer TX
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 40

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for all
operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVJ

Volume flow rate ranges and minimum differential pressure values

l/s
800 400

900 400

1000 400

500 500

600 500

700 500

800 500

900 500

Nominal size
650
1300
2280
3250
735
1440
2520
3670
820
1640
2850
4100
510
1000
1750
2540
610
1200
2100
3050
710
1400
2450
3550
810
1600
2800
4050
915
1800
3150
4570

m/h
2340
4680
8208
11700
2646
5184
9072
13212
2952
5904
10260
14760
1836
3600
6300
9144
2196
4320
7560
10980
2556
5040
8820
12780
2916
5760
10080
14580
3294
6480
11340
16452

pst min
Pa

5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40

10
25
75
150
10
25
75
150
10
25
75
150
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155

%
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

Nominal
size

1000 500

600 600

800 600

1000 600

800 800

1000 800

1000 1000

l/s
1020
2000
3500
5100
730
1440
2520
3650
970
1920
3360
4850
1220
2400
4200
6100
1300
2560
4480
6500
1620
3200
5600
8100
2020
4000
7000
10100

m/h
3672
7200
12600
18360
2628
5184
9072
13140
3492
6912
12096
17460
4392
8640
15120
21960
4680
9216
16128
23400
5832
11520
20160
29160
7272
14400
25200
36360

pst min
Pa

5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40

10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155

14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

TVJ
TVJ with secondary silencer TX
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 41

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVJ

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values
and spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
200 x 100

300 x 100

400 x 100

500 x 100

600 x 100

200 x 200

300 x 200

400 x 200

500 x 200

600 x 200

700 x 200

800 x 200

m/h
45
85
150
215
65
120
210
320
85
170
300
425
105
200
350
535
130
260
450
650
85
160
280
415
125
240
420
620
165
330
580
825
205
400
700
1035
250
500
870
1250
290
560
980
1450
330
660
1160
1650

162
306
540
774
234
432
756
1152
306
612
1080
1530
378
720
1260
1926
468
936
1620
2340
306
576
1008
1494
450
864
1512
2232
594
1188
2088
2970
738
1440
2520
3726
900
1800
1800
4500
1044
2016
3528
5220
1188
2376
4176
5940

LPA

LPA1
43
47
49
49
44
47
48
48
45
47
47
48
46
47
47
48
46
47
47
48
45
48
48
49
46
47
48
48
46
46
47
48
46
46
47
48
46
46
47
47
46
46
47
47
46
46
47
47

Case-radiated noise

dB(A)
17
26
36
41
18
27
34
40
20
28
35
40
20
28
34
40
22
28
35
39
20
28
35
40
21
27
34
39
22
27
34
39
22
27
34
39
22
27
34
39
22
27
34
39
22
27
34
39

LPA2

LPA3
31
35
38
41
32
35
38
41
33
37
40
43
34
37
41
44
34
38
42
45
33
36
41
43
34
37
41
44
35
38
43
46
36
39
44
47
36
40
45
47
37
40
45
48
37
41
46
49

19
24
29
33
20
25
30
34
21
27
32
36
22
27
32
37
22
29
34
37
21
26
32
36
22
27
33
37
23
29
35
39
24
30
36
40
25
31
37
41
25
31
38
42
26
32
38
42

TVJ
TVJ with secondary silencer TX
TVJ-D

K5 1.1 42

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TVJ

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values
and spectral data can
be calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
300 x 300

400 x 300

500 x 300

600 x 300

700 x 300

800 x 300

900 x 300

1000 x 300

400 x 400

500 x 400

600 x 400

700 x 400

m/h
185
360
630
920
245
480
840
1230
305
600
1050
1535
370
740
1290
1850
430
840
1470
2150
490
980
1720
2450
555
1080
1890
2770
620
1240
2150
3100
325
640
1120
1630
410
800
1400
2040
490
980
1720
2450
570
1120
1960
2850

666
1296
2268
3312
882
1728
3024
4428
1098
2160
3780
5526
1332
2664
4644
6660
1548
3024
5292
7740
1764
3528
6192
8820
1998
3888
6804
9972
2232
4464
7740
11160
1170
2304
4032
5868
1476
2880
5040
7344
1764
3528
6192
8820
2052
4032
7056
10260

LPA

LPA1
46
46
47
47
46
46
46
47
46
46
47
47
46
46
47
47
46
46
46
47
45
46
46
47
46
46
46
47
45
46
46
47
45
46
46
47
45
46
46
47
45
46
46
47
45
46
46
47

Case-radiated noise

dB(A)
21
26
33
39
21
27
33
39
22
27
33
39
22
27
33
39
22
27
33
39
22
27
33
39
22
27
33
39
22
28
33
38
21
27
34
40
21
27
34
40
21
27
34
39
22
27
33
39

LPA2

LPA3
35
39
43
46
36
40
44
47
67
41
45
48
37
42
46
49
38
42
47
50
38
43
47
50
39
43
48
51
39
44
48
51
37
41
45
49
38
42
46
50
38
43
47
50
39
43
48
51

23
29
35
39
24
30
37
41
25
31
38
42
26
32
39
42
27
33
40
43
27
34
40
44
28
34
41
44
28
35
41
45
26
31
37
42
27
32
38
43
27
33
40
44
28
34
40
44

TVJ
TVJ with secondary silencer TX
TVJ-D

05/2015 DE/en

K5 1.1 43

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVJ

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values
and spectral data can
be calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
800 x 400

900 x 400

1000 x 400

500 x 500

600 x 500

700 x 500

800 x 500

900 x 500

1000 x 500

600 x 600

800 x 600

1000 x 600

m/h
650
1300
2280
3250
735
1440
2520
3670
820
1640
2850
4100
510
1000
1750
2540
610
1200
2100
3050
710
1400
2450
3550
810
1600
2800
4050
915
1800
3150
4570
1020
2000
3500
5100
730
1440
2520
3650
970
1920
3360
4850
1220
2400
4200
6100

2340
4680
8208
11700
2646
5184
9072
13212
2952
5904
10260
14760
1836
3600
6300
9144
2196
4320
7560
10980
2556
5040
8820
12780
2916
5760
10080
14580
3294
6480
11340
16452
3672
7200
12600
18360
2628
5184
9072
13140
3492
6912
12096
17460
4392
8640
15120
21960

LPA

LPA1
45
45
46
47
45
46
46
47
45
45
46
47
45
46
46
47
45
46
46
47
45
46
46
47
45
45
46
47
45
46
46
47
44
45
46
46
45
45
46
46
45
45
46
46
45
45
46
46

Case-radiated noise

dB(A)
22
27
33
39
22
26
33
39
22
27
33
38
21
26
33
39
21
26
33
39
21
27
33
39
22
27
33
39
21
27
33
39
22
27
33
38
21
27
33
39
22
27
33
39
22
27
33
38

LPA2

LPA3
39
44
48
51
40
44
49
52
40
44
49
52
38
43
47
50
39
43
48
51
39
44
48
52
40
44
49
52
40
45
50
53
41
45
50
53
40
44
49
52
41
45
50
53
41
46
51
54

28
35
41
45
29
35
41
46
29
36
42
46
27
33
39
44
28
34
40
44
29
35
41
45
29
36
42
46
30
36
42
47
30
37
43
47
28
35
41
45
30
36
43
47
31
37
44
48

TVJ
TVJ with secondary silencer TX
TVJ-D

K5 1.1 44

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TVJ

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values
and spectral data can
be calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

05/2015 DE/en

Nominal size
l/s
800 x 800

1000 x 800

1000 x 1000

m/h
1300
2560
4480
6500
1620
3200
5600
8100
2020
4000
7000
10100

4680
9216
16128
23400
5832
11520
20160
29160
7272
14400
25200
36360

LPA

LPA1
44
45
46
46
44
45
46
46
44
45
45
46

Case-radiated noise

dB(A)
21
27
33
39
21
26
33
39
21
26
33
39

LPA2

LPA3
42
47
51
55
42
47
52
55
43
48
53
57

31
38
44
49
32
39
45
49
33
40
46
51

TVJ
TVJ with secondary silencer TX
TVJ-D

K5 1.1 45

VAV terminal units

TOC

Dimensions and weight TVJ


VAV terminal unit for the control
of variable air volume flow rates

VAV terminal unit,


variant TVJ
Dimensions

TVJ
B

400

M238FG1

Description

TVJ

M238FG1

13 20

B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
400 100
500 100
600 100
200 200
300 200
400 200
500 200
600 200
700 200
800 200
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300

K5 1.1 46

H
200
300
400
500
600
200
300
400
500
600
700
800
300
400
500
600
700
800
900
1000

B1
100
100
100
100
100
200
200
200
200
200
200
200
300
300
300
300
300
300
300
300

mm
234
334
434
534
634
234
334
434
534
634
734
834
334
434
534
634
734
834
934
1034

B2

H1
276
376
476
576
676
276
376
476
576
676
776
876
376
476
576
676
776
876
976
1076

H2
134
134
134
134
134
234
234
234
234
234
234
234
334
334
334
334
334
334
334
334

m
kg
176
176
176
176
176
276
276
276
276
276
276
276
376
376
376
376
376
376
376
376

6
7
8
9
10
9
10
11
12
13
14
15
10
11
12
13
15
16
18
19

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVJ


Dimensions

TVJ

TVJ

M238FG1

400

M238FG1

13 20

B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600
800 800
1000 800
1000 1000

05/2015 DE/en

H
400
500
600
700
800
900
1000
500
600
700
800
900
1000
600
800
1000
800
1000
1000

B1
400
400
400
400
400
400
400
500
500
500
500
500
500
600
600
600
800
800
1000

mm
434
534
634
734
834
934
1034
534
634
734
834
934
1034
634
834
1034
834
1034
1034

B2

H1
476
576
676
776
876
976
1076
576
676
776
876
976
1076
676
876
1076
876
1076
1076

H2
434
434
434
434
434
434
434
534
534
534
534
534
534
634
634
634
834
834
1034

m
kg
476
476
476
476
476
476
476
576
576
576
576
576
576
676
676
676
876
876
1076

14
15
16
17
18
21
20
19
20
22
23
25
26
19
23
27
28
32
38

K5 1.1 47

VAV terminal units

TOC

Dimensions and weight TVJ-D

VAV terminal unit,


variant TVJ-D
Dimensions

VAV terminal unit with acoustic cladding


for the control of variable air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The rectangular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted

TVJ-D
B

400

Description

TVJ

M8

B
B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
400 100
500 100
600 100
200 200
300 200
400 200
500 200
600 200
700 200
800 200
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300

K5 1.1 48

H
200
300
400
500
600
200
300
400
500
600
700
800
300
400
500
600
700
800
900
1000

B1
100
100
100
100
100
200
200
200
200
200
200
200
300
300
300
300
300
300
300
300

mm
234
334
434
534
634
234
334
434
534
634
734
834
334
434
534
634
734
834
934
1034

B2

H1
280
380
480
580
680
280
380
480
580
680
780
880
380
480
580
680
780
880
980
1080

H2
134
134
134
134
134
234
234
234
234
234
234
234
334
334
334
334
334
334
334
334

m
kg
180
180
180
180
180
280
280
280
280
280
280
280
380
380
380
380
380
380
380
380

9
11
12
14
15
14
15
17
18
20
21
23
15
17
18
20
22
24
26
29

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVJ-D


Dimensions

TVJ

TVJ-D

400

M8

B
B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600
800 800
1000 800
1000 1000

05/2015 DE/en

H
400
500
600
700
800
900
1000
500
600
700
800
900
1000
600
800
1000
800
1000
1000

B1
400
400
400
400
400
400
400
500
500
500
500
500
500
600
600
600
800
800
1000

mm
434
534
634
734
834
934
1034
534
634
734
834
934
1034
634
834
1034
834
1034
1034

B2

H1
480
580
680
780
880
980
1080
580
680
780
880
980
1080
680
880
1080
880
1080
1080

H2
434
434
434
434
434
434
434
534
534
534
534
534
534
634
634
634
834
834
1034

m
kg
480
480
480
480
480
480
480
580
580
580
580
580
580
680
680
680
880
880
1080

21
23
24
26
27
29
32
28
30
32
35
37
39
29
35
41
42
48
57

K5 1.1 49

VAV terminal units

TOC

Installation details

Junction, vertical

2H

4H

A bend with a straight duct section of at least


2H upstream of the VAV terminal unit has only a
negligible effect on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can
only be achieved with a straight duct section
of at least 4H upstream. Shorter upstream
sections require a perforated plate in the branch
and before the VAV terminal unit. If there is no
straight upstream section at all, the control
will not be stable, even with a perforated plate.

Bend, horizontal

Junction, horizontal

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend, vertical

Upstream conditions

TVJ

2B

A bend with a straight duct section of at least


2B upstream of the VAV terminal unit has only a
negligible effect on the volume flow rate accuracy.

K5 1.1 50

4B

A junction causes strong turbulence.


The stated volume flow rate accuracy can
only be achieved with a straight duct section
of at least 4B upstream. Shorter upstream
sections require a perforated plate in the branch
and before the VAV terminal unit. If there is no
straight upstream section at all, the control
will not be stable, even with a perforated plate.

05/2015 DE/en

VAV terminal units

TOC

Installation details

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance.
It may be necessary
to provide sufficiently
sized inspection
access openings.

Access to attachments

Access to attachments

1
150

Space requirement
for commissioning
and maintenance

TVJ

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Attachments

VARYCONTROL
Easy controller
400
Compact controller
400
Universal controller
500
LABCONTROL
EASYLAB
500
TCU-LON-II
500

mm
H
H
H

300
300
300

H
H

400
300

H: Unit height

05/2015 DE/en

K5 1.1 51

VAV terminal units

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can
be generated with our
Easy Product Finder
design programme.

Rectangular VAV terminal units for variable


and constant air volume systems, suitable for
supply or extract air, available in 39 nominal sizes.
High volume flow rate control accuracy.
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement and damper blades.
Factory assembled control components
complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Both ends suitable for the connection of ducts.
Position of the damper blades indicated
externally at the shaft extension.
Casing air leakage to EN 1751, class B.
Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Shafts made of galvanised steel
Damper blades and differential pressure
sensor made of aluminium
Gears made of anti-static plastic (ABS),
heat resistant to 50 C
Plastic bearings
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool

TOC

TVJ
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Technical data
Nominal sizes: 200 100 to 1000 1000 mm
Volume flow rate range:
45 to 10100 l/s or 162 to 36360 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 20 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 40 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 20 100 %
of the nominal volume flow rate
Clearly visible external indicator light
for signalling the functions: Set, not set,
and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

K5 1.1 52

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
VARYCONTROL

Type
TVJ
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

TVJ
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

05/2015 DE/en

K5 1.1 53

VAV terminal units

TOC

Specification text

Order options
LABCONTROL
EASYLAB

TVJ

Type
TVJ
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
SC
EC

Single operation
Supply air controller
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

K5 1.1 54

05/2015 DE/en

VAV terminal units

Specification text
Order options
LABCONTROL
TCU-LON-II

Types
TVJ
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

05/2015 DE/en

TOC

TVJ
Equipment function
RS
Room supply air
RE
Room extract air
PS
Differential pressure control supply air
(Pressure Supply)
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
RE: day / night / constant
PS: / constant / psetpoint
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract
air volume flow rate for the room

K5 1.1 55

TVT

TOC

1.1

X X TVTtestregistrierung

VAV terminal units

Type TVT

Universal controller

Compact controller

For normal and high volume flow rate ranges


and air-tight shut-off
Rectangular VAV terminal units for standard applications regarding the supply air
or extract air control in variable air volume systems where low-leakage
shut-off is required
For volume flow rate ranges up to 21,000 m/h or 5,800 l/s
Suitable for the control of volume flow rate, room pressure or duct pressure
Electronic control components for different applications
(Easy, Compact, Universal, and LABCONTROL)
High control accuracy
Suitable for airflow velocities up to 10 m/s

Easy controller

Closed blade air leakage to EN 1751, class 3


Casing air leakage to EN 1751, up to class C
Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TX for the reduction of air-regenerated noise
Hot water heat exchanger of Type WT for reheating the airflow

With sealing elements


for low-leakage shut-off

05/2015 DE/en

K5 1.1 56

VAV terminal units

TOC

General information

TVT
Page

Type

TVT

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVT
Dimensions and weight TVT-D
Installation details
Specification text

1.1 57
1.1 61
1.1 64
1.1 66
1.1 69
1.1 71
1.1 73
1.1 75

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVT

VAV terminal unit, variant TVT-D

Application
Rectangular VARYCONTROL VAV terminal
units of Type TVT for the precise supply air
or extract air flow control in variable
air volume systems
Closed-loop volume flow control
using an external power supply
For controlling, restricting, or shutting
off the airflow in air conditioning systems
Shut-off by means of switching
(equipment supplied by others)

Attachments
Easy controller: Compact unit consisting
of controller with potentiometers,
differential pressure transducer and actuator
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
TVT: VAV terminal unit
TVT-D: VAV terminal unit with acoustic cladding
Units with acoustic cladding and/or secondary
silencer Type TX for demanding
acoustic requirements
Acoustic cladding cannot be retrofitted
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Nominal sizes
36 nominal sizes from 200 100 to 1000 600
Up to nominal size 800 300 including
all attachments, larger units only
with actuators with higher torque

K5 1.1 57

Useful additions
Secondary silencer Type TX
for demanding acoustic requirements
Heat exchanger Type WT
Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary

05/2015 DE/en

VAV terminal units

TOC

General information
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blades
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High volume flow rate control accuracy
Construction features
Rectangular casing
Flanges on both sides,
suitable for duct connection
Opposed blade action, blades connected
by internal gears (enclosed) at both ends
Damper blades with replaceable seals
Position of the damper blade indicated
externally at shaft extension
Bearings with ring seals

TVT
Installation and commissioning
Any installation orientation (except units
with static differential pressure transducer)
With flanges on both ends
to make connections to the ducting
TVT-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller
Standards and guidelines
Closed blade air leakage to EN 1751, class 3
Meets the general requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class C
(B + H 400, class B)
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Materials and surfaces


Galvanised sheet steel construction
Casing made of galvanised sheet steel
Shaft and linkage made of galvanised steel
Damper blades and differential pressure
sensor made of aluminium
Gears made of anti-static plastic (ABS),
heat resistant to 50 C
Plastic bearings
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

05/2015 DE/en

K5 1.1 58

VAV terminal units

TOC

General information

TVT

Attachments: VARYCONTROL control components for Type TVT


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B11
B1B
XC3

Volume flow rate

Actuator
Spring return actuator

Universal controller, static


BP1
BPB
BPG
BB1
BBB
XD1
XD3
BR1
BRB
BS1
BSB
BSG
BG1
BGB
BH1
BHB
XE1
XE3
XF1
XF3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Static

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Static, integral
Static, integral 100 Pa

Universal controller with MP bus interface


TROX/Belimo

Differential pressure

Differential pressure controller


TROX/Belimo

Differential pressure controller


TROX/Gruner

Static, integral 600 Pa


Static, integral 100 Pa
Static, integral 600 Pa
Static, integral 100 Pa
Static, integral 600 Pa

Attachments: LABCONTROL control components for Type TVT


Order code detail
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Technical data

K5 1.1 59

Control function

Controller

Differential pressure transducer

Actuator

Room supply air


Room extract air
Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running
actuator

Static, integral

Fast-running
actuator
Fast-running
actuator
(brushless motor)

Room supply air


Room extract air
Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

200 100 to 1000 600 mm


45 6100 l/s or 162 21960 m/h
Approx. 20 to 100 % of the nominal volume flow rate
5 40 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information

Function

TVT

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring
the volume flow rate. The control components
(attachments) include a differential pressure
transducer that transforms the differential
pressure (effective pressure) into an electric
signal, a controller, and an actuator; the control
functions can be achieved with an Easy controller,
with a Compact controller, or with individual
components (Universal or LABCONTROL).
For most applications, the setpoint value comes
from a room temperature controller.
The controller compares the actual value with
the setpoint value and alters the control signal
of the actuator if there is a difference between
the two values.

Schematic illustration of the TVT

Differential pressure sensor


Damper blade with seal

K5 1.1 60

Gears
Control components, e.g. an Easy controller

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
VARYCONTROL

TVT

TVT, TVT/.../Easy

TVT D P1 / 600400 / B1B / E 0 / 200 900 / NO

TVT D / 600400 / Easy

Type
TVT VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
Nominal size [mm]
BH
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B11 Universal controller

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2 10 V DC
2
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

Order example

TVT/500300/BC0/E0/20005500 m/h

VARYCONTROL

Acoustic cladding
Material
Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rate

05/2015 DE/en

Without
Galvanised sheet steel
500 300 mm
Compact controller
Single
0 10 V DC
2000 5500 m/h

K5 1.1 61

VAV terminal units

TOC

Order code

Order code

TVT

TVT with EASYLAB for room control and single operation

LABCONTROL

TVT D P1 / 600400 / ELAB / RS / ULZ / LAB / ...

EASYLAB

TVT D / P1 / 600400 / ELAB / EC E0 / ULZ / ...

Type
TVT VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
Nominal size [mm]
BH

L
B
M
I
R

Equipment function
Room control
RS
Supply air control (Room Supply)
RE
Extract air control (Room Exhaust)
PC
Differential pressure control

Single operation
Supply air controller
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
EM-TRF for 230 V AC
T
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Attachments (control component)


ELAB EASYLAB controller TCU3
with fast-running actuator

SC
EC

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

K5 1.1 62

05/2015 DE/en

VAV terminal units

TOC

Order code

TVT

Order example

TVT/600400/ELAB/SC/2P/3000/7000

LABCONTROL

Acoustic cladding

EASYLAB

Nominal size

Without
600 400 mm

Attachment

EASYLAB controller TCU3 with fast-running actuator

Equipment function

Supply air controller

External volume flow rate setting

Order code

On-site switch contacts for 2 switching steps, 3000 and 7000 m/h

TVT with TCU-LON-II

LABCONTROL

TVT D P1 / 600400 / TMA / RE / 1500 / 750 / 100

TCU-LON-II

Types
TVT VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1
Nominal size [mm]
BH
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

Order example

TVT-P1/600400/TMB/RE/1500/750/100

LABCONTROL

Acoustic cladding
Material
Nominal size
Attachment
Equipment function

TCU-LON-II

Operating values

05/2015 DE/en

Equipment function
RS
Room supply air
RE
Room extract air
PS
Differential pressure control supply air
(Pressure Supply)
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
RE: day / night / constant
PS: / constant / psetpoint
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

Without
Powder-coated RAL 7001, silver grey
600 400 mm
TCU-LON-II with fast-running actuator (brushless motor)
Room extract air
Total extract air day-time operation = 1500 m/h,
total extract air night-time operation = 750 m/h,
constant volume flow rates = 100 m/h

K5 1.1 63

VAV terminal units

TOC

Aerodynamic data

Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for all
operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVT

Volume flow rate ranges and minimum differential pressure values

200 100

300 100

400 100

500 100

600 100

200 200

300 200

400 200

500 200

600 200

700 200

Nominal size
l/s

m/h

45
85
150
215
65
120
210
320
85
170
300
425
105
200
350
535
130
260
450
650
85
160
280
415
125
240
420
620
165
330
580
825
205
400
700
1035
250
500
870
1250
290
560
980
1450

162
306
540
774
234
432
756
1152
306
612
1080
1530
378
720
1260
1926
468
936
1620
2340
306
576
1008
1494
450
864
1512
2232
594
1188
2088
2970
738
1440
2520
3726
900
1800
3132
4500
1044
2016
3528
5220

pst min
Pa

5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40

10
25
80
155
10
25
70
155
10
25
80
155
10
25
70
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
80
155
10
25
75
155
10
25
80
155
10
25
75
155

%
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

l/s
800 200

300 300

400 300

500 300

600 300

700 300

800 300

900 300

1000 300

400 400

500 400

Nominal size

m/h

330 1188
660 2376
1160 4176
1650 5940
185
666
360 1296
630 2268
920 3312
245
882
480 1728
840 3024
1230 4428
305 1098
600 2160
1050 3780
1535 5526
370 1332
740 2664
1290 4644
1850 6660
430 1548
840 3024
1470 5292
2150 7740
490 1764
980 3528
1720 6192
2450 8820
555 1998
1080 3888
1890 6804
2770 9972
620 2232
1240 4464
2150 7740
3100 11160
325 1170
640 2304
1120 4032
1630 5868
410 1476
800 2880
1400 5040
2040 7344

pst min
Pa

5
10
20
40
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35

10
25
80
155
10
25
75
150
10
25
70
150
10
25
70
150
10
25
75
150
10
25
70
150
10
25
75
150
10
25
70
150
10
25
75
150
10
25
75
150
10
25
75
150

14
8
5
5
14
8
5
5
14
8
8
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

TVT
TVT with secondary silencer TX
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 64

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for all
operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVT

Volume flow rate ranges and minimum differential pressure values

600 400

700 400

800 400

900 400

1000 400

500 500

600 500

Nominal size
l/s

m/h

490
980
1720
2450
570
1120
1960
2850
650
1300
2280
3250
735
1440
2520
3670
820
1640
2850
4100
510
1000
1750
2540
610
1200
2100
3050

1764
3528
6192
8820
2052
4032
7056
10260
2340
4680
8208
11700
2646
5184
9072
13212
2952
5904
10260
14760
1836
3600
6300
9144
2196
4320
7560
10980

pst min
Pa

5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
35
5
10
20
40
5
10
20
40

10
25
75
150
10
25
75
150
10
25
75
150
10
25
75
150
10
25
75
150
10
25
75
155
10
25
75
155

%
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

l/s
700 500

800 500

900 500

1000 500

600 600

800 600

1000 600

Nominal size
710
1400
2450
3550
810
1600
2800
4050
915
1800
3150
4570
1020
2000
3500
5100
730
1440
2520
3650
970
1920
3360
4850
1220
2400
4200
6100

m/h
2556
5040
8820
12780
2916
5760
10080
14580
3294
6480
11340
16452
3672
7200
12600
18360
2628
5184
9072
13140
3492
6912
12096
17460
4392
8640
15120
21960

pst min
Pa

5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40
5
10
20
40

10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155
10
25
75
155

14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5
14
8
5
5

TVT
TVT with secondary silencer TX
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 65

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVT

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
200 x 100

300 x 100

400 x 100

500 x 100

600 x 100

200 x 200

300 x 200

400 x 200

500 x 200

600 x 200

700 x 200

800 x 200

m/h
45
85
150
215
65
120
210
320
85
170
300
425
105
200
350
535
130
260
450
650
85
160
280
415
125
240
420
620
165
330
580
825
205
400
700
1035
250
500
870
1250
290
560
980
1450
330
660
1160
1650

162
306
540
774
234
432
756
1152
306
612
1080
1530
378
720
1260
1926
468
936
1620
2340
306
576
1008
1494
450
864
1512
2232
594
1188
2088
2970
738
1440
2520
3726
900
1800
1800
4500
1044
2016
3528
5220
1188
2376
4176
5940

LPA

LPA1
43
47
49
49
44
47
48
48
45
47
47
48
46
47
47
48
46
47
47
48
45
48
48
49
46
47
48
48
46
46
47
48
46
46
47
48
46
46
47
47
46
46
47
47
46
46
47
47

Case-radiated noise

dB(A)
17
26
36
41
18
27
34
40
20
28
35
40
20
28
34
40
22
28
35
39
20
28
35
40
21
27
34
39
22
27
34
39
22
27
34
39
22
27
34
39
22
27
34
39
22
27
34
39

LPA2

LPA3
31
35
38
41
32
35
38
41
33
37
40
43
34
37
41
44
34
38
42
45
33
36
41
43
34
37
41
44
35
38
43
46
36
39
44
47
36
40
45
47
37
40
45
48
37
41
46
49

19
24
29
33
20
25
30
34
21
27
32
36
22
27
32
37
22
29
34
37
21
26
32
36
22
27
33
37
23
29
35
39
24
30
36
40
25
31
37
41
25
31
38
42
26
32
38
42

TVT
TVT with secondary silencer TX
TVT-D

K5 1.1 66

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TVT

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
300 x 300

400 x 300

500 x 300

600 x 300

700 x 300

800 x 300

900 x 300

1000 x 300

400 x 400

500 x 400

600 x 400

700 x 400

m/h
185
360
630
920
245
480
840
1230
305
600
1050
1535
370
740
1290
1850
430
840
1470
2150
490
980
1720
2450
555
1080
1890
2770
620
1240
2150
3100
325
640
1120
1630
410
800
1400
2040
490
980
1720
2450
570
1120
1960
2850

666
1296
2268
3312
882
1728
3024
4428
1098
2160
3780
5526
1332
2664
4644
6660
1548
3024
5292
7740
1764
3528
6192
8820
1998
3888
6804
9972
2232
4464
7740
11160
1170
2304
4032
5868
1476
2880
5040
7344
1764
3528
6192
8820
2052
4032
7056
10260

LPA

LPA1
46
46
47
47
46
46
46
47
46
46
47
47
46
46
47
47
46
46
46
47
45
46
46
47
46
46
46
47
45
46
46
47
45
46
46
47
45
46
46
47
45
46
46
47
45
46
46
47

Case-radiated noise

dB(A)
21
26
33
39
21
27
33
39
22
27
33
39
22
27
33
39
22
27
33
39
22
27
33
39
22
27
33
39
22
28
33
38
21
27
34
40
21
27
34
40
21
27
34
39
22
27
33
39

LPA2

LPA3
35
39
43
46
36
40
44
47
67
41
45
48
37
42
46
49
38
42
47
50
38
43
47
50
39
43
48
51
39
44
48
51
37
41
45
49
38
42
46
50
38
43
47
50
39
43
48
51

23
29
35
39
24
30
37
41
25
31
38
42
26
32
39
42
27
33
40
43
27
34
40
44
28
34
41
44
28
35
41
45
26
31
37
42
27
32
38
43
27
33
40
44
28
34
40
44

TVT
TVT with secondary silencer TX
TVT-D

05/2015 DE/en

K5 1.1 67

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVT

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
800 x 400

900 x 400

1000 x 400

500 x 500

600 x 500

700 x 500

800 x 500

900 x 500

1000 x 500

600 x 600

800 x 600

1000 x 600

m/h
650
1300
2280
3250
735
1440
2520
3670
820
1640
2850
4100
510
1000
1750
2540
610
1200
2100
3050
710
1400
2450
3550
810
1600
2800
4050
915
1800
3150
4570
1020
2000
3500
5100
730
1440
2520
3650
970
1920
3360
4850
1220
2400
4200
6100

2340
4680
8208
11700
2646
5184
9072
13212
2952
5904
10260
14760
1836
3600
6300
9144
2196
4320
7560
10980
2556
5040
8820
12780
2916
5760
10080
14580
3294
6480
11340
16452
3672
7200
12600
18360
2628
5184
9072
13140
3492
6912
12096
17460
4392
8640
15120
21960

LPA

LPA1
45
45
46
47
45
46
46
47
45
45
46
47
45
46
46
47
45
46
46
47
45
46
46
47
45
45
46
47
45
46
46
47
44
45
46
46
45
45
46
46
45
45
46
46
45
45
46
46

Case-radiated noise

dB(A)
22
27
33
39
22
26
33
39
22
27
33
38
21
26
33
39
21
26
33
39
21
27
33
39
22
27
33
39
21
27
33
39
22
27
33
38
21
27
33
39
22
27
33
39
22
27
33
38

LPA2

LPA3
39
44
48
51
40
44
49
52
40
44
49
52
38
43
47
50
39
43
48
51
39
44
48
52
40
44
49
52
40
45
50
53
41
45
50
53
40
44
49
52
41
45
50
53
41
46
51
54

28
35
41
45
29
35
41
46
29
36
42
46
27
33
39
44
28
34
40
44
29
35
41
45
29
36
42
46
30
36
42
47
30
37
43
47
28
35
41
45
30
36
43
47
31
37
44
48

TVT
TVT with secondary silencer TX
TVT-D

K5 1.1 68

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVT


Description

TVT

VAV terminal unit for the control


of variable air volume flow rates

VAV terminal unit,


variant TVT
Dimensions

TVT
B

M238FG1

400

M238FG1

13 20

B
B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
400 100
500 100
600 100
200 200
300 200
400 200
500 200
600 200
700 200
800 200
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300

05/2015 DE/en

H
200
300
400
500
600
200
300
400
500
600
700
800
300
400
500
600
700
800
900
1000

B1
100
100
100
100
100
200
200
200
200
200
200
200
300
300
300
300
300
300
300
300

mm
234
334
434
534
634
234
334
434
534
634
734
834
334
434
534
634
734
834
934
1034

B2

H1
276
376
476
576
676
276
376
476
576
676
776
876
376
476
576
676
776
876
976
1076

H2
134
134
134
134
134
234
234
234
234
234
234
234
334
334
334
334
334
334
334
334

m
kg
176
176
176
176
176
276
276
276
276
276
276
276
376
376
376
376
376
376
376
376

6
7
8
9
10
9
10
11
12
13
14
15
10
11
12
13
15
16
18
19

K5 1.1 69

VAV terminal units

TOC

Dimensions and weight TVT


TVT
B

400

M238FG1

Dimensions

TVT

M238FG1

13 20

B
B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600

K5 1.1 70

H
400
500
600
700
800
900
1000
500
600
700
800
900
1000
600
800
1000

B1
400
400
400
400
400
400
400
500
500
500
500
500
500
600
600
600

mm
434
534
634
734
834
934
1034
534
634
734
834
934
1034
634
834
1034

B2

H1
476
576
676
776
876
976
1076
576
676
776
876
976
1076
676
876
1076

H2
434
434
434
434
434
434
434
534
534
534
534
534
534
634
634
634

m
kg
476
476
476
476
476
476
476
576
576
576
576
576
576
676
676
676

14
15
16
17
18
21
20
19
20
22
23
25
26
19
23
27

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVT-D


Description

VAV terminal unit,


variant TVT-D
Dimensions

TVT

VAV terminal unit with acoustic cladding


for the control of variable air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The rectangular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted

TVT-D
B

400

M8

B
B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
400 100
500 100
600 100
200 200
300 200
400 200
500 200
600 200
700 200
800 200
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300

05/2015 DE/en

H
200
300
400
500
600
200
300
400
500
600
700
800
300
400
500
600
700
800
900
1000

B1
100
100
100
100
100
200
200
200
200
200
200
200
300
300
300
300
300
300
300
300

mm
234
334
434
534
634
234
334
434
534
634
734
834
334
434
534
634
734
834
934
1034

B2

H1
280
380
480
580
680
280
380
480
580
680
780
880
380
480
580
680
780
880
980
1080

H2
134
134
134
134
134
234
234
234
234
234
234
234
334
334
334
334
334
334
334
334

m
kg
180
180
180
180
180
280
280
280
280
280
280
280
380
380
380
380
380
380
380
380

9
11
12
14
15
14
15
17
18
20
21
23
15
17
18
20
22
24
26
29

K5 1.1 71

VAV terminal units

TOC

Dimensions and weight TVT-D


TVT-D
B

400

Dimensions

TVT

M8

B
B
~ 80

Dimensions [mm] and weight [kg]


Nominal size
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600

K5 1.1 72

H
400
500
600
700
800
900
1000
500
600
700
800
900
1000
600
800
1000

B1
400
400
400
400
400
400
400
500
500
500
500
500
500
600
600
600

mm
434
534
634
734
834
934
1034
534
634
734
834
934
1034
634
834
1034

B2

H1
480
580
680
780
880
980
1080
580
680
780
880
980
1080
680
880
1080

H2
434
434
434
434
434
434
434
534
534
534
534
534
534
634
634
634

m
kg
480
480
480
480
480
480
480
580
580
580
580
580
580
680
680
680

21
23
24
26
27
29
32
28
30
32
35
37
39
29
35
41

05/2015 DE/en

VAV terminal units

TOC

Installation details
Junction, vertical

2H

4H

A bend with a straight duct section of at least


2H upstream of the VAV terminal unit has only a
negligible effect on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
4H upstream. Shorter upstream sections require
a perforated plate in the branch and before
the VAV terminal unit. If there is no straight
upstream section at all, the control will
not be stable, even with a perforated plate.

Bend, horizontal

Junction, horizontal

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing or
widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend, vertical

Upstream conditions

TVT

2B

A bend with a straight duct section of at least


2B upstream of the VAV terminal unit has only a
negligible effect on the volume flow rate accuracy.

05/2015 DE/en

4B

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
4B upstream. Shorter upstream sections require
a perforated plate in the branch and before
the VAV terminal unit. If there is no straight
upstream section at all, the control will
not be stable, even with a perforated plate.

K5 1.1 73

VAV terminal units

TOC

Installation details

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Access to attachments

Access to attachments

150

Space requirement
for commissioning
and maintenance

TVT

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Attachments

VARYCONTROL
Easy controller
400
Compact controller
400
Universal controller
500
LABCONTROL
EASYLAB
500
TCU-LON-II
500

mm
H
H
H

300
300
300

H
H

400
300

H: Unit height

K5 1.1 74

05/2015 DE/en

VAV terminal units

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular VAV terminal units for variable


and constant air volume systems, suitable for
supply or extract air, available in 36 nominal sizes.
High volume flow rate control accuracy.
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement and damper blades.
Factory assembled control components
complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Both ends suitable for the connection of ducts.
Position of the damper blades indicated
externally at the shaft extension.
Closed blade air leakage to EN 1751, class 3.
Casing air leakage to EN 1751,
class C (B + H 400, class B)
Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Shaft and linkage made of galvanised steel
Damper blades and differential pressure
sensor made of aluminium
Gears made of anti-static plastic (ABS),
heat resistant to 50 C
Plastic bearings
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated

TOC

TVT
Technical data
Nominal sizes: 200 100 to 1000 600 mm
Volume flow rate range:
45 to 6100 l/s or 162 to 21960 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 20 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 40 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 20 100 %
of the nominal volume flow rate
Clearly visible external indicator light
for signalling the functions: Set, not set,
and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Variant with acoustic cladding (-D)


Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)

05/2015 DE/en

K5 1.1 75

VAV terminal units

TOC

Specification text

Order options

Type
TVT
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B11 Universal controller

TVT
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

K5 1.1 76

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

TVT

Type
TVT
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
SC
EC

Single operation
Supply air controller
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

05/2015 DE/en

K5 1.1 77

VAV terminal units

Specification text

Order options
LABCONTROL
TCU-LON-II

Types
TVT
VAV terminal unit
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

K5 1.1 78

TOC

TVT
Equipment function
RS
Room supply air
RE
Room extract air
PS
Differential pressure control supply air
(Pressure Supply)
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
RE: day / night / constant
PS: / constant / psetpoint
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

05/2015 DE/en

TZ-Silenzio

TOC

1.1

X X TZ-Silenziotestregistrierung

VAV terminal units

Type TZ-Silenzio

For supply air systems with demanding


acoustic requirements and low airflow velocities

Rectangular connections
on both ends

Rectangular VAV terminal units for the supply air or extract air control in buildings
with variable air volume systems, demanding acoustic requirements
and low airflow velocities
Highly effective integral attenuator
Optimised for airflow velocities of 0.7 6 m/s
High control accuracy even in case of unfavourable upstream conditions
Compact construction with rectangular connections on both ends
Electronic control components for different applications
(Easy, Compact, Universal, and LABCONTROL)

Closed blade air leakage to EN 1751, class 4


p

For all upstream conditions

Casing air leakage to EN 1751, class B


Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TS for the reduction of air-regenerated noise
Hot water heat exchanger of Type WT for reheating the airflow

ET

HY

SCH GET
E

ST

I
EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 79

VAV terminal units

TOC

General information

TZ-Silenzio
Page

Type

TZ-Silenzio

Description

VAV terminal unit


Type TZ-Silenzio
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TZ-Silenzio
Dimensions and weight TZ-Silenzio-D
Installation details
Specification text

1.1 80
1.1 83
1.1 86
1.1 87
1.1 88
1.1 89
1.1 90
1.1 92

Basic information and nomenclature

1.5 1

Application
VARYCONTROL VAV terminal units
of Type TZ-Silenzio for the supply air control
in variable air volume systems
with low airflow velocities
Closed-loop volume flow control
using an external power supply
Integral attenuator for demanding
acoustic requirements
Shut-off by means of switching
(equipment supplied by others)
Variants
TZ-Silenzio: Supply air unit
TZ-Silenzio-D: Supply air unit
with acoustic cladding
Units with acoustic cladding
and/or secondary silencer Type TS
for very demanding acoustic requirements
Acoustic cladding cannot be retrofitted
Nominal sizes
125, 160, 200, 250, 315
Attachments
Easy controller:
Compact unit with potentiometers
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems
Useful additions
Secondary silencer Type TS
Heat exchanger Type WT
Special characteristics
Hygiene tested and certified
Direct connection of ducting
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary

K5 1.1 80

Parts and characteristics


Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blade
Integral attenuator
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy even in case
of unfavourable upstream conditions
Construction features
Rectangular casing
Replaceable seals
Flanges on both ends
for connection to ductwork
Position of the damper blade indicated
externally at shaft extension
Thermal and acoustic insulation (lining)
Materials and surfaces
Casing made of galvanised sheet steel
Damper blade and differential
pressure sensor made of aluminium
Lining is mineral wool
Plastic bearings
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

05/2015 DE/en

VAV terminal units

TOC

General information

TZ-Silenzio

Installation and commissioning


Any installation orientation (except units
with static differential pressure transducer)
Return edges of the casing with drilled
holes suitable for M10 threaded rods
TZ-Silenzio-D: For constructions with acoustic
cladding, ducts on the room side should have
cladding up to the acoustic cladding
of the controller

Standards and guidelines


Hygiene conforms to VDI 6022
VDI 2083, air cleanliness class 3,
and US standard 209E, class 100
Closed blade air leakage to EN 1751, class 4
Meets the increased requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class B
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Attachments: VARYCONTROL control components for Type TZ-Silenzio


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B13
B1B
XC3

Volume flow rate

Actuator

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Spring return actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BRG
BG3
BGB
XE1
XE3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Static, integral

Universal controller with MP bus interface


TROX/Belimo
Differential pressure

Static

Static, 100 Pa

Differential pressure controller


TROX/Belimo
Differential pressure controller
TROX/Gruner

Static, integral 100 Pa

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TZ-Silenzio


Order code detail
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Control function

Controller

Differential pressure transducer

Actuator

Room supply air


Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room supply air


Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

05/2015 DE/en

Fast-running actuator
Static, integral

Fast-running actuator
(brushless motor)

K5 1.1 81

VAV terminal units

TOC

General information

Technical data

Function

TZ-Silenzio

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

125 315
30 840 l/s or 108 3024 m/h
Approx. 10 to 100 % of the nominal volume flow rate
5 65 Pa
1000 Pa
10 50 C

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow
rate. The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator;
the control functions can be achieved
with an Easy controller, with a Compact controller,
or with individual components (Universal).
For most applications, the setpoint value comes
from a room temperature controller.
The controller compares the actual value
with the setpoint value and alters the control
signal of the actuator if there is a difference
between the two values.
An integral attenuator reduces the noise
that is created by the restriction of the airflow.

Schematic illustration of the TZ-Silenzio

Integral attenuator
Differential pressure sensor

K5 1.1 82

Control components, e.g. an Easy controller


Damper blade with seal

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TZ-Silenzio

TZ-Silenzio, TZ-Silenzio/.../Easy

VARYCONTROL

TZSilenzio D / 200 / B1B / E 0 / 400 1200 / NO

TZSilenzio D / 200 / Easy

Type
TZ-Silenzio

VAV terminal unit, supply air

Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

Order example

TZ-Silenzio/200/BC0/E0/3001200 m/h

VARYCONTROL

Acoustic cladding
Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rate

05/2015 DE/en

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting (operating mode A)
Damper blade position
Only with spring return actuators
Power off to OPEN
NO
NC
Power off to CLOSE

Without
200
Compact controller
Single
0 10 V DC
300 1200 m/h

K5 1.1 83

VAV terminal units

TOC

Order code

Order code

TZ-Silenzio

TZ-Silenzio with EASYLAB for room control and single operation

LABCONTROL

TZSilenzio D / 200 / ELAB / RS / ULZ / LAB / ...

EASYLAB

TZSilenzio D / 200 / ELAB / SC E0 / ULZ / ...

Type
TZ-Silenzio

VAV terminal unit, supply air

Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315

L
B
M
I
R

Equipment function
Room control
RS
Supply air control (Room Supply)
PC
Differential pressure control

Single operation
Supply air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
Volume flow rate constant value,
F
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
EM-TRF-USV for 230 V AC, provides
U
uninterruptible power supply (UPS)

Attachments (control component)


ELAB EASYLAB controller TCU3
with fast-running actuator

SC

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa]
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

K5 1.1 84

05/2015 DE/en

VAV terminal units

TOC

Order code

TZ-Silenzio

Order example

TZSilenzio/200/ELAB/RS/LAB

LABCONTROL

Acoustic cladding
Nominal size
Attachment
Equipment function
Additional function

EASYLAB

Order code

Without
200
EASYLAB controller TCU3 with fast-running actuator
Supply air control (Room Supply)
Extract air led system for laboratories

TZ-Silenzio with TCU-LON-II

LABCONTROL

TZSilenzio D / 200 / TMA / RS / -100 / -100

TCU-LON-II

Type
TZ-Silenzio

VAV terminal unit, supply air

Acoustic cladding
No entry: none
D
With acoustic cladding

Equipment function
Room supply air
RS
PS
Differential pressure control supply air
(Pressure Supply)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
PS: / constant / pSoll
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

Nominal size
125
160
200
250
315
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Order example

TZSilenzio-D/125/TMA/RS/100/400

LABCONTROL

Acoustic cladding

TCU-LON-II

Nominal size
Attachment
Equipment function
Operating values

05/2015 DE/en

With
125
TCU-LON-II with fast-running actuator
Supply air control (Room Supply)
Volume flow rate difference 100 m/h, constant volume flow rates 400 m/h

K5 1.1 85

VAV terminal units

TOC

Aerodynamic data

Volume flow rate ranges

TZ-Silenzio

Volume flow rate ranges and minimum differential pressure values

The minimum differential


pressure of VAV terminal
units is an important
factor in designing the
ductwork and in rating
the fan including
speed control.

Nominal size

Sufficient duct pressure


must be ensured for all
operating conditions
and for all control units.
he measurement points
for fan speed control must
be selected accordingly.

160

125

200

250

315

l/s

m/h
30
70
125
180
45
110
195
275
65
150
265
380
85
200
345
495
145
335
590
840

pst min
Pa

108
252
450
648
162
396
702
990
234
540
954
1368
306
720
1242
1782
522
1206
2124
3024

5
10
35
65
5
10
30
55
5
10
30
55
5
10
30
60
5
15
35
65

%
5
20
60
120
5
20
55
105
5
20
60
120
5
20
60
115
5
20
50
105

8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5

TZ-Silenzio
TZ-Silenzio with secondary silencer TS
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 86

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TZ-Silenzio

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

m/h
30
70
125
180
45
110
195
275
65
150
265
380
85
200
345
495
145
335
590
840

108
252
450
648
162
396
702
990
234
540
954
1368
306
720
1242
1782
522
1206
2124
3024

LPA

LPA1
15
26
34
39
15
27
34
37
13
23
29
32
14
23
28
32
15
23
28
32

Case-radiated noise

dB (A)
5
16
23
28
5
17
23
27
1
12
17
22
3
12
17
20
4
11
16
21

LPA2

LPA3
10
19
26
30
13
22
29
34
12
22
28
33
13
23
30
34
17
27
35
39

8
19
26
31
10
21
29
34
8
18
26
31
8
19
26
31
12
23
31
36

TZ-Silenzio
TZ-Silenzio with secondary silencer TS
TZ-Silenzio-D

05/2015 DE/en

K5 1.1 87

VAV terminal units

TOC

Dimensions and weight TZ-Silenzio


VAV terminal unit for the control
of variable supply air volume flows

Description

VAV terminal unit


Type TZ-Silenzio

TZ-Silenzio

Dimensions

20

20

M238FG1

30

M8

HB

TZ-Silenzio

Detail of flange

Compressible seal,
to be provided by others

~ 80

Air duct profile

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315

K5 1.1 88

H3

B3
1035
1035
1250
1250
1250

300
410
560
700
900

B1

mm
236
236
281
311
361

198
308
458
598
798

H
232
342
492
632
832

H1
152
152
210
201
252

m
kg
186
186
244
235
286

17
21
32
41
54

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TZ-Silenzio-D


Description

VAV terminal unit with acoustic cladding for


the control of variable supply air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The ducts for the room under consideration
must have adequate acoustic insulation
(to be provided by others) on the fan end
Acoustic cladding cannot be retrofitted

Dimensions

TZ-Silenzio-D

TZ-Silenzio

20

20

HB

30

M8

Detail of flange

Compressible seal,
to be provided by others

~ 80

Air duct profile

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315

05/2015 DE/en

H3

B3
1035
1035
1250
1250
1250

380
490
640
780
980

B1

mm
316
316
361
391
441

198
308
458
598
798

H
232
342
492
632
832

H1
152
152
210
201
252

m
kg
186
186
244
235
286

32
38
64
72
91

K5 1.1 89

VAV terminal units

TOC

Installation details
Bend, vertical

Junction, vertical

The volume flow rate


accuracy applies
to all upstream conditions.

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed in a branch just off the main duct.

Bend, horizontal

Junction, horizontal

A bend without a straight duct section upstream


of the VAV terminal unit has only a negligible
effect on the volume flow rate accuracy.

Upstream conditions

TZ-Silenzio

A bend without a straight duct section upstream


of the VAV terminal unit has only a negligible
effect on the volume flow rate accuracy.

K5 1.1 90

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed in a branch just off the main duct.

05/2015 DE/en

VAV terminal units

TOC

Installation details

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Access to attachments

Access to attachments

1
150

Space requirement
for commissioning
and maintenance

TZ-Silenzio

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Attachments

VARYCONTROL
Easy controller
700
Compact controller
700
Universal controller
700
LABCONTROL
EASYLAB
700

05/2015 DE/en

mm
300
300
300

300
300
300

350

400

K5 1.1 91

VAV terminal units

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular VAV terminal units for variable


and constant air volume systems for demanding
acoustic requirements, suitable for supply
or extract air, available in 5 nominal sizes.
High control accuracy even in case
of unfavourable upstream conditions.
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement, a damper blade, and an integral
attenuator. Factory-assembled control
components complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Both ends suitable for the connection
of air duct profiles.
Casing with acoustic and thermal insulation.
Position of the damper blade indicated
externally at shaft extension.
Closed blade air leakage to EN 1751, class 4.
Casing air leakage to EN 1751, class B.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.
Hygiene complies with VDI 6022, DIN 1946,
part 4, as well as EN 13779 and VDI 3803.
Special characteristics
Hygiene tested and certified
Direct connection of ducting
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary
Materials and surfaces
Casing made of galvanised sheet steel
Damper blade and differential
pressure sensor made of aluminium
Lining is mineral wool
Plastic bearings

TOC

TZ-Silenzio
Technical data
Nominal sizes: 125 315
Volume flow rate range:
30 to 840 l/s or 108 to 3024 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 10 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 65 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Clearly visible external indicator
light for signalling the functions:
Set, not set, and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Variant with acoustic cladding (-D)


Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

K5 1.1 92

05/2015 DE/en

VAV terminal units

Specification text
Order options

Type
TZ-Silenzio VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

05/2015 DE/en

TOC

TZ-Silenzio
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

K5 1.1 93

VAV terminal units

TOC

Specification text

Order options
LABCONTROL
EASYLAB

TZ-Silenzio

Type
TZ-Silenzio VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
PC
Differential pressure control
SC

Single operation
Supply air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa]
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

K5 1.1 94

05/2015 DE/en

VAV terminal units

Specification text
Order options
LABCONTROL
TCU-LON-II

Type
TZ-Silenzio VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315

TOC

TZ-Silenzio
Equipment function
RS
Room supply air
PS
Differential pressure control supply air
(Pressure Supply)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
PS: / constant / pSoll
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

05/2015 DE/en

K5 1.1 95

TA-Silenzio

TOC

1.1

X X TA-Silenzio testregistrierung

VAV terminal units

Type TA-Silenzio

For extract air systems with demanding acoustic


requirements and low airflow velocities

Rectangular connections
on both ends

Rectangular VAV terminal units for the extract air control in buildings with variable
air volume systems, demanding acoustic requirements and low airflow velocities
Highly effective integral attenuator
Optimised for airflow velocities of 0.7 6 m/s
High control accuracy even in case of unfavourable upstream conditions
Compact construction with rectangular connections on both ends
Electronic control components for different applications
(Easy, Compact, Universal, and LABCONTROL)
Closed blade air leakage to EN 1751, class 4

For all upstream conditions

Casing air leakage to EN 1751, class B


Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TS for the reduction of air-regenerated noise

H GE

TE

ET

HY

ISC

ST

EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 96

VAV terminal units

TOC

General information

TA-Silenzio
Page

Type

TA-Silenzio

Description

VAV terminal unit


Type TA-Silenzio
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TA-Silenzio
Dimensions and weight TA-Silenzio-D
Installation details
Specification text

1.1 97
1.1 100
1.1 103
1.1 104
1.1 105
1.1 106
1.1 107
1.1 109

Basic information and nomenclature

1.5 1

Application
VARYCONTROL VAV terminal units
of Type TA-Silenzio for the extract air flow
control in variable air volume systems
with low airflow velocities
Closed-loop volume flow control
using an external power supply
Integral attenuator for demanding
acoustic requirements
Shut-off by means of switching
(equipment supplied by others)
Variants
TA-Silenzio: Extract air unit
TA-Silenzio-D: Extract air unit
with acoustic cladding
Units with acoustic cladding
and/or secondary silencer Type TS
for very demanding acoustic requirements
Acoustic cladding cannot be retrofitted
Nominal sizes
125, 160, 200, 250, 315
Attachments
Easy controller:
Compact unit with potentiometers
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems
Useful additions
Secondary silencer Type TS
Special features
Hygiene tested and certified
Direct connection of ducting
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary

K5 1.1 97

Parts and characteristics


Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blade
Integral attenuator
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy even in case
of unfavourable upstream conditions
Construction features
Rectangular casing
Replaceable seals
Flanges on both ends
for connection to ductwork
Position of the damper blade
indicated externally at shaft extension
Thermal and acoustic insulation (lining)
Materials and surfaces
Casing made of galvanised sheet steel
Damper blade and differential
pressure sensor made of aluminium
Lining is mineral wool
Plastic bearings
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

05/2015 DE/en

VAV terminal units

TOC

General information

TA-Silenzio

Installation and commissioning


Any installation orientation (except units
with static differential pressure transducer)
Return edges of the casing with drilled holes
suitable for M10 threaded rods
TA-Silenzio-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller

Standards and guidelines


Hygiene conforms to VDI 6022
VDI 2083, air cleanliness class 3,
and US standard 209E, class 100
Closed blade air leakage to EN 1751, class 4
Meets the increased requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class B
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Attachments: VARYCONTROL control components for Type TA-Silenzio


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B13
B1B
XC3

Volume flow rate

Actuator

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Spring return actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BRG
BG3
BGB
XE1
XE3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Universal controller
TROX/Gruner

Static, integral

Universal controller with MP bus interface


TROX/Belimo
Differential pressure

Static

Universal controller
TROX/Belimo

Static, 100 Pa

Differential pressure controller


TROX/Belimo
Differential pressure controller
TROX/Gruner

Static, integral 100 Pa

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TA-Silenzio


Order code detail Control function
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Controller

Differential pressure transducer

Actuator

Room extract air


Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room extract air


Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Static, integral

05/2015 DE/en

Fast-running actuator
Fast-running actuator
(brushless motor)

K5 1.1 98

VAV terminal units

TOC

General information

Technical data

Function

TA-Silenzio

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

125 315
30 840 l/s or 108 3024 m/h
Approx. 10 to 100 % of the nominal volume flow rate
5 65 Pa
1000 Pa
10 50 C

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow
rate. The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator; the control
functions can be achieved with an Easy controller,
with a Compact controller, or with individual
components (Universal). For most applications,
the setpoint value comes from a room
temperature controller. The controller compares
the actual value with the setpoint value
and alters the control signal of the actuator
if there is a difference between the two values.
An integral attenuator reduces the noise
that is created by the restriction of the airflow.

Schematic illustration of the TA-Silenzio

Differential pressure sensor


Indicator light

K5 1.1 99

Control components, e.g. an Easy controller


Damper blade with seal

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TA-Silenzio

TA-Silenzio, TA-Silenzio/.../Easy

VARYCONTROL

TASilenzio D / 200 / B1B / E 0 / 400 1200 / NO

TASilenzio D / 200 / Easy

Type
TA-Silenzio

VAV terminal unit, extract air

Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

Order example

TA-Silenzio/250/BC0/M0/5001500 m/h

VARYCONTROL

Acoustic cladding
Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rate

05/2015 DE/en

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting (operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

Without
250
Compact controller
Master
0 10 V DC
500 1500 m/h

K5 1.1 100

VAV terminal units

TOC

Order code

Order code

TA-Silenzio

TA-Silenzio with EASYLAB for room control and single operation

LABCONTROL

TASilenzio D / 200 / ELAB / RE / ULZ / LAB / ...

EASYLAB

TASilenzio D / 200 / ELAB / EC E0 / ULZ / ...

Type
TA-Silenzio

VAV terminal unit, extract air

Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315

L
B
M
I
R

Equipment function
Room control
RE
Extract air control (Room Exhaust)
PC
Differential pressure control

Single operation
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Attachments (control component)


ELAB EASYLAB controller TCU3
with fast-running actuator

EC

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa]
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

K5 1.1 101

05/2015 DE/en

VAV terminal units

TOC

Order code

TA-Silenzio

Order example

TASilenzio/200/ELAB/EC/E0/300-1000

LABCONTROL

Acoustic cladding
Nominal size
Attachment
Equipment function
External volume flow rate setting
Operating values

EASYLAB

Order code

Without
200
EASYLAB controller TCU3 with fast-running actuator
Extract air controller
Voltage signal 0 10 V DC
300 1000 m/h

TA-Silenzio with TCU-LON-II

LABCONTROL

TASilenzio D / 200 / TMA / RE / 1200 / 750 / 100

TCU-LON-II

Type
TA-Silenzio

VAV terminal unit, extract air

Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315

Equipment function
Room extract air
RE
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RE: day / night / constant
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Order example

TASilenzio-D/200/TMB/RE/1200/750/100

LABCONTROL

Acoustic cladding
Nominal size
Attachment
Equipment function

TCU-LON-II

Operating values

05/2015 DE/en

With
200
TCU-LON-II with fast-running actuator (brushless motor)
Room extract air
Total extract air day-time operation 1200 m/h,
total extract air night-time operation 750 m/h,
constant volume flow rate 100 m/h

K5 1.1 102

VAV terminal units

TOC

Aerodynamic data

Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including speed
control.
Sufficient duct pressure
must be ensured for all
operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TA-Silenzio

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

315

Nominal size

m/h
30
70
125
180
45
110
195
275
65
150
265
380
85
200
345
495
145
335
590
840

pst min
Pa

108
252
450
648
162
396
702
990
234
540
954
1368
306
720
1242
1782
522
1206
2124
3024

5
10
35
65
5
10
30
55
5
10
30
55
5
10
30
60
5
15
35
65

%
5
20
60
120
5
20
55
105
5
20
60
120
5
20
60
115
5
20
50
105

8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5

TA-Silenzio
TA-Silenzio with secondary silencer TS
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 103

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TA-Silenzio

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

m/h
30
70
125
180
45
110
195
275
65
150
265
380
85
200
345
495
145
335
590
840

108
252
450
648
162
396
702
990
234
540
954
1368
306
720
1242
1782
522
1206
2124
3024

LPA

LPA1
13
23
30
33
14
25
30
33
13
22
26
29
14
22
26
29
16
22
26
29

Case-radiated noise

dB(A)
3
13
21
26
4
14
21
26
0
10
16
21
2
10
15
19
3
9
14
20

LPA2

LPA3
10
19
26
30
13
22
29
34
12
22
28
33
13
23
30
34
17
27
35
39

8
19
26
31
10
21
29
34
8
18
26
31
8
19
26
31
12
23
31
36

TA-Silenzio
TA-Silenzio with secondary silencer TS
TA-Silenzio-D

05/2015 DE/en

K5 1.1 104

VAV terminal units

TOC

Dimensions and weight TA-Silenzio


VAV terminal unit for the control
of variable extract air volume flows

Description

VAV terminal unit


Type TA-Silenzio

TA-Silenzio

Dimensions

20

20

M238FG1

30

M8

HB

TA-Silenzio

Detail of flange

Compressible seal,
to be provided by others

~ 80

Air duct profile

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315

K5 1.1 105

H3

B3
1035
1035
1250
1250
1250

300
410
560
700
900

B1

mm
236
236
281
311
361

198
308
458
598
798

H
232
342
492
632
832

H1
152
152
210
201
252

m
kg
186
186
244
235
286

17
21
32
41
54

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TA-Silenzio-D


Description

VAV terminal unit with acoustic cladding for


the control of variable extract air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The ducts for the room under consideration
must have adequate acoustic insulation
(to be provided by others) on the fan end
Acoustic cladding cannot be retrofitted

Dimensions

TA-Silenzio-D

TA-Silenzio

20

20

HB

30

M8

Detail of flange

Compressible seal,
to be provided by others

~ 80

Air duct profile

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315

05/2015 DE/en

H3

B3
1035
1035
1250
1250
1250

380
490
640
780
980

B1

mm
316
316
361
391
441

198
308
458
598
798

H
232
342
492
632
832

H1
152
152
210
201
252

m
kg
186
186
244
235
286

32
38
64
72
91

K5 1.1 106

VAV terminal units

TOC

Installation details
Bend, vertical

Convergence of two airflows, vertical

The volume flow rate


accuracy applies
to all upstream conditions.

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed at a junction and at the point
of convergence of two airflows.

Bend, horizontal

Convergence of two airflows, horizontal

A bend without a straight duct section upstream


of the VAV terminal unit has only a negligible
effect on the volume flow rate accuracy.

Upstream conditions

TA-Silenzio

A bend without a straight duct section upstream


of the VAV terminal unit has only a negligible
effect on the volume flow rate accuracy.

K5 1.1 107

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed at a junction and at the point
of convergence of two airflows.

05/2015 DE/en

VAV terminal units

TOC

Installation details

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Access to attachments

Access to attachments

1
150

Space requirement
for commissioning
and maintenance

TA-Silenzio

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Attachments

VARYCONTROL
Easy controller
700
Compact controller
700
Universal controller
700
LABCONTROL
EASYLAB
700

05/2015 DE/en

mm
300
300
300

300
300
300

350

400

K5 1.1 108

VAV terminal units

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular VAV terminal units for variable


and constant air volume systems for demanding
acoustic requirements, suitable for extract air,
available in 5 nominal sizes.
High control accuracy even in case
of unfavourable upstream conditions.
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement, a damper blade, and an integral
attenuator. Factory-assembled control
components complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Both ends suitable for the connection
of air duct profiles.
Casing with acoustic and thermal insulation.
Position of the damper blade indicated
externally at shaft extension.
Closed blade air leakage to EN 1751, class 4.
Casing air leakage to EN 1751, class B.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.
Hygiene complies with VDI 6022, DIN 1946,
part 4, as well as EN 13779 and VDI 3803.
Special features
Hygiene tested and certified
Direct connection of ducting
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Materials and surfaces
Casing made of galvanised sheet steel
Damper blade and differential
pressure sensor made of aluminium
Lining is mineral wool
Plastic bearings

TOC

TA-Silenzio
Technical data
Nominal sizes: 125 315
Volume flow rate range:
30 to 840 l/s or 108 to 3024 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 10 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 65 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Clearly visible external indicator
light for signalling the functions:
Set, not set, and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Variant with acoustic cladding (-D)


Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

K5 1.1 109

05/2015 DE/en

VAV terminal units

Specification text
Order options
VARYCONTROL

Type
TA-Silenzio VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

05/2015 DE/en

TOC

TA-Silenzio
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

K5 1.1 110

VAV terminal units

TOC

Specification text

Order options
LABCONTROL
EASYLAB

TA-Silenzio

Type
TA-Silenzio VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
EC

Single operation
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point
correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa]
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

K5 1.1 111

05/2015 DE/en

VAV terminal units

Specification text
Order options
LABCONTROL
TCU-LON-II

Type
TA-Silenzio VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size
125
160
200
250
315

TOC

TA-Silenzio
Equipment function
RE
Room extract air
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RE: day / night / constant
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

05/2015 DE/en

K5 1.1 112

TVZ

TOC

1.1

X X TVZtestregistrierung

VAV terminal units

Type TVZ
Easy controller

Compact controller

Rectangular connection
on the room end

For supply air systems with demanding


acoustic requirements
VAV terminal units for the supply air control in buildings
with variable air volume systems and demanding acoustic requirements
Highly effective integral attenuator
Box style construction for the reduction of the airflow velocity
Electronic control components for different applications
(Easy, Compact, Universal, and LABCONTROL)
Suitable for airflow velocities up to 13 m/s
Closed blade air leakage to EN 1751, up to class 4
Casing air leakage to EN 1751, class A

Circular connection
on the fan end

Secondary silencer Type TS for the reduction of air-regenerated noise


Hot water heat exchanger of Type WT for reheating the airflow

ET

HY

SCH GET
E

ST

I
EN

Optional equipment and accessories


Acoustic cladding for the reduction of case-radiated noise

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 113

VAV terminal units

TOC

General information

TVZ
Page

Type

TVZ

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVZ
Dimensions and weight TVZ-D
Installation details
Specification text

1.1 114
1.1 118
1.1 121
1.1 122
1.1 123
1.1 124
1.1 125
1.1 127

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVZ

VAV terminal unit, variant TVZ-D

Application
VARYCONTROL VAV terminal units
of Type TVZ for the supply air control
in variable air volume systems
Closed-loop volume flow control
using an external power supply
Integral attenuator for demanding
acoustic requirements
Shut-off by means of switching
(equipment supplied by others)

Useful additions
Secondary silencer Type TS
Heat exchanger Type WT

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
TVZ: Supply air unit
TVZ-D: Supply air unit with acoustic cladding
Units with acoustic cladding
and/or secondary silencer Type TS
for very demanding acoustic requirements
Acoustic cladding cannot be retrofitted
Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Easy controller: Compact unit consisting
of controller with potentiometers,
differential pressure transducer and actuator
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems

Special characteristics
Integral attenuator with at least 26 dB
insertion loss at 250 Hz
Hygiene tested and certified
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Inspection access for cleaning to VDI 6022
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blade
Integral attenuator
Inspection access
Factory assembled control components
complete with wiring and tubing
Aerodynamic functional testing on a special
test rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy
(even with upstream bend R = 1D)

Accessories
Lip seal (factory fitted)

K5 1.1 114

05/2015 DE/en

VAV terminal units

TOC

General information

TVZ

Construction features
Rectangular casing
Spigot on the fan end suitable
for circular ducts to EN 1506 or EN 13180
Spigot with groove for lip seal
Connection on the room end suitable
for air duct profiles
Baffle plate is fitted after the damper blade
for optimum aerodynamic performance
Position of the damper blade indicated
externally at shaft extension
Thermal and acoustic insulation (lining)

Standards and guidelines


Hygiene conforms to VDI 6022
VDI 2083, air cleanliness class 3,
and US standard 209E, class 100
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 125 and 160, class 3)
Nominal sizes 125 and 160 meet the general
requirements, nominal sizes 200 400 meet
the increased requirements of DIN 1946,
part 4, with regard to the acceptable
closed blade air leakage
Casing air leakage to EN 1751, class A

Materials and surfaces


Casing and damper blade
made of galvanised sheet steel
Damper blade seal made of TPE plastic
Lining is mineral wool
Differential pressure sensor made of aluminium
Plastic bearings

Maintenance
Maintenance-free as construction
and materials are not subject to wear

Variant with acoustic cladding (-D)


Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth
Installation and commissioning
Any installation orientation (except units
with static differential pressure transducer)
Return edges of the casing with drilled
holes suitable for M10 threaded rods
TVZ-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller

05/2015 DE/en

K5 1.1 115

VAV terminal units

TOC

General information

TVZ

Attachments: VARYCONTROL control components for Type TVZ


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B13
B1B

Volume flow rate

XC3

Actuator
Spring return actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BRG
BG3
BGB
XE1
XE3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Universal controller
TROX/Gruner

Static, integral

Universal controller with MP bus interface


TROX/Belimo
Differential pressure

Static

Universal controller
TROX/Belimo

Static, 100 Pa

Differential pressure controller


TROX/Belimo
Differential pressure controller
TROX/Gruner

Static, integral 100 Pa

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TVZ


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Room supply air


Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room supply air


Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Static, integral

EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Technical data

K5 1.1 116

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

Fast-running actuator
Fast-running actuator
(brushless motor)

125 400 mm
15 1680 l/s or 54 6048 m/h
Approx. 10 100 % of the nominal volume flow rate
5 80 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information
Function

TVZ

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow
rate. The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator; the control functions
can be achieved with an Easy controller,
with a Compact controller, or with individual
components (Universal or LABCONTROL).
For most applications, the setpoint value
comes from a room temperature controller.
The controller compares the actual value
with the setpoint value and alters the control
signal of the actuator if there is a difference
between the two values. An integral attenuator
reduces the noise that is created by the restriction
of the airflow. The airflow velocity at the room
end is, due to the larger rectangular cross section,
about half the velocity in the circular duct.

Schematic illustration of the TVZ

Differential pressure sensor


Lip seal
Inspection access

05/2015 DE/en

Damper blade
Integral attenuator
Control components, e.g. an Easy controller

K5 1.1 117

VAV terminal units

TOC

Order code

Order code

TVZ

TVZ, TVZ/.../Easy

VARYCONTROL

TVZ D / 160 / D1 / B1B / E 0 / 200 900 / NO

TVZ D / 160 / D1 / Easy

Type
TVZ VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller
Order example

TVZ-D/160/D1/BC0/E0/180850 m/h

VARYCONTROL

Acoustic cladding
Nominal size
Accessories
Attachment
Operating mode
Signal voltage range
Volume flow rate

K5 1.1 118

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting (operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

With
160 mm
Lip seal
Compact controller
Single
0 10 V DC
180 850 m/h

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TVZ

TVZ with EASYLAB for room control and single operation

LABCONTROL

TVZ D / 160 / D1 / ELAB / RS / ULZ / LAB / ...

EASYLAB

TVZ D / 160 / D1 / ELAB / SC E0 / ULZ / ...

Type
TVZ VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
ELAB EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
PC
Differential pressure control
SC

Single operation
Supply air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
EM-TRF-USV for 230 V AC, provides uninU
terruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

05/2015 DE/en

K5 1.1 119

VAV terminal units

TOC

Order code

TVZ

Order example

TVZ/200/ELAB/RS/CLR-RMF/3500/1000/5000/250/0/-150

LABCONTROL

Acoustic cladding
Nominal size
Attachment
Equipment function
Additional functions

EASYLAB

Without
200 mm
EASYLAB controller TCU3 with fast-running actuator
Supply air control (Room Supply)
Supply air led system
Total supply air standard mode 3500 m/h
Reduced operation 1000 m/h
Increased operation 5000 m/h
Constant supply air 250 m/h Constant extract air 0
Supply air/extract air difference 150 m/h

Operating values

Order code

TVZ with TCU-LON-II

LABCONTROL

TVZ D / 160 / D1 / TMA / RS / -100 / -100

TCU-LON-II

Type
TVZ VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
Room supply air
RS
PS
Differential pressure control supply air
(Pressure Supply)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
PS: / constant / pSoll
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

Order example

TVZ/200/TMA/PS/-120/-300

LABCONTROL

Acoustic cladding

Without

TCU-LON-II

Nominal size

200 mm

Attachment
Equipment function

K5 1.1 120

TCU-LON-II with fast-running actuator


Differential pressure control supply air (Pressure Supply)

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for all
operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVZ

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

315

400

Nominal size

m/h
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
100
410
720
1030
170
670
1175
1680

Pa
54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
360
1476
2592
3708
612
2412
4230
6048

pst min
5
15
45
90
5
15
40
80
5
15
40
80
5
15
40
80
5
15
40
80
5
15
40
80

Pa

%
5
25
65
130
5
20
50
100
5
20
50
100
5
20
50
100
5
20
60
120
5
20
60
120

19
8
7
5
19
8
7
5
19
8
7
5
19
8
7
5
19
8
7
5
19
8
7
5

TVZ
TVZ with secondary silencer TS
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 121

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVZ

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

400

m/h
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
105
410
720
1030
170
670
1175
1680

54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
378
1476
2592
3708
612
2412
4230
6048

LPA

LPA1
17
24
29
34
18
28
35
36
16
21
23
31
16
17
22
31
18
21
24
29
17
19
26
32

Case-radiated noise

dB(A)
16
20
24
29
16
24
29
30
<15
17
17
24
15
<15
15
21
15
16
18
22
<15
15
20
27

LPA2

LPA3
21
24
27
32
20
25
29
35
22
27
31
39
22
26
29
37
21
27
33
38
25
29
33
43

<15
16
19
23
<15
18
21
27
15
20
23
31
16
19
22
28
15
19
24
29
17
20
25
35

TVZ
TVZ with secondary silencer TS
TVZ-D

K5 1.1 122

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVZ

TVZ

VAV terminal unit for the control


of variable supply air volume flows

Description

VAV terminal unit,


variant TVZ

TVZ

Dimensions

Detail of flange

20

20

50

~ 80

Compressible seal,
to be provided by others

Air duct profile

HB

30

M8

Inspection access

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

05/2015 DE/en

D
124
159
199
249
314
399

L
1185
1235
1520
1690
1690
2070

B3
300
410
560
700
900
1000

H3
236
236
281
311
361
446

B
mm
198
308
458
598
798
898

B1
232
342
492
632
832
932

H
152
152
210
201
252
354

H1
186
186
244
235
286
388

m
kg

150
200
200
250
250
250

115
115
115
215
215
215

21
25
33
55
73
118

K5 1.1 123

VAV terminal units

TOC

Dimensions and weight TVZ-D


VAV terminal unit with acoustic cladding for
the control of variable supply air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others) on the fan end
Acoustic cladding cannot be retrofitted

Description

VAV terminal unit,


variant TVZ-D

TVZ-D

Dimensions

L
B

20

20

Detail of flange

50

Compressible seal,
to be provided by others

~ 80
W

M8

Air duct profile

30

HB

TVZ

Inspection access

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

K5 1.1 124

D
124
159
199
249
314
399

L
1185
1235
1520
1690
1690
2070

B3
380
490
640
780
980
1080

H3
316
316
361
391
441
526

B
mm
198
308
458
598
798
898

B1
232
342
492
632
832
932

H
152
152
210
201
252
354

H1
186
186
244
235
286
388

m
kg

110
160
160
210
210
210

155
155
155
255
255
255

41
50
63
95
133
193

05/2015 DE/en

VAV terminal units

TOC

Installation details

05/2015 DE/en

1
D

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Junction

Bend

1D

Upstream conditions

TVZ

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

5D

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require
a perforated plate in the branch and before the
VAV terminal unit. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

K5 1.1 125

VAV terminal units

TOC

Installation details
Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Inspection access

Space required
Attachments

Space required

mm

VARYCONTROL
Easy controller
400
Compact controller
400
Universal controller
700
LABCONTROL
EASYLAB
900
TCU-LON-II
700

300
300
300

300
300
300

350
300

400
300

Part
Inspection access

mm
400

300

300

Access to attachments

150

Space requirement
for commissioning
and maintenance

TVZ

25
0
250

Separate space for fixing and accessing


the battery pack (LABCONTROL EASYLAB accessory)

K5 1.1 126

05/2015 DE/en

VAV terminal units

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular VAV terminal units for variable


and constant air volume systems,
suitable for supply air, available in 6 nominal sizes.
High control accuracy
(even with upstream bend R = 1D).
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement, a damper blade, and an integral
attenuator. Factory-assembled control
components complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
On the fan end, spigot with groove for lip seal,
suitable for connecting ducts according
to EN 1506 or EN 13180.
Room end suitable for the connection
of air duct profiles.
Baffle plate is fitted after the damper blade for
optimum acoustic and aerodynamic performance.
Casing with acoustic and thermal insulation.
Position of the damper blade indicated
externally at shaft extension.
Closed blade air leakage to EN 1751, class 4
(nominal sizes 125 and 160, class 3).
Casing air leakage to EN 1751, class B.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.
Hygiene complies with VDI 6022, DIN 1946,
part 4, as well as EN 13779 and VDI 3803.
Special characteristics
Integral attenuator with at least 26 dB
insertion loss at 250 Hz
Hygiene tested and certified
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Inspection access for cleaning to VDI 6022
Materials and surfaces
Casing and damper blade
made of galvanised sheet steel
Damper blade seal made of TPE plastic
Lining is mineral wool
Differential pressure sensor made of aluminium
Plastic bearings
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise

05/2015 DE/en

TOC

TVZ
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth
Technical data
Nominal sizes: 125 to 400 mm
Volume flow rate range:
15 to 1680 l/s or 54 to 6048 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 10 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 80 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Clearly visible external indicator light
for signalling the functions:
Set, not set, and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

K5 1.1 127

VAV terminal units

TOC

Specification text

Order options
VARYCONTROL

Type
TVZ
VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

K5 1.1 128

TVZ
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Z
Differential pressure control supply air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

TVZ

Type
TVZ
VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RS
Supply air control (Room Supply)
PC
Differential pressure control
SC

Single operation
Supply air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

05/2015 DE/en

K5 1.1 129

VAV terminal units

Specification text

Order options
LABCONTROL
TCU-LON-II

Type
TVZ
VAV terminal unit, supply air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal

K5 1.1 130

TOC

TVZ
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
RS
Room supply air
PS
Differential pressure control supply air
(Pressure Supply)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RS: / constant
PS: / constant / pSoll
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

05/2015 DE/en

TVA

TOC

1.1

X X TVA testregistrierung

VAV terminal units

Type TVA
Easy controller

Compact controller

For extract air systems with demanding


acoustic requirements
VAV terminal units for the extract air control in buildings
with variable air volume systems and demanding acoustic requirements
Highly effective integral attenuator

Circular connection
on the fan end

Box style construction for the reduction of the airflow velocity


Electronic control components for different applications
(Easy, Compact, Universal, and LABCONTROL)
Suitable for airflow velocities up to 13 m/s
Closed blade air leakage to EN 1751, class 4
Casing air leakage to EN 1751, class A
Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise

Rectangular connection
on the room end

H GE

TE

ET

HY

ISC

ST

EN

Secondary silencer Type TS for the reduction of air-regenerated noise

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 131

VAV terminal units

TOC

General information

TVA
Page

Type

TVA

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVA
Dimensions and weight TVA-D
Installation details
Specification text

1.1 132
1.1 136
1.1 139
1.1 140
1.1 141
1.1 142
1.1 143
1.1 145

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVA

VAV terminal unit, variant TVA-D

Application
VARYCONTROL VAV terminal units
of Type TVA for the extract air flow control
in variable air volume systems
Closed-loop volume flow control
using an external power supply
Integral attenuator for demanding
acoustic requirements
Shut-off by means of switching
(equipment supplied by others)

Useful additions
Secondary silencer Type TS

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
TVA: Extract air unit
TVA-D: Extract air unit with acoustic cladding
Units with acoustic cladding and/or
secondary silencer Type TS
for very demanding acoustic requirements
Acoustic cladding cannot be retrofitted
Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Easy controller: Compact unit consisting
of controller with potentiometers,
differential pressure transducer and actuator
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems

Special features
Integral attenuator with at least 26 dB
insertion loss at 250 Hz
Hygiene tested and certified
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blade
Integral attenuator
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy even in case
of unfavourable upstream conditions

Accessories
Lip seal (factory fitted)

K5 1.1 132

05/2015 DE/en

VAV terminal units

TOC

General information

TVA

Construction features
Rectangular casing
Spigot on the fan end suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
Connection on the room end suitable
for air duct profiles
Baffle plate is fitted after the damper blade
for optimum aerodynamic performance
Position of the damper blade indicated
externally at shaft extension
Thermal and acoustic insulation (lining)

Standards and guidelines


Hygiene conforms to VDI 6022
VDI 2083, air cleanliness class 3,
and US standard 209E, class 100
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 125 and 160, class 3).
Nominal sizes 125 and 160 meet the general
requirements, nominal sizes 200 400 meet
the increased requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class A

Materials and surfaces


Casing and damper blade made of galvanised
sheet steel
Damper blade seal made of TPE plastic
Lining is mineral wool
Differential pressure sensor made of aluminium
Plastic bearings

Maintenance
Maintenance-free as construction
and materials are not subject to wear

Variant with acoustic cladding (-D)


Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth
Installation and commissioning
Any installation orientation (except units
with static differential pressure transducer)
Return edges of the casing with drilled holes
suitable for M10 threaded rods
TVA-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller

05/2015 DE/en

K5 1.1 133

VAV terminal units

TOC

General information

TVA

Attachments: VARYCONTROL control components for Type TVA


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Easy controller
TROX

Dynamic, integral

Integral

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller with LonWorks interface
TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Dynamic, integral

Easy controller
Easy
Compact controller
BC0
BL0
XB0
LN0
Universal controller, dynamic
B13
B1B

Volume flow rate

XC3

Actuator
Spring return actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BRG
BS3
BG3
BGB
XE1
XE3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Static

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Static, integral

Universal controller with MP bus interface


TROX/Belimo
Differential pressure

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator

Static, 100 Pa

Actuator

Differential pressure controller


TROX/Belimo
Differential pressure controller
TROX/Gruner

Static, integral 100 Pa

Spring return actuator


Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TVA


Order code detail Control function
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Controller

Differential pressure transducer

Actuator

Room extract air


Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room extract air


Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Static, integral

Technical data

K5 1.1 134

Nominal sizes
Volume flow rate range
Volume flow rate control range
(unit with dynamic differential pressure measurement)
Minimum differential pressure
Maximum differential pressure
Operating temperature

Fast-running actuator
Fast-running actuator
(brushless motor)

125 400 mm
15 1680 l/s or 54 6048 m/h
Approx. 10 to 100 % of the nominal volume flow rate
5 190 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information
Function

TVA

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow
rate. The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator; the control functions
can be achieved with an Easy controller,
with a Compact controller, or with individual
components (Universal or LABCONTROL).
For most applications, the setpoint value
comes from a room temperature controller.
The controller compares the actual value
with the setpoint value and alters the control
signal of the actuator if there is a difference
between the two values. An integral attenuator
reduces the noise that is created by the restriction
of the airflow. The airflow velocity at the room end
is, due to the larger rectangular cross section,
about half the velocity in the circular duct.

Schematic illustration of the TVA

Integral attenuator
Lip seal
Damper blade

05/2015 DE/en

Differential pressure sensor


Control components, e.g. an Easy controller

K5 1.1 135

VAV terminal units

TOC

Order code

Order code

TVA

TVA, TVA/.../Easy

VARYCONTROL

TVA D / 160 / D1 / B1B / E 0 / 200 900 / NO

TVA D / 160 / D1 / Easy

Type
TVA VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller
Order example

TVA-D/160/D1/BC0/E0/200800 m/h

VARYCONTROL

Acoustic cladding
Nominal size
Accessories
Attachment
Operating mode
Signal voltage range
Volume flow rate

K5 1.1 136

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting (operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

With
160 mm
Lip seal
Compact controller
Single
0 10 V DC
200 800 m/h

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TVA

TVA with EASYLAB for room control and single operation

LABCONTROL

TVA D / 160 / D1 / ELAB / RE / ULZ / LAB / ...

EASYLAB

TVA D / 160 / D1 / ELAB / EC E0 / ULZ / ...

Type
TVA VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
ELAB EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
EC

Single operation
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01
40-character display

05/2015 DE/en

K5 1.1 137

VAV terminal units

TOC

Order code

TVA

Order example

TVA/200/ELAB/RE/TZ/CLR

LABCONTROL

Acoustic cladding
Nominal size
Attachment
Equipment function

Without
200 mm
EASYLAB controller TCU3 with fast-running actuator
Extract air control (Room Exhaust)

Module expansions

EM-TRF for 230 V AC,


EM-AUTOZERO Solenoid valve for automatic zero point correction

Additional function

Supply air led system (clean rooms), room management function is active

EASYLAB

Order code

TVA with TCU-LON-II

LABCONTROL

TVA D / 160 / D1 / TMA / RE / 1500 / 750/ 100

TCU-LON-II

Type
TVA VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal

Order example

TVA-D/400/D1/TMB/PE/1500/750/250/20

LABCONTROL

Acoustic cladding
Nominal size
Accessories
Attachment

TCU-LON-II

Equipment function
Operating values

K5 1.1 138

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
Room extract air
RE
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RE: day / night / constant
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

With
400 mm
Lip seal
TCU-LON-II with fast-running actuator (brushless motor)
Differential pressure control extract air (Pressure Extract)
Total room extract air day-time operation 1500 m/h,
total room extract air night-time operation 750 m/h,
constant volume flow rate 100 m/h,
pressure setpoint value 20 Pa

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVA

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

315

400

Nominal size

m/h
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
100
410
720
1030
170
670
1175
1680

Pa

54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
360
1476
2592
3708
612
2412
4230
6048

5
25
75
150
5
25
75
150
5
30
95
190
5
25
75
150
5
30
90
180
5
25
75
150

pst min

%
5
35
95
190
5
30
85
170
5
35
105
210
5
30
85
170
5
35
110
220
5
35
95
190

19
8
7
5
19
8
7
5
19
8
7
5
19
8
7
5
19
8
7
5
19
8
7
5

TVA
TVA with secondary silencer TS
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 139

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVA

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

400

m/h
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
105
410
720
1030
170
670
1175
1680

54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
378
1476
2592
3708
612
2412
4230
6048

LPA

LPA1
18
24
26
25
16
28
28
23
15
20
23
26
16
19
20
27
17
26
25
27
16
18
23
32

Case-radiated noise

dB(A)
16
21
23
25
15
23
23
22
<15
17
18
25
<15
16
18
27
15
21
22
27
<15
<15
19
29

LPA2

LPA3
15
26
30
33
15
24
29
32
16
24
30
32
15
25
29
33
15
28
34
37
17
32
37
42

<15
21
25
27
<15
20
24
27
<15
20
25
27
<15
20
24
28
<15
23
29
32
<15
26
32
38

TVA
TVA with secondary silencer TS
TVA-d

K5 1.1 140

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVA

TVA

VAV terminal unit for the control


of variable extract air volume flows

Description

VAV terminal unit,


variant TVA

TVA

Dimensions

20

HB

30

20

50

~ 80

Detail of flange

Compressible seal,
to be provided by others
Air duct profile

M8

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

05/2015 DE/en

D
124
159
199
249
314
399

L
1220
1205
1460
1540
1685
1995

B3
300
410
560
700
900
1000

H3
236
236
281
311
361
446

B
mm
198
308
458
598
798
898

B1
232
342
492
632
832
932

H1
152
152
210
201
252
354

m
kg

186
186
244
235
286
388

185
170
138
97
245
176

21
25
33
55
73
118

K5 1.1 141

VAV terminal units

TOC

Dimensions and weight TVA-D


VAV terminal unit with acoustic cladding for
the control of variable extract air volume flows
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others) on the fan end
Acoustic cladding cannot be retrofitted

Description

VAV terminal unit,


variant TVA-D

TVA-D

Dimensions

20

20

30

Detail of flange

HB

~ 80

50

Compressible seal,
to be provided by others
Z

M8

Air duct profile

TVA

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

K5 1.1 142

D
124
159
199
249
314
399

L
1220
1205
1460
1540
1685
1995

B3
380
490
640
780
980
1080

H3
316
316
361
391
441
526

B
mm
198
308
458
598
798
898

B1
232
342
492
632
832
932

H1
152
152
210
201
252
354

186
186
244
235
286
388

m
kg
145
130
98
57
205
136

41
50
63
95
133
193

05/2015 DE/en

VAV terminal units

TOC

Installation details

Convergence of two airflows, vertical

A bend without a straight duct section upstream


of the VAV terminal unit has only a negligible
effect on the volume flow rate accuracy.

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed at a junction and at the point
of convergence of two airflows.

Bend, horizontal

Convergence of two airflows, horizontal

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend, vertical

Upstream conditions

TVA

A bend without a straight duct section upstream


of the VAV terminal unit has only a negligible
effect on the volume flow rate accuracy.

05/2015 DE/en

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed at a junction and at the point
of convergence of two airflows.

K5 1.1 143

VAV terminal units

TOC

Installation details

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Access to attachments

Access to attachments

150

Space requirement
for commissioning
and maintenance

TVA

25
0

250

Separate space for fixing


and accessing the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Attachments

VARYCONTROL
Easy controller
400
Compact controller
400
Universal controller
700
LABCONTROL
EASYLAB
900
TCU-LON-II
700

K5 1.1 144

mm
300
300
300

300
300
300

350
300

400
300

05/2015 DE/en

VAV terminal units

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular VAV terminal units for variable


and constant air volume systems,
suitable for extract air, available in 6 nominal sizes.
High volume flow rate control accuracy.
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement, a damper blade, and an integral
attenuator. Factory-assembled control
components complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
On the fan end, spigot with groove for lip seal,
suitable for connecting ducts to EN 1506
or EN 13180.
Room end suitable for the connection
of air duct profiles.
Baffle plate is fitted after the damper blade for
optimum acoustic and aerodynamic performance.
Casing with acoustic and thermal insulation.
Position of the damper blade indicated externally
at shaft extension.
Closed blade air leakage to EN 1751, class 4
(nominal sizes 125 and 160, class 3).
Casing air leakage to EN 1751, class B.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.
Hygiene complies with VDI 6022, DIN 1946,
part 4, as well as EN 13779 and VDI 3803.
Special features
Integral attenuator with at least 26 dB
insertion loss at 250 Hz
Hygiene tested and certified
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Materials and surfaces
Casing and damper blade made of galvanised
sheet steel
Damper blade seal made of TPE plastic
Lining is mineral wool
Differential pressure sensor made of aluminium
Plastic bearings
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise

05/2015 DE/en

TOC

TVA
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth
Technical data
Nominal sizes: 125 to 400 mm
Volume flow rate range:
15 to 1680 l/s or 54 to 6048 m/h
Volume flow rate control range (unit with
dynamic differential pressure measurement):
approx. 10 to 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 190 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic Easy
controller to connect an external control signal;
actual value signal can be integrated
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Potentiometers with percentage scales
to set the volume flow rates min and max
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Clearly visible external indicator
light for signalling the functions:
Set, not set, and power failure
Electrical connections with screw terminals.
Double terminals for looping the supply voltage,
i.e. for the simple connection of voltage
transmission to the next controller.
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

K5 1.1 145

VAV terminal units

TOC

Specification text

Order options
VARYCONTROL

Type
TVA
VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
Example
Easy Easy controller
BC0 Compact controller
B13 Universal controller

K5 1.1 146

TVA
Operating mode
E
Single
M
Master
S
Slave
F
Constant value
A
Differential pressure control extract air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s],
differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating mode A)
Damper blade position
Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

TVA

Type
TVA
VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
EC

Single operation
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
BE-LCD-01 40-character display

05/2015 DE/en

K5 1.1 147

VAV terminal units

Specification text

Order options
LABCONTROL
TCU-LON-II

Type
TVA
VAV terminal unit, extract air
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
D1
Lip seal

K5 1.1 148

TOC

TVA
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
RE
Room extract air
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
RE: day / night / constant
PE: day / night / constant / psetpoint
The room control volume flow rates
are related to the total extract air volume
flow rate for the room

05/2015 DE/en

TVM

TOC

1.1

X X TVMtestregistrierung

VAV terminal units

Type TVM

Variant TVM-S

For dual duct systems


VAV dual duct terminal units for dual duct systems
with variable volume flows in buildings with demanding acoustic requirements
Individual temperature control for each room or zone
Highly effective integral attenuator
Rectangular connection
on the room end

Electronic control components for different applications


(Compact and Universal)
Suitable for airflow velocities up to 13 m/s
Closed blade air leakage to EN 1751, up to class 4
Casing air leakage to EN 1751, class A
Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TS for the reduction of air-regenerated noise

Circular connection
on the fan end

H GE

TE

ET

HY

ISC

ST

EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 149

VAV terminal units

TOC

General information

TVM
Page

Type

TVM

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVM-S
Dimensions and weight TVM-S-D
Dimensions and weight TVM
Dimensions and weight TVM-D
Specification text

1.1 150
1.1 155
1.1 156
1.1 157
1.1 158
1.1 159
1.1 160
1.1 161
1.1 162

Basic information and nomenclature

1.5 1

VAV dual duct terminal unit, variant TVM-S

VAV dual duct terminal unit, variant TVM-S-D

VAV dual duct terminal unit, variant TVM

VAV dual duct terminal unit, variant TVM-D

Application
VARYCONTROL VAV dual duct terminal units
of Type TVM for the supply air control in dual
duct variable or constant air volume systems
Closed-loop volume flow control
using an external power supply
For maximum acoustic and thermal comfort
Demand-based mixing of cold and warm air
Shut-off by means of switching
(equipment supplied by others)

Attachments
Compact controller: Compact unit consisting
of controller, differential pressure
transducer and actuator
Universal controller: Controller, differential
pressure transducer and actuators
for special applications

Variants
TVM-S Dual duct unit, 60 spigot arrangement
TVM-S-D Dual duct unit with acoustic cladding,
60 spigot arrangement
TVM: Dual duct unit, 90 spigot arrangement
TVM-D: Dual duct unit with acoustic cladding,
90 spigot arrangement
Units with acoustic cladding and/or
secondary silencer Type TS
for very demanding acoustic requirements
Acoustic cladding cannot be retrofitted

Useful additions
Secondary silencer Type TS

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.

Nominal sizes
TVM-S: 125, 160, 200
TVM: 125, 160, 200, 250, 315, 400

K5 1.1 150

Accessories
Lip seals (factory fitted)

Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Integral attenuator with at least 26 dB
insertion loss at 250 Hz
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Inspection access for cleaning to VDI 6022

05/2015 DE/en

VAV terminal units

TOC

General information
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensors
for volume flow rate measurement, one in
the cold air spigot and one in the silencer
Damper blade
Integral attenuator
Inspection access
Factory assembled control components
complete with wiring and tubing
Aerodynamic functional testing on a special
test rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy
(even with upstream bend R = 1D)
Construction features
Rectangular casing
Spigot on the fan end suitable
for circular ducts to EN 1506 or EN 13180
Spigot with groove for lip seal
Connection on the room end suitable
for air duct profiles
Baffle plate is fitted after the damper blade
for optimum aerodynamic performance
Position of the damper blade indicated
externally at shaft extension
Thermal and acoustic insulation (lining)

TVM
Installation and commissioning
Any installation orientation
Connecting spigots for warm and cold air
arranged at an angle of 60 (TVM-S)
or 90 (TVM)
Return edges of the casing
with drilled holes suitable for threaded rods
Standards and guidelines
Hygiene conforms to VDI 6022
VDI 2083, air cleanliness class 3,
and US standard 209E, class 100
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 125 and 160, class 3)
Nominal sizes 125 and 160 meet the general
requirements, nominal sizes 200 400 meet
the increased requirements of DIN 1946,
part 4, with regard to the acceptable
closed blade air leakage
Casing air leakage to EN 1751, class A
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Materials and surfaces


Casing and damper blade
made of galvanised sheet steel
Damper blade seal made of TPE plastic
Lining is mineral wool
Differential pressure sensor made of aluminium
Plastic bearings
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

05/2015 DE/en

K5 1.1 151

VAV terminal units

TOC

General information

TVM

Attachments: VARYCONTROL control components for Type TVM


Order code detail

Control function

Controller

Volume flow rate

Compact controller with MP bus interface


TROX/Belimo
Compact controller
TROX/Gruner
Compact controller
Siemens

Dynamic, integral

Integral

Volume flow rate

Universal controller
TROX/Belimo

Dynamic, integral

Actuator

Compact controller
BF0
XG0
LY0

Differential pressure transducer Actuator

Universal controller, dynamic


B27

Technical data

K5 1.1 152

Nominal sizes
Volume flow rate range
Volume flow rate control range
Minimum differential pressure
Maximum differential pressure
Operating temperature

125 400 mm
45 1680 l/s or 162 6048 m/h
Approx. 30 to 100 % of the nominal volume flow rate
120 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information
Function

TVM

Functional description
The VAV terminal unit is fitted with two differential
pressure sensors for measuring the volume flow
rates, one in the cold air flow and one in the total
air flow. The control components (attachments)
include two differential pressure transducers
that transform the differential pressure
(effective pressure) into an electric signal,
two controllers, and two actuators;
the control functions can be achieved
with a Compact controller or with individual
components. In most cases, the setpoint value
for the dual duct terminal unit comes from a room
temperature controller. The room temperature
controller 'leads' the cold air volume flow controller
and alters the setpoint for the cold air flow rate
between 0 and the maximum volume flow max.
The controller compares the actual value with
the setpoint value and alters the control signal
of the damper actuator if there is a difference
between the two values. The warm/total air
controller is set to the minimum volume flow rate
min and controls the warm air damper blade.
As a consequence, a corresponding proportion
of warm air is added. As the demand for cooling
increases, the warm air damper blade closes such
that eventually only cold air flows.
An integral attenuator reduces the noise
that is created by the restriction of the airflow.
The airflow velocity at the room end is, due to
the larger rectangular cross section,
about half the velocity in the circular duct.

Schematic illustration of the TVM-S

Damper blade cold air


Lip seal
Differential pressure sensor cold air
Control components, e. g. a Compact controller

05/2015 DE/en

Inspection access
Differential pressure sensor total air
Acoustic insulation
Damper blade warm air

K5 1.1 153

VAV terminal units

TOC

General information

TVM

Control loop

Control diagram

+ -

Volumenstrom

Sollwertsignal

Effective pressure transducer


Actuator for cold air duct
Volume flow controller
Setpoint value signal
Volume flow controller for tot (warm)
Effective pressure transducer for tot
Actuator for warm air duct

Cold air supply


Warm air supply
Total extract air at the unit outlet

Single operation

Slave operation (master-slave)

+ + -

+ -

Static differential pressure


p

K5 1.1 154

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
VARYCONTROL

TVM

TVM

TVM S D / 160 / D2 / B27 / E 0 / 300 900 / 0 900

Type
TVM Dual duct terminal unit
Spigot arrangement
No entry: 90
S
60 (up to nominal size 200)
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400

Attachments (control component)


Example
BF0 Compact controller
B27 Universal controller
Operating mode
E
Single
M
Master
F
Constant value
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s]
warm, min warm, max / cold, min cold, max
for factory setting

Accessories
No entry: none
D2
Lip seal
Order example

TVM/160/BF0/E0/300900 m/h/0900 m/h

VARYCONTROL

Spigot arrangement
Acoustic cladding
Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rate, warm
Volume flow rate, cold

05/2015 DE/en

90
Without
160 mm
Compact controller
Single
0 10 V DC
300 900 m/h
0 900 m/h

K5 1.1 155

VAV terminal units

TOC

Aerodynamic data

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

Volume flow rate ranges and minimum differential pressure values

Nominal size
l/s

m/h
45
60
100
150
75
100
170
250
120
180
280
405
185
270
470
615
310
420
720
1030
505
710
1250
1680

125

160

200

250

315

400

pst min
Pa

162
216
360
540
270
360
612
900
432
648
1008
1458
666
972
1692
2214
1116
1512
2592
3708
1818
2556
4500
6048

120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120
120

warm

%
160
160
160
160
140
140
140
140
140
140
140
140
145
145
145
145
160
160
160
160
160
160
160
160

8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5
8
7
5
5

17
15
12
7
17
15
12
7
17
15
12
7
17
15
12
7
17
15
12
7
17
15
12
7

TVM, TVM-S
TVM, TVM-S with secondary silencer TS
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

The upstream conditions


shown apply to cold air.
For warm air, no particular
upstream conditions
are required.

K5 1.1 156

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Junction

Bend

Upstream conditions

1D

Volume flow rate ranges

TVM

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

5D

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require a
perforated plate in the branch and before the VAV
terminal unit. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

05/2015 DE/en

VAV terminal units

TOC

Quick sizing
Air-regenerated noise

TVM

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

400

m/h
45
60
100
150
75
100
170
250
120
180
280
405
185
270
470
615
310
420
720
1030
505
710
1250
1680

162
216
360
540
270
360
612
900
432
648
1008
1458
666
972
1692
2214
1116
1512
2592
3708
1818
2556
4500
6048

LPA

LPA1
25
28
34
38
25
28
34
37
24
28
31
34
18
23
30
34
21
24
31
37
18
23
31
37

Case-radiated noise

dB(A)
15
19
24
29
16
19
25
28
15
18
21
25
8
12
19
24
8
11
18
26
6
9
16
21

LPA2

LPA3
25
28
32
36
35
36
39
41
30
33
36
39
25
29
34
37
30
32
35
38
28
32
37
40

21
24
29
33
26
28
33
37
25
28
33
37
20
24
30
33
27
30
33
35
25
29
35
38

TVM, TVM-S
TVM, TVM-S with secondary silencer TS
TVM-D, TVM-S-D

05/2015 DE/en

K5 1.1 157

VAV terminal units

TOC

Dimensions and weight TVM-S


VAV terminal unit for the control
of variable supply air volume flows
Connecting spigots for warm
and cold air arranged at an angle of 60

Description

VAV dual duct terminal


unit, variant TVM-S

TVM-S

Dimensions

20

H50

20

30

HB

< 800
W

Detail of flange

Compressible seal,
to be provided by others

Air duct profile

300

60

TVM

M8

Inspection access
Keep clear to provide access to attachments

Dimensions [mm] and weight [kg]


Nominal size
125
160
200

K5 1.1 158

D
124
159
199

L
1385
1630
1920

B3
300
410
560

H3
236
236
281

L1

1190
1360
1660

198
308
458

mm

B1
232
342
492

H
152
152
210

H1
186
186
244

A
245
335
340

B4
525
690
800

m
kg

173
173
173

30
35
50

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVM-S-D


Description

VAV dual duct terminal


unit, variant TVM-S-D

TVM

VAV terminal unit with acoustic cladding for


the control of variable supply air volume flows
Connecting spigots for warm
and cold air arranged at an angle of 60
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others) on the fan end
Acoustic cladding cannot be retrofitted

TVM-S-D

Dimensions

20

30

HB

Detail of flange

Compressible seal,
to be provided by others

60

Air duct profile

20

H


L

Inspection access
Keep clear to provide access to attachments

Dimensions [mm] and weight [kg]


Nominal size
125
160
200

05/2015 DE/en

D
124
159
199

L
1385
1630
1920

B3
380
490
640

H3
316
316
361

L1

1215
1410
1710

198
308
458

mm

B1
232
342
492

H
152
152
210

H1
186
186
244

A
225
295
300

B4
525
690
800

m
kg

160
180
180

45
55
80

K5 1.1 159

VAV terminal units

TOC

Dimensions and weight TVM


VAV terminal unit for the control
of variable supply air volume flows
Connecting spigots for warm
and cold air arranged at an angle of 90

Description

VAV dual duct terminal


unit, variant TVM

TVM

Dimensions

20

20

50

Detail of flange

C
50

Compressible seal,
to be provided by others




300

150

Air duct profile


200 300

300

H

30

HB

TVM



Inspection access
Keep clear to provide access to attachments

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

K5 1.1 160

D
124
159
199
249
314
399

B3

1355 300
1455 410
1790 560
2015 700
2575 900
2090 1000

H3
236
236
281
311
361
446

L1
1205
1255
1590
1765
1840
2325

B
198
308
458
598
798
898

B1

H
mm

232
342
492
632
832
932

152
152
210
201
252
354

H1

186
186
244
235
286
388

150
200
200
250
250
250

A1

170
150
125
160
130
180

125
145
170
200
240
290

C1

240
295
350
415
535
625

265
265
265
540
540
540

m
kg
28
34
50
65
90
130

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVM-D


Description

VAV dual duct terminal


unit, variant TVM-D

TVM

VAV terminal unit with acoustic cladding for


the control of variable supply air volume flows
Connecting spigots for warm
and cold air arranged at an angle of 90
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others) on the fan end
Acoustic cladding cannot be retrofitted

TVM-D

Dimensions

20

20

Compressible seal,
to be provided by others

H

Detail of flange

Air duct profile





Z

HB

30

Inspection access
Keep clear to provide access to attachments

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

05/2015 DE/en

D
124
159
199
249
314
399

B3

1355 380
1455 490
1790 640
2015 780
2575 980
2090 1080

H3
316
316
361
391
441
526

L1
1245
1295
1630
1805
1880
2365

B
198
308
458
598
798
898

B1

H
mm

232
342
492
632
832
932

152
152
210
201
252
354

H1

186
186
244
235
286
388

110
160
160
210
210
210

A1

130
110
85
120
90
140

165
185
210
240
280
330

C1

280
335
390
455
575
665

305
305
305
580
580
580

m
kg
42
51
78
105
140
200

K5 1.1 161

VAV terminal units

TOC

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular VAV dual duct terminal units for dual


duct systems with variable and constant volume
flows, available in 6 nominal sizes.
Connecting spigots for warm and cold air
arranged at an angle of 90. Up to nominal
size 200 an angle of 60 is also possible,
hence ideal for for the refurbishment
of older systems with dual duct units.
High control accuracy
(even with upstream bend R = 1D).
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains two averaging
differential pressure sensors for volume flow rate
measurement, one in the cold air flow and one
in the total air flow, two damper blades,
and an integral attenuator. Factory-assembled
control components complete with wiring
and tubing. Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
On the fan end, spigot with groove for lip seal,
suitable for connecting ducts to EN 1506
or EN 13180.
Room end suitable for the connection
of air duct profiles.
Two baffle plates, one fitted after each damper
blade for optimum acoustic
and aerodynamic performance.
Casing with acoustic and thermal insulation.
Position of the damper blade indicated
externally at shaft extension.
Closed blade air leakage to EN 1751, class 4
(nominal sizes 125 and 160, class 3).
Casing air leakage to EN 1751, class B.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.
Hygiene complies with VDI 6022, DIN 1946,
part 4, as well as EN 13779 and VDI 3803.
Special characteristics
Integral differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Integral attenuator with at least 26 dB
insertion loss at 250 Hz
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can later be measured
and adjusted on site; additional adjustment
device may be necessary
Inspection access for cleaning to VDI 6022

TVM
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth
Technical data
Nominal sizes: 125 to 400 mm
Volume flow rate range:
45 to 1680 l/s or 162 to 6048 m/h
Volume flow rate control range:
approx. 30 100 %
of the nominal volume flow rate
Minimum differential pressure: 120 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic
Compact controller to switch an external control
signal and an actual value signal for integration
into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC or 2 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Volume flow rate control range:
approx. 30 100 % of the nominal
volume flow rate
Sizing data
warm, min warm, max[m/h]
cold, min cold, max[m/h]
pst[Pa]
LPA air-regenerated noise[dB(A)]
LPA Case-radiated noise[dB(A)]

Materials and surfaces


Casing and damper blade
made of galvanised sheet steel
Damper blade seal made of TPE plastic
Lining is mineral wool
Differential pressure sensor made of aluminium
Plastic bearings
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Lining is mineral wool
Rubber elements for the insulation
of structure-borne noise

K5 1.1 162

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
VARYCONTROL

Type
TVM
Dual duct terminal unit
Spigot arrangement
No entry: 90
S
60 (up to nominal size 200)
Acoustic cladding
No entry: none
D
With acoustic cladding
Nominal size [mm]
125
160
200
250
315
400

TVM
Attachments (control component)
Example
BF0 Compact controller
B27 Universal controller
Operating mode
E
Single
M
Master
F
Constant value
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC
Volume flow rates [m/h or l/s]
warm, min warm, max / cold, min cold, max
for factory setting

Accessories
No entry: none
D2
Lip seal

05/2015 DE/en

K5 1.1 163

TVRK

TOC

1.1

X X TVRKtestregistrierung

VAV terminal units

Type TVRK

For contaminated air


Easy cleaning of sensor tubes

Plastic circular VAV terminal units for aggressive extract air


in variable air volume systems
Casing and damper blade made of flame-resistant polypropylene
Slide-out differential pressure sensor allows for easy cleaning
Suitable for the control of volume flow rate, room pressure or duct pressure
Electronic control components for different applications
(Universal and LABCONTROL)
Suitable for airflow velocities up to 13 m/s
Closed blade air leakage to EN 1751, class 3
Casing air leakage to EN 1751, class B

Variant with flange

Matching flanges for both ends


Plastic secondary silencer Type CAK for the reduction of air-regenerated noise
ET

HY

SCH GET
NI
E

ST

Optional equipment and accessories


With flanges on both ends

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 164

VAV terminal units

TOC

General information

TVRK
Page

Type

TVRK

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVRK
Dimensions and weight TVRK-FL
Installation details
Specification text

1.1 165
1.1 168
1.1 172
1.1 173
1.1 174
1.1 176
1.1 178
1.1 180

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVRK

VAV terminal unit, variant TVRK-FL

Application
Circular VARYCONTROL VAV terminal units
of Type TVRK, made of plastic,
preferably for the extract air flow control
in variable air volume systems
Closed-loop volume flow control using
an external power supply
Suitable for contaminated air
Shut-off by means of switching
(equipment supplied by others)

Special characteristics
Integral slide-out differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary

Product examples

Description
For detailed information
on control components
see Chapter K5 1.3.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
TVRK: VAV terminal unit
TVRK-FL: VAV terminal unit
with flanges on both ends
Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
LABCONTROL: Control components
for air management systems
Accessories
Matching flanges for both ends, including seals
Useful additions
Plastic secondary silencer Type CAK
for demanding acoustic requirements

K5 1.1 165

Parts and characteristics


Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement;
can be removed for cleaning
Damper blade
Factory-assembled control components
complete with wiring and tubing
Aerodynamic function testing on a special test
rig prior to shipping of each unit
Set-up data is given on a label
or volume flow rate scale affixed to the unit
High control accuracy
(even with upstream bend R = 1D)
Construction features
Circular casing
Spigot suitable for ducts according to DIN 8077
Both spigots with same diameter
Position of the damper blade
indicated externally at shaft extension

05/2015 DE/en

VAV terminal units

TOC

General information

TVRK

Materials and surfaces


Casing and damper blade
made of flame-resistant polypropylene (PPs)
Differential pressure sensor
and plain bearings made of polypropylene (PP)
Damper blade seal
made of chloroprene rubber (CR)

Standards and guidelines


Hygiene conforms to VDI 6022
Closed blade air leakage to EN 1751, class 3
Meets the general requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class B

Installation and commissioning


Installation orientation must be
as shown on the sticker

Maintenance
Maintenance-free as construction
and materials are not subject to wear
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Attachments: VARYCONTROL control components for Type TVRK


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Universal controller, static


BP3
BPB
BPG
BB3
BBB
XD1
XD3
BR3
BRB
BRG
BS3
BSB
BSG
BG3
BGB
BH3
BHB
XE1
XE3
XF1
XF3

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate

Static

Universal controller
TROX/Belimo
Universal controller
TROX/Gruner

Static, integral
Static, integral 100 Pa

Universal controller with MP bus interface


TROX/Belimo
Static, integral 600 Pa
Differential pressure

Differential pressure controller


TROX/Belimo

Differential pressure controller


TROX/Gruner

Static, integral 100 Pa


Static, integral 600 Pa
Static, integral 100 Pa
Static, integral 600 Pa

Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Fast-running actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator
Actuator
Spring return actuator

Attachments: LABCONTROL control components for Type TVRK


Order code detail
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Control function

Controller

Differential pressure transducer

Actuator

Room supply air


Room extract air
Room pressure
Fume cupboard
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Room supply air


Room extract air
Room pressure
Fume cupboard

Electronic controller TCU-LON-II


with LonWorks interface

Static, integral

Technical data

05/2015 DE/en

Nominal sizes
Volume flow rate range
Volume flow rate control range
Minimum differential pressure
Maximum differential pressure
Operating temperature

Fast-running actuator
Fast-running actuator
(brushless motor)

125 400 mm
25 1680 l/s or 90 6048 m/h
Approx. 17 to 100 % of the nominal volume flow rate
5 90 Pa
1000 Pa
10 50 C

K5 1.1 166

VAV terminal units

TOC

General information

Function

TVRK

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow
rate. The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator; the control functions
can be achieved with individual components
(Universal or LABCONTROL).
For most applications, the setpoint value
comes from an external setpoint adjuster.
The controller compares the actual value
with the setpoint value and alters the control
signal of the actuator if there is a difference
between the two values.

Schematic illustration of the TVRK

Differential pressure sensor


Damper blade
Casing

K5 1.1 167

Actuator
Control components, e.g. a Universal controller

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TVRK

TVRK

VARYCONTROL

Type
TVRK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Z
Differential pressure control supply air
A
Differential pressure control extract air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC

Accessories
No entry: none
GK
Matching flanges for both ends

Volume flow rates [m/h or l/s],


differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)

Attachments (control component)


Example
BB3 Universal controller with
static differential pressure transducer

Damper blade position


Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

Order example

TVRK/160/BB3/E2/200900 m/h

VARYCONTROL

Nominal size
Attachment
Operating mode
Signal voltage range
Volume flow rate

05/2015 DE/en

TVRK FL / 160 / GK / BB3 / E 2 / 200 900 / NO

160 mm
Universal controller with static differential pressure transducer
Single
2 10 V DC
200 900 m/h

K5 1.1 168

VAV terminal units

TOC

Order code

Order code

TVRK

TVRK with EASYLAB for room control and single operation

LABCONTROL

TVRK FL / 160 / GK / ELAB / RE / ULZ / LAB / ...

EASYLAB

TVRK FL / 160 / GK / ELAB / EC E0 / ULZ / ...

Type
TVRK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends
Attachment (control component)
ELAB EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
EC

Single operation
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
On-site switch contacts
3P
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control (equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF
Extract air led system (LAB)
CLR-RMF
Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function 'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel (only for room control)
BE-LCD-01
40-character display

K5 1.1 169

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TVRK

TVRK with EASYLAB for fume cupboard control

LABCONTROL

TVRK FL / 160 / GK / ELAB / FH VS / ULZS / 200 900

EASYLAB

Type
TVRK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400

Attachments (control component)


ELAB EASYLAB controller TCU3 with fast-running actuator
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
EM-TRF for 230 V AC
T
EM-TRF-USV for 230 V AC, provides uninU
terruptible power supply (UPS)

L
B
M
I

Accessories
No entry: none
GK
Matching flanges for both ends

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP, Modbus/IP and
webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket for the connection
of lighting and for switching the lighting on/
off using the control panel (only with
EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-SEG-** OLED display
BE-LCD-01 40-character display

Order example

TVRK/200/ELAB/FH-2P/TZ/600/1200

LABCONTROL

Nominal size

EASYLAB

Attachment
Equipment function

Two switching steps

Expansion modules

EM-TRF for 230 V AC, EM-AUTOZERO Solenoid valve for automatic zero point correction

Operating values

05/2015 DE/en

200 mm
EASYLAB controller TCU3 with fast-running actuator

600 1200 m/h

K5 1.1 170

VAV terminal units

TOC

Order code

Order code

TVRK

TVRK with TCU-LON-II

LABCONTROL

TVRK FL / 160 / GK / TMA / RE / 1500 / 750 / 100

TCU-LON-II

Type
TVRK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Order example

TVRK/160/TMB/RE/2000/750/100

LABCONTROL

Nominal size
Attachment
Equipment function

TCU-LON-II

Operating values

K5 1.1 171

Equipment function
FH
Fume cupboard
RE
Room extract air
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
FH: min max
RE: day / night / constant
PE: Tag / night / constant / psetpoint
The room control volume flow rates
(RS, RE, PS, PE) are related to the total
extract air volume flow rate for the room
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-TCU-LON-II Control panel

160 mm
TCU-LON-II with fast-running actuator (brushless motor)
Room extract air
Total extract air day-time operation 2000 m/h,
total extract air night-time operation 750 m/h,
constant volume flow rate 100 m/h

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVRK

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

315

400

Nominal size

m/h
25
60
105
150
40
80
145
250
65
180
310
405
95
270
470
615
155
425
740
1030
255
715
1250
1680

90
216
378
540
144
288
522
900
234
648
1116
1458
342
972
1692
2214
558
1530
2664
3708
918
2574
4500
6048

Pa

5
15
45
90
5
10
30
80
5
15
45
70
5
10
30
50
5
5
5
5
5
10
25
40

5
20
50
100
5
10
30
90
5
15
45
75
5
15
35
55
5
10
25
45
5
10
25
45

pst min

%
5
20
55
110
5
10
35
95
5
20
50
80
5
15
35
60
5
10
25
50
5
10
25
45

5
20
60
115
5
15
35
100
5
20
50
85
5
15
40
65
5
10
30
50
5
10
30
50

9
7
6
5
9
8
7
5
9
7
5
5
9
7
5
5
9
7
6
5
9
7
6
5

TVRK
TVRK with secondary silencer CAK, insulation thickness 50 mm, length 500 mm
TVRK with secondary silencer CAK, insulation thickness 50 mm, length 1000 mm
TVRK with secondary silencer CAK, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 172

VAV terminal units

TOC

Quick sizing

Air-regenerated noise

TVRK

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

400

25
60
105
150
40
80
145
250
65
180
310
405
95
270
470
615
155
425
740
1030
255
715
1250
1680

m/h
90
216
378
540
144
288
522
900
234
648
1116
1458
342
972
1692
2214
558
1530
2664
3708
918
2574
4500
6048

LPA1

LPA
34
44
51
55
36
42
49
53
44
44
43
41
39
45
44
44
39
46
50
53
37
44
49
51

19
30
38
41
23
31
37
41
33
33
33
33
29
35
35
35
29
37
41
44
29
37
42
44

Case-radiated noise

LPA2

dB(A)

<15
25
32
35
18
27
34
38
28
28
29
30
23
31
30
31
24
33
37
40
25
33
38
40

<15
20
28
31
<15
23
30
34
25
25
26
29
19
27
27
29
21
29
33
37
22
30
36
38

17
27
32
37
21
28
33
40
33
34
35
35
28
35
37
39
29
40
45
50
30
40
46
50

TVRK
TVRK with secondary silencer CAK, insulation thickness 50 mm, length 500 mm
TVRK with secondary silencer CAK, insulation thickness 50 mm, length 1000 mm
TVRK with secondary silencer CAK, insulation thickness 50 mm, length 1500 mm

K5 1.1 173

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVRK


Description

TVRK

VAV terminal unit for the control


of variable air volume flow rates
Spigot to make connections to the ducting

VAV terminal unit,


variant TVRK,
nominal sizes 125 200
Dimensions

TVRK,
Nominal sizes 125 200

Dimensions [mm] and weight [kg]


Nominal size
125
160
200

05/2015 DE/en

L
mm
125
160
200

394
394
394

H3

B3
195
230
270

m
kg
145
180
220

4.5
4.8
5.2

K5 1.1 174

VAV terminal units

TOC

Dimensions and weight TVRK


VAV terminal unit for the control
of variable air volume flow rates
Spigot to make connections to the ducting

VAV terminal unit,


variant TVRK
Dimensions

TVRK,
Nominal sizes 250 400

Description

TVRK

Dimensions [mm] and weight [kg]


Nominal size
250
315
400

K5 1.1 175

L
mm
250
315
400

394
594
594

H3

B3
320
385
470

m
kg
270
335
420

6.4
8.5
10.7

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVRK-FL


Description

TVRK

VAV terminal unit for the control


of variable air volume flow rates
With flanges to make detachable
connections to the ductwork

VAV terminal unit,


variant TVRK-FL,
nominal sizes 125 200
Dimensions

TVRK-FL,
nominal sizes 125 200


T

Dimensions [mm] and weight [kg]


Nominal size
125
160
200

05/2015 DE/en

D
125
160
200

B3
400
400
400

mm
195
230
270

H3

D1
145
180
270

165
200
240

D2
185
230
270

n
8
8
8

mm

kg
8
8
8

4.7
5.2
5.7

K5 1.1 176

VAV terminal units

TOC

Dimensions and weight TVRK-FL


VAV terminal unit for the control
of variable air volume flow rates
With flanges to make detachable
connections to the ductwork

VAV terminal unit,


variant TVRK-FL
Dimensions

TVRK-FL, nominal sizes 250 400

Description

TVRK


T

Dimensions [mm] and weight [kg]


Nominal size
250
315
400

K5 1.1 177

D
250
315
400

B3
400
600
600

mm
320
385
470

H3

D1
270
335
420

290
350
445

D2
320
395
475

n
12
12
16

mm

kg
8
10
10

7.0
9.4
11.9

05/2015 DE/en

VAV terminal units

TOC

Installation details

Space requirement
for commissioning
and maintenance

D
p

5D

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require a
perforated plate in the branch and before the VAV
terminal unit. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access to attachments

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Attachments

Space required

Space required

VARYCONTROL
Universal controller
300

05/2015 DE/en

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Junction

Bend

1D

Upstream conditions

TVRK

mm
320

300

Attachments

mm
LABCONTROL

EASYLAB

300

250

300

350

350

400

TCU-LON-II

250

200

250

320

250

300

K5 1.1 178

VAV terminal units

TOC

Installation details

TVRK
Access to attachments

Access to sensor tubes for cleaning

150

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Nominal size
125 200
250 400

mm
100
100

100
160

D
D

D: Casing diameter

K5 1.1 179

05/2015 DE/en

VAV terminal units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular VAV terminal units made of PPs plastic,


for variable and constant air volume systems,
suitable for extract air, available in 6 nominal sizes.
High control accuracy
(even with upstream bend R = 1D).
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components. Each unit contains an averaging
differential pressure sensor for volume flow rate
measurement and a damper blade.
Factory-assembled control components
complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Spigot, suitable for ducts according to DIN 8077.
Position of the damper blade indicated externally
at shaft extension.
Closed blade air leakage to EN 1751, class 3.
Casing air leakage to EN 1751, class B.
Hygiene conforms to VDI 6022
Special characteristics
Integral slide-out differential pressure sensor
with 3 mm measuring holes
(resistant to dust and pollution)
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool may be necessary

TVRK
Technical data
Nominal sizes: 125 to 400 mm
Volume flow rate range:
25 to 1680 l/s or 90 to 6048 m/h
Volume flow rate control range:
approx. 17 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 90 Pa
Maximum differential pressure: 1000 Pa
Attachments
Variable volume flow control with electronic
Universal controller to switch an external control
signal and an actual value signal
for integration into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC or 2 10 V DC
Possible override controls with external
switches using volt-free contacts:
CLOSED, OPEN, min and max
Volume flow rate control range:
approx. 17 100 %
of the nominal volume flow rate
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Materials and surfaces


Casing and damper blade
made of flame-resistant polypropylene (PPs)
Differential pressure sensor
and plain bearings made of polypropylene (PP)
Damper blade seal
made of chloroprene rubber (CR)

Order options
VARYCONTROL

Type
TVRK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400

05/2015 DE/en

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Z
Differential pressure control supply air
A
Differential pressure control extract air
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC
2
2 10 V DC

Accessories
No entry: none
GK
Matching flanges for both ends

Volume flow rates [m/h or l/s],


differential pressure [Pa]
min max for factory setting
pmin for factory setting
(operating modes A, Z)

Attachments (control component)


Example
BB3 Universal controller with static
differential pressure transducer

Damper blade position


Only with spring return actuators
NO
Power off to OPEN
NC
Power off to CLOSE

K5 1.1 180

VAV terminal units

TOC

Specification text

Order options
LABCONTROL
EASYLAB

TVRK

Type
TVRK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends
Attachment (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
Room control
RE
Extract air control (Room Exhaust)
PC
Differential pressure control
EC

Single operation
Extract air controller

External volume flow rate setting


Only for single operation
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Additional functions
Only for room control
(equipment function)
Raum management function
has been deactivated
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
Raum management function is active
LAB-RMF Extract air led system (LAB)
CLR-RMF Supply air led system (CLR)
Operating values [m3/h or l/s, Pa
For equipment function 'room control'
with additional function RMF
Total room extract air/supply air
1: Standard mode
2: Reduced operation
3: Increased operation
4: Constant room supply air
5: Constant room extract air
6: Supply air/extract air difference
psetpoint: Setpoint pressure
(only with differential pressure control)
For equipment function
'single operation'
E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Room control panel
(only for room control)
BE-LCD-01 40-character display

K5 1.1 181

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
TVRK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

TVRK
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket
for the connection of lighting
and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-SEG-** OLED display
BE-LCD-01 40-character display

05/2015 DE/en

K5 1.1 182

VAV terminal units

Specification text

Order options
LABCONTROL
TCU-LON-II

Type
TVRK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)

K5 1.1 183

TOC

TVRK
Equipment function
FH
Fume cupboard
RE
Room extract air
PE
Differential pressure control extract air
(Pressure Extract)
Operating values [m3/h or l/s, Pa]
Depending on equipment function
FH: min max
RE: day / night / constant
PE: Tag / night / constant / psetpoint
The room control volume flow rates
(RS, RE, PS, PE) are related to the total
extract air volume flow rate for the room
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-TCU-LON-II Control panel

05/2015 DE/en

TVLK

TOC

1.1

X X TVLKtestregistrierung

VAV terminal units

Type TVLK
Easy cleaning of sensor tubes

Variant with nozzle


and connecting circular spigot

Variant with bluff body


and flange

Optimised for use in laboratories and on fume cupboards


Plastic circular VAV terminal units for aggressive extract air in laboratories
and production facilities
Casing and damper blade made of flame-resistant polypropylene
Compact construction, only 400 mm long
High control accuracy even in case of unfavourable upstream conditions
Combination with fast-running actuators (air management systems)

Volume flow rate measurement with bluff body or nozzle

Slide-out sensor tubes allow for easy cleaning


Closed blade air leakage to EN 1751, class 4

For all upstream conditions

H GE

TE

Plastic secondary silencer Type CAK for the reduction of air-regenerated noise

ET

HY

ISC

Optional equipment and accessories


With flanges on both ends
ST

EN

Casing air leakage to EN 1751, class C

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.1 184

VAV terminal units

TOC

General information

TVLK
Page

Type

TVLK

Variants

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight TVLK
Dimensions and weight TVLK-FL
Installation details
Specification text

1.1 185
1.1 189
1.1 193
1.1 195
1.1 196
1.1 197
1.1 198
1.1 199

Basic information and nomenclature

1.5 1

VAV terminal unit, variant TVLK,


with bluff body and connecting circular spigot

VAV terminal unit, variant TVLK,


with bluff body and flange

VAV terminal unit, variant TVLK,


with nozzle and connecting circular spigot

VAV terminal unit, variant TVLK,


with nozzle and flange

Product examples

K5 1.1 185

05/2015 DE/en

VAV terminal units

General information
Description
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.
For detailed information
on control components
see Chapter K5 1.3.

Application
Circular LABCONTROL VAV terminal units
of Type TVLK, made of plastic, to control
the volume flow rate of fume cupboards
and fume hoods
Suitable for contaminated air
Closed-loop volume flow control using
an external power supply
Shut-off by means of switching
(equipment supplied by others)
Variants
TVLK: VAV terminal unit
TVLK-FL: VAV terminal unit
with flanges on both ends
Nominal sizes
Bluff body: 250 100, 250 160
Nozzle: 250 D08, 250 D10, 250 D16
Bluff body available in two sizes and nozzle
available in three sizes for different
volume flow rate ranges
Attachments
LABCONTROL: Control components
(attachments) for air management systems
Universal controller: Controller, differential
pressure transducer and actuators
for special applications
Accessories
Matching flanges for both ends, including seals
Useful additions
Plastic secondary silencer Type CAK
for demanding acoustic requirements
Special characteristics
High control accuracy even in case
of unfavourable upstream conditions
Integral slide-out differential pressure
sensor with 3 mm measuring holes
(resistant to dust and pollution)
No metal parts come into contact
with the airflow
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool or configuration
software may be necessary

TOC

TVLK
Construction features
Circular casing
Short casing: 392 mm without flange,
400 mm with flange
Spigot suitable for ducts according to DIN 8077
Both spigots with same diameter (250 mm)
Position of the damper blade indicated
externally at shaft extension
Materials and surfaces
Casing and damper blade
made of flame-resistant polypropylene (PP),
flammability to UL 94, V-0
Differential pressure sensor
(with bluff body, or nozzle) and plain bearing
made of polypropylene (PP)
Damper blade seal made of thermoplastic
elastomers (TPE)
Installation and commissioning
Installation orientation must be as shown
on the sticker
Standards and guidelines
Hygiene conforms to VDI 6022
Closed blade air leakage to EN 1751, class 4
Meets the increased requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Parts and characteristics


Ready-to-commission unit which consists
of mechanical parts and control components
(attachments)
Averaging differential pressure sensor
for volume flow rate measurement;
can be removed for cleaning
Damper blade
Factory assembled control components
(attachments) complete with wiring and tubing
Aerodynamic functional testing on a special
test rig prior to shipping of each unit
Unit carries test label with relevant data

05/2015 DE/en

K5 1.1 186

VAV terminal units

TOC

General information

TVLK

Attachments: VARYCONTROL control components for Type TVLK


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Universal controller, static


BP3
BPG

Universal controller with MP bus interface


TROX/Belimo
Volume flow rate
Static, integral
Universal controller
TROX/Belimo

BB3

Actuator
Fast-running actuator
Actuator

Attachments: LABCONTROL control components for Type TVLK


Order code detail
EASYLAB
ELAB
TCU-LON-II
TMA
TMB

Control function

Controller

Differential pressure transducer

Actuator

Fume cupboard
Room supply air
Room extract air
Room pressure
Single controller

EASYLAB controller TCU3

Static, integral

Fast-running actuator

Fume cupboard
Room supply air
Room extract air
Room pressure

Electronic controller TCU-LON-II


with LonWorks interface

Technical data

K5 1.1 187

Nominal sizes
Volume flow rate range
Volume flow rate control range
Minimum differential pressure
Maximum differential pressure
Operating temperature

Fast-running actuator
Static, integral

Fast-running actuator
(brushless motor)

250 mm
30 515 l/s or 108 1854 m/h
Approx. 15 to 100 % of the nominal volume flow rate
5 130 Pa
1000 Pa
10 50 C

05/2015 DE/en

VAV terminal units

TOC

General information
Function

TVLK

Functional description
For measuring the volume flow rate the VAV
terminal unit is fitted either with a bluff body
and a differential pressure sensor or with a nozzle.
The control components (attachments) include
a differential pressure transducer that transforms
the differential pressure (effective pressure)
into an electric signal, a controller,
and an actuator.
Fume cupboard control: The volume flow rate
setpoint depends on the control strategy
for the fume cupboard and is based on the face
velocity, the sash position, or a constant value.
Volume flow control: The volume flow rate
setpoint comes from an external unit.
The controller compares the actual value with
the setpoint value and alters the control signal
of the actuator if there is a difference between
the two values.

Schematic illustration of the TVLK




Nozzle (optional)
EASYLAB control component
Casing

05/2015 DE/en

Actuator
Bluff body and sensor tubes

K5 1.1 188

VAV terminal units

TOC

Order code

Order code

TVLK

TVLK with Universal controller

VARYCONTROL

TVLK FL / 250 100 / GK / BB3 / E0 / 200 900

Type
TVLK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC (only BP3 and BPG)
2
2 10 V DC
Volume flow rates [m/h or l/s]
min max for factory setting

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
Example
BB3 Universal controller
with static differential pressure transducer
BPG Universal controller with MP bus interface
and static differential pressure transducer,
fast-running actuator
Order example

TVLK/250-D16/BPG/E2/150-650

VARYCONTROL

Nominal size
Attachment
Operating mode
Operating values

K5 1.1 189

250 with nozzle D16


Universal controller with MP bus interface
and static differential pressure transducer,
fast-running actuator
Single
150 650 m/h

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
LABCONTROL
EASYLAB

TVLK

TVLK with EASYLAB for fume cupboard control

TVLK FL / 250 100 / GK / ELAB / FH VS / ULZS / 200 900

Type
TVLK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16

Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I

Accessories
No entry: none
GK
Matching flanges for both ends

Attachments (control component)


ELAB EASYLAB controller TCU3
with fast-running actuator

Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket for the connection
of lighting and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-SEG-** OLED display
BE-LCD-01 40-character display

Order example

TVLK/250100/ELAB/FHVS/200900 m/h

LABCONTROL

Nominal size
Attachment
Equipment function
Volume flow rates

EASYLAB

05/2015 DE/en

250 with bluff body 100


EASYLAB controller with fast-running actuator
Fume cupboard control with face velocity transducer
200 900 m/h

K5 1.1 190

VAV terminal units

TOC

Order code

Order code

TVLK

TVLK with EASYLAB for single controllers

LABCONTROL

TVLK FL / 250 100 / GK / ELAB / EC E0 / ULZ / ...

EASYLAB

Type
TVLK VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
ELAB EASYLAB controller TCU3
with fast-running actuator
Equipment function
EC

Control with single controller


Extract air controller

External volume flow rate setting


E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
EM-TRF-USV for 230 V AC, provides
U
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Operating values [m3/h or l/s, Pa]


E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1

Order example

TVLK/250-D08/ELAB/E2/400-1600

LABCONTROL

Nominal size
Attachment
External volume flow rate setting
Operating values

EASYLAB

K5 1.1 191

250 with nozzle D08


EASYLAB controller TCU3 with fast-running actuator
Voltage signal 2 10 V DC
400 1600 m/h

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code
LABCONTROL
TCU-LON-II

TVLK

TVLK with TCU-LON-II

TVLK FL / 250 100 / GK / TMB / FH / 200 900

Type
TVLK VAV terminal unit made of plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16
Accessories
No entry: none
GK
Matching flanges for both ends

Order example

TVLK-FL/250D16/GK/TMA/FH/250700 m/h

LABCONTROL

Flange
Nominal size
Accessories
Attachment
Equipment function
Volume flow rate

TCU-LON-II

05/2015 DE/en

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
FH
Fume cupboard
Face velocity control
with face velocity transducer
RE
Extract air controller (Room Extract)
Operating values [m/h or l/s]
FH: min max
RE: day / night / constant
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-TCU-LON-II Control panel

Both ends
250 with Venturi nozzle D16
Matching flanges
TCU-LON-II with fast-running actuator
Fume cupboard
250 700 m/h

K5 1.1 192

VAV terminal units

TOC

Aerodynamic data

Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVLK

Volume flow ranges and minimum pressure differences for the TVLK
with EASYLAB or TCU-LON II
Nominal size
l/s
250-100

250-160

250-D08

250-D10

250-D16

198
504
792
1296
108
288
432
702
342
756
1134
1854
198
504
792
1296
108
288
432
702

pst min

m/h
55
140
220
360
30
80
120
195
95
210
315
515
55
140
220
360
30
80
120
195

Pa

5
15
35
85
5
25
50
130
5
10
20
45
5
10
20
50
5
15
30
70

5
15
35
85
5
25
50
130
5
10
20
50
5
10
20
50
5
15
30
70

%
5
15
35
85
5
25
50
130
5
10
20
55
5
10
20
55
5
15
30
75

5
15
35
90
5
25
50
130
5
10
20
55
5
10
20
55
5
15
30
75

10
7
6
5
10
7
6
5
10
7
6
5
10
7
6
5
10
7
6
5

TVLK
TVLK with circular silencer CAK, insulation thickness 50 mm, length 500 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1000 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 193

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data

TVLK

Volume flow rate ranges and minimum differential pressure values for the TVLK
with VARYCONTROL Universal controller

Nominal size
l/s
250-100

250-160

250-D08

250-D10

250-D16

234
648
1044
1296
126
360
576
702
342
756
1134
1854
234
648
1044
1296
126
360
576
702

pst min

m/h
65
180
290
360
35
100
160
195
95
210
315
515
65
180
290
360
35
100
160
195

Pa

5
25
55
85
5
35
90
130
5
10
20
45
5
15
35
50
5
20
50
70

5
25
55
85
5
35
90
130
5
10
20
50
5
15
35
50
5
20
50
70

%
5
25
55
85
5
35
90
130
5
10
20
55
5
15
35
55
5
20
50
75

5
25
60
90
5
35
90
130
5
10
20
55
5
15
35
55
5
20
50
75

10
7
6
5
10
7
6
5
10
7
6
5
10
7
6
5
10
7
6
5

TVLK
TVLK with circular silencer CAK, insulation thickness 50 mm, length 500 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1000 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 194

VAV terminal units

TOC

Quick sizing

Air-regenerated noise
Quick sizing tables
provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

TVLK

Quick sizing: Sound pressure level at differential pressure 150 Pa TVLK


with EASYLAB or TCU-LON-II
Air-regenerated noise

Nominal size
l/s
250-100

250-160

250-D08

250-D10

250-D16

m/h

55
140
220
360
30
80
120
195
95
210
315
515
55
140
220
360
30
80
120
195

LPA1

LPA

198
504
792
1296
108
288
432
702
342
756
1134
1854
198
504
792
1296
108
288
432
702

40
46
47
48
37
41
43
49
36
40
41
44
36
42
43
45
33
39
42
47

33
38
39
39
32
35
37
42
26
31
32
34
28
34
35
37
28
33
36
42

Case-radiated noise

LPA2

dB(A)
29
34
35
35
28
31
33
38
23
27
29
31
24
30
31
33
24
30
33
38

26
31
31
32
25
28
30
35
20
24
26
28
21
27
28
29
22
28
30
36

26
33
37
42
22
29
32
40
23
29
33
38
24
31
35
38
21
28
31
38

TVLK
TVLK with circular silencer CAK, insulation thickness 50 mm, length 500 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1000 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1500 mm

Quick sizing: Sound pressure level at differential pressure 150 Pa,


TVLK with VARYCONTROL Universal controller
Air-regenerated noise

Nominal size
l/s
250-100

250-160

250-D08

250-D10

250-D16

65
180
290
360
35
100
160
195
95
210
315
515
65
180
290
360
35
100
160
195

m/h
234
648
1044
1296
126
360
576
702
342
756
1134
1854
234
648
1044
1296
126
360
576
702

LPA1

LPA
41
46
47
48
38
42
45
49
36
40
41
44
37
43
44
45
34
41
43
47

34
38
39
39
33
36
37
42
26
31
32
34
30
35
36
37
29
35
37
42

Case-radiated noise

LPA2

dB(A)
30
34
35
35
29
32
34
38
23
27
29
31
26
31
32
33
25
32
34
38

27
31
31
32
26
29
31
35
20
24
26
28
22
28
29
29
23
29
32
36

27
35
40
42
23
30
34
40
23
29
33
38
25
33
36
38
22
30
32
38

TVLK
TVLK with circular silencer CAK, insulation thickness 50 mm, length 500 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1000 mm
TVLK with circular silencer CAK, insulation thickness 50 mm, length 1500 mm

K5 1.1 195

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVLK


VAV terminal unit for the control
of variable air volume flow rates
Spigot to make connections to the ducting

VAV terminal unit, variant


TVLK, with connecting
circular spigot
Dimensions

TVLK

250

285

392

120

AIR

Description

TVLK

~ 80

Weight
Nominal size
250

K5 1.1 196

m
kg
5.1

05/2015 DE/en

VAV terminal units

TOC

Dimensions and weight TVLK-FL


Description

TVLK

VAV terminal unit for the control


of variable air volume flow rates
With flanges to make detachable
connections to the ductwork

VAV terminal unit, variant


TVLK, with flange
Dimensions

TVLK-FL

250

285

319
289

12 x 10

40

AIR

400

120

~ 80

Weight
Nominal size
250

05/2015 DE/en

m
kg
5.7

K5 1.1 197

VAV terminal units

TOC

Installation details
Junction

Bend

1D

The volume flow rate


accuracy applies
to all upstream conditions.

p
p

Space requirement
for commissioning
and maintenance
Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed in a branch just off the main duct.
Even the installation on the dome
of a fume cupboard will have no adverse effect.

Access to attachments

Access to attachments

Space required

Space required

Attachments

Attachments

mm

VARYCONTROL
Universal controller
300

320

300

Access to sensor tubes for cleaning

mm
LABCONTROL

EASYLAB

350

350

400

300

250

300

TCU-LON-II

320

250

300

250

200

250

Access to attachments

150

Upstream conditions

TVLK

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)

Space required
Nominal size
250-1**
Bluff body
250-D**
Nozzle

mm
100

160

100

160

100

D: Casing diameter

K5 1.1 198

05/2015 DE/en

VAV terminal units

TOC

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular VAV terminal units made of flameresistant plastic, for variable air volume systems
and fume cupboards. Suitable for the control
of extract air containing aggressive media since all
components coming into contact with the airflow
are made of plastic (no interior metal parts).
Ready-to-commission unit which consists
of the mechanical parts and the electronic control
components (attachments). Each unit contains
an averaging differential pressure sensor
with bluff body or a nozzle for volume flow rate
measurement, and a damper blade. Factory
assembled control components (attachments)
complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Spigot, suitable for ducts according to DIN 8077.
Position of the damper blade indicated
externally at shaft extension.
Closed blade air leakage to EN 1751, class 4.
Casing air leakage to EN 1751, class C.
Special characteristics
High control accuracy even in case
of unfavourable upstream conditions
Integral slide-out differential pressure
sensor with 3 mm measuring holes
(resistant to dust and pollution)
No metal parts come into contact
with the airflow
Factory set-up or programming
and aerodynamic function testing
Volume flow rate can be measured
and subsequently adjusted on site;
additional adjustment tool or configuration
software may be necessary

Order options
VARYCONTROL

Type
TVLK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16

TVLK
Materials and surfaces
Casing and damper blade
made of flame-resistant polypropylene (PP),
flammability to UL 94, V-0
Differential pressure sensor
(with bluff body, or nozzle) and plain bearing
made of polypropylene (PP)
Damper blade seal made of thermoplastic
elastomers (TPE)
Technical data
Nominal sizes: 250 mm
Volume flow rate range:
30 to 515 l/s or 108 to 1854 m/h
Volume flow rate control range:
approx. 15 100 %
of the nominal volume flow rate
Minimum differential pressure: 5 130 Pa
Maximum differential pressure: 10 50 C
Attachments
Variable volume flow control with electronic
EASYLAB controller for fume cupboards.
Supply voltage 24 V AC
Fast and stable control
Static differential pressure measurement
Fast-running actuator
Easy commissioning due to plug and play
communication system
Controller is a modular system
and can be expanded
Volume flow rate monitoring
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Operating mode
E
Single
M
Master
S
Slave
F
Constant value
Signal voltage range
For the actual and setpoint value signals
0
0 10 V DC (only BP3 and BPG)
2
2 10 V DC
Volume flow rates [m/h or l/s]
min max for factory setting

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
Example
BB3 Universal controller with static
differential pressure transducer
BPG Universal controller with MP bus
interface and static differential pressure
transducer, fast-running actuator

K5 1.1 199

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
TVLK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

TVLK
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket
for the connection of lighting
and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-SEG-** OLED display
BE-LCD-01 40-character display

05/2015 DE/en

K5 1.1 200

VAV terminal units

TOC

Specification text

Order options
LABCONTROL
EASYLAB

TVLK

Type
TVLK
VAV terminal unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
with fast-running actuator
Equipment function
EC

Control with single controller


Extract air controller

External volume flow rate setting


E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Operating values [m3/h or l/s, Pa]


E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1

Order options
LABCONTROL
TCU-LON-II

Type
TVLK
VAV terminal unit made of plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16
Accessories
No entry: none
GK
Matching flanges for both ends

K5 1.1 201

Attachments (control component)


TMA TCU-LON-II with fast-running actuator
TMB TCU-LON-II with fast-running actuator
(brushless motor)
Equipment function
FH
Fume cupboard
Face velocity control
with face velocity transducer
RE
Extract air controller (Room Extract)
Operating values [m/h or l/s]
FH: min max
RE: day / night / constant
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-TCU-LON-II Control panel

05/2015 DE/en

TVR-Ex

TOC

1.1

X X TVR-Extestregistrierung

VAV terminal units

Type TVR-Ex

For the control of variable air volume flows


in potentially explosive atmospheres (ATEX)
Circular VAV terminal units for variable air volume systems, approved
and certified for potentially explosive atmospheres (ATEX)
ATEX-compliant construction and parts
Approved for all gases, mists and vapours in zones 1 and 2,
with electronic control additionally for dusts in zones 21 and 22
Suitable for the control of supply
or extract air as well as for differential pressure control
Electronic or pneumatic control components
Closed blade air leakage to EN 1751, up to class 4
Casing air leakage to EN 1751, class C

ATEX-compliant parts and units

Optional equipment and accessories


Spring return actuator
Auxiliary switch with adjustable switching points
for capturing the end positions

ATEX-Zertifizierung

05/2015 DE/en

K5 1.1 202

VAV terminal units

TOC

General information

TVR-Ex
Page

Type

TVR-Ex

Variants

General information
Order code
Aerodynamic data Electronic
Aerodynamic data Pneumatic
Quick sizing Electronic
Quick sizing Pneumatic
Dimensions and weight
Installation details
Specification text

1.1 203
1.1 207
1.1 209
1.1 210
1.1 211
1.1 212
1.1 213
1.1 214
1.1 215

Basic information and nomenclature

1.5 1

Schematic illustration of the TVR-Ex


with electronic control

Schematic illustration of the TVR-Ex


with pneumatic control

Product examples





VAV terminal unit


Static differential pressure transducer
Actuator
Terminal box
Electronic volume flow controller

Description

VAV terminal unit


Type TVR-Ex

Application
Circular EXCONTROL VAV terminal units
of Type TVR-Ex for the precise supply air
or extract air flow control in variable
air volume systems
For use in potentially explosive atmospheres
(ATEX)
Closed-loop volume flow control
using an external power supply
Electronic or pneumatic volume flow control
Shut-off by means of switching
(equipment supplied by others)
Classification
Electronic control: Equipment group II
Zones 1 and 2 (atmosphere: gases):
II 2 G c II T5/T6
Zones 21 and 22 (atmosphere: dusts):
II 2 D c II 80 C
Pneumatic control: Equipment group II
Zones 1 and 2 (atmosphere: gases):
II 2 G c II T5/T6

K5 1.1 203

VAV terminal unit


Pneumatic volume flow controller
Pneumatic actuator

Construction
Galvanised sheet steel
P1: Inner duct powder-coated,
silver grey (RAL 7001)
A2: Inner duct in stainless steel
Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Electronic control
Pneumatic control
Accessories
Actuator with auxiliary switch
for capturing the end positions
Spring return actuator
Useful additions
Secondary silencer Type CA
for demanding acoustic requirements

05/2015 DE/en

VAV terminal units

General information
Special features
ATEX mark and certification
ATEX equipment group II, approved for use
in zones 1 and 2; electronic control also
for zones 21 and 22
Volume flow rate can later be measured
and adjusted on site; configuration is possible
using personal computer software
Parts and characteristics
Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement
Damper blade
Connection for equipotential bonding
Cable bushings suitable for use
in potentially explosive atmospheres
ATEX-compliant control components,
factory assembled and complete
with wiring and tubing
Aerodynamic functional testing on a special
test rig prior to shipping of each unit
Unit carries test label with relevant data
High control accuracy
(even with upstream bend R = 1D)

TOC

TVR-Ex
Standards and guidelines
Directive 94/9/EC: Equipment
and protective systems intended
for use in potentially explosive atmospheres
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 125 and 160, class 3)
Nominal sizes 125 and 160 meet the general
requirements, nominal sizes 200 400 meet
the increased requirements of DIN 1946,
part 4, with regard to the acceptable
closed blade air leakage
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear
Electronic control
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Construction features
Construction and materials comply
with the EU directive and guidelines for use
in potentially explosive atmospheres (ATEX)
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180
Materials and surfaces
Casing and inner tube
made of galvanised sheet steel
Control components made of die cast
aluminium (pneumatic control: plastic)
Plastic bearings
Damper blade of stainless steel
and with TPE seal (thermoplastic elastomer)
Differential pressure sensor made of aluminium
Air duct (inner tube) in stainless steel
or powder-coated as options
Installation and commissioning
Connections for equipotential bonding:
Suitable cables must be connected by others
Electronic control
Any installation orientation
Zero point correction required
Pneumatic control
Installation orientation must be as shown
on the sticker

05/2015 DE/en

K5 1.1 204

VAV terminal units

TOC

General information

TVR-Ex

Attachments: EXCONTROL Electric control components for Type TVR-Ex


Order code detail Control function

Controller

Differential pressure transducer

Actuator

Static, integral

Actuator
Spring return actuator
Actuator with auxiliary switches
Spring return actuator
with auxiliary switch

Static

Actuator
Spring return actuator
Actuator with auxiliary switches
Spring return actuator
with auxiliary switch

Internal controller
S1S
S1F
S1X
S1Y

Universal controller
(use in areas with
Volume flow rate
potentially explosive atmospheres)
Schischek

External controller
TES
TEF
TEX
TEY

Volume flow rate controller TCU3


(use in areas with
Volume flow rate
potentially explosive atmospheres)
TROX/Schischek

Attachments: EXCONTROL Pneumatic control components for Type TVR-Ex


Order code detail

Control function

Controller

Differential pressure transducer

Actuator

Volume flow rate

Volume flow controller


Sauter

Integral

Actuator

Room pressure controller 20 Pa


Volume flow controller
Sauter
Room pressure controller 50 Pa
Volume flow controller
Sauter

Integral

Actuator

Volume flow controllers


PG5

Pressure and volume flow cascade


PJ5
Room pressure
PL5

Technical data

Nominal sizes
Volume flow rate range
Volume flow rate control range
Maximum differential pressure
Operating temperature

Electronic

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

Pneumatic

Operating pressure
Air consumption volume flow control
Air consumption pressure and volume flow
cascade
Control pressure
Maximum pressure
Compressed air
Protection level

K5 1.1 205

125 400 mm
15 1680 l/s or 54 6048 m/h
Approx. 15 to 100 % of the nominal volume flow rate
1000 Pa
10 50 C

24 V AC 10 %, 50/60 Hz
24 V DC 10 %
20 VA max.
20 W max.
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
ATEX to 94/9/EG, EMC to 2004/108/EG, low voltage to 2006/95/EG

1.3 bar 0.1 bar


50 ln/h
100 ln/h
0.2 1.0 bar
1.5 bar
Compressed air for instruments, free of oil, water and dust
IP 42

05/2015 DE/en

VAV terminal units

TOC

General information
Function

TVR-Ex

Functional description
The VAV terminal unit is fitted with a differential
pressure sensor for measuring the volume flow
rate. The control components (attachments)
include a differential pressure transducer
that transforms the differential pressure
(effective pressure) into an electric signal,
a controller, and an actuator. For most
applications, the setpoint value comes from
a room temperature controller which is installed
outside of the potentially explosive atmosphere.
The controller compares the actual value with
the setpoint value and alters the control signal
of the damper actuator if there is a difference
between the two values. The connections for
the supply voltage and for the voltage signals
are made in a terminal box that is suitable
for use in potentially explosive atmospheres.

Schematic illustration of the TVR-Ex


with electronic control

Schematic illustration of the TVR-Ex


with pneumatic control

Auxiliary switch
Static differential pressure transducer
Terminal box
Cable bushing
Equipotential bonding
Actuator

05/2015 DE/en

Actuator
Room pressure controller
Pneumatic connections
Volume flow controller
Equipotential bonding

K5 1.1 206

VAV terminal units

TOC

Order code

Order code

TVR-Ex

TVR-Ex

EXCONTROL

TVREx P1 / 125 / S1S / 200 400 / NO

Type
TVR-Ex VAV terminal unit for use
in potentially explosive atmospheres
Material
No entry: galvanised sheet steel
P1
Inner duct powder-coated,
silver grey (RAL 7001)
A2
Inner duct in stainless steel
Nominal size [mm]
125
160
200
250
315
400

Operating values [m/h or l/s, Pa]


Electronic control
min max
Pneumatic control
Volume flow rate min max
Pressure and volume flow cascade
min max / psetpoint
Damper blade position
Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

Attachments (control component)


For example
Electronic control
S1S Internal controller and actuator
PG5
PJ5

Pneumatic control
Volume flow controller with actuator
Pressure and volume flow cascade
(20 Pa)

Order examples

TVR-Ex/200/S1S/4001200 m/h

EXCONTROL

Material

Galvanised sheet steel

Nominal size

200 mm

Attachments

Electronic controller, internal, pressure transducer and actuator

Volume flow rate

400 1200 m/h

TVR-Ex/160/PG5/200500 m/h/NO
Material
Nominal size
Attachments
Volume flow rate
Damper blade position

K5 1.1 207

Galvanised sheet steel


160 mm
Pneumatic volume flow controller with actuator
200 500 m/h
Pressure off to OPEN

05/2015 DE/en

VAV terminal units

TOC

Order code
Order code

TVR-Ex

TVR-Ex with EASYLAB for single operation

LABCONTROL

TVREx P1 / 160 / TES / EC E0 / ULZ / ...

EASYLAB

Type
TVR-Ex VAV terminal unit for use
in potentially explosive atmospheres
Material
No entry: galvanised sheet steel
P1
Inner duct powder-coated,
silver grey (RAL 7001)
A2
Inner duct in stainless steel
Nominal size [mm]
125
160
200
250
315
400

Module expansions
Option 1: Power supply
No entry: 24 V AC
EM-TRF for 230 V AC
T
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Attachments (control component)


For example
Electronic control
TES External controller,
pressure transducer and actuator

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock

Operating values [m3/h or l/s, P]


E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1

Equipment function
Single operation
Supply air controller
SC
EC
Extract air controller
External volume flow rate setting
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling
Order example

TVR-Ex/160/TEX/SCE0/T/200900 m/h

LABCONTROL

Material

EASYLAB

Nominal size

160 mm

Attachments

Electronic controller, external, pressure transducer and actuator with auxiliary switch

Equipment function

Supply air controller

Expansion modules

EM-TRF for 230 V AC

Volume flow rate

05/2015 DE/en

Galvanised sheet steel

200 900 m/h

K5 1.1 208

VAV terminal units

TOC

Aerodynamic data Electronic

Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVR-Ex

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

315

400

Nominal size

m/h
22
60
105
150
35
100
175
250
60
160
280
405
90
245
430
615
145
410
720
1030
240
670
1175
1680

79
216
378
540
126
360
630
900
216
576
1008
1458
324
882
1548
2214
522
1476
2592
3708
864
2412
4230
6048

pst min
Pa

5
15
45
90
5
15
35
70
5
15
35
65
5
10
25
45
5
5
15
30
5
5
15
25

5
20
50
100
5
15
40
80
5
15
35
70
5
10
25
50
5
10
20
35
5
5
15
30

%
5
20
55
110
5
15
45
85
5
15
40
75
5
10
30
55
5
10
20
40
5
5
15
30

5
20
60
115
5
15
45
95
5
15
40
80
5
10
35
65
5
10
20
40
5
5
15
35

15
7
6
5
15
8
7
5
15
7
5
5
15
7
5
5
15
7
6
5
15
7
6
5

TVR-Ex
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

K5 1.1 209

05/2015 DE/en

VAV terminal units

TOC

Aerodynamic data Pneumatic


Volume flow rate ranges

The minimum differential


pressure of VAV terminal
units is an important
factor in designing
the ductwork and in rating
the fan including
speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

TVR-Ex

Volume flow rate ranges and minimum differential pressure values

l/s
125

160

200

250

315

400

Nominal size

m/h
15
40
70
100
25
75
125
175
40
125
210
300
60
200
340
475
105
330
555
775
170
545
920
1300

54
144
252
360
90
270
450
630
144
450
756
1080
216
720
1224
1710
378
1188
1998
2790
612
1962
3312
4680

Pa

5
10
20
40
5
10
20
35
5
10
20
40
5
5
15
30
5
5
10
20
5
5
10
15

5
10
25
45
5
10
20
40
5
10
20
40
5
10
15
30
5
5
10
20
5
5
10
20

pst min

%
5
10
25
50
5
10
25
45
5
10
25
45
5
10
20
35
5
5
15
25
5
5
10
20

5
10
25
55
5
10
25
45
5
10
25
45
5
10
20
40
5
5
15
25
5
5
10
20

15
10
7
5
15
10
7
5
15
10
7
5
15
10
7
5
15
10
7
5
15
10
7
5

TVR-Ex
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm
The volume flow rates given for VAV terminal units depend on the nominal size and on the control component
(attachment) that is installed. The table gives the minimum and maximum values for a VAV terminal unit.
Some control components may only have a limited volume flow rate range. This applies in particular to control
components with a static differential pressure transducer. For volume flow rate ranges for all control components
refer to our Easy Product Finder design programme.

05/2015 DE/en

K5 1.1 210

VAV terminal units

TOC

Quick sizing Electronic

Air-regenerated noise

TVR-Ex

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

400

22
60
105
150
35
100
175
250
60
160
280
405
90
245
430
615
145
410
720
1030
240
670
1175
1680

m/h
79
216
378
540
126
360
630
900
216
576
1008
1458
324
882
1548
2214
522
1476
2592
3708
864
2412
4230
6048

LPA1

LPA
36
45
49
52
41
47
50
53
41
47
50
54
38
47
48
52
43
47
49
53
43
44
47
50

25
36
40
41
30
39
42
44
32
40
44
45
30
40
42
44
36
42
44
48
36
38
42
44

Case-radiated noise

LPA2

dB(A)
16
30
34
34
22
34
37
39
24
34
40
39
24
34
38
38
29
35
39
42
29
32
36
38

<15
28
32
32
19
31
34
36
22
33
38
38
22
32
37
37
26
34
38
41
26
30
35
37

16
25
31
35
22
28
32
37
21
29
32
38
22
35
37
42
29
39
42
46
31
37
41
46

TVR-Ex
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm

K5 1.1 211

05/2015 DE/en

VAV terminal units

TOC

Quick sizing Pneumatic


Air-regenerated noise

TVR-Ex

Quick sizing: Sound pressure level at differential pressure 150 Pa


Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
125

160

200

250

315

400

15
40
70
100
25
75
125
175
40
125
210
300
60
200
340
475
105
330
555
775
170
545
920
1300

m/h
54
144
252
360
90
270
450
630
144
450
756
1080
216
720
1224
1710
378
1188
1998
2790
612
1962
3312
4680

LPA1

LPA
33
39
46
49
40
45
49
50
40
46
48
51
41
44
47
49
42
45
47
50
43
43
45
48

22
29
37
40
28
35
41
42
31
37
41
44
32
36
40
42
35
40
42
44
36
37
40
42

Case-radiated noise

LPA2

dB(A)

<15
22
31
34
20
29
36
37
23
31
36
40
24
31
35
38
28
33
36
39
30
31
34
37

<15
19
29
32
16
26
33
34
20
30
35
38
22
29
34
37
25
31
35
38
26
29
33
35

<15
20
26
31
20
25
29
32
20
26
30
33
21
30
36
38
28
35
40
43
30
35
39
43

TVR-Ex
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm
TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm

05/2015 DE/en

K5 1.1 212

VAV terminal units

TOC

Dimensions and weight


TVR-Ex
600

536

Dimensions

TVR-Ex

Dimensions
Nominal size
125
160
200
250
315
400

D
124
159
199
249
314
399

B3

mm

372
372
463
463
627
627

H3
221
221
311
311
461
461

C
129
111
182
157
289
246

Weight
TVR-Ex/.../TEx

TVR-Ex/.../Pxx
m

Nominal size

kg
125
160
200
250
315
400

17.5
17.5
19.0
19.0
23.0
23.0

15.5
15.5
17.0
17.0
21.0
21.0

TVR-Ex/.../TEx: Electronic control


TVR-Ex/.../Pxx: Pneumatic control

K5 1.1 213

05/2015 DE/en

VAV terminal units

TOC

Installation details

Space requirement
for commissioning
and maintenance

Junction

1
D

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

TVR-Ex

5D

A bend with a centre line curvature radius


of at least 1D without an additional straight
duct section upstream of the VAV terminal
unit has only a negligible effect
on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require a
perforated plate in the branch and before the VAV
terminal unit. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

Space required
Nominal size
125
160
200
250
315
400

05/2015 DE/en

mm
600
600
600
600
600
600

220
220
310
310
460
460

300
300
300
300
300
300

K5 1.1 214

VAV terminal units

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

VAV terminal units for variable and constant air


volume systems in potentially explosive
atmospheres, suitable for supply or extract air,
available in 6 nominal sizes.
High control accuracy
(even with upstream bend R = 1D).
Ready-to-commission unit which consists
of the mechanical parts, the electronic control
components, and parts for equipotential bonding
and for use in potentially explosive atmospheres.
Each unit contains an averaging differential
pressure sensor for volume flow rate
measurement and a damper blade.
Factory-assembled control components
complete with wiring and tubing.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180.
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 125 and 160, class 3).
Casing air leakage to EN 1751, class C.

TOC

TVR-Ex
Attachments
Variable volume flow control with electronic
controller to switch a control signal and an actual
value signal for integration into the central BMS.
Supply voltage 24 V AC
Supply voltage for actuator: 230 V AC
Signal voltages 0 10 V DC
The actual value signal relates to the nominal
volume flow rate such that commissioning
and subsequent adjustment are simplified
Volume flow rate control range:
approx. 15 100 %
of the nominal volume flow rate
Actuator with adjustable running time,
7.5 120 s
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Special features
ATEX mark and certification
ATEX equipment group II, approved for use
in zones 1 and 2; electronic control also
for zones 21 and 22
Volume flow rate can later be measured
and adjusted on site; configuration is possible
using personal computer software
Materials and surfaces
Casing and inner tube
made of galvanised sheet steel
Control components made of die cast
aluminium (pneumatic control: plastic)
Plastic bearings
Damper blade of stainless steel
and with TPE seal (thermoplastic elastomer)
Differential pressure sensor made of aluminium
Air duct (inner tube) in stainless steel
or powder-coated as options
Construction
Galvanised sheet steel
P1: Inner duct powder-coated,
silver grey (RAL 7001)
A2: Inner duct in stainless steel
Technical data
Nominal sizes: 125 to 400 mm
Volume flow rate range:
15 to 1680 l/s or 54 to 6048 m/h
Volume flow rate control range:
approx. 15 100 %
of the nominal volume flow rate
Maximum differential pressure: 1000 Pa

K5 1.1 215

05/2015 DE/en

VAV terminal units

TOC

Specification text
Order options
EXCONTROL

TVR-Ex

Type
TVR-Ex VAV terminal unit for use
in potentially explosive atmospheres
Material
No entry: galvanised sheet steel
P1
Inner duct powder-coated, silver grey
(RAL 7001)
A2
Inner duct in stainless steel
Nominal size [mm]
125
160
200
250
315
400

Operating values [m/h or l/s, Pa]


Electronic control
min max
Pneumatic control
Volume flow rate min max
Pressure and volume flow cascade
min max / psetpoint
Damper blade position
Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

Attachments (control component)


For example
Electronic control
S1S Internal controller and actuator
PG5
PJ5
Order options
LABCONTROL
EASYLAB

Pneumatic control
Volume flow controller with actuator
Pressure and volume flow cascade
(20 Pa)

Type
TVR-Ex VAV terminal unit for use
in potentially explosive atmospheres
Material
No entry: galvanised sheet steel
P1
Inner duct powder-coated, silver grey
(RAL 7001)
A2
Inner duct in stainless steel
Nominal size [mm]
125
160
200
250
315
400
Attachments (control component)
For example
Electronic control
TES External controller,
pressure transducer and actuator

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock

Operating values [m3/h or l/s, Pa


E0, E2: min / max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1

Equipment function
Single operation
SC
Supply air controller
EC
Extract air controller
External volume flow rate setting
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
2P
On-site switch contacts
for 2 switching steps
3P
On-site switch contacts
for 3 switching steps
F
Volume flow rate constant value,
without signalling

05/2015 DE/en

K5 1.1 216

CA

TOC

1.2

X X CAtestregistrierung

Secondary silencers
for VAV terminal units

Type CA

For the reduction of noise in circular ducts,


suitable for all circular VAV terminal units
and CAV controllers, galvanised sheet steel construction
Circular silencers Type CA for the reduction of noise in the circular ducts
of air conditioning systems
Absorption material is non-combustible mineral wool with RAL quality mark,
biosoluble and hence hygienically safe according to the German TRGS 905
(Technical Rules for Hazardous Substances) and EU directive 97/69/EG
Mineral wool faced with non-woven glass fibre as protection against erosion
due to airflow velocities up to 20 m/s
Casing and perforated inner duct are galvanised sheet steel
Variant with spigot has a groove for a lip seal,
suitable for circular connecting ducts to EN 1506 or EN 13180
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class B
Optional equipment and accessories
With flanges on both ends
With lip seals on both ends

05/2015 DE/en

K5 1.2 1

Secondary silencers for VAV terminal units

TOC

General information

CA

Type

CA

Description

Circular silencer Type CA

Page
General information
Order code
Dimensions and weight CA
Dimensions and weight CA/.../VF1
Dimensions and weight CA/.../VF2
Specification text

1.2 2
1.2 3
1.2 4
1.2 5
1.2 6
1.2 7

Basic information and nomenclature

1.5 1

Application
Circular silencers Type CA for the reduction
of noise in the circular ducts
of air conditioning systems
For the reduction of air-regenerated noise
of air terminal units such as LVC and TVR,
and of mechanical self-powered controllers
such as RN and VFC
For the reduction of fan noise
Can be used as cross talk silencer to reduce
the transfer of noise through ducts between
neighbouring rooms
Variants
050: Circular silencer with 50 mm insulation
100: Circular silencer with 100 mm insulation
VF1: Circular silencer with flange on one end
VF2: Circular silencer with flanges
on both ends
Special versions upon request
Nominal sizes
100, 125, 160, 200, 250, 315, 400, 450, 500,
560, 630, 710, 800 mm
For VAV terminal units and CAV controllers
100, 125, 160, 200, 250, 315, 400 mm

Materials and surfaces


Casing and perforated inner duct
are galvanised sheet steel
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre as protection against
erosion through airflow velocities up to 20 m/s
Inert to fungal and bacterial growth
Standards and guidelines
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class B
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Accessories
GE: Matching flange for one end
GZ: Matching flanges for both ends
VD2: Lip seals on both ends (factory fitted)
Special features
Insertion loss measured according to ISO 7235
Absorption material is non-combustible
Insulation thickness 50 mm or 100 mm
Parts and characteristics
Casing
Perforated inner tube
Absorption material
Construction features
Circular casing
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
Operating pressure up to 1000 Pa
Operating temperature up to 100 C

K5 1.2 2

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Order code
Order code

CA

Type
CA
Circular silencer
Insulation thickness [mm]
050 50
100 100
Nominal size [mm]
100
125
160
200
250
315
400
450
500
560
630
710
800

Nominal length [mm]


500
1000
1500
Matching flange
No entry: none
on one end (only VF1)
GE
GZ
on both ends (only VF2)
Type of connection
No entry: spigot
VD2 Spigot with lip seal on both ends
VF1 Flange on one end
VF2 Flanges on both ends

CA-100/3151500/GE/VF1
Packungsdicke
Nenngre
Lnge
Gegenflansch
Anschlussvariante

05/2015 DE/en

CA 050 / 3151000 / GZ / VF2

For available
combinations of insulation
thickness, nominal size
and nominal length
see the Weight table.

Order example

CA

100 mm
315 mm
1500 mm
Einseitig
Flansch einseitig

K5 1.2 3

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CA


Application

Circular silencer for the reduction of noise


Spigot to make connections to the ducting

Dimensions

CA
L
60

CA

For more technical data


see the Multileaf Dampers,
Sound Attenuators,
External Weather Louvres
catalogue,
chapter K3 6.3.

Dimensions

The table shows


the weight for each
nominal size, length
and insulation thickness

Weight

Nominal size
100
125
160
200
250
315
400

Dimensions
CA-050

CA-100

D3

D3
mm

199
224
259
299
349
414
499

299
324
359
399
449
514
599

Nominal length

mm

500
1000
1500

99
124
159
199
249
314
399

500
1000
1500

CA-050
Nominal size

500

L1
380
880
1380

CA-100

1000

1500

500

1000

1500

m
kg

100
125
160
200
250
315
400

K5 1.2 4

4
5
70
7
9
12
15

7
9
12
13
16
20
25

22
28
34

6
7
9
9
11
14
18

11
13
16
17
20
25
30

29
35
42

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CA/.../VF1

CA

Application

Circular silencer for the reduction of noise


Spigot on one end to make connections
to the ducting
With flange on one end to make a detachable
connection to the ducting

Dimensions

CA/.../VF1

L
60

50

For more technical data


see the Multileaf Dampers,
Sound Attenuators,
External Weather Louvres
catalogue,
chapter K3 6.3.

Dimensions

Dimensions
CA-050 CA-100

Nominal size
100
125
160
200
250
315
400

The table shows


the weight for each
nominal size, length
and insulation thickness

n x 9.5

D3

D3

D D1 D2

mm

199
224
259
299
349
414
499

299
324
359
399
449
514
599

99
124
159
199
249
314
399

152
177
212
253
303
378
464

4
4
6
6
6
8
8

mm

500
1000
1500

mm
132
157
192
233
283
352
438

Nominal length

4
4
4
4
4
4
4

L1

490
990
1490

380
880
1380

Weight
CA-050
Nominal size

500

CA-100

1000

1500

500

1000

1500

m
kg

100
125
160
200
250
315
400

05/2015 DE/en

4
5
8
8
10
13
16

7
9
13
14
17
21
26

23
29
35

6
7
10
10
12
15
19

11
13
17
18
21
26
31

30
36
43

K5 1.2 5

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CA/.../VF2


Application

Circular silencer for the reduction of noise


With flanges on both ends to make detachable
connections to the ducting

Dimensions

CA/.../VF2
L

50

CA

n x 9.5
T

For more technical data


see the Multileaf Dampers,
Sound Attenuators,
External Weather Louvres
catalogue,
chapter K3 6.3.

Dimensions
CA-050 CA-100
Nominal size
100
125
160
200
250
315
400

The table shows


the weight for each
nominal size, length
and insulation thickness

Dimensions

D3

D3

D D1 D2

mm

199
224
259
299
349
414
499

299
324
359
399
449
514
599

132
157
192
233
283
352
438

152
177
212
253
303
378
464

4
4
6
6
6
8
8

mm

500
1000
1500

mm

99
124
159
199
249
314
399

Nominal length

4
4
4
4
4
4
4

L1

480
980
1480

380
880
1380

Weight
CA-050
Nominal size

500

CA-100

1000

1500

500

1000

1500

m
kg

100
125
160
200
250
315
400

K5 1.2 6

4
6
8
8
10
14
18

7
10
13
14
17
22
28

23
30
37

6
8
10
10
12
16
21

11
14
17
18
21
27
33

30
37
45

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Order options

Circular silencers for air conditioning systems,


rigid construction, available in 13 nominal sizes.
Insertion loss measured according to ISO 7235.
Casing with acoustic and thermal insulation.
Various types of connection, suitable for circular
ducts to EN 1506 or EN 13180.
Casing air leakage to EN 15727, class B.
Special features
Insertion loss measured according to ISO 7235
Absorption material is non-combustible
Insulation thickness 50 mm or 100 mm

Type
CA
Circular silencer
Insulation thickness [mm]
050 50
100 100
Nominal size [mm]
100
125
160
200
250
315
400
450
500
560
630
710
800

05/2015 DE/en

CA
Materials and surfaces
Casing and perforated inner duct
are galvanised sheet steel
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre as protection against
erosion through airflow velocities up to 20 m/s
Inert to fungal and bacterial growth

Nominal length [mm]


500
1000
1500
Matching flange
No entry: none
GE
on one end (only VF1)
GZ
on both ends (only VF2)
Type of connection
No entry: spigot
VD2 Spigot with lip seal on both ends
VF1 Flange on one end
VF2 Flanges on both ends

K5 1.2 7

CS

TOC

1.2

X X CStestregistrierung

Secondary silencers
for VAV terminal units

Type CS

For the reduction of noise in circular ducts,


suitable for all circular VAV terminal units
and CAV controllers, aluminium construction
Circular silencers, in rigid aluminium construction,
for the reduction of noise in the circular ducts of air conditioning systems
Absorption material is non-combustible mineral wool with RAL quality mark,
biosoluble and hence hygienically safe according to the German TRGS 905
(Technical Rules for Hazardous Substances) and EU directive 97/69/EG
Casing and perforated inner duct made of aluminium
Variant with spigot has a groove for a lip seal,
suitable for circular connecting ducts to EN 1506 or EN 13180
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class D
Optional equipment and accessories
Socket-type spigots on both ends
Raised edges at both ends
With lip seals on both ends

05/2015 DE/en

K5 1.2 

Secondary silencers for VAV terminal units

TOC

General information

CS

Type

CS

Description

Circular silencer Type CS

Page
General information
Order code
Dimensions and weight CS
Dimensions and weight CS/.../AS2
Dimensions and weight CS/.../BK2
Specification text

1.2 9
1.2 10
1.2 11
1.2 12
1.2 13
1.2 14

Basic information and nomenclature

1.5 1

Application
Circular silencers Type CS for the reduction
of air-regenerated noise in the circular ducts
of air conditioning systems
For the reduction of air-regenerated noise of air
terminal units LVC and TVR, and of mechanical
self-powered controllers RN and VFC
For the reduction of fan noise
Can be used as cross talk silencer to reduce
the transfer of noise through ducts between
neighbouring rooms
Variants
025: Circular silencer with 25 mm insulation
050: Circular silencer with 50 mm insulation
AS2: Circular silencer with socket-type
spigots on both ends
BK2: Circular silencer with raised edges
at both ends
Special versions upon request
Nominal sizes
80, 100, 125, 160, 200, 250, 315, 400 mm
Accessories
VD2: Lip seals on both ends (factory fitted)
AS2: Socket-type spigots on both ends
BK2: Raised edges at ends

Materials and surfaces


Casing and perforated inner duct
made of aluminium
Lining is mineral wool
End pieces made ABS plastic, flammability
to UL 94, V-0 (nominal sizes 80 125)
End pieces made of aluminium
(nominal sizes 160 400)
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Inert to fungal and bacterial growth
Standards and guidelines
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class D
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Special features
Insertion loss measured according to ISO 7235
Absorption material is non-combustible
Insulation thickness 25 mm or 50 mm
Parts and characteristics
Casing
Perforated inner tube
Absorption material
Construction features
Circular casing
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
Maximum operating pressure 1000 Pa
Maximum operating temperature 100 C

K5 1.2 

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Order code
Order code

CS

CS

CS 025 / 1601000 / VD2

Type
CS
Circular silencer
Insulation thickness [mm]
025 25
050 50
Nominal size [mm]
80
100
125
160
200
250
315
400
Order example

Nominal length [mm]


500
1000
1500
Type of connection
No entry: spigot
VD2 Spigot with lip seal on both ends
AS2 Socket-type spigots on both ends
BK2 Raised edges at both ends

CS-050/2501500/VD2
Packungsdicke
Nenngre
Lnge
Anschlussvariante

05/2015 DE/en

50 mm
250 mm
1500 mm
Rohrstutzen mit Lippendichtung beidseitig

K5 1.2 1

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CS


Application

Circular silencer for the reduction of noise


Spigot to make connections to the ducting

Dimensions

CS
L


For more technical data see Dimensions


the Multileaf Dampers,
Sound Attenuators,
Nominal size
External Weather Louvres
catalogue, chapter K3 6.3.
80
100
125
160
200
250
315
400
The table shows
the weight for each
nominal size, length
and insulation thickness

55

CS

Dimensions
CS-025

CS-050

D3

D3
mm

135
160
191
221
261
311
376
461

192
212
236
271
311
366
426
511

Nominal length

mm

500
1000
1500

79
99
124
159
199
249
314
399

L1

650
1150
1650

500
1000
1500

Weight
CS-025
Nominal size

500

CS-050

1000

1500

500

1000

1500

m
kg

80
100
125
160
200
250
315
400

K5 1.2 1

1.0
1.2
1.4
1.6
2.0
2.5
2.9
3.7

1.8
2.1
2.5
2.9
3.6
4.4
5.2
6.6

2.6
3.1
3.7
4.2
5.2
6.2
7.5
9.4

1.4
1.6
1.9
2.1
2.6
3.1
3.5
4.5

2.6
2.9
3.3
3.8
4.6
5.5
6.2
7.9

3.7
4.2
4.7
5.4
6.5
7.8
8.9
11.3

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CS/.../AS2


Application

Circular silencer for the reduction of noise


Socket-type spigots to make connections
to the ducting

Dimensions

CS/.../AS2

CS

1
L

For more technical data see Dimensions


the Multileaf Dampers,
Sound Attenuators,
Nominal size
External Weather Louvres
catalogue, chapter K3 6.3.
80
100
125
160
200
250
315
400
The table shows
the weight for each
nominal size, length
and insulation thickness

55

Dimensions
CS-025

CS-050

D3

D3
mm

135
160
191
221
261
311
376
461

192
212
236
271
311
366
426
511

Nominal length

mm

500
1000
1500

80
100
125
160
200
250
315
400

L1

650
1150
1650

500
1000
1500

Weight
CS-025
Nominal size

500

CS-050

1000

1500

500

1000

1500

m
kg

80
100
125
160
200
250
315
400

05/2015 DE/en

1.0
1.2
1.4
1.6
2.0
2.5
2.9
3.7

1.8
2.1
2.5
2.9
3.6
4.4
5.2
6.6

2.6
3.1
3.7
4.2
5.2
6.2
7.5
9.4

1.4
1.6
1.9
2.1
2.6
3.1
3.5
4.5

2.6
2.9
3.3
3.8
4.6
5.5
6.2
7.9

3.7
4.2
4.7
5.4
6.5
7.8
8.9
11.3

K5 1.2 1

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CS/.../BK2


Circular silencer for the reduction of noise
With raised edges to make detachable
connections to the ducting

Dimensions

CS/.../BK2
L

Application

CS

For more technical data see Dimensions


the Multileaf Dampers,
CS-025
Sound Attenuators,
Nominal size D3
External Weather Louvres
catalogue, chapter K3 6.3.
80
100
125
160
200
250
315
400
The table shows
the weight for each
nominal size, length
and insulation thickness

135
160
191
221
261
311
376
461

Dimensions
CS-050
D3

mm

192
212
236
271
311
366
426
511

79
99
124
159
199
249
314
399

Nominal length

D2

mm

500
1000
1500

93
113
138
173
213
263
328
413

L1

638
1138
1638

500
1000
1500

Weight
CS-025
Nominal size

500

CS-050

1000

1500

500

1000

1500

m
kg

80
100
125
160
200
250
315
400

K5 1.2 1

1.0
1.2
1.4
1.6
2.0
2.5
2.9
3.7

1.8
2.1
2.5
2.9
3.6
4.4
5.2
6.6

2.6
3.1
3.7
4.2
5.2
6.2
7.5
9.4

1.4
1.6
1.9
2.1
2.6
3.1
3.5
4.5

2.6
2.9
3.3
3.8
4.6
5.5
6.2
7.9

3.7
4.2
4.7
5.4
6.5
7.8
8.9
11.3

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Order options

Circular silencers for air conditioning systems,


rigid construction, available in 8 nominal sizes.
Insertion loss measured according to ISO 7235.
Casing with acoustic and thermal insulation.
Spigot with groove for lip seal, suitable for circular
connecting ducts to EN 1506 or EN 13180.
Casing air leakage to EN 15727, class D.
Special features
Insertion loss measured according to ISO 7235
Absorption material is non-combustible
Insulation thickness 25 mm or 50 mm

Type
CS
Circular silencer
Insulation thickness [mm]
025 25
050 50
Nominal size [mm]
80
100
125
160
200
250
315
400

05/2015 DE/en

CS
Materials and surfaces
Casing and perforated inner duct
made of aluminium
Lining is mineral wool
End pieces made ABS plastic, flammability
to UL 94, V-0 (nominal sizes 80 125)
End pieces made of aluminium
(nominal sizes 160 400)
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Inert to fungal and bacterial growth
Nominal length [mm]
500
1000
1500
Type of connection
No entry: spigot
VD2 Spigot with lip seal on both ends
AS2 Socket-type spigots on both ends
BK2 Raised edges at both ends

K5 1.2 1

CF

TOC

1.2

X X CFtestregistrierung

Secondary silencers
for VAV terminal units

Type CF

For the reduction of noise in circular ducts,


suitable for all circular VAV terminal units
and CAV controllers, flexible aluminium construction
Circular silencers, in flexible aluminium construction,
for the reduction of noise in the circular ducts of air conditioning systems
Absorption material is non-combustible mineral wool with RAL quality mark,
biosoluble and hence hygienically safe according to the German TRGS 905
(Technical Rules for Hazardous Substances) and EU directive 97/69/EG
Casing and perforated inner duct made of aluminium
Variant with spigot has a groove for a lip seal,
suitable for circular connecting ducts to EN 1506 or EN 13180
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class D
Optional equipment and accessories
Socket-type spigots on both ends
Raised edges at both ends
With lip seals on both ends

05/2015 DE/en

K5 1.2 1

Secondary silencers for VAV terminal units

TOC

General information

CF

Type

CF

Description

Flexible circular silencer


Type CF

Page
General information
Order code
Dimensions and weight CF
Dimensions and weight CF/.../AS2
Dimensions and weight CF/.../BK2
Specification text

1.2 16
1.2 17
1.2 18
1.2 19
1.2 20
1.2 21

Basic information and nomenclature

1.5 1

Application
Flexible circular silencers Type CF
for the reduction of noise in the circular ducts
of air conditioning systems
For the reduction of air-regenerated noise of air
terminal units LVC and TVR, and of mechanical
self-powered controllers RN and VFC
For the reduction of fan noise
Can be used as cross talk silencer to reduce
the transfer of noise through ducts between
neighbouring rooms
Variants
025: Circular silencer with 25 mm insulation
050: Circular silencer with 50 mm insulation
AS2: Circular silencer with socket-type
spigots on both ends
BK2: Circular silencer with raised
edges at both ends
Special versions upon request
Nominal sizes
80, 100, 125, 160, 200, 250, 315, 400 mm
Accessories
VD2: Lip seals on both ends (factory fitted)
AS2: Socket-type spigots on both ends
BK2: Raised edges at ends

Materials and surfaces


Casing and perforated inner duct
made of aluminium
Lining is mineral wool
End pieces made ABS plastic, flammability
to UL 94, V-0 (nominal sizes 80 125)
End pieces made of aluminium
(nominal sizes 160 400)
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Inert to fungal and bacterial growth
Standards and guidelines
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class D
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Special characteristics
Insertion loss measured according to ISO 7235
Very flexible and consequently suitable
for installation in complicated duct systems
and restricted spaces
Absorption material is non-combustible
Insulation thickness 25 or 100 mm
Minimum bend radius 3 outer diameter D
of the silencer
Parts and characteristics
Casing
Perforated inner tube
Absorption material
Construction features
Circular casing
Flexible construction
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot connections with groove for lip seal
Maximum operating pressure 1000 Pa
Maximum operating temperature 100 C

K5 1.2 16

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Order code
Order code

CF

CF

CF 025 / 1601000 / VD2

Type
CF
Flexible circular silencer
Insulation thickness [mm]
025 25
050 50
Nominal size [mm]
80
100
125
160
200
250
315
400
Order example

Nominal length [mm]


500
1000
1500
2000
Type of connection
No entry: spigot
VD2 Spigot with lip seal on both ends
AS2 Socket-type spigots on both ends
BK2 Raised edges at both ends

CF-050/1601000/VD2
Packungsdicke
Nenngre
Lnge
Anschlussvariante

05/2015 DE/en

50 mm
160 mm
1000 mm
Rohrstutzen mit Lippendichtung beidseitig

K5 1.2 17

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CF


Application

Circular silencer for the reduction of noise


Spigot to make connections to the ducting

Dimensions

CF
L


For more technical data see Dimensions


the Multileaf Dampers,
Sound Attenuators,
Nominal size
External Weather Louvres
catalogue, chapter K3 6.3.

55

CF

Dimensions
CF-025

CF-050

D3

D3

80
100
125
160
200
250
315
400
The table shows
the weight for each
nominal size, length
and insulation thickness

Nominal length

mm

135
160
191
221
261
311
376
461

192
212
236
271
311
366
426
511

500
1000
1500
2000

79
99
124
159
199
249
314
399

L1

mm
650
1150
1650
2150

500
1000
1500
2000

Weight
CF-025
Nominal size

500

1000

CF-050

1500

2000

500

1000

1500

2000

m
kg

80
100
125
160
200
250
315
400

K5 1.2 18

0.6
0.8
0.9
1.1
1.3
1.6
1.9
2.5

1.0
1.3
1.5
1.8
2.2
2.7
3.2
4.1

1.5
1.7
2.1
2.5
3.0
3.7
4.5
5.6

1.9
2.2
2.7
3.2
3.9
4.7
5.7
7.2

0.9
1.1
1.2
1.4
1.7
2.1
2.4
3.1

1.5
1.8
2.0
2.4
2.9
3.5
4.0
5.1

2.2
2.5
2.9
3.3
4.0
4.8
5.6
7.1

2.8
3.2
3.7
4.3
5.1
6.2
7.2
9.1

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CF/.../AS2


Application

Circular silencer for the reduction of noise


Socket-type spigots to make connections
to the ducting

Dimensions

CF/.../AS2

CF

1
L

For more technical data see Dimensions


the Multileaf Dampers,
Sound Attenuators,
Nominal size
External Weather Louvres
catalogue, chapter K3 6.3.

55

Dimensions
CF-025

CF-050

D3

D3

80
100
125
160
200
250
315
400
The table shows
the weight for each
nominal size, length
and insulation thickness

mm

135
160
191
221
261
311
376
461

192
212
236
271
311
366
426
511

Nominal length

500
1000
1500
2000

80
100
125
160
200
250
315
400

L1

mm
650
1150
1650
2150

500
1000
1500
2000

Weight
CF-025
Nominal size

500

1000

CF-050

1500

2000

500

1000

1500

2000

m
kg

80
100
125
160
200
250
315
400

05/2015 DE/en

0.6
0.8
0.9
1.1
1.3
1.6
1.9
2.5

1.0
1.3
1.5
1.8
2.2
2.7
3.2
4.1

1.5
1.7
2.1
2.5
3.0
3.7
4.5
5.6

1.9
2.2
2.7
3.2
3.9
4.7
5.7
7.2

0.9
1.1
1.2
1.4
1.7
2.1
2.4
3.1

1.5
1.8
2.0
2.4
2.9
3.5
4.0
5.1

2.2
2.5
2.9
3.3
4.0
4.8
5.6
7.1

2.8
3.2
3.7
4.3
5.1
6.2
7.2
9.1

K5 1.2 19

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CF/.../BK2


Circular silencer for the reduction of noise
With raised edges to make detachable
connections to the ducting

Dimensions

CF/.../BK2
L

Application

CF

For more technical data see Dimensions


the Multileaf Dampers,
CF-025
Sound Attenuators,
D3
Nominal
size
External Weather Louvres
catalogue, chapter K3 6.3.
80
100
125
160
200
250
315
400
The table shows
the weight for each
nominal size, length
and insulation thickness

Dimensions
CF-050

135
160
191
221
261
311
376
461

D3

D2

mm

192
212
236
271
311
366
426
511

79
99
124
159
199
249
314
399

Nominal length
500
1000
1500
2000

93
113
138
173
213
263
328
413

L1

mm
638
1138
1638
2138

500
1000
1500
2000

Weight
CF-025
Nominal size

500

1000

CF-050

1500

2000

500

1000

1500

2000

m
kg

80
100
125
160
200
250
315
400

K5 1.2 20

0.6
0.8
0.9
1.1
1.3
1.6
1.9
2.5

1.0
1.3
1.5
1.8
2.2
2.7
3.2
4.1

1.5
1.7
2.1
2.5
3.0
3.7
4.5
5.6

1.9
2.2
2.7
3.2
3.9
4.7
5.7
7.2

0.9
1.1
1.2
1.4
1.7
2.1
2.4
3.1

1.5
1.8
2.0
2.4
2.9
3.5
4.0
5.1

2.2
2.5
2.9
3.3
4.0
4.8
5.6
7.1

2.8
3.2
3.7
4.3
5.1
6.2
7.2
9.1

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Order options

Circular silencers for air conditioning systems,


flexible construction, available in 8 nominal sizes.
Insertion loss measured according to ISO 7235.
Casing with acoustic and thermal insulation.
Spigot with groove for lip seal, suitable for circular
connecting ducts to EN 1506 or EN 13180.
Casing air leakage to EN 15727, class D.
Special characteristics
Insertion loss measured according to ISO 7235
Very flexible and consequently suitable
for installation in complicated duct systems
and restricted spaces
Absorption material is non-combustible
Insulation thickness 25 or 100 mm
Minimum bend radius 3 outer diameter D
of the silencer

Type
CF
Flexible circular silencer
Insulation thickness [mm]
025 25
050 50
Nominal size [mm]
80
100
125
160
200
250
315
400

05/2015 DE/en

CF
Materials and surfaces
Casing and perforated inner duct
made of aluminium
Lining is mineral wool
End pieces made ABS plastic, flammability
to UL 94, V-0 (nominal sizes 80 125)
End pieces made of aluminium
(nominal sizes 160 400)
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Inert to fungal and bacterial growth

Nominal length [mm]


500
1000
1500
2000
Type of connection
No entry: spigot
VD2 Spigot with lip seal on both ends
AS2 Socket-type spigots on both ends
BK2 Raised edges at both ends

K5 1.2 21

TS

TOC

1.2

X X TStestregistrierung

Secondary silencers for


VAV terminal units

Type TS

For the reduction of air-regenerated noise


of air terminal units Type TVZ, TVA, TZ-Silenzio,
TA-Silenzio or TVM
Rectangular secondary silencers for the reduction of air-regenerated noise
of air terminal units Type TVZ, TVA, TZ-Silenzio, TA-Silenzio or TVM
Absorption material is non-combustible mineral wool with RAL quality mark,
biosoluble and hence hygienically safe according to the German TRGS 905
(Technical Rules for Hazardous Substances) and EU directive 97/69/EG
Mineral wool faced with glass fibre fabric as protection against erosion due
to airflow velocities up to 20 m/s
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class B

H GE

TE

ET

HY

ISC

ST

EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 1.2 22

Secondary silencers for VAV terminal units

TOC

General information

TS

Type

TS

Description

Secondary silencer
Type TS

Page
General information

1.2 23

Basic information and nomenclature

1.5 1

Application
Secondary silencers of Type TS to reduce
the air-regenerated noise of air terminal units
For air terminal units TVZ, TVA,
TZ-Silenzio, TA-Silenzio, and TVM

Installation and commissioning


Connection profiles fit air terminal units TVZ,
TVA, TZ-Silenzio, TA-Silenzio, and TVM
Return edges of the casing with drilled
holes suitable for M10 threaded rods

Nominal sizes
125, 160, 200, 250, 315, 400

Standards and guidelines


Hygiene conforms to VDI 6022
Casing air leakage to EN 15727, class B

Parts and characteristics


Casing
Absorption material

Maintenance
Maintenance-free as construction
and materials are not subject to wear

Construction features
Rectangular casing
Connection on the room end suitable
for air duct profiles
Thermal and acoustic insulation (lining)
Materials and surfaces
Casing made of galvanised sheet steel
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

Order code

TS

TS / 200

Type
TS
Secondary silencer

Order example

Nominal size
125
160
200
250
315
400

TS/200
Nominal size

K5 1.2 23

200 mm

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

General information

TS

TS

Dimensions

20

20

Detail of flange

Compressible seal,
to be provided by others

56

HB

30

M8

End facing the room

Air duct profile

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

Specification text

Order options

05/2015 DE/en

B3
806
806
956
956
1056
1306

300
410
560
700
900
1000

H3

B1

mm
236
236
281
311
361
446

198
308
458
598
798
898

H
232
342
492
632
832
932

H1
152
152
210
201
252
354

m
kg
186
186
244
235
286
388

Rectangular secondary silencers for VAV


terminal units to reduce the air-regenerated noise,
available in 6 nominal sizes
Casing with acoustic and thermal insulation.
Flanges on both sides,
suitable for duct connection.
Casing air leakage to EN 15727, class B.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.
Hygiene complies with VDI 6022, DIN 1946,
part 4, as well as EN 13779 and VDI 3803.

Materials and surfaces


Casing made of galvanised sheet steel
Lining is mineral wool

Type
TS
Secondary silencer

Nominal size
125
160
200
250
315
400

10
15
22
37
42
50

Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

K5 1.2 24

TX

TOC

1.2

X X TXtestregistrierung

Secondary silencers
for VAV terminal units

Type TX

For the reduction of air-regenerated noise


of air terminal units Type TVJ, TVT or EN
Rectangular secondary silencers for the reduction of air-regenerated noise
of air terminal units Type TVJ, TVT or EN
Absorption material is non-combustible mineral wool with RAL quality mark,
biosoluble and hence hygienically safe according to the German TRGS 905
(Technical Rules for Hazardous Substances) and EU directive 97/69/EG
Mineral wool faced with glass fibre fabric as protection against erosion due
to airflow velocities up to 20 m/s
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class A

05/2015 DE/en

K5 1.2 25

Secondary silencers for VAV terminal units

TOC

General information

TX

Type

TX

Description

Secondary silencer
Type TX

Page
General information
Dimensions and weight
Specification text

1.2 26
1.2 27
1.2 29

Basic information and nomenclature

1.5 1

Application
Secondary silencer Type TX to reduce
the air-regenerated noise of air terminal units
For air terminal units TVJ and TVT,
and for mechanical self-powered controllers EN
Nominal sizes
43 nominal sizes from 200 100 to
1000 1000
Parts and characteristics
Casing
Sound attenuator splitters
without resonating panels
Construction features
Absorption sound attenuator
without resonating panels
Rectangular casing
Connection on the room end suitable
for 30 mm air duct profiles
Splitters with aerodynamically profiled frames
Maximum splitter thickness 100 mm
Splitter arrangement and number depends
on the nominal size
50 % free area for all nominal sizes

Materials and surfaces


Casing and splitter frames made of galvanised
sheet steel
Absorption material is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth
Installation and commissioning
Air duct profiles fit air terminal units
TVJ and TVT, and mechanical self-powered
controllers EN
Connect the non-active section
of the secondary silencer
to the VAV terminal unit
Standards and guidelines
Casing air leakage to EN 15727, class A
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Order code

TX

TX / 600400

Type
TX
Secondary silencer

Order example

Nominal size [mm]


BH

TX/600400
Nominal size (B H)

K5 1.2 26

600 400 mm

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Dimensions and weight


TX

500

13

Dimensions

TX

1500

End facing the terminal unit


End facing the room

Splitter section
Non-active section

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
400 100
500 100
600 100
300 150
200 200
300 200
400 200
500 200
600 200
700 200
800 200
400 250
500 250
600 250
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300

05/2015 DE/en

H
200
300
400
500
600
300
200
300
400
500
600
700
800
400
500
600
300
400
500
600
700
800
900
1000

B1
100
100
100
100
100
150
200
200
200
200
200
200
200
250
250
250
300
300
300
300
300
300
300
300

mm
235
335
435
535
635
335
235
335
435
535
635
735
835
435
535
635
335
435
535
635
735
835
935
1035

B2

H1
260
360
460
560
660
360
260
360
460
560
660
760
860
460
560
660
360
460
560
660
760
860
960
1060

H2
135
135
135
135
135
185
235
235
235
235
235
235
235
285
285
285
335
335
335
335
335
335
335
335

m
kg
160
160
160
160
160
210
260
260
260
260
260
260
260
310
310
310
360
360
360
360
360
360
360
360

10
12
15
17
20
15
16
20
25
29
34
39
44
27
30
36
24
29
34
40
45
50
55
60

K5 1.2 27

Secondary silencers for VAV terminal units

TOC

Dimensions and weight


TX

500

13

Dimensions

TX

1500

End facing the terminal unit


End facing the room

Splitter section
Non-active section

Dimensions [mm] and weight [kg]


Nominal size
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600
800 800
1000 800
1000 1000

K5 1.2 28

H
400
500
600
700
800
900
1000
500
600
700
800
900
1000
600
800
1000
800
1000
1000

B1
400
400
400
400
400
400
400
500
500
500
500
500
500
600
600
600
800
800
1000

mm
435
535
635
735
835
935
1035
535
635
735
835
935
1035
635
835
1035
835
1035
1035

B2

H1
460
560
660
760
860
960
1060
560
660
760
860
960
1060
660
860
1060
860
1060
1060

H2
435
435
435
435
435
435
435
535
535
535
535
535
535
635
635
635
835
835
1035

m
kg
460
460
460
460
460
460
460
560
560
560
560
560
560
660
660
660
860
860
1060

34
39
45
50
56
61
67
45
50
56
62
68
73
55
67
80
79
93
107

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Specification text
Description

TX

Rectangular secondary silencers


for VAV terminal units to reduce
the air-regenerated noise,
available in 43 nominal sizes
Insertion loss at least 9 dB at 250 Hz
Splitters with aerodynamically profiled frames.
Connecting flanges on both ends,
suitable for 30 mm duct connection
Casing air leakage to EN 15727, class A.
Complies with VDI 2083, clean room class 3,
and US standard 209E, class 100.

Materials and surfaces


Casing and splitter frames made of galvanised
sheet steel
Absorption material is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre fabric as protection
against erosion through airflow velocities
of up to 20 m/s
Inert to fungal and bacterial growth

Order options

05/2015 DE/en

Type
TX
Secondary silencer

Nominal size [mm]


BH

K5 1.2 29

CAK

TOC

1.2

X X CAKtestregistrierung

Secondary silencers for


VAV terminal units

Type CAK

For the reduction of noise in plastic circular ducts,


suitable for all circular VAV terminal units and CAV
controllers, plastic construction for contaminated air
Plastic circular silencers for the reduction of noise in the circular ducts
of extract air systems for aggressive media
Absorption material is non-combustible mineral wool with RAL quality mark,
biosoluble and hence hygienically safe according to the German TRGS 905
(Technical Rules for Hazardous Substances) and EU directive 97/69/EG
Mineral wool faced with non-woven glass fibre as protection against erosion
due to airflow velocities up to 20 m/s
Casing and perforated inner duct are flame-resistant polypropylene (PPs)
to DIN 4102, building class B1
Variant with spigot suitable for circular ducts according to DIN 8077
or DIN 8078
Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class D
Optional equipment and accessories
With flanges on both ends

05/2015 DE/en

K5 1.2 30

Secondary silencers for VAV terminal units

TOC

General information

CAK
Page

Type

CAK

Description

Circular silencer
Type CAK

General information
Order code
Dimensions and weight CAK
Dimensions and weight CAK/.../VF2
Specification text

1.2 31
1.2 32
1.2 33
1.2 34
1.2 35

Basic information and nomenclature

1.3 1

Application
Plastic circular silencers Type CAK
for the reduction of noise in the circular ducts
of air conditioning systems
Suitable for contaminated air
For the reduction of air-regenerated noise
of air terminal units TVRK and TVLK
For the reduction of fan noise

Standards and guidelines


Insertion loss measured according to ISO 7235
Casing air leakage to EN 15727, class D
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Variants
CAK: Circular silencer
VF2: Circular silencer
with flanges on both ends
Nominal sizes
125, 160, 200, 250, 315, 400 mm
Accessories
GZ: Matching flanges for both ends
Special features
Insertion loss measured according to ISO 7235
Absorption material is non-combustible
Parts and characteristics
Casing
Perforated inner tube
Absorption material
Konstruktionsmerkmale
Rundes Gehuse
Rohrstutzen passend fr runde Luftleitungen
nach DIN 8077 oder DIN 8078
Maximaler Betriebsdruck 1000 Pa
Maximale Betriebstemperatur 100 C
Materials and surfaces
Casing and perforated inner duct
are flame-resistant polypropylene (PPs)
to DIN 4102, building class B1
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A2,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre as protection against
erosion through airflow velocities up to 20 m/s
Inert to fungal and bacterial growth

K5 1.2 31

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Order code
Order code

CAK

CAK

CAK / 1601000 / GZ / VF2

Type
CAK Circular silencer
Nominal size [mm]
125
160
200
250
315
400

Matching flange
No entry: none
on both ends (only VF2)
GZ
Type of connection
No entry: spigot
VF2 Flanges on both ends

Length [mm]
500
1000
1500
Order example

CAK/2001000
Nominal size
Length
Type of connection

05/2015 DE/en

200 mm
1000 mm
Spigot

K5 1.2 32

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CAK


Application

Circular silencer for the reduction of noise


Spigot to make connections to the ducting

Dimensions

CAK
L

CAK

For more technical data see Dimensions


the Multileaf Dampers,
Sound Attenuators,
Nominal size
External Weather Louvres
catalogue, chapter K3 6.3.
125
160
200
250
315
400
The table shows
the weight for each
nominal size and length

Dimensions
D

D3

mm
125
160
200
250
315
400

Nominal length
225
250
280
355
415
500

500
1000
1500

L
mm
595
1095
1595

L1
495
995
1495

Weight
500

1000

1500

Nominal size

kg
125
160
200
250
315
400

K5 1.2 33

2.2
2.6
3.2
4.3
4.6
5.2

4.1
4.7
5.8
7.6
8.6
9.3

5.9
6.8
8.5
10.9
12.5
13.4

05/2015 DE/en

Secondary silencers for VAV terminal units

TOC

Dimensions and weight CAK/.../VF2


Circular silencer for the reduction of noise
With flanges to make detachable connections
to the ductwork

Dimensions

CAK/.../VF2

n x 10

For more technical data see Dimensions


the Multileaf Dampers,
Sound Attenuators,
Nominal size
External Weather Louvres
catalogue, chapter K3 6.3.
125
160
200
250
315
400
The table shows
the weight for each
nominal size and length

Application

CAK

Dimensions
D

D3

D1

D2

mm

125
160
200
250
315
400

225
250
280
355
415
500

165
200
240
290
350
445

185
230
270
320
395
475

mm

8
8
8
12
12
16

8
8
8
8
10
10

Nominal length
500
1000
1500

L
mm
595
1095
1595

L1
495
995
1495

Weight
500

1000

1500

Nominal size

kg
125
160
200
250
315
400

05/2015 DE/en

2.5
3.0
3.6
4.9
5.3
6.8

4.4
5.1
6.2
8.2
9.3
10.9

6.2
7.2
8.9
11.5
13.7
15.0

K5 1.2 34

Secondary silencers for VAV terminal units

TOC

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Plastic circular silencers for use in extract air


systems subject to aggressive media;
they reduce the air-regenerated noise
in plastic ducts (absorption principle).
Insertion loss measured according to ISO 7235.
Absorption material is mineral wool
with RAL quality mark RAL-GZ 388.
Spigot, suitable for ducts according to DIN 8077.
Casing air leakage to EN 15727, class D.
Special features
Insertion loss measured according to ISO 7235
Absorption material is non-combustible

Order options

Type
CAK
Circular silencer
Nominal size [mm]
125
160
200
250
315
400

CAK
Materials and surfaces
Casing and perforated inner duct
are flame-resistant polypropylene (PPs)
to DIN 4102, building class B1
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A2,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Faced with glass fibre as protection against
erosion through airflow velocities up to 20 m/s
Inert to fungal and bacterial growth

Matching flange
No entry: none
GZ
on both ends (only VF2)
Type of connection
No entry: spigot
VF2 Flanges on both ends

Length [mm]
500
1000
1500

K5 1.2 35

05/2015 DE/en

Easy

TOC

1.3

X X Easytestregistrierung

Control components
for VAV terminal units

Type Easy

Quick and easy handling


Control components for VAV terminal units,
to be mounted on the terminal unit for easy operation
Simplified ordering and on-site assignment to rooms as selection is based on
the nominal size of the duct
Rapid volume flow rate setting without additional device
Indicator light simplifies functional checking
Proven technology of the Compact volume flow controllers
Suitable for constant and variable volume flows
as well as for min / max switching

05/2015 DE/en

K5 1.3 1

Control components for VAV terminal units

TOC

General information

Easy
Page

Type

Easy

The Easy principle

General information
Wiring and commissioning

1.3 2
1.3 6

Basic information and nomenclature

1.5 1

Select nominal size

Set flow rates

Green light: Ready!

K5 1.3 2

05/2015 DE/en

Control components for VAV terminal units

TOC

General information
Description

Easyregler LMV-D3A
Example

Easy

Application
Electronic volume flow controllers of Type Easy
are compact, all-in-one control devices
for VAV terminal units
Dynamic differential pressure transducer,
electronic controller, and actuator are fitted
together in one casing
Suitable for different control tasks depending
on how the input for the setpoint value signal
is used
The output signals of the room temperature
controller, central BMS, air quality controller
or similar units control the volume
flow rate setpoint
Override control by means of switches or relays
Volume flow rate actual value is available
as linear voltage signal
Standard filtration in comfort air conditioning
systems allows for use of the controller in the
supply air without additional dust protection.
Since a partial volume flow is passed through
the transducer in order to measure the volume
flow rate, please note:
With heavy dust levels in the room,
suitable extract air filters must be provided.
If the air is polluted with fluff or sticky particles,
or if it contains aggressive media,
Easy controllers cannot be used

Commissioning
Use the potentiometer to set the minimum
or maximum volume flow rate (by others)
Take the adjustment value from the volume flow
rate scale (sticker on each VAV terminal unit)
Comply with the volume flow rate control range,
do not set a volume flow rate which is below
the minimum flow rate
Once the VAV terminal unit has been installed
and wired, and the volume flow rate has been
set, the unit is ready for operation
Remove the transparent cover of the Easy
controller only temporarily for wiring
and commissioning

Signal voltage range


0 10 V DC
Operating modes
Variable volume flow
min: minimum volume flow rate
max: maximum volume flow rate
Constant value
min: constant volume flow rate
max: 100 %

Easy controllers for VAV terminal units


Part number
M466EU1
M466EU2
M466ES1
M466DC3
M466ES3
M466ES2

05/2015 DE/en

Type

Type of VAV terminal unit


LMV-D3AL-F
227V-024T-05-013
LMV-D3A-F
227V-024T-05-002
SMV-D3A
LMV-D3A

LVC
LVC
TVR
TVR
TVJ, TVT
TZ-Silenzio, TA-Silenzio, TVZ, TVA

K5 1.3 3

Control components for VAV terminal units

TOC

General information

Functional description
The volume flow rate is determined by measuring
the differential pressure (effective pressure).
For this purpose the VAV terminal unit is fitted
with a differential pressure sensor.
The integral differental pressure transducer
transforms the effective pressure into a voltage
signal. The volume flow rate actual value is hence
available as a voltage signal. The factory setting
is such that 10 V DC always corresponds
to the nominal volume flow rate (nom).
The volume flow rate setpoint value comes from
a higher-level controller (e.g. room temperature
controller, air quality controller, central BMS)
or from switch contacts. Variable volume flow
control results in a value between min and max.
It is possible to override the room temperature
control, e.g. by a complete shut-off of the duct.

The controller compares the volume flow rate


setpoint value to the actual value and controls
the integral actuator accordingly.
The volume flow rate parameters min and max
can be set on potentiometers.

Principle of operation Easy and Compact


controllers

Easy controller

Volume flow control


The volume flow controller works independent
of the duct pressure
Differential pressure fluctuations do not result
in permanent volume flow rate changes
To prevent the control from becoming unstable,
a dead band is allowed within which
the damper blade does not move.
The factory set volume flow rate parameters
can be altered by the customer

Differential pressure transducer


Actuator
Volume flow controller
Setpoint value signal

Easy controller
max - Potentiometer
min - Potentiometer
Indicator light
Service button
Connections for effective pressure sensor
Protective cover
Shaft clamp

Illustration shows LMV-D3A-F


Characteristics

Characteristic of the setpoint value signal


min unit

10

Characteristic of the actual value signal

max nom

min

min unit

10

max nom

min

9
8

U [Volt]

w [Volt]

Function

Easy

4
3

10

20

30

40

50

60

70

80

[%]

Soll = w max min) + min


10

K5 1.3 4

90

100

10

20

30

40

50

60

70

80

90

100

[%]

Ist = U Nenn
10

05/2015 DE/en

Control components for VAV terminal units

General information
Technical data

Easy controller
LMV-D3AL-F

TOC

Easy

Easy controller LMV-D3AL-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
3.5 VA max.
2 W max.
120 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 0.5 mA
III (protective extra-low voltage)
IP 20
EMC to 2004/108/EC, low voltage to 2006/95/EC

Easy controller 227V-024T-05-013

Easy controller
227V-024T-05-013

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
5 VA max.
3 W max.
100 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 0.5 mA
III (protective extra-low voltage)
IP 20
EMC according to 2004/108/EC

Easy controller LMV-D3A und LMV-D3A-F

Easy controller
LMV-D3A-F

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
5 VA max.
2.5 W max.
110 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 0.5 mA
III (protective extra-low voltage)
IP 20
EMC according to 2004/108/EC

Easy controller 227V-024T-05-002

Easy controller
227V-024T-05-002

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
5 VA max.
3 W max.
100 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 0.5 mA
III (protective extra-low voltage)
IP 20
EMC according to 2004/108/EC

Easy controller SMV-D3A

Easy controller SMV-D3A

05/2015 DE/en

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
6 VA max.
3 W max.
110 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 0.5 mA
III (protective extra-low voltage)
IP 20
EMC according to 2004/108/EC

K5 1.3 5

Control components for VAV terminal units

TOC

Wiring and commissioning


Electrical connection

Easy

Terminal connections

Setpoint value signal 0 20 mA


0,5 W
2
~
+

2
~
+

U
Easy

1 , :
2 ~, +:
3 w:
4 U:

Room temperature controller


~ y

2
~
+

2
~
+

4
U

3
w

2
~
+

Easy

Constant volume flow control

Variable volume flow control

2
~
+

Setpoint value signal 0 20 mA

Ground
Supply voltage 24 V
Setpoint value signal 0 10 V DC
Actual value signal 0 10 V DC

24 V

4
U

3
w

24 V

2
~
+

2
~
+

3
w

4
U
Easy

Easy

The supply voltage and the remote room


temperature controller must be connected
as shown.

As soon as the 24 V supply voltage is applied,


the controller runs the set min value as a constant
volume flow rate.

min/max switching for one controller

Override control OPEN/CLOSED

24 V AC

24 V

S2
S3

S1

2
~
+

2
~
+

3
w

4
U
Easy

2
~
+

2
~
+

3
w

4
U
Easy

Diode 1N 4007

Switch S1 enables switching between


the two constant volume flow rates min and max.

05/2015 DE/en

External switches (volt-free contacts) can be used


to OPEN or CLOSE the damper blade,
thereby overriding other control settings
(only for AC voltage).
Switch S2 closed:.............Damper blade CLOSED
Switch S3 closed:................. Damper blade OPEN
All override controls can be combined both
with each other and with the different
switching options.

K5 1.3 6

Control components for VAV terminal units

TOC

Wiring and commissioning

Easy

Easy controllers connected in parallel

24 V

2
~
+
Easy

K5 1.3 7

3
w

2
~
+
Easy

3
w

2
~
+

3
w

Easy

05/2015 DE/en

Control components for VAV terminal units

TOC

Wiring and commissioning


Commissioning

Easy

Volume flow rate scale for TVR-Easy

1
D 200

TVR-Easy
%
m/h
l/s

10

200

50

20

30
400
100

40
600
150

50

60

70

800
200

1000
250

300

80

90

1200

100
1400

350

400

Each VAV terminal unit with Easy controller carries a sticker with a volume flow rate scale to determine
the setting values at the customer's site (see example: TVR Easy, nominal size 200).
The percentages refer to the control range that can be used.
Constant volume flow control

Variable volume flow control

The required volume flow rates must be set


by others. If min is set higher than max, min
is provided as a constant volume flow rate even
if a setpoint value signal is transmitted.

The constant volume flow rate is set using


the min potentiometer. The setting of the
max potentiometer is in this case irrelevant.

Control input signal from the central BMS

Factory setting

To have the central BMS determine the volume


flow rate, the min potentiometer must be set
to 0 % and the max potentiometer to 100 %.
If the setpoint value signal falls below 0.1 V DC,
the damper blade closes (shut-off). Since
the setpoint signal may or may not fall below
0.1 V DC, override control is recommended
for shut-off.

05/2015 DE/en

Units are delivered with settings


min = 40 % and max = 80 %.

K5 1.3 8

Compact

TOC

1.3

X X Compacttestregistrierung

Control components
for VAV terminal units

Type Compact

With service interface and bus communication facility


Compact device for use with VAV terminal units
Controller, differential pressure transducer,
and actuator are fitted together in one casing
Volume flow rates min and max are factory set as parameters

Ideal for carrying out service from the switch cabinet or control panel
Change of parameters using adjustment devices
Suitable for constant and variable volume flows
as well as for min / max switching

Bus communication is possible due to MP bus or LonWorks interfaces

05/2015 DE/en

K5 1.3 9

Control components for VAV terminal units

TOC

General information

Compact
Page

Type

Compact

Description

Compact controller
LMV-D3-MP-F

General information
Special information BC0, BF0
Special information BL0
Special information XB0, XG0
Special information LN0, LY0

1.3 10
1.3 12
1.3 18
1.3 21
1.3 26

Basic information and nomenclature

1.5 1

Application
Electronic volume flow controllers
of Type Compact are compact, all-in-one
control devices for VAV terminal units
Dynamic differential pressure transducer,
electronic controller, and actuator are fitted
together in one casing
Suitable for different control tasks depending
on how the input for the setpoint value signal
is used
The output signals of the room temperature
controller, central BMS, air quality controller
or similar units control the volume flow rate
setpoint
Override control by means of switches or relays
Volume flow rate actual value is available
as linear voltage signal
Controller parameters are factory set

Commissioning
On-site adjusting is not required
Integration of voltage signals
into the central BMS
If data transmission via bus interfaces
is required, a system integrator should be
involved in commissioning

Standard filtration in comfort air conditioning


systems allows for use of the controller in
the supply air without additional dust protection.
Since a partial volume flow is passed through
the transducer in order to measure the volume
flow rate, please note:

Example

With heavy dust levels in the room,


suitable extract air filters must be provided.
If the air is polluted with fluff or sticky particles
or contains aggressive media,
Compact controllers cannot be used

Any attachments must be


defined with the order code
of the VAV terminal unit.

Compact controllers for VAV terminal units


Order code detail

Part number

BC0
BC0
BC0
BC0
BF0
BL0
BL0
XB0
XG0
LN0
LY0

M466BA0
A00000043141
A00000043140
A00000043142
A00000043140
M466ES7
M466ES8
M466DC1
M466DC1
M466EG7
M466EG7

Type
LMV-D3L-MP-F
LMV-D3-MP-F
LMV-D3-MP
NMV-D3-MP
LMV-D3-MP
LMV-D3LON
NMV-D3LON
227V-024-10
227V-024-10
GLB181.1E/3
GLB181.1E/3

Type of VAV terminal unit

LVC
TVR
TVJ, TVT
TZ-Silenzio, TA-Silenzio, TVZ, TVA
TVM

K5 1.3 10

05/2015 DE/en

Control components for VAV terminal units

TOC

General information
Function

Compact

Functional description
The volume flow rate is determined by measuring
the differential pressure (effective pressure).
For this purpose the VAV terminal unit is fitted
with a differential pressure sensor.
The integral differental pressure transducer
transforms the effective pressure into a voltage
signal. The volume flow rate actual value is hence
available as a voltage signal. The factory setting
is such that 10 V DC always corresponds
to the nominal volume flow rate (nom).
The volume flow rate setpoint value comes from
a higher-level controller (e.g. room temperature
controller, air quality controller, central BMS)
or from switch contacts. Variable volume flow
control results in a value between min and max.
It is possible to override the room temperature
control, e.g. by a complete shut-off of the duct.
The controller compares the volume flow rate
setpoint value to the actual value and controls
the integral actuator accordingly.
Volume flow rate parameters and voltage ranges
are factory stored in the controller. Changes on
the customer's site can easily be carried out using
an adjustment device, a notebook with service
tool, or a bus interface.

Volume flow control


The volume flow controller
works independent of the duct pressure
Differential pressure fluctuations do not result
in permanent volume flow rate changes
To prevent the control from becoming unstable,
a dead band is allowed within which
the damper blade does not move.

Principle of operation Easy and Compact


controllers

Differential pressure transducer


Actuator
Volume flow controller
Setpoint value signal

05/2015 DE/en

K5 1.3 11

Control components for VAV terminal units

TOC

Special information BC0, BF0

Description

... / BC0 / ...


Order code detail

... / BF0 / ...


Order code detail
For detailed information
on adjustment devices
see chapter K5 1.4

Application
Electronic volume flow controller LMV-D3L-MPF, LMV-D3-MP, LMV-D3-MP-F or NMV-D3-MP
as Compact controller
Variable air or constant air volume flow control
The flow rate is measured using the dynamic
measurement principle
Voltage range for the actual and setpoint
value signals 0 10 V DC or 2 10 V DC
MP bus interface: Up to eight users
can be addressed on an MP bus (LAN).
This allows for the integration with higher-level
systems (LonWorks, EIB-Konex, Modbus RTU
and BACnet); as an alternative, a DDC
controller with MP bus interface can control
the Compact controller.
Controller with NFC technology, i.e. settings
and operating values can be read out using
a smartphone app
Construction
BC0: LMV-D3L-MP-F fr LVC
BC0: LMV-D3-MP-F for TVR
BC0: NMV-D3-MP for TVJ, TVT
BC0: LMV-D3-MP for TZ-Silenzio,
TA-Silenzio, TVZ, TVA
BF0: LMV-D3-MP for TVM
Useful additions
AT-VAV-B: Adjustment device

Compact
Operating modes
E: Single and M: Master
min: minimum volume flow rate
max: maximum volume flow rate
S: Slave
min: 0 %
max: Volume flow rate ratio
to the master controller
F: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation and wiring
the controller is ready for use
on the analog interface
If the MP bus interface is used, additional
commissioning steps are required

Signal voltage range


0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.1 V DC)

Technical data

Compact controller LMV-D3L-MP-F


Supply voltage (AC
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
3.5 VA max.
2 W max.
5 Nm
120 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 54
EMC to 2004/108/EC, low voltage to 2006/95/EC
0.5 kg

Compact controller
LMV-D3L-MP-F

K5 1.3 12

05/2015 DE/en

Control components for VAV terminal units

Special information BC0, BF0

TOC

Compact

Compact controller LMV-D3-MP und LMV-D3-MP-F


Supply voltage (AC
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
4 VA max.
2 W max.
5 Nm
110 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.5 kg

Compact controller
LMV-D3-MP-F

Compact controller NMV-D3-MP


Supply voltage (AC
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
5.5 VA max.
3 W max.
10 Nm
110 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.7 kg

Compact controller
NMV-D3-MP

05/2015 DE/en

K5 1.3 13

Control components for VAV terminal units

TOC

Special information BC0, BF0


VAV-Compact

VAV-Compact
Gear release button
Connections for differential pressure sensor
Service socket
Blade shaft clamp
Rotation stop
Indicator lights
Connecting cable

Characteristics

Characteristic of the setpoint value signal

Characteristic of the actual value signal


nom (100%)

nom (100%)

min

Setting range

Volume flow

max

Volume flow

Function

Compact

min unit

min unit
0

0 10 V DC
2 10 V DC

10 V DC

Setpoint value signal

0 10 V DC
setpoint = w max min) + min
10

2 10 V DC
setpoint = w 2 max min) + min
8

K5 1.3 14

10 V DC

0 10 V DC
2 10 V DC

Actual value signal U5

0 10 V DC
actual = U5 nom
10

2 10 V DC
actual = U5 2 nom
8

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information BC0, BF0


Electrical connection

Compact

Connecting cable core identification


BK

1 , :
2 ~, +:
3 w:
5 U5/MP:

RD

WT

OR

U5/MP

Compact

Ground, neutral
Supply voltage
Setpoint value signal and override control
Actual value signal and communication

Compact: LMV-D3-MP, LMV-D3-MP-F,


NMV-D3-MP, LMV-D3L-MP-F

... / BC0 / ...

Variable volume flow control and override control, voltage signal 0 to 10 V DC

Order code detail

Room temperature
controller
y
~

24 V

S5 S4 S3

S1

5
Compact

Operating mode E, M, F

Slave controller Compact


Operating mode S

Switch functions
S1 Room temperature control
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC)
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Compact: LMV-D3-MP, LMV-D3-MP-F, NMV-D3-MP, LMV-D3L-MP-F

05/2015 DE/en

K5 1.3 15

Control components for VAV terminal units

TOC

Special information BC0, BF0

... / BC0 / ...

Compact

Variable volume flow control and override control, voltage signal 2 to 10 V DC

Order code detail

Room temperature
controller
y
~

24 V

S5 S4 S3

S2

S1

5
Compact

Operating mode E, M, F

Slave controller Compact


Operating mode S

Switch functions
S1 Room temperature control
S2 Shut-off CLOSED
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC)
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Compact: LMV-D3-MP, LMV-D3-MP-F, NMV-D3-MP, LMV-D3L-MP-F

K5 1.3 16

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information BC0, BF0


... / BF0 / ...

Compact

Dual duct terminal units Type TVM

Order code detail


Room temperature
controller
y
~

24 V

TVM

Compact controller for warm air duct

Compact controller for cold air duct

Operating mode E, M, F

3
Folgeregler Compact
Operating mode S

Compact: LMV-D3-MP, LMV-D3-MP-F, NMV-D3-MP, LMV-D3L-MP-F

05/2015 DE/en

K5 1.3 17

Control components for VAV terminal units

TOC

Special information BL0

Description

... / BL0
Order code detail
For detailed information
on adjustment devices
see chapter K5 1.4

Application
Electronic volume flow controller LMV-D3LON
or NMV-D3LON as Compact controller
Variable air or constant air volume flow control
The flow rate is measured using the dynamic
measurement principle
Voltage range for the actual value signal
2 10 V DC
Volume flow controller
with LonMark certification
LonWorks interfaces for the transmission
of standard network variables
Functional profiles: Node-Object #0,
Damper-Actuator-Object #8110,
Open-Loop-Sensor-Object #1
and Thermostat-Object #8060
The Thermostat-Object #8060
enables individual room control
A plug-in for all LNS-based network integration
tools (LNS version 3.3 and higher) is available
for configuration

Compact
Useful additions
AT-VAV-B: Adjustment device
Signal voltage range
Actual value signal
2: 2 10 V DC
Commissioning
A trained LonWorks systems integrator must
carry out the integration into the overall system

Construction
BL0: LMV-D3LON for TVR, TZ-Silenzio,
TA-Silenzio, TVZ, TVA
BL0: NMV-D3LON for TVJ, TVT

Technical data

Compact controller LMV-D3LON


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Communication
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
4.5 VA max.
2.5 W max.
5 Nm
110 150 s
LonWorks-Transceiver FTT-10A, free topology, twisted pair
2 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.5 kg

Compact controller
LMV-D3LON

K5 1.3 18

05/2015 DE/en

Control components for VAV terminal units

Special information BL0

TOC

Compact

Compact controller NMV-D3LON


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Communication
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
6 VA max.
3,5 W max.
10 Nm
110 150 s
LonWorks-Transceiver FTT-10A, free topology, twisted pair
2 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.7 kg

Compact controller
NMV-D3LON

Function

VAV-Compact

VAV-Compact
Gear release button
Connections for differential pressure sensor
Service socket
Blade shaft clamp
Rotation stop
Indicator lights and LonWorks service button
Connecting cable

05/2015 DE/en

K5 1.3 19

Control components for VAV terminal units

TOC

Special information BL0

Characteristic of the actual value signal


nom (100%)

Setting range

Volume flow

Characteristics

Compact

min unit

10 V DC

Actual value signal U5

2 10 V DC
actual = U5 2 nom
8

Electrical connection

Connecting cable core identification


BK RD WT OR PK GR
1

2
~
+

Y MFT LON LON


Compact

1 , :
Ground, neutral
2 ~, +:
Supply voltage
3 Y:
Connection of external sensor or switch
5 MFT: Actual value signal and communication
6, 7 LON: LonWorks
Compact: LMV-D3LON, NMV-D3LON

Volume flow control

24 V
LonWorks

Compact

Compact: LMV-D3LON, NMV-D3LON

K5 1.3 20

05/2015 DE/en

Control components for VAV terminal units

Special information XB0, XG0

Description

... / XB0 / ...


Order code detail

... / XG0 / ...


Order code detail
For detailed information
on adjustment devices
see chapter K5 1.4

Application
Electronic volume flow controller 227V-024-10
as Compact controller
Variable air or constant air volume flow control
The flow rate is measured using the dynamic
measurement principle
Voltage range for the actual and setpoint value
signals 0 10 V DC or 2 10 V DC

TOC

Compact
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation and wiring
the controller is ready for use

Construction
XB0: 227V-024-10 for TVR, TVJ, TVT,
TZ-Silenzio, TA-Silenzio, TVZ, TVA
BG0: 227V-024-10 for TVM
Useful additions
AT-VAV-G: Adjustment device
Signal voltage range
0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.8 V DC)
Operating modes
E: Single and M: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S: Slave operation
min: 0 %
max: Volume flow rate ratio
to the master controller
F: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.

Technical data

Compact controller 227V-024-10


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
5.5 VA max.
3 W max.
10 Nm
100 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 0.5 mA
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC
0.570 kg

Compact controller
227V-024-10

K5 1.3 21

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information XB0, XG0


Function

Compact

VAV-Compact

VAV-Compact
Connections for differential pressure sensor
Gear release button
Service socket
Connecting cable

Characteristics

Characteristic of the setpoint value signal

Characteristic of the actual value signal


nom (100%)

nom (100%)

min

Setting range

Volume flow

Volume flow

max

min unit
0

10 V DC

0 10 V DC
2 10 V DC

Setpoint value signal Y

0 10 V DC
setpoint = Y max min) + min
10

2 10 V DC
setpoint = Y 2 max min) + min
8

05/2015 DE/en

min unit
0

0 10 V DC
2 10 V DC

10 V DC

Actual value signal U

0 10 V DC
actual = U nom
10

2 10 V DC
actual = U 2
8

nom

K5 1.3 22

Control components for VAV terminal units

TOC

Special information XB0, XG0

Electrical connection

Compact

Connecting cable core identification


BL

BR

BK

GR

2
+
~

Y/Z

U/pp
Compact

1 , :
2 ~, +:
3 Y/Z:
4 U/pp:

Ground, neutral
Supply voltage
Setpoint value signal and override control
Actual value signal and communication

Compact: 227V-024-10

... / XB0 / ...

Variable volume flow control and override control, voltage signal 0 to 10 V DC

Order code detail

Room temperature
controller
y
~

24 V

S5 S4 S3

S1

4
Compact

Operating mode E, M, F

4
Compact

Operating mode E, M, F

Switch functions
All OPEN: Minimum volume flow rate min
S1 Room temperature control
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC)

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Compact: 227V-024-10

K5 1.3 23

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information XB0, XG0


... / XB0 / ...

Compact

Variable volume flow control and override control, voltage signal 2 to 10 V DC

Order code detail

Room temperature
controller
y
~

24 V AC

S5 S4 S3

S2

S1

4
Compact

Operating mode E, M, F

4
Compact

Operating mode E, M, F

Switch functions
S1 Room temperature control
S2 Shut-off CLOSED
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC)
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Compact: 227V-024-10

05/2015 DE/en

K5 1.3 24

Control components for VAV terminal units

TOC

Special information XB0, XG0

... / XG0 / ...

Compact

Dual duct terminal units Type TVM

Order code detail

Room temperature
controller
y
~

24 V

TVM

Compact controller for warm air duct

Compact controller for cold air duct

Operating mode E, M, F

3
Slave controller Compact
Operating mode S

Compact: 227V-024-10

K5 1.3 25

05/2015 DE/en

Control components for VAV terminal units

Special information LN0, LY0


Description

... / LN0 / ...


Order code detail

... / LY0 / ...


Order code detail
For detailed information
on adjustment devices
see chapter K5 1.4

Application
Electronic volume flow controller GLB181.1E/3
as Compact controller
Variable air or constant air volume flow control
The flow rate is measured using
the dynamic measurement principle
Voltage range for the actual
and setpoint value signals 0 10 V DC
For room temperature controllers
with output signal 0 10 V DC

TOC

Compact
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation
and wiring the controller is ready for use

Construction
LN0: GLB181.1E/3 for TVR, TVJ, TVT,
TZ-Silenzio, TA-Silenzio, TVZ, TVA
LY0: GLB181.1E/3 for TVM
Useful additions
AT-VAV-S: Adjustment device
Signal voltage range
0: 0 10 V DC
Operating modes
E: Single and M: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S: Slave
min: 0 %
max: Volume flow rate ratio
to the master controller
F: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.

Technical data

Compact controller GLB181.1E/3


Supply voltage (AC)
Power rating (AC)
Torque
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
3 VA max.
10 Nm
125 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, max. 1 mA
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.6 kg

Compact controller
GLB 181.1E/3

05/2015 DE/en

K5 1.3 26

Control components for VAV terminal units

TOC

Special information LN0, LY0


VAV-Compact

Rotation stop
Blade shaft clamp
Position indicator
Service socket
Gear release button
Connections for differential pressure sensor
Connecting cable

Characteristics

Characteristic of the setpoint value signal

Characteristic of the actual value signal

Nenn (100%)

Nenn (100%)

Volumenstrom

Einstellbereich

max

Volumenstrom

Function

Compact

min
min Gert

min Gert
10 V DC

0 10 V DC

Sollwertsignal YC

0 10 V DC
setpoint = YC max min) + min
10

K5 1.3 27

10 V DC

0 10 V DC

Istwertsignal U

0 10 V DC
actual = U nom
10

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information LN0, LY0


Electrical connection

Compact

Connecting cable core identification

1
G

VI OR GR PK

RD BK

G0 Y1 Y2 YC

Compact

1 G:
2 G0:
6 Y1:
7 Y2:
8 YC:
9 U:

Supply voltage
Ground, neutral
Override control
Override control
Setpoint value signal and communication
Actual value signal

Compact: GLB181.1E/3

... / LN0 / ...

Variable volume flow control


and override control

Order code detail

Room temperature
controller
G G0 Y

24 V AC

S1

G0

S2

Y1

Y2

YC

Compact

G0

Y1

Y2

YC

Slave controller Compact

Switch functions
S1 Damper blade OPEN
S2 Damper blade CLOSED
S1 und S2
Maximum volume flow rate max
All OPEN: Room temperature control
or minimum volume flow rate min

Compact: GLB181.1E/3

05/2015 DE/en

K5 1.3 28

Control components for VAV terminal units

TOC

Special information LN0, LY0

... / LN0 / ...

Compact

Dual duct terminal unit Type TVM

Order code detail

Room temperature
controller
y
G0
G

24 V AC

TVM

G0

Y1

Y2

YC

Compact controller for cold air duct

Y1

G0

Y2

YC

Compact controller for warm air duct

Operating mode E, M, F

G0

Y1

Y2

YC

Slave controller Compact


Operating mode S

Compact: GLB181.1E/3

K5 1.3 29

05/2015 DE/en

Universal, dynamic

X X Universal,

TOC

1.3

dynamictestregistrierung

Control components
for VAV terminal units

Type Universal, dynamic

For different actuators


Modular control components for VAV terminal units
Module selection based on application
Actuators with selected actuator forces
Options
Actuators with safety function for 'damper blade OPEN'
and 'damper blade CLOSED' (spring return actuators)

05/2015 DE/en

K5 1.3 30

Control components for VAV terminal units

TOC

General information

Universal, dynamic

Type

Page

Universal, dynamic

Description

Universal controller VRD3


Example

Any attachments must be


defined with the order code
of the VAV terminal unit.

General information
Special information B1*, B27
Special information XC3

1.3 31
1.3 33
1.3 39

Basic information and nomenclature

1.5 1

Application
Electronic volume flow controllers
of Type Universal (dynamic) are designed
for use with VAV terminal units.
Dynamic differential pressure transducer
and electronic controller are fitted together
in one casing
Actuator or spring return actuator is separate
The output signals of the room temperature
controller, central BMS, air quality controller
or similar units control the volume flow rate
setpoint
Override control by means of switches or relays
Volume flow rate actual value is available
as linear voltage signal
Controller parameters are factory set
On-site adjusting is not required
Standard filtration in comfort air conditioning
systems allows for use of the controller
in the supply air without additional dust protection.
Since a partial volume flow is passed through
the transducer in order to measure
the volume flow rate, please note:
With heavy dust levels in the room,
suitable extract air filters must be provided
If the air is polluted with fluff or sticky particles
or contains aggressive media,
Universal (dynamic) controllers cannot be used

Universal controller, dynamic, for VAV terminal units


Order code detail

Controller
Part number

Actuator

Type

B13
B11

M546GA4
M546GA4

VRD3
VRD3

B1B

M546GA4

VRD3

B27

M546GA4

VRD3

XC3

M546ED4 GUAC-D3

Part number

Type

M466DJ8
M466DG8

NM24A-V
SM24A-V
NF24A-V
M466DR1
(spring return actuator)
M466DJ8
NM24A-V

A00000028400

381C-024-20-V-004
(spring return actuator)

Type of VAV
terminal unit

TVR
TVJ
TVT
TZ-Silenzio, TA-Silenzio, TVZ, TVA
TVM

K5 1.3 31

05/2015 DE/en

Control components for VAV terminal units

TOC

General information
Function

Universal, dynamic

Functional description
The volume flow rate is determined by measuring
the differential pressure (effective pressure).
For this purpose the VAV terminal unit is fitted
with a differential pressure sensor.
The integral differental pressure transducer
transforms the effective pressure into a voltage
signal. The volume flow rate actual value is hence
available as a voltage signal. The factory setting
is such that 10 V DC always corresponds
to the nominal volume flow rate (nom).
The volume flow rate setpoint value comes from
a higher-level controller (e.g. room temperature
controller, air quality controller, central BMS)
or from switch contacts. Variable volume flow
control results in a value between min and max.
It is possible to override the room temperature
control, e.g. by a complete shut-off of the duct.
The controller compares the volume flow rate
setpoint value to the actual value and controls
the integral actuator accordingly.
The volume flow rate parameters min and max
are factory set on potentiometers. Voltage ranges
are factory stored in the controller. Changes on
the customer's site can easily be carried out using
an adjustment device or a notebook with service
tool.

Volume flow control


The volume flow controller works independent
of the duct pressure
Differential pressure fluctuations do not result
in permanent volume flow rate changes
To prevent the control from becoming unstable,
a dead band is allowed within which
the damper blade does not move.
The factory set volume flow rate parameters
can be altered by the customer

Principle of operation Universal

Differential pressure transducer


Actuator
Volume flow controller
Setpoint value signal

05/2015 DE/en

K5 1.3 32

Control components for VAV terminal units

Special information B1*, B27

Description

... / B1* / ...


Order code detail

... / B27 / ...


Order code detail

Application
Electronic volume flow controller VRD3
as Universal controller
Variable air or constant air volume flow control
The flow rate is measured using the dynamic
measurement principle
Voltage range for the actual and setpoint value
signals 0 10 V DC or 2 10 V DC
Separate inputs for override controls enable the
centralised switching of groups of controllers

TOC

Universal, dynamic
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation and wiring
the controller is ready for use
The volume flow rate parameters min and max
can be adjusted at a later stage using
a potentiometer or an adjustment device

Construction
Volume flow controller VRD3 with
B13: Actuator NM24A-V for TVR, TVJ,
TZ-Silenzio, TA-Silenzio TVZ, TVA
B11: Actuator SM24A-V for TVT
B1B: Spring return actuator NF24A-V for TVR,
TVJ, TVT, TZ-Silenzio, TA-Silenzio TVZ, TVA
B27: Actuator NM24A-V for TVM
Useful additions
AT-VAV-B: Adjustment device
Signal voltage range
0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.1 V DC)
Operating modes
E: Single and M: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S: Slave operation
min: 0 %
max: Volume flow rate ratio
to the master controller
F: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.
The jumper for input w is factory set to VRD3.

Technical data

Volume flow controller VRD3


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
without actuator max. 3.5 VA
without actuator max. 2 W
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 40
EMC according to 2004/108/EC
0.440 kg

Universal controller VRD3

K5 1.3 33

05/2015 DE/en

Control components for VAV terminal units

Special information B1*, B27

TOC

Universal, dynamic

Actuators NM24A-V and NM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


5.5 VA max.
4 W max.
10 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.710 kg

Actuator NM24A-V

Actuators SM24A-V and SM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


6 VA max.
4 W max.
20 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.910 kg

Actuator NM24A-V

05/2015 DE/en

K5 1.3 34

Control components for VAV terminal units

TOC

Special information B1*, B27

Universal, dynamic

Spring return actuators NF24A-V and NF24A-V-ST

Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


9 VA max.
6.5 W max.
10 Nm
< 75 s
< 20 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
1.91 kg

Spring return actuator


NF24A

Function

VRD3

Controller VRD3
max potentiometer
min potentiometer
Service socket
Jumper for input w
Actuator cable
Cable bushings for supply voltage,
setpoint value signal and actual value signal
Indicator light
Connections for differential pressure sensor

K5 1.3 35

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information B1*, B27


Characteristics

Characteristic of the setpoint value signal

Universal, dynamic
Characteristic of the actual value signal

Nenn (100%)

Nenn (100%)

min

Einstellbereich

Volumenstrom

Volumenstrom

max

min Gert

min Gert
0

0 10 V DC
2 10 V DC

Wiring

10 V DC

Sollwertsignal w

10 V DC

0 10 V DC
2 10 V DC

Istwertsignal U5

0 10 V DC

0 10 V DC

Soll = w max min) + min


10

Ist = U5 Nenn
10

2 10 V DC

2 10 V DC

Soll = w 2 max min) + min


8

Ist = U5 2 Nenn
8

Terminal connections

2
~
+

3
w

4 5 6
PP U5 z1

7
z2

Universal

Plug connection for actuator


Plug connection for adjustment device
1 , :
Ground, neutral
2 ~, +:
Supply voltage
3 w:
Setpoint value signal
4 PP:
Connection for adjustment device
5 U5:
Actual value signal
6 z1:
Override control 1 (OPEN)
7 z2:
Override control 2 (CLOSE, min, max)
Universal: VRD3

05/2015 DE/en

K5 1.3 36

Control components for VAV terminal units

TOC

Special information B1*, B27

... / B1* / ...

Universal, dynamic

Variable volume flow control and override control

Order code detail

Raumtemperaturregler

~
y

24 V

S4 S3 S2 S1
1

Universal
Betriebsart E, M, F

Folgeregler Universal
Betriebsart S

Switch functions
S1 Shut-off CLOSED
S2 Maximum volume flow rate max
S3 Minimum volume flow rate min
(only with supply voltage 24 V AC)
S4 Damper blade OPEN
All OPEN: Variable volume flow

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: VRD3

K5 1.3 37

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information B1*, B27


... / B27 / ...

Universal, dynamic

Dual duct terminal units Type TVM

Order code detail

24 V

Raumtemperaturregler
~
y

TVM

Kaltregler Universal

Warmregler Universal

Betriebsart E, M, F

Folgeregler Universal
Betriebsart S

Universal: VRD3

05/2015 DE/en

K5 1.3 38

Control components for VAV terminal units

Special information XC3

Description

... / XC3 / ...


Order code detail

Application
Electronic volume flow controller GUAC-D3
as Universal controller
Variable air or constant air volume flow control
The flow rate is measured using
the dynamic measurement principle
Voltage range for the actual and setpoint
value signals 0 10 V DC or 2 10 V DC
Construction
XC3: Volume flow controller GUAC-D3 with spring
return actuator 381C-024-20-V-004 for TVR, TVJ,
TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA
Useful additions
AT-VAV-G: Adjustment device
Signal voltage range
0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.8 V DC)

Technical data

Universal controller
GUAC-D3

TOC

Universal, dynamic
Operating modes
E: Single and M: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S: Slave operation
min: 0 %
max: Volume flow rate ratio
to the master controller
F: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation and wiring
the controller is ready for use
The volume flow rate parameters min and max
can be adjusted at a later stage using
a potentiometer or an adjustment device

Volume flow controller GUAC-D3


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
without actuator max. 1.2 VA
without actuator max. 0.6 W
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Spring return actuator 381C-024-20-V-004


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


10 VA max.
7.5 W max.
20 Nm
150 s
< 15 s
from the controller
III (protective extra-low voltage)
IP 54 (cable entry at the bottom)
EMC according to 2004/108/EC
1.8 kg

Spring return actuator


381C-024-20-V-004

K5 1.3 39

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information XC3


Function

Universal, dynamic

Universal controller GUAC-D3

Connection for actuator


Service socket
Connection of supply voltage,
setpoint value signal and actual value signal
Connections for differential pressure sensor

Characteristics

Characteristic of the setpoint value signal

Characteristic of the actual value signal


Nenn (100%)

Nenn (100%)

min

Einstellbereich

Volumenstrom

Volumenstrom

max

min Gert

min Gert
0

10 V DC

0 10 V DC
2 10 V DC

Sollwertsignal Y

0 10 V DC
2 10 V DC

10 V DC

Istwertsignal U

0 10 V DC

0 10 V DC

Soll = Y max min) + min


10

Ist = U Nenn
10

2 10 V DC
Soll = Y 2 max min) + min
8

05/2015 DE/en

2 10 V DC
Ist = U 2
8

Nenn

K5 1.3 40

Control components for VAV terminal units

TOC

Special information XC3

Wiring

Universal, dynamic

Terminal connections

... / XC3 / ...


Order code detail

BU

BN
+
~

BK
Y/Z

GY
U/PP
Universal

BU , :
BN ~, +:
BK Y/Z:
GY U/PP:

Ground, neutral
Supply voltage
Setpoint value signal and override control
Actual value signal and communication

Universal: GUAC-D3, GUAC-S3, GUAC-P1, GUAC-P6

... / XC3 / ...


Order code detail

Variable volume flow control and override control, voltage signal 0 to 10 V DC


Raumtemperaturregler
~
y

24 V

S5 S4 S3

BU

BN

BK

S1

GY
Universal

Betriebsart E,M, F

BU

BN

BK

GY

Folgeregler Universal
Betriebsart S

Switch functions
S1 Room temperature control
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC);
takes priority over all other override controls
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: GUAC-D3, GUAC-S3

K5 1.3 41

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information XC3


... / XC3 / ...
Order code detail

Universal, dynamic

Variable volume flow control and override control, voltage signal 2 to 10 V DC


Raumtemperaturregler

~
y

24 V

S5 S4 S3

BU

BN

BK

S2

S1

GY
Universal

Betriebsart E, M, F

BU

BN

BK

GY

Folgeregler Universal
Betriebsart S

Switch functions
S1 Room temperature control
S2 Shut-off CLOSED
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC);
takes priority over all other override controls
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: GUAC-D3, GUAC-S3

05/2015 DE/en

K5 1.3 42

Universal, static

X X Universal,

TOC

1.3

statictestregistrierung

Control components
for VAV terminal units

Type Universal, static

For contaminated extract air or for pressure control


Modular control components for VAV terminal units,
especially for aggressive media in extract air systems
Module selection based on application
Actuators with selected actuator forces
Options
Actuators with safety function for 'damper blade OPEN'
and 'damper blade CLOSED' (spring return actuators)

05/2015 DE/en

K5 1.3 43

Control components for VAV terminal units

TOC

General information

Universal, static

Type

Page

Universal, static

General information
Volume flow control BP*
Volume flow control BB*
Volume flow control XD*
Differential pressure control BR*, BS*
Differential pressure control BG*, BH*
Differential pressure control XE*, XF*

1.3 44
1.3 48
1.3 54
1.3 59
1.3 64
1.3 70
1.3 75

Basic information and nomenclature

1.5 1

Application
Electronic volume flow controllers of Type
Universal (static) are designed for use
with VAV terminal units.
Volume flow control or differential pressure
control based on static differential pressure
measurement
Dynamic differential pressure transducer
and electronic controller can be fitted together
in one casing or in separate casings
Actuator or spring return actuator is separate
The output signals of the room temperature
controller, central BMS, air quality controller
or similar units control the volume flow rate
setpoint
Override control by means of switches or relays
Volume flow rate actual value or differential
pressure actual value is available as linear
voltage signal
Controller parameters are factory set
On-site adjusting is not required
Please note that in critical cases,
material compatibility testing must be carried
out on the air terminal unit and the differential
pressure transducer, taking into consideration
the harmful substances involved
and the concentrations in which they occur.

Description

Universal controller
VRP-M
Example

Maintenance
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Universal controller, static, for VAV terminal units, volume flow control
Order code
detail

Controller
Part number

Static differential pressure transducer

Type

Part number

Type

Actuator
Part number

BP3
BP1

M466EN6
M466EN6

VRP-M
VRP-M

M546EJ1
M546EJ1

VFP-300
VFP-300

M466EQ9
M466ER0

BPB

M466EN6

VRP-M

M546EJ1

VFP-300

M466DR2

BPG

M466EN6

VRP-M

M546EJ1

VFP-300

M466EQ2

BPG

M466EN6

VRP-M

M546EJ1

VFP-300

M466EQ3

BB3
BB1

M546EG2
M546EG2

VRP
VRP

M546EJ1
M546EJ1

VFP-300
VFP-300

M466DJ8
M466DG8

BBB

M546EG2

VRP

M546EJ1

VFP-300

M466DR1

XD1

M546ED5 GUAC-S3

Included with GUAC-S3

M466EL7

XD3

M546ED5 GUAC-S3

Included with GUAC-S3 A00000028400

VAV terminal units


Type

NM24A-V-ST
SM24A-V-ST
NF24A-V-ST
spring return actuator
LMQ24A-SRV-ST
fast-running actuator
NMQ24A-SRV-ST
fast-running actuator
NM24A-V
SM24A-V
NF24A-V
spring return actuator
227-024-08-V
381C-024-20-V-004
spring return actuator

TVR, TVZ, TVA up to nominal size 250


TVR, TVZ, TVA from nominal size 315
TVJ
TVT
TZ-Silenzio, TA-Silenzio
TVRK up to nominal size 250
TVRK from nominal size 315
TVLK

K5 1.3 44

05/2015 DE/en

Control components for VAV terminal units

TOC

General information

Universal, static

Universal controller, static, for VAV terminal units, differential pressure control
Order
code
detail

Controller
Part number

Static differential pressure transducer

Type

Part number

Type

Actuator

VAV terminal units

Part number

Type

BR3
BR1

M466EN6
M466EN6

VRP-M
VRP-M

M546EJ6
M546EJ6

VFP-100
VFP-100

M466EQ9
M466ER0

BRB

M466EN6

VRP-M

M546EJ6

VFP-100

M466DR2

BRG

M466EN6

VRP-M

M546EJ6

VFP-100

M466EQ2

BRG

M466EN6

VRP-M

M546EJ6

VFP-100

M466EQ3

BS3
BS1

M466EN6
M466EN6

VRP-M
VRP-M

M546EJ7
M546EJ7

VFP-600
VFP-600

M466EQ9
M466ER0

BSB

M466EN6

VRP-M

M546EJ7

VFP-600

M466DR2

BSG

M466EN6

VRP-M

M546EJ7

VFP-600

M466EQ2

BSG

M466EN6

VRP-M

M546EJ7

VFP-600

M466EQ3

BG3

M546ED1

M546EJ6

VFP-100

M466DJ8

NM24A-V

BG1

M546ED1

M546EJ6

VFP-100

M466DG8

SM24A-V

BGB

M546ED1

M546EJ6

VFP-100

M466DR1

NF24A-V
spring return
actuator

BH3

M546ED1

M546EJ7

VFP-600

M466DJ8

NM24A-V

BH1

M546ED1

M546EJ7

VFP-600

M466DG8

SM24A-V

BHB

M546ED1

VRPSTP

M546EJ7

VFP-600

M466DR1

XE1

M546ED6

GUACP1

NF24A-V
spring return
actuator

Included with GUACP1

M466EL7

227-024-08-V

XE3

M546ED6

GUACP1

Included with GUAC- A0000002840


P1
0

XF1

M546ED7

GUACP6

Included with GUACP6

381C-024-20-V-004
spring return
actuator

M466EL7

227-024-08-V

XF3

M546ED7

GUACP6

Included with GUAC- A0000002840


P6
0

381C-024-20-V-004
spring return
actuator

VRPSTP
VRPSTP
VRPSTP
VRPSTP
VRPSTP

NM24A-V-ST
SM24A-V-ST
NF24A-V-ST
spring return
actuator
LMQ24A-SRV-ST
fast-running actuator
NMQ24A-SRV-ST
fast-running actuator
NM24A-V-ST
SM24A-V-ST
NF24A-V-ST
spring return
actuator
LMQ24A-SRV-ST
fast-running actuator
NMQ24A-SRV-ST
fast-running actuator

TVR up to nominal size 250


TVR from nominal size 315
TVJ
TVT
TZ-Silenzio, TA-Silenzio
TVRK up to nominal size 250
TVRK from nominal size 315
TVRK up to nominal size 250
TVRK from nominal size 315
Any attachments are defined with the order code of the VAV terminal unit.

K5 1.3 45

05/2015 DE/en

Control components for VAV terminal units

TOC

General information
Function
Volume flow control

Universal, static

Functional description
The volume flow rate is determined by measuring
the differential pressure (effective pressure).
For this purpose the VAV terminal unit is fitted
with a differential pressure sensor.
The static differential pressure transducer
transforms the effective pressure into a voltage
signal. The volume flow rate actual value is hence
available as a voltage signal. The factory setting
is such that 10 V DC always corresponds
to the nominal volume flow rate (nom).
The volume flow rate setpoint value comes from
a higher-level controller (e.g. room temperature
controller, air quality controller, central BMS)
or from switch contacts. Variable volume flow
control results in a value between min and max.
It is possible to override the room temperature
control, e.g. by a complete shut-off of the duct.
The controller compares the volume flow rate
setpoint value to the actual value and controls
the actuator accordingly if there is a difference.
The volume flow rate parameters min and max
are set on potentiometers (VRP) or stored in the
controller. Voltage ranges are factory stored in the
controller. Changes on the customer's site can
easily be carried out using a potentiometer, an
adjustment device or a notebook with service tool.

Volume flow control


The volume flow controller works independent
of the duct pressure
Differential pressure fluctuations do not result
in permanent volume flow rate changes
To prevent the control from becoming unstable,
a dead band is allowed within
which the damper blade does not move.
The factory set volume flow rate parameters
can be altered by the customer

Principle of operation Universal TROX/


Belimo

Principle of operation Universal TROX/


Gruner

Differential pressure transducer


Actuator
Volume flow controller
Setpoint value signal

05/2015 DE/en

Differential pressure transducer


Actuator
Volume flow controller
Setpoint value signal

K5 1.3 46

Control components for VAV terminal units

TOC

General information

Functional description
The static differental pressure transducer
transforms the differential pressure into a voltage
signal. The differential pressure actual value
is available as a voltage signal. The factory setting
is such that 10 V DC always corresponds
to the nominal differential pressure (pnom).
The differential pressure setpoint value is either
a constant value or it comes from a setpoint
adjuster or from switch contacts.
The controller compares the differential pressure
setpoint value to the actual value and controls
the actuator accordingly.
The differential pressure parameters are set on
a potentiometer (VRP-STP) or stored in
the controller. Voltage ranges are factory stored
in the controller. Changes on the customer's site
can easily be carried out using a potentiometer,
an adjustment device or a notebook
with service tool.
Constant pressure control
The differential pressure controller
works independent of the duct pressure
Pressure fluctuations do not result
in permanent differential pressure changes
To prevent the control from becoming unstable,
a dead band is allowed within which
the damper blade does not move.
The factory set differential pressure parameters
can be altered by the customer
Variable pressure control
Relays or switch contacts connected
to the control signal input Y/Z can be used
to achieve constant pressures pmin and pmax
or to override various control settings.

Principle of operation Universal TROX/


Belimo

Differential pressure transducer


Actuator
Differential pressure controller
Setpoint value signal
p Differential pressure connection

K5 1.3 47

Principle of operation Universal TROX/


Gruner

Differential
pressure control

Universal, static

Differential pressure transducer


Actuator
Differential pressure controller
Setpoint value signal
p Differential pressure connection

05/2015 DE/en

Control components for VAV terminal units

TOC

Volume flow control BP*


Description

... / BP* / ...


Order code detail

Universal, static

Application
Electronic volume flow controller VRP-M,
combined with a static differential pressure
transducer VFP-300, as Universal controller
Variable air or constant air volume flow control
The flow rate is measured using the static
measurement principle
Voltage range for the actual and setpoint
value signals 0 10 V DC or 2 10 V DC
Separate inputs for override controls enable the
centralised switching of groups of controllers
With MP bus interface: Up to eight users,
such as VRP-M, can be addressed on an MP
bus (LAN). This allows for the integration with
higher-level systems. DDC controller with MP
bus interface to control the Universal controller.
Belimo interface UK24LON for LonWorks
systems; UK24EIB for EIB systems; UK24MOD
for Modbus systems; UK24BAC for BACnet
When the MP bus interface is used, the analog
0 10 V or 2 10 V interface cannot be used at
the same time.
The MP bus interface cannot be used
with fast-running actuators
Construction
Volume flow controller VRP-M with static
differential pressure transducer VFP-300
BP3: Actuator NM24A-V-ST for TVR, TVJ,
TZ-Silenzio, TA-Silenzio TVZ, TVA, TVLK
BP1: Actuator SM24A-V-ST for TVT
BPB: Spring return actuator NF24A-V-ST
for TVR, TVJ, TVT, TZ-Silenzio,
TA-Silenzio TVZ, TVA, TVRK
BPG: Fast-running actuator LMQ24A-SRV-ST
for TVR, TVZ, TVA, TVRK up to nominal
size 250, and TVLK or NMQ24A-SRV-ST
for TVR, TVZ, TVA, TVRK from nominal
size 315 and TVJ, TVT, TZ-Silenzio, TA-Silenzio

Technical data

Useful additions
AT-VAV-B: Adjustment device
Signal voltage ranges
0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.1 V DC)
Operating modes
E: Single and M: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S: Slave operation
min: 0 %
max: Volume flow rate ratio
to the master controller
F: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation and wiring
the controller is ready for use
Carry out zero point correction
for the controller and adapt the actuator.
The volume flow rate parameters min and max
can be adjusted at a later stage using
an adjustment device

Volume flow and differential pressure controller VRP-M


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 10 %
including differential pressure transducer, without actuator max. 2.6 VA
including differential pressure transducer, without actuator max. 1.1 VA
0 10 V DC, Ra > 200 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Universal controller
VRP-M

05/2015 DE/en

K5 1.3 48

Control components for VAV terminal units

Volume flow control BP*

TOC

Universal, static

Static differential pressure transducer VFP-300

Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 300 Pa
3 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-300

Actuators NM24A-V and NM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


5.5 VA max.
4 W max.
10 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.710 kg

Actuator NM24A-V-ST

Actuators SM24A-V and SM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


6 VA max.
4 W max.
20 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.910 kg

Actuator SM24A-V-ST

K5 1.3 49

05/2015 DE/en

Control components for VAV terminal units

Volume flow control BP*

TOC

Universal, static

Spring return actuators NF24A-V and NF24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


9 VA max.
6.5 W max.
10 Nm
< 75 s
< 20 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
1.91 kg

Spring return actuator


NF24A-V-ST

Fast-running actuator LMQ24A-SRV-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from controller VRP-M


23 VA max.
13 W max.
4 Nm
2.5 s
from controller VRP-M
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.810 kg

Fast-running actuator
LMQ24A-SRV-ST

05/2015 DE/en

K5 1.3 50

Control components for VAV terminal units

TOC

Volume flow control BP*

Universal, static

Fast-running actuator NMQ24A-SRV-ST

Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from controller VRP-M


23 VA max.
13 W max.
8 Nm
4s
from controller VRP-M
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.970 kg

Fast-running actuator
NMQ24A-SRV-ST

Function

VRP-M

Controller VRP-M
Cable for differential pressure transducer
Actuator cable
Indicator lights

K5 1.3 51

05/2015 DE/en

Control components for VAV terminal units

TOC

Volume flow control BP*


Characteristics

Characteristic of the setpoint value signal

Universal, static
Characteristic of the actual value signal

Nenn (100%)

Nenn (100%)

min

Einstellbereich

Volumenstrom

Volumenstrom

max

min Gert

min Gert
0

0 10 V DC
2 10 V DC

Wiring

10 V DC

Sollwertsignal w

10 V DC

0 10 V DC
2 10 V DC

Istwertsignal U5

0 10 V DC

0 10 V DC

Soll = w max min) + min


10

Ist = U5 Nenn
10

2 10 V DC

2 10 V DC

Soll = w 2 max min) + min


8

Ist = U5 2 Nenn
8

Terminal connections

2
~

3
4 5 6
w MP U5 z1

7
z2

Universal

Plug connection for differential pressure transducer


Plug connection for actuator
Plug connection for adjustment device
1 :
Ground, neutral
2 ~:
Supply voltage
3 w:
Setpoint value signal
4 MP:
MP bus
5 U5:
Actual value signal
6 z1:
Override control 1
7 z2:
Override control 2
Universal: VRP-M

05/2015 DE/en

K5 1.3 52

Control components for VAV terminal units

TOC

Volume flow control BP*

Universal, static

Variable volume flow control and override control

24 V

Raumtemperaturregler
~

S5
S4 S3 S2 S1
1

Universal
Betriebsart E, M, F

Folgeregler Universal
Betriebsart S

Switch functions
S1 Shut-off CLOSED
S2 Maximum volume flow rate max
S3 Intermediate flow rate mid
(only with supply voltage 24 V AC)
S4 Damper blade OPEN;
takes priority over all other override controls
All OPEN: Variable volume flow or min (S5)
S5 Variable volume flow, when open min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: VRP-M

K5 1.3 53

05/2015 DE/en

Control components for VAV terminal units

Volume flow control BB*


Description

... / BB* / ...


Order code detail

Application
Electronic volume flow controller VRP,
combined with a static differential pressure
transducer VFP-300, as Universal controller
Variable air or constant air volume flow control
The flow rate is measured using
the static measurement principle
Voltage range for the actual and setpoint
value signals 2 10 V DC
Separate inputs for override controls enable the
centralised switching of groups of controllers
Construction
Volume flow controller VRP with static differential
pressure transducer VFP-300
BB3: Actuator NM24A-V-ST for TVR, TVJ,
TZ-Silenzio, TA-Silenzio, TVZ, TVA,
TVRK, TVLK
BB1: Actuator SM24A-V-ST for TVT
BBB: Spring return actuator NF24A-V-ST
for TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio,
TVZ, TVA, TVRK
Signal voltage range
2: 2 10 V DC

Technical data

TOC

Universal, static
Operating modes
E2: Single and M2: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S2: Slave operation
min: 0 %
max: Volume flow rate ratio
to the master controller
F2: Constant value
min: constant volume flow rate
max: 100 %
Parameters are factory set. The customer defines
the required operating mode and the volume flow
rates in the order code at the time of ordering.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation
and wiring the controller is ready for use
Carry out zero point correction
for the controller and adapt the actuator
The volume flow rate parameters min and max
can be adjusted at a later stage
using potentiometers

Volume flow controller VRP


Supply voltage (AC)
Power rating (AC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
without actuator max. 2.6 VA
2 10 V DC, Ra >100 k
2 10 V DC linear, max. 0.5 mA
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Universal controller VRP

Static differential pressure transducer VFP-300


Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 300 Pa
3 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-300

05/2015 DE/en

K5 1.3 54

Control components for VAV terminal units

Volume flow control BB*

TOC

Universal, static

Actuators NM24A-V and NM24A-V-ST

Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


5.5 VA max.
4 W max.
10 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.710 kg

Actuator NM24A-V

Actuators SM24A-V and SM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


6 VA max.
4 W max.
20 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.910 kg

Actuator NM24A-V

K5 1.3 55

05/2015 DE/en

Control components for VAV terminal units

TOC

Volume flow control BB*

Universal, static

Spring return actuators NF24A-V and NF24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


9 VA max.
6.5 W max.
10 Nm
< 75 s
< 20 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
1.91 kg

Spring return actuator


NF24A

Function

VRP

Controller VRP
min potentiometer
max potentiometer
Cable for differential pressure transducer
Actuator cable

05/2015 DE/en

K5 1.3 56

Control components for VAV terminal units

TOC

Volume flow control BB*

Characteristic of the setpoint value signal

Characteristic of the actual value signal


Nenn (100%)

Nenn (100%)

Volumenstrom

Einstellbereich

max

Volumenstrom

Characteristics

Universal, static

min
min Gert

min Gert
0

10 V DC

Sollwertsignal w

Wiring

10 V DC

Istwertsignal U5

2 10 V DC
Soll =

2 10 V DC

w 2
max min) + min
8

Ist = U5 2 Nenn
8

Terminal connections

2
~

3
4 5
U5

6
y

7
z

Universal

Plug connection
for differential pressure transducer VFP
Plug connection for actuator
1 :
Ground, neutral
2 ~:
Supply voltage
3 w:
Setpoint value signal
4 w:
Setpoint value signal (0 20 V phase cut)
5 U5:
Actual value signal
6 y:
Actuator signal
7 z:
Override control
Universal: VRP

K5 1.3 57

05/2015 DE/en

Control components for VAV terminal units

TOC

Volume flow control BB*

Universal, static

Variable volume flow control and override control, voltage signal 2 10 V DC

Raumtemperaturregler

24 V

S4 S3 S2 S1
1

Universal
Betriebsart E, M, F

Folgeregler Universal
Betriebsart S

Switch functions
S1 Shut-off CLOSED
S2 Maximum volume flow rate max
S3 Minimum volume flow rate min
S4 Damper blade OPEN
All OPEN: Variable volume flow

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: VRP

05/2015 DE/en

K5 1.3 58

Control components for VAV terminal units

Volume flow control XD*

Description

... / XD* / ...


Order code detail

Application
Electronic volume flow controller GUAC-S3
as Universal controller with integral differential
pressure transducer
Variable air or constant air volume flow control
The flow rate is measured using
the static measurement principle
Voltage range for the actual and setpoint
value signals 0 10 V DC or 2 10 V DC

Universal controller
GUAC-S3

Universal, static
Operating modes
E: Single and M: Master
min: Minimum volume flow rate
max: Maximum volume flow rate
S: Slave operation
min: 0 %
max: Volume flow rate ratio
to the master controller

Construction
Volume flow controller GUAC-S3
XD1: Actuator 227-024-08-V for TVR, TVJ, TVT,
TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVRK
XD3: Spring return actuator
381C-024-20-V-004 for TVR, TVJ, TVT,
TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVRK

F: Constant value
min: constant volume flow rate
max: 100 %

Useful additions
AT-VAV-G: Adjustment device

Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered volume flow rates
After successful installation
and wiring the controller is ready for use
Carry out zero point correction for the controller
The volume flow rate parameters min and max
can be adjusted at a later stage using
an adjustment device

Signal voltage ranges


0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.8 V DC)

Technical data

TOC

Parameters are factory set. The customer defines


the required operating mode and the volume flow
rates in the order code at the time of ordering.

Volume flow controller GUAC-S3


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
without actuator max. 1.2 VA
without actuator max. 0.6 W
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Actuator 227-024-08-V
Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


3 VA max.
2 W max.
8 Nm
60 120 s
from the controller
III (protective extra-low voltage)
IP 54 (cable entry at the bottom)
EMC according to 2004/108/EC
0.530 kg

Actuator 227-024-08-V

K5 1.3 59

05/2015 DE/en

Control components for VAV terminal units

TOC

Volume flow control XD*

Universal, static

Spring return actuator 381C-024-20-V-004


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


10 VA max.
7.5 W max.
20 Nm
150 s
< 15 s
from the controller
III (protective extra-low voltage)
IP 54 (cable entry at the bottom)
EMC according to 2004/108/EC
1.8 kg

Spring return actuator


381C-024-20-V-004

Function

Universal controller GUAC-S3

Connection for actuator


Service socket
Connection of supply voltage,
setpoint value signal and actual value signal
Connections for differential pressure sensor

05/2015 DE/en

K5 1.3 60

Control components for VAV terminal units

TOC

Volume flow control XD*

Characteristic of the setpoint value signal

Characteristic of the actual value signal


Nenn (100%)

Nenn (100%)

min

Einstellbereich

Volumenstrom

max

Volumenstrom

Characteristics

Universal, static

min Gert

min Gert

10 V DC

0 10 V DC
2 10 V DC

Sollwertsignal Y

0 10 V DC
2 10 V DC

10 V DC

Istwertsignal U

0 10 V DC

0 10 V DC

Soll = Y max min) + min


10

Ist = U Nenn
10

2 10 V DC

2 10 V DC

Soll = Y 2 max min) + min


8

Wiring

Ist = U 2
8

Nenn

Terminal connections

BU

BN
+
~

BK
Y/Z

GY
U/PP
Universal

BU , :
BN ~, +:
BK Y/Z:
GY U/PP:

Ground, neutral
Supply voltage
Setpoint value signal and override control
Actual value signal and communication

Universal: GUAC-D3, GUAC-S3, GUAC-P1, GUAC-P6

K5 1.3 61

05/2015 DE/en

Control components for VAV terminal units

TOC

Volume flow control XD*

Universal, static

Variable volume flow control and override control, voltage signal 0 to 10 V DC


Raumtemperaturregler

~
y

24 V

S5 S4 S3

BU

BN

BK

S1

GY
Universal

Betriebsart E,M, F

BU

BN

BK

GY

Folgeregler Universal
Betriebsart S

Switch functions
S1 Room temperature control
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC);
takes priority over all other override controls
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: GUAC-D3, GUAC-S3

05/2015 DE/en

K5 1.3 62

Control components for VAV terminal units

TOC

Volume flow control XD*

Universal, static

Variable volume flow control and override control, voltage signal 2 to 10 V DC

24 V

S5 S4 S3

BU

BN

BK

Raumtemperaturregler
~
y

S2

S1

GY
Universal

Betriebsart E, M, F

BU

BN

BK

GY

Folgeregler Universal
Betriebsart S

Switch functions
S1 Room temperature control
S2 Shut-off CLOSED
S3 Maximum volume flow rate max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC);
takes priority over all other override controls
All OPEN: Minimum volume flow rate min

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: GUAC-D3, GUAC-S3

K5 1.3 63

05/2015 DE/en

Control components for VAV terminal units

Differential pressure control BR*, BS*


Description

... / BR* / ...


Order code detail

... / BS* / ...


Order code detail

Application
Electronic differential pressure controller
VRP-M, combined with a static differential
pressure transducer VFP-100 or VFP-600,
as Universal controller
Variable or constant differential
pressure control
The differential pressure is measured
using the static measurement principle
Voltage range for the actual and setpoint
value signals 0 10 V DC or 2 10 V DC
Separate inputs for override controls enable the
centralised switching of groups of controllers
With MP bus interface: Up to eight VRP-M
users can be addressed on an MP bus (LAN);
Belimo-Interface UK24LON for LonWorks
systems; UK24EIB for EIB systems; UK24MOD
for Modbus systems; UK24BAC for BACnet;
DDC controllers with MP bus interface can
control the Universal controller via data transfer
When the MP bus interface is used,
the analog 0 10 V or 2 10 V interface
cannot be used at the same time.
The MP bus interface cannot be used
with fast-running actuators
Construction
Differential pressure controller VRP-M with static
differential pressure transducer VFP-100
BR3: Actuator NM24A-V-ST for TVR, TVJ,
TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVRK
BR1: Actuator SM24A-V-ST for TVT
BRB: Spring return actuator NF24A-V-ST
for TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio,
TVZ, TVA, TVRK
BRG: Fast-running actuator LMQ24A-SRV-ST
for TVR, TVZ, TVA, TVRK up to nominal
size 250, and TVLK or NMQ24A-SRV-ST
for TVR, TVZ, TVA,
TVRK from nominal size 315

TOC

Universal, static
Operating modes
Z: Supply air
A: Extract air
Factory settings are as follows:
Differential pressure pmin as ordered
and for room pressure controllers the adequate
pnom. The effective pressure sensor
of the VAV terminal unit is short circuited.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered differential pressures
Tubing of the static differential pressure
transducer by others
For positive room pressure: Connect room
pressure to Plus, reference room to Minus
For negative room pressure: Connect room
pressure to Minus, reference room to Plus
For supply air duct pressure: Connect static
pressure of the duct to Plus
For extract air duct pressure: Connect static
pressure of the duct to Minus
After successful installation, tubing and wiring
the controller is ready for use
Carry out zero point correction for the controller
and adapt the actuator.
The differential pressure settings
can be adjusted at a later stage using
an adjustment device

Volume flow controller VRP-M with static


differential pressure transducer VFP-600
BS3: Actuator NM24A-V-ST for TVR,
TVJ, TVRK
BS1: Actuator SM24A-V-ST for TVT
BSB: Spring return actuator NF24A-V-ST
for TVR, TVJ, TVT, TVRK
BSG: Fast-running actuator LMQ24A-SRV-ST
for TVR, TVRK up to nominal size 250,
or NMQ24A-SRV-ST for TVJ, TVT and TVR,
TVRK from nominal size 315
Useful additions
AT-VAV-B: Adjustment device
Signal voltage ranges
0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.1 V DC)

05/2015 DE/en

K5 1.3 64

Control components for VAV terminal units

TOC

Differential pressure control BR*, BS*

Technical data

Universal, static

Volume flow and differential pressure controller VRP-M


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 10 %
including differential pressure transducer, without actuator max. 2.6 VA
including differential pressure transducer, without actuator max. 1.1 VA
0 10 V DC, Ra > 200 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Universal controller
VRP-M

Static differential pressure transducer VFP-100


Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 100 Pa
1 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-100

Static differential pressure transducer VFP-600


Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 600 Pa
6 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-600

K5 1.3 65

05/2015 DE/en

Control components for VAV terminal units

Differential pressure control BR*, BS*

TOC

Universal, static

Actuators NM24A-V and NM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


5.5 VA max.
4 W max.
10 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.710 kg

Actuator NM24A-V-ST

Actuators SM24A-V and SM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


6 VA max.
4 W max.
20 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.910 kg

Actuator SM24A-V-ST

Spring return actuators NF24A-V and NF24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


9 VA max.
6.5 W max.
10 Nm
< 75 s
< 20 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
1.91 kg

Spring return actuator


NF24A-V-ST

05/2015 DE/en

K5 1.3 66

Control components for VAV terminal units

TOC

Differential pressure control BR*, BS*

Universal, static

Fast-running actuator NMQ24A-SRV-ST

Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from controller VRP-M


23 VA max.
13 W max.
8 Nm
4s
from controller VRP-M
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.970 kg

Fast-running actuator
NMQ24A-SRV-ST

Function

Constant pressure control


The differential pressure setpoint value as given
in the order code is stored as pmin
in the controller. The nominal differentia
pressure pnom is the reference unit.
To maximise the control accuracy, different
pressure ranges with the corresponding nominal
differential pressures are used. The correct range
is factory set. It is possible to change pmin at
a later stage but only within the factory set
pressure range.

Variable pressure control


A setpoint value signal enables variable pressure
control. The control range is pmin to pmax, based
on the setpoint value signal 0 (2) 10 V.

VRP-M

Pressure ranges
Differential pressure
transducer

plimit

Min

Max

pnom

VFP 100

2.5
2.5
2.5

30
15
7.5

80
40
20

100
50
25

VFP 600

15
7.5

180
90

480
240

600
300

Min: Minimum value for pmin and pmax


Max: Maximum value for pmin and pmax
Using a control signal also setpoint values < 30 %
of pnom can be set. Pressure values smaller than plimit
will be set to zero because they cannot be
precisely controlled.

Controller VRP-M
Cable for differential pressure transducer
Actuator cable
Indicator lights

K5 1.3 67

05/2015 DE/en

Control components for VAV terminal units

TOC

Differential pressure control BR*, BS*


Characteristics

Characteristic of the setpoint value signal

Universal, static
Characteristic of the actual value signal

nom (Pa)

(Pa)

min

Setting range





max

min unit


0

10 V DC

0 10 V DC
2 10 V DC

w

0 10 V DC
= w (max ) +
10

2 10 V DC
= w 2 (max ) +
8

05/2015 DE/en

0 10 V DC
2 10 V DC

10 V DC

Actual value signal U5

0 10 V DC
actual = U5 nom
10

2 10 V DC
actual = U5 2 nom
8

K5 1.3 68

Control components for VAV terminal units

TOC

Differential pressure control BR*, BS*

Wiring

Universal, static

Terminal connections

3
4 5 6
w MP U5 z1

2
~

7
z2

Universal

Plug connection for differential pressure transducer


Plug connection for actuator
Plug connection for adjustment device
1 :
Ground, neutral
2 ~:
Supply voltage
3 w:
Setpoint value signal
4 MP:
MP bus
5 U5:
Actual value signal
6 z1:
Override control 1
7 z2:
Override control 2
Universal: VRP-M

Differential pressure control and override control


24 V

Sollwertgeber
~

S5
S4 S3 S2 S1
1

Universal
Betriebsart Z, A

Parallelregler Universal
Betriebsart Z, A

Switch functions
S1 Shut-off CLOSED
S2 Maximum differential pressure pmax
S3 Stop actuator (only with supply voltage 24 V AC)
S4 Damper blade OPEN;
takes priority over all other override controls
All OPEN: Variable differential pressure or pmin (S5)
S5 Variable differential pressure, when OPEN pmin

When combining several override controls


the switches must be interlocked to prevent
short-circuits.
Diode: e.g. 1N 4007

Universal: VRP-M

K5 1.3 69

05/2015 DE/en

Control components for VAV terminal units

Differential pressure control BG*, BH*


Description

... / BG* / ...


Order code detail

... / BH* / ...


Order code detail

Application
Electronic differential pressure controller
VRP-STP, combined with a static differential
pressure transducer VFP-100 or VFP-600,
as Universal controller
Variable or constant differential
pressure control
The differential pressure is measured
using the static measurement principle
Voltage range for the actual and setpoint
value signals 2 10 V DC
Separate inputs for override controls enable the
centralised switching of groups of controllers
Construction
Differential pressure controller VRP-STP with
static differential pressure transducer VFP-100
BG3: Actuator NM24A-V for TVR, TVJ,
TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVRK
BG1: Actuator SM24A-V-ST for TVT
BGB: Spring return actuator NF24A-V for TVR,
TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA,
TVRK
Differential pressure controller VRP-STP with
static differential pressure transducer VFP-600
BH3: Actuator NM24A-V for TVR, TVJ, TVRK
BH1: Actuator SM24A-V-ST for TVT
BHB: Spring return actuator NF24A-V for TVR,
TVJ, TVT, TVRK

TOC

Universal, static
Operating modes
Z: Supply air
A: Extract air
Factory settings are as follows: Differential
pressure pmin as ordered and for room pressure
controllers the adequate pnom. The effective
pressure sensor of the VAV terminal unit
is short circuited.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered differential pressures
Tubing of the static differential pressure
transducer by others
For positive room pressure: Connect room
pressure to Plus, reference room to Minus
For negative room pressure: Connect room
pressure to Minus, reference room to Plus
For supply air duct pressure: Connect static
pressure of the duct to Plus
For extract air duct pressure: Connect static
pressure of the duct to Minus
After successful installation, tubing and wiring
the controller is ready for use
Carry out zero point correction for the controller
and adapt the actuator.
The differential pressure settings can be
adjusted at a later stage using a potentiometer

Signal voltage ranges


2: 2 10 V DC

Technical data

Differential pressure controller VRP-STP


Supply voltage (AC)
Power rating (AC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
including static differential pressure transducer, without actuator max. 2.6 VA
2 10 V DC, Ra >100 k
2 10 V DC linear, max. 0.5 mA
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Differential pressure
controller VRP-STP

Static differential pressure transducer VFP-100


Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 100 Pa
1 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-100

05/2015 DE/en

K5 1.3 70

Control components for VAV terminal units

Differential pressure control BG*, BH*

TOC

Universal, static

Static differential pressure transducer VFP-600

Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 600 Pa
6 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-600

Actuators NM24A-V and NM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


5.5 VA max.
4 W max.
10 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.710 kg

Actuator NM24A-V-ST

Actuators SM24A-V and SM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


6 VA max.
4 W max.
20 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.910 kg

Actuator SM24A-V-ST

K5 1.3 71

05/2015 DE/en

Control components for VAV terminal units

TOC

Differential pressure control BG*, BH*

Universal, static

Spring return actuators NF24A-V and NF24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


9 VA max.
6.5 W max.
10 Nm
< 75 s
< 20 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
1.91 kg

Spring return actuator


NF24A-V-ST
Function

Constant pressure control


The differential pressure setpoint value that has
been ordered (order code) is factory set as p
in the controller. The nominal differential
pressure pnom is the reference unit.
To maximise the control accuracy, different
pressure ranges with the corresponding nominal
differential pressures are used. The correct range
is factory set. It is possible to change p at a later
stage but only within the factory set
pressure range.

Variable pressure control


A setpoint value signal enables variable pressure
control. The control range is from plimit to pmax.

VRP-STP

Pressure ranges
Differential pressure
transducer

plimit

Min

Max

pnom

VFP 100

2.5
2.5
2.5

30
15
7.5

80
40
20

100
50
25

VFP 600

15
7.5

180
90

480
240

600
300

Min: Minimum value (10 V) for p


Max: Maximum value (10 V) for p
Using a control signal also setpoint values < 30 %
of pnom can be set. Pressure values smaller than plimit
will be set to zero because they cannot
be precisely controlled.
Variable pressure control requires that the link between
terminals 2 and 4 is removed.

Controller VRP-STP
Actuator cable
p potentiometer
Cable for differential pressure transducer
Setting p
The p potentiometer is used to set the required
differential pressure. For variable control the pressure
can be limited to the maximum value p; this value
is maintained as long as the input signal is 10 V DC.
The percentages relate to the nominal differential
pressure (pnom). The setting range is from 30 80 %.

05/2015 DE/en

K5 1.3 72

Control components for VAV terminal units

TOC

Differential pressure control BG*, BH*


Characteristic of the setpoint value signal

Characteristic of the actual value signal


nom (Pa)

nom (Pa)
max

Setting range

Differential pressure

Differential pressure

Characteristics

Universal, static

min unit

10 V DC

Setpoint value signal w


2 10 V DC
w1< 2 V DC may lead to unstable control behaviour

2 10 V DC
=

Wiring

10 V DC

2 10 V DC

Actual value signal U5

2 10 V DC

w 2
max
8

actual = U5 2 nom
8

Terminal connections

2
~

3
4 5
U5

6
y

7
z

Universal

Plug connection for differential pressure


transducer VFP
Plug connection for actuator
Wire link, factory mounted
(constant pressure control)
To connect a setpoint adjuster the control signal
must be connected to the controller with a two-wire
cable. The link (2 4) must then be removed.
1 :
2 ~:
3 w:
4 w:
5 U5:
6 y:
7 z:

Ground, neutral
Supply voltage
Setpoint value signal
Setpoint value signal (0 20 V phase cut)
Actual value signal
Actuator signal
Override control

Universal: VRP-STP

K5 1.3 73

05/2015 DE/en

Control components for VAV terminal units

TOC

Differential pressure control BG*, BH*

Universal, static

Differential pressure control including parallel control and override control


24 V

Sollwertgeber

S3
1

S2 S1

Universal
Betriebsart Z, A

Parallelregler Universal
Betriebsart Z, A

Switch functions
S1 Shut-off CLOSED
S2 Maximum differential pressure pmax
S3 Damper blade OPEN
All OPEN: Variable differential pressure
When combining several override controls the switches
must be interlocked to prevent short-circuits.

Diode: e.g. 1N 4007

Universal: VRP-STP

05/2015 DE/en

K5 1.3 74

Control components for VAV terminal units

Differential pressure control XE*, XF*


Description

... / XE* / ...


Order code detail

... / XF* / ...


Order code detail

Application
Electronic volume flow controller GUAC-S3
with integral static differential
pressure transducer
Variable or constant differential
pressure control
The differential pressure is measured
using the static measurement principle
Voltage range for the actual and setpoint
value signals 0 10 V DC or 2 10 V DC
Construction
Volume flow controller GUAC-P1
XE1: Actuator 227-024-08-V for TVR,
TVJ, TVT, TVRK
XE3: Spring return actuator
381C-024-20-V-004 for TVR, TVJ, TVT, TVRK
Volume flow controller GUAC-P6
XF1: Actuator 227-024-08-V for TVR,
TVJ, TVT, TVRK
XF3: Spring return actuator
381C-024-20-V-004 for TVR, TVJ, TVT, TVRK
Useful additions
AT-VAV-G: Adjustment device
Signal voltage ranges
0: 0 10 V DC
2: 2 10 V DC with shut-off function
(< 0.8 V DC)

Technical data

Differential pressure
controller GUAC-P1

TOC

Universal, static
Operating modes
Z: Supply air
A: Extract air
The required differential pressure is set
at the factory. The effective pressure sensor
of the VAV terminal unit is short circuited.
Commissioning
On-site adjusting is not required
When installing the VAV terminal units
it is important to assign each room the correct
unit based on the ordered differential pressures
Tubing of the static differential pressure
transducer by others
For positive room pressure: Connect room
pressure to Plus, reference room to Minus
For negative room pressure: Connect room
pressure to Minus, reference room to Plus
For supply air duct pressure: Connect static
pressure of the duct to Plus
For extract air duct pressure: Connect static
pressure of the duct to Minus
After successful installation, tubing and wiring
the controller is ready for use
Carry out zero point correction for the controller
The differential pressure settings can be
adjusted at a later stage using
an adjustment device

Differential pressure controller GUAC-P1


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Measuring range
Linearity
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
without actuator max. 1.2 VA
without actuator max. 0.6 W
0 100 Pa
1 Pa
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Differential pressure controller GUAC-P6

Differential pressure
controller GUAC-P6

05/2015 DE/en

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Measuring range
Linearity
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
without actuator max. 1.2 VA
without actuator max. 0.6 W
0 600 Pa
6 Pa
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

K5 1.3 75

Control components for VAV terminal units

Differential pressure control XE*, XF*

TOC

Universal, static

Actuator 227-024-08-V

Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


3 VA max.
2 W max.
8 Nm
60 120 s
from the controller
III (protective extra-low voltage)
IP 54 (cable entry at the bottom)
EMC according to 2004/108/EC
0.530 kg

Actuator 227-024-08-V

Spring return actuator 381C-024-20-V-004


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Spring return time
Control signal
IEC protection class
Protection level
EC conformity
Weight

from the controller


10 VA max.
7.5 W max.
20 Nm
150 s
< 15 s
from the controller
III (protective extra-low voltage)
IP 54 (cable entry at the bottom)
EMC according to 2004/108/EC
1.8 kg

Spring return actuator


381C-024-20-V-004

K5 1.3 76

05/2015 DE/en

Control components for VAV terminal units

TOC

Differential pressure control XE*, XF*


Function

Universal, static

Constant pressure control


The differential pressure setpoint value
as given in the order code is stored as pmin
in the controller. The nominal differential
pressure pnom is the reference unit.
To maximise the control accuracy, different
pressure ranges with the corresponding nominal
differential pressures are used. The correct range
is factory set. It is possible to change pmin
at a later stage but only within the factory set
pressure range.

Variable pressure control


A setpoint value signal enables variable pressure
control. The control range is pmin to pmax, based
on the setpoint value signal 0 (2) 10 V.

Universal controller GUAC-P1

Pressure ranges
Differential pressure
transducer

Connection for actuator


Service socket
Connection of supply voltage,
setpoint value signal and actual value signal
Connections for differential pressure sensor

Characteristics

plimit

Characteristic of the setpoint value signal

Min

Max

pnom

GUAC-P1

2.5
2.5
2.5

30
15
7.5

80
40
20

100
50
25

GUAC-P6

15
7.5

180
90

480
240

600
300

Min: Minimum value for pmin


Max: Maximum value for pmin and pmax
Using a control signal also setpoint values < 30 %
of pnom can be set. Pressure values smaller than plimit
will be set to zero because they cannot be
precisely controlled.

Characteristic of the actual value signal


nom (Pa)

(Pa)

min

Setting range





max

min unit


0

10 V DC

0 10 V DC
2 10 V DC

Y

0 10 V DC
= Y (max ) +
10
2 10 V DC
= Y 2 (max ) +
8

05/2015 DE/en

10 V DC

0 10 V DC
2 10 V DC

Actual value signal U

0 10 V DC
actual = U nom
10
2 10 V DC
actual = U 2 nom
8

K5 1.3 77

Control components for VAV terminal units

TOC

Differential pressure control XE*, XF*

Wiring

Universal, static

Terminal connections

BU

BN
+
~

BK
Y/Z

GY
U/PP
Universal

BU , :
BN ~, +:
BK Y/Z:
GY U/PP:

Ground, neutral
Supply voltage
Setpoint value signal and override control
Actual value signal and communication

Universal: GUAC-D3, GUAC-S3, GUAC-P1, GUAC-P6

Differential pressure control and override control, voltage signal 0 10 V DC

24 V AC

S5 S4 S3

BU

BN

BK

Sollwertgeber
~
y

S1

GY
Universal

Betriebsart Z, A

BU

BN

BK

GY
Universal

Betriebsart Z, A

Switch functions
S1 Differential pressure control
S3 Maximum differential pressure p max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC)
S5 Damper blade OPEN
(only with supply voltage 24 V AC)
All OPEN: Minimum differential pressure pmin

When combining several override controls the switches


must be interlocked to prevent short-circuits.
Diode: e.g. 1N 4007

Universal: GUAC-P1, GUAC-P6

K5 1.3 78

05/2015 DE/en

Control components for VAV terminal units

TOC

Differential pressure control XE*, XF*

Universal, static

Differential pressure control and override control, voltage signal 2 10 V DC

24 V AC

S5 S4 S3

BU

BN

BK

Sollwertgeber
~
y

S2

S1

GY
Universal

Betriebsart Z, A

BU

BN

BK

GY
Universal

Betriebsart Z, A

Switch functions
S1 Differential pressure control
S2 Shut-off CLOSED
S3 Maximum differential pressure p max
S4 Damper blade CLOSED
(only with supply voltage 24 V AC);
takes priority over all other override controls
S5 Damper blade OPEN
(only with supply voltage 24 V AC)
All OPEN: Minimum differential pressure pmin

When combining several override controls the switches


must be interlocked to prevent short-circuits.
Diode: e.g. 1N 4007

Universal: GUAC-P1, GUAC-P6

05/2015 DE/en

K5 1.3 79

RETROFIT

TOC

1.3

X X RETROFITtestregistrierung

Control components
for VAV terminal units

Type RETROFIT

Rapid replacement without interruption


of system operation
Control components for VAV terminal units as a replacement for previous types
while the VAV terminal unit remains installed
Easy alternative to replacing a complete unit
Replacement in case of modernisation
Extended range of functions
Installation without interruption of system operation
For circular ducts of nominal sizes 100 to 400 mm
Retrofit parts kit consists of:
Control components Easy, Compact or Universal
Differential pressure sensor
Accessories

05/2015 DE/en

K5 1.3 80

Control components for VAV terminal units

TOC

General information

RETROFIT

Type

RETROFIT

Description

Page
General information
Order code
Quick selection
Special information EasySet
Special information CompactSet
Specification text

1.3 81
1.3 82
1.3 83
1.3 85
1.3 86
1.3 88

Basic information and nomenclature

1.5 1

RETROFIT

RETROFIT EasySet

Application
RETROFIT parts kits for the replacement
or modernisation of control components
in existing VAV terminal units
Ideal for cases where it is not possible
to replace the entire VAV terminal unit
Replacement of faulty or dirty electronic
or pneumatic units
Replacement of faulty units
with airflow velocity sensors
Conversion of a constant air
to a variable air volume system
Extension of range of functions to save energy,
for more comfort, or for integration
with the central BMS
No changes to ductwork necessary
since the existing unit continues to be used

Special features
Quick replacement
Low modernisation cost,
quick return on investment
No interruption of system operation
Low costs of disposal
Electronic compatibility remains unchanged

Variants
EasySet
CompactSet
UniversalSet
Nominal sizes
For circular ducts with nominal size 100, 112,
125, 140, 160, 180, 200, 225, 250, 280, 315,
355, or 400
Accessories
1: Special adapter for EasySet
and CompactSet
2: Special adapter for UniversalSet

K5 1.3 81

Parts and characteristics


Kits consist of control components
and accessories
Electronic volume flow controller and actuator
Differential pressure sensor
for volume flow rate measurement
Stickers for VAV terminal unit
and for inspection or maintenance documents
Installation and commissioning
Remove the control components;
the damper blade continues to be used
Installing the differential pressure
sensor where suitable
Install the RETROFIT control components
Connect the tubes of the differential
pressure sensor to the control components
Do the wiring
Set the volume flow rates min and max
(EasySet and UniversalSet: potentiometer;
CompactSet: adjustment device
to be supplied by others)
Functional test

05/2015 DE/en

Control components for VAV terminal units

TOC

Order code
Order code

RETROFIT

RETROFIT

EasySet / 1

Parts kit
EasySet
CompactSet
UniversalSet

05/2015 DE/en

Accessories
No entry: none
Special adapters are available for units
with 8 x 8 mm square shafts
or with short circular shafts
1
For EasySet and CompactSet
2
For UniversalSet

K5 1.3 82

Control components for VAV terminal units

TOC

Quick selection

Selection of parts kit

Existing controller

VR1

VR2

VRD

VRD2

NMV24-V

NMV24-D

NMV-D2

NMV-D2M

K5 1.3 83

RETROFIT

Signal voltage range

RETROFIT solution

0 10 V DC

EasySet
CompactSet
UniversalSet

2 10 V DC

CompactSet
UniversalSet

2 10 V DC

EasySet (only 0 10 V DC)


CompactSet
UniversalSet

0 10 V DC
2 10 V DC

CompactSet
UniversalSet

0 10 V DC

EasySet
CompactSet
UniversalSet

0 10 V DC

EasySet
CompactSet
UniversalSet

0 10 V DC
2 10 V DC

EasySet (only 0 10 V DC)


CompactSet
UniversalSet

0 10 V DC
2 10 V DC

CompactSet
UniversalSet

05/2015 DE/en

Control components for VAV terminal units

TOC

Quick selection

RETROFIT

Criteria for the selection of the kit


The selection of the required RETROFIT parts
kit depends on the existing control components
A further criterion is the voltage range
of the existing system
The following overview shows which
of the 3 RETROFIT kits are suitable to replace
the existing control components
and will provide the same range of functions
CompactSet and UniversalSet are suitable
for all existing controllers and may even provide
an extended range of functions
EasySet and CompactSet are suitable
for 10 20 mm circular shafts
and for 8 16 mm square shafts
with the shaft end projecting at least 45 mm
UniversalSet is suitable for 8 20 mm
circular shafts and for 8 18 mm square shafts
with the shaft end projecting at least 25 mm
Other types of shafts require special adapters

Existing controllers VR1, VR2, VRD and VRD2


are combined with actuators
KM24-I, SM24-I, NM24-V or SM24-V.

Shaft clamp

Volume flow rate ranges

Special adapter 1 for EasySet and CompactSet

Special adapter 2 for UniversalSet

Existing shaft

Existing shaft
- 8 mm x 8 mm square shaft
(existing actuator KM 24-I)

Nominal size
100
112
125
140
160
180
200
225
250
280
315
355
400

05/2015 DE/en

l/s

Nenn
95
125
155
195
250
315
405
525
615
795
1030
1275
1675

m/h

l/s
342
450
558
702
900
1134
1458
1890
2214
2862
3708
4590
6030

min
10
13
15
20
25
32
40
53
62
80
105
130
170

m/h
36
47
54
72
90
115
144
191
223
288
378
468
612

K5 1.3 84

Control components for VAV terminal units

Special information EasySet


Description

RETROFIT EasySet

Function

Application
RETROFIT parts kit with
Easy controller LMV-D3A
Parts and characteristics
Differential pressure sensor
for the measurement of volume flows
using the effective pressure principle
Easy controller combines volume flow
controller and actuator in one casing
Tubes, small parts, operating manual, sticker

TOC

RETROFIT
Installation and commissioning
Set the volume flow rate percentages
on scaled potentiometers,
without additional adjustment device
Start the functional test by pressing
the function button
Green indicator light shows the operating state

EasySet

Easy controller
Protective cover
Existing damper blade
Existing sensor
Wire clamping bracket
Effective pressure sensor
Tubing

Technical data

Easy controller LMV-D3A and LMV-D3A-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

05/2015 DE/en

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
5 VA max.
2.5 W max.
110 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 20
EMC according to 2004/108/EC

K5 1.3 85

Control components for VAV terminal units

TOC

Special information CompactSet

Description

RETROFIT CompactSet

Function

Application
RETROFIT parts kit
with Compact controller LMV-D3-MP
Parts and characteristics
Differential pressure sensor
for the measurement of volume flows
using the effective pressure principle
Compact controller combines volume
flow controller and actuator in one casing
Tubes, small parts, operating manual, sticker

RETROFIT
Installation and commissioning
Set the volume flow rates with an adjustment
device or using an interface and dedicated
software (to be supplied by others)
Set the operating mode 0 10 V DC
or 2 10 V DC
Carry out a functional test using adjustment
device, software or voltage measurement

CompactSet

Compact controller
Existing damper blade
Existing sensor
Effective pressure sensor
Tubing

Technical data

Compact controller LMV-D3-MP and LMV-D3-MP-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

K5 1.3 86

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
4 VA max.
2 W max.
5 Nm
110 150 s
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.5 kg

05/2015 DE/en

Control components for VAV terminal units

Special information CompactSet


Description

RETROFIT UniversalSet

Function

Application
RETROFIT parts kit with Universal
controller VRD3 and actuator NM24A-V
Parts and characteristics
Differential pressure sensor
for the measurement of volume flows
using the effective pressure principle
Universal controller
Actuator
Tubes, small parts, operating manual, sticker

TOC

RETROFIT
Installation and commissioning
Set the volume flow rate percentages
on scaled potentiometers,
without additional adjustment device
Alternatively, set the volume flow rates
with an adjustment device or using an interface
and dedicated software
(to be supplied by others)
Set the operating mode 0 10 V DC
or 2 10 V DC
Carry out a functional test using adjustment
device, software or voltage measurement

CompactSet

Compact controller
Existing damper blade
Existing sensor
Effective pressure sensor
Tubing

Technical data

Volume flow controller VRD3


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
without actuator max. 3.5 VA
without actuator max. 2 W
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 40
EMC according to 2004/108/EC
0.440 kg

Actuators NM24A-V and NM24A-V-ST


Supply voltage
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
IEC protection class
Protection level
EC conformity
Weight

05/2015 DE/en

from the controller


5.5 VA max.
4 W max.
10 Nm
150 s
from the controller
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
0.710 kg

K5 1.3 87

Control components for VAV terminal units

Specification text

TOC

RETROFIT

EasySet

Parts kit for the modernisation of VAV terminal


units in systems with circular ducts, for nominal
sizes 100 to 400 mm, for supply or extract air.
Customers can easily set the volume flow rates
on the Easy controller using potentiometers
with percentage scales. No supply voltage
and no additional devices are required.
A transparent protective cover prevents
inadvertent resetting and provides general safety.
Clearly visible external indicator light for signalling
the functions: Set, not set, no supply voltage.

Electrical connections with screw terminals.


Double terminal for looping the supply voltage, i.e.
for the simple connection of voltage transmission
to the next controllers.
Voltage range for control signal and actual value
signal 0 to 10 V DC. Possible override controls
with external switches using volt-free contacts:
CLOSED, OPEN,
switching between min and max.
Same, linear characteristic for all sizes.

CompactSet

Parts kit for the modernisation of VAV terminal


units in systems with circular ducts, for nominal
sizes 100 to 400 mm, for supply or extract air.
Customers can easily set the volume flow rates
on the Compact controller using the adjustment
device or dedicated software.

Voltage range for control and actual value signal


0 10 or 2 10 V DC. Possible override controls
with external switches using volt-free contacts:
CLOSED, OPEN,
switching between min and max.
Same, linear characteristic for all sizes.

UniversalSet

Parts kit for the modernisation of VAV terminal


units in systems with circular ducts, for nominal
sizes 100 to 400 mm, for supply or extract air.
Customers can easily set the volume flow rates
on the Universal controller using the adjustment
buttons on the controller, an adjustment device,
or dedicated software.

Voltage range for control and actual value signal


0 10 or 2 10 V DC. Possible override controls
with external switches using volt-free contacts:
CLOSED, OPEN,
switching between min and max.
Same, linear characteristic for all sizes.
Separate actuator.

Special features
Quick replacement
Low modernisation cost,
quick return on investment
No interruption of system operation
Low costs of disposal
Electronic compatibility remains unchanged

Parts kit
EasySet
CompactSet
UniversalSet

05/2015 DE/en

Accessories
No entry: none
Special adapters are available
for units with 8 x 8 mm square shafts
or with short circular shafts
1
For EasySet and CompactSet
2
For UniversalSet

K5 1.3 88

RC

TOC

1.3

X X RCtestregistrierung

Control components
for VAV terminal units

Type RC

For the individual temperature control in rooms


Lower operating costs due to intelligent sensor technology
Temperature range 10 45 C
For variable air volume systems and 2-pipe or 4-pipe air water systems
With integral temperature sensor
Optional equipment
Room occupant can select the operating mode
Remote control for RC/M1

Room temperature controller


ETN-24-VAV-227-P

05/2015 DE/en

K5 1.3 89

Control components for VAV terminal units

TOC

General information

RC

Type

RC

Variants
Product examples

Description

Function

K5 1.3 90

Room temperature
controller CR24-B1

Page
General information
Order code
Special information RC/B1
Special information RC/B2
Special information RC/B3
Special information RC/M1
Specification text

1.3 90
1.3 92
1.3 93
1.3 94
1.3 95
1.3 96
1.3 97

Basic information and nomenclature

1.5 1

Room temperature
controller
ETN-24-VAV-227-P

Application
Room temperature controller
Ideally suited for the control
of VAV terminal units using Easy,
Compact, or Universal controllers
Comfortable room temperature control
Low energy consumption due
to demand-based operating modes
Cooling and/or heating
Device versions with different
output sequences for many different ventilation
and air conditioning systems,
including air-water systems

Variants
B1: Room temperature controller
with one analog output for cooling or heating
(changeover)
B2: Room temperature controller with two
analog outputs for cooling or heating (3 point)
B3: Room temperature controller with three
analog outputs for cooling or heating
(0 10 V DC and 3 point)
M1: Room temperature controller with two
analog outputs for cooling or heating
(0 10 V DC)
Commissioning
Configure the control function using
a micro switch
Functional test

Functional description
Room temperature controller and VAV terminal
unit, including control components,
form a functional unit that allows occupants
to control the room temperature individually
and at the lowest possible energy consumption.
It also allows to control the water valves
of hot water or cold water systems.
Room temperature control is a closed loop control.
The controller is fitted with a temperature sensor
that measures the room temperature. The setpoint
can be a constant value or it can be changed
by room occupants. The controller compares
the actual value with the setpoint value
and alters the volume flow rate setpoint
value and/or the valve settings accordingly.
The room temperature control is P control
or PI control. Maximum energy efficiency
is achieved because of demand-based operating
modes that can be activated by the room
occupant or at a higher level.

05/2015 DE/en

Control components for VAV terminal units

TOC

General information

RC

Operating modes
Energy-saving mode
The room temperature is such that devices will
not suffer, i.e. the setpoint temperature for heating
is very low, and the setpoint temperature
for cooling is very high, for example in a room
with an open window.

Frost mode
If the room temperature falls below 10 C,
the anti-freeze function is activated.

Standby mode
The setpoint temperature for heating is just slightly
reduced, and the setpoint temperature for cooling
is just slightly increased, e.g. for a room that
is currently not used.

Boost
Room ventilation with the maximum volume
flow rate (max), or maximum heating or cooling.

Changeover
Changeover from cooling to heating
or from heating to cooling.

Control diagram with heating


and cooling sequence
100%

Volume flow

Heating valve

max

min

Setpoint
Heating

Cooling

Single operation

05/2015 DE/en

K5 1.3 91

Control components for VAV terminal units

TOC

Order code

Order code

RC

RC

RC / B1

Type
RC
Room temperature controller

Order example

Type
B1
CR24-B1
B2
CR24-B2
B3
CR24-B3
M1
ETN-24-VAV-277V-P
M2
Remote control for M1

RC/M1
Type

K5 1.3 92

ETN-24-VAV-277V-P

05/2015 DE/en

Control components for VAV terminal units

Special information RC/B1


Description

Room temperature
controller CR24-B1

TOC

RC

Application
Room temperature controller CR24-B1
with one output, for room applications
Cooling or heating (changeover)
Analog output 0 10 V DC for the control
of VAV terminal units with Easy,
Compact or Universal controllers

Parts and characteristics


Attractive unit for wall mounting,
signal white (RAL 9003)
Integral temperature sensor
Setpoint adjuster
Operating mode push button
Status indicator light
Analog output 0 10 V DC
for variable volume flow control
Analog inputs 0 10 V DC for external
temperature sensor and for setpoint
changes by an external unit
Digital inputs for energy-saving mode,
standby operation or changeover
Micro switch for configuration
Communication connection
for adjustment devices
Commissioning
Configure the control function using
a micro switch
Functional test

Technical data

Supply voltage
Power rating
External temperature sensor
External setpoint changes
Output for variable volume flow
IEC protection class
Protection level
EC conformity
Dimensions (B H T)
Weight

Electrical connection

Terminal connections

24 V AC 20 %, 50/60 Hz
3 VA
NTC, 5 k, 10 45 C
0 10 V DC corresponding to 0 10 K
0 10 V DC, 5 mA max.
III (protective extra-low voltage)
IP 30
EMC according to 2004/108/EG
84 99 32 mm
0.105 kg

3 4 5 6 7 8
2
~ ai/di1 di2 ai2 ao1 PP1 PP2
CR24-B1

1 :
2 ~:
3 ai/di1:
4 di2:
5 ai2:
6 ao1:
7 PP1:
8 PP2:

05/2015 DE/en

Neutral
Supply voltage
External temperature sensor
or energy-saving mode
Standby/Changeover
External setpoint changes
Volume flow controller
Diagnosis connection 1
Diagnosis connection 2

K5 1.3 93

Control components for VAV terminal units

TOC

Special information RC/B2

Description

Room temperature
controller CR24-B2

Technical data

Application
Room temperature controller CR24-B2
with two outputs, for room applications
Cooling and heating
Analog output 0 10 V DC for the control
of VAV terminal units with Easy,
Compact or Universal controllers
3-point output for heating

Commissioning
Configure the control function
using a micro switch
Functional test

Parts and characteristics


Attractive unit for wall mounting,
signal white (RAL 9003)
Integral temperature sensor
Setpoint adjuster
Operating mode push button
Status indicator light
Analog output 0 10 V DC
for variable volume flow control
3-point output for controlling a heating valve
Analog inputs 0 10 V DC for external
temperature sensor and for setpoint
changes by an external unit
Digital inputs for energy-saving mode,
standby operation or changeover
Micro switch for configuration
Communication connection
for adjustment devices

Supply voltage
Power rating
External temperature sensor
External setpoint changes
Output for variable volume flow

24 V AC 20 %, 50/60 Hz
3 VA
NTC, 5 k, 10 45 C
0 10 V DC corresponding to 0 10 K
0 10 V DC, 5 mA max.
3-point, 24 V AC, max. 0.5 A, 10 VA,
optimised for actuators with a running time of approx. 150 s
III (protective extra-low voltage)
IP 30
EMC according to 2004/108/EG
84 99 32 mm
0.105 kg

Output for heating valve


IEC protection class
Protection level
EC conformity
Dimensions (B H T)
Weight

Electrical connection

RC

Terminal connections

3 4 5 6 7 8
9 10 12
2
~ ai/di1 di2 ai2 ao1 PP1 PP2 ao3 ao3 di3
CR24-B2

1 :
2 ~:
3 ai/di1:

Neutral
Supply voltage
External temperature sensor
or energy-saving mode
4 di2:
Standby
5 ai2:
External setpoint changes
6 ao1:
Volume flow controller
7 PP1:
Diagnosis connection 1
8 PP2:
Diagnosis connection 2
9,10 ao3: Heating valve (3-point)
12 di3:
Maximum volume flow rate

K5 1.3 94

05/2015 DE/en

Control components for VAV terminal units

TOC

Special information RC/B3


Description

RC

Application
Room temperature controller CR24-B3
with three outputs, for room applications
Cooling and heating
Analog output 0 10 V DC for the control
of VAV terminal units with Easy, Compact
or Universal controllers
Analog output 0 10 V DC cooling
or heating (changeover)
3-point output for heating

Room temperature
controller CR24-B3

Parts and characteristics


Attractive unit for wall mounting,
signal white (RAL 9003)
Integral temperature sensor
Setpoint adjuster
Operating mode push button
Status indicator light
Analog output 0 10 V DC
for variable volume flow control
Analog output 0 10 V DC
for controlling a water valve
3-point output for controlling a heating valve
Analog inputs 0 10 V DC for external
temperature sensor and for setpoint
changes by an external unit
Digital inputs for energy-saving mode,
standby operation or changeover
Micro switch for configuration
Communication connection
for adjustment devices
Commissioning
Configure the control function
using a micro switch
Functional test

Technical data

Supply voltage
Power rating
External temperature sensor
External setpoint changes
Output for variable volume flow
Output for heating/cooling

24 V AC 20 %, 50/60 Hz
3 VA
NTC, 5 k, 10 45 C
0 10 V DC corresponding to 0 10 K
0 10 V DC, 5 mA max.
0 10 V DC, 5 mA max.
3-point, 24 V AC, max. 0.5 A, 10 VA,
optimised for actuators with a running time of approx. 150 s
III (protective extra-low voltage)
IP 30
EMC according to 2004/108/EG
84 99 32 mm
0.105 kg

Output for heating valve


IEC protection class
Protection level
EC conformity
Dimensions (B H T)
Weight

Electrical connection

Terminal connections

3 4 5 6 7 8
9 10 11 12
2
~ ai/di1 di2 ai2 ao1 PP1 PP2 ao3 ao3 ao2 di3
CR24-B3

1 :
2 ~:
3 ai/di1:

Neutral
Supply voltage
External temperature sensor
or energy-saving mode
4 di2:
Standby
5 ai2:
External setpoint changes
6 ao1:
Volume flow controller
7 PP1:
Diagnosis connection 1
8 PP2:
Diagnosis connection 2
9,10 ao3: Heating valve (3-point)
11 ao2: Heating/cooling valve (0 10 V DC)
12 di3:
Maximum volume flow rate/changeover
or dew point

05/2015 DE/en

K5 1.3 95

Control components for VAV terminal units

TOC

Special information RC/M1

RC

Description

Application
Room temperature controller
ETN-24-VAV-227V-P with two outputs,
for room applications
Cooling and heating
Analog output 0 10 V DC for the control
of VAV terminal units with Easy, Compact
or Universal controllers (cooling operation)
Analog output 0 10 V DC
controlling the reheating

Room temperature
controller
ETN-24-VAV-227-P

Useful additions
M2: Remote control
Parts and characteristics
Attractive unit for wall mounting, white
Setpoint adjuster
Operating mode push button
Integral temperature sensor
Analog input for external temperature sensor
Display for temperature and status
Analog output 0 10 V DC
for variable volume flow control
Analog output 0 10 V DC
controlling a heating valve
Communication connection
for adjustment devices
Commissioning
Configuring the control function
Functional test

Remote control
for room temperature
controller
ETN-24-VAV-227-P
Technical data

Supply voltage

24 V AC, 50/60 Hz

Power rating

1.2 VA

External temperature sensor

Thermistor 50 k at 45 C

Analog outputs for cooling operation, heating operation


IEC protection class
Protection level

IP 30

EC conformity

EMC according to 2004/108/EC

Dimensions (B H T)

92 80 22 mm

Weight
Electrical connection

0 10 V DC, max. 5 mA
III (protective extra-low voltage)

0.136 kg

Terminal connections

To

ENT-24-VAV-227V-P

R :
C ~:
0:
Y:
To, T:
X:
W:

K5 1.3 96

Neutral
Supply voltage
Ground
0 10 V output for cooling
(volume flow controller)
External temperature sensor
Communication (pp)
0 10 V output for heating (valve)

05/2015 DE/en

Control components for VAV terminal units

TOC

Specification text

Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

RC

Room temperature controller for the control


of VAV terminal units Attractive unit for wall
mounting, with a setpoint adjuster and a push
button to select the operating mode Integral
temperature sensor (NTC) and input for external
temperature measuring unit. Voltage output
0 10 V DC for connection to an electronic
volume flow controller for cooling,
or for heating and cooling in changeover mode.
Technical data
Supply voltage: 24 V AC, 50/60 Hz
Power rating:3 VA
External setpoint changes: 0 10 V DC
Output for variable volume flow: 0 10 V DC

Type
RC
Room temperature controller

K5 1.3 97

Type
B1
B2
B3
M1
M2

CR24-B1
CR24-B2
CR24-B3
ETN-24-VAV-277V-P
Remote control for M1

05/2015 DE/en

Adjustment devices

X X Adjustment

TOC

1.4

devices testregistrierung

Adjustment devices
for VAV terminal units

Type Adjustment devices

For service and commissioning


Adjustment devices for the service and commissioning of VAV terminal units.
For the display of actual values and parameters, and for functional tests.
Display of actual and setpoint values
Display and changing of parameters and operating modes
Easy plug connection to the controller or terminal connection
to the switch cabinet
Easy operation
Portable devices for use on site

05/2015 DE/en

K5 1.4 1

Adjustment devices for VAV terminal units

TOC

General information

Adjustment devices
Page

Type

Adjustment devices

Description

General information
Order code
Special information AT-VAV-B
Special information AT-VAV-G
Special information AT-VAV-S

1.4 2
1.4 3
1.4 4
1.4 6
1.4 7

Basic information and nomenclature

1.5 1

Application
Adjustment devices for VAV terminal units,
used to facilitate service and commissioning
Read actual values and setpoint values
Read and change parameters
Read and set operating modes
Functional test
Installation and commissioning
Recommendation: The signal line
for the individual adjustment devices
should be connected in an easily accessible
place; this avoids having to open any false
ceilings for inspection
or service at a later stage
Easily accessible places include: switch
cabinet, floor distribution box, or an unused
terminal on the room temperature controller
Important: The ground (and perhaps 24 V)
must also be available.
Wire connection to an additional service terminal in the switch cabinet

24 V

Room temperature
controller
y
~

Switch cabinet
or
floor distributor

Volume flow controller

Function

K5 1.4 2

Functional description
The adjustment device communicates
with the controller using the voltage signal line
for the actual value or setpoint value.
The adjustment device recognises the controller
type and allows access to the available operating
values and parameters.
The values are displayed.
Operation is with push buttons.

05/2015 DE/en

Adjustment devices for VAV terminal units

TOC

Order code
Order code

Adjustment devices

AT

AT VAV B

Type
AT-VAV Adjustment devices
for VAV terminal units

Order example

Variants
B
ZTH-EU for TROX/Belimo
volume flow controllers
G
for TROX/Gruner volume flow controllers
S
AST10 for Siemens volume flow controllers

AT-VAV S
Adjustment device for volume flow controllers

05/2015 DE/en

Siemens

K5 1.4 3

Adjustment devices for VAV terminal units

TOC

Special information AT-VAV-B

Description

Application
Adjustment device ZTH-EU
for VAV terminal units with TROX/Belimo
volume flow controllers, used to facilitate
service and commissioning
Read actual values and setpoint values
Read and change min and max
Read and change signal voltage ranges
Read and change the operating mode
Reset parameters to the factory settings
MP bus test
Measure and display the supply voltage
Integral ZIP-USB interface to connect
the device to a notebook on which
the Belimo PC tool is installed
Compatible volume flow controllers
The volume flow controllers are attachments
for VAV terminal units.
BC0; BF0: LMV-D*-MP, NMV-D*-MP
BL0: LMV-D3LON
BM0: LMV-D3-MOD*, NMV-D3-MOD*
BP1, BP3, BPB, BPG; BR1, BR3, BRB, BRG;
BS1, BS3, BSB, BSG: VRP-M
B11, B13, B1B; B27: VRD3

Adjustment devices
AT-VAV-B

Display
OK confirm selected value
Push button increase value
Push button decrease value
ESC cancel / back
i display additional information
MP socket for controller communication
with ZK1-GEN, ZK2-GEN
USB socket for PC communication

Parts and characteristics


Adjustment device ZTH-EU
Cable 1 (ZK1-GEN) with Belimo plug,
for the controller
Cable 2 (ZK2-GEN) with bare wire ends
that can be connected to terminals
Cable with USB 2.0 plug that can be connected
to PCs with the Belimo PC tool

K5 1.4 4

05/2015 DE/en

Adjustment devices for VAV terminal units

TOC

Special information AT-VAV-B


Electrical connection

Adjustment devices

Plug connection to the controller

Terminal connection to the controller


or switch cabinet

WT BL

TQ

1 2
5
~
*MV-D*-MP, VRD2

ZK1-GEN

WT BL

TQ

1 2
4
~
VRD3, VRP-M

Connecting cable

Connection to the PC tool

MP

USB

esc

ok

ZK1-GEN
USB 2.0
PC tool

05/2015 DE/en

K5 1.4 5

Adjustment devices for VAV terminal units

TOC

Special information AT-VAV-G

Description

Application
Adjustment device GUIV-A for
VAV terminal units with TROX/Gruner volume
flow controllers, used to facilitate service
and commissioning
Read actual values and setpoint values
Read and change min and max
Read and change signal voltage ranges
Read and change the operating mode
Reset parameters to the factory settings
Integral interface (replaces GUIV-S)
for the connection to a notebook
with Gruner VAV Tool Software installed
Compatible volume flow controllers
The volume flow controllers are attachments
for VAV terminal units.
XB0, XG0: 227V-024-**, 227P-024-**
XC3: GUAC-D3, GUAC-DM3
XD1, XD3: GUAC-S3, GUAC-SM3
XE1, XE3: GUAC-P1, GUAC-PM1
XF1, XF3: GUAC-P6, GUAC-PM6
Parts and characteristics
Adjustment device
Cable 1 with plug for the controller
Connecting cable 2 with two bare wire ends
that can be connected to terminals

Electrical connection

Plug connection to the controller

Adjustment devices
AT-VAV-G

Display
+/- push buttons
Set (acknowledge)
Escape (cancel)
Menu selection
Indicator lights
Connection for personal computer (mini USB)
Connection for controller

Terminal connection to the controller


or switch cabinet

BL BR

BK

1 2
4
~
227V, GUAC-*

Connecting cable

K5 1.4 6

05/2015 DE/en

Adjustment devices for VAV terminal units

TOC

Special information AT-VAV-S


Description

Application
Adjustment device Type AST10
for VAV terminal units with Siemens volume
flow controllers, used to facilitate service
and commissioning
Read actual values and setpoint values
Read and change min and max
Read and change the operating mode
Reset parameters to the factory settings
Compatible volume flow controllers
The volume flow controllers are attachments
for VAV terminal units.
LN0, LY0: GLB181.1E/3
LK0: GLB181.1E/KN
Parts and characteristics
Adjustment device
Cable 1 with 3-pole socket and 6-pole plug
connector for controllers up to Type D
Cable 2 with 3-pole socket and 7-pole plug
connector for controllers from Type E
Cable 3 with 3-pole socket and bare wire ends
that can be connected to terminals

Electrical connection

Plug connection to the controller

Adjustment devices
AT-VAV-S

Display
Increase value
Decrease value
Select parameters
Set (acknowledge)
Activate factory settings
Display reference value (n) or min
Display max or Y
3-pole plug connector as an adapter
for the supplied cables

Terminal connection to the controller


or switch cabinet

BR
1

Individual
di id l cables
bl

05/2015 DE/en

WT
2
~

GN
9

GLB181.1

Connecting cable

K5 1.4 7

TOC

1.5

X X Grundlagen

und Definitionentestregistrierung

Variable volume flow control


VARYCONTROL

Basic information
and nomenclature

Product selection
Principal dimensions
Nomenclature
Construction
Correction values for system attenuation
Measurements
Sizing and sizing example
Function
Operating modes

05/2015 DE/en

K5 1.5 1

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature

Product selection

Type
LVC

TVR

TVJ

TVT

Supply air

Extract air

TZ-Silenzio TA-Silenzio

TVZ

TVA

TVM

TVRK

TVLK TVR-Ex

Type of system

Dual duct (supply air)

Duct connection, fan end


Circular

Rectangular

Volume flow rate range


Up to [m/h]

1080

6050

36360 36360

3025

3025

6050

6050

6050

6050

1295

6050

Up to [l/s]

300

1680

10100 10100

840

840

1680

1680

1680

1680

360

1680

Filtered

Office extract air

Air quality

Polluted

Contaminated
Control function
Variable

Constant

Min/Max

Master

Pressure control
Master/Slave

Shut-off mode
Leakage
Low leakage

Acoustic requirements
High < 40 dB(A)
Low < 50 dB (A)
Other functions
Volume flow rate measurement
Special areas
Areas with explosive atmospheres
Labs, clean rooms,
operating theatres
(EASYLAB, TCU-LON II)

Possible
Possible under certain conditions: Robust unit variant and/or specific control component (attachment) or useful additional product
Not possible

K5 1.5 2

05/2015 DE/en

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature


Principal dimensions

Nomenclature

D [mm]
VAV terminal units made of stainless steel:
Outside diameter of the spigot
VAV terminal units made of plastic:
Inside diameter of the connecting spigot

B [mm]
Outside dimension of flange (width)

D [mm]
Pitch circle diameter of flanges

H [mm]
Duct height

D [mm]
Outside diameter of flanges

H [mm]
Screw hole pitch of flange (vertical)

D [mm]
Inside diameter of the screw holes of flanges

H [mm]
Outside dimension of flange (height)

L [mm]
Length of unit including connecting spigot

H [mm]
Unit height

L [mm]
Length of casing or acoustic cladding

n[]
Number of flange screw holes

B [mm]
Duct width

T [mm]
Flange thickness

B [mm]
Screw hole pitch of flange (horizontal)

m [kg]
Unit weight including the minimum required
attachments (e.g. Compact controller)

Acoustic data

Definition of noise

B [mm]
Width of device

fm [Hz]
Octave band centre frequency
LPA [dB(A)]
A-weighted sound pressure level
of air-regenerated noise of the VAV terminal unit,
system attenuation taken into account
LPA1 [dB(A)]
A-weighted sound pressure level
of air-regenerated noise of the VAV terminal unit
with secondary silencer, system attenuation taken
into account

LPA

Air-regenerated noise
Case-radiated noise

LPA2 [dB(A)]
A-weighted sound pressure level
of case-regenerated noise of the VAV terminal
unit, system attenuation taken into account
LPA3 [dB(A)]
A-weighted sound pressure level
of case-regenerated noise of the VAV terminal unit
with acoustic cladding, system attenuation taken
into account
All sound pressure levels are based on 20 Pa.

05/2015 DE/en

K5 1.5 3

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature


Volume flow rates

nom [m/h] and [l/s]


Nominal volume flow rate (100 %)
The value depends on product type
and nominal size
Values are published on the internet
and in technical leaflets, and stored
in the Easy Product Finder design software.
Reference value for calculating percentages
(e.g. max)
Upper limit of the setting range
and maximum volume flow rate setpoint
value for the VAV terminal unit
min unit [m/h] and [l/s]
Technically possible minimum volume flow rate
The value depends on product type, nominal
size and control component (attachment)
Values are stored
in the Easy Product Finder design software
Lower limit of the setting range and minimum
volume flow rate setpoint value
for the VAV terminal unit
Depending on the controller,
setpoint values below min unit
(if min equals zero) may result
in unstable control or shut-off

min [m/h] and [l/s]


Lower limit of the operating range for the VAV
terminal unit that can be set by customers
min should be smaller than or equal to max
Do not set min smaller than min unit,
otherwise the control may become unstable
or the damper blade may close
min may equal zero
In case of analog signalling to volume flow
controllers (which are typically used),
the set minimum value (min) is allocated
to the setpoint signal minimum (0 or 2 V)
(see characteristic)
[m/h] and [l/s]
Volume flow rate
[ %]
Volume flow rate tolerance from setpoint value
warm [ %]
Volume flow rate tolerance
for the warm air flow of dual duct terminal units

max [m/h] and [l/s]


Upper limit of the operating range
for the VAV terminal unit that can be
set by customers
max can only be smaller than or equal to nom
In case of analog signalling to volume flow
controllers (which are typically used),
the set maximum value (max) is allocated
to the setpoint signal maximum (10 V)
(see characteristic)
Characteristic of the setpoint value signal

Characteristic of the actual value signal


nom (100%)

nom (100%)

min

Setting range

Volume flow

Volume flow

max

min unit

min unit
0

0 10 V DC
2 10 V DC

K5 1.5 4

10 V DC

Setpoint value signal

10 V DC

0 10 V DC
2 10 V DC

Actual value signal U5

05/2015 DE/en

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature


Differential pressure

Static differential pressure

pst [Pa]
Static differential pressure
pst min [Pa]
Static differential pressure, minimum
The static minimum differential pressure
is equal to the pressure loss of the VAV terminal
unit when the damper blade is open,
caused by flow resistance
(sensor tubes, damper mechanism)
If the pressure on the VAV terminal unit
is too low, the setpoint volume flow rate may
not be achieved, not even when the damper
blade is open
Important factor in designing the ductwork
and in rating the fan including speed control
Sufficient duct pressure must be ensured for all
operating conditions and for all terminal units,
and the measurement point or points for speed
control must have been selected accordingly
to achieve this

Constructions

Galvanised sheet steel


Casing made of galvanised sheet steel
Parts in contact with the airflow as described
for the product type
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

st

Stainless steel (A2)


Casing made of stainless steel 1.4201
Parts in contact with the airflow
are powder-coated or made of stainless steel
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

Powder-coated surface (P1)


Casing made of galvanised sheet steel,
powder-coated RAL 7001, silver grey
Parts in contact with the airflow
are powder-coated or made of plastic
Due to production, some parts that come
into contact with the airflow may be stainless
steel or aluminium, powder-coated
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

05/2015 DE/en

K5 1.5 5

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature

The quick sizing tables


show the sound pressure
levels that can be
expected in a room both
for the air-regenerated
noise and for the caseradiated noise. The sound
pressure level in a room
results from the sound
power level of the
products for a given
volume flow rate and
differential pressure
and the attenuation
and insulation on site.
Generally accepted
attenuation and insulation
values have been taken
into account.
The distribution of air
across the ductwork,
changes of direction,
end reflection, and room
attenuation all affect
the sound pressure level
of the air-regenerated
noise.Ceiling insulation
and room attenuation
influence the sound
pressure level of the caseradiated noise.

Reducing the sound pressure level of the air-regenerated noise

Correction values
for acoustic quick sizing

Octave correction for the distribution in the ducting,


used to calculate the air-regenerated noise

The correction values


for the distribution
in the ducting are based
on the number of diffusers
assigned to any one
air terminal unit.
If there is just one diffuser
(assumption: 140 l/s or
500 m/h), no correction
is necessary.

One change of direction,


e.g. at the horizontal
connection of the diffuser
plenum box, has been
taken into consideration
for the system attenuation
values. Vertical
connection of the plenum
box does not result
in a system attenuation.
Additional bends result
in lower sound pressure
levels.

End reflection
Ceiling insulation

VAV terminal unit


Distribution in the ducting
Change of direction

in [m/h]

500

1000

1500

2000

2500

3000

4000

[l/s]

140

280

420

550

700

840

1100

[dB]

5000
1400
9

10

System attenuation per octave to VDI 2081 for the calculation of the air-regenerated noise
63

125

250

500

Centre frequency [Hz]

1000

2000

4000

8000

L
dB

Change of direction

Mndungsreflexion

10

Room attenuation

The calculation is based on the end reflection for nominal size 250

Octave correction for the calculation of case-radiated noise


63

125

250

500

Centre frequency [Hz]

1000

2000

4000

8000

L
dB

K5 1.5 6

Ceiling insulation

Room attenuation

05/2015 DE/en

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature


Measurements

The acoustic data


for the air-regenerated
noise and case-radiated
noise are determined
according to
EN ISO 5135.
All measurements
are carried out in a
reverberation chamber
to EN ISO 3741.

Measuring the air-regenerated noise

st

Reverberation chamber
VAV terminal unit
Microphone

LP

Fan
Sound attenuator

The sound pressure levels for air-regenerated noise LPA given by us result from measurements
in a reverberation chamber. The sound pressure LP is measured for the entire frequency range.
The evaluation of the measurements, including system attenuation and A-weighting,
results in the sound pressure level LPA.
Measuring the case-radiated noise

Reverberation chamber
VAV terminal unit
Microphone

st

LP

Fan
Sound attenuator

The sound pressure levels for case-radiated noise LPA2 given by us result from measurements
in a reverberation chamber. The sound pressure LP is measured for the entire frequency range.
The evaluation of the measurements, including system attenuation and A-weighting,
results in the sound pressure level LPA2.

05/2015 DE/en

K5 1.5 7

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature


Sizing with
the help of this catalogue

This catalogue provides convenient quick sizing


tables for VAV terminal units. The sound pressure
levels for air-regenerated noise and for caseradiated noise are provided for all nominal sizes.
In addition, generally accepted attenuation
and insulation values have been taken into
account. Sizing data for other volume flow
rates and differential pressures can be
determined quickly and precisely using
the Easy Product Finder design programme.

Sizing example

Given data
max = 280 l/s (1010 m3/h)
pst = 150 Pa
Required sound pressure
level in the room 30 dB(A)

Quick sizing
TVZ-D/200
Air-regenerated noise LPA = 23 dB(A)
Case-radiated noise LPA3 = 24 dB(A)
Sound pressure level in the room = 27 dB(A)
(logarithmic addition since the terminal unit
is installed in the suspended ceiling of the room)

Easy Product Finder

The Easy Product Finder


allows you to size
products using your
project-specific data.
You will find
the Easy Product Finder
on our website.

05/2015 DE/en

K5 1.5 8

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature

Volume flow control


The volume flow rate is controlled in a closed loop.
The controller receives from the transducer
the actual value that results from the effective
pressure. For most applications, the setpoint
value comes from a room temperature controller.
The controller compares the actual value with
the setpoint value and alters the command signal
of the actuator if there is a difference between
the two values.
Correction of duct pressure changes
The controller detects and corrects changes
of the duct pressure that may occur, for example,
due to volume flow rate changes from other units.
Pressure changes will therefore not affect
the room temperature.

Supply/extract air tracking control


In individual rooms and closed-off office areas,
where the balance between supply and extract
air flow rate has to be maintained. Otherwise,
annoying whistling noises can occur at door gaps,
and the doors can be difficult to open.
For this reason, the extract air should also
have variable control in a VAV system.
The supply air actual value (for dual duct
terminal units the actual value signal
of the warm air controller) is signalled to
the extract air controller (slave controller)
as setpoint signal. As a consequence,
the extract air always follows the supply air.

Variable volume flow


If the input signal is changed, the controller
adjusts the volume flow rate to the new setpoint.
The variable volume flow rate range is limited,
i.e. there is a minimum value and a maximum
value. This control strategy can be overridden,
e.g. by shutting off the duct.
Control loop

Control diagram

max

Volume flow

Function

min

Effective pressure transducer


Actuator
Volume flow controller
Setpoint value signal

K5 1.5 9

Supply air
Extract air

Setpoint adjuster

05/2015 DE/en

Variable volume flow control VARYCONTROL

TOC

Basic information and nomenclature


Operating modes

Single operation

Slave operation (master)

Constant value

1
+

Slave operation (slave)

05/2015 DE/en

K5 1.5 10

Constant volume flow control CONSTANTFLOW

TOC

Table of contents
2.

Constant volume flow control CONSTANTFLOW


CONSTANTFLOW volume flow controllers are mechanical self-powered controllers
for the control of supply air or extract air in constant air volume systems. The controllers
work basically without external power supply. For special applications they can be fitted
with actuators.

2.1 CAV controllers

Type

Page

For the precise control of constant


volume flow rates

RN

2.1 1

For low airflow velocities

VFC

2.1 17

Volume flow limiter for insertion


into ducting

VFL

2.1 26

For the precise control of normal and


high constant volume flows

EN

2.1 35

For the precise control of constant


volume flows in potentially explosive
atmospheres (ATEX)

RN-Ex

2.1 48

For the precise control of normal and


high constant volume flows in potentially EN-Ex
explosive atmospheres (ATEX)

2.1 59

Circular

Rectangular

Acoustically optimised

2.2 Actuators for CAV controllers

For constant volume flows with


min/max switching in
air conditioning systems

Min/Max
actuators

2.2 1

For variable volume flows in air


conditioning systems

Modulating
actuators

2.2 11

For variable volume flows or


min/max switching in room air
conditioning systems

Retrofit kits

2.2 17

2.3 Basic information and nomenclature


Constant volume flow control
CONSTANTFLOW

K5 2.0 1

2.3 1

05/2015 DE/en

RN

TOC

2.1

X X RNtestregistrierung

CAV controllers
Type RN

For the precise control of constant volume flow rates


Circular self-powered volume flow controllers for the control of supply air
or extract air in constant air volume systems
Volume flow rate can be set using an external scale, no tools required
High control accuracy
No on-site test measurements required for commissioning
Suitable for airflow velocities of up to 12 m/s
Any installation orientation; maintenance-free
Casing air leakage to EN 1751, class C
Actuator for switching
between setpoint values

H GE

TE

ET

HY

ISC

ST

EN

VD

Optional equipment and accessories


Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type CA, CS or CF for the reduction
of air-regenerated noise
Hot water heat exchanger Type WL and electric air heater Type EL
for reheating the airflow
Actuator for switching between setpoint values

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 2.1 1

CAV controllers

TOC

General information

RN

Type
RN

Variants

Page
General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight RN-S
Dimensions and weight RN
Dimensions and weight RN-D
Dimensions and weight RN-FL
Dimensions and weight RN-D-FL
Installation details
Specification text

2.1 2
2.1 6
2.1 7
2.1 8
2.1 9
2.1 10
2.1 11
2.1 12
2.1 13
2.1 14
2.1 15

Basic information and nomenclature

2.3 1

CAV controller variant RN-S, compact height

CAV controller variant RN

CAV controller variant RN-D

CAV controller variant RN, with actuator


for switching between setpoint values

Application
Circular CONSTANTFLOW CAV controllers
of Type RN for the precise supply air or extract
air flow control in constant air volume systems
Mechanical self-powered volume flow control
without external power supply
Simplified project handling
with orders based on nominal size
Volume flow rate setpoint
can be set on external scale
Switching between min and max using
optional actuator

Variants
RN-S: Compact-height volume flow controller
RN: Volume flow controller
RN-D: Volume flow controller
with acoustic cladding
RN-FL: Volume flow controller
with flanges on both ends
RN-D-FL: Volume flow controller with
acoustic cladding and flanges on both ends
Units with acoustic cladding and/or
a secondary silencer Type CA, CS or CF
for demanding acoustic requirements
Acoustic cladding cannot be retrofitted

Product examples

Description
For detailed information
on actuators see Chapter
K5 2.2.

K5 2.1 2

05/2015 DE/en

CAV controllers

TOC

General information
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Nominal sizes
RN-S: 80, 100, 125
RN: 80, 100, 125, 160, 200, 250, 315, 400
RN-FL: 100, 125, 160, 200, 250, 315, 400
Attachments
Min/Max actuators: Actuators for switching
between minimum and maximum volume
flow rate setpoint values
Modulating actuators: Actuators
for the stepless adjustment of volume
flow rates or to switch between minimum
and maximum volume flow rate setpoint values
Retrofit kits:
Actuators and installation accessories
Variant RN-S cannot be combined
with an actuator
Accessories
Lip seals on both ends (factory fitted)
Matching flanges for both ends
Useful additions
Secondary silencer Type CA, CS or CF
Heat exchanger Type WL
Electric air heater Type EL
Special features
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation
Parts and characteristics
Ready-to-commission controller
Damper blade with low-friction bearings
Bellows that acts as an oscillation damper
Cam plate with leaf spring
Scale with pointer to set the volume
flow rate setpoint
Aerodynamic function testing of each unit
on a special test rig prior to shipping
Correct operation even under unfavourable
upstream conditions
(1.5 D straight section required upstream)
Construction features
Circular casing
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
(RN-P1/80 without groove)
RN-FL: Circular flanges to EN 12220

05/2015 DE/en

RN
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel
Polyurethane bellows
Plain bearings with PTFE coating
Leaf spring made of stainless steel
Powder-coated construction (P1)
Casing made of galvanised
sheet steel, powder-coated
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel,
powder-coated
Stainless steel construction (A2)
Casing made of stainless steel 1.4301
Interior parts made of stainless steel
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Installation and commissioning
Any installation orientation
Volume flow rate can be set using
an external scale; no tools required
No repeat measurements or adjustments
by an air conditioning engineer are necessary
RN-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller
Standards and guidelines
Hygiene conforms to VDI 6022
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear

K5 2.1 3

CAV controllers

TOC

General information

RN

Attachments
Order code detail

Min/Max actuators
B50
B52
B60
B62
Modulating actuators
B70
B72

Technical data

K5 2.1 4

Actuator

Actuator with mechanical stops


TROX/Belimo

Actuator with mechanical stops


TROX/Belimo

Nominal sizes
Volume flow rate range
Volume flow rate control range
Scale accuracy
Minimum differential pressure
Maximum differential pressure
Operating temperature

Supply voltage
24 V AC/DC
230 V AC

24 V AC/DC

Auxiliary switch

80 400 mm
11 1400 l/s or 40 5040 m/h
Approx. 25 to 100 % of the nominal volume flow rate
4%
50 Pa
1000 Pa
10 50 C

05/2015 DE/en

CAV controllers

TOC

General information
Function

RN

Functional description
The volume flow controller is a mechanical
self-powered unit and works without external
power supply. A damper blade with low-friction
bearings is adjusted by aerodynamic forces such
that the set volume flow rate is maintained
within the differential pressure range.
The aerodynamic forces of the airflow create
a closing torque on the damper blade.
The bellows extends and increases this force
while at the same time acting as an oscillation
damper. The closing force is countered by a leaf
spring that unrolls over a cam plate. The shape
of the cam plate is such that a change
in the differential pressure leads to an adjustment
of the damper blade in a way that the volume
flow rate is maintained almost exactly.

Efficient commissioning
The volume flow rate setpoint value can be
set quickly and easily using the pointer on the
external scale; no measurements are required.
The advantage over flow adjustment dampers
is that there is no need for repeat measurements
or adjustments by an air conditioning engineer.
Should the system pressure change, e.g. by
opening or closing of duct sections, the flow
rates in the entire system will also change if flow
adjustment dampers are used; however, this is
not the case with mechanical self-powered
volume flow controllers A mechanical selfpowered controller reacts immediately and adjusts
the damper blade such that the set constant
volume flow rate is maintained.

Schematic illustration of the RN

Damper blade
Bellows
Bellows inlet
Crossbar
Leaf spring

05/2015 DE/en

Cam plate
Volume flow rate scale lock
Volume flow rate scale
Lip seal

K5 2.1 5

CAV controllers

TOC

Order code
Order code

RN
RN-S

RN-S P1 / 100 / D2

Type
RN-S Volume flow controller

Nominal size [mm]


80
100
125

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel

Order code

Accessories
No entry: none
D2
Lip seals on both ends

RN

RN D P1 FL / 160 / G2 / B50 / 300 800

Type
RN
Volume flow controller
Acoustic cladding
No entry: none
D
With acoustic cladding

Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel

Actuator
No entry: without
For example
B50 24 V AC/DC, 3-point
B52 24 V AC/DC, 3-point, with auxiliary switch
B70 24 V AC/DC, modulating 2 10 V DC

Flange
No entry: none
Flanges on both ends
FL

Volume flow rates [m3/h or l/s]


only actuators
min max for factory setting

Nominal size [mm]


80
100
125
160
200
250
315
400
Order examples

RN/160/D2
Nominal size
Material
Accessories

160
Galvanised sheet steel
Lip seal on both ends

RN-D-FL/250/G2/B50
Acoustic cladding
Flange
Material
Nominal size
Accessories
Actuator

K5 2.1 6

With
Both ends
Galvanised sheet steel
250
Matching flanges for both ends
B50

05/2015 DE/en

CAV controllers

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of CAV controllers
is an important factor
in designing the ductwork
and in rating the fan
including speed control.

Sufficient duct pressure


must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

RN

Volume flow rate ranges and minimum differential pressure values

l/s
80

100

125

160

200

250

315

400

Nominal size

m/h
11
20
40
45
22
40
70
90
35
60
115
140
60
105
190
240
90
160
300
360
145
255
470
580
230
400
750
920
350
610
1130
1400

40
72
144
162
79
144
252
324
126
216
414
504
216
378
684
864
324
576
1080
1296
522
918
1692
2088
828
1440
2700
3312
1260
2196
4068
5040

pst min
Pa

100
100
100
100
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

105
105
110
110
55
55
60
60
55
55
60
60
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55

%
105
105
115
120
55
55
65
70
55
55
65
70
55
55
60
65
55
55
60
60
55
55
60
60
55
55
60
60
55
55
55
55

105
105
120
125
55
60
70
80
55
55
70
80
55
55
60
70
55
55
65
65
55
55
60
65
55
55
60
65
55
55
55
60

20
15
10
8
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5

RN
RN with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
RN with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
RN with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm

K5 2.1 7

05/2015 DE/en

CAV controllers

TOC

Quick sizing
Air-regenerated noise

RN
Quick sizing: Sound pressure level at differential pressure 150 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
80

100

125

160

200

250

315

400

11
20
40
45
22
40
70
90
35
60
115
140
60
105
190
240
90
160
300
360
145
255
470
580
230
400
750
920
350
610
1130
1400

m/h
40
72
144
162
79
144
252
324
126
216
414
504
216
378
684
864
324
576
1080
1296
522
918
1692
2088
828
1440
2700
3312
1260
2196
4068
5040

LPA1

LPA
37
39
47
48
37
40
47
50
37
43
50
52
40
45
49
50
40
43
48
49
41
42
46
48
39
42
44
46
46
48
50
51

24
27
34
35
24
47
47
50
27
34
41
44
32
37
41
41
31
35
40
41
32
34
39
41
33
35
38
41
39
42
44
45

Case-radiated noise

dB(A)
17
19
24
25
17
22
27
30
21
27
35
39
26
32
35
36
24
28
33
35
24
28
33
35
26
29
32
35
33
36
38
40

15
17
22
24
15
20
26
29
18
25
33
37
24
29
33
34
22
26
32
33
22
26
31
34
23
27
31
34
29
32
35
37

LPA2

LPA3
22
24
31
32
22
21
29
33
15
19
27
30
29
33
39
41
28
32
40
42
29
33
40
43
30
35
40
43
45
49
54
56

<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
16
<15
<15
17
20
15
<15
19
22
<15
<15
19
23
<15
18
24
27

RN
RN with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
RN with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
RN with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm
RN-D

05/2015 DE/en

K5 2.1 8

CAV controllers

TOC

Dimensions and weight RN-S


Description

Compact-height volume flow controller


for constant volume flow rate control
Spigot to make connections to the ducting

CAV controller
variant RN-S,
compact height
Dimensions

RN-S, nominal size 80

RN-S, nominal size 80, lip seal


250

330
40

30

RNS 80

RNS 80

130

130

RN-S/80, RN-S-P1/80, RN-S-A2/80

RN-S/80/D2, RN-S-P1/80/D2

Dimensions [mm] and weight [kg]


Nominal size

mm

kg

80

79

1.4

RN-S, nominal size 100, 125


L
40

RN

130

Dimensions [mm] and weight [kg]


Nominal size
100
125

K5 2.1 9

mm
99
124

kg
250
250

50
50

1.8
2.0

05/2015 DE/en

CAV controllers

TOC

Dimensions and weight RN


Description

RN

Volume flow controller for constant


air volume flow control
Spigot to make connections to the ducting

CAV controller variant RN


Dimensions

RN
L

182

Dimensions [mm] and weight [kg]


D

Nominal size

mm

80
100
125
160
200
250
315
400

79
99
124
159
199
249
314
399

RN-P1/80

kg
310
310
310
310
310
400
400
400

50
50
50
50
50
50
50
50

1.4
1.8
2.0
2.5
3.0
3.5
4.8
5.7

RN-P1/80/D2
250

330

79

40

79

30

RN 80

RN 80

182

182

RN-A2/80
310

79

50

RN 80

182

05/2015 DE/en

K5 2.1 10

CAV controllers

TOC

Dimensions and weight RN-D


Description

RN

Volume flow controller with acoustic cladding


for constant air volume flow control
Spigot to make connections to the ducting
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted

CAV controller
variant RN-D
Dimensions

RN-D
L

Dimensions [mm] and weight [kg]


D

L
mm

80
100
125
160
200
250
315
400

79
99
124
159
199
249
314
399

181
200
220
262
300
356
418
500

232
232
232
232
232
312
312
312

310

232

232

181

330

RN 80

2.2
3.6
4.0
5.0
6.0
7.3
9.8
11.8

RN 80

182

05/2015 DE/en

310
310
310
310
310
400
400
400

m
kg

RN-D-A2/80

79

181

RN-D-P1/80/D2

L1

D3

79

Nominal size

182

K5 2.1 11

CAV controllers

TOC

Dimensions and weight RN-FL

RN

Description

Volume flow controller for constant


air volume flow control
With flanges to make detachable connections
to the ductwork

Dimensions

RN-FL





Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

K5 2.1 12

L
mm
99
124
159
199
249
314
399

290
290
290
290
380
380
380

D2

D1
132
157
192
233
283
352
438

n
152
177
212
253
303
378
464

4
4
6
6
6
8
8

mm

kg
4
4
4
4
4
4
4

2.4
2.7
3.5
4.4
5.3
7.3
9.6

05/2015 DE/en

CAV controllers

TOC

Dimensions and weight RN-D-FL


Description

Volume flow controller with acoustic cladding


for constant air volume flow control
With flanges to make detachable connections
to the ductwork
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others) on the fan
and room ends
Acoustic cladding cannot be retrofitted
Powder-coated surface (P1) or stainless steel
construction (A2) not possible

RN-D-FL
L

Dimensions

RN


T


Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

05/2015 DE/en

D
99
124
159
199
249
314
399

D1
370
370
370
370
460
460
460

mm

132
157
192
233
283
352
438

D2
152
177
212
253
303
378
464

D3
200
220
262
300
356
418
500

L1

n
232
232
232
232
312
312
312

4
4
6
6
6
8
8

mm

kg
4
4
4
4
4
4
4

4.2
4.7
6.0
7.4
9.1
12.3
15.7

K5 2.1 13

CAV controllers

TOC

Installation details
Junction

D
D

1.5D

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the CAV controller has only a
negligible effect on the volume flow rate accuracy.

Free air intake only


with a straight duct
section of 1D upstream.

Space requirement
for commissioning
and maintenance
Sufficient space
must be kept clear near
any attachments to allow
for commissioning
and maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access for commissioning and maintenance

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

RN

Space required
Attachments
Without actuator
With actuator

K5 2.1 14

mm
200
200

200
320

200
300

05/2015 DE/en

CAV controllers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular volume flow controllers for constant air


volume systems, mechanical self-powered,
without external power supply, suitable for supply
or extract air, available in 8 nominal sizes.
Ready-to-commission unit consists of the casing
containing a damper blade with low-friction
bearings, bellows, external cam plate
and leaf spring.
Volume flow controllers without actuators
are factory set to a reference volume flow rate
(customers can set the required
volume flow rate on site).
Spigot with groove for lip seal,
suitable for connecting ducts according to
EN 1506 or EN 13180.
Casing air leakage to EN 1751, class C.
Special features
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel
Polyurethane bellows
Plain bearings with PTFE coating
Leaf spring made of stainless steel

RN
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Technical data
Nominal sizes: 80 to 400 mm
Volume flow rate range:
11 to 1400 l/s or 40 to 5040 m/h
Volume flow rate control range:
approx. 25 100 %
of the nominal volume flow rate
Minimum differential pressure: 50 Pa
Maximum differential pressure: 1000 Pa
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Powder-coated construction (P1)


Casing made of galvanised
sheet steel, powder-coated
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel,
powder-coated
Stainless steel construction (A2)
Casing made of stainless steel 1.4301
Interior parts made of stainless steel
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool

Order options

Type
RN-S
Volume flow controller
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel

05/2015 DE/en

Nominal size [mm]


80
100
125
Accessories
No entry: none
D2
Lip seals on both ends

K5 2.1 15

CAV controllers

TOC

Specification text
Order options

Type
RN
Volume flow controller
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel

Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
80
100
125
160
200
250
315
400

K5 2.1 16

RN
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Actuator
No entry: without
For example
B50 24 V AC/DC, 3-point
B52 24 V AC/DC, 3-point,
with auxiliary switch
B70 24 V AC/DC, modulating 2 10 V DC
Volume flow rates [m3/h or l/s]
only actuators
min max for factory setting

05/2015 DE/en

VFC

TOC

2.1

X X VFCtestregistrierung

CAV controllers
Type VFC

Variant with rotary knob

Actuator
with mechanical stops

For low airflow velocities


Circular mechanical self-powered volume flow controllers for the control of supply air
or extract air in constant air volume systems with low airflow velocities
Suitable for airflow velocities from 0.8 m/s
Very simple commissioning
Volume flow rate can be set using a rotary knob
and a scale on the outside of the casing
Simple retrofit of an actuator for variable volume flows
Any installation orientation; maintenance-free
Casing air leakage to EN 1751, class C

Actuator
with potentiometers

H GE

TE

ET

HY

ISC

ST

EN

Optional equipment and accessories


Secondary silencer Type CA, CS or CF
for the reduction of air-regenerated noise

VD

Hot water heat exchanger Type WL and electric air heater Type EL
for reheating the airflow
Actuator for variable volume flows or for min / max switching

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 2.1 17

CAV controllers

TOC

General information

VFC

Type
VFC

Page
General information
Order code
Quick sizing
Dimensions and weight
Installation details
Specification text

2.1 18
2.1 21
2.1 22
2.1 23
2.1 24
2.1 25

Basic information and nomenclature

2.3 1

VFC system

CAV controller with rotary knob


Actuator E0* with potentiometers

Description

CAV controller
variant VFC,
with rotary knob
For detailed information
on actuators see Chapter
K5 2.2.

Application
Circular CAV controllers of Type VFC
for the precise supply air or extract air flow
control in constant air volume systems
Mechanical self-powered volume flow control
without external power supply
For low airflow velocities
Simplified project handling with orders based
on nominal size
Nominal sizes
80, 100, 125, 160, 200, 250
Attachments
Min/Max actuators: Actuators for switching
between minimum and maximum volume flow
rate setpoint values
Modulating actuators: Actuators
for the stepless adjustment
of volume flow rates
Useful additions
Secondary silencer Type CA, CS or CF
Heat exchanger Type WL
Electric air heater Type EL

K5 2.1 18

Actuator M0* with mechanical stops

Special features
Volume flow rate can be set using
an external scale; no tools required
Simple retrofit of an actuator is possible
Correct operation even under unfavourable
upstream or downstream conditions
(1.5 D straight section required upstream)
Any installation orientation
Aerodynamic function testing of each unit
on a special test rig prior to shipping
Parts and characteristics
Ready-to-commission controller
Damper blade with low-friction bearings
Bellows that acts as an oscillation damper
Leaf spring
Rotary knob with pointer
for setting the volume flow rate
Lip seal
Construction features
Circular casing
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180
Damper blade with low-friction
bearings and special bellows

05/2015 DE/en

CAV controllers

TOC

General information

VFC

Materials and surfaces


Casing made of galvanised sheet steel
Damper blade and other parts
made of high-quality plastic, to UL 94, V1;
to DIN 4102, material classification B2
Leaf spring made of stainless steel
Polyurethane bellows
Installation and commissioning
Any installation orientation
Take the adjustment value
from the characteristic on the sticker
(on each volume flow controller)
Volume flow rate setpoint
can be set on external scale

Standards and guidelines


Hygiene conforms to VDI 6022
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Attachments
Order code detail
Min/Max actuators
E01
E02
M01
M02
Modulating actuators
E03

Technical data

05/2015 DE/en

Actuator

Supply voltage

Auxiliary switch

Actuator with potentiometers


TROX/Gruner

24 V AC/DC
230 V AC
24 V AC/DC
230 V AC

24 V AC/DC

Actuator with mechanical stops


TROX/Belimo
Actuator with potentiometers
TROX/Gruner

Nominal sizes
Volume flow rate range
Volume flow rate control range
Volume flow rate accuracy
Minimum differential pressure
Maximum differential pressure
Operating temperature

80 250 mm
6 370 l/s or 22 1332 m/h
Approx. 10 to 100 % of the nominal volume flow rate
approx. 10 % of the nominal volume flow rate
30 Pa
500 Pa
10 50 C

K5 2.1 19

CAV controllers

TOC

General information
Function

VFC

Functional description
The volume flow controllers work without
an external power supply. A damper blade
with low-friction bearings is adjusted
by aerodynamic forces such that a set volume
flow rate is maintained within the differential
pressure range. The aerodynamic forces
of the airflow create a closing torque
on the damper blade. The bellows extends
and increases this force while at the same
time acting as an oscillation damper.
The closing force is countered by a leaf spring.
As the differential pressure changes, the leaf
spring adjusts the position of the damper blade
such that the volume flow rate is maintained
almost exactly.

Efficient commissioning
The volume flow rate setpoint value can be set
quickly and easily using the pointer on the
external scale; no measurements are required.
The advantage over flow adjustment dampers
is that there is no need for repeat measurements
or adjustments by an air conditioning engineer.
Should the system pressure change, e.g. by
opening or closing of duct sections, the flow rates
in the entire system will also change if flow
adjustment dampers are used; however, this
is not the case with mechanical self-powered
volume flow controllers A mechanical selfpowered controller reacts immediately and adjusts
the damper blade such that the set constant
volume flow rate is maintained.

Schematic illustration of the VFC

Damper blade
Leaf spring
Volume flow rate scale
Rotary knob locking screw

K5 2.1 20

Rotary knob
Lip seal
Diagram with setting values
Bellows inlet

05/2015 DE/en

CAV controllers

TOC

Order code
Order code

VFC
VFC

VFC / 100 / E01

Type
VFC Volume flow controller
Nominal size [mm]
80
100
125
160
200
250
Order example

Actuator
No entry: manual operation
For example
E01 24 V AC/DC, 3-point, potentiometer
E03 24 V AC/DC, modulating 2 10 V DC,
potentiometer
M01 24 V AC/DC, 3-point, mechanical stops

VFC/100/E03
Nominal size
Actuator

05/2015 DE/en

100 mm
Variable volume flow, 24 V AC/DC, potentiometer, control signal 0 to 10 V DC

K5 2.1 21

CAV controllers

TOC

Quick sizing
Air-regenerated noise

VFC
Quick sizing: Sound pressure level at differential pressure 50 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
80

100

125

160

200

250

6
10
20
42
6
15
30
65
10
20
45
100
18
45
85
185
25
60
120
250
37
100
185
370

m/h
22
36
72
151
22
54
108
234
36
72
162
360
65
162
306
666
90
216
432
900
133
360
666
1332

LPA1

LPA
25
28
33
39
29
33
37
41
22
27
34
41
25
32
36
41
27
31
35
37
31
35
36
37

<15
16
21
27
15
20
26
33
<15
16
25
34
16
24
29
35
16
22
27
30
21
25
28
29

Case-radiated noise

LPA2

dB(A)

<15
<15
<15
18
<15
<15
18
26
<15
<15
18
29
<15
18
24
30
<15
16
21
25
<15
18
21
23

<15
<15
<15
16
<15
<15
17
25
<15
<15
16
27
<15
16
22
28
<15
<15
19
24
<15
16
19
22

<15
<15
<15
17
<15
15
18
21
<15
<15
<15
16
<15
18
22
27
<15
18
22
26
18
22
25
29

VFC
VFC with secondary silencer CS/CF, insulation thickness 50 mm, length 500 mm
VFC with secondary silencer CS/CF, insulation thickness 50 mm, length 1000 mm
VFC with secondary silencer CS/CF, insulation thickness 50 mm, length 1500 mm

K5 2.1 22

05/2015 DE/en

CAV controllers

TOC

Dimensions and weight


Dimensions

VFC

VFC
232
50

15

CAV controller
variant VFC,
with rotary knob

VFC/.../E0*
232
50

CAV controller
variant VFC/.../E0*, with
actuator (potentiometer)

85

VFC/.../M0*
232
50

CAV conotroller
variant VFC/.../M0*
with actuator
(mechanical stops)

35

Dimensions [mm] and weight [kg]


VFC VFC/.../E0* VFC/.../M0*
Nominal size

m
kg

80
100
125

05/2015 DE/en

0.5
0.6
0.7

0.8
0.9
1.0

VFC VFC/.../E0* VFC/.../M0*


Nominal size

mm
0.7
0.8
0.9

79
99
124

kg
160
200
250

0.8
1.0
1.3

1.1
1.3
1.6

D
mm

1.0
1.2
1.5

159
199
249

K5 2.1 23

CAV controllers

TOC

Installation details

Junction

D
D

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

VFC

1.5D

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the CAV controller has only a
negligible effect on the volume flow rate accuracy.

Free air intake only


with a straight duct
section of 1D upstream.

Space requirement
for commissioning
and maintenance

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required
Attachments
Without actuator
With actuator E0*
With actuator M0*

K5 2.1 24

mm
200
200
200

200
200
200

200
300
230

05/2015 DE/en

CAV controllers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular volume flow controllers for constant


and variable air volume systems with low airflow
velocities, mechanical self-powered,
without external power supply, suitable for supply
or extract air, available in 6 nominal sizes.
Ready-to-commission unit consists of the casing
containing a damper blade with low-friction
bearings, bellows, leaf spring, and a rotary knob
to set the volume flow rate setpoint.
Differential pressure: 30 500 Pa
Volume flow rate: max. 10 : 1
Spigot with lip seal, for circular
connecting ducts to EN 1506 or EN 13180.
Casing air leakage to EN 1751, class C.
Special features
Volume flow rate can be set using
an external scale; no tools required
Simple retrofit of an actuator is possible
Correct operation even under unfavourable
upstream or downstream conditions
(1.5 D straight section required upstream)
Any installation orientation
Aerodynamic function testing of each unit
on a special test rig prior to shippin

VFC
Technical data
Nominal sizes: 80 to 250 mm
Volume flow rate range:
6 to 370 l/s or 22 to 1332 m/h
Volume flow rate control range:
approx. 10 100 %
of the nominal volume flow rate
Volume flow rate accuracy:
approx. 10 % of the nominal volume flow rate
Minimum differential pressure: 30 Pa
Maximum differential pressure: 500 Pa
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Materials and surfaces


Casing made of galvanised sheet steel
Damper blade and other parts
made of high-quality plastic, to UL 94, V1;
to DIN 4102, material classification B2
Leaf spring made of stainless steel
Polyurethane bellows

Order options

Type
VFC
Volume flow controller
Nominal size [mm]
80
100
125
160
200
250

05/2015 DE/en

Actuator
No entry: manual operation
For example
E01 24 V AC/DC, 3-point, potentiometer
E03 24 V AC/DC, modulating 2 10 V DC,
potentiometer
M01 24 V AC/DC, 3-point, mechanical stops

K5 2.1 25

VFL

TOC

2.1

X X VFLtestregistrierung

CAV controllers
Type VFL

Aerodynamic damper blade

Sticker showing volume


flow rates

Set the volume flow rate

Volume flow limiter for insertion into ducting


Circular, mechanical self-powered controllers for insertion into ducting,
for the quick and easy balancing of constant volume flow rates in ventilation
and air conditioning systems
Unique damper blade edge for acoustic optimisation
Simple and quick commissioning on site
Range of volume flow rate setpoints for each nominal size
Precise and simple setting of volume flow rates using a scale
Best accuracy among controllers for insertion
Suitable for low airflow velocities from 0.8 m/s
Any installation orientation; maintenance-free

Insert

H GE

TE

ET

HY

ISC

ST

EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 2.1 26

CAV controllers

TOC

General information

VFL
Page

Type
VFL

General information
Order code
Quick sizing
Dimensions and weight
Specification text

2.1 27
2.1 30
2.1 31
2.1 33
2.1 34

Basic information and nomenclature

2.3 1

Set

Insert

Done

K5 2.1 27

05/2015 DE/en

CAV controllers

TOC

General information
Description

Volume flow limiter


Type VFL

Application
Circular volume flow limiters of Type VFL
for the simple balancing of volume flow rates
in air conditioning systems
Mechanical self-powered volume flow limiter
without external power supply
Simplified project handling with orders based
on nominal size
Set the required volume flow rate using a scale
Nominal sizes
80, 100, 125, 150, 160, 200, 250
Special features
Mechanical self-powered
Low-friction bellows
For circular ducts
Lip seal for tight and secure fit
Aerodynamically tested and factory
set to a reference volume flow rate
Sticker showing volume flow rates
(in l/s, m/h and cfm)
that can be set each limiter
Parts and characteristics
Ready-to-commission limiter
Damper blade with low-friction bearings
Bellows that acts as an oscillation damper
Leaf spring
Lip seal
Multi-level volume flow rate setpoint values

Technical data

05/2015 DE/en

Nominal sizes
Volume flow rate range
Volume flow rate control range
Volume flow rate accuracy
Minimum differential pressure
Maximum differential pressure
Operating temperature

VFL
Construction features
Circular casing
Suitable for insertion into circular ducts
to EN 1506 or EN 13180
Lip seal for tight and secure fit
Acoustically optimised damper blade
with low-friction bearings and special bellows
Different damper blade construction
and volume flow rate sticker
for nominal size 150
Materials and surfaces
Casing and damper blade made of high-quality
plastic, to UL 94, V0; to DIN 4102,
material classification B2
Leaf spring made of stainless steel
Polyurethane bellows
Installation and commissioning
Any installation orientation
Set the required volume flow rate using a scale
Insert the unit into the duct
Mark the installation location
Standards and guidelines
Hygiene conforms to VDI 6022
Maintenance
Maintenance-free as construction
and materials are not subject to wear

80 250 mm
4 212 l/s or 14 764 m/h
< 20 100 % of the nominal volume flow rate
approx. 10 % of the nominal volume flow rate
30 Pa
300 Pa
10 50 C

K5 2.1 28

CAV controllers

TOC

General information
Function

VFL

Functional description
The volume flow limiter is a mechanica
self-powered unit and works without external
power supply. A damper blade with low-friction
bearings is adjusted by aerodynamic forces
such that the set volume flow rate is limited
as a consequence. The aerodynamic forces
of the airflow create a closing torque
on the damper blade. The bellows extends
and increases this force while at the same time
acting as an oscillation damper. The closing force
is countered by a leaf spring. As the differential
pressure changes, the leaf spring adjusts#
the position of the damper blade such
that the volume flow rate is limited.

Efficient commissioning
The volume flow limiter performs the previously
tedious and expensive balancing of volume flow
rates in ventilation and air conditioning systems.
Simple handling and perfect function help to save
valuable working time on site. The required
volume flow rate can be set at the point
of installation, then the volume flow limiter
is inserted into the duct. The set volume
flow rate will then be limited and maintained
within close tolerances.

Schematic illustration of the VFL

Damper blade
Bellows inlet
Bellows

K5 2.1 29

Crossbar
Volume flow rate scale

05/2015 DE/en

CAV controllers

TOC

Order code
Order code

VFL
VFL

VFL / 100

Type
VFL Volume flow limiter

Order example

Nominal size [mm]


80
100
125
150
160
200
250

VFL/100
Nominal size

05/2015 DE/en

100 mm

K5 2.1 30

CAV controllers

TOC

Quick sizing
Volume flow rate ranges

VFL
Available volume flow rate setpoint values [m3/h]
1

The volume flow limiters are


factory set to the reference
volume flow rate ref.
Customers can then simply
set the required volume flow
rate (setting values 1 to 11).

10

11

Nominal size

Nenn

ref

m/h
80
100
125
150
160
200
250

14
18
39
50
58
94
159

17
24
48
70
82
127
215

22
33
58
85
102
166
278

28
39
69
105
128
207
337

33
48
82
120
156
253
399

39
58
98
140
175
297
473

50
71
113
160
195
343
519

62
79
131
185
217
391
574

73
92
150
205
242
436
632

17
22
37
51
60
109
160

20
26
42
57
67
121
175

82
105
171
230
272
481
705

122
195
265
323
529
764

82
122
195
265
323
529
764

33
71
98
160
156
297
473

Available volume flow rate setpoint values [l/s]


1

10

11

Nominal size

Nenn

ref

l/s
80
100
125
150
160
200
250

Free air intake only


with a straight duct
section of 1D upstream.

K5 2.1 31

6
9
16
24
28
46
77

8
11
19
29
36
58
94

9
13
23
33
43
70
111

11
16
27
39
49
83
131

14
20
31
44
54
95
144

23
29
48
64
76
134
196

34
54
74
90
147
212

23
34
54
74
90
147
212

9
20
27
44
43
83
131

Junction

Bend

D
D

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

5
7
13
19
23
35
60

1D

Upstream conditions

4
5
11
14
16
26
44

1.5D
1,5D

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the volume flow limiter has only a
negligible effect on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the volume flow limiter. If there is no straight
upstream section at all, the control will not be
stable, even with a perforated plate.

05/2015 DE/en

CAV controllers

TOC

Quick sizing
Air-regenerated noise
Quick sizing tables
provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on generally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
volume flow limiter
is required.

VFL
Quick sizing: Sound pressure level at differential pressure 50 Pa

l/s

80

100

125

150

160

200

250

05/2015 DE/en

Air-regenerated noise

Nominal size

LPA

m/h
4
6
14
20
23
5
11
16
26
34
11
19
27
42
54
14
29
44
57
74
16
28
49
67
90
26
70
109
134
147
44
94
144
175
212

dB (A)
14
22
50
73
82
18
39
58
92
122
39
69
98
150
195
50
105
160
205
265
58
102
175
242
323
94
253
391
481
529
159
337
519
632
764

30
30
32
33
34
31
33
35
36
37
36
37
37
38
39
32
32
33
33
34
26
29
32
34
36
23
27
30
31
31
23
26
28
28
28

K5 2.1 32

CAV controllers

TOC

Dimensions and weight


Dimensions

VFL

VFL

m/h

DN 80

Volume flow limiter


Type VFL

Dimensions [mm] and weight [kg]


Nominal size
80
100
125
160
200
250

K5 2.1 33

mm
78
98
122
156
196
246

kg
86
100
118
148
175
220

0.10
0.15
0.25
0.40
0.50
0.70

05/2015 DE/en

CAV controllers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular volume flow limiters in 7 nominal sizes,


made of high-quality plastic, to limit and control
volume flows in air conditioning systems.
Ready-to-commission unit which consists
of the casing with setpoint scale and the control
mechanism with leaf spring and low-friction,
silicone-free bellows.
Easy insertion into circular ducts to EN 1506
or EN 13180; secure fit ensured by a lip seal.
Aerodynamically tested and factory set
to a reference volume flow rate.
Can be subsequently accurately adjusted
within a volume flow rate range of at least 5 : 1.
Special features
Mechanical self-powered
Low-friction bellows
For circular ducts
Lip seal for tight and secure fit
Aerodynamically tested and factory
set to a reference volume flow rate
Sticker showing volume flow rates
(in l/s, m/h and cfm) that can be
set each limiter

Order options

05/2015 DE/en

Type
VFL
Volume flow limiter

VFL
Materials and surfaces
Casing and damper blade made of high-quality
plastic, to UL 94, V0; to DIN 4102,
material classification B2
Leaf spring made of stainless steel
Polyurethane bellows
Technical data
Nominal sizes: 80 250 mm
Volume flow rate range:
4 to 212 l/s or 14 to 764 m/h
Volume flow rate control range:
< 20 to 100 % of the nominal volume flow rate
Volume flow rate accuracy:
approx. 10 % of the nominal volume flow rate
Minimum differential pressure: 30 Pa
Maximum differential pressure: 300 Pa
Sizing data
[m/h]
pst[Pa]
LPA air-regenerated noise[dB(A)]

Nominal size [mm]


80
100
125
150
160
200
250

K5 2.1 34

EN

TOC

2.1

X X ENtestregistrierung

CAV controllers
Type EN

For the precise control of normal


and high constant volume flows
Rectangular self-powered volume flow controllers for the control
of supply air or extract air in constant air volume systems
Suitable for volume flow rates up to 12,096 m/h or 3,360 l/s
Volume flow rate can be set using an external scale, no tools required
High control accuracy
No on-site test measurements required for commissioning
Suitable for airflow velocities of up to 8 m/s
Casing air leakage to EN 1751, up to class C

Actuator for switching


between setpoint values

Optional equipment and accessories


Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TX for the reduction of air-regenerated noise
Hot water heat exchanger of Type WT for reheating the airflow
Actuator for switching between setpoint values

Unit with two controllers

05/2015 DE/en

K5 2.1 35

CAV controllers

TOC

General information

EN

Type
EN

2
Variants

Page
General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight EN
Dimensions and weight EN-D
Installation details
Specification text

2.1 36
2.1 39
2.1 40
2.1 42
2.1 44
2.1 45
2.1 46
2.1 47

Basic information and nomenclature

2.3 1

Volume flow controller Type EN

CAV controller Type EN-D

Application
Rectangular CONSTANTFLOW
CAV controllers of Type EN for the precise
supply air or extract air flow control
in constant air volume systems
Mechanical self-powered volume flow control
without external power supply
Simplified project handling with orders based
on nominal size

Useful additions
Secondary silencer Type TX
Heat exchanger Type WT

Product examples

Description
For detailed information
on actuators see Chapter
K5 2.2.

Variants
EN: Volume flow controller
EN-D: Volume flow controller
with acoustic cladding
Units with acoustic cladding and/or secondary
silencer Type TX for demanding acoustic
requirements
Acoustic cladding cannot be retrofitted
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Nominal sizes
19 nominal sizes from 200 100 to 600 600
Attachments
Min/Max actuators: Actuators for switching
between minimum and maximum
volume flow rate setpoint values
Modulating actuators: Actuators for the
stepless adjustment of volume flow rates
or to switch between minimum
and maximum volume flow rate setpoint values
Retrofit kits: Actuators
and installation accessories
EN with actuator only up to H = 300 mm

K5 2.1 36

Special characteristics
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation
Correct operation even under unfavourable
upstream conditions
(1.5 B straight section required upstream)
Parts and characteristics
Ready-to-commission controller
Damper blade with low-friction bearings
Bellows that acts as an oscillation damper
Cam plate with leaf spring
Scale with pointer to set the volume
flow rate setpoint
Aerodynamic function testing of each
unit on a special test rig prior to shipping
Construction features
Rectangular casing
Flanges on both sides,
suitable for duct connection
Volume flow controllers from H = 400 mm
are fitted with two damper blades
and two volume flow rate scales

05/2015 DE/en

CAV controllers

TOC

General information

EN

Materials and surfaces


Galvanised sheet steel construction
Casing and damper blade
made of galvanised sheet steel
Leaf spring made of stainless steel
Polyurethane bellows
Plain bearings with PTFE coating

Standards and guidelines


Casing air leakage to EN 1751, class C
(B + H 400, class B)
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Powder-coated construction (P1)


Casing and damper blade
made of galvanised sheet steel, powder-coated

Variant with acoustic cladding (-D)


Acoustic cladding
made of galvanised sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Installation and commissioning
Any installation orientation
Volume flow rate can be set using
an external scale; no tools required
No repeat measurements or adjustments
by an air conditioning engineer are necessary
EN-D: For constructions with acoustic cladding,
ducts on the room side should have cladding
up to the acoustic cladding of the controller

Attachments
Order code detail
Min/Max actuators
B50
B52
B60
B62
Modulating actuators
B70
B72

Technical data

05/2015 DE/en

Actuator

Actuator with mechanical stops


TROX/Belimo

Actuator with mechanical stops


TROX/Belimo

Nominal sizes
Volume flow rate range
Volume flow rate control range
Scale accuracy
Minimum differential pressure
Maximum differential pressure
Operating temperature

Supply voltage
24 V AC/DC
230 V AC

24 V AC/DC

Auxiliary switch

200 100 to 600 600 mm


40 3360 l/s or 144 12096 m/h
Approx. 25 to 100 % of the nominal volume flow rate
4%
50 Pa
1000 Pa
10 50 C

K5 2.1 37

CAV controllers

TOC

General information
Function

EN

Functional description
The volume flow controller is a mechanical
self-powered unit and works without external
power supply. A damper blade with low-friction
bearings is adjusted by aerodynamic forces such
that the set volume flow rate is maintained within
the differential pressure range.
The aerodynamic forces of the airflow create
a closing torque on the damper blade.
The bellows extends and increases this force
while at the same time acting as an oscillation
damper. The closing force is countered by a leaf
spring that unrolls over a cam plate. The shape
of the cam plate is such that a change in
the differential pressure leads to an adjustment
of the damper blade in a way that the volume
flow rate is maintained almost exactly.

Efficient commissioning
The volume flow rate setpoint value can be
set quickly and easily using the pointer on the
external scale; no measurements are required.
The advantage over flow adjustment dampers is
that there is no need for repeat measurements
or adjustments by an air conditioning engineer.
Should the system pressure change, e.g. by
opening or closing of duct sections, the flow rates
in the entire system will also change if flow
adjustment dampers are used; however,
this is not the case with mechanical self-powered
volume flow controllers A mechanical
self-powered controller reacts immediately
and adjusts the damper blade such that the set
constant volume flow rate is maintained.

Schematic illustration of the EN

Volume flow rate scale


Volume flow rate scale lock
Crossbar
Cam plate

K5 2.1 38

Leaf spring
Bellows inlet
Bellows
Damper blade

05/2015 DE/en

CAV controllers

TOC

Order code
Order code

EN
EN

EN D P1 / 400200 / B50 / 800 3000

Nominal size [mm]


BH

Acoustic cladding
No entry: none
D
With acoustic cladding

Actuator
No entry: without
For example
B50 24 V AC/DC, 3-point
B52 24 V AC/DC, 3-point, with auxiliary switch
B70 24 V AC/DC, modulating 2 10 V DC
Volume flow rates [m3/h or l/s]
only actuators
min max for factory setting

EN-D/200100
Acoustic cladding
Material
Nominal size

05/2015 DE/en

Type
EN
Volume flow controller

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey

Order example

With
Galvanised sheet steel
200 100 mm

K5 2.1 39

CAV controllers

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of CAV controllers
is an important factor
in designing the ductwork
and in rating the fan
including speed control.

Sufficient duct pressure


must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

EN

Volume flow rate ranges and minimum differential pressure values

l/s
200 100

300 100

300 150

300 200

400 200

500 200

600 200

400 250

500 250

600 250

400 300

500 300

Nominal size

m/h
40
80
120
160
65
130
195
260
105
210
315
420
130
260
390
520
210
420
630
840
230
460
690
920
255
510
765
1020
220
440
660
880
300
600
900
1200
320
640
960
1280
315
630
945
1260
375
750
1125
1500

pst min
Pa

144
288
432
576
234
468
702
936
378
756
1134
1512
468
936
1404
1872
756
1512
2268
3024
828
1656
2484
3312
918
1836
2754
3672
792
1584
2376
3168
1080
2160
3240
4320
1152
2304
3456
4608
1134
2268
3402
4536
1350
2700
4050
5400

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

%
60
80
115
160
60
80
120
170
60
80
115
160
60
80
110
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160

13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5

EN
EN with secondary silencer TX

K5 2.1 40

05/2015 DE/en

CAV controllers

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of CAV controllers
is an important factor
in designing the ductwork
and in rating the fan
including speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

EN

Volume flow rate ranges and minimum differential pressure values

l/s
600 300

400 400

500 400

600 400

500 500

600 500

600 600

Nominal size

m/h
420
840
1260
1680
420
840
1260
1680
460
920
1380
1840
510
1020
1530
2040
600
1200
1800
2400
640
1280
1920
2560
840
1680
2520
3360

pst min
Pa

1512
3024
4536
6048
1512
3024
4536
6048
1656
3312
4968
6624
1836
3672
5508
7344
2160
4320
6480
8640
2304
4608
6912
9216
3024
6048
9072
12096

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

%
60
75
110
150
60
85
120
175
60
80
115
160
60
80
115
160
60
80
115
160
55
70
95
130
60
75
105
145

13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5

EN
EN with secondary silencer TX

05/2015 DE/en

K5 2.1 41

CAV controllers

TOC

Quick sizing
Air-regenerated noise

EN
Quick sizing: Sound pressure level at differential pressure 150 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
200 100

300 100

300 150

300 200

400 200

500 200

600 200

400 250

500 250

600 250

400 300

500 300

40
80
120
160
65
130
195
260
105
210
315
420
130
260
390
520
210
420
630
840
230
460
690
920
255
510
765
1020
220
440
660
880
300
600
900
1200
320
640
960
1280
315
630
945
1260
375
750
1125
1500

m/h
144
288
432
576
234
468
702
936
378
756
1134
1512
468
936
1404
1872
756
1512
2268
3024
828
1656
2484
3312
918
1836
2754
3672
792
1584
2376
3168
1080
2160
3240
4320
1152
2304
3456
4608
1134
2268
3402
4536
1350
2700
4050
5400

LPA

LPA1
35
41
44
46
38
44
45
47
41
44
46
47
45
46
46
47
42
43
44
44
40
40
41
42
38
39
39
40
44
45
45
45
41
42
43
43
40
40
41
42
45
46
47
47
43
44
44
45

Case-radiated noise

dB(A)
19
28
34
38
22
30
35
38
24
31
35
38
24
29
33
35
23
27
31
33
21
26
29
31
20
24
28
31
23
28
31
34
21
26
30
33
20
25
28
31
25
29
34
36
22
28
31
33

LPA2

LPA3
21
28
33
35
24
32
36
39
28
34
39
41
31
35
38
40
30
35
38
40
28
33
36
38
27
31
35
37
32
37
39
41
31
36
39
41
30
34
37
39
53
40
43
45
34
38
41
43

<15
21
26
30
16
24
29
32
19
26
32
35
21
26
29
32
20
26
30
33
18
24
28
31
17
23
27
31
22
27
30
33
21
27
30
33
20
25
29
32
25
30
34
36
23
29
32
35

EN
EN with secondary silencer TX
EN-D

K5 2.1 42

05/2015 DE/en

CAV controllers

TOC

Quick sizing
Air-regenerated noise

EN
Quick sizing: Sound pressure level at differential pressure 150 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
600 300

400 400

500 400

600 400

500 500

600 500

600 600

420
840
1260
1680
420
840
1260
1680
460
920
1380
1840
510
1020
1530
2040
600
1200
1800
2400
640
1280
1920
2560
840
1680
2520
3360

m/h
1512
3024
4536
6048
1512
3024
4536
6048
1656
3312
4968
6624
1836
3672
5508
7344
2160
4320
6480
8640
2304
4608
6912
9216
3024
6048
9072
12096

LPA

LPA1
41
42
42
43
47
49
49
50
45
46
47
47
43
44
44
45
47
48
49
49
45
46
46
46
46
47
48
48

Case-radiated noise

dB(A)
21
26
30
32
27
32
36
38
24
29
33
35
22
27
31
33
26
31
35
37
24
29
32
35
26
30
35
37

LPA2

LPA3
33
37
40
42
39
44
47
49
37
42
44
46
36
40
43
45
40
45
48
50
39
43
46
48
41
46
49
51

22
28
31
34
29
34
37
40
27
32
35
37
25
30
33
36
30
35
39
41
28
33
36
39
31
36
39
42

EN
EN with secondary silencer TX
EN-D

05/2015 DE/en

K5 2.1 43

CAV controllers

TOC

Dimensions and weight EN


Description

Volume flow controller for constant


air volume flow control

Volume flow controller


Type EN
Dimensions

EN

400

m/h
l/s

900

1200
360

2100

720

2400

1800

600

1500

480

EN

2700

300
0
/h
m

EN 400 x 200

1320

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
300 150
300 200
400 200
400 250
400 300
400 400
500 200
500 250
500 300
500 400
500 500
600 200
600 250
600 300
600 400
600 500
600 600

K5 2.1 44

Nominal width Nominal height

B2

B1

H1

H2

mm
200
300
300
300
400
400
400
400
500
500
500
500
500
600
600
600
600
600
600

100
100
150
200
200
250
300
400
200
250
300
400
500
200
250
300
400
500
600

234
334
334
334
434
434
434
434
534
534
534
534
534
634
634
634
634
634
634

kg
276
376
376
376
476
476
476
476
576
576
576
576
576
676
676
676
676
676
676

134
134
184
234
234
284
334
434
234
284
334
434
534
234
284
334
434
534
634

176
176
226
276
276
326
376
476
276
326
376
476
576
276
326
376
476
576
676

5
6
7
7
9
10
12
18
11
12
13
18
19
13
14
15
18
19
20

05/2015 DE/en

CAV controllers

TOC

Dimensions and weight EN-D


Description

CAV controller Type EN-D


Dimensions

EN

Volume flow controller with acoustic cladding


for constant air volume flow control
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The rectangular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted

EN-D

400

m/h
l/s

900

1200

360

2100

2400
2700

300

1800

600
720

1500
480

m
/h

EN 400 x 200

M8

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
300 150
300 200
400 200
400 250
400 300
400 400
500 200
500 250
500 300
500 400
500 500
600 200
600 250
600 300
600 400
600 500
600 600

05/2015 DE/en

Nominal width Nominal height

B2

B1

H1

H2

mm
200
300
300
300
400
400
400
400
500
500
500
500
500
600
600
600
600
600
600

100
100
150
200
200
250
300
400
200
250
300
400
500
200
250
300
400
500
600

234
334
334
334
434
434
434
434
534
534
534
534
534
634
634
634
634
634
634

kg
280
380
380
380
480
480
480
480
580
580
580
580
580
680
680
680
680
680
680

134
134
184
234
234
284
334
434
234
284
334
434
534
234
284
334
434
534
634

180
180
230
280
280
330
380
480
280
330
380
480
580
280
330
380
480
580
680

8
10
11
12
15
17
18
26
17
18
19
26
28
20
22
22
26
29
30

K5 2.1 45

CAV controllers

TOC

Installation details

Junction, vertical

1.5B

1.5B
1,5B

The stated volume flow rate accuracy


can only be achieved with a straight duct section
of at least 1.5H upstream between any bend
and the controller.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5H upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Bend, horizontal

Junction, horizontal

Free air intake only


with a straight duct
section of 1B upstream.

1.5B

1.5B
1,5B

The stated volume flow rate accuracy


can only be achieved with a straight duct section
of at least 1.5B upstream between any bend
and the controller.

Space requirement
for commissioning
and maintenance

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5B upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access for commissioning and maintenance

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may
be necessary to provide
sufficiently sized
inspection access
openings.

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend, vertical

Upstream conditions

EN

Space required
Attachments
Without actuator
With actuator

mm
200
200

H
H

200
300

H: Unit height

K5 2.1 46

05/2015 DE/en

CAV controllers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular volume flow controllers for constant


air volume systems, mechanical self-powered,
without external power supply, suitable for supply
or extract air, available in 19 nominal sizes.
Ready-to-commission unit consists of the casing
containing a damper blade with low-friction
bearings, bellows, external cam plate
and leaf spring. Volume flow controllers without
actuators are factory set to a reference volume
flow rate (customers can set the required
volume flow rate on site).
Both ends suitable for the connection of ducts.
Casing air leakage to EN 1751, class C
(B + H 400, class B)
Special characteristics
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation
Correct operation even under unfavourable
upstream conditions
(1.5 B straight section required upstream)

EN
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Technical data
Nominal sizes: 200 100 to 600 600 mm
Volume flow rate range:
40 to 3360 l/s or 144 to 12096 m/h
Volume flow rate control range:
approx. 25 100 %
of the nominal volume flow rate
Minimum differential pressure: 50 Pa
Maximum differential pressure: 1000 Pa
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Materials and surfaces


Galvanised sheet steel construction
Casing and damper blade
made of galvanised sheet steel
Leaf spring made of stainless steel
Polyurethane bellows
Plain bearings with PTFE coating
Powder-coated construction (P1)
Casing and damper blade
made of galvanised sheet steel, powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding
made of galvanised sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

Order options

Type
EN
Volume flow controller

Nominal size [mm]


BH

Acoustic cladding
No entry: none
D
With acoustic cladding

Actuator
No entry: without
For example
B50 24 V AC/DC, 3-point
B52 24 V AC/DC, 3-point,
with auxiliary switch
B70 24 V AC/DC, modulating 2 10 V DC

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey

Volume flow rates [m3/h or l/s]


only actuators
min max for factory setting

K5 2.1 47

05/2015 DE/en

RN-Ex

TOC

2.1

X X RN-Extestregistrierung

CAV controllers
Type RN-Ex

For the precise control of constant volume flows


in potentially explosive atmospheres (ATEX)

Adjustment scale

Circular, mechanical self-powered volume flow controllers for the control of supply air
or extract air in constant air volume systems,
approved and certified for potentially explosive atmospheres (ATEX)
ATEX-compliant construction
Approved for gases, mists, vapours and dusts in zones 1, 2, 21 and 22
Volume flow rate can be set using an external scale, no tools required
No on-site test measurements required for commissioning
Suitable for airflow velocities of up to 12 m/s
Any installation orientation

ATEX-Zertifizierung

Optional equipment and accessories


Acoustic cladding for the reduction of case-radiated noise
ET

HY

SCH GET
E

ST

I
EN

Casing air leakage to EN 1751, class C

VD

Secondary silencer Type CA for the reduction of air-regenerated noise

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 2.1 48

CAV controllers

TOC

General information

RN-Ex
Page

Type
RN-Ex

2
Description

CAV controllers
Type RN-Ex

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight RN-Ex
Dimensions and weight RN-Ex-D
Installation details
Specification text

2.1 49
2.1 52
2.1 53
2.1 54
2.1 55
2.1 56
2.1 57
2.1 58

Basic information and nomenclature

2.3 1

Application
Circular EXCONTROL CAV controllers
of Type RN-Ex for the precise supply air
or extract air flow control in constant air
volume systems
For use in potentially explosive atmospheres
(ATEX)
Mechanical self-powered volume flow control
without external power supply
Simplified project handling with orders based
on nominal size
Classification
According to type examination certificate
TUEV 05 ATEX 7159 X
Zones 1 and 2 (atmosphere: gases):
II 2 G c II T5 / T6
Zones 21 and 22 (atmosphere: dusts):
II 2 D c II T 80 C
Variants
RN-Ex: Volume flow controller
RN-Ex-D: Volume flow controller
with acoustic cladding
Units with acoustic cladding and/or Type CA
secondary silencers for demanding
acoustic requirements
Acoustic cladding cannot be retrofitted

Parts and characteristics


Ready-to-commission controller
Damper blade with low-friction bearings
Bellows that acts as an oscillation damper
Cam plate with leaf spring
Scale with pointer to set the volume flow rate
setpoint
Connection for equipotential bonding
Aerodynamic function testing of each
unit on a special test rig prior to shipping
Construction features
Circular casing
Construction and materials comply
with the EU directive for use in potentially
explosive atmospheres (ATEX)
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal (RN-P1/80
without groove)

Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Nominal sizes
80, 100, 125, 160, 200, 250, 315, 400
Accessories
Lip seals on both ends (factory fitted)
Useful additions
Secondary silencer Type CA
Special features
ATEX mark and certification
ATEX equipment group II,
approved for zones 1, 2, 21 and 22
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation
Correct operation even under unfavourable
upstream or downstream conditions
(1.5 D straight section required upstream)

K5 2.1 49

05/2015 DE/en

CAV controllers

TOC

General information
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel
Polyurethane bellows
Plain bearings with PTFE coating
Leaf spring made of stainless steel
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel,
powder-coated
Stainless steel construction (A2)
Casing made of stainless steel 1.4301
Interior parts made of stainless steel
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool

RN-Ex
Installation and commissioning
Connections for equipotential bonding:
Suitable cables must be connected by others
Any installation orientation
Volume flow rate can be set using
an external scale; no tools required
No repeat measurements or adjustments
by an air conditioning engineer are necessary
RN-Ex-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller
Standards and guidelines
Directive 94/9/EC: Equipment and protective
systems intended for use in potentially
explosive atmospheres
Hygiene conforms to VDI 6022
Casing air leakage to EN 1751, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

Technical data

05/2015 DE/en

Nominal sizes
Volume flow rate range
Volume flow rate control range
Scale accuracy
Minimum differential pressure
Maximum differential pressure
Operating temperature

80 400 mm
11 1400 l/s or 40 5040 m/h
Approx. 25 to 100 % of the nominal volume flow rate
4%
50 Pa
1000 Pa
10 50 C

K5 2.1 50

CAV controllers

TOC

General information
Function

RN-Ex

Functional description
The volume flow controller is a mechanical
self-powered unit and works without external
power supply. A damper blade with low-friction
bearings is adjusted by aerodynamic forces
such that the set volume flow rate is maintained
within the differential pressure range.
The aerodynamic forces of the airflow create
a closing torque on the damper blade.
The bellows extends and increases this force
while at the same time acting as an oscillation
damper. The closing force is countered by a leaf
spring that unrolls over a cam plate. The shape
of the cam plate is such that a change
in the differential pressure leads to an adjustment
of the damper blade in a way that the volume
flow rate is maintained almost exactly.

Efficient commissioning
The volume flow rate setpoint value can be
set quickly and easily using the pointer on
the external scale; no measurements are required.
The advantage over flow adjustment dampers
is that there is no need for repeat measurements
or adjustments by an air conditioning engineer.
Should the system pressure change, e.g. by
opening or closing of duct sections, the flow
rates in the entire system will also change if flow
adjustment dampers are used; however, this is not
the case with mechanical self-powered volume
flow controllers A mechanical self-powered
controller reacts immediately and adjusts
the damper blade such that the set constant
volume flow rate is maintained.

Schematic illustration of the RN-Ex

Damper blade
Bellows
Bellows inlet
Crossbar
Leaf spring

K5 2.1 51

Cam plate
Volume flow rate scale lock
Volume flow rate scale
Lip seal

05/2015 DE/en

CAV controllers

TOC

Order code
Order code

RN-Ex
RN-Ex

RN Ex D P1 / 160 / D2

Type
RN-Ex Volume flow controller
for potentially explosive atmospheres
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel

Order example

Nominal size [mm]


80
100
125
160
200
250
315
400

Accessories
No entry: none
D2
Lip seals on both ends

RN-Ex/160/D2
Nominal size
Material
Accessories

05/2015 DE/en

160
Galvanised sheet steel
Lip seals on both ends

K5 2.1 52

CAV controllers

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of CAV controllers
is an important factor
in designing the ductwork
and in rating the fan
including speed control.

Sufficient duct pressure


must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

RN-Ex

Volume flow rate ranges and minimum differential pressure values

l/s
80

100

125

160

200

250

315

400

Nominal size

m/h
11
20
40
45
22
40
70
90
35
60
115
140
60
105
190
240
90
160
300
360
145
255
470
580
230
400
750
920
350
610
1130
1400

40
72
144
162
79
144
252
324
126
216
414
504
216
378
684
864
324
576
1080
1296
522
918
1692
2088
828
1440
2700
3312
1260
2196
4068
5040

pst min
Pa

100
100
100
100
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

105
105
110
110
55
55
60
60
55
55
60
60
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55

%
105
105
115
120
55
55
65
70
55
55
65
70
55
55
60
65
55
55
60
60
55
55
60
60
55
55
60
60
55
55
55
55

105
105
120
125
55
60
70
80
55
55
70
80
55
55
60
70
55
55
65
65
55
55
60
65
55
55
60
65
55
55
55
60

20
15
10
8
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5
10
8
6
5

RN-Ex
RN-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm
RN-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm
RN-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm

K5 2.1 53

05/2015 DE/en

CAV controllers

TOC

Quick sizing
Air-regenerated noise

RN-Ex
Quick sizing: Sound pressure level at differential pressure 150 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
80

100

125

160

200

250

315

400

11
20
40
45
22
40
70
90
35
60
115
140
60
105
190
240
90
160
300
360
145
255
470
580
230
400
750
920
350
610
1130
1400

m/h
40
72
144
162
79
144
252
324
126
216
414
504
216
378
684
864
324
576
1080
1296
522
918
1692
2088
828
1440
2700
3312
1260
2196
4068
5040

LPA1

LPA
37
39
47
48
37
40
47
50
37
43
50
52
40
45
49
50
40
43
48
49
41
42
46
48
39
42
44
46
46
48
50
51

24
27
34
35
24
47
47
50
27
34
41
44
32
37
41
41
31
35
40
41
32
34
39
41
33
35
38
41
39
42
44
45

Case-radiated noise

dB(A)
17
19
24
25
17
22
27
30
21
27
35
39
26
32
35
36
24
28
33
35
24
28
33
35
26
29
32
35
33
36
38
40

15
17
22
24
15
20
26
29
18
25
33
37
24
29
33
34
22
26
32
33
22
26
31
34
23
27
31
34
29
32
35
37

LPA2

LPA3
22
24
31
32
22
21
29
33
15
19
27
30
29
33
39
41
28
32
40
42
29
33
40
43
30
35
40
43
45
49
54
56

<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
<15
16
<15
<15
17
20
15
<15
19
22
<15
<15
19
23
<15
18
24
27

RN-Ex
RN-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm
RN-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm
RN-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm
RN-Ex-D

05/2015 DE/en

K5 2.1 54

CAV controllers

TOC

Dimensions and weight RN-Ex


Description

Volume flow controller for constant


air volume flow control
Spigot to make connections to the ducting

CAV controllers
Type RN-Ex
Dimensions

RN-Ex
L

RNEx 160

182

Dimensions [mm] and weight [kg]


D

Nominal size

mm

80
100
125
160
200
250
315
400

79
99
124
159
199
249
314
399

RN-Ex-P1/80

kg
310
310
310
310
310
400
400
400

50
50
50
50
50
50
50
50

1.4
1.8
2.0
2.5
3.0
3.5
4.8
5.7

RN-Ex-P1/80/D2
250

330

30

79

79

40

RN 80

RN 80

182

182

RN-Ex-A2/80
310
50

79

RN-Ex

RN 80

182

K5 2.1 55

05/2015 DE/en

CAV controllers

TOC

Dimensions and weight RN-Ex-D

RN-Ex

Description

Volume flow controller with acoustic cladding


for constant air volume flow control
Spigot to make connections to the ducting
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The circular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)
on the fan and room ends
Acoustic cladding cannot be retrofitted

Dimensions

RN-Ex-DRN-Ex-D

RNExD 160

182

Dimensions [mm] and weight [kg]


D

L
mm

80
100
125
160
200
250
315
400

79
99
124
159
199
249
314
399

181
200
220
262
300
356
418
500

232
232
232
232
232
312
312
312

310

232

232

181

330

RN 80

2.2
3.6
4.0
5.0
6.0
7.3
9.8
11.8

RN 80

182

K5 2.1 56

310
310
310
310
310
400
400
400

m
kg

RN-Ex-D-A2/80

79

181

RN-Ex-D-P1/80/D2

L1

D3

79

Nominal size

182

05/2015 DE/en

CAV controllers

TOC

Installation details
Junction

D
D

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

RN-Ex

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the CAV controller has only a
negligible effect on the volume flow rate accuracy.

Free air intake only


with a straight duct
section of 1D upstream.

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access for commissioning and maintenance

Space requirement
for commissioning
and maintenance

1.5D

Space required
Attachments
Without actuator

05/2015 DE/en

mm
200

200

200

K5 2.1 57

CAV controllers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular volume flow controllers for constant air


volume systems in potentially explosive
atmospheres, mechanical self-powered,
without external power supply, suitable for supply
or extract air, available in 8 nominal sizes.
Ready-to-commission unit consists of the casing
containing a damper blade with low-friction
bearings, bellows, external cam plate with leaf
spring, and parts for equipotential bonding
and for protection in potentially explosive
atmospheres. Volume flow controllers are factory
set to a reference volume flow rate (customers
can set the required volume flow rate on site).
Spigot with groove for lip seal,
suitable for connecting ducts according to
EN 1506 or EN 13180.
Casing air leakage to EN 1751, class C.
Special features
ATEX mark and certification
ATEX equipment group II,
approved for zones 1, 2, 21 and 22
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation
Correct operation even under unfavourable
upstream or downstream conditions
(1.5 D straight section required upstream)
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel
Polyurethane bellows
Plain bearings with PTFE coating
Leaf spring made of stainless steel

RN-Ex
Variant with acoustic cladding (-D)
Acoustic cladding made of galvanised
sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A1,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Technical data
Nominal sizes: 80 to 400 mm
Volume flow rate range:
11 to 1400 l/s or 40 to 5040 m/h
Volume flow rate control range:
approx. 25 100 %
of the nominal volume flow rate
Minimum differential pressure: 50 Pa
Maximum differential pressure: 1000 Pa
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Powder-coated construction (P1)


Casing made of galvanised sheet steel,
powder-coated
Interior parts, nominal sizes 80 125:
stainless steel 1.4301, nominal sizes
160 400: galvanised sheet steel,
powder-coated
Stainless steel construction (A2)
Casing made of stainless steel 1.4301
Interior parts made of stainless steel

Order options

Type
RN-Ex Volume flow controller for potentially
explosive atmospheres
Acoustic cladding
No entry: none
D
With acoustic cladding
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel

K5 2.1 58

Nominal size [mm]


80
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends

05/2015 DE/en

EN-Ex

TOC

2.1

X X EN-Extestregistrierung

CAV controllers
Type EN-Ex

For the precise control of normal and high constant


volume flows in potentially explosive atmospheres
(ATEX)
Rectangular, mechanical self-powered volume flow controllers for the control
of supply air or extract air in constant air volume systems,
approved and certified for potentially explosive atmospheres (ATEX)
ATEX-compliant construction
Approved for gases, mists, vapours and dusts in zones 1, 2, 21 and 22
Suitable for volume flow rates up to 12,096 m/h or 3,360 l/s
Volume flow rate can be set using an external scale, no tools required
Adjustment scale

High control accuracy


No on-site test measurements required for commissioning
Suitable for airflow velocities up to 8 m/s
Casing air leakage to EN 1751, up to class C
Optional equipment and accessories
Acoustic cladding for the reduction of case-radiated noise
Secondary silencer Type TX for the reduction of air-regenerated noise

ATEX-Zertifizierung

05/2015 DE/en

K5 2.1 59

CAV controllers

TOC

General information

EN-Ex
Page

Type
EN-Ex

2
Description

CAV controllers
Type EN-Ex

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight EN-Ex
Dimensions and weight EN-Ex-D
Installation details
Specification text

2.1 60
2.1 63
2.1 64
2.1 66
2.1 68
2.1 69
2.1 70
2.1 71

Basic information and nomenclature

2.3 1

Application
Rectangular EXCONTROL CAV controllers of
Type EN-Ex for the precise supply air or extract
air flow control in constant air volume systems
For use in potentially explosive atmospheres
(ATEX)
Mechanical self-powered volume flow control
without external power supply
Simplified project handling with orders based
on nominal size
Classification
According to type examination certificate
TUEV 05 ATEX 7159 X
Zones 1 and 2 (atmosphere: gases):
II 2 G c II T5/T6
Zones 21 and 22 (atmosphere: dusts):
II 2 D c II T 80 C
Variants
EN-Ex: Volume flow controller
EN-Ex-D: Volume flow controller
with acoustic cladding
Units with acoustic cladding and/or
secondary silencer Type TX for demanding
acoustic requirements
Acoustic cladding cannot be retrofitted
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Nominal sizes
19 nominal sizes from 200 100 to 600 600
Useful additions
Secondary silencer Type TX
Special features
ATEX mark and certification
ATEX equipment group II,
approved for zones 1, 2, 21 and 22
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation

K5 2.1 60

Parts and characteristics


Ready-to-commission controller
Damper blade with low-friction bearings
Bellows that acts as an oscillation damper
Cam plate with leaf spring
Scale with pointer to set the volume flow rate
setpoint
Connection for equipotential bonding
Aerodynamic functional testing of each
unit on a special test rig prior to shipping
Correct operation even under unfavourable
upstream conditions
(1.5 B straight section required upstream)
Construction features
Rectangular casing
Construction and materials comply
with the EU directive for use in potentially
explosive atmospheres (ATEX)
Flanges on both sides,
suitable for duct connection
Volume flow controllers from H = 400 mm
are fitted with two damper blades
and two volume flow rate scales
Materials and surfaces
Galvanised sheet steel construction
Casing and damper blade
made of galvanised sheet steel
Leaf spring made of stainless steel
Polyurethane bellows
Plain bearings with PTFE coating
Powder-coated construction (P1)
Casing and damper blade
made of galvanised sheet steel, powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding
made of galvanised sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A2,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

05/2015 DE/en

CAV controllers

TOC

General information
Installation and commissioning
Any installation orientation
Connect the equipotential
bonding to the ductwork
Volume flow rate can be set using
an external scale; no tools required
No repeat measurements or adjustments
by an air conditioning engineer are necessary
EN-Ex-D: For constructions with acoustic
cladding, ducts on the room side should
have cladding up to the acoustic cladding
of the controller

EN-Ex
Maintenance
Maintenance-free as construction
and materials are not subject to wear

Standards and guidelines


Directive 94/9/EC: Equipment
and protective systems intended for use
in potentially explosive atmospheres
Casing air leakage to EN 1751, class C
(B + H 400, class B)

Technical data

05/2015 DE/en

Nominal sizes
Volume flow rate range
Volume flow rate control range
Scale accuracy
Minimum differential pressure
Maximum differential pressure
Operating temperature

200 100 to 600 600 mm


40 3360 l/s or 144 12096 m/h
Approx. 25 to 100 % of the nominal volume flow rate
4%
50 Pa
1000 Pa
10 50 C

K5 2.1 61

CAV controllers

TOC

General information
Function

EN-Ex

Functional description
The volume flow controller is a mechanical
self-powered unit and works without external
power supply. A damper blade with low-friction
bearings is adjusted by aerodynamic forces
such that the set volume flow rate is maintained
within the differential pressure range.
The aerodynamic forces of the airflow create
a closing torque on the damper blade.
The bellows extends and increases this force
while at the same time acting as an oscillation
damper. The closing force is countered by a leaf
spring that unrolls over a cam plate. The shape
of the cam plate is such that a change
in the differential pressure leads to an adjustment
of the damper blade in a way that the volume
flow rate is maintained almost exactly.

Efficient commissioning
The volume flow rate setpoint value can be
set quickly and easily using the pointer on
the external scale; no measurements are required.
The advantage over flow adjustment dampers
is that there is no need for repeat measurements
or adjustments by an air conditioning engineer.
Should the system pressure change, e.g. by
opening or closing of duct sections, the flow
rates in the entire system will also change if flow
adjustment dampers are used; however, this is not
the case with mechanical self-powered volume
flow controllers A mechanical self-powered
controller reacts immediately and adjusts the
damper blade such that the set constant
volume flow rate is maintained.

Schematic illustration of the EN-Ex

Volume flow rate scale


Volume flow rate scale lock
Crossbar
Cam plate

K5 2.1 62

Leaf spring
Bellows inlet
Bellows
Damper blade

05/2015 DE/en

CAV controllers

TOC

Order code
Order code

EN-Ex
EN-Ex

EN Ex D P1 / 400200

Order example

Type
EN-Ex Volume flow controller
for potentially explosive atmospheres

Material
No entry: galvanised sheet steel
Powder-coated (RAL 7001), silver grey
P1

Acoustic cladding
No entry: none
D
With acoustic cladding

Nominal size [mm]


BH

EN-Ex-D/200100
Acoustic cladding
Material
Nominal size

05/2015 DE/en

With
Galvanised sheet steel
200 100 mm

K5 2.1 63

CAV controllers

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of CAV controllers
is an important factor
in designing the ductwork
and in rating the fan
including speed control.

Sufficient duct pressure


must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

EN-Ex

Volume flow rate ranges and minimum differential pressure values

l/s
200 100

300 100

300 150

300 200

400 200

500 200

600 200

400 250

500 250

600 250

400 300

500 300

Nominal size

m/h
40
80
120
160
65
130
195
260
105
210
315
420
130
260
390
520
210
420
630
840
230
460
690
920
255
510
765
1020
220
440
660
880
300
600
900
1200
320
640
960
1280
315
630
945
1260
375
750
1125
1500

pst min
Pa

144
288
432
576
234
468
702
936
378
756
1134
1512
468
936
1404
1872
756
1512
2268
3024
828
1656
2484
3312
918
1836
2754
3672
792
1584
2376
3168
1080
2160
3240
4320
1152
2304
3456
4608
1134
2268
3402
4536
1350
2700
4050
5400

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

%
60
80
115
160
60
80
120
170
60
80
115
160
60
80
110
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160
60
80
115
160

13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5

EN-Ex
EN-Ex with secondary silencer TX

K5 2.1 64

05/2015 DE/en

CAV controllers

TOC

Aerodynamic data
Volume flow rate ranges

The minimum differential


pressure of CAV controllers
is an important factor
in designing the ductwork
and in rating the fan
including speed control.
Sufficient duct pressure
must be ensured for
all operating conditions
and for all control units.
The measurement points
for fan speed control must
be selected accordingly.

EN-Ex

Volume flow rate ranges and minimum differential pressure values

l/s
600 300

400 400

500 400

600 400

500 500

600 500

600 600

Nominal size

m/h
420
840
1260
1680
420
840
1260
1680
460
920
1380
1840
510
1020
1530
2040
600
1200
1800
2400
640
1280
1920
2560
840
1680
2520
3360

Pa
1512
3024
4536
6048
1512
3024
4536
6048
1656
3312
4968
6624
1836
3672
5508
7344
2160
4320
6480
8640
2304
4608
6912
9216
3024
6048
9072
12096

pst min
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

Pa

%
60
75
110
150
60
85
120
175
60
80
115
160
60
80
115
160
60
80
115
160
55
70
95
130
60
75
105
145

13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5

EN-Ex
EN-Ex with secondary silencer TX

05/2015 DE/en

K5 2.1 65

CAV controllers

TOC

Quick sizing
Air-regenerated noise

EN-Ex
Quick sizing: Sound pressure level at differential pressure 150 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
200 100

300 100

300 150

300 200

400 200

500 200

600 200

400 250

500 250

600 250

400 300

500 300

m/h
40
80
120
160
65
130
195
260
105
210
315
420
130
260
390
520
210
420
630
840
230
460
690
920
255
510
765
1020
220
440
660
880
300
600
900
1200
320
640
960
1280
315
630
945
1260
375
750
1125
1500

144
288
432
576
234
468
702
936
378
756
1134
1512
468
936
1404
1872
756
1512
2268
3024
828
1656
2484
3312
918
1836
2754
3672
792
1584
2376
3168
1080
2160
3240
4320
1152
2304
3456
4608
1134
2268
3402
4536
1350
2700
4050
5400

LPA

LPA1
35
41
44
46
38
44
45
47
41
44
46
47
45
46
46
47
42
43
44
44
40
40
41
42
38
39
39
40
44
45
45
45
41
42
43
43
40
40
41
42
45
46
47
47
43
44
44
45

Case-radiated noise

dB(A)
19
28
34
38
22
30
35
38
24
31
35
38
24
29
33
35
23
27
31
33
21
26
29
31
20
24
28
31
23
28
31
34
21
26
30
33
20
25
28
31
25
29
34
36
22
28
31
33

LPA2

LPA3
21
28
33
35
24
32
36
39
28
34
39
41
31
35
38
40
30
35
38
40
28
33
36
38
27
31
35
37
32
37
39
41
31
36
39
41
30
34
37
39
53
40
43
45
34
38
41
43

<15
21
26
30
16
24
29
32
19
26
32
35
21
26
29
32
20
26
30
33
18
24
28
31
17
23
27
31
22
27
30
33
21
27
30
33
20
25
29
32
25
30
34
36
23
29
32
35

EN-Ex
EN-Ex with secondary silencer TX
EN-Ex-D

K5 2.1 66

05/2015 DE/en

CAV controllers

TOC

Quick sizing
Air-regenerated noise

EN-Ex
Quick sizing: Sound pressure level at differential pressure 150 Pa
Air-regenerated noise

Quick sizing tables


provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.
The first selection criteria
for the nominal size are
the actual volume flow
rates min and max.
The quick sizing tables
are based on normally
accepted attenuation
levels. If the sound
pressure level exceeds
the required level, a larger
VAV terminal unit and/or
a silencer is required.

Nominal size
l/s
600 x 300

400 x 400

500 x 400

600 x 400

500 x 500

600 x 500

600 x 600

m/h
420
840
1260
1680
420
840
1260
1680
460
920
1380
1840
510
1020
1530
2040
600
1200
1800
2400
640
1280
1920
2560
840
1680
2520
3360

1512
3024
4536
6048
1512
3024
4536
6048
1656
3312
4968
6624
1836
3672
5508
7344
2160
4320
6480
8640
2304
4608
6912
9216
3024
6048
9072
12096

LPA

LPA1
41
42
42
43
47
49
49
50
45
46
47
47
43
44
44
45
47
48
49
49
45
46
46
46
46
47
48
48

Case-radiated noise

dB(A)
21
26
30
32
27
32
36
38
24
29
33
35
22
27
31
33
26
31
35
37
24
29
32
35
26
30
35
37

LPA2

LPA3
33
37
40
42
39
44
47
49
37
42
44
46
36
40
43
45
40
45
48
50
39
43
46
48
41
46
49
51

22
28
31
34
29
34
37
40
27
32
35
37
25
30
33
36
30
35
39
41
28
33
36
39
31
36
39
42

EN-Ex
EN-Ex with secondary silencer TX
EN-Ex-D

05/2015 DE/en

K5 2.1 67

CAV controllers

TOC

Dimensions and weight EN-Ex


Description

Volume flow controller for constant


air volume flow control

CAV controllers
Type EN-Ex
Dimensions

EN-Ex


m/h
l/s

900

1200
360

2100

720

2400

1800

600

1500

480

EN-Ex

2700

300
0

m
/h

ENEX

13

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
300 150
300 200
400 200
400 250
400 300
400 400
500 200
500 250
500 300
500 400
500 500
600 200
600 250
600 300
600 400
600 500
600 600

K5 2.1 68

Nominal width Nominal height

B2

B1

H1

H2

mm
200
300
300
300
400
400
400
400
500
500
500
500
500
600
600
600
600
600
600

100
100
150
200
200
250
300
400
200
250
300
400
500
200
250
300
400
500
600

234
334
334
334
434
434
434
434
534
534
534
534
534
634
634
634
634
634
634

kg
276
376
376
376
476
476
476
476
576
576
576
576
576
676
676
676
676
676
676

134
134
184
234
234
284
334
434
234
284
334
434
534
234
284
334
434
534
634

176
176
226
276
276
326
376
476
276
326
376
476
576
276
326
376
476
576
676

5
6
7
7
9
10
12
18
11
12
13
18
19
13
14
15
18
19
20

05/2015 DE/en

CAV controllers

TOC

Dimensions and weight EN-Ex-D


Description

EN-Ex

Volume flow controller with acoustic cladding


for constant air volume flow control
For rooms where the case-radiated noise of the
unit is not sufficiently reduced by a false ceiling
The rectangular ducts for the room under
consideration must have adequate acoustic
insulation (provided by others)#
on the fan and room ends
Acoustic cladding cannot be retrofitted

2
Dimensions

EN-Ex-D


m/h
l/s

900

1200

360

2100

2400
2700

1800

600
720

1500

480

3000
m
/h

ENEX

M8


Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
300 150
300 200
400 200
400 250
400 300
400 400
500 200
500 250
500 300
500 400
500 500
600 200
600 250
600 300
600 400
600 500
600 600

05/2015 DE/en

Nominal width Nominal height

B2

B1

H1

H2

mm
200
300
300
300
400
400
400
400
500
500
500
500
500
600
600
600
600
600
600

100
100
150
200
200
250
300
400
200
250
300
400
500
200
250
300
400
500
600

234
334
334
334
434
434
434
434
534
534
534
534
534
634
634
634
634
634
634

kg
280
380
380
380
480
480
480
480
580
580
580
580
580
680
680
680
680
680
680

134
134
184
234
234
284
334
434
234
284
334
434
534
234
284
334
434
534
634

180
180
230
280
280
330
380
480
280
330
380
480
580
280
330
380
480
580
680

8
10
11
12
15
17
18
26
17
18
19
26
28
20
22
22
26
29
30

K5 2.1 69

CAV controllers

TOC

Installation details

Junction, vertical

1.5B

1.5B
1,5B

The stated volume flow rate accuracy


can only be achieved with a straight duct section
of at least 1.5H upstream between any bend
and the controller.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5H upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Bend, horizontal

Junction, horizontal

Free air intake


only with a straight duct
section of 1B upstream.

1.5B

1.5B
1,5B

The stated volume flow rate accuracy


can only be achieved with a straight duct section
of at least 1.5B upstream between any bend
and the controller.

Space requirement
for commissioning
and maintenance

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
1.5B upstream. Shorter upstream sections require
a perforated plate in the branch and before
the CAV controller. If there is no straight upstream
section at all, the control will not be stable,
even with a perforated plate.

Access for commissioning and maintenance

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend, vertical

Upstream conditions

EN-Ex

Space required
Attachments
Without actuator

mm
200

200

H: Unit height

K5 2.1 7

05/2015 DE/en

CAV controllers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular volume flow controllers


for constant air volume systems in potentially
explosive atmospheres, mechanical self-powered,
without external power supply, suitable for supply
or extract air, available in 19 nominal sizes.
Ready-to-commission unit consists of the casing
containing a damper blade with low-friction
bearings, bellows, external cam plate with leaf
spring, and parts for equipotential bonding
and for protection in potentially explosive
atmospheres. Volume flow controllers are factory
set to a reference volume flow rate (customers
can set the required volume flow rate on site).
Both ends suitable for the connection of ducts.
Casing air leakage to EN 1751, class C
(B + H 400, class B)
Special features
ATEX mark and certification
ATEX equipment group II,
approved for zones 1, 2, 21 and 22
Volume flow rate can be set using
an external scale; no tools required
High volume flow rate control accuracy
Any installation orientation

EN-Ex
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Technical data
Nominal sizes: 200 100 to 600 600
Volume flow rate range:
40 to 3360 l/s or 144 to 12096 m/h
Volume flow rate control range:
approx. 25 100 %
of the nominal volume flow rate
Minimum differential pressure: 50 Pa
Maximum differential pressure: 1000 Pa
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LPA air-regenerated noise __________ [dB(A)]
LPA Case-radiated noise ___________ [dB(A)]

Materials and surfaces


Galvanised sheet steel construction
Casing and damper blade
made of galvanised sheet steel
Leaf spring made of stainless steel
Polyurethane bellows
Plain bearings with PTFE coating
Powder-coated construction (P1)
Casing and damper blade
made of galvanised sheet steel, powder-coated
Variant with acoustic cladding (-D)
Acoustic cladding
made of galvanised sheet steel
Rubber profile for the insulation
of structure-borne noise
Lining is mineral wool
Mineral wool
To EN 13501, fire rating class A2,
non-combustible
RAL quality mark RAL-GZ 388
Biosoluble and hence hygienically
safe according to the German TRGS 905
(Technical Rules for Hazardous Substances)
and EU directive 97/69/EG

Order options

Type
EN-Ex Volume flow controller
for potentially explosive atmospheres
Acoustic cladding
No entry: none
D
With acoustic cladding

K5 2.1 7

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH

05/2015 DE/en

Min/Max actuators

X X Min/Max

TOC

2.2

actuatorstestregistrierung

Actuators
for CAV controllers

Type Min/Max actuators

For constant volume flows with min/max switching


in air conditioning systems
Actuators for mechanical self-powered CAV controllers Type EN, RN, or VFC,
and for flow adjustment dampers Type VFR
Switching between two volume flow setpoint values,
e.g. for daytime and night-time operation
Supply voltage 24 V AC/DC or 230 V AC
Control input signal: 1-wire control or 2-wire control (3-point)
Potentiometer or mechanical stops
Positive lock connection with CAV controller
Retrofit possible

05/2015 DE/en

K5 2.2 1

Actuators for CAV controllers

TOC

General information

Min/Max actuators
Page

Type
Min/Max actuators

2
Description

General information
Special information B5*
Special information B6*
Special information B*2
Special information E01
Special information M01
Special information E02
Special information M02

2.2 2
2.2 4
2.2 5
2.2 6
2.2 7
2.2 8
2.2 9
2.2 10

Basic information and nomenclature

2.3 1

Application
Actuators for min/max switching
Switching between volume flow setpoint values
of mechanical self-powered CAV controllers
Type RN, EN or VFC
Change of the damper blade positions
of flow adjustment dampers Type VFR
Parts and characteristics
Potentiometer or mechanical stops
for setting the volume flow rate setpoints
Supply voltage 24 V AC/DC or 230 V AC
Overload protection
1-wire control or 2-wire control (3-point)
Optional auxiliary switch for capturing
the end positions

Any attachments
must be defined
with the order code
of the CAV controller.

Actuators for volume flow controllers Type RN or EN


Order code detail
B50
B52
B60
B62

Actuator
Part number
M466DT4
M466DT4
M466DT5
M466DT5

Auxiliary switch

Type

Supply voltage

LM24A-F
LM24A-F
LM230A-F
LM230A-F

24 V
24 V
230 V
230 V

Part number

Type

M536AI3

M536AI3

S2A

S2A

Actuators for volume flow controllers Type VFC and for flow adjustment dampers Type VFR
Order code detail
E01
M01
E02
M02

K5 2.2 2

Part number
M466EP6
M466EP4
M466EP8
M466EP5

Type
224-024-02-001
CM24-F
224-230-02-002
CM230-F

Setpoint setting

Supply voltage

Potentiometer
Mechanical stops
Potentiometer
Mechanical stops

24 V
24 V
230 V
230 V

05/2015 DE/en

Actuators for CAV controllers

TOC

General information
Function

Min/Max actuators

Functional description
The actuator moves a damper blade or a damper
blade mechanism to the minimum or maximum
position. Minimum and maximum positions can
be set on potentiometers or using mechanical
stops. 1-wire control or 2-wire control (3-point)
can be used. 1-wire control is actually
an open/close control or min/max control.

1-wire control

2-wire control (3-point)

S2

S1

1
N

2
L
~
+

1
N

3
L
~
+

Switch functions
S1 open: Direction of rotation 1
S1 closed: Direction of rotation 2

2
L
~
+

S1

3
L
~
+

Switch functions
S1 open
S2 open: Actuator has stopped (any position)
S2 closed: Direction of rotation 1
S1 closed
S2 open: Direction of rotation 2
S2 closed: Direction of rotation 2

Effect of actuator action


in case of factory setting
Order code detail
B5*
B6*
E01
E02
M01
M02

05/2015 DE/en

Direction of rotation
1

2
min
min
min
min
max
max

max
max
max
max
min
min

K5 2.2 3

Actuators for CAV controllers

TOC

Special information B5*


Description

/ B50
/ B52
Order code detail

Min/Max actuators

Application
Actuator LM24A-F for the min/max switching
of volume flow setpoint values of mechanical
self-powered volume flow controllers
Type RN or EN (only up to a height of 300 mm)
Variants
B52: with auxiliary switch for capturing
the end positions

Commissioning
Set the mechanical stops according to the
minimum and maximum volume flow rates
Change the direction of rotation if necessary,
using the switch, to switch between
min andmax

Parts and characteristics


Supply voltage 24 V AC/DC
1-wire control or 2-wire control (3-point)
Mechanical stops for setting the volume
flow rate setpoints
Switch for setting the direction of rotation
Positive lock connection with damper
blade shaft
Release button to allow for manual operation

Technical data

Actuators LM24A and LM24A-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
2 VA max.
1 W max.
5 Nm
150 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
0.5 kg

Actuator LM24A-F

Wiring

Connecting cable core identification


BK RD WH

For control options


see General information
function

2
~
+

3
~
+

LM24A

1 , :
2 ~, +:
3 ~, +:

Ground, neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

LM24A and LM24A-F

K5 2.2 4

05/2015 DE/en

Actuators for CAV controllers

TOC

Special information B6*


Description

/ B60
/ B62
Order code detail

Min/Max actuators

Application
Actuator LM230A-F for the min/max switching
of volume flow setpoint values of mechanical
self-powered volume flow controllers
Type RN or EN (only up to a height of 300 mm)
Variants
B62: with auxiliary switch for capturing
the end positions

Commissioning
Set the mechanical stops according to
the minimum and maximum volume flow rates
Change the direction of rotation if necessary,
using the switch, to switch between
min andmax

Parts and characteristics


Supply voltage 230 V AC
1-wire control or 2-wire control (3-point)
Mechanical stops for setting the volume
flow rate setpoints
Switch for setting the direction of rotation
Positive lock connection
with damper blade shaft
Release button to allow for manual operation

Technical data

Actuator LM230A
Supply voltage
Power rating
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

85 265 V AC, 50/60 Hz


4 VA max.
5 Nm
150 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.5 kg

Actuator LM230A-F

Wiring

Connecting cable core identification


BU BN WH

For control options


see General information
function

1
N

2
L

3
L

LM230A

1 N:
2 L:
3 L:

05/2015 DE/en

Neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

K5 2.2 5

Actuators for CAV controllers

TOC

Special information B*2


Description

/ B52
/ B62
Order code detail

Min/Max actuators

Application
Auxiliary switch S2A for capturing damper
blade end positions (end positions reached
through actuator operation)
Volt-free contacts for signalling
or activating switch functions
Two integral switches, e.g. for damper blade
OPEN and damper blade CLOSED
Potentiometer for setting any switch point

2
Auxiliary switch S2A

Auxiliary switch S2A

Type of contact
Max. switching voltage (AC)
Max. switching current (AC)
Max. switching voltage (DC)
Max. switching current (DC)
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight
1)

Wiring

2 changeover contacts1)
250 V AC
3 A (resistive load); 0.5 A (inductive load)
110 V DC
0.5 A (resistive load); 0.2 A (inductive load)
6 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.250 kg

If both auxiliary switches are used the switching voltages must be the same

Connecting cable core identification


VT RD WH OG PK GY

S1 S2 S3 S4 S5 S6
S2A

S1:
Common contact
S2:
Mechanical stop 1 < x
S3:
Mechanical stop 1 > x
S4:
Common contact
S5:
Mechanical stop 2 < x
S6:
Mechanical stop 2 > x
x: 0 100 % Switching point (adjustable)

K5 2.2 6

05/2015 DE/en

Actuators for CAV controllers

TOC

Special information E01


Description

/ E01
Order code detail

Min/Max actuators

Application
Actuator 224-024-02-001
for min/max switching
Min/Max switching between volume
flow setpoint values of mechanical
self-powered CAV controllers Type VFC
Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Commissioning
Use the potentiometer to set the minimum
or maximum volume flow rate or the damper
blade position

Parts and characteristics


Supply voltage 24 V AC/DC
1-wire control or 2-wire control (3-point)
Potentiometer for setting the volume flow
rate setpoints
Positive lock connection with damper
blade shaft
Functional test button: Motor drives first
to minimum position, then to maximum
position, then returns to the set position
Indicator light: Actuator has reached setpoint,
actuator in motion, actuator blocked

Technical data

Actuator 224-024-02-001

Wiring

Actuator 224-24-02-001
Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
3 VA max.
2 W max.
1 Nm
20 60 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC
30 to 50 C
0.300 kg

Connecting cable core identification


BU BN BK

For control options


see General information
function

2
~
+

3
~
+

224-24-02-001

1 , :
2 ~, +:
3 ~, +:

05/2015 DE/en

Ground, neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

K5 2.2 7

Actuators for CAV controllers

TOC

Special information M01


Description

/ M01
Order code detail

Min/Max actuators

Application
Actuator CM24-F for min/max switching
Min/Max switching between volume flow
setpoint values of mechanical self-powered
CAV controllers Type VFC
Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Commissioning
Set the mechanical stops according
to the minimum and maximum volume
flow rates or the damper blade position

Parts and characteristics


Supply voltage 24 V AC/DC
1-wire control or 2-wire control (3-point)
Mechanical stops for setting the volume
flow rates
Positive lock connection
with damper blade shaft
Gear release magnet

Technical data

Actuator CM24-F
Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
1 VA max.
0.5 W max.
2 Nm
75 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
0.185 kg

Actuator CM24-F

Wiring

Connecting cable core identification


BK RD WH

For control options


see General information
function

2
~
+

3
~
+

CM24-F

1 , :
2 ~, +:
3 ~, +:

K5 2.2 8

Ground, neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

05/2015 DE/en

Actuators for CAV controllers

TOC

Special information E02


Description

/ E02
Order code detail

Min/Max actuators

Application
Actuator 224-230-02-002
for min/max switching
Min/Max switching between volume
flow setpoint values of mechanical
self-powered CAV controllers Type VFC
Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Commissioning
Use the potentiometer to set the minimum
or maximum volume flow rate or the damper
blade position

Parts and characteristics


Supply voltage 230 V AC
1-wire control or 2-wire control (3-point)
Potentiometer for setting the volume
flow rate setpoints
Positive lock connection
with damper blade shaft
Functional test button: Motor drives
first to minimum position, then to maximum
position, then returns to the set position
Indicator light: Actuator has reached setpoint,
actuator in motion, actuator blocked

Technical data

Actuator 224-230-02-002
Supply voltage
Power rating
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

230 V AC, 50/60 Hz


3 VA
1 Nm
20 60 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
II (protective insulation)
IP 42
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.300 kg

Actuator 224-230-02-002

Wiring

Connecting cable core identification


BU BN BK

For control options


see General information
function

1
N

2
L

3
L

224-230-02-002

1 N:
2 L:
3 L:

05/2015 DE/en

Neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

K5 2.2 9

Actuators for CAV controllers

TOC

Special information M02


Description

/ M02
Order code detail

Min/Max actuators

Application
Actuator CM230-F for min/max switching
Min/Max switching between volume
flow setpoint values of mechanical
self-powered CAV controllers Type VFC
Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Commissioning
Set the mechanical stops according
to the minimum and maximum volume flow
rates or the damper blade position

Parts and characteristics


Supply voltage 230 V AC
1-wire control or 2-wire control (3-point)
Mechanical stops for setting the volume
flow rate setpoints
Positive lock connection
with damper blade shaft
Gear release magnet

Technical data

Actuator CM230-F
Supply voltage
Power rating
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

100 to 240 V AC 15 % +10 %, 50/60 Hz


3 VA
2 Nm
75 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.185 kg

Actuator CM230-F

Wiring

Connecting cable core identification


BU BN WH

For control options


see General information
function

1
N

2
L

3
L

CM230-F

1 N:
2 L:
3 L:

K5 2.2 10

Neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

05/2015 DE/en

Modulating actuators

X X Modulating

TOC

2.2

actuatorstestregistrierung

Actuators
for CAV controllers

Type Modulating actuators

For variable volume flows in air conditioning systems


Actuators for mechanical self-powered CAV controllers Type EN, RN, or VFC,
and for flow adjustment dampers Type VFR
Setpoint value adjustment
Supply voltage 24 V AC/DC
Control input signal: Voltage signal 0 10 V DC or 2 10 V DC
Potentiometer or mechanical stops
Positive lock connection with CAV controller or flow adjustment damper
Retrofit possible

05/2015 DE/en

K5 2.2 11

Actuators for CAV controllers

TOC

General information

Modulating actuators
Page

Type
Modulating actuators

Description

General information
Special information B7*
Special information B*2
Special information E03

2.2 12
2.2 14
2.2 15
2.2 16

Basic information and nomenclature

2.3 1

Application
Actuators for variable adjustment
Variable adjustment of volume flow
setpoint values of mechanical self-powered
CAV controllers Type EN, RN or VFC
Setting of various damper blade positions
of flow adjustment dampers Type VFR
Parts and characteristics
Potentiometer or mechanical stops
for setting the volume flow rate setpoints
Supply voltage 24 V AC/DC
Overload protection
Setpoint value signal 0 10 V DC
or 2 10 V DC

Any attachments
must be defined
with the order code
of the CAV controller.

Actuators for volume flow controllers Type RN or EN


Order code detail
B70
B72

Actuator
Part number
M466DT6
M466DT6

Auxiliary switch

Type

Supply voltage

LM24A-SR-F
LM24A-SR-F

24 V AC/DC
24 V AC/DC

Part number

Type

M536AI3

S2A

Actuators for volume flow controllers Type VFC and for flow adjustment dampers Type VFR
Order code detail
E03

K5 2.2 12

Part number
M466EP7

Type
224C-024-02-003

Setpoint setting

Supply voltage

Potentiometer

24 V AC/DC

05/2015 DE/en

Actuators for CAV controllers

TOC

General information
Function

Modulating actuators

Functional description
The actuator moves the damper blade mechanism
to any position between minimum and maximum.
Minimum and maximum positions can be set
on potentiometers. The control input signal
is a voltage signal. The output signal indicates
the damper blade position rather than the volume
flow rate actual value since the CAV controller
does not perform any measurements.

2
Applies to attachments
with order codes B7*
and E03

Variable control initiated by a voltage signal


Sollwertgeber

24 V

U Voltage signal 0 10 V DC or 2 10 V DC

Applies to attachments
with order code B7*

1-wire control for modulating actuators

2-wire control (3-point)


for modulating actuators

S2

S1

2
~
+

3
Y

5
U

Switch functions
S1 open: Direction of rotation 1
S1 closed: Direction of rotation 2

2
~
+

S1

3
Y

5
U

Switch functions
S1 open
S2 open: Actuator has stopped (any position)
S2 closed: Direction of rotation 1
S1 closed
S2 open: Direction of rotation 2
S2 closed: Direction of rotation 2

Effect of actuator action


in case of factory setting
Order code detail
B7*

05/2015 DE/en

Direction of rotation
1

2
min

max

K5 2.2 13

Actuators for CAV controllers

TOC

Special information B7*


Description

/ B70
/ B72
Order code detail

Modulating actuators

Application
Actuator LM24A-SR for the variable adjustment
of volume flow setpoint values of mechanical
self-powered volume flow controllers
Type RN or EN (only up to a height of 300 mm)

Commissioning
Set the mechanical stops according to the
minimum and maximum volume flow rates
Change the direction of rotation if necessary,
using the switch

Variants
B72: with auxiliary switch
for capturing the end positions
Parts and characteristics
Supply voltage 24 V AC/DC
Control input signal: Setpoint value signal
2 10 V DC, corresponds to the total rotation
range (90), working range is limited
by mechanical stops
Output: Position feedback 2 10 V
Mechanical stops for setting
the volume flow rates
Switch for setting the direction of rotation
Positive lock connection
with damper blade shaft
Release button to allow for manual operation

Technical data

Actuators LM24A-SR and LM24A-SR-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Position feedback
Control signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
2 VA
1W
5 Nm
150 s
2 10 V DC, 1 mA
2 10 V DC, Ra > 100 k
4 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
0.5 kg

Actuator LM24A-SR-F

Electrical connection

Connecting cable core identification


BK RD WH OG

For control options see


General information
function

2
~
+

3
Y

5
U

LM24A-SR

1 , :
2 ~, +:
3 Y:
5 U:

Ground, neutral
Supply voltage
Setpoint value signal
Position feedback

LM24A-SR and LM24A-SR-F

K5 2.2 14

05/2015 DE/en

Actuators for CAV controllers

TOC

Special information B*2


Description

/ B52
/ B62
Order code detail

Modulating actuators

Application
Auxiliary switch S2A for capturing damper
blade end positions (end positions reached
through actuator operation)
Volt-free contacts for signalling or activating
switch functions
Two integral switches, e.g. for damper blade
OPEN and damper blade CLOSED
Potentiometer for setting any switch point

2
Auxiliary switch S2A

Auxiliary switch S2A

Type of contact
Max. switching voltage (AC)
Max. switching current (AC)
Max. switching voltage (DC)
Max. switching current (DC)
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight
1)

Wiring

2 changeover contacts1)
250 V AC
3 A (resistive load); 0.5 A (inductive load)
110 V DC
0.5 A (resistive load); 0.2 A (inductive load)
6 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.250 kg

If both auxiliary switches are used the switching voltages must be the same

Connecting cable core identification


VT RD WH OG PK GY

S1 S2 S3 S4 S5 S6
S2A

S1:
Common contact
S2:
Mechanical stop 1 < x
S3:
Mechanical stop 1 > x
S4:
Common contact
S5:
Mechanical stop 2 < x
S6:
Mechanical stop 2 > x
x: 0 100 % Switching point (adjustable)

K5 2.2 1

05/2015 DE/en

Actuators for CAV controllers

TOC

Special information E03


Description

/ E03
Order code detail

Modulating actuators

Application
Actuator 224C-024-02-003
for variable adjustment
Variable adjustment of volume flow setpoint
values of mechanical self-powered
CAV controllers Type VFC
Setting of various damper blade positions
of flow adjustment dampers Type VFR

Commissioning
Use the potentiometer to set the minimum
or maximum volume flow rate

Parts and characteristics


Supply voltage 24 V AC/DC
Control input signal: Setpoint value signal
2 10 V DC, corresponds to the working range
(set on potentiometers)
Output: Position feedback 0 10 V
Potentiometer for setting
the volume flow rate setpoints
Positive lock connection
with damper blade shaft
Functional test button: Motor drives
first to minimum position, then to maximum
position, then returns to the set position
Indicator light: Actuator has reached setpoint,
actuator in motion, actuator blocked

Technical data

Actuator 224C-024-02

Wiring

Actuator 224C-024-02-003
Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
3 VA
2W
5 Nm
20 60 s
0 10 V DC, Ra > 100 k
3 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC
30 to 50 C
0.5 kg

Connecting cable core identification


BU BN BK GY

For control options


see General information
function

2
~
+

3
Y

4
U

224C-024-02-003

1 , :
2 ~, +:
3 Y:
4 U:

05/2015 DE/en

Ground, neutral
Supply voltage
Setpoint value signal
Position feedback

K5 2.2 1

Retrofit kits

X X Retrofit

TOC

2.2

kitstestregistrierung

Actuators for CAV controllers


Type Retrofit kits

Actuator for switching


between setpoint values
with Type EN

Actuator for switching


between setpoint values
with Type RN

For variable volume flows or min / max


switching in room air conditioning systems
Actuators and installation accessories for mechanical self-powered CAV
controllers Type EN, RN, or VFC, and flow adjustment dampers Type VFR
Parts kits for easy retrofit
Potentiometer or mechanical stops
Supply voltage 24 V AC/DC or 230 V AC
Control input signal: Signal voltage 0 10 V for modulating actuators

Actuator with
mechanical stops
for Type VFC or VFR

Control input signal: 1-wire control or 2-wire control (3-point)


for min/max switching
Positive lock connection with CAV controller or flow adjustment damper
Optional accessories for Types RN and EN
Auxiliary switch with adjustable switching points,
for example for capturing the end positions

Actuator with
potentiometers
for Type VFC or VFR

05/2015 DE/en

K5 2.2 1

Actuators for CAV controllers

TOC

General information

Retrofit kits
Page

Type
Retrofit kits

Description

General information

2.2 20

Basic information and nomenclature

2.3 1

Application
Parts kits for the retrofit of mechanica
self-powered volume flow controllers
or flow adjustment dampers with actuators.
CAV controllers Type EN or RN, as well as for VFC
Min/Max switching
of volume flow setpoint values
Variable adjustment
of volume flow rate setpoints
Flow adjustment dampers Type VFR
Min/Max change of the damper blade position

Parts and characteristics


Damper blade can take various positions
Mechanical stops or potentiometers
(only for Types VFC and VFR)
to set the volume flow rates
Supply voltage 24 V AC/DC or 230 V AC
Switching between setpoint values#
or signal voltage range0 10 V DC

Actuators for volume flow controllers Type RN or EN


Part number

Construction

Supply voltage

Type

Identical to attachment

NR-VAV-B50

Min/Max switching, mechanical stops

24 V AC/DC

LM24A-F

B50

NR-VAV-B60

Min/Max switching, mechanical stops

230 V AC

LM230A-F

B60

NR-VAV-B70

Variable adjustment, mechanical stops

24 V AC/DC LM24A-SR-F

B70

Auxiliary switch

S2A

Included with B*2

NR-VAV-S2
NR-VAV-RNMAT

Installation accessories for RN

NR-VAV-ENMAT

Installation accessories for EN

Installation accessories for CAV controllers Type EN or RN are to be ordered separately

Actuator for switching


between setpoint values
(B*05, B6*, B7*)
for Type RN or EN

Auxiliary switch (B*2) S2A

K5 2.2 

05/2015 DE/en

Actuators for CAV controllers

TOC

General information

Retrofit kits

Actuators for volume flow controllers Type VFC and for flow adjustment dampers Type VFR
Part number

Actuator with
potentiometers (E0*)
for Types VFC and VFR

Construction

Supply voltage

Type

Identical to attachment

NR-VAV-E01

Min/Max switching, potentiometer

24 V AC/DC

224-024-02-001

E01

NR-VAV-E02

Min/Max switching, potentiometer

230 V AC

224-230-02-002

E02

NR-VAV-E03

Variable adjustment, potentiometer

24 V AC/DC 224C-024-02-003

E03

NR-VAV-M01 Min/Max switching, mechanical stops

24 V AC/DC

CM24-F

M01

NR-VAV-M02 Min/Max switching, mechanical stops

230 V AC

CM230-F

M02

Actuator with
mechanical stops (M0*)
for Type VFC or VFR

Order code

Retrofit kits for EN, RN, VFC, VFR

NR-VAV-E01

Retrofit kit
For Types EN and RN
NR-VAV-B50 Retrofit actuator for min/max
switching, identical to attachment B50
NR-VAV-B60 Retrofit actuator for min/max
switching, identical to attachment B60
NR-VAV-B50 Retrofit actuator for variable
adjustment, identical to attachment E03
NR-VAV-B70 Retrofit actuator for variable
adjustment, identical to attachment B70
NR-VAV-S2 Retrofit auxiliary switch,
identical to attachment B*2
NR-VAV-ENMAT Retrofit installation accessories
for EN
NR-VAV-RNMAT Retrofit installation accessories
for RN

05/2015 DE/en

For Types VFC and VFR


NR-VAV-E01 Retrofit actuator for min/max
switching, identical to attachment E01
NR-VAV-E02 Retrofit actuator for min/max
switching, identical to attachment E02
NR-VAV-E03 Retrofit actuator for variable
adjustment, identical to attachment E03
NR-VAV-M01 Retrofit actuator for min/max
switching, identical to attachment M01
NR-VAV-M02 Retrofit actuator for min/max
switching, identical to attachment M02

K5 2.2 

TOC

2.3

X X Grundlagen

und Definitionentestregistrierung

Constant volume flow control


CONSTANTFLOW

Basic information
and nomenclature

Product selection
Principal dimensions
Nomenclature
Construction
Correction values for system attenuation
Measurements
Sizing and sizing example

05/2015 DE/en

K5 2.3 1

Constant volume flow control CONSTANTFLOW

TOC

Basic information and nomenclature


Product selection

Type

RN

EN

VFL

VFC

RN-Ex

EN-Ex

Type of system
Supply air

Extract air

Duct connection, fan end


Circular

Rectangular

Volume flow rate range


Up to [m/h]

5040

12100

900

1330

5040

12100

Up to [l/s]

1400

3360

250

370

1400

3360

Filtered

Office extract air

Polluted

Contaminated

Constant

Variable

Min/Max

Air quality

Control function

Acoustic requirements
High < 40 dB(A)

Low < 50 dB (A)

Special areas
Areas with explosive atmospheres

Possible
Possible under certain conditions: Robust unit variant and/or specific actuator or a useful additional product
Not possible

K5 2.3 2

05/2015 DE/en

Constant volume flow control CONSTANTFLOW

TOC

Basic information and nomenclature


Principal dimensions

D [mm]
Outside diameter of the spigot

B [mm]
Width of device

D [mm]
Pitch circle diameter of flanges

H [mm]
Duct height

D [mm]
Outside diameter of flanges

H [mm]
Screw hole pitch of flange (vertical)

D [mm]
Inside diameter of the screw holes of flanges

H [mm]
Outside dimension of flange (height)

L [mm]
Length of unit including connecting spigot

H [mm]
Unit height

L [mm]
Length of casing or acoustic cladding

n[]
Number of flange screw holes

B [mm]
Duct width

T [mm]
Flange thickness

B [mm]
Screw hole pitch of flange (horizontal)

m [kg]
Unit weight including the minimum
required attachments for manual adjustment

B [mm]
Outside dimension of flange (width)

Nomenclature

Acoustic data

Definition of noise

fm [Hz]
Octave band centre frequency
LPA [dB(A)]
A-weighted sound pressure level of airregenerated noise of the VAV terminal unit, system
attenuation taken into account
LPA1 [dB(A)]
A-weighted sound pressure level of airregenerated noise of the VAV terminal unit with
secondary silencer, system attenuation taken into
account

LPA

Air-regenerated noise
Case-radiated noise

LPA2 [dB(A)]
A-weighted sound pressure level of caseregenerated noise of the VAV terminal unit, system
attenuation taken into account
LPA3 [dB(A)]
A-weighted sound pressure level of caseregenerated noise of the VAV terminal unit with
acoustic cladding, system attenuation taken into
account
All sound pressure levels are based on 20 Pa.

05/2015 DE/en

K5 2.3 3

Constant volume flow control CONSTANTFLOW

TOC

Basic information and nomenclature


Volume flow rates

nom [m/h] and [l/s]


Nominal volume flow rate (100 %)
The value depends on product type
and nominal size
Values are published on the internet
and in technical leaflets, and stored
in the Easy Product Finder design software.
Upper limit of the setting range and maximum
volume flow rate setpoint value
for the CAV controller

Differential pressure

[m/h] and [l/s]


Volume flow rate
[ %]
Volume flow rate tolerance from setpoint value

Static differential pressure

pst [Pa]
Static differential pressure
pst min [Pa]
Static differential pressure, minimum
The static minimum differential pressure
is equal to the pressure loss of the CAV
controller when the damper blade is open,
caused by flow resistance (bellows, crossbar)
If the pressure on the CAV controller is too low,
the setpoint volume flow rate may not be
achieved, not even when the damper blade
is open
Important factor in designing the ductwork
and in rating the fan including speed control
Sufficient duct pressure must be ensured
for all operating conditions and for all
controllers, and the measurement point
or points for speed control must have been
selected accordingly to achieve this

Constructions

Galvanised sheet steel


Casing made of galvanised sheet steel
Parts in contact with the airflow
as described for the product type
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

st

Stainless steel (A2)


Casing made of stainless steel 1.4201
Parts in contact with the airflow
are powder-coated or made of stainless steel
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

Powder-coated surface (P1)


Casing made of galvanised sheet steel,
powder-coated RAL 7001, silver grey
Parts in contact with the airflow
are powder-coated or made of plastic
Due to production, some parts that come
into contact with the airflow may be stainless
steel or aluminium, powder-coated
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

K5 2.3 4

05/2015 DE/en

Constant volume flow control CONSTANTFLOW

TOC

Basic information and nomenclature


The quick sizing tables
show the sound pressure
levels that can be
expected in a room both
for the air-regenerated
noise and for the caseradiated noise. The sound
pressure level in a room
results from the sound
power level of the
products for a given
volume flow rate and
differential pressure
and the attenuation
and insulation on site.
Generally accepted
attenuation and insulation
values have been taken
into account.
The distribution of air
across the ductwork,
changes of direction,
end reflection, and room
attenuation all affect the
sound pressure level of
the air-regenerated noise.
Ceiling insulation
and room attenuation
influence the sound
pressure level of the caseradiated noise.

Reducing the sound pressure level of the air-regenerated noise

Correction values
for acoustic quick sizing

Octave correction for the distribution in the ducting,


used to calculate the air-regenerated noise

The correction values


for the distribution
in the ducting are based
on the number of diffusers
assigned to any one air
terminal unit. If there
is just one diffuser
(assumption: 140 l/s or
500 m/h), no correction
is necessary.
One change of direction,
e.g. at the horizontal
connection of the diffuser
plenum box, has been
taken into consideration
for the system attenuation
values. Vertical
connection of the plenum
box does not result in
a system attenuation.
Additional bends result
in lower sound pressure
levels.

End reflection
Ceiling insulation

VAV terminal unit


Distribution in the ducting
Change of direction

in [m/h]

500

1000

1500

2000

2500

3000

4000

[l/s]

140

280

420

550

700

840

1100

[dB]

5000
1400
9

10

System attenuation per octave to VDI 2081 for the calculation of the air-regenerated noise
63

125

250

500

Centre frequency [Hz]

1000

2000

4000

8000

L
dB

Change of direction

Mndungsreflexion

10

Room attenuation

The calculation is based on the end reflection for nominal size 250

Octave correction for the calculation of case-radiated noise


63

125

250

500

Centre frequency [Hz]

1000

2000

4000

8000

L
dB

05/2015 DE/en

Ceiling insulation

Room attenuation

K5 2.3 5

Constant volume flow control CONSTANTFLOW

TOC

Basic information and nomenclature


Measurements

The acoustic data


for the air-regenerated
noise and case-radiated
noise are determined
according to
EN ISO 5135.
All measurements
are carried out in a
reverberation chamber
to EN ISO 3741.

Measuring the air-regenerated noise

st

Reverberation chamber
VAV terminal unit
Microphone

LP

Fan
Sound attenuator

The sound pressure levels for air-regenerated noise LPA given by us result from measurements
in a reverberation chamber. The sound pressure LP is measured for the entire frequency range.
The evaluation of the measurements, including system attenuation and A-weighting,
results in the sound pressure level LPA.
Measuring the case-radiated noise

Reverberation chamber
VAV terminal unit
Microphone

st

LP

Fan
Sound attenuator

The sound pressure levels for case-radiated noise LPA2 given by us result from measurements
in a reverberation chamber. The sound pressure LP is measured for the entire frequency range.
The evaluation of the measurements, including system attenuation and A-weighting,
results in the sound pressure level LPA2.

K5 2.3 6

05/2015 DE/en

Constant volume flow control CONSTANTFLOW

TOC

Basic information and nomenclature


Sizing with
the help of this catalogue

This catalogue provides convenient quick sizing


tables for CAV controllers. The sound pressure
levels for air-regenerated noise and for caseradiated noise are provided for all nominal sizes.
In addition, generally accepted attenuation and
insulation values have been taken into account.
Sizing data for other volume flow rates and
differential pressures can be determined quickly
and precisely using the Easy Product Finder
design programme.

Sizing example

Given data
max = 280 l/s (1010 m3/h)
pst = 150 Pa
Required sound pressure
level in the room 35 dB(A)

Quick sizing
RN/200 with circular silencer CS 050/2001000
Air-regenerated noise LPA = 26 dB(A)
Case-radiated noise LPA = 31 dB(A)

Easy Product Finder

The Easy Product Finder


allows you to size
products using your
project-specific data.
You will find
the Easy Product Finder
on our website.

K5 2.3 

05/2015 DE/en

Shut-off and restriction

TOC

Table of contents
3

Shut-off and flow adjustment


Flow adjustment dampers are circular dampers for the manual balancing of volume flow
rates. Shut-off dampers are used for low-leakage shut-off or for the balancing of volume
flow rates.

3.1 Shut-off dampers

Type

Page

For low-leakage shut-off

AK

3.1 1

For contaminated air

AKK

3.1 12

For low-leakage shut-off of volume flows


in potentially explosive atmospheres
(ATEX)

AK-Ex

3.1 22

VFR

3.2 1

For the opening and closing of


shut-off dampers in air conditioning
systems

Open/Close
actuators

3.3 1

For moving the damper blades


of shut-off dampers to any position

Modulating
actuators

3.3 12

Circular

Optimum resistance

For use in potentially


explosive atmospheres

3.2 Flow adjustment dampers


Circular

For the reliable balancing


of volume flow rates

3.3 Actuators for shut-off dampers

3.4 Basic information and nomenclature


Shut-off and flow adjustment

K5 3.0 1

3.4 1

05/2015 DE/en

AK

TOC

3.1

X X AKtestregistrierung

Shut-off dampers
Type AK

For low-leakage shut-off


Circular shut-off dampers for shutting off volume flows in ventilation
ducts of air conditioning systems
Maintenance-free damper blade mechanism
Closed blade air leakage to EN 1751, up to class 4
Casing air leakage to EN 1751, class C
Optional equipment and accessories
Electric actuator
Spring return actuator
Variant for manual operation

H GE

TE

ET

HY

ISC

Auxiliary switch with adjustable switching points


for capturing the end positions

ST

EN

Pneumatic actuator

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 3.1 1



TOC

General information

AK
Page

Type
AK

Variants

General information
Order code
Quick sizing
Dimensions and Weight AK...
Dimensions and Weight AK.../.../B**
Dimensions and Weight AK.../.../TN0
Installation details
Specification text

3.1 2
3.1 5
3.1 6
3.1 7
3.1 8
3.1 9
3.1 10
3.1 11

Basic information and nomenclature

3.4 1

Shut-off damper, variant AK

Shut-off dampers Type AK with actuator

Application
Circular shut-off dampers Type AK for shutting
off or restricting the airflow in ventilation ducts
of air conditioning systems

Parts and characteristics


Ready-to-install shut-off damper
Damper blade with blade mechanism

Product examples

Description

Variants
AK: Shut-off damper
AK-FL: Shut-off damper
with flanges on both ends
Shut-off damper,
variant AK, with actuator
For detailed information
on actuators see Chapter
K5 3.3.

Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Nominal sizes
100, 125, 160, 200, 250, 315, 400
Attachments
Min/Max actuators: Actuators for switching
between minimum and maximum
volume flow rate setpoint values
Auxiliary switch for capturing the end positions
Accessories
Lip seals on both ends (factory fitted)
Matching flanges for both ends
Special features
Damper blade can be actuated manually,
electrically or pneumatically
Low-leakage shut-off
Safety function provided by optional
spring return actuator

K5 3.1 2

Construction features
Circular casing
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
Position of the damper blade indicated
externally at the shaft extension
AK-FL: Flanges to EN 12220
Materials and surfaces
Galvanised sheet steel construction
Casing and damper
blade made of galvanised sheet steel
Blade seal made of TPE plastic
Plain bearings made of polyurethane
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Shut-off damper and shaft made of stainless
steel 1.4301
Stainless steel construction (A2)
Casing, damper blade and shaft
made of stainless steel 1.4301
Installation and commissioning
Any installation orientation

05/2015 DE/en



TOC

General information

AK

Standards and guidelines


Hygiene conforms to VDI 6022
Closed blade air leakage to EN 1751, class 4
(nominal sizes 100, 125 and 160, class 3)
Nominal sizes 100, 125, and 160 meet the
general requirements, nominal sizes 200 400
meet the increased requirements of DIN 1946,
part 4, with regard to the acceptable
closed blade air leakage
Casing air leakage to EN 1751, class C

Maintenance
Maintenance-free as construction
and materials are not subject to wear

Attachments: electric
Order code detail
Open/Close actuators
B30
B32
B40
B42
BP0
BP2
BR0
BR2
Modulating actuators
B20

Actuator

Supply voltage

Auxiliary switch

24 V AC/DC

Actuator with mechanical stops


TROX/Belimo

230 V AC
24 V AC/DC

Spring return actuator with mechanical stops


TROX/Belimo

230 V AC

Modulating actuator 0 10 V with mechanical stops


TROX/Belimo

24 V AC/DC

Attachments: pneumatic
Order code detail
Pneumatic actuators
TN0

Technical data

05/2015 DE/en

Actuator

Control pressure

Auxiliary switch

Pneumatic actuator
TROX

0.2 1.0 bar

Nominal sizes
Acceptable static differential pressure
Operating temperature

100 400 mm
1500 Pa
10 50 C

K5 3.1 3



TOC

General information
Function

AK

Schematic illustration of the AK

Damper blade
Lip seal

K5 3.1 4

Casing
Actuator

05/2015 DE/en



TOC

Order code
Order code

AK

AK

AK P1 FL / 160 / G2 / BP0 / NO

Type
AK
Shut-off damper
Material
No entry: galvanised sheet steel
P1
Powder-coated, silver grey (RAL 7001)
A2
Stainless steel
Construction
No entry: none
Flanges on both ends
FL
Nominal size [mm]
100
125
160
200
250
315
400

Actuator
No entry: manual operation
For example
B20 24 V AC/DC, modulating 2 10 V DC
B30 24 V AC/DC, 3-point
B32 24 V AC/DC, 3-point, with auxiliary switch
TN0 Pneumatic 0.2 1 bar
Damper blade position
Only for spring return actuators
and pneumatic actuators
Pressure off/power off to OPEN
NO
NC
Power off/Pressure off to close

Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Order examples

AK/160/D2/B30
Material
Nominal size
Accessories
Actuator

Galvanised sheet steel


160 mm
Lip seals on both ends
Supply voltage 24 V AC/DC

AK-A2-FL/200/G2
Material
Construction
Nominal size
Accessories

05/2015 DE/en

Stainless steel
Flanges on both ends
200 mm
Matching flanges for both ends

K5 3.1 5



TOC

Quick sizing
Air-regenerated noise
Quick sizing tables
provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.

AK

Quick sizing: Static differential pressure and sound pressure levels with open damper blade

l/s
100

125

160

200

250

315

400

K5 3.1 6

Nominal size

m/h
10
40
65
95
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
100
410
720
1030
170
670
1175
1680

Differential pressure

Air-regenerated
noise

pst

LPA

Pa
36
144
234
342
54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
360
1476
2592
3708
612
2412
4230
6048

dB(A)
5
10
25
55
5
10
25
50
5
10
20
45
5
10
20
40
<5
5
15
30
<5
5
15
25
<5
5
10
15

<15
27
38
49
<15
24
36
45
<15
22
33
41
<15
21
31
39
<15
19
29
38
<15
21
34
43
<15
34
50
61

05/2015 DE/en



TOC

Dimensions and Weight AK...


Dimensions

AK

AK
L

Shut-off damper,
variant AK

12

50

< 70

AK-FL
L

50

12

< 70

n 9.5
T

Dimensions [mm] and weight [kg]


AK
Nominal size
100
125
160
200
250
315
400

05/2015 DE/en

Flange dimensions

AK-FL

mm

kg

mm

kg

250
250
250
250
250
400
400

1.1
1.4
1.8
2.5
3.5
5.1
7.1

230
230
230
230
230
380
380

1.8
2.0
3.0
3.9
5.2
8.2
11.0

AK-FL
Nominal size

mm
99
124
159
199
249
314
399

100
125
160
200
250
315
400

D1

mm

132
157
192
233
283
352
438

D2
152
177
212
253
303
378
464

mm
4
4
6
6
6
8
8

4
4
4
4
4
4
4

K5 3.1 7



TOC

Dimensions and Weight AK.../.../B**

AK

AK/.../B** (electric actuators)


L
50

12

Shut-off dampers
Type AK with actuator

~ 100

1)

~ 110

for spring return actuators up to 195

AK-FL/.../B** (electric actuators)


L

50

12

n 9.5
9,5
T
~ 110

~ 100

1)

for spring return actuators up to 195

Dimensions [mm] and weight [kg]


AK/.../B**
Nominal size
100
125
160
200
250
315
400

K5 3.1 8

Flange dimensions

AK-FL/.../B**

mm

kg

mm

kg

250
250
250
250
250
400
400

2.6
2.9
3.3
4.0
5.0
6.6
8.6

230
230
230
230
230
380
380

3.2
3.5
4.4
5.4
6.7
9.7
12.5

AK-FL
Nominal size

mm
99
124
159
199
249
314
399

100
125
160
200
250
315
400

D1

mm

132
157
192
233
283
352
438

D2
152
177
212
253
303
378
464

mm
4
4
6
6
6
8
8

4
4
4
4
4
4
4

05/2015 DE/en



TOC

Dimensions and Weight AK.../.../TN0

AK

AK/.../TN0 (pneumatic drive)


600

50

~ 110

AK-FL/.../TN0 (pneumatic drive)


580

50




Dimensions [mm] and weight [kg]


AK/.../TN0
Nominal size
100
125
160
200
250
315
400

05/2015 DE/en

Flange dimensions

AK-FL/.../TN0

mm

kg

mm

kg

600
600
600
600
600
600
600

3.3
3.6
4.2
5.1
6.1
7.2
9.4

580
580
580
580
580
580
580

3.9
4.2
5.3
6.5
7.8
10.3
13.3

AK-FL
Nominal size

mm
99
124
159
199
249
314
399

100
125
160
200
250
315
400

D1

mm

132
157
192
233
283
352
438

D2
152
177
212
253
303
378
464

mm
4
4
6
6
6
8
8

4
4
4
4
4
4
4

K5 3.1 9

Shut-off dampers

TOC

Installation details
Space requirement
for commissioning
and maintenance

AK

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required

Attachments

K5 3.1 10

mm

Without actuator

250

200

200

With electric actuator

200

300

300

With pneumatic actuator

400

300

300

05/2015 DE/en

Shut-off dampers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular shut-off dampers for shutting


off or restricting the airflow in ventilation ducts
of air conditioning systems, for supply air
or extract air, available in 7 nominal sizes
Suitable for duct pressures up to 1500 Pa.
Ready-to-install unit consists of the casing
with a damper blade. Spigot with groove for lip
seal, suitable for connecting ducts according
to EN 1506 or EN 13180.
Position of the damper blade indicated
externally at the shaft extension.
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 100, 125 and 160, class 3).
Casing air leakage to EN 1751, class C.

AK
Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Technical data
Nominal sizes: 100 400 mm
Acceptable static differential pressure: 1500 Pa
Sizing data
[m/h]
LPA air-regenerated noise[dB(A)]

Special features
Damper blade can be actuated manually,
electrically or pneumatically
Low-leakage shut-off
Safety function provided by optional
spring return actuator

Materials and surfaces


Galvanised sheet steel construction
Casing and damper
blade made of galvanised sheet steel
Blade seal made of TPE plastic
Plain bearings made of polyurethane
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Shut-off damper and shaft made of stainless
steel 1.4301
Stainless steel construction (A2)
Casing, damper blade and shaft
made of stainless steel 1.4301

Order options

Type
AK
Shut-off damper
Material
No entry: galvanised sheet steel
P1
Powder-coated, silver grey (RAL 7001)
A2
Stainless steel
Construction
No entry: none
FL
Flanges on both ends
Nominal size [mm]
100
125
160
200
250
315
400

Actuator
No entry: manual operation
For example
B20 24 V AC/DC, modulating 2 10 V DC
B30 24 V AC/DC, 3-point
B32 24 V AC/DC, 3-point,
with auxiliary switch
TN0 Pneumatic 0.2 1 bar
Damper blade position
Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends

05/2015 DE/en

K5 3.1 11

AKK

TOC

3.1

X X AKKtestregistrierung


Type AKK

Variant with circular spigot

For contaminated air


Plastic circular shut-off dampers for shutting off aggressive media volume flows
in air conditioning systems
Maintenance-free damper blade mechanism
Closed blade air leakage to EN 1751, class 3
Casing air leakage to EN 1751, class B
Optional equipment and accessories
Electric actuator
Spring return actuator

Variant for manual operation

H GE

TE

ET

HY

ISC

Auxiliary switch with adjustable switching points


for capturing the end positions

ST

EN

Pneumatic actuator

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 3.1 12



TOC

General information

AKK

Type
AKK

Variants

Page
General information
Order code
Quick sizing
Dimensions and Weight AKK
Dimensions and Weight AKK-FL
Installation details
Specification text

3.1 14
3.1 16
3.1 17
3.1 18
3.1 20
3.1 21
3.1 22

Basic information and nomenclature

3.4 1

Shut-off dampers Type AKK

Shut-off damper, variant AKK, with actuator

Application
Plastic circular shut-off dampers Type AKK
for shutting off or restricting the airflow
in ventilation ducts of air conditioning systems
Suitable for contaminated air

Construction features
Circular casing
Spigot suitable for ducts according to DIN 8077
Position of the damper blade indicated
externally at the shaft extension
All components coming into contact
with the airflow are made of plastic
(no interior metal parts)

Product examples

Description
For detailed information
on actuators see Chapter
K5 3.3.

Variants
AKK: Shut-off damper
AKK-FL: Shut-off damper
with flanges on both ends
Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Min/Max actuators: Actuators
for switching between minimum
and maximum volume flow rate setpoint values
Auxiliary switch for capturing the end positions

K5 3.1 13

Materials and surfaces


Casing and damper blade
made of flame-resistant polypropylene (PPs)
Plain bearings made of polypropylene (PP)
Damper blade seals in chloroprene
rubber (CR)
Installation and commissioning
Any installation orientation

Special features
Damper blade can be actuated manually,
electrically or pneumatically
Low-leakage shut-off
Safety function provided by optional spring
return actuator

Standards and guidelines


Hygiene conforms to VDI 6022
Closed blade air leakage to EN 1751, class 3
Meets the general requirements of DIN 1946,
part 4, with regard to the acceptable closed
blade air leakage
Casing air leakage to EN 1751, class B

Parts and characteristics


Ready-to-install shut-off damper
Damper blade with blade mechanism

Maintenance
Maintenance-free as construction
and materials are not subject to wear

05/2015 DE/en



TOC

General information

AKK

Attachments: electric
Order code detail

Actuator

Open/Close actuators
B30
B32
B40
B42
BP0
BP2
BR0
BR2
Modulating actuators

Supply voltage

24 V AC/DC

Actuator with mechanical stops


TROX/Belimo

230 V AC
24 V AC/DC

Spring return actuator with mechanical stops


TROX/Belimo

230 V AC

Modulating actuator 0 10 V with mechanical stops


TROX/Belimo

B20

Auxiliary switch

24 V AC/DC

Attachments: pneumatic
Order code detail
Pneumatic actuators
TN0

Actuator

Control pressure

Auxiliary switch

Pneumatic actuator
TROX

0.2 1.0 bar

Technical data

Nominal sizes
Acceptable static differential pressure
Operating temperature

Function

Schematic illustration of the AKK (construction variant with flange)

125 400 mm
1500 Pa
10 50 C

Damper blade
Plain bearings

05/2015 DE/en

Flange
Actuator

K5 3.1 14



TOC

Order code
Order code

AKK

AKK

AKK FL / 160 / GK / BP0 / NO

Type
AKK Shut-off damper, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400

Actuator
No entry: manual operation
For example
B20 24 V AC/DC, modulating 2 10 V DC
B30 24 V AC/DC, 3-point
B32 24 V AC/DC, 3-point, with auxiliary switch
TN0 Pneumatic 0.2 1 bar
Damper blade position
Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

Accessories
No entry: none
GK
Matching flanges for both ends
Order example

AKK/160/B30
Nominal size
Actuator

K5 3.1 15

160 mm
Supply voltage 24 V AC/DC

05/2015 DE/en



TOC

Quick sizing
Air-regenerated noise
Quick sizing tables
provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.

AKK

Quick sizing: Static differential pressure and sound pressure levels with open damper blade

l/s
125

160

200

250

315

400

05/2015 DE/en

Nominal size

m/h
15
60
105
150
25
100
175
250
40
160
280
405
60
250
430
615
100
410
720
1030
170
670
1175
1680

Differential pressure

Air-regenerated
noise

pst

LPA

Pa
54
216
378
540
90
360
630
900
144
576
1008
1458
216
900
1548
2214
360
1476
2592
3708
612
2412
4230
6048

dB(A)
5
10
25
50
5
10
20
45
5
10
20
40
<5
5
15
30
<5
5
15
25
<5
5
10
15

<15
24
36
45
<15
22
33
41
<15
21
31
39
<15
19
29
38
<15
21
34
43
<15
34
50
61

K5 3.1 16



TOC

Dimensions and Weight AKK


Dimensions

AKK

AKK

Shut-off dampers
Type AKK
230

AKK/.../.../TN0 (pneumatic actuator)

Dimensions [mm] and weight [kg]


AKK
Nominal size

AKK/.../TN0
m

kg
125
160
200
250
315
400

K5 3.1 17

1.2
1.5
1.9
3.1
5.0
7.2

B3

H3

mm
2.9
3.2
3.6
4.8
6.7
8.9

125
160
200
250
315
400

394
394
394
594
594
594

195
230
270
320
385
470

145
180
220
270
335
420

05/2015 DE/en



TOC

Dimensions and Weight AKK

AKK

AKK/.../B** (electric actuators)

~ 80

Shut-off damper,
variant AKK, with actuator

Dimensions [mm] and weight [kg]


AKK/.../B**
Nominal size

kg
125
160
200
250
315
400

05/2015 DE/en

B3

H3

mm
3.1
3.4
3.8
5.0
6.9
9.1

125
160
200
250
315
400

394
394
394
594
594
594

195
230
270
320
385
470

145
180
220
270
335
420

K5 3.1 18



TOC

Dimensions and Weight AKK-FL

AKK

AKK-FL

L

~ 80

Shut-off damper,
variant AKK

n x 10

3
Dimensions [mm] and weight [kg]
AKK-FL AKK-FL/.../B** AKK-FL/.../TN0
Nominal size

K5 3.1 19

H3

D1

D2

m
kg

125
160
200
250
315
400

B3

1.5
1.9
2.4
3.7
6.0
8.5

3.4
3.8
4.3
5.6
7.9
10.4

mm
3.2
3.6
4.1
5.4
7.7
10.2

125
160
200
250
315
400

400
400
400
600
600
600

195
230
270
320
385
470

mm
145
180
220
270
335
420

165
200
240
290
350
445

185
230
270
320
395
475

8
8
8
12
12
16

8
8
8
8
10
10

05/2015 DE/en

Shut-off dampers

TOC

Installation details
Space requirement
for commissioning
and maintenance

AKK

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required
Attachments

05/2015 DE/en

mm

Without actuator
With electric actuator

250
300

150
200

200
300

With pneumatic actuator

400

350

300

K5 3.1 20

Shut-off dampers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular shut-off dampers in PPs plastic for air


conditioning systems, available in 6 nominal sizes.
Suitable for shutting off or restricting extract air
flows containing aggressive substances since all
components coming into contact with the airflow
are made of plastic (no interior metal parts).
Suitable for duct pressures up to 1500 Pa.
Ready-to-install unit consists of the casing
with a damper blade.
Spigot, suitable for ducts according to DIN 8077.
Position of the damper blade indicated
externally at the shaft extension.
Closed blade air leakage to EN 1751, class 3.
Casing air leakage to EN 1751, class B.

AKK
Materials and surfaces
Casing and damper blade
made of flame-resistant polypropylene (PPs)
Plain bearings made of polypropylene (PP)
Damper blade seals in chloroprene
rubber (CR)
Technical data
Nominal sizes: 125 400 mm
Acceptable static differential pressure: 1500 Pa
Sizing data
[m/h]
LPA air-regenerated noise[dB(A)]

Special features
Damper blade can be actuated manually,
electrically or pneumatically
Low-leakage shut-off
Safety function provided by optional spring
return actuator

Order options

Type
AKK
Shut-off damper, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400

Actuator
No entry: manual operation
For example
B20 24 V AC/DC, modulating 2 10 V DC
B30 24 V AC/DC, 3-point
B32 24 V AC/DC, 3-point,
with auxiliary switch
TN0 Pneumatic 0.2 1 bar
Damper blade position
Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

Accessories
No entry: none
GK
Matching flanges for both ends

K5 3.1 21

05/2015 DE/en

AK-Ex

TOC

3.1

X X AK-Ex testregistrierung

Shut-off dampers
Type AK-Ex

For low-leakage shut-off of volume flows in potentially


explosive atmospheres (ATEX)
Circular shut-off dampers for shutting off ducts,
approved and certified for potentially explosive atmospheres (ATEX)
ATEX-compliant construction and parts
Approved for all gases, mists and vapours in zones 1 and 2,
with electric actuator additionally for dusts in zones 21 and 22
Suitable for supply air and extract air
Electric or pneumatic actuator
Any installation orientation
ATEX-compliant parts
and units

Closed blade air leakage to EN 1751, up to class 4


Casing air leakage to EN 1751, class C
Optional equipment and accessories
Spring return actuator
Auxiliary switch with adjustable switching points
for capturing the end positions

ATEX-Zertifizierung

05/2015 DE/en

K5 3.1 22



TOC

General information

AK-Ex

Type

Page

AK-Ex

General information
Order code
Quick sizing
Dimensions and weight
Installation details
Specification text

3.1 24
3.1 27
3.1 28
3.1 29
3.1 30
3.1 31

Basic information and nomenclature

3.4 1

Schematic illustration of the AK-Ex


with electronic control

Schematic illustration of the AK-Ex


with pneumatic control

Save Area





Shut-off damper
Electric actuator
Terminal box
Switch (to be provided by others)
Description

Shut-off damper
Type AK-Ex

Application
Circular EXCONTROL shut-off dampers
Type AK-Ex for shutting off or restricting
the airflow in ventilation ducts
of air conditioning systems
For use in potentially explosive atmospheres
(ATEX)
Input signal to control shut-off damper blade
is to be provided by others
Classification
Electronic control: Equipment group II
Zones 1 and 2 (atmosphere: gases):
II 2 G c II T5/T6
Zones 21 and 22 (atmosphere: dusts):
II 2 D c II 80 C
Pneumatic control: Equipment group II
Zones 1 and 2 (atmosphere: gases):
II 2 G c II T5/T6
Construction
Galvanised sheet steel
P1: Inner duct powder-coated, silver grey
(RAL 7001)
A2: Inner duct in stainless steel

K5 3.1 23

Shut-off damper
Pneumatic actuator
Valve or control signal 0 1 bar
(to be provided by others)

Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Electronic actuator:
Auxiliary switch for capturing the end positions
Pneumatic actuator
Special features
ATEX mark and certification
ATEX equipment group II, approved for use
in zones 1 and 2; electric actuator
also for zones 21 and 22
Parts and characteristics
Ready-to-install shut-off damper
Damper blade with blade mechanism
Connection for equipotential bonding
Cable bushings suitable for use
in potentially explosive atmospheres
ATEX-compliant actuator is factory
assembled and wired
Construction features
Circular casing
Construction and materials comply
with the EU directive for use in potentially
explosive atmospheres (ATEX)
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180

05/2015 DE/en



TOC

General information

AK-Ex

Materials and surfaces


Casing and damper blade
made of galvanised sheet steel
Blade seal made of TPE plastic
Plain bearings made of polyurethane
Electric actuator made of die cast aluminium
Pneumatic actuator made of plastic
Inner tube either made of stainless steel (A2)
or powder-coated (P1)
Installation and commissioning
Connections for equipotential bonding:
Suitable cables must be connected by others
Any installation orientation

Technical data

Nominal sizes
Acceptable static differential pressure
Operating temperature

Electronic

Supply voltage
Power rating
IEC protection class
Protection level
EC conformity

Pneumatic

Control pressure
Maximum pressure
Compressed air
Protection level
Air consumption (100 % stroke)

Maintenance
Maintenance-free as construction
and materials are not subject to wear

125 400 mm
1500 Pa
10 50 C

24 230 V AC 10 %, 50/60 Hz
120 VA max.
I (protective earth)
IP 66
ATEX to 94/9/EG, EMC to 2004/108/EG, low voltage to 2006/95/EG

0 1.2 bar
1.5 bar
Compressed air for instruments, free of oil, water and dust
IP 20
0.3 l/n (nominal sizes 125 250) to 0.5 l/n max. (nominal size 315 400)

Schematic illustration of the AK-Ex


with electronic control

Standards and guidelines


Directive 94/9/EC: Equipment and protective
systems intended for use in potentially
explosive atmospheres
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 100 and 160, class 3)
Nominal sizes 125 and 160 meet the general
requirements, nominal sizes 200 400 meet
the increased requirements of DIN 1946,
part 4, with regard to the acceptable
closed blade air leakage
Casing air leakage to EN 1751, class C

Schematic illustration of the AK-Ex


with pneumatic control

05/2015 DE/en

Cover
Auxiliary switch
Electric actuator
Terminal box
Cable bushing
Equipotential bonding
Damper blade

Cover
Pneumatic actuator
Control signal connection
Equipotential bonding
Damper blade

K5 3.1 24



TOC

Order code
Order code

AK-Ex

AK-Ex

AK-Ex P1 / 125 / T0F / NO

Type
AK-Ex Shut-off damper for potentially
explosive atmospheres
Material
No entry: galvanised sheet steel
P1
Inner duct powder-coated, silver grey
(RAL 7001)
A2
Inner duct in stainless steel
Nominal size [mm]
125
160
200
250
315
400
Order examples

Actuator
Electronic
T0S Actuator
T0F Spring return actuator
T0X Actuator with auxiliary switch
T0Y Spring return actuator with auxiliary switch
P50

Pneumatic
Actuator

Damper blade position


Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

AK-Ex/125/T0S
Material
Nominal size
Actuator

Galvanised sheet steel


125 mm
Electric actuator

AK-Ex/200/P50/NO
Material
Nominal size
Actuator
Damper blade position

05/2015 DE/en

Galvanised sheet steel


200 mm
Pneumatic actuator
Pressure off to OPEN

K5 3.1 25



TOC

Quick sizing
Air-regenerated noise
Quick sizing tables
provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.

AK-Ex

Quick sizing: Static differential pressure and sound pressure levels with open damper blade

l/s
125

160

200

250

315

400

K5 3.1 26

Nominal size

m/h
49
74
98
147
80
121
161
241
126
188
251
377
196
295
393
589
312
468
623
935
503
754
1005
1508

Differential pressure

Air-regenerated
noise

pst

LPA

Pa
177
265
353
530
290
434
579
869
452
679
905
1357
707
1060
1414
2121
1122
1683
2244
3367
1810
2714
3619
5429

dB(A)
5
12
21
46
4
10
17
39
4
8
14
32
3
6
11
25
2
4
8
18
1
3
5
10

20
28
34
45
18
26
32
40
17
24
29
37
16
22
28
37
16
24
30
41
26
37
45
58

05/2015 DE/en



TOC

Dimensions and weight


Dimensions

AK-Ex

AK-Ex
600

536

Dimensions
Nominal size
125
160
200
250
315
400

D
124
159
199
249
314
399

B3

mm

372
372
463
463
627
627

H3
221
221
311
311
461
461

C
129
111
182
157
289
246

Weight
AK-Ex/.../T0*

AK-Ex/.../P..

Nominal size

125
160
200
250
315
400

16.5
16.5
18.0
18.0
22.0
22.0

kg

05/2015 DE/en

15.0
15.0
16.5
16.5
20.5
20.5

K5 3.1 27

Shut-off dampers

TOC

Installation details
Space requirement
for commissioning
and maintenance

AK-Ex

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required

Nominal size
125
160
200
250
315
400

K5 3.1 28

mm
600
600
600
600
600
600

220
220
310
310
460
460

300
300
300
300
300
300

05/2015 DE/en

Shut-off dampers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular shut-off dampers for shutting off


or restricting the airflow in potentially explosive
atmospheres, for supply air or extract air,
available in 6 nominal sizes.
Suitable for duct pressures up to 1500 Pa.
Ready-to-install unit consists of the casing with
damper blade, and parts for equipotential bonding
and for use in potentially explosive atmospheres.
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180.
Closed blade air leakage to EN 1751,
class 4 (nominal sizes 125 and 160, class 3).
Casing air leakage to EN 1751, class C.

AK-Ex
Construction
Galvanised sheet steel
P1: Inner duct powder-coated,
silver grey (RAL 7001)
A2: Inner duct in stainless steel
Technical data
Nominal sizes: 125 400 mm
Acceptable static differential pressure: 1500 Pa
Sizing data
[m/h]
LPA air-regenerated noise[dB(A)]

Special features
ATEX mark and certification
ATEX equipment group II,
approved for use in zones 1 and 2; electric
actuator also for zones 21 and 22

Materials and surfaces


Casing and damper blade
made of galvanised sheet steel
Blade seal made of TPE plastic
Plain bearings made of polyurethane
Electric actuator made of die cast aluminium
Pneumatic actuator made of plastic
Inner tube either made of stainless steel (A2)
or powder-coated (P1)

Order options

Type
AK-Ex Shut-off damper for potentially
explosive atmospheres
Material
No entry: galvanised sheet steel
P1
Inner duct powder-coated,
silver grey (RAL 7001)
A2
Inner duct in stainless steel
Nominal size [mm]
125
160
200
250
315
400

05/2015 DE/en

Actuator
Electronic
T0S Actuator
T0F Spring return actuator
T0X Actuator with auxiliary switch
T0Y Spring return actuator
with auxiliary switch
P50

Pneumatic
Actuator

Damper blade position


Only for spring return actuators
and pneumatic actuators
NO
Pressure off/power off to OPEN
NC
Power off/Pressure off to close

K5 3.1 29

VFR

TOC

3.2

X X VFRtestregistrierung

Flow adjustment dampers

Type VFR

3
Variant with rotary knob

Actuator with potentiometers

For the reliable balancing of volume flow rates


Circular flow adjustment dampers for the adjustment of volume flow rates
and pressures in supply air and extract air systems
Each flow adjustment damper carries a diagram
with setting values that ensure rapid commissioning on site
Suitable for duct pressures up to 1000 Pa.
Volume flow rate can be set using a rotary knob
and a scale on the outside of the casing
Simple retrofit of an actuator
Casing air leakage to EN 1751, class C

Actuator with mechanical


stops

Optional equipment and accessories


Actuator with potentiometer
Actuator with mechanical stops

H GE

TE

ET

HY

ISC

ST

EN

VD

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 3.2 1

Flow adjustment dampers

TOC

General information

VFR

Type

Page

VFR

General information
Order code
Aerodynamic data
Quick sizing
Dimensions and weight
Installation details
Specification text

3.2 2
3.2 5
3.2 6
3.2 7
3.2 8
3.2 9
3.2 10

Basic information and nomenclature

3.4 1

Type VFR The System

Flow adjustment damper VFR with rotary knob


Actuator E0* with potentiometers

Actuator M0* with mechanical stops

Diagram with setting values

VFR
125
VFR 100
100
125

500
400
300

Pa

St

200
150
100
80
60
50
40
30
20
15
60

20
80

30
100

40
150

60
200

80
100 l/s 140
300
500
m3/h

Diagram to determine the setting values on site (example for nominal size 125)

K5 3.2 2

05/2015 DE/en

Flow adjustment dampers

TOC

General information
Description

Flow adjustment
damper, variant VFR,
with rotary knob
For detailed information
on actuators see Chapter
K5 2.2.

VFR

Application
Circular flow adjustment dampers Type VFR
for the simple balancing of volume flow rates
and pressures in air conditioning systems
Stepless adjustment of the volume flow rate
using a rotary knob with position indicator
Simple retrofit of an actuator
At the minimum setting (closed position 0)
a system pressure dependent leakage
flow rate occurs

Materials and surfaces


Rotary knob, damper blade and bearings
made of plastic, flame retardant (V-0) to UL 94
Galvanised sheet steel construction (P1)
Casing made of galvanised sheet steel
Stainless steel construction (A2)
Casing made of stainless steel 1.4301

Construction
Galvanised sheet steel
A2: Stainless steel

Installation and commissioning


Any installation orientation
Volume flow rate setpoint
can be set on external scale

Nominal sizes
80, 100, 125, 140, 150, 160, 180 ,
200, 224, 250

Standards and guidelines


Hygiene conforms to VDI 6022
Casing air leakage to EN 1751, class C

Attachments
Min/Max actuators: Actuators for switching
between minimum and maximum volume
flow rate setpoint values
Modulating actuators: Actuators for the
stepless adjustment of volume flow rates

Maintenance
Maintenance-free as construction
and materials are not subject to wear

Special features
Diagram with setting values on each
flow adjustment damper
Simple retrofit of an actuator is possible
Parts and characteristics
Ready-to-install flow adjustment damper
Rotary knob with position indicator
Stepless adjustment from 0 to 10
Diagram with setting values
Lip seal
Construction features
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180
Very good dimensional stability due
to double grooves
Damper blade without seal but
with perimeter gap of 3 mm
Attachments
Order code detail
Min/Max actuators
E01
E02
M01
M02
Modulating actuators
E03

Technical data

05/2015 DE/en

Actuator

Supply voltage

Auxiliary switch

Actuator with potentiometers


TROX/Gruner

24 V AC/DC
230 V AC
24 V AC/DC
230 V AC

24 V AC/DC

Actuator with mechanical stops


TROX/Belimo
Actuator with potentiometers
TROX/Gruner

Nominal sizes
Volume flow rate range
Minimum differential pressure
Maximum differential pressure
Operating temperature

80 250 mm
20 485 l/s or 72 1746 m/h
20 Pa
1000 Pa
10 50 C

K5 3.2 3

Flow adjustment dampers

TOC

General information
Function

VFR

Functional description
For balancing the volume flow rates of duct
sections and air terminal devices the differential
pressure must be set on the flow adjustment
dampers. The value to be set for a certain required
volume flow rate at a given differential pressure
can be taken from the diagram that each flow
adjustment damper carries. This value can then
be set using the rotary knob with the position
indicator (stepless adjustment between 0 and 10).

Schematic illustration of the VFR

Damper blade
Scale
Rotary knob

K5 3.2 4

Rotary knob locking screw


Lip seal
Diagram with setting values

05/2015 DE/en

Flow adjustment dampers

TOC

Order code
Order code

VFR

VFR

VFR A2 / 160 / E01

Type
VFR Flow adjustment damper
Material
No entry: galvanised sheet steel
A2
Stainless steel
Nominal size [mm]
80
100
125
140
150
160
180
200
224
250
Order example

Actuator
No entry: manual operation
potentiometer
E01 24 V AC/DC, 3-point
E02 230 V AC, 3-point
E03 24 V AC/DC, modulating 0 10 V DC
Mechanical stops
M01 24 V AC/DC, 3-point
M02 230 V AC, 3-point

VFR/160/M01
Nominal size
Actuator

05/2015 DE/en

160 mm
24 V AC/DC, mechanical stops

K5 3.2 5

Flow adjustment dampers

TOC

Aerodynamic data

VFR

Closed blade air leakage


Nominal size
l/s
80
100
125
140
150
160
180
200
224
250

pst [Pa]

100

200

m/h
9
13
16
17
18
21
19
21
22
25

l/s
32
45
58
61
66
76
69
74
80
89

500
m/h

13
18
23
25
26
30
27
29
32
35

l/s
46
64
82
89
93
107
98
105
114
125

m/h
20
28
36
39
41
47
43
46
50
55

72
101
130
140
148
169
155
166
180
198

K5 3.2 6

05/2015 DE/en

Flow adjustment dampers

TOC

Quick sizing
Air-regenerated noise
Quick sizing tables
provide a good overview
of the room sound
pressure levels that can
be expected. Approximate
intermediate values can
be interpolated. Precise
intermediate values and
spectral data can be
calculated with our
Easy Product Finder
design programme.

Quick sizing: Sound pressure level


Nominal size

Volume flow rate


l/s

80

100

125

140

150

160

180

200

224

250

05/2015 DE/en

VFR

10

20

pst [Pa]

30

50

72
108
144
180
109
163
217
272
180
252
342
432
215
323
431
538
252
378
504
619
612
432
558
702
358
540
720
900
450
665
882
1116
557
828
1115
1386
702
1043
1386
1746

100

200

LPA

m/h
20
30
40
50
30
45
60
75
50
70
95
120
60
90
120
150
70
105
140
170
80
120
155
195
100
150
200
250
125
185
245
310
155
230
310
385
195
290
385
485

80

dB(A)
25
30
33
36
27
32
36
40
28
33
37
41
25
31
35
39
26
31
35
37
27
33
38
41
25
31
35
38
26
32
36
39
24
28
32
34
24
28
31
34

28
33
36
40
29
35
39
43
31
36
41
45
29
34
39
43
30
35
39
42
30
37
41
45
29
35
39
42
30
36
40
44
28
32
36
38
28
33
36
39

30
35
38
42
31
37
41
45
33
38
43
47
31
37
42
45
32
37
42
44
33
39
44
47
32
38
42
45
33
39
43
46
31
35
38
41
32
36
40
43

32
37
41
44
34
39
44
48
36
41
46
50
34
40
45
49
36
41
45
48
36
42
47
50
35
41
45
48
37
42
47
50
35
39
42
44
36
40
44
47

35
40
43
47
36
42
46
50
39
44
49
53
38
44
48
52
39
44
48
51
39
45
50
53
39
45
48
51
41
46
50
54
39
42
45
48
41
45
49
52

36
41
45
48
38
43
48
52
41
46
50
54
40
45
50
54
41
46
50
53
41
47
51
54
41
47
50
53
43
48
52
56
41
44
47
49
43
47
51
54

41
45
49
53
44
48
52
56
47
51
55
59
47
51
56
59
48
52
56
58
48
53
57
59
48
53
56
59
51
55
59
62
47
50
53
55
52
56
59
62

K5 3.2 7

Flow adjustment dampers

TOC

Dimensions and weight


Dimensions

VFR

VFR
232
50

15

Flow adjustment
damper, variant VFR,
with rotary knob

VFR/.../E0*

232
50

Flow adjustment damper,


variant VFR, with actuator
(potentiometer)

85

VFR/.../M0*
232
50

Flow adjustment damper,


variant VFR, with actuator
(mechanical stops)

35

Dimensions [mm] and weight [kg]


VFR
Nominal size

VFR/.../E0* VFR/.../M0*
m
kg

80
100
125
140
150

K5 3.2 8

0.5
0.6
0.7
0.8
0.8

0.8
0.9
1.0
1.1
1.1

VFR VFR/.../E0* VFR/.../M0*


Nominal size

mm
0.7
0.8
0.9
1.0
1.0

79
99
124
139
149

kg
160
180
200
224
250

0.8
0.9
1.0
1.2
1.3

1.1
1.2
1.3
1.4
1.6

D
mm

1.0
1.1
1.2
1.4
1.5

159
179
199
223
249

05/2015 DE/en

Flow adjustment dampers

TOC

Installation details
Space requirement
for commissioning
and maintenance

VFR

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required
Attachments
Without actuator
With actuator E0*
With actuator M0*

05/2015 DE/en

mm
200
200
200

200
200
200

200
300
230

K5 3.2 9

Flow adjustment dampers

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular flow adjustment dampers for the simple


balancing of volume flow rates in air conditioning
systems, for supply air and extract air,
available in 10 nominal sizes.
Suitable for duct pressures up to 1000 Pa.
Ready-to-install unit consists of the casing
with damper blade and rotary knob for the
stepless adjustment of volume flow rates.
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180.
Casing air leakage to EN 1751, class C.

VFR
Technical data
Nominal sizes: 80 to 250 mm
Volume flow rate range:
9 to 615 l/s or 32 to 2215 m/h
Minimum differential pressure: 20 Pa
Maximum differential pressure: 1000 Pa
Sizing data
[m/h]
pst[Pa]
LPA air-regenerated noise[dB(A)]

Special features
Diagram with setting values
on each flow adjustment damper
Simple retrofit of an actuator is possible
Materials and surfaces
Rotary knob, damper blade and bearings
made of plastic, flame retardant (V-0) to UL 94

Galvanised sheet steel construction (P1)


Casing made of galvanised sheet steel
Stainless steel construction (A2)
Casing made of stainless steel 1.4301
Construction
Galvanised sheet steel
A2: Stainless steel

Order options

Type
VFR
Flow adjustment damper
Material
No entry: galvanised sheet steel
A2
Stainless steel
Nominal size [mm]
80
100
125
140
150
160
180
200
224
250

K5 3.2 10

Actuator
No entry: manual operation
potentiometer
E01 24 V AC/DC, 3-point
E02 230 V AC, 3-point
E03 24 V AC/DC, modulating 0 10 V DC
Mechanical stops
M01 24 V AC/DC, 3-point
M02 230 V AC, 3-point

05/2015 DE/en

Open/Close actuators

X X Open/Close

TOC

3.3

actuatorstestregistrierung

Actuators
for shut-off dampers

Type Open/Close actuators

For the opening and closing of shut-off dampers


in air conditioning systems
Actuators for Type AK or AKK shut-off dampers
Change of the damper blade position for two different operating situations
Supply voltage 24 V AC/DC or 230 V AC or operating pressure 1 bar
Control input signal: 1-wire control or 2-wire control (3-point)
Mechanical stops
Retrofit possible

05/2015 DE/en

K5 3.3 1

Actuators for shut-off dampers

TOC

General information

Open/Close actuators
Page

Type
Open/Close actuators

Description

General information
Special information B3*
Special information B4*
Special information B*2
Special information BP0
Special information BP2
Special information BR0
Special information BR2
Special information TN0

3.3 2
3.3 4
3.3 5
3.3 6
3.3 7
3.3 8
3.3 9
3.3 10
3.3 11

Basic information and nomenclature

3.4 1

Application
Actuators for opening and closing
Opening and closing of Type AK or AKK
shut-off dampers
Parts and characteristics
Mechanical stops for setting
the damper blade positions
Electric or pneumatic operation
Overload protection
Control input signal: 1-wire control,
2-wire control (3-point) or pneumatic control
Optional spring return actuator
for damper blade safety function
Optional auxiliary switch for capturing
the end positions

Any attachments
must be defined
with the order code
of the shut-off damper.

K5 3.3 2

Actuators for Type AK or AKK shut-off dampers


Order code detail

Actuator
Part number

B30
B32
B40
B42

M466DU5
M466DU5
M466DU4
M466DU4

BP0

M466ET0

BP2

M466ET2

BR0

M466ET1

BR2

M466ET3

TN0

B555DC2

Type
LM24A
LM24A
LM230A
LM230A
NF24A spring
return actuator
NF24A-S2 spring
return actuator
NFA spring return
actuator
NFA-S2 spring
return actuator
Pneumatic control

Auxiliary switch
Supply voltage

Part number

Type

24 V
24 V
230 V
230 V

M536AI3

M536AI3

S2A

S2A

24 V

24 V
24 240 V AC
24 125 V DC
24 240 V AC
24 125 V DC
0.2 1 bar

integrated

integrated

05/2015 DE/en

Actuators for shut-off dampers

TOC

General information

Open/Close actuators

Function

Functional description
The actuator opens or closes the damper blade.
Minimum and maximum positions can be set
using mechanical stops. 1-wire control or 2-wire
control (3-point) can be used. 1-wire control
is actually an open/close control. A spring return
actuator moves the damper blade to the safe
position in case of a power failure.

Define the safe position with the order code:


NC (normally closed) or NO (normally open).
The spring return actuator is factory set according
to the safe position. The normal position of the
damper blade is only achieved with 1-wire control
(control voltage).

Applies to attachments
with order codes B3*, B4*

1-wire control

2-wire control (3-point)

S2

S1

1
N

2
L
~
+

1
N

3
L
~
+

Switch functions
S1 open: Direction of rotation 1
S1 closed: Direction of rotation 2

2
L
~
+

S1

3
L
~
+

Switch functions
S1 open
S2 open: Actuator has stopped (any position)
S2 closed: Direction of rotation 1
S1 closed
S2 open: Direction of rotation 2
S2 closed: Direction of rotation 2

Effect of actuator action


in case of factory setting
Direction of rotation

Order code detail

B30, B32
B40, B42
Applies to attachments
with order codes BP*
and BR*

CLOSED
CLOSED

2
OPEN
OPEN

1-wire control
(control input signal for spring return actuator)

S1

1
N

2
L
~
+

Switch functions
S1 open: Safe position (spring return)
S1 closed: Normal operation
(spring-winding mechanism)
Damper blade position (OPEN or CLOSED),
depending on defined safe position

05/2015 DE/en

K5 3.3 3

Actuators for shut-off dampers

TOC

Special information B3*


Description

/ B30
/ B32
Order code detail

Open/Close actuators

Application
Actuator LM24A
Opening and closing of Type AK or AKK
shut-off dampers

Installation and commissioning


Change the direction of rotation
if necessary, using the switch

Variants
B32: with auxiliary switch
for capturing the end positions
Parts and characteristics
Supply voltage 24 V AC/DC
1-wire control or 2-wire control (3-point)
Mechanical stops for setting
the volume flow rate setpoints
Switch for setting the direction of rotation
Release button to allow for manual operation

Technical data

Actuators LM24A and LM24A-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
2 VA max.
1 W max.
5 Nm
150 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
0.5 kg

Actuator LM24A

Wiring

Connecting cable core identification


BK RD WH

For control options


see General information
function

2
~
+

3
~
+

LM24A

1 , :
2 ~, +:
3 ~, +:

Ground, neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

LM24A and LM24A-F

05/2015 DE/en

K5 3.3 4

Actuators for shut-off dampers

TOC

Special information B4*


Description

/ B40
/ B42
Order code detail

Open/Close actuators

Application
Actuator LM230A
Opening and closing of Type AK or AKK
shut-off dampers

Installation and commissioning


Change the direction of rotation
if necessary, using the switch

Variants
B42: with auxiliary switch
for capturing the end positions
Parts and characteristics
Supply voltage 100 240 V AC
1-wire control or 2-wire control (3-point)
Mechanical stops for setting the volume
flow rate setpoints
Switch for setting the direction of rotation
Release button to allow for manual operation

Technical data

Actuator LM230A
Supply voltage
Power rating
Torque
Running time for 90
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

85 265 V AC, 50/60 Hz


4 VA max.
5 Nm
150 s
1-wire control or 2-wire control (3-point)
3 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.5 kg

Actuator LM230A

Wiring

Connecting cable core identification


BU BN WH

For control options


see General information
function

1
N

2
L

3
L

LM230A

1 N:
2 L:
3 L:

K5 3.3 5

Neutral
Control voltage for direction of rotation 1
Control voltage for direction of rotation 2

05/2015 DE/en

Actuators for shut-off dampers

TOC

Special information B*2


Description

/ B52
/ B62
Order code detail

Open/Close actuators

Application
Auxiliary switch S2A for capturing damper
blade end positions (end positions reached
through actuator operation)
Volt-free contacts for signalling
or activating switch functions
Two integral switches, e.g. for damper blade
OPEN and damper blade CLOSED
Potentiometer for setting any switch point

Auxiliary switch S2A

Auxiliary switch S2A

Type of contact
Max. switching voltage (AC)
Max. switching current (AC)
Max. switching voltage (DC)
Max. switching current (DC)
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight
1)

Wiring

2 changeover contacts1)
250 V AC
3 A (resistive load); 0.5 A (inductive load)
110 V DC
0.5 A (resistive load); 0.2 A (inductive load)
6 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
0.250 kg

If both auxiliary switches are used the switching voltages must be the same

Connecting cable core identification


VT RD WH OG PK GY

S1 S2 S3 S4 S5 S6
S2A

S1:
Common contact
S2:
Mechanical stop 1 < x
S3:
Mechanical stop 1 > x
S4:
Common contact
S5:
Mechanical stop 2 < x
S6:
Mechanical stop 2 > x
x: 0 100 % Switching point (adjustable)

05/2015 DE/en

K5 3.3 6

Actuators for shut-off dampers

TOC

Special information BP0


Description

/ BP0 / NO

Open/Close actuators

Application
Pneumatic actuator NF24A for the opening and
closing of Type AK or AKK shut-off dampers
Opening and closing with safety function
The safety function of the shut-off damper
is defined with the order code

Order code detail

Technical data

Spring return actuator NF24A


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Motor running time for 90
Spring return time
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

Parts and characteristics


Supply voltage 24 V AC/DC
Control input signal: Supply voltage on/off
Mechanical stops for setting the volume
flow rate setpoints
Manual operation using crank handle
and position lock

24 V AC 20 %, 50/60 Hz
24 V DC 10 %, +20 %
8.5 VA max.
6 W max.
10 Nm
< 75 s
20 s (for < 20 C up to 60 s)
Supply voltage on/off
2 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
1.8 kg

Spring return actuator


NF24A

Wiring

Connecting cable core identification


BK RD

For control options


see General information
function

~
+

NF24A

1 , :
2 ~, +:

K5 3.3 7

Ground, neutral
Control voltage for direction of rotation 1

05/2015 DE/en

Actuators for shut-off dampers

TOC

Special information BP2


Description

/ BP2 / NO
Order code detail

Technical data

Spring return actuator


NF24A-S2

Wiring

Open/Close actuators

Application
Spring return actuator NF24A-S2 with integral
auxiliary switches for the opening and closing
of Type AK or AKK shut-off dampers
Opening and closing of shut-off dampers
with safety function
The safety function of the shut-off damper
is defined with the order code

Parts and characteristics


Supply voltage 24 V AC/DC
Control input signal: Supply voltage on/off
Mechanical stops for setting the volume
flow rate setpoints
Manual operation using crank handle
and position lock
One fixed and one adjustable auxiliary
switch for signalling rotation angles
of 10 % and 10 90 %.
Fixed auxiliary switch, switching point 10 %
Adjustable auxiliary switch,
switching point 10 90 %

Spring return actuator NF24A-S2


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Motor running time for 90
Spring return time
Control input signal
Auxiliary switch: type of contact
Max. switching voltage (AC)
Max. switching current (AC)
Max. switching voltage (DC)
Max. switching current (DC)
Connecting cable actuator
Connecting cable auxiliary switch
IEC protection class
Protection level
EC conformity
Operating temperature
Weight
1)

24 V AC 20 %, 50/60 Hz
24 V DC 10 %, +20 %
8.5 VA max.
6 W max.
10 Nm
< 75 s
20 s (for < 20 C up to 60 s)
Supply voltage on/off
2 changeover contacts1)
250 V AC
3 A (resistive load); 0.5 A (inductive load)
110 V DC
0.5 A (resistive load); 0.2 A (inductive load)
2 0.75 mm, 1 m long
6 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
2.0 kg

If both auxiliary switches are used the switching voltages must be the same

Connecting cable core identification


BK RD VT RD WH OG PK GY

For control options


see General information
function

2
~
+

S1 S2 S3 S4 S5 S6

NF24A-S2

1 , :
Ground, neutral
2 ~, +:
Control voltage for direction of rotation 1
S1:
Common contact
S2:
Mechanical stop 1 < x
S3:
Mechanical stop 1 > x
S4:
Common contact
S5:
Mechanical stop 2 < y
S6:
Mechanical stop 2 > y
x: 10 % Switching point 1
y: 10 ... 90 % Switching point 2 (adjustable)

05/2015 DE/en

K5 3.3 8

Actuators for shut-off dampers

TOC

Special information BR0


Description

/ BR0 / NO

Open/Close actuators

Application
Pneumatic actuator NFA for the opening and
closing of Type AK or AKK shut-off dampers
Opening and closing with safety function
The safety function of the shut-off damper
is defined with the order code

Order code detail

Technical data

Spring return actuator NFA


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Motor running time for 90
Spring return time
Control input signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

Parts and characteristics


Supply voltage 24 240 V AC/24 125 V DC
Control input signal: Supply voltage on/off
Mechanical stops for setting the volume
flow rate setpoints
Manual operation using crank handle
and position lock

19.2 264 V AC, 50/60 Hz


21.6 137 V DC
9.5 VA max.
6 W max.
10 Nm
< 75 s
20 s (for < 20 C up to 60 s)
Supply voltage on/off
2 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
2.0 kg

Spring return actuator


NFA

Wiring
For control options
see General information
function

Connecting cable core identification


BU BN
1
N

2
L
~
+
NFA

1 N , : Ground, neutral
2 L ~, +: Control voltage for direction of rotation 1

K5 3.3 9

05/2015 DE/en

Actuators for shut-off dampers

TOC

Special information BR2

Open/Close actuators

Order code detail

Application
Spring return actuator NFA-S2 with integral
auxiliary switches for the opening and closing
of Type AK or AKK shut-off dampers
Opening and closing with safety function
The safety function of the shut-off damper
is defined with the order code

Technical data

Spring return actuator NFA-S2

Description

/ BR2 / NO

Spring return actuator


NFA-S2

Wiring
For control options see
General information
function

Supply voltage (AC)


Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Motor running time for 90
Spring return time
Control input signal
Auxiliary switch: type of contact
Max. switching voltage (AC)
Max. switching current (AC)
Max. switching voltage (DC)
Max. switching current (DC)
Connecting cable actuator
Connecting cable auxiliary switch
IEC protection class
Protection level
EC conformity
Operating temperature
Weight
1)

Parts and characteristics


Supply voltage 24 240 V AC or 24 125 V DC
Control input signal: Supply voltage on/off
Mechanical stops for setting
the volume flow rates
Manual operation using
crank handle and position lock
Two auxiliary switches with volt-free contacts
for signalling or activating switch functions
Fixed auxiliary switch, switching point 10 %
Adjustable auxiliary switch,
switching point 10 90 %

19.2 264 V AC, 50/60 Hz


21.6 137 V DC
9.5 VA max.
6 W max.
10 Nm
< 75 s
20 s (for < 20 C up to 60 s)
Supply voltage on/off
2 changeover contacts1)
250 V AC
3 A (resistive load); 0.5 A (inductive load)
110 V DC
0.5 A (resistive load); 0.2 A (inductive load)
2 0.75 mm, 1 m long
6 0.75 mm, 1 m long
II (protective insulation)
IP 54
EMC to 2004/108/EU, low voltage to 2006/95/EU
30 to 50 C
2.2 kg

If both auxiliary switches are used the switching voltages must be the same

Connecting cable core identification


BU BN VT RD WH OG PK GY
1

2
~
+

S1 S2 S3 S4 S5 S6

NFA-S2

1 N, , : Ground, neutral
2 L1,~, +: Control voltage for direction of rotation 1
S1:
Common contact
S2:
Mechanical stop 1 < x
S3:
Mechanical stop 1 > x
S4:
Common contact
S5:
Mechanical stop 2 < y
S6:
Mechanical stop 2 > y
x: 10 % Switching point 1
y: 10 ... 90 % Switching point 2 (adjustable)

05/2015 DE/en

K5 3.3 10

Actuators for shut-off dampers

Special information TN0


Description

/ TN0 / NO
Order code detail

TOC

Open/Close actuators

Application
Pneumatic actuator B555DC2
for the opening and closing of Type AK or AKK
shut-off dampers
Opening and closing with safety function
The safety function of the shut-off damper
is defined with the order code
Parts and characteristics
Control pressure 0.2 1 bar
Control input signal: pneumatic,
control pressure on/off
Piston rod with 85 mm stroke
When the control pressure increases,
the piston rod extends; it retracts by means
of the spring force

Technical data

Pneumatic actuator B555DC2


Control pressure
Maximum pressure
Compressed air
Weight

0.2 1.0 bar


2.0 bar
Compressed air for instruments, free of oil, water and dust
0.840 kg

Pneumatic actuator
B555DC2

K5 3.3 11

05/2015 DE/en

Modulating actuators

X X Modulating

TOC

3.3

actuatorstestregistrierung

Actuators
for shut-off dampers

Type Modulating actuators

For moving the damper blades of shut-off dampers


to any position
Modulating actuators for Type AK or AKK shut-off dampers
Various damper blade positions
Supply voltage 24 V AC/DC
Control input signal: Voltage signal 2 10 V
Mechanical stops
Retrofit possible

05/2015 DE/en

K5 3.3 12

Actuators for shut-off dampers

TOC

General information

Modulating actuators
Page

Type
Modulating actuators

Description

General information
Special information B20

2.2 1
2.2 15

Basic information and nomenclature

2.3 1

Application
Actuators for variable adjustment
For moving the damper blades
of Type AK and AKK shut-off dampers
to any position
Parts and characteristics
Mechanical stops for limiting
the damper blade positions
Supply voltage 24 V AC/DC
Overload protection
Setpoint value signal 2 10 V DC
Release button to allow for manual operation

Actuator LM24A-SR
Any attachments
must be defined
with the order code
of the shut-off damper.

K5 3.3 13

Actuators for the variable adjustment of shut-off dampers


Order code detail
B20

Actuator
Part number
M466DT6 with M536AJ4

Supply voltage

Type
LM24A-SR

24 V

05/2015 DE/en

Actuators for shut-off dampers

TOC

General information
Function

Modulating actuators

Functional description
The actuator moves the blade of a shut-off
damper to any position between the OPEN
and CLOSED positions.
The control input signal is a voltage signal.
Variable control initiated by a voltage signal
Sollwertgeber

24 V

U Voltage signal 0 10 V DC or 2 10 V DC

1-wire control for modulating actuators

2-wire control (3-point)


for modulating actuators

S2

S1

2
~
+

3
Y

5
U

Switch functions
S1 open: Direction of rotation 1
S1 closed: Direction of rotation 2

2
~
+

S1

3
Y

5
U

Switch functions
S1 open
S2 open: Actuator has stopped (any position)
S2 closed: Direction of rotation 1
S1 closed
S2 open: Direction of rotation 2
S2 closed: Direction of rotation 2

Effect of actuator action


in case of factory setting
Order code detail
B20

05/2015 DE/en

Direction of rotation
1
OPEN

2
CLOSED

K5 3.3 14

Actuators for shut-off dampers

TOC

Special information B20


Description

/ B20

Modulating actuators

Application
Actuator LM24A-SR
Stepless adjustment as well as opening
and closing of shut-off dampers

Order code detail

Technical data

Actuators LM24A-SR and LM24A-SR-F


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Torque
Running time for 90
Position feedback
Control signal
Connecting cable
IEC protection class
Protection level
EC conformity
Operating temperature
Weight

Parts and characteristics


Supply voltage 24 V AC/DC
Control input signal: Setpoint value signal
2 10 V DC, corresponds to the total rotation
range (90), working range is limited
by mechanical stops
Output: Position feedback 2 10 V
Mechanical stops
Direction of action can be reversed
Release button to allow for manual operation

24 V AC 20 %, 50/60 Hz
24 V DC 20 %
2 VA
1W
5 Nm
150 s
2 10 V DC, 1 mA
2 10 V DC, Ra > 100 k
4 0.75 mm, 1 m long
III (protective extra-low voltage)
IP 54
EMC according to 2004/108/EC
30 to 50 C
0.5 kg

Actuator LM24A-SR

Wiring

Connecting cable core identification


BK RD WH OG

For control options


see General information
function

2
~
+

3
Y

5
U

LM24A-SR

1 , :
2 ~, +:
3 Y:
5 U:

Ground, neutral
Supply voltage
Setpoint value signal
Position feedback

LM24A-SR and LM24A-SR-F

K5 3.3 15

05/2015 DE/en

TOC

3.4

X X Grundlagen

und Definitionentestregistrierung

Shut-off and restriction

Basic information
and nomenclature

Product selection
Principal dimensions
Nomenclature
Construction
Correction values for system attenuation
Measurements
Sizing and sizing example

05/2015 DE/en

K5 3.4 1

Shut-off and restriction

TOC

Basic information and nomenclature


Product selection

Type

Type of system
Supply air
Extract air
Duct connection
Circular
Rectangular
Volume flow rate range
Up to [m/h]
Up to [l/s]
Air quality
Filtered
Office extract air
Polluted
Contaminated
Shut-off
Manually
Electric/pneumatic actuator
Safe position
Restriction
Manually
Electric actuator
Special areas
Areas with explosive atmospheres

AK

AK-Ex

AKK

VFR

5435
1510

5435
1510

5435
1510

1745
485

Possible
Possible under certain conditions: Robust unit variant and/or specific actuator
Not possible

K5 3.4 2

05/2015 DE/en

Shut-off and restriction

TOC

Basic information and nomenclature


Principal dimensions

D [mm]
Shut-off and flow adjustment dampers
made of stainless steel: Outside diameter
of the connecting spigot
Shut-off dampers made of plastic:
Inside diameter of the connecting spigot
D [mm]
Pitch circle diameter of flanges

L [mm]
Length of casing or acoustic cladding
n[]
Number of flange screw holes
T [mm]
Flange thickness

D [mm]
Outside diameter of flanges
D [mm]
Inside diameter of the screw holes of flanges

Nomenclature

L [mm]
Length of unit including connecting spigot

m [kg]
Unit weight including
the minimum required attachments

LPA [dB(A)]
A-weighted sound pressure level
of air-regenerated noise of the shut-off
or flow adjustment damper,
system attenuation taken into account
[m/h] and [l/s]
Volume flow rate
pst [%]
Static differential pressure
All sound pressure levels are based on 20 Pa.
Definition of noise

Static differential pressure

LPA

st

Air-regenerated noise
Case-radiated noise

Constructions

Galvanised sheet steel


Casing made of galvanised sheet steel
Parts in contact with the airflow as described
for the product type
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

Stainless steel (A2)


Casing made of stainless steel 1.4201
Parts in contact with the airflow
are powder-coated or made of stainless steel
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

Powder-coated surface (P1)


Casing made of galvanised sheet steel,
powder-coated RAL 7001, silver grey
Parts in contact with the airflow
are powder-coated or made of plastic
Due to production, some parts that come
into contact with the airflow may be stainless
steel or aluminium, powder-coated
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

05/2015 DE/en

K5 3.4 3

Shut-off and restriction

TOC

Basic information and nomenclature

The quick sizing tables


show the sound pressure
levels that can be
expected in a room both
for the air-regenerated
noise and for the caseradiated noise. The sound
pressure level in a room
results from the sound
power level of the
products for a given
volume flow rate and
differential pressure
and the attenuation
and insulation on site.
Generally accepted
attenuation and insulation
values have been taken
into account.
The distribution of air
across the ductwork,
changes of direction,
end reflection, and room
attenuation all affect the
sound pressure level of
the air-regenerated noise.
Ceiling insulation and
room attenuation
influence the sound
pressure level of the caseradiated noise.

Reducing the sound pressure level of the air-regenerated noise

Correction values
for acoustic quick sizing

Octave correction for the distribution in the ducting,


used to calculate the air-regenerated noise

The correction values


for the distribution in the
ducting are based on the
number of diffusers
assigned to any one shutoff damper or flow
adjustment damper.
If there is just one diffuser
(assumption: 140 l/s or
500 m/h), no correction
is necessary.
One change of direction,
e.g. at the horizontal
connection of the diffuser
plenum box, has been
taken into consideration
for the system attenuation
values. Vertical
connection of the plenum
box does not result in
a system attenuation.
Additional bends result
in lower sound pressure
levels.

End reflection
Ceiling insulation

VAV terminal unit


Distribution in the ducting
Change of direction

in [m/h]

500

1000

1500

2000

2500

3000

4000

[l/s]

140

280

420

550

700

840

1100

[dB]

5000
1400
9

10

System attenuation per octave to VDI 2081 for the calculation of the air-regenerated noise
63

125

250

500

Centre frequency [Hz]

1000

2000

4000

8000

L
dB

Change of direction

Mndungsreflexion

10

Room attenuation

The calculation is based on the end reflection for nominal size 250

Octave correction for the calculation of case-radiated noise


63

125

250

500

Centre frequency [Hz]

1000

2000

4000

8000

L
dB

K5 3.4 4

Ceiling insulation

Room attenuation

05/2015 DE/en

Shut-off and restriction

TOC

Basic information and nomenclature


Measurements

The acoustic data


for the air-regenerated
noise and caseradiated noise are
determined according
to EN ISO 5135.
All measurements
are carried out in a
reverberation chamber
to EN ISO 3741.

Measuring the air-regenerated noise

st

LP

3
Reverberation chamber
VAV terminal unit
Microphone

Fan
Sound attenuator

The sound pressure levels for air-regenerated noise LPA given by us result from measurements
in a reverberation chamber. The sound pressure LP is measured for the entire frequency range.
The evaluation of the measurements, including system attenuation and A-weighting,
results in the sound pressure level LPA.
Measuring the case-radiated noise

Reverberation chamber
VAV terminal unit
Microphone

st

LP

Fan
Sound attenuator

The sound pressure levels for case-radiated noise LPA2 given by us result from measurements
in a reverberation chamber. The sound pressure LP is measured for the entire frequency range.
The evaluation of the measurements, including system attenuation and A-weighting,
results in the sound pressure level LPA2.

05/2015 DE/en

K5 3.4 5

Shut-off and restriction

TOC

Basic information and nomenclature


Sizing with
the help of this catalogue

This catalogue provides convenient quick sizing


tables for shut-off and flow adjustment dampers.
The sound pressure levels for air-regenerated
noise are provided for all nominal sizes.
The quick sizing tables are based
on normally accepted attenuation levels.
Sizing data for other volume flow rates
and differential pressures can be determined
quickly and precisely using the Easy Product
Finder design programme.

Sizing example

Given data
max = 280 l/s (1010 m3/h)
pst = 150 Pa
Required sound pressure level
in the room 30 dB(A)

Quick sizing
AK/100/00H
Air-regenerated noise LPA = 23 dB(A)

Easy Product Finder

The Easy Product Finder


allows you to size
products using your
project-specific data.
You will find
the Easy Product Finder
on our website.

05/2015 DE/en

K5 3.4 7

Volume flow rate measurement

TOC

Table of contents
4

Volume flow rate measurement


Volume flow rate measuring units are used for the recording of volume flow rates.

4.1 Volume flow rate measuring units

Type

Page

For the measurement of volume flow


rates in ducts

VMR

4.1 1

For the measurement of volume flow


rates in ducts

VME

4.1 15

For the measurement of volume flow


rates in ducts with contaminated air

VMRK

4.1 27

For the measurement of volume flow


rates in ducts with contaminated air from VMLK
laboratories

4.1 40

Circular

Rectangular

Acoustically optimised

4.2 Differential pressure transducers for volume flow rate measuring units

For the dynamic measurement of


effective and differential pressures

Dynamic
differential
pressure
transducers

4.2 1

For the static effective and differential


pressure measurement

Static differential
pressure
transducers

4.2 5

4.3 Basic information and nomenclature


Volume flow rate measurement

K5 4.0 1

4.3 1

05/2015 DE/en

VMR

TOC

4.1

X X VMRtestregistrierung

Volume flow rate


measuring units

Type VMR

Variant with circular spigot

Static differential
pressure transducer

For the measurement of volume flow rates in ducts


Circular volume flow rate measuring units
for the recording or monitoring of volume flow rates
Manual volume flow rate measuring
Permanent volume flow rate measuring
Recording of measured values for other controllers
or for the LABCONTROL air management system
Pressure transducer for the automatic recording of measured values,
factory assembled and complete with wiring and tubing

Dynamic differential
pressure transducer

Optional equipment and accessories


With flanges on both ends
ET

HY

SCH GET
NI
E

ST

Casing air leakage to EN 15727, class C

VD

Lip seal
Dynamic or static differential pressure transducers

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 4.1 1

Volume flow rate measuring units

TOC

General information

VMR

Type
VMR

Variants

Page
General information
Order code
Aerodynamic data
Dimensions and weight VMR
Dimensions and weight VMR-FL
Installation details
Specification text

4.1 2
4.1 4
4.1 7
4.1 8
4.1 9
4.1 10
4.1 11

Basic information and nomenclature

4.3 1

Volume flow rate measuring unit, variant VMR

Volume flow rate measuring unit, variant VMR,


with differential pressure transducer

Application
Circular volume flow rate measuring units
Type VMR for the manual recording
or automatic measuring of volume flow rates
Simplified commissioning,
approval and maintenance
Suitable for permanent installation
because of low differential pressure
Optional static differential pressure
transducer for systems with polluted air

Parts and characteristics


Ready-to-commission unit which consists
of the mechanical parts and an optional
pressure transducer
Averaging differential pressure sensor
for volume flow rate measurement
Optional factory-assembled pressure
transducers complete with wiring and tubing
High measurement accuracy
(even with upstream bend R = 1D).

Variants
VMR: Volume flow rate measuring unit
VMR-FL: Volume flow rate measuring unit
with flanges on both ends

Construction features
Circular casing
Spigot suitable for circular ducts
to EN 1506 or EN 13180
Spigot with groove for lip seal
Connecting nipple for tubes
with 6 mm inside diameter
VMR-FL: Circular flanges to EN 12220

Product examples

4
Description
For detailed information
on pressure transducers
see chapter K5 4.2.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel
Nominal sizes
100, 125, 160, 200, 250, 315, 400
Attachments
Dynamic differential pressure transducer
Static differential pressure transducer
LABCONTROL: Components
for air management systems
Accessories
Lip seals on both ends (factory fitted)
Matching flanges for both ends
Special characteristics
Measurement accuracy 5 %
Low differential pressure
of only about 10 26 %
of the measured effective pressure

K5 4.1 2

Materials and surfaces


Galvanised sheet steel construction
Casing made of galvanised sheet steel
Aluminium sensor tubes
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Sensor tubes made of aluminium,
powder-coated
Stainless steel construction (A2)
Casing, damper blade
and shaft made of stainless steel 1.4301
Sensor tubes made of aluminium,
powder-coated

05/2015 DE/en

Volume flow rate measuring units

TOC

General information

VMR

Installation and commissioning


Any installation orientation (except units
with static differential pressure transducer)
Note the upstream conditions
Static differential pressure transducer:
Check zero point and correct, if necessary
Standards and guidelines
Hygiene conforms to VDI 6022
Casing air leakage to EN 15727, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Attachments: VARYCONTROL differential pressure transducer for Type VMR


Order code detail
Universal

Differential pressure transducer

Measurement principle

Universal controller with integral differential pressure transducer


TROX/Belimo
Universal controller with separate differential pressure transducer
TROX/Belimo

B10
BB0

Dynamic
Static

Attachments: LABCONTROL differential pressure transducer for Type VMR


Order code detail
EASYLAB

ELAB

TM0

Technical data

Differential pressure transducer


EASYLAB TCU3 (recording of measured values for EASYLAB system)
TCU-LON-II
Electronic controller TCU-LON-II with LonWorks interface

Nominal sizes

Static
Static

100 400 mm

Volume flow rate range

10 1680 l/s or 36 6048 m/h

Measurement accuracy

5 % of the measured value

Effective pressure range


Measuring unit differential pressure (pressure loss)
Operating temperature

05/2015 DE/en

Measurement principle

approx. 5 250 Pa
10 26 % of the measured effective pressure
10 50 C

K5 4.1 3

Volume flow rate measuring units

TOC

Order code
Order code

VMR

VMR

VARYCONTROL

VMR P1 FL / 160 / G2 / B10 / E0

Type
VMR Circular volume flow rate measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
Flanges on both ends
FL
Nominal size [mm]
100
125
160
200
250
315
400

4
Order example

VMR/160/D2/B10/E0

VARYCONTROL

Nominal size
Accessories
Differential pressure transducer
Actual value signal

K5 4.1 4

Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments
(differential pressure transducer)
No entry: none
B10 Dynamic differential pressure transducer
BB0 Static differential pressure transducer
Signal voltage range
For the actual value signal
Only for attachment B10
E0
0 10 V
E2
2 10 V

160 mm
Lip seals on both ends
Dynamic
0 10 V

05/2015 DE/en

Volume flow rate measuring units

TOC

Order code
Order code
LABCONTROL
EASYLAB

VMR

VMR with EASYLAB for the recording of measured values

VMR P1 FL / 160 / G2 / ELAB / EC E0 / ULZ

Type
VMR Circular volume flow rate measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated, silver grey (RAL 7001)
A2
Stainless steel
Flange
No entry: none
Flanges on both ends
FL
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB EASYLAB TCU3

05/2015 DE/en

Equipment function
SC
Supply air recording
EC
Extract air recording
Voltage range for the actual value signal
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
EM-TRF-USV for 230 V AC, provides
U
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

K5 4.1 5

Volume flow rate measuring units

TOC

Order code
Order code
LABCONTROL
EASYLAB

VMR

VMR with EASYLAB for fume cupboard control with external signalling (frequency converter)

VMR P1 FL / 160 / G2 / ELAB / FH VS / ULZS / ...

Type
VMR Circular volume flow rate measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated, silver grey (RAL 7001)
A2
Stainless steel
Flange
No entry: none
Flanges on both ends
FL
Nominal size [mm]
100
125
160
200
250
315
400

Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB EASYLAB controller TCU3
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

K5 4.1 6

Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket for the connection
of lighting and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-SEG-** 2-character display
BE-LCD-01 40-character display

05/2015 DE/en

Volume flow rate measuring units

TOC

Aerodynamic data
Volume flow rate ranges

Nominal size
100
125
160
200
250
315
400

l/s

Nenn

95
150
250
405
615
1030
1680

VMR
m/h

min

l/s

342
540
900
1458
2214
3708
6048

10
15
25
40
60
105
170

C-Wert
m/h
36
54
90
144
216
378
612

l/s

pst

m/h

6.1
9.7
15.9
25.5
39.0
65.0
106.0

22
35
57
92
140
234
382

%
26
24
22
19
17
15
10

5
5
5
5
5
5
5

K value for air density 1.2 kg/m, pst in relation to the measured effective pressure

Volume flow rate


calculation

Calculation conditions
The volume flow rate is calculated
based on the measured effective pressure
The effective pressure is measured using
an electronic manometer
or an inclined tube manometer
Air density = 1.2 kg/m

Volume flow rate calculation


for air density 1.2 kg/m
= C

Volume flow rate calculation


for other air densities
= C

Calculation example

Given data
VMR/160
pw = 100 Pa
(manometer reading of effective pressure)
Volume flow rate [m/h]
Unit data
K value from table: K = 57 m/h (15.9 l/s)

05/2015 DE/en

1.2

Calculation procedure
= 15.9 100
= 159 l/s

K5 4.1 7

Volume flow rate measuring units

TOC

Dimensions and weight VMR


Description

VMR

Volume flow rate measuring unit


Spigot to make connections to the ducting

Volume flow rate


measuring unit,
variant VMR
Dimensions

VMR
400
50

50

Weight without attachments

Dimensions [mm] and weight [kg]


VMR
Nominal size
100
125
160
200
250
315
400

K5 4.1 8

mm

kg
99
124
159
199
249
314
399

0.8
1.0
1.4
1.7
2.1
2.7
3.4

05/2015 DE/en

Volume flow rate measuring units

TOC

Dimensions and weight VMR-FL


Description

VMR

Volume flow rate measuring unit


With flanges on both ends to make detachable
connections to the ducting

Volume flow rate


measuring unit,
variant VMR/.../BB0
Dimensions

VMR-FL

380

4
n 9,5
4

Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

05/2015 DE/en

D2

D1
mm

99
124
159
199
249
314
399

132
157
192
233
283
352
438

n
152
177
212
253
303
378
464

4
4
6
6
6
8
8

mm

kg
4
4
4
4
4
4
4

1.2
1.5
2.1
2.7
3.3
4.5
5.7

K5 4.1 9

Volume flow rate measuring units

TOC

Installation details

D
p

5D

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the volume flow rate measuring unit
has only a negligible effect on the volume flow
rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the measuring unit. If there is no straight upstream
section at all, the actual value signal may
not be stable, even with a perforated plate.

Access to attachments

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

150

Space requirement
for commissioning
and maintenance

Junction

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions or a
narrowing or widening of
the duct cause turbulence
that may affect
measurement. Duct
connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

VMR

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)
Space required
Attachments

Without attachments
200
VARYCONTROL
Universal controller
250
LABCONTROL
EASYLAB
350

K5 4.1 10

mm
200

200

200

250

350

400

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

VMR

Circular volume flow rate measuring unit


for the measurement of volume flow rates in air
conditioning systems, available in 7 nominal sizes.
For the manual volume flow rate measuring
or for the permanent monitoring
of the actual value signal.
Ready-to-commission unit which consists
of the casing with an averaging differential
pressure sensor.
Differential pressure sensor with 3 mm measuring
holes, thus resistant to dust and pollution.
Both ends spigot with groove for lip seal, suitable
for connecting ducts to EN 1506 or EN 13180.
Casing air leakage to EN 1751, class C.

Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
A2: Stainless steel

Special characteristics
Measurement accuracy 5 %
Low differential pressure
of only about 10 26 %
of the measured effective pressure

Attachments
Volume flow rate measurement with static
differential pressure transducer emitting an actual
value signal for integration into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC or 2 10 V DC
TCU-LON-II: Integration with LonWorks
EASYLAB: Integration using either 0 10 V DC
signals or expansion modules
(LonWorks, BACnet MS/TP, Modbus RTU)

Materials and surfaces


Galvanised sheet steel construction
Casing made of galvanised sheet steel
Aluminium sensor tubes
Powder-coated construction (P1)
Casing made of galvanised
sheet steel, powder-coated
Sensor tubes made of aluminium,
powder-coated

Technical data
Nominal sizes: 100 to 400 mm
Volume flow rate range:
10 to 1680 l/s or 36 to 6048 m/h
Effective pressure range: approx. 5 250 Pa
Measuring unit differential pressure
(pressure loss):
10 26 % of the measured effective pressure
Operating temperature: 10 to 50 C

Sizing data
[m/h]

Stainless steel construction (A2)


Casing, damper blade and shaft
made of stainless steel 1.4301
Sensor tubes made of aluminium,
powder-coated

Order options
VARYCONTROL

Type
VMR
Circular volume flow rate measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
A2
Stainless steel
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
100
125
160
200
250
315
400

05/2015 DE/en

Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments
(differential pressure transducer)
No entry: none
B10 Dynamic differential
pressure transducer
BB0 Static differential pressure transducer
Signal voltage range
For the actual value signal
Only for attachment B10
E0
0 10 V
E2
2 10 V

K5 4.1 11

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
VMR
Circular volume flow rate measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated, silver grey (RAL 7001)
A2
Stainless steel
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends

Attachments (control component)


ELAB
EASYLAB TCU3

K5 4.1 12

VMR
Equipment function
SC
Supply air recording
EC
Extract air recording
Voltage range for the actual value signal
E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC
Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
VMR
Circular volume flow rate measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated, silver grey (RAL 7001)
A2
Stainless steel
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
100
125
160
200
250
315
400
Accessories
No entry: none
D2
Lip seals on both ends
G2
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

05/2015 DE/en

VMR
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket
for the connection of lighting
and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-SEG-** 2-character display
BE-LCD-01 40-character display

K5 4.1 13

VME

TOC

4.1

X X VMEtestregistrierung

Volume flow rate measuring


units

Type VME

For the measurement of volume flow rates in ducts


Rectangular volume flow rate measuring units for the recording
or monitoring of volume flow rates
Manual volume flow rate measuring
Permanent volume flow rate measuring
Recording of measured values for other controllers
or for the LABCONTROL air management system
Suitable for airflow velocities of up to 10 m/s
Static differential
pressure transducer

Pressure transducer for the automatic recording of measured values,


factory assembled and complete with wiring and tubing
Casing air leakage to EN 15727, up to class C

Dynamic differential
pressure transducer

05/2015 DE/en

K5 4.1 15

Volume flow rate measuring units

TOC

General information

VME

Type
VME

Variants

Page
General information
Order code
Aerodynamic data
Dimensions and weight
Installation details
Specification text

4.1 16
4.1 18
4.1 20
4.1 22
4.1 24
4.1 25

Basic information and nomenclature

4.3 1

Volume flow rate measuring unit, variant VME

Volume flow rate measuring unit, variant VME,


with differential pressure transducer

Application
Rectangular volume flow rate measuring
units Type VME for the manual recording
or automatic measuring of volume flow rates
Simplified commissioning,
approval and maintenance
Suitable for permanent installation
because of low differential pressure

Parts and characteristics


Ready-to-commission unit which consists
of the mechanical parts and an optional
pressure transducer
Averaging differential pressure sensor
for volume flow rate measurement
Optional factory-assembled pressure
transducers complete with wiring and tubing
High measurement accuracy

Product examples

4
Description
For detailed information
on pressure transducers
see chapter K5 4.2.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Nominal sizes
39 nominal sizes
from 200 100 to 1000 1000
Attachments
Dynamic differential pressure transducer
Static differential pressure transducer
LABCONTROL: Components
for air management systems
Special features
Measurement accuracy 5 % even
with unfavourable upstream conditions
Effective pressure range: approx. 8 200 Pa
Low differential pressure
of only about 17 32 %
of the measured effective pressure

K5 4.1 16

Construction features
Rectangular casing
Flanges on both sides,
suitable for duct connection
Connecting nipple for tubes
with 6 mm inside diameter
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Aluminium sensor tubes
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated
Installation and commissioning
Any installation orientation (except units
with static differential pressure transducer)
Note the upstream and downstream conditions
Static differential pressure transducer:
Check zero point and correct, if necessary

05/2015 DE/en

Volume flow rate measuring units

TOC

General information

VME

Standards and guidelines


Casing air leakage to EN 15727,
class C (B + H) 400, class B)
Maintenance
Maintenance-free as construction
and materials are not subject to wear
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Attachments: VARYCONTROL differential pressure transducer for Type VME


Order code detail
Universal
B10
BB0

Differential pressure transducer

Measurement principle

Universal controller with integral differential pressure transducer


TROX/Belimo
Universal controller with separate differential pressure transducer
TROX/Belimo

Dynamic
Static

Attachments: LABCONTROL differential pressure transducer for Type VME


Order code detail
EASYLAB
ELAB
TCU-LON-II
TM0
Technical data

Differential pressure transducer

Measurement principle

EASYLAB TCU3 (recording of measured values for EASYLAB system)

Static

Electronic controller TCU-LON-II with LonWorks interface

Static

Nominal sizes
Volume flow rate range

45 10100 l/s or 162 36360 m/h

Measurement accuracy

5 % of the measured value

Effective pressure range


Measuring unit differential pressure (pressure loss)
Operating temperature

05/2015 DE/en

200 x 100 1000 x 1000

Approx. 8 200 Pa
17 32 % of the measured effective pressure
10 50 C

K5 4.1 17

Volume flow rate measuring units

TOC

Order code
Order code

VME

VME

VARYCONTROL

VME P1 / 600400 / B10 / E0

Type
VME Rectangular volume flow rate
measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH

Order example

K5 4.1 18

Attachments
(differential pressure transducer)
No entry: none
B10 Dynamic differential pressure transducer
BB0 Static differential pressure transducer
Signal voltage range
For the actual value signal
Only for attachment B10
E0
0 10 V
E2
2 10 V

VME/600400/B10/E0
Nominal size
Differential pressure transducer
Actual value signal

600 400 mm
Dynamic
0 10 V

05/2015 DE/en

Volume flow rate measuring units

TOC

Order code
Order code
LABCONTROL
EASYLAB

VME

VME with EASYLAB for the recording of measured values

VME P1 / 600400 / ELAB / EC E0 / ULZ / ...

Type
VME Rectangular volume flow rate
measuring unit

Equipment function
SC
Supply air recording
EC
Extract air recording

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey

Voltage range for the actual value signal


Voltage signal 0 10 V DC
E0
E2
Voltage signal 2 10 V DC

Nominal size [mm]


BH

Module expansions
Option 1: Power supply
No entry: 24 V AC
EM-TRF for 230 V AC
T
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Attachments
ELAB EASYLAB controller TCU3

L
B
M
I
R

05/2015 DE/en

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

K5 4.1 19

Volume flow rate measuring units

TOC

Aerodynamic data
Volume flow rate ranges

Nominal size
200 100
300 100
400 100
500 100
600 100
200 200
300 200
400 200
500 200
600 200
700 200
800 200
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600
800 800
1000 800
1000 1000

l/s

Nenn

215
320
425
535
650
415
620
825
1035
1250
1450
1650
920
1230
1535
1850
2150
2450
2770
3100
1630
2040
2450
2850
3250
3670
4100
2540
3050
3550
4050
4570
5100
3650
4850
6100
6500
8100
10100

VME
m/h
774
1152
1530
1926
2340
1494
2232
2970
3726
4500
5220
5940
3312
4428
5526
6660
7740
8820
9972
11160
5868
7344
8820
10260
11700
13212
14760
9144
10980
12780
14580
16452
18360
13140
17460
21960
23400
29160
36360

l/s

min

45
65
85
105
130
85
125
165
205
250
290
330
185
245
305
370
430
490
555
620
325
410
490
570
650
735
820
510
610
710
810
915
1020
730
970
1220
1300
1620
2020

C-Wert
m/h
162
234
306
378
468
306
450
594
738
900
1044
1188
666
882
1098
1332
1548
1764
1998
2232
1170
1476
1764
2052
2340
2646
2952
1836
2196
2556
2916
3294
3672
2628
3492
4392
4680
5832
7272

l/s
14.8
21.2
28.8
35.0
44.0
30.0
45.0
60.0
75.0
90.0
107.0
120.0
75.0
100.0
137.0
147.0
174.0
207.0
228.0
254.0
146.0
183.0
212.0
239.0
281.0
320.0
359.0
207.0
234.0
284.0
318.0
361.0
409.0
297.0
396.0
508.0
543.0
681.0
904.0

pst

m/h

53
76
104
126
158
108
162
216
270
324
385
432
270
360
493
529
626
745
821
914
526
659
763
860
1012
1152
1292
745
842
1022
1145
1300
1472
1069
1426
1829
1955
2452
3254

%
19
18
18
17
18
21
21
21
21
21
22
21
23
23
28
22
23
25
24
24
28
28
26
25
26
27
27
27
24
26
25
25
26
26
27
28
28
28
32

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5

K value for air density 1.2 kg/m, pst in relation to the measured effective pressure

K5 4.1 20

05/2015 DE/en

Volume flow rate measuring units

TOC

Aerodynamic data
Volume flow rate
calculation

Calculation conditions
The volume flow rate is calculated
based on the measured effective pressure
The effective pressure is measured using
an electronic manometer
or an inclined tube manometer
Air density = 1.2 kg/m

VME
Volume flow rate calculation
for air density 1.2 kg/m
= C

Volume flow rate calculation


for other air densities
= C

Calculation example

Given data
VME/400 200
pw = 100 Pa
(manometer reading of effective pressure)
Volume flow rate [m/h]
Unit data
K value from table: K = 216 m/h (60 l/s)

05/2015 DE/en

1.2

Calculation procedure
= 60.0 100
= 600 l/s

K5 4.1 21

Volume flow rate measuring units

TOC

Dimensions and weight


Dimensions

VME

VME
400

38

1320

B
B

Dimensions [mm] and weight [kg]


Nominal size
200 100
300 100
400 100
500 100
600 100
200 200
300 200
400 200
500 200
600 200
700 200
800 200
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300

K5 4.1 22

Nominal width Nominal height

B1

B2

H1

H2

mm
200
300
400
500
600
200
300
400
500
600
700
800
300
400
500
600
700
800
900
1000

100
100
100
100
100
200
200
200
200
200
200
200
300
300
300
300
300
300
300
300

234
334
434
534
634
234
334
434
534
634
734
834
334
434
534
634
734
834
934
1034

kg
276
376
476
576
676
276
376
476
576
676
776
876
376
476
576
676
776
876
976
1076

134
134
134
134
134
234
234
234
234
234
234
234
334
334
334
334
334
334
334
334

176
176
176
176
176
276
276
276
276
276
276
276
376
376
376
376
376
376
376
376

5.0
6.0
7.0
8.0
10.0
6.0
7.0
8.5
10.0
11.0
12.5
13.5
8.0
9.5
11.0
12.0
13.5
14.5
16.0
17.0

05/2015 DE/en

Volume flow rate measuring units

TOC

Dimensions and weight


Dimensions

VME

VME
400

38

1320

B
B

Dimensions [mm] and weight [kg]


Nominal size
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
500 500
600 500
700 500
800 500
900 500
1000 500
600 600
800 600
1000 600
800 800
1000 800
1000 1000

05/2015 DE/en

Nominal width Nominal height

B2

B1

H1

H2

mm
400
500
600
700
800
900
1000
500
600
700
800
900
1000
600
800
1000
800
1000
1000

400
400
400
400
400
400
400
500
500
500
500
500
500
600
600
600
800
800
1000

434
534
634
734
834
934
1034
534
634
734
834
934
1034
634
834
1034
834
1034
1034

kg
476
576
676
776
876
976
1076
576
676
776
876
976
1076
676
876
1076
876
1076
1076

434
434
434
434
434
434
434
534
534
534
534
534
534
634
634
634
834
834
1034

476
476
476
476
476
476
476
576
576
576
576
576
576
676
676
676
876
876
1076

10.5
11.5
13.0
14.5
15.5
17.0
18.0
14.0
16.0
17.5
19.5
23.0
20.5
17.0
20.0
23.0
22.0
25.0
27.0

K5 4.1 23

Volume flow rate measuring units

TOC

Installation details

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Junction, vertical

Bend, vertical

Upstream conditions

VME

2H

4H

A bend with a straight duct section of at least


2H upstream of the volume flow rate measuring
unit has only a negligible effect on the volume
flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
4H upstream. Shorter upstream sections require
a perforated plate in the branch and before
the measuring unit. If there is no straight upstream
section at all, the actual value signal may not be
stable, even with a perforated plate.

Bend, horizontal

Junction, horizontal

4
p

2B

4B

A bend with a straight duct section of at least


2B upstream of the volume flow rate measuring
unit has only a negligible effect on the volume
flow rate accuracy.
Space requirement
for commissioning
and maintenance
Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Access to attachments

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
4B upstream. Shorter upstream sections require
a perforated plate in the branch and before
the measuring unit. If there is no straight upstream
section at all, the actual value signal may not be
stable, even with a perforated plate.

Space required
Attachments

Without attachments
200
VARYCONTROL
Universal controller
300
LABCONTROL
EASYLAB
500

mm
H

200

300

400

H: Unit height

K5 4.1 24

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Rectangular volume flow rate measuring unit


for the measurement of volume flow rates in air
conditioning systems, available in 39 nominal
sizes. For the manual volume flow rate measuring
or for the permanent monitoring of the actual
value signal. Ready-to-commission unit which
consists of the casing with an averaging
differential pressure sensor. Differential pressure
sensor with 3 mm measuring holes
(resistant to dust and pollution).
Both ends suitable for the connection
of air duct profiles.
Casing air leakage to EN 15727, class B.

VME
Attachments
Volume flow rate measurement with static
differential pressure transducer emitting an actual
value signal for integration into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC or 2 10 V DC
TCU-LON-II: Integration with LonWorks
EASYLAB: Integration using either 0 10 V DC
signals or expansion modules
(LonWorks, BACnet MS/TP, Modbus RTU)
Sizing data
[m/h]

Special features
Measurement accuracy 5 % even
with unfavourable upstream conditions
Effective pressure range: approx. 8 200 Pa
Low differential pressure
of only about 17 32 %
of the measured effective pressure
Materials and surfaces
Galvanised sheet steel construction
Casing made of galvanised sheet steel
Aluminium sensor tubes
Powder-coated construction (P1)
Casing made of galvanised sheet steel,
powder-coated

Construction
Galvanised sheet steel
P1: Powder-coated, silver grey (RAL 7001)
Technical data
Nominal sizes: 200 100 to 1000 1000
Volume flow rate range:
45 to 10100 l/s or 162 to 36360 m/h
Effective pressure range: approx. 8 200 Pa
Measuring unit differential pressure
(pressure loss):
17 32 % of the measured effective pressure
Operating temperature: 10 to 50 C

Order options
VARYCONTROL

Type
VME
Rectangular volume flow rate
measuring unit
Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey
Nominal size [mm]
BH

K5 4.1 25

Attachments
(differential pressure transducer)
No entry: none
B10 Dynamic differential
pressure transducer
BB0 Static differential pressure transducer
Signal voltage range
For the actual value signal
Only for attachment B10
E0
0 10 V
E2
2 10 V

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

VME

Type
VME
Rectangular volume flow rate
measuring unit

Equipment function
SC
Supply air recording
EC
Extract air recording

Material
No entry: galvanised sheet steel
P1
Powder-coated (RAL 7001), silver grey

Voltage range for the actual value signal


E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC

Nominal size [mm]


BH

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Attachments
ELAB
EASYLAB controller TCU3

L
B
M
I
R

05/2015 DE/en

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

K5 4.1 26

VMRK

TOC

4.1

X X VMRKtestregistrierung

Volume flow rate measuring


units

Type VMRK

Variant with circular spigot

For the measurement of volume flow rates in ducts


with contaminated air
Plastic circular volume flow rate measuring units for the recording
or monitoring of volume flow rates
Manual volume flow rate measuring
Permanent volume flow rate measuring
Recording of measured values for other controllers
or for the LABCONTROL air management system
Pressure transducer for the automatic recording of measured values,
factory assembled and complete with wiring and tubing

Static differential
pressure transducer

Casing made of flame-resistant polypropylene (PPs)


Casing air leakage to EN 15727, class C
ET

HY

SCH GET
E

ST

I
EN

VD

Optional equipment and accessories


With flanges on both ends

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 4.1 27

Volume flow rate measuring units

TOC

General information

VMRK

Type
VMRK

Variants

Page
General information
Order code
Aerodynamic data
Dimensions and weight VMRK
Dimensions and weight VMRK-FL
Installation details
Specification text

4.1 28
4.1 30
4.1 33
4.1 34
4.1 35
4.1 36
4.1 37

Basic information and nomenclature

4.3 1

Volume flow rate measuring unit,


variant VMRK

Volume flow rate measuring unit,


variant VMRK-FL

Application
Plastic circular volume flow rate measuring
units Type VMRK for the manual
or automatic measuring of volume flow rates
Suitable for contaminated air
Simplified commissioning,
approval and maintenance
Suitable for permanent installation
because of low differential pressure

Parts and characteristics


Ready-to-commission unit which consists
of the mechanical parts and an optional
pressure transducer
Averaging differential pressure sensor
for volume flow rate measurement;
can be removed for cleaning
Optional factory-assembled pressure
transducers complete with wiring and tubing
High measurement accuracy
(even with upstream bend R = 1D)

Product examples

4
Description
For detailed information
on pressure transducers
see chapter K5 4.2.
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

Variants
VMRK: Volume flow rate measuring unit
VMRK-FL: Volume flow rate measuring unit
with flanges on both ends
Nominal sizes
125, 160, 200, 250, 315, 400
Attachments
Static differential pressure transducer
LABCONTROL components
for air management systems
Accessories
Matching flanges for both ends
Special features
Measurement accuracy 5 % even
with unfavourable upstream conditions
Effective pressure range: approx. 5 250 Pa
Low differential pressure
of only about 15 24 %
of the measured effective pressure

K5 4.1 28

Construction features
Circular casing
Spigot suitable for ducts according to DIN 8077
Connecting nipple for tubes
with 6 mm inside diameter
Materials and surfaces
Casing made of flame-resistant
polypropylene (PPs)
Differential pressure sensor
made of polypropylene (PP)
Installation and commissioning
Installation orientation is relevant
Static differential pressure transducer:
Check zero point and correct, if necessary
Standards and guidelines
Hygiene conforms to VDI 6022
Casing air leakage to EN 15727, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear
Zero point correction of the static differential
pressure transducer should be carried out once
per year (recommendation)

05/2015 DE/en

Volume flow rate measuring units

TOC

General information

VMRK

Attachments: VARYCONTROL differential pressure transducer for Type VMRK


Order code detail
Universal
BB0

Differential pressure transducer

Measurement principle

Universal controller with separate differential pressure transducer


TROX/Belimo

Static

Attachments: LABCONTROL differential pressure transducer for Type VMRK


Order code detail
EASYLAB
ELAB
TCU-LON-II
TM0

Technical data

Differential pressure transducer

Measurement principle

EASYLAB TCU3 (recording of measured values for EASYLAB system)

Static

Electronic controller TCU-LON-II with LonWorks interface

Static

Nominal sizes

125 400 mm

Volume flow rate range

25 1680 l/s or 90 6048 m/h

Measurement accuracy

5 % of the measured value

Effective pressure range


Measuring unit differential pressure (pressure loss)
Operating temperature

approx. 5 250 Pa
15 24 % of the measured effective pressure
10 50 C

05/2015 DE/en

K5 4.1 29

Volume flow rate measuring units

TOC

Order code
Order code

VMRK

VMRK

VARYCONTROL

VMRK FL / 160 / GK / BB0

Type
VMRK Volume flow rate measuring unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Order example

VMRK/160/BB0

VARYCONTROL

Nominal size
Differential pressure transducer

K5 4.1 30

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments
(differential pressure transducer)
No entry: none
BB0 Static differential pressure transducer

160 mm
Static

05/2015 DE/en

Volume flow rate measuring units

TOC

Order code
Order code
LABCONTROL
EASYLAB

VMRK

VMRK with EASYLAB for the recording of measured values

VMRK FL / 160 / GK / ELAB / EC E0 / ULZ / ...

Type
VMRK Volume flow rate measuring unit, plastic

Equipment function
EC
Extract air recording

Flange
No entry: none
FL
Flanges on both ends

Voltage range for the actual value signal


E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC

Nominal size [mm]


125
160
200
250
315
400

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments
ELAB EASYLAB TCU3

L
B
M
I
R

05/2015 DE/en

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

K5 4.1 31

Volume flow rate measuring units

TOC

Order code
Order code
LABCONTROL
EASYLAB

VMRK

VMRK with EASYLAB for fume cupboard control with external signalling (frequency converter)

VMLK FL / 160 / GK / ELAB / FH VS / ULZS / 200 800

Type
VMRK Volume flow rate measuring unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends

Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Attachments (control component)


ELAB EASYLAB controller TCU3

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket for the connection
of lighting and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-SEG-** 2-character display
BE-LCD-01 40-character display

K5 4.1 32

05/2015 DE/en

Volume flow rate measuring units

TOC

Aerodynamic data
Volume flow rate ranges

Nominal size
125
160
200
250
315
400

l/s

Nenn

150
250
405
615
1030
1680

VMRK
m/h

min

l/s

540
900
1458
2214
3708
6048

25
40
65
95
155
255

C-Wert
m/h
90
144
234
342
558
918

l/s

pst

m/h

8.6
15.1
24.3
38.0
62.0
102.7

31
54
87
137
223
370

%
24
22
19
17
15
15

5
5
5
5
5
5

K value for air density 1.2 kg/m, pst in relation to the measured effective pressure

Volume flow rate


calculation

Calculation conditions
The volume flow rate is calculated
based on the measured effective pressure.
The effective pressure is measured using
an electronic manometer
or an inclined tube manometer
Air density = 1.2 kg/m

Volume flow rate calculation


for air density 1.2 kg/m
= C

Volume flow rate calculation


for other air densities
= C

Calculation example

Given data
VMRK/160
pw = 100 Pa
(manometer reading of effective pressure)
Volume flow rate [m/h]
Unit data
K value from table: K = 54 m/h (15.1 l/s)

05/2015 DE/en

1.2

Calculation procedure
= 15.9 100
= 159 l/s

K5 4.1 33

Volume flow rate measuring units

TOC

Dimensions and weight VMRK


Description

VMRK

Volume flow rate measuring unit


Spigot to make connections to the ducting

Volume flow rate


measuring unit,
variant VMRK
Dimensions

VMRK Nenngre 125 200


394

4
VMRK nominal sizes 250 400
L

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

K5 4.1 34

L
mm

125
160
200
250
315
400

394
394
394
594
594
594

B3
195
230
270
320
385
470

H3
145
180
220
270
335
420

m
kg
2.0
2.2
2.5
3.5
5.1
6.9

05/2015 DE/en

Volume flow rate measuring units

TOC

Dimensions and weight VMRK-FL


Description

VMRK

Volume flow rate measuring unit


With flanges on both ends to make detachable
connections to the ducting

Volume flow rate


measuring unit,
variant VMRK-FL
Dimensions

VMRK-FL nominal size 125 200


400

n 10

VMRK-FL nominal size 250 400


L

n 10
T

Dimensions [mm] and weight [kg]


Nominal size
125
160
200
250
315
400

05/2015 DE/en

D
125
160
200
250
315
400

B3
400
400
400
600
600
600

mm
195
230
270
320
385
470

H3

D1
145
180
220
270
335
420

165
200
240
290
350
445

D2
185
230
270
320
395
475

n
8
8
8
12
12
16

mm

kg
8
8
8
8
10
10

2.2
2.6
3.0
4.4
6.1
8.2

K5 4.1 35

Volume flow rate measuring units

TOC

Installation details

Space requirement
for commissioning
and maintenance

Junction

The volume flow rate


accuracy applies
to a straight upstream
section of the duct.
Bends, junctions
or a narrowing
or widening of the duct
cause turbulence that
may affect measurement.
Duct connections, e.g.
branches off the main
duct, must comply
with EN 1505. Some
installation situations
require straight duct
sections upstream.

Bend

1D

Upstream conditions

VMRK

5D

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the volume flow rate measuring
unit has only a negligible effect
on the volume flow rate accuracy.

A junction causes strong turbulence.


The stated volume flow rate accuracy can only
be achieved with a straight duct section of at least
5D upstream. Shorter upstream sections require
a perforated plate in the branch and before
the measuring unit. If there is no straight upstream
section at all, the actual value signal may not be
stable, even with a perforated plate.

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required

Attachments

mm

Without attachments
200
VARYCONTROL
Universal controller
300
LABCONTROL
EASYLAB
350

200

200

320

300

350

400

Access to attachments

Access to sensor tubes for cleaning

150

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)

Space required
Nominal size
125 200
250 400

mm
100
100

100
160

D
D

D: Casing diameter

05/2015 DE/en

K5 4.1 36

Volume flow rate measuring units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Plastic (PPs) circular volume flow rate measuring


unit for the measurement of volume flow rates
in air conditioning systems, available in 6 nominal
sizes. For the manual volume flow rate measuring
or for the permanent monitoring of the actual value
signal. Ready-to-commission unit which consists
of the casing with an averaging differential
pressure sensor. Spigot, suitable for ducts
according to DIN 8077. Casing air leakage
to EN 15727, class C.
Special features
Measurement accuracy 5 % even
with unfavourable upstream conditions
Effective pressure range: approx. 5 250 Pa
Low differential pressure
of only about 15 24 %
of the measured effective pressure
Materials and surfaces
Casing made of flame-resistant
polypropylene (PPs)
Differential pressure sensor
made of polypropylene (PP)

Order options
VARYCONTROL

Type
VMRK Volume flow rate measuring unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400

05/2015 DE/en

VMRK
Technical data
Nominal sizes: 125 400 mm
Volume flow rate range:
25 to 1680 l/s or 90 to 6048 m/h
Effective pressure range: approx. 5 250 Pa
Measuring unit differential pressure
(pressure loss):
15 24 % of the measured effective pressure
Operating temperature: 10 to 50 C
Attachments
Volume flow rate measurement with static
differential pressure transducer emitting an actual
value signal for integration into the central BMS.
Supply voltage 24 V AC/DC
Signal voltages 0 10 V DC or 2 10 V DC
TCU-LON-II: Integration with LonWorks
EASYLAB: Integration using either 0 10 V DC
signals or expansion modules
(LonWorks, BACnet MS/TP, Modbus RTU)
Sizing data
[m/h]

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments
(differential pressure transducer)
No entry: none
BB0 Static differential pressure transducer

K5 4.1 37

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

VMRK

Type
VMRK Volume flow rate measuring unit, plastic

Equipment function
EC
Extract air recording

Flange
No entry: none
FL
Flanges on both ends

Voltage range for the actual value signal


E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC

Nominal size [mm]


125
160
200
250
315
400

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments
ELAB
EASYLAB TCU3

L
B
M
I
R

K5 4.1 38

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
VMRK Volume flow rate measuring unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
125
160
200
250
315
400
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

VMRK
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket
for the connection of lighting
and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-SEG-** 2-character display
BE-LCD-01 40-character display

05/2015 DE/en

K5 4.1 39

VMLK

TOC

4.1

X X VMLKtestregistrierung

Volume flow rate


measuring units

Type VMLK
Easy cleaning of sensor tubes

Variant with nozzle


and connecting circular spigot

Variant with bluff body


and flange

For the measurement of volume flow rates in ducts


with contaminated air from laboratories
Plastic circular volume flow rate measuring units for the recording
or monitoring of volume flow rates
Permanent volume flow rate measuring
Recording of measured values and use for slave controllers

For combination with LABCONTROL control components

For all upstream conditions

Volume flow rate control for fume cupboards


by signalling to frequency converters
Measurement accuracy 5 % even with unfavourable upstream conditions
Casing made of flame-resistant polypropylene (PPs)

H GE

Casing air leakage to EN 15727, class C

TE

ET

HY

ISC

ST

EN

VD

Optional equipment and accessories


With flanges on both ends

I 6022

Tested to VDI 6022

05/2015 DE/en

K5 4.1 40

Volume flow rate measuring units

TOC

General information

VMLK

Type
VMLK

Variants
Product examples

Page
General information
Order code
Aerodynamic data
Dimensions and weight VMLK
Dimensions and weight VMLK-FL
Installation details
Specification text

4.1 41
4.1 44
4.1 46
4.1 47
4.1 48
4.1 49
4.1 50

Basic information and nomenclature

4.3 1

Volume flow rate measuring unit,


variant VMLK,
with bluff body and circular spigot

Volume flow rate measuring unit,


variant VMLK,
with bluff body and flange

Volume flow rate measuring unit,


variant VMLK, with nozzle and circular spigot

Volume flow rate measuring unit,


variant VMLK, with nozzle and flange

K5 4.1 41

05/2015 DE/en

Volume flow rate measuring units

TOC

General information
Description
For detailed information
on the LABCONTROL
control system see
the Control Systems
catalogue.

VMLK

Application
Circular LABCONTROL volume flow rate
measuring units Type VMLK for the automatic
measurement of volume flow rates from fume
cupboards and fume hoods
Suitable for contaminated air
Volume flow rate control for fume cupboards
by signalling to frequency converters
Simplified commissioning,
approval and maintenance
Suitable for permanent installation
because of low differential pressure
Variants
VMLK: Volume flow rate measuring unit
VMLK-FL: Volume flow rate measuring unit
with flanges on both ends
Nominal sizes
Bluff body: 250 100, 250 160
Nozzle: 250 D08, 250 D10, 250 D16
Bluff body available in two sizes and nozzle
available in three sizes for different volume
flow rate ranges
Attachments
LABCONTROL: Control components
for air management systems
Accessories
Matching flanges for both ends
Special features
High measurement accuracy
with any upstream conditions
Effective pressure range: approx. 5 250 Pa

Parts and characteristics


Ready-to-commission unit which consists
of mechanical parts and control components
Averaging differential pressure sensor
for volume flow rate measurement;
can be removed for cleaning
Factory-assembled control component
complete with tubing
Construction features
Circular casing
Spigot suitable for ducts according to DIN 8077
Short casing: 392 mm without flange,
400 mm with flange
Materials and surfaces
Casing made of flame-resistant
polypropylene (PP),
flame retardant (V-0) to UL 94
Differential pressure sensor
(with bluff body, or nozzle) and plain bearing
made of polypropylene (PP)
Installation and commissioning
Installation orientation is relevant
For any upstream and downstream conditions
Static differential pressure transducer:
Check zero point and correct, if necessary
Standards and guidelines
Hygiene conforms to VDI 6022
Casing air leakage to EN 15727, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear
Zero point correction of the static differential
pressure transducer should be carried
out once per year (recommendation)

Attachments: VARYCONTROL differential pressure transducer for Type VMRK


Order code detail
Universal
BB0

Differential pressure transducer

Measurement principle

Universal controller with separate differential pressure transducer


TROX/Belimo

Static

Attachments: LABCONTROL differential pressure transducer for Type VMLK


Order code detail
EASYLAB
ELAB
TCU-LON-II
TM0

Technical data

Differential pressure transducer

Measurement principle

EASYLAB TCU3 (recording of measured values for EASYLAB system)

Static

Electronic controller TCU-LON-II with LonWorks interface

Static

Nominal sizes

30 515 l/s or 108 1854 m/h

Measurement accuracy

5 % of the measured value

Effective pressure range


Measuring unit differential pressure (pressure loss)
Operating temperature

05/2015 DE/en

250 mm

Volume flow rate range

approx. 5 250 Pa
19 65 % of the measured effective pressure
10 50 C

K5 4.1 42

Volume flow rate measuring units

TOC

General information
Function

VMLK

Functional description
The measuring unit is fitted either with a bluff body
and a differential pressure sensor or with a nozzle.
The control components (attachments) include
a differential pressure transducer that transforms
the differential pressure (effective pressure)
into an electric signal, and a controller.
Fume cupboard control: The volume flow rate
setpoint depends on the control strategy
for the fume cupboard control and is based on
the face velocity, the sash position,
or a constant value.
Volume flow control: The volume flow rate
setpoint comes from an external unit or device.
The controller compares the actual value
with the setpoint value and alters the control
signal of the frequency converter or of the actuator
if there is a difference between the two values.

Schematic illustration of the VMLK

Flange
Casing
Sticker showing the correct installation orientation
Control equipment

K5 4.1 43

Sensor head
Effective pressure sensor
Bluff body

05/2015 DE/en

Volume flow rate measuring units

TOC

Order code
Order code
LABCONTROL
EASYLAB

VMLK

VMLK with EASYLAB for fume cupboard control with external signalling (frequency converter)

VMLK FL / 250 100 / GK / ELAB / FH VS / ULZS / 200 900

Type
VMLK Volume flow rate measuring unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
250-100 Bluff body 100
250-160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16

Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I

Accessories
No entry: none
GK
Matching flanges for both ends

Attachments (control component)


ELAB EASYLAB controller TCU3

Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket for the connection
of lighting and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard controller,
for displaying the functions of the control
system according to EN 14175
BE-SEG-** 2-character display
BE-LCD-01 40-character display

05/2015 DE/en

K5 4.1 44

Volume flow rate measuring units

TOC

Order code
Order code

VMLK

VMLK with EASYLAB for the recording of measured values

LABCONTROL

VMLK FL / 250 100 / GK / ELAB / EC E0 / ULZ / ...

EASYLAB

Flange
No entry: none
FL
Flanges on both ends

Voltage range for the actual value signal


E0
Voltage signal 0 10 V DC
Voltage signal 2 10 V DC
E2

Nominal size [mm]


250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
EM-TRF-USV for 230 V AC, provides
U
uninterruptible power supply (UPS)

L
B
M
I
R

Order example

VMLK-FL/250100/GK/ELAB/FH-F/250 m/h

LABCONTROL

Flange
Nominal size
Attachment
Equipment function
Volume flow rate

K5 4.1 45

Equipment function
Extract air recording
EC

Attachments
ELAB EASYLAB TCU3

EASYLAB

Type
VMLK Volume flow rate measuring unit, plastic

Accessories
No entry: none
GK
Matching flanges for both ends

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3: Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

Both ends
250 with bluff body 100
EASYLAB controller
Fume cupboard control with volume flow rate constant value
for signalling to the frequency converter
250 m/h

05/2015 DE/en

Volume flow rate measuring units

TOC

Aerodynamic data
Volume flow rate ranges

Nominal size
250 100
250 160
250 D08
250 D10
250 D16

l/s

Nenn
360
195
515
360
195

VMLK
m/h
1296
702
1854
1296
702

l/s

min
55
30
95
55
30

C-Wert
m/h
198
108
342
198
108

l/s

m/h
25.0
13.3
34.0
24.3
13.8

90
48
122
87
50

pst

%
43
65
19
23
37

5
5
5
5
5

K value for air density 1.2 kg/m, pst in relation to the measured effective pressure

05/2015 DE/en

K5 4.1 46

Volume flow rate measuring units

TOC

Dimensions and weight VMLK


Description

VMLK

Application
Plastic circular volume flow rate measuring
units for volume flow rate measurement
Spigot to make connections to the ducting

Volume flow rate


measuring unit,
variant VMLK, with bluff
body and circular spigot
Dimensions

VMLK

250

120

AIR

392

285

Weight

Nominal size

250 D08,
250 D10,
250 D16

250 100,
250 160
m
kg

250

K5 4.1 47

2.1

2.6

05/2015 DE/en

Volume flow rate measuring units

TOC

Dimensions and weight VMLK-FL


Description

VMLK

Application
Plastic circular volume flow rate measuring
units for volume flow rate measurement
With flanges on both ends to make detachable
connections to the ducting

Volume flow rate


measuring unit,
variant VMLK, with bluff
body and flange
Dimensions

VMLK-FLVMLK-FL

250

285

319

12 x 10

AIR

400

120

289

Weight

Nominal size

250 D10,
250 D16,
250 D08

250 100,
250 160
m
kg

250

05/2015 DE/en

2.6

3.1

K5 4.1 48

Volume flow rate measuring units

TOC

Installation details
Upstream conditions

VMLK

Bend

Junction

1D

The volume flow rate


accuracy applies
to all upstream conditions.

p
p

A bend with a curvature radius of at least


1D without an additional straight duct section
upstream of the volume flow rate measuring
unit has only a negligible effect on the volume
flow rate accuracy.
Space requirement
for commissioning
and maintenance

Access to attachments

Space required

Attachments

mm

Without attachments
200
VARYCONTROL
Universal controller
300
LABCONTROL
EASYLAB
350

200

200

320

300

350

400

Access to sensor tubes for cleaning

Access to attachments

150

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

The stated volume flow rate accuracy


will be achieved even when the VAV terminal unit
is installed in a branch just off the main duct.

25
0

250

Separate space for fixing and accessing


the battery pack
(LABCONTROL EASYLAB accessory)

Space required
Nominal size
250-1**
Bluff body
250-D**
Nozzle

mm
100

160

100

160

100

D: Casing diameter

K5 4.1 49

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Standard text
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Circular volume flow rate measuring unit made


of flame-resistant plastic for the measurement of
volume flow rates in variable air volume systems
and fume cupboards. Suitable for the permanent
monitoring of the volume flow rate (actual value
signal) of extract air containing aggressive media
since all components coming into contact with
the airflow are made of plastic (no interior metal
parts). Measurement accuracy 5 % even
with unfavourable upstream and downstream
conditions. Suitable also for volume flow rate
control by signalling to frequency converters.
Ready-to-commission unit which consists of
the casing with either averaging effective pressure
sensor and bluff body or with nozzle,
and an electronic controller.
Differential pressure sensor with 3 mm
measuring holes (resistant to dust and pollution)
Spigot, suitable for ducts according to DIN 8077.
Casing air leakage to EN 15727, class C.

VMLK
Attachments
Volume flow rate control with electronic EASYLAB
controller for fume cupboards.
Supply voltage 24 V AC
Static differential pressure measurement
Easy commissioning due to plug and play
communication system
Controller is a modular system
and can be expanded
Volume flow rate monitoring
Sizing data
[m/h]

Special features
High measurement accuracy
with any upstream conditions
Effective pressure range: approx. 5 250 Pa
Materials and surfaces
Casing made of flame-resistant
polypropylene (PP),
flame retardant (V-0) to UL 94
Differential pressure sensor
(with bluff body, or nozzle) and plain bearing
made of polypropylene (PP)

Technical data
Nominal sizes: 250 mm
Volume flow rate range:
30 to 515 l/s or 108 to 1854 m/h
Measurement accuracy 5 % even
with unfavourable upstream
and downstream conditions.
Effective pressure range: approx. 5 250 Pa
Measuring unit differential pressure
(pressure loss): 19 65 %
of the measured effective pressure
Operating temperature: 10 to 50 C

K5 4.1 50

05/2015 DE/en

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

Type
VMLK
Volume flow rate measuring unit, plastic
Flange
No entry: none
FL
Flanges on both ends
Nominal size [mm]
250-100 Bluff body 100
250-160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16
Accessories
No entry: none
GK
Matching flanges for both ends
Attachments (control component)
ELAB
EASYLAB controller TCU3
Equipment function
With face velocity transducer
FH-VS Face velocity control
With sash distance sensor
FH-DS Linear control strategy
FH-DV Safety-optimised control strategy
With switching steps
for on-site switch contacts
FH-2P 2 switching steps
FH-3P 3 switching steps
Without signalling
FH-F Volume flow rate constant value

VMLK
Expansion modules
Option 1: Supply voltage
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

L
B
M
I
R

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid
valve for automatic zero point correction
Option 4: Lighting
No entry: none
EM-LIGHT Wired socket
for the connection of lighting
and for switching the lighting
on/off using the control panel
(only with EM-TRF or EM-TRF-USV)

Operating values [m/h or l/s]


Depending on the equipment function
VS: min max
DS: min max
DV: min max
2P: 1 / 2
3P: 1 / 2 / 3
F: 1
Useful additions
Control panel for fume cupboard
controller, for displaying the functions
of the control system according to
EN 14175
BE-SEG-** 2-character display
BE-LCD-01 40-character display

05/2015 DE/en

K5 4.1 51

Volume flow rate measuring units

TOC

Specification text
Order options
LABCONTROL
EASYLAB

VMLK

Type
VMLK
Volume flow rate measuring unit, plastic

Equipment function
EC
Extract air recording

Flange
No entry: none
FL
Flanges on both ends

Voltage range for the actual value signal


E0
Voltage signal 0 10 V DC
E2
Voltage signal 2 10 V DC

Nominal size [mm]


250 100 Bluff body 100
250 160 Bluff body 160
250 D08 Nozzle D08
250 D10 Nozzle D10
250 D16 Nozzle D16

Module expansions
Option 1: Power supply
No entry: 24 V AC
T
EM-TRF for 230 V AC
U
EM-TRF-USV for 230 V AC, provides
uninterruptible power supply (UPS)

Accessories
No entry: none
GK
Matching flanges for both ends
Attachments
ELAB
EASYLAB TCU3

L
B
M
I
R

K5 4.1 52

Option 2: Communication interface


No entry: none
EM-LON for LonWorks FTT-10A
EM-BAC-MOD-01 for BACnet MS/TP
EM-BAC-MOD-01 for Modbus RTU
EM-IP for BACnet/IP,
Modbus/IP and webserver
EM-IP with real time clock
Option 3:
Automatic zero point correction
No entry: none
EM-AUTOZERO Solenoid valve
for automatic zero point correction

05/2015 DE/en

Dynamic differential pressure transducers

X X Dynamic

TOC

4.2

differential pressure transducers testregistrierung

Differential pressure
transducers for volume
flow rate measuring units

Type Dynamic
differential pressure transducers

For the dynamic measurement of effective


and differential pressures
Differential pressure transducers based on the dynamic measurement principle
for volume flow rate measuring units Type VMR or VME
Linear volume flow rate actual value 0 10 V DC or 2 10 V DC
Recording of measured values for the display of volume flow rates
or for the control of slave controllers
Any installation orientation
Parameters are factory set

05/2015 DE/en

K5 4.2 1

Differential pressure transducers for volume flow rate measuring units

General information

Dyn. transducers

Type

Page

Dynamic differential
pressure transducers

Description

Universal controller VRD3

Any attachments must be


defined with the order
code of the volume flow
rate measuring unit.

TOC

General information
Special information B10

4.2 2
4.2 3

Basic information and nomenclature

4.3 1

Application
Electronic volume flow controller Universal
with dynamic differential pressure transducer
for use with volume flow rate measuring units
Parameters are factory set
On-site adjusting is not required
Standard filtration in comfort air conditioning
systems allows for use of the transmitter
in the supply air without additional dust protection.
Since a partial volume flow is passed through
the differential pressure transducer in order
to measure the volume flow rate, please note:
With heavy dust levels in the room,
suitable extract air filters must be provided.
If the air is polluted with fluff or sticky particles,
or if it contains aggressive media,
dynamic pressure transducers cannot be used

For this application the Universal controller


is only used for measuring the differential pressure
and for transforming the measured value
into a linear voltage signal. Connections
for setpoint value signal and actuator
are not relevant, and neither are
the corresponding technical data.
Volume flow rate actual
value is available as linear voltage signal

Dynamic differential pressure transducers for volume flow rate measuring units
Attachment

Order code detail

Part number

B10

Function

Volume flow rate measuring


unit

Controller

Type

M546GA4

VRD3

VMR, VME

Functional description
The volume flow rate is determined by measuring
the effective pressure. For this reason
the measuring unit is fitted with an effective
pressure sensor. The integral differental pressure
transducer transforms the effective pressure into
a voltage signal. The volume flow rate actual value
is hence available as a voltage signal. The factory
setting is such that 10 V DC always corresponds
to the nominal volume flow rate (nom).
Voltage ranges are factory stored in the controller.
Changes on the customer's site can easily
be carried out using an adjustment device
or a notebook with service tool.
Principle of operation dynamic differential
pressure transducer

Differential pressure transducer


Volume flow controller
Actual value signal

K5 4.2 2

05/2015 DE/en

Differential pressure transducers for volume flow rate measuring units

Special information B10


Description

/ B10
Order code detail

Technical data

TOC

Dyn. transducers

Application
Electronic volume flow controller VRD3
with dynamic differential pressure transducer
for use with volume flow rate measuring units
Differential pressure transducer and controller
electronics are fitted together in one casing

Useful additions
AT-VAV-B: Adjustment device
Signal voltage range
0: 0 10 V DC
2: 2 10 V DC

Volume flow controller VRD3


Supply voltage (AC)
Supply voltage (DC)
Power rating (AC)
Power rating (DC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity
Weight

24 V AC 20 %, 50/60 Hz
24 V DC 10/+20 %
without actuator max. 3.5 VA
without actuator max. 2 W
0 10 V DC, Ra > 100 k
0 10 V DC, 0.5 mA max.
III (protective extra-low voltage)
IP 40
EMC according to 2004/108/EC
0.440 kg

Universal controller VRD3

Function

VRD3

Controller VRD3
max potentiometer
min potentiometer
Service socket
Jumper for input w
Actuator cable
Cable bushings for supply voltage,
setpoint value signal and actual value signal
Indicator light
Connections for differential pressure sensor

05/2015 DE/en

K5 4.2 3

Differential pressure transducers for volume flow rate measuring units

Special information B10


Characteristics

Dyn. transducers

Characteristic of the actual value signal

Setting range

Volume flow

nom (100%)

min unit
0

10 V DC

0 10 V DC
2 10 V DC

Actual value signal U5

0 10 V DC

2 10 V DC

actual = U5 nom
10

4
Wiring

actual = U5 2 nom
8

Terminal connections

2
~
+

3
w

4 5 6
PP U5 z1

7
z2

Universal

Plug connection for actuator


Plug connection for adjustment device
1 , :
Ground, neutral
2 ~, +:
Supply voltage
3 w:
Setpoint value signal
4 PP:
Connection for adjustment device
5 U5:
Actual value signal
6 z1:
Override control 1 (OPEN)
7 z2:
Override control 2 (CLOSE, min, max)
Universal: VRD3

K5 4.2 4

05/2015 DE/en

TOC

Static differential pressure transducers

X X Static

TOC

4.2

differential pressure transducers testregistrierung

Differential pressure
transducers for volume
flow rate measuring units
Type Static differential
pressure transducers

For the static effective and differential


pressure measurement
Differential pressure transducers based on the static measurement
principle for volume flow rate measuring units Type VMR, VMRK or VME
Linear volume flow rate actual value 2 10 V DC
Recording of measured values for the display of volume flow rates
or for the control of slave controllers
Parameters are factory set

Universal controller VRP

05/2015 DE/en

K5 4.2 5

Differential pressure transducers for volume flow rate measuring units

General information

TOC

Static differential pressure transducers

Type

Page

Static differential pressure


transducers

Description

Universal controller VRP

Any attachments must


be defined with the order
code of the volume flow
rate measuring unit.

4.2 6
4.2 7

Basic information and nomenclature

4.3 1

Application
Electronic volume flow controller Universal
with static differential pressure transducer
for use with volume flow rate measuring units
For applications with polluted extract air,
e.g. with fluff, sticky particles
or aggressive substances
Parameters are factory set
On-site adjusting is not required
For this application the Universal controller
is only used for measuring the differential
pressure and for transforming the measured
value into a linear voltage signal. Connections
for setpoint value signal and actuator are not
relevant, and neither are the corresponding
technical data.
Volume flow rate actual value is available
as linear voltage signal

Installation and commissioning


Installation orientation is relevant
Zero point correction required
Maintenance
Zero point correction
once per year is recommended

Static differential pressure transducers for volume flow rate measuring units
Order code detail

Controller
Part number

BB0

Function

General information
Special information BB0

M546EG2

Volume flow rate


measuring unit

Static differential pressure transducer

Type

Part number

VRP

M546EJ1

Type
VFP-300

VMR, VME, VMRK

Functional description
The volume flow rate is determined by measuring
the effective pressure. For this reason
the measuring unit is fitted with an
effective pressure sensor. The static
differential pressure transducer
(diaphragm pressure transducer) transforms
the effective pressure into a voltage signal.
The volume flow rate actual value is hence
available as a voltage signal. The factory setting
is such that 10 V DC always corresponds
to the nominal volume flow rate (nom).
Principle of operation static differential
pressure transducer

Differential pressure transducer


Volume flow controller
Actual value signal

K5 4.2 6

05/2015 DE/en

Differential pressure transducers for volume flow rate measuring units

TOC

Special information BB0 Static differential pressure transducers


Description

/ BB0
Order code detail

Application
Electronic volume flow controller VRP
with static differential pressure transducer
for use with volume flow rate measuring units
Separate casings for differential pressure
transducer and controller electronics
Signal voltage range
2 10 V DC

Technical data

Installation and commissioning


Installation orientation is relevant
Zero point correction required
Maintenance
Zero point correction once per year
is recommended

Volume flow controller VRP


Supply voltage (AC)
Power rating (AC)
Setpoint value signal input
Actual value signal output
IEC protection class
Protection level
EC conformity

24 V AC 20 %, 50/60 Hz
without actuator max. 2.6 VA
2 10 V DC, Ra >100 k
2 10 V DC linear, max. 0.5 mA
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Universal controller VRP

Static differential pressure transducer VFP-300


Supply voltage
Measuring range
Linearity
IEC protection class
Protection level
EC conformity

from the controller


0 300 Pa
3 Pa
III (protective extra-low voltage)
IP 42
EMC according to 2004/108/EC

Static differential pressure


transducer VFP-300

05/2015 DE/en

K5 4.2 7

Differential pressure transducers for volume flow rate measuring units

TOC

Special information BB0 Static differential pressure transducers


Function

VRP

VFP-300

Controller VRP
min potentiometer
max potentiometer
Cable for differential pressure transducer
Actuator cable

Characteristics

Connecting cable to Universal controller


Tube connection for effective pressure sensor

Characteristic of the actual value signal

Terminal connections

Nenn (100%)

Einstellbereich

Wiring

Volumenstrom

min Gert
0

10 V DC

Istwertsignal U5

2
~

3
4 5
U5

6
y

7
z

Universal

Plug connection for differential pressure transducer


VFP
Plug connection for actuator
1 :
Ground, neutral
2 ~:
Supply voltage
3 w:
Setpoint value signal
4 w:
Setpoint value signal (0 20 V phase cut)
5 U5:
Actual value signal
6 y:
Actuator signal
7 z:
Override control
Universal: VRP

2 10 V DC
Ist = U5 2 Nenn
8

K5 4.2 8

05/2015 DE/en

TOC

4.3

X X Grundlagen

und Definitionentestregistrierung

Volume flow rate


measurement

Basic information
and nomenclature

Product selection
Principal dimensions
Nomenclature
Construction
Sizing and sizing example

05/2015 DE/en

K5 4.3 1

Volume flow rate measurement

TOC

Basic information and nomenclature


Product selection

Type
VMR

VME

VMRK

VMLK

Supply air

Extract air

Type of system

Duct connection
Circular

Rectangular

Volume flow rate range


Up to [m/h]

6048

36360

6048

1854

Up to [l/s]

1680

10100

1680

515

Filtered

Office extract air

Polluted

Contaminated

Manually

Automatically

Air quality

Volume flow rate measurement

Special areas
Labs, clean rooms, operating theatres
(EASYLAB, TCU-LON II)

Possible
Possible under certain conditions: Robust unit variant and/or specific differential pressure transducer
Not possible

K5 4.3 2

05/2015 DE/en

Volume flow rate measurement

TOC

Basic information and nomenclature


Principal dimensions

Nomenclature

Constructions

D [mm]
VAV terminal units made of stainless steel:
Outside diameter of the spigot
VAV terminal units made of plastic:
Inside diameter of the connecting spigot

B [mm]
Outside dimension of flange (width)

D [mm]
Pitch circle diameter of flanges

H [mm]
Duct height

D [mm]
Outside diameter of flanges

H [mm]
Screw hole pitch of flange (vertical)

D [mm]
Inside diameter of the screw holes of flanges

H [mm]
Outside dimension of flange (height)

L [mm]
Length of unit including connecting spigot

H [mm]
Unit height

L [mm]
Length of casing or acoustic cladding

n[]
Number of flange screw holes

B [mm]
Duct width

T [mm]
Flange thickness

B [mm]
Screw hole pitch of flange (horizontal)

m [kg]
Weight including attachments for the automatic
differential pressure measurement

nom [m/h] and [l/s]


Nominal volume flow rate (100 %)

K value [m/h] and [l/s]


Unit-related constant for air density 1.2 kg/m

min [m/h] and [l/s]


Volume flow rate

pw [Pa]
Effective pressure

[ %]
Volume flow rate accuracy

pst [%]
Static differential pressure in relation
to the measured effective pressure

Galvanised sheet steel


Casing made of galvanised sheet steel
Parts in contact with the airflow as described
for the product type
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

Stainless steel (A2)


Casing made of stainless steel 1.4201
Parts in contact with the airflow
are powder-coated or made of stainless steel
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

B [mm]
Width of device

Powder-coated surface (P1)


Casing made of galvanised sheet steel,
powder-coated RAL 7001, silver grey
Parts in contact with the airflow
are powder-coated or made of plastic
Due to production, some parts that come into
contact with the airflow may be stainless steel
or aluminium, powder-coated
External parts, e.g. mounting brackets
or covers, are usually made of galvanised
sheet steel

05/2015 DE/en

K5 4.3 3

Volume flow rate measurement

TOC

Basic information and nomenclature


Sizing with
the help of this catalogue

This catalogue provides convenient quick sizing


tables for volume flow rate measuring unit,
based on aerodynamic data. Volume flow rate
ranges are provided for all nominal sizes.

Sizing example

Given data
max = 280 l/s (1010 m3/h)
Quick sizing
VMR/200
C = 25.5 l/s (92 m3/h)
pst = 19 %
pw = 121 Pa
pst = 23 Pa (121 Pa 0,19)

Easy Product Finder

4
The Easy Product Finder
allows you to size
products using your
project-specific data.
You will find
the Easy Product Finder
on our website.

K5 4.3 4

05/2015 DE/en

Heat transfer

TOC

Table of contents
5

Heat transfer
Heat exchangers are used to heat the volume flow in ducts.
They are installed in ducts in order to meet individual comfort requirements.

5.1 Heat exchanger

Type

Page

For the reheating of airflows in circular


ducting

WL

5.1 1

For the electric reheating of airflows in


circular ducting

EL

5.1 7

For the reheating of airflows in


rectangular ducting

WT

5.1 15

Circular

Rectangular

5.2 Basic information and nomenclature

Heat transfer

K5 5.0 1

5.2 1

05/2015 DE/en

WL

TOC

5.1

X X WLtestregistrierung

Heat exchanger
Type WL

For the reheating of airflows in circular ducting


Circular hot water heat exchanger for the reheating of airflows,
suitable for VAV terminal units Type TVR
and mechanical self-powered CAV controllers Type RN or VFC
For hot water up to 100 C

Copper tubes arranged in two rows, with aluminium fins


Installation in horizontal or vertical ducts independent of airflow direction
Suitable for circular ducts to EN 1506 or EN 13180
With lip seal and inspection access
Maximum water-side operating pressure is 8 bar
Casing air leakage to EN 15727, class C

Heat exchanger
with copper tubes
and aluminium fins

05/2015 DE/en

K5 5.1 1

Heat exchanger

TOC

General information

WL

Type
WL

Description

Page
General information
Order code
Quick sizing
Dimensions and weight
Specification text

5.1 2
5.1 3
5.1 4
5.1 5
5.1 6

Basic information and nomenclature

5.2 1

Application
Hot water heat exchanger Type WT
for reheating the airflow in circular ducting
For VAV terminal units Type TVR
and for CAV controllers Type RN or VFC
For hot water up to 100 C
Nominal sizes
100, 125, 160, 200, 250, 315, 400

Heat exchanger Type WL

Parts and characteristics


Ready-to-install heat exchanger
Copper tubes arranged in two rows
Lip seal
Inspection access
Tested for leakage
Construction features
Rectangular casing
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180
Maximum water-side operating
pressure is 10 bar
Horizontal water connection
Plain copper tube ends for water connection

Technical data

K5 5.1 2

Nominal sizes
Volume flow rate range
Thermal output
Maximum hot water temperature
Maximum water-side operating pressure
Water-side differential pressure
Static differential pressure

Materials and surfaces


Casing made of galvanised sheet steel
Copper tubes
Aluminium fins
Installation and commissioning
Installation in horizontal or vertical ducts
independent of airflow direction
Capacity control and supply connections
to be provided by others
Venting and draining by others
Standards and guidelines
Casing air leakage to EN 15727, class C
Maintenance
Maintenance-free as construction
and materials are not subject to wear

100 400 mm
10 750 l/s or 36 2700 m/h
0.25 18 kW
100 C
10 bar
0.3 12 kPa
5 80 Pa

05/2015 DE/en

Heat exchanger

TOC

Order code
Order code

WL
WL

WL / 160

Type
WL
Hot water heat exchanger
for VAV terminal units TVR
and CAV controllers RN and VFC

Order example

Nominal size [mm]


100
125
160
200
250
315
400

WL/160
Nominal size

160 mm

05/2015 DE/en

K5 5.1 3

Heat exchanger

TOC

Quick sizing

WL

WL for TVR, RN and VFC

Nominal size
l/s
100
100
100
100
100
125
125
125
125
125
160
160
160
160
160
200
200
200
200
200
250
250
250
250
250
315
315
315
315
315
400
400
400
400
400

5
:
PWW:
t e:
ta:
w:
pv:
pst:

K5 5.1 4

10
20
30
40
45
18
35
50
65
75
28
50
70
95
115
45
80
115
150
180
70
125
180
235
290
115
200
285
375
460
185
325
465
605
750

pst
m/h
36
72
108
144
162
65
126
180
234
270
101
180
252
342
414
162
288
414
540
648
252
450
648
846
1044
414
720
1026
1350
1656
666
1170
1674
2178
2700

Pa

PWW 50/40, te = 16 C

kW
5
10
15
25
30
5
20
40
60
80
5
10
15
25
35
5
20
35
55
80
5
15
25
40
60
5
15
25
40
60
5
15
30
50
75

0.25
0.38
0.47
0.55
0.58
0.36
0.51
0.62
0.70
0.76
0.69
1.05
1.35
1.70
1.94
0.97
1.49
1.94
2.29
2.57
1.53
2.35
3.10
3.76
4.29
2.50
3.82
5.02
6.05
6.89
4.02
6.24
8.06
9.54
10.92

ta

C
36.1
31.3
28.8
27.2
26.5
32.0
27.9
26.0
24.8
24.2
36.1
33.1
31.7
30.6
29.7
33.6
31.2
29.7
28.4
27.6
33.8
31.3
30.0
29.0
28.1
33.7
31.5
30.4
29.1
28.2
33.7
31.6
30.1
28.8
27.9

kg/h
21
33
41
48
51
31
44
53
61
66
60
91
117
147
168
84
129
168
199
223
133
203
269
326
372
217
331
436
525
597
348
542
699
827
947

pv

kPa
0.3
0.4
0.5
0.6
0.7
0.3
0.5
1.0
1.2
1.5
1.0
2.0
4.0
5.0
7.0
2.0
4.0
7.0
9.0
11.0
1.0
2.0
3.0
5.0
6.0
1.0
2.0
4.0
5.0
7.0
2.0
3.0
5.0
7.0
9.0

PWW 70/55, te = 16 C

kW
0.40
0.62
0.79
0.95
1.02
0.58
0.87
1.09
1.30
1.44
1.17
1.83
2.32
2.85
3.23
1.69
2.54
3.23
3.37
4.30
2.67
4.14
5.29
6.29
7.20
4.41
6.66
8.45
10.11
11.52
7.08
10.55
13.40
15.89
18.22

ta

C
48.5
41.2
37.5
35.2
34.4
42.2
36.2
33.8
32.3
31.6
49.9
45.8
43.0
40.4
38.8
46.5
41.8
38.8
36.8
35.4
47.0
43.0
39.9
37.8
36.2
47.2
43.1
40.1
37.9
36.4
47.2
42.4
39.5
37.4
35.8

kg/h
23
36
46
55
59
34
51
64
76
84
68
107
135
166
188
98
148
188
223
251
155
242
308
367
420
257
388
493
589
672
413
615
781
927
1062

pv

kPa
0.5
0.6
0.7
0.8
1.0
0.5
0.8
1.0
1.3
1.5
1.0
3.0
4.0
6.0
7.0
2.0
5.0
7.0
10.0
12.0
1.0
3.0
4.0
5.0
7.0
1.0
3.0
4.0
6.0
7.0
2.0
4.0
6.0
8.0
10.0

Thermal capacity
Fully pumped heating system, flow temperature/return temperature
Inlet airflow temperature
Outlet airflow temperature
Water flow rate
Water-side differential pressure
Static differential pressure

05/2015 DE/en

Heat exchanger

TOC

Dimensions and weight


Dimensions

WL

WL
L
A

Heat exchanger Type WL

Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

L
99
124
159
199
249
314
399

H3

B3
356
356
356
356
356
356
356

H1

mm
238
238
313
313
398
473
557

188
188
263
263
338
413
512

A
137
137
212
212
250
325
400

D5
40
40
40
40
40
40
65

m
kg
10
10
10
10
22
22
22

3.7
3.5
5.4
5.3
7.7
9.9
13.1

05/2015 DE/en

K5 5.1 5

Heat exchanger

TOC

Specification text
Standard text

Circular hot water heat exchangers


for reheating the airflow in air conditioning
systems. Dimensions fit VAV terminal units TVR
as well as CAV controllers RN and VFC.
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180.
Casing air leakage to EN 15727, class C.
Materials and surfaces
Casing made of galvanised sheet steel
Copper tubes
Aluminium fins

Order options

Type
WL
Hot water heat exchanger
for VAV terminal units TVR
and CAV controllers RN and VFC

WL
Technical data
Volume flow rate range:
10 to 750 l/s or 36 to 2700 m/h
Thermal capacity: 0.25 18 kW
Maximum water temperature: 100 C
Maximum water-side operating pressure:
10 bar
Water-side differential pressure: 0.3 12 kPa
Static differential pressure: 5 80 Pa
Sizing data
[m/h]
te[C]
PWW[C]
[kW]

Nominal size [mm]


100
125
160
200
250
315
400

K5 5.1 6

05/2015 DE/en

EL

TOC

5.1

X X ELtestregistrierung

Heat exchanger
Type EL

For the electric reheating of airflows in circular ducting


Circular electric air heater for the heating of airflows, suitable for VAV terminal units
Type TVR and mechanical self-powered CAV controllers Type RN or VFC
Outlet airflow temperature max. 50 C
Smooth surface stainless steel heating element 1.4301
Integral overheating protection with temperature monitor (auto reset)
and thermal cut-out (manual reset)
Installation in horizontal or vertical ducts independent of airflow direction
Suitable for circular ducts to EN 1506 or EN 13180
With lip seal
Protection level IP 43
Casing air leakage to EN 15727, up to class D

Heat exchanger with


smooth surface stainless steel heating elements

05/2015 DE/en

K5 5.1 7

Heat exchanger

TOC

General information

EL

Type
EL

Description

Heat exchanger Type WL

Page
General information
Order code
Quick sizing
Dimensions and weight
Installation details
Specification text

5.1 8
5.1 9
5.1 10
5.1 11
5.1 12
5.1 13

Basic information and nomenclature

5.2 1

Application
Electric air heater Type EL
for reheating the airflow in circular ducting
For VAV terminal units Type TVR
and for CAV controllers Type RN or VFC

Materials and surfaces


Casing and switch cabinet
made of galvanised sheet steel
Heating element made of stainless
steel 1.4301

Nominal sizes
100, 125, 160, 200, 250, 315, 400

Installation and commissioning


Installation in horizontal or vertical ducts
Capacity control and supply connections
to be provided by others
A straight duct section of at least 2D upstream
or downstream is required between a bend,
a branch, etc., and a component, fan,
or flow adjustment damper.
Airflow direction is indicated by an arrow
Switch cabinet can be located on top
or at the side

Parts and characteristics


Ready-to-install air heater
Encased smooth surface stainless steel
heating elements
Overheating protection with temperature
monitor (auto reset) and thermal cut-out
(manual reset)
Connection terminals inside
Casing is ready for cable penetration;
wire clamping bracket and cable gland
(M20 or M25) to be provided by others
Construction features
Circular casing with rectangular switch cabinet
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180

5
Technical data

K5 5.1 8

Nominal sizes
Volume flow rate range
Thermal output
Minimum airflow velocity
Maximum outlet airflow temperature
Max. operating temperature
Static differential pressure
Supply voltage for nominal sizes 100 200
Supply voltage for nominal size 250
Supply voltage for nominal sizes 315, 400
Protection level
EC conformity

Standards and guidelines


Casing air leakage to EN 15727, class D
Maintenance
Maintenance-free as construction
and materials are not subject to wear

100 400 mm
12 750 l/s or 43 2700 m/h
0.4 9 kW
1.5 m/s
50 C
40 C
5 75 Pa
230 V AC, 1-phase
400 V AC, 2-phase
400 V AC, 3-phase
IP 43
EMC to 2004/108/EU, low voltage to 2006/95/EU

05/2015 DE/en

Heat exchanger

TOC

Order code
Order code

EL
EL

EL / 160

Type
EL
Electric air heater for VAV terminal units
Type TVR and for CAV controllers
Type RN or VFC

Order example

Nominal size [mm]


100
125
160
200
250
315
400

EL/160
Nominal size

160 mm

05/2015 DE/en

K5 5.1 9

Heat exchanger

TOC

Quick sizing

EL
EL for TVR, RN and VFC

Nominal size
l/s

100

125

160

200

250

315

400

:
te:
t a:

K5 5.1 10

pst
m/h

12
20
30
40
45
20
35
50
65
75
30
50
70
95
115
50
80
115
150
180
75
125
180
235
290
115
200
285
375
460
190
325
465
605
750

Pa
43
72
108
144
162
72
126
180
234
270
108
180
252
342
414
180
288
414
540
648
275
450
648
846
1044
414
720
1026
1350
1656
684
1170
1674
2178
2700

te = 16 C

kW
5
10
15
25
30
5
20
40
60
80
5
10
15
25
35
5
20
35
55
80
5
15
25
40
60
5
15
25
40
60
5
15
30
50
75

ta

C
0.40
0.40
0.40
0.40
0.40
0.88
0.90
0.90
0.90
0.90
1.20
1.20
1.20
1.20
1.20
2.10
2.10
2.10
2.10
2.10
3.00
3.00
3.00
3.00
3.00
5.07
6.00
6.00
6.00
6.00
8.37
9.00
9.00
9.00
9.00

41.8
31.4
26.3
23.7
22.9
50.0
35.8
29.9
26.7
25.3
46.9
34.5
29.2
25.7
24.1
48.4
36.3
30.1
26.8
25.0
46.9
34.5
28.9
25.9
24.0
50.0
39.1
32.2
28.3
26.1
50.0
37.4
30.9
27.5
25.3

Thermal capacity
Inlet airflow temperature
Outlet airflow temperature

05/2015 DE/en

Heat exchanger

TOC

Dimensions and weight


Dimensions

EL

EL
375
278
42

Heat exchanger Type EL

~ 85

Prepared for cable bushings (M20 and M25)

Dimensions [mm] and weight [kg]


Nominal size
100
125
160
200
250
315
400

D
mm
99
124
159
199
249
314
399

H3

kg
116
141
176
216
266
331
416

2.0
2.5
2.9
3.7
4.5
6.7
8.1

05/2015 DE/en

K5 5.1 11

Heat exchanger

TOC

Installation details
Space requirement
for commissioning
and maintenance

EL

Access to attachments

Sufficient space
must be kept clear near
any attachments to allow
for commissioning and
maintenance. It may be
necessary to provide
sufficiently sized
inspection access
openings.

Space required
Nominal size
100
125
160
200
250
315
400

mm
375
375
375
375
375
375
375

115
140
175
215
265
330
415

300
300
300
300
300
300
300

K5 5.1 12

05/2015 DE/en

Heat exchanger

TOC

Specification text
Standard text

Circular electric air heater for reheating


the airflow in air conditioning systems
Dimensions fit VAV terminal units TVR
as well as CAV controllers RN and VFC.
Integral overheating protection with temperature
monitor (auto reset) and thermal cut-out
(manual reset).
Spigot with lip seal, for circular connecting
ducts to EN 1506 or EN 13180.
Casing air leakage to EN 15727, class C.
Materials and surfaces
Casing and switch cabinet
made of galvanised sheet steel
Heating element made of stainless
steel 1.4301

Order options

Type
EL
Electric air heater for VAV terminal units
Type TVR and for CAV controllers
Type RN or VFC

EL
Technical data
Volume flow rate range:
12 to 750 l/s or 43 to 2700 m/h
Thermal output: 0.4 9 kW
Maximum outlet airflow temperature: 50 C
Static differential pressure: 5 75 Pa
Supply voltage: 1 230 V AC 3 400 V AC
Protection level: IP 43
Sizing data
[m/h]
te[C]
PWW[C]
[kW]

Nominal size [mm]


100
125
160
200
250
315
400

05/2015 DE/en

K5 5.1 13

WT

TOC

5.1

X X WTtestregistrierung

Heat exchanger
Type WT

For the reheating of airflows in rectangular ducting


Rectangular hot water heat exchanger for the reheating of airflows,
suitable for VAV terminal units Type TVR, TZ-Silenzio, TVJ or TVT,
and mechanical self-powered CAV controllers Type EN
For hot water up to 100 C

Horizontal water connection


Copper tubes arranged in two rows, with aluminium fins
Maximum water-side operating pressure is 16 bar
Casing air leakage to EN 15727, up to class D

Heat exchanger
with copper tubes
and aluminium fins

05/2015 DE/en

K5 5.1 15

Heat exchanger

TOC

General information

WT

Type
WT

Description

Heat exchangers Type WT

Page
General information
Order code
Quick sizing
Dimensions and weight
Specification text

5.1 16
5.1 17
5.1 18
5.1 22
5.1 24

Basic information and nomenclature

5.2 1

Application
Hot water heat exchanger Type WT
for reheating the airflow in rectangular ducting
For VAV terminal units TZ-Silenzio, TVZ,
TVJ, and TVT, and for CAV controllers EN
For hot water up to 100 C
Nominal sizes
125, 160, 200, 250, 315, 400
for TZ-Silenzio and TVZ
43 nominal sizes from
200 x 100 to 1000 x 1000
for TVJ, TVT and EN
Parts and characteristics
Ready-to-install heat exchanger
Copper tubes arranged in two rows
Construction features
Rectangular casing
Flanges on both ends for connection
to ductwork
Maximum water-side operating pressure
is 16 bar
Horizontal water connection
Water connection with external thread

5
Technical data

K5 5.1 16

Nominal sizes for TZ-Silenzio and TVZ


Nominal sizes for TVJ, TVT and EN
Volume flow rate range
Thermal output
Maximum hot water temperature
Maximum water-side operating pressure
Water-side differential pressure
Static differential pressure

Materials and surfaces


Casing made of galvanised sheet steel
Copper tubes
Aluminium fins
Installation and commissioning
Installation in horizontal or vertical ducts
independent of airflow direction
Water connection must be horizontal
Capacity control and supply connections
to be provided by others
Venting and draining by others
Standards and guidelines
Casing air leakage to EN 15727,
class D (H 400 mm, class C)
Maintenance
Maintenance-free as construction
and materials are not subject to wear

125 400 mm
200 100 to 1000 1000 mm
15 6000 l/s or 55 21600 m/h
0.4 117 kW
100 C
16 bar
0.1 25 kPa
25 170 Pa

05/2015 DE/en

Heat exchanger

TOC

Order code
Order code

WT
WT for TZ-Silenzio and TVZ

WT / 160

Type
WT
Hot water heat exchanger
for VAV terminal units TZ-Silenzio and TVZ

Order code

Nominal size
125
160
200
250
315
400

WT for TVJ, TVT and EN

WT / 400200

Type
WT
Hot water heat exchanger
for CAV controllers EN
and for VAV terminal units TVJ and TVT
Order examples

Nominal size [mm]


BH

WT/200
Nominal size

200 mm

WT/400x200
Nominal size B H

05/2015 DE/en

400 200 mm

K5 5.1 17

Heat exchanger

TOC

Quick sizing

WT

WT for TZ-Silenzio and TVZ

Nominal size
l/s

125
125
125
125
125
160
160
160
160
160
200
200
200
200
200
250
250
250
250
250
315
315
315
315
315
400
400
400
400
400
:
PWW:
t e:
ta:
w:
pv:
pst:

K5 5.1 18

15
35
60
95
150
25
65
100
170
250
40
110
180
280
405
60
170
280
470
615
105
265
420
720
1025
170
445
710
1250
1680

pst
m/h
54
126
216
342
540
90
234
360
612
900
144
396
648
1008
1458
216
612
1008
1692
2214
378
954
1512
2592
3690
612
1602
2556
4500
6048

Pa
5
10
25
55
120
5
15
25
70
140
5
10
25
50
100
5
15
30
75
125
5
10
25
65
125
5
15
30
80
135

PWW 50/40, te = 16 C

kW
0.40
0.77
1.12
1.49
1.95
0.65
1.36
1.82
2.53
3.16
1.07
2.41
3.39
4.48
5.58
1.58
3.55
4.96
6.80
7.94
2.75
5.64
7.72
10.79
13.23
4.43
9.30
12.73
18.00
21.32

ta

C
37.8
34.3
31.5
29.1
26.8
37.6
33.4
31.1
28.3
26.5
38.3
34.2
31.6
29.3
27.4
37.9
33.3
30.7
28.0
26.7
37.7
33.7
31.3
28.4
26.7
37.6
33.3
30.9
28.0
26.5

kg/h
34
66
96
128
168
56
117
157
217
271
92
207
291
385
480
136
305
426
585
683
236
485
664
928
1138
381
800
1094
1548
1833

pv

kPa
0.2
0.7
1.5
2.5
4.1
0.1
0.5
0.9
1.7
2.6
0.1
0.4
0.8
1.3
1.9
0.2
0.9
1.8
3.2
4.3
0.5
1.8
3.1
5.8
8.5
0.7
2.5
4.5
8.6
11.8

PWW 70/55, te = 16 C

kW
0.64
1.24
1.80
2.41
3.14
1.05
2.20
2.93
4.07
5.08
1.74
3.89
5.46
7.22
8.98
2.56
5.72
7.98
10.95
12.77
4.44
9.10
12.44
17.37
21.29
7.17
15.00
20.51
28.97
34.30

ta

C
51.4
45.5
40.9
37.0
33.4
51.0
44.0
40.3
35.9
32.9
52.1
45.3
41.2
37.4
34.4
51.4
43.9
39.7
35.3
33.2
51.1
44.5
40.6
36.0
33.2
51.0
44.0
40.0
35.2
32.9

kg/h
37
71
103
138
180
60
126
168
233
291
100
223
313
414
515
147
328
458
628
732
255
522
713
996
1221
411
860
1176
1661
1966

pv

kPa
0.2
0.8
1.6
2.7
4.5
0.1
0.6
1.0
1.9
2.8
0.1
0.4
0.8
1.4
2.1
0.2
1.0
1.9
3.5
4.6
0.5
1.9
3.4
6.3
9.2
0.7
2.8
4.9
9.4
12.8

Thermal capacity
Fully pumped heating system, flow temperature/return temperature
Inlet airflow temperature
Outlet airflow temperature
Water flow rate
Water-side differential pressure
Static differential pressure

05/2015 DE/en

Heat exchanger

TOC

Quick sizing

WT

WT for TVJ, TVT and EN

Nominal size
l/s
200 100
200 100
200 100
300 100
300 100
300 100
400 100
400 100
400 100
500 100
500 100
500 100
600 100
600 100
600 100
300 150
300 150
300 150
200 200
200 200
200 200
300 200
300 200
300 200
400 200
400 200
400 200
500 200
500 200
500 200
600 200
600 200
600 200
700 200
700 200
700 200
800 200
800 200
800 200
400 250
400 250
400 250
500 250
500 250
500 250
:
PWW:
t e:
ta:
w:
pv:
pst:

05/2015 DE/en

pst
m/h

40
80
120
60
120
180
80
160
240
100
200
300
120
240
360
90
180
270
80
160
240
120
240
360
160
320
480
200
400
600
240
480
720
280
560
840
320
640
960
200
400
600
250
500
750

144
288
432
216
432
648
288
576
864
360
720
1080
432
864
1296
324
648
972
288
576
864
432
864
1296
576
1152
1728
720
1440
2160
864
1728
2592
1008
2016
3024
1152
2304
3456
720
1440
2160
900
1800
2700

Pa
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170

PWW 50/40, te = 16 C

kW
0.75
1.15
1.45
1.12
1.72
2.17
1.50
2.30
2.89
1.87
2.87
3.62
2.25
3.45
4.34
1.68
2.59
3.25
1.50
2.30
2.89
2.25
3.45
4.34
2.99
4.60
5.79
3.74
5.75
7.23
4.49
6.90
8.68
8.44
12.95
16.29
9.65
14.80
18.61
3.74
5.75
7.23
4.68
7.18
9.04

ta

C
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
41.0
35.2
32.1
41.0
35.2
32.1
31.5
27.9
26.0
31.5
27.9
26.0

kg/h
64
99
124
97
148
187
129
198
249
161
247
311
193
296
373
145
222
280
129
198
249
193
296
373
257
395
498
322
494
622
386
593
746
484
742
934
553
848
1067
322
494
622
402
618
777

pv

kPa
0.5
1.1
1.7
1.3
2.9
4.5
2.7
5.9
9.1
4.7
10.3
15.8
1.5
3.3
5.0
4.0
8.7
13.4
3.2
7.2
11.1
1.6
3.6
5.6
3.2
7.2
11.0
5.5
12.3
18.8
1.5
3.3
5.0
2.3
5.2
7.9
3.2
7.1
10.9
5.7
12.8
19.6
3.6
8.0
12.2

PWW 70/55, te = 16 C

kW
1.21
1.85
2.33
1.81
2.78
3.49
2.41
3.70
4.65
3.02
4.62
5.82
3.62
5.55
6.98
2.71
4.16
5.24
2.41
3.70
4.65
3.62
5.55
6.98
4.82
7.40
9.31
6.03
9.25
11.63
7.24
11.10
13.96
8.44
12.95
16.29
9.65
14.80
18.61
6.03
9.25
11.63
7.54
11.56
14.54

ta

C
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1

kg/h
69
106
133
104
159
200
138
212
267
173
265
333
207
318
400
156
239
300
138
212
267
207
318
400
277
424
534
346
530
667
415
636
800
484
742
934
553
848
1067
346
530
667
432
663
834

pv

kPa
0.5
1.2
1.9
1.4
3.2
4.9
2.9
6.4
9.8
5.1
11.1
17.0
1.6
3.6
5.5
4.3
9.5
14.5
3.5
7.8
12.1
1.8
4.0
6.1
3.5
7.8
12.1
6.0
13.4
20.5
1.6
3.6
5.5
2.3
5.2
7.9
3.2
7.1
10.9
6.3
13.9
21.4
3.9
8.7
13.3

Thermal capacity
Fully pumped heating system, flow temperature/return temperature
Inlet airflow temperature
Outlet airflow temperature
Water flow rate
Water-side differential pressure
Static differential pressure

K5 5.1 19

Heat exchanger

TOC

Quick sizing

WT

WT for TVJ, TVT and EN

Nominal size
l/s
600 250
600 250
600 250
300 300
300 300
300 300
400 300
400 300
400 300
500 300
500 300
500 300
600 300
600 300
600 300
700 300
700 300
700 300
800 300
800 300
800 300
900 300
900 300
900 300
1000 300
1000 300
1000 300
400 400
400 400
400 400
500 400
500 400
500 400
600 400
600 400
600 400
700 400
700 400
700 400
800 400
800 400
800 400
900 400
900 400
900 400

:
PWW:
t e:
ta:
w:
pv:
pst:

K5 5.1 20

pst
m/h

300
600
900
180
360
540
240
480
720
300
600
900
360
720
1080
420
840
1260
480
960
1440
540
1080
1620
600
1200
1800
320
640
960
400
800
1200
480
960
1440
560
1120
1680
640
1280
1920
720
1440
2160

1080
2160
3240
648
1296
1944
864
1728
2592
1080
2160
3240
1296
2592
3888
1512
3024
4536
1728
3456
5184
1944
3888
5832
2160
4320
6480
1152
2304
3456
1440
2880
4320
1728
3456
5184
2016
4032
6048
2304
4608
6912
2592
5184
7776

Pa
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170

PWW 50/40, te = 16 C

kW
5.61
8.62
10.85
3.37
5.17
6.51
4.49
6.90
8.68
5.61
8.62
10.85
6.73
10.34
13.02
7.86
12.07
15.19
8.98
13.79
17.36
10.10
15.51
19.52
11.22
17.24
21.69
5.99
9.19
11.57
7.48
11.49
14.46
9.98
13.79
17.36
10.47
16.09
20.25
11.97
18.39
23.14
13.47
20.69
26.03

ta

C
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0

kg/h
483
741
933
290
445
560
386
593
746
483
741
933
579
889
1119
676
1038
1306
772
1186
1493
869
1334
1679
965
1482
1866
515
791
995
643
988
1244
772
1186
1493
901
1384
1741
1029
1581
1990
1158
1779
2239

pv

kPa
5.6
12.4
19.0
4.6
10.3
15.9
3.2
7.2
11.0
2.6
5.9
9.0
4.1
9.1
14.0
6.0
13.3
20.3
3.0
6.6
10.0
3.9
8.7
13.4
5.1
11.3
17.3
3.2
7.2
11.0
5.5
12.3
18.8
2.9
6.5
9.9
6.8
15.0
22.9
5.9
13.0
19.9
3.9
8.7
13.4

PWW 70/55, te = 16 C

kW
9.04
13.87
17.45
5.43
8.32
10.47
7.24
11.10
13.96
9.04
13.87
17.45
10.85
16.65
20.94
12.66
19.42
24.43
14.47
22.20
27.92
16.28
24.97
31.41
18.09
27.75
34.90
9.65
14.80
18.61
12.06
18.50
23.27
14.47
22.20
27.92
16.88
25.90
32.57
19.29
29.60
37.23
21.71
33.30
41.88

ta

C
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1

kg/h
519
795
1000
311
477
600
415
636
800
519
795
1000
622
954
1201
726
1114
1401
830
1273
1601
933
1432
1801
1037
1591
2001
553
848
1067
691
1061
1334
830
1273
1601
968
1485
1868
1106
1697
2134
1244
1909
2401

pv

kPa
6.1
13.4
20.6
5.1
11.3
17.4
3.5
7.8
12.1
2.9
6.4
9.8
4.5
9.9
15.2
6.5
14.4
22.1
3.2
7.1
10.9
4.3
9.5
14.5
5.5
12.2
18.7
3.5
7.8
12.1
6.0
13.4
20.5
3.2
7.1
10.8
7.3
16.2
24.9
6.4
14.1
21.6
4.3
9.5
14.5

Thermal capacity
Fully pumped heating system, flow temperature/return temperature
Inlet airflow temperature
Outlet airflow temperature
Water flow rate
Water-side differential pressure
Static differential pressure

05/2015 DE/en

Heat exchanger

TOC

Quick sizing

WT

WT for TVJ, TVT and EN

Nominal size
l/s
1000 400
1000 400
1000 400
500 500
500 500
500 500
600 500
600 500
600 500
700 500
700 500
700 500
800 500
800 500
800 500
900 500
900 500
900 500
1000 500
1000 500
1000 500
600 600
600 600
600 600
800 600
800 600
800 600
1000 600
1000 600
1000 600
800 800
800 800
800 800
1000 800
1000 800
1000 800
1000 1000
1000 1000
1000 1000
:
PWW:
te :
ta:
w:
pv:
pst:

05/2015 DE/en

800
1600
2400
500
1000
1500
600
1200
1800
700
1400
2100
800
1600
2400
900
1800
2700
1000
2000
3000
720
1440
2160
960
1920
2880
1200
2400
3600
1280
2560
3840
1600
3200
4800
2000
4000
6000

pst
m/h
2880
5760
8640
1800
3600
5400
2160
4320
6480
2520
5040
7560
2880
5760
8640
3240
6480
9720
3600
7200
10800
2592
5184
7776
3456
6912
10368
4320
8640
12960
4608
9216
13824
5760
11520
17280
7200
14400
21600

Pa
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170
25
80
170

PWW 50/40, te = 16 C

kW
14.96
22.98
28.93
9.35
14.36
18.08
11.22
17.24
21.69
13.09
20.11
25.31
14.96
22.98
28.93
16.83
52.86
32.54
18.70
28.73
36.16
13.47
20.69
26.03
17.96
27.58
34.71
22.45
34.47
43.39
23.94
36.77
46.28
29.93
45.97
57.85
37.41
57.46
72.31

ta

C
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0
31.5
27.9
26.0

kg/h
1287
1977
2488
804
1235
1555
965
1482
1866
1126
1729
2177
1287
1977
2488
1448
2224
2799
1609
2471
3109
1158
1779
2239
1544
2372
2985
1930
2965
3731
2059
3162
3980
2574
3953
4975
3217
4941
6219

pv

kPa
5.1
11.3
17.3
5.5
12.3
18.8
5.6
12.4
19.0
3.8
8.3
12.8
5.2
11.5
17.7
7.0
15.4
23.6
5.1
11.3
17.3
4.1
9.1
14.0
5.9
13.0
19.9
5.1
11.3
17.3
5.9
13.0
19.9
5.1
11.3
17.3
5.1
11.3
17.3

PWW 70/55, te = 16 C

kW
24.12
36.99
46.53
15.07
23.12
29.08
18.09
27.75
34.90
21.10
32.37
40.72
24.12
36.99
46.53
27.13
41.62
52.35
30.15
46.24
58.17
21.71
33.30
41.88
28.94
44.39
55.84
36.18
55.49
69.80
38.59
59.19
74.45
48.23
73.99
93.07
60.29
92.49
116.33

ta

C
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1
41.0
35.2
32.1

kg/h
1383
2121
2668
864
1326
1667
1037
1591
2001
1210
1856
2334
1383
2121
2668
1556
2386
3001
1728
2651
3335
1244
1909
2401
1659
2545
3202
2074
3182
4002
2212
3394
4269
2765
4242
5336
3457
5303
6670

pv

kPa
5.5
12.2
18.7
6.0
13.4
20.5
6.1
13.4
20.6
4.1
9.1
13.9
5.7
12.5
19.2
7.6
16.7
25.5
5.5
12.2
18.7
4.5
9.9
15.2
6.4
14.1
21.6
5.5
12.2
18.7
6.4
14.1
21.6
5.5
12.2
18.7
5.5
12.2
18.7

Thermal capacity
Fully pumped heating system, flow temperature/return temperature
Inlet airflow temperature
Outlet airflow temperature
Water flow rate
Water-side differential pressure
Static differential pressure

K5 5.1 21

Heat exchanger

TOC

Dimensions and weight


Dimensions

WT

WT


L

Heat exchangers Type WT

Dimensions and weight WT for TZ-Silenzio and TVZ


Nominal size

125
160
200
250
315
400

B
70
70
70
70
70
70

198
308
458
598
798
898

H
152
152
210
201
252
354

B1
232
342
492
632
832
932

B2

mm
258
368
518
658
868
958

B3
336
446
596
736
936
1036

H1
186
186
244
235
286
388

H2
212
212
263
263
314
416

D4

"

kg

10
10
10
10
10
10

2.4
3.3
4.8
6.0
8.7
12.7

Dimensions and weight WT for TVJ, TVT and EN


Nominal size
200 100
300 100
400 100
500 100
600 100
300 150
200 200
300 200
400 200
500 200
600 200
700 200
800 200
400 250
500 250
600 250

K5 5.1 22

B
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80

200
300
400
500
600
300
200
300
400
500
600
700
800
400
500
600

H
100
100
100
100
100
150
200
200
200
200
200
200
200
250
250
250

B1
234
334
434
534
634
334
234
334
434
534
634
734
834
434
534
634

B2

mm
276
376
476
576
676
376
276
376
476
576
676
776
876
476
576
676

B3
338
438
538
638
738
438
338
438
538
638
738
838
938
538
638
738

H1
134
134
134
134
134
184
234
234
234
234
234
234
234
284
284
284

H2
176
176
176
176
176
210
276
276
276
276
276
276
276
310
310
310

D4
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13

"

kg

1.3
1.7
2.1
2.5
2.9
2.1
1.9
2.5
3.0
4.0
5.0
6.0
7.0
3.9
4.9
5.8

05/2015 DE/en

Heat exchanger

TOC

Dimensions and weight


Dimensions

WT

WT


L

Heat exchangers Type WT

Dimensions and weight WT for TVJ, TVT and EN


Nominal size
300 300
400 300
500 300
600 300
700 300
800 300
900 300
1000 300
400 400
500 400
600 400
700 400
800 400
900 400
1000 400
600 600
800 600
1000 600
800 800
1000 800
1000 1000

05/2015 DE/en

B
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80

100
100
100

300
400
500
600
700
800
900
1000
400
500
500
600
600
700
700
800
800
900
900
1000
1000
600
800
1000
800
1000
1000

H
300
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
400
400
400
400
400
600
600
600
800
800
1000

B1
334
434
534
634
734
834
934
1034
434
534
534
634
634
734
734
834
834
934
934
1034
1034
634
834
1034
834
1034
1034

B2

B3

H1

H2

376
476
576
676
776
876
976
1076
476
576
576
676
676
776
776
876
876
976
976
1076
1076
676
876
1076
876
1076
1076

438
538
638
738
838
938
1038
1138
538
638
638
738
738
838
838
938
938
1038
1038
1138
1138
738
938
1138
938
1138
1138

334
334
334
334
334
334
334
334
434
434
434
434
434
434
434
434
434
434
434
434
434
634
634
634
834
834
1034

376
376
376
376
376
376
376
376
476
476
476
476
476
476
476
476
476
476
476
476
476
676
676
676
876
876
1076

mm

D4
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13

"

kg

1
1
1
1

3.2
4.5
5.8
6.5
7.2
7.9
8.5
9.2
6.5
8.7
7.3
8.1
9.6
10.5
8.9
9.7
11.4
10.5
12.3
11.2
13.2
11.1
13.9
15.9
17.7
20.2
27.9

K5 5.1 23

Heat exchanger

TOC

Specification text

WT

Rectangular hot water heat exchangers


for reheating the airflow in air conditioning
systems. Dimensions fit VAV terminal
units TZ-Silenzio, TVZ, TVJ, and TVT,
as well as CAV controllers EN.
Flanges on both sides,
suitable for duct connection.
Casing air leakage to EN 15727,
class D (H 400 mm, class C)

Technical data
Volume flow rate range:
15 to 6000 l/s or 55 to 21600 m/h
Thermal capacity: 0.4 115 kW
Maximum water temperature: 100 C
Maximum water-side operating pressure:
16 bar
Water-side differential pressure: 0.1 25 kPa
Static differential pressure: 25 170 Pa

Materials and surfaces


Casing made of galvanised sheet steel
Copper tubes
Aluminium fins

Sizing data
[m/h]
te[C]
PWW[C]
[kW]

Order options

Type
WT
Hot water heat exchanger
for VAV terminal units TZ-Silenzio
and TVZ

Nominal size
125
160
200
250
315
400

Order options

Type
WT
Hot water heat exchanger
for CAV controllers EN
and for VAV terminal units TVJ and TVT

Nominal size [mm]


BH

Standard text

K5 5.1 24

05/2015 DE/en

TOC

5.2

X X Grundlagen

und Definitionentestregistrierung

Heat transfer

Basic information
and nomenclature

Product selection
Principal dimensions
Nomenclature

05/2015 DE/en

K5 5.2 1

Heat transfer

TOC

Basic information and nomenclature


Product selection

Type
WT

WL

EL

Function
Heating
Cooling
Energy transfer medium
Hot water
Electric current

Duct connection
Circular
Rectangular

Can be used with VAV terminal unit Type


TVR
TVZ

TZ-Silenzio

TVJ

TVT

RN
EN

VFC

Possible
Not possible

Principal dimensions

D [mm]
Outside diameter of the spigot

H [mm]
Duct height

L [mm]
Length of unit including connecting spigot

H [mm]
Screw hole pitch of flange (vertical)

L [mm]
Length of casing or acoustic cladding

H [mm]
Outside dimension of flange (height)

B [mm]
Duct width

H [mm]
Unit height

B [mm]
Screw hole pitch of flange (horizontal)

R ['']
Diameter of connecting threaded pipes

B [mm]
Outside dimension of flange (width)

m [kg]
Unit weight including the minimum required
attachments (e.g. Compact controller)

B [mm]
Width of device
Nomenclature

[m/h] and [l/s]


Volume flow rate
pst [Pa]
Static differential pressure
pv [kPa]
Water-side differential pressure
[kW]
Thermal capacity

PWW [C]
Pumped warm water heating system,
flow temperature/return temperature
te [C]
Inlet airflow temperature
ta [C]
Outlet airflow temperature

w [kg/h]
Water flow rate

K5 5.2 2

05/2015 DE/en

TOC

Product index
AK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 1

RETROFIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 80

AK-Ex. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 22

RN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 1

AKK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 12

RN-Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 48

Open/Close actuators . . . . . . . . . . . . . . . . . . . . . . . . 3.3 1

Static differential pressure transducers . . . . . . . . . . 4.2 5

CA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 1

TA-Silenzio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 96

CAK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 30

TS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 22

CF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 15

TVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 113

Compact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 9

TVJ. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 32

CS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 8

TVLK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 184

Dynamic differential pressure transducers . . . . . . . 4.2 1

TVM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 149

Easy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 1

TVR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 11

Adjustment devices . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4 1

TVR-Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 202

EL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1 7

TVRK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 164

EN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 35

TVT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 56

EN-Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 59

TVZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 113

Basic information and nomenclature

TX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 25

Shut-off and flow adjustment. . . . . . . . . . . . . . . . . . . 3.4 1

TZ-Silenzio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 79

Basic information and nomenclature

Universal, dynamic. . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 30

CONSTANTFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 1

Universal, static . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 43

Basic information and nomenclature

VAV terminal units . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 11

VARYCONTROL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5 1

VFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 17

Basic information and nomenclature

VFL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 26

Volume flow rate measurement. . . . . . . . . . . . . . . . . 4.3 1

VFR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 1

Basic information and nomenclature

VME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 15

Heat transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 1

VMLK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 40

LVC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 1

VMR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 1

Min/Max actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 1

VMRK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 27

Modulating acuators. . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 11

WL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1 1

Modulating acuators. . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 12

WT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1 15

Retrofit kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 17


RC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 89

05/2015 DE/en

K5 Z 1

TOC

Disclaimer

Disclaimer
The information provided in this product catalogue is without obligation and does in particular not constitute a guarantee of the properties of a product. The described applications are
not binding but are rather meant for general information as they may vary from case to case.
The products and systems shown are examples. Some products and systems shown may have
been designed for individual customers and hence represent customised solutions. Some of
these products and systems come with special parts or equipment that is only available at
a surcharge. Technical data is subject to change due to the results of ongoing research and
development. The information regarding the scope of delivery, appearance, performance,
dimensions, and weights was correct at the time of going to press. For up-to-date information please refer to our website www.troxtechnik.com. Subject to change. All rights reserved.
Feature requests are binding only if they are included in the sales contract. Terms of delivery
and technical details are subject to change.
All business relationships with TROX GmbH are subject to our General Terms and Conditions valid at that time. These Terms and Conditions are available on our website
http://www.troxtechnik.com/en/site_services/dpt/index.html. Alternatively, we will send
them to you upon request.
This edition replaces all previous editions.

K5 Z 2

05/2015 DE/en

TOC

TROX Contact information

The art of handling air


TROX GmbH

Phone +49 (0) 28 45 202-0


Fax +49 (0) 28 45 202-265
E-mail trox@trox.de

Heinrich-Trox-Platz
47504 Neukirchen-Vluyn

TROX Germany

TROX International

North branch
Hannover oce
Bothfelder Strae 23
30916 Isernhagen, Germany
Phone +49 (0) 511 61003435
Fax
+49 (0) 511 619820
E-mail nln@trox.de

Subsidiaries

South branch
Munich oce
Liebigstrae 2
85301 Schweitenkirchen, Germany
Phone +49 (0) 8444 9250
Fax
+49 (0) 8444 92510
E-mail nls@trox.de
Central branch
Frankfurt oce
Kaiserleistrae 43
63067 Oenbach, Germany
Phone +49 (0) 69 985560
Fax
+49 (0) 69 98556111
E-mail nlm@trox.de

Argentina
TROX Argentina S.A.

Netherlands
TROX Nederland B.V.

Australia
TROX Australia Pty Ltd

Norway
TROX Auranor Norge AS

Belgium
S.A. TROX Belgium N.V.

Austria
TROX Austria GmbH

Brazil
TROX do Brasil Ltda.

Poland
TROX Austria GmbH

Bulgaria
TROX Austria GmbH

Romania
TROX Austria GmbH

China
TROX Air Conditioning Components
(Suzhou) Co., Ltd.

Russia
OOO TROX RUS

Denmark
TROX Danmark A/S

Serbia
TROX Austria GmbH

France
TROX France Sarl

Spain
TROX Espaa, S.A.

Southwest branch
Stuttgart oce
Hohentwielstrae 28
70199 Stuttgart, Germany
Phone +49 (0) 711 648620
Fax
+49 (0) 711 6486220
E-mail nlsw@trox.de

Great Britain
TROX UK Ltd.

West branch
Neukirchen-Vluyn oce
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn, Germany
Phone +49 (0) 2845 202611
Fax
+49 (0) 2845 202612
E-mail nlw@trox.de

Italy
TROX Italia S.p.A.

East branch
Berlin oce
Rotherstrae 18
10245 Berlin, Germany
Phone +49 (0) 30 2618051
Fax
+49 (0) 30 2629078
E-mail nlobb@trox.de

Mexico
TROX Mexico S.A. de C.V.

Foreign representatives

Dresden oce
Zur Wetterwarte 50, Haus 337/G
01109 Dresden, Germany
Phone +49 (0) 351 889091112
Fax
+49 (0) 351 8890910
E-mail nlobd@trox.de

Abu Dhabi
Egypt
Bosnia-Herzegovina
Finland
Greece
Indonesia
Ireland

05/2015 DE/en

Switzerland
TROX HESCO Schweiz AG

South Africa
TROX South Africa (Pty) Ltd

Hong Kong
TROX Hong Kong Ltd.

Czech Republic
TROX Austria GmbH

India
TROX INDIA Pvt. Ltd.

Turkey
TROX TURKEY LTD. STI.
Hungary
TROX Austria GmbH

Croatia
TROX Austria GmbH
Malaysia
TROX Malaysia Sdn. Bhd.

Iceland
Israel
Latvia
Lithuania
Malta
Morocco
New Zealand

USA
TROX USA, Inc.
United Arab Emirates
TROX Middle East (LLC)

Oman
Pakistan
Philippines
Portugal
Sweden
Slovak Republic
Slovenia

South Korea
Taiwan
Thailand
Ukraine
Uruguay
Vietnam
Zimbabwe

K5 Z 3

TOC

Control Units
2015

The art of handling air


TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Phone +49(0) 28 45 202-0


Fax
+49(0) 28 45 202-265
www.troxtechnik.com