Академический Документы
Профессиональный Документы
Культура Документы
ANALYSIS
H. Wallace Tinsley III
Member, IEEE
Eaton Electrical
130 Commonwealth Drive
Warrendale, PA 15086
Michael Hodder
Member, IEEE
Eaton Electrical
4120B Sladeview Cres
Mississauga, ON L5L 5Z3
INTRODUCTION
Upon completing the initial arc flash analysis, the next step
is to review the results of the study with the facility safety,
maintenance and electrical staff.
Prior to labeling the
equipment, several items need to be addressed in order to
finalize the arc flash analysis calculations.
A.
Aidan M. Graham
Senior Member, IEEE
Eaton Electrical
13205 SE 30th St, Ste 101
Bellevue, WA 98005
>0
1.2
< 1.2
<4
<8
< 25
25
< 40
PRESENTED AT THE 2007 IEEE IAS PULP AND PAPER INDUSTRY CONFERENCE IN WILLIAMSBURG, VA: IEEE 2007 - PERSONAL USE OF THIS MATERIAL IS PERMITTED.
A.
than 125 kVA, labels should still be provided for these locations
and are typically labeled as hazard risk category zero.
Single-phase and DC Equipment: Generic warning labels
may be placed on single-phase and direct-current (DC)
equipment, but no published standards presently provide the
calculation methods for these circuits. One should not assume
that there is no hazard at these locations, but any quantification
of energy will be based on preliminary testing, personal
experience, and reasonable hypothesis.
Equipment not Routinely Accessed: As stated in NEC
Section 110.16, the labels are applicable to those locations
likely to require examination, adjustment, servicing or
maintenance will energized. [3] In contrast, labels do not need
to be applied to equipment locations that are not routinely
accessed while energized. For example, in most cases,
transformers, junction boxes, and conduit need not be labeled.
C. Selecting Meaningful Information for Labels.
With this flexibility to customize the labels, care should be
given to provide adequate, meaningful information to qualified
persons without overwhelming the reader.
Generic arc flash warning labels meet the minimum
requirements, but do not provide quantification of the hazard. A
qualified person is required by OSHA to be able to determine
the hazards and the boundaries associated with the work to be
performed. The Arc Flash Hazard and the associated Flash
Protection Boundary are included in this requirement. If the arc
flash warning label does not display this information, the
qualified person must either determine the hazard(s) and the
boundaries by an approved calculation method or they are
required to reference some previous documentation containing
these calculations for the location in question.
The information on the labels should be selected to reflect
the established safety policy and procedures of a given facility.
The labels should not be designed to replace or inclusively
duplicate to contents of the safety policy.
New
Calculated
Energy
(cal/cm^2)
1.44
New
Calculated
HRC
where:
2
( )
0.208-1 kV
1.641
0.208-1 kV
Switchgear
1.473
1-15 kV
Switchgear
0.973
E Dx = Y
System
Distance x
Equipment Type
Voltage (kV)
Factor
Equation 1
E
D
x
36
1182.9288
x
t 610
E = C f En
x
0.2 D
Enter New
Working
Distance
Calculated
x
Y = E (D )
E.
Quantity of Labels
on job
require
training
specific
B.
2.
3.
VII. CONCLUSION
The Arc Flash Safety Program is not complete after the
calculations are done. There are many other steps to be taken
which include:
- Reducing the arc flash hazard at locations above
acceptable thresholds
- Implementation of the recommendations or changes
- Communication and training to affected employees
- Proper and meaningful labeling
In addition, there is ongoing maintenance required to
achieve a successful arc flash safety program.
VIII. ACKNOWLEDGEMENT
The authors thank W. S. Vilcheck for his sponsorship,
advice, and encouragement.
IX. REFERENCES
[1]
[2]
[3]
X.
BIOGRAPHIES