Академический Документы
Профессиональный Документы
Культура Документы
mimic panel connections indicated in the manual were accommplished. The bypass valve in the
located after the pump and the drain valve at the bottom of the process vessel were closed and
the air vent valve was opened. The software displayed the panel for the valve voltage input and
the voltage output for the level transducer. Pump 2 was set to manual and its control knob was
turned to minimum. The run button was clicked in the software and the valve voltage was set to
10 V. The manual control for pump 2 was turned to achieve the right flow rate at which it is
manageable for the experimenters to read and record the corresponding transducer voltage for
the height readings in the process vessel. For every 10 mm increment in the height starting at 10
mm, the person assigned to the process vessel will give the signal so that the person assigned to
the computer will read the transducer voltage. The person assigned to record then writes the
transducer voltage reading with the corresponding water level in the process vessel in a table.
The data table produced was then compared to the manufacturer indicated boundary conditions
of 0 V at 0 mm and 10 V at 180 mm to determine the calibration needed by the level transducer.
Lastly, the height recorded in the table was plotted with the corresponding output voltage to
produce the characteristic curve for the level transducer.
For procedure 4-1, the circuit file exp1-4.ict was opened and the memory was cleared
of data from previous experiments. The drain valve was then fully opened. After that, the
necessary mimic panel connections were done as shown in the manual and pump 2 was switched
to external . The valve and pump input voltage panel , the level transducer voltage output and
plot versus time was displayed by the software. The voltage for pump 2 was set to 4 V and the
voltage for the valve was set to 10 V. After that, the run and record button were clicked in the
software. The pump voltage was then finely adjusted so that the water level would stabilize just
above the heat exchanger. After reaching the desired equilibrium level,the system was allowed to
run for ten minutes to ensure that the height of the water was stable. The achieved equilibrium
level was labeled A and the level and flow rate for this was recorded on paper. Next, the pump
voltage was increased by 0.5 volts and the system was monitored and allowed to reach a higher
steady state water level. The next level reached by the water was labeled B and the
corresponding height reading and flow voltage were written down. The stop button was clicked
and the data recorded by the software was exported into a text file. Using the data produced in
the procedure, the water level versus time plot was produced and the time constant () was
derived using all the three methods previously enumerated. Finally, the resulting time constant
for each method used was compared to each other.
Results and Discussions
The data acquired for transducer voltage with the corresponding height readings on the
process vessel were tabulated as shown below.
Water Level
(mm)
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
12
10
8
Transducer Voltage
6
4
2
0
0
50
100
150
200
250
12
10
8
Voltage
6
4
2
0
0
200
400
600
Based on Figure 4 and observation on the encoded data in the file, the filling process to
reach level B began at 1,118.7 seconds and stabilized at 1548.7 seconds with a difference of 430
seconds. Taking the 63.2% of this results to 271.76 which is the time constant. The table
produced for the h/q method is shown below.
Level
A
Level
B
Flow(
V)
3.3
Flow(L/m
in.)
3.3
Flow(m^
2/s)
0.000055
h(m)
3.5
3.5
0.000058
333
0.000003
333
0.172
Area(m
^2)
R
0.054
Dif
0.118
0.017
671
16201
.62
286.3
063
For the h/q method, the time constant computed is 286.3063, which is 5.4% larger
than the result from the plot estimation.
The block diagram for the system experiment 4 procedure 1 was made and shown in the figure
below.
Conclusion
References