Вы находитесь на странице: 1из 157

HC HEAT - EXCHANGERS

Index
page 1 of 2
01-10-2009

CATALOGUE INDEX

PAGE

PRODUCT

DESCRIPTION
WELCOME TO HC

COILS

CUSTOMER COILS

HCV-500-A

AIR COOLED CONDENSER

12

HCV-630-A

AIR COOLED CONDENSER

16

HCV-800-A

AIR COOLED CONDENSER

21

HVV-500-A

V SHAPED AIR COOLED CONDENSER

25

HVV-630-B

V SHAPED AIR COOLED CONDENSER

28

HVV-800-B

V SHAPED AIR COOLED CONDENSER

32

HAV-350-A

REMOTE AIR COOLED CONDENSER

35

HAV-400-A

REMOTE AIR COOLED CONDENSER

38

HAV-500-A

REMOTE AIR COOLED CONDENSER

41

HCB-200-A

AIR COOLED CONDENSER + BASE

44

HCB-250-B

AIR COOLED CONDENSER + BASE

47

HCBC-300-A AIR COOLED CONDENSER + BASE

50

HCB-300-A

AIR COOLED CONDENSER + BASE

53

HCB-350-A

AIR COOLED CONDENSER + BASE

56

HCB-400-A

AIR COOLED CONDENSER + BASE

59

HCB-500-B

AIR COOLED CONDENSER + BASE

62

HCB-630-D AIR COOLED CONDENSER + BASE

65

HLR

LIQUID RECEIVER

Note: subject to change without notice

Index
page 2 of 2
01-10-2009

CATALOGUE INDEX

PAGE PRODUCT

DESCRIPTION

68

RONDO - B

UNIT COOLER

72

HWM-300 - A

WALL MOUNTED COOLER

75

HDD 200

DUAL DISCHARGE UNIT COOLER

78

HDD 250

DUAL DISCHARGE UNIT COOLER

82

HDD 300

DUAL DISCHARGE UNIT COOLER

87

HDD 350

DUAL DISCHARGE UNIT COOLER

93

HDD 500

DUAL DISCHARGE UNIT COOLER

101

HCT-250

LOW SILHOUETTE UNIT COOLER

104

HCR-300
HCR 300

LOW SILHOUETTE UNIT COOLER

107

HDR-300

UNIT COOLER

110

HSR-300

UNIT COOLER

114

HSR-350

UNIT COOLER

117

HSR-50

UNIT COOLER

121

HRR-5081,7&22/(5

126

HPR-500

UNIT COOLER

131

HMR-630

UNIT COOLER

136

HDC-500

DRY-COOLER

139

HDC-63

DRY-COOLER

142

Appendix A

UNIT COOLER CORRECTION FACTORS

146

Appendix B

EC FAN WIRING- 500mm Fan

149

Appendix C

EC FAN WIRING- 800mm Fan

153

Appendix D

Catalogue Summery
Note:subjecttochangewithoutnotice

WELCOME TO HC HEAT-EXCHANGERS (Pty) Ltd


The Heatingg Centre ggroupp was founded in 1973 and rapidly
p y built a reputation
p
for superb
p
engineering and manufacture of airconditioning and refrigeration systems and components.
Quality and service was a key contribution to this success.
For a period from 1995 to 2001 the company was owned by a German concern, which traded as
Gntner SA. After the Germans withdrew from South Africa the Company was re-purchased
and opened as HC Heat-Exchangers concentrating on customized coils, refrigeration unit
coolers and condensers
condensers.
HC Heat-Exchangers has drawn from its rich engineering background to supply you, the
customer, with an unsurpassed product in terms of engineering, quality and service.
HC Heat-Exchangers credits its success to the committed people who make up this family.
The HC family is proud to introduce this catalogue and looks forward to a mutually beneficial
association with you
you.

On behalf of HC Heat-Exchangers

Robert Kruger
Managing Director

Page 4

Page 5

COILS
Page 1 of 2
01-10-2009

HC HEAT - EXCHANGERS
CUSTOMER COILS
General Description

HC Heat-Exchangers manufacture a wide range of plate fin type coils for air conditioning,refrigeration and
industrial applications suitable for chilled water, hot water, steam, evaporator and condenser systems.
Tubes are mechanicaly expanded into plate fins and after brazing all coils are leak tested to 3200 kPa
using dry Nitrogen under water.Tube options are 9.53mm, 12 mm and 15.88 mm OD copper tube (plane
or rifle bore) or 12 mm OD 304L stainless steel tubes. Fin options are aluminium, copper and coated
aluminium while casings are available in galvanised iron, aluminium stainless steel or copper.
Only the finest materials are used to give a top quality product with a long, trouble free service life.
Coil selections are computer generated to accomodate the many variables encountered.

NOMENCLATURE
X XX - XX - XX x XXXX x X R x XX F x XX C
Tube Material

No of circuits

Coil Type

Fins per inch

Fin pattern

Rows deep

No tubes high

Finned length [mm]

Fin Pattern
Tube size

3A

3B

3C

9.53mm

4A

12mm

4B

5A

5B

15.88mm

Coil Type:

3A

3B

3C

4A

4B

5A

5B

Chilled water [CW]


Hot Water [HW]
Steam [ST]
Condenser [AC]
Evaporator [DX]
Flooded ammonia[FA]

*CW-3A

*CW-3B

*CW-3C

**CW-4A

*CW-4B

*CW-5A

*CW-5B

*HW-3A

*HW-3B

*HW-3C

**HW-4A

*HW-4B

*HW-5A

*HW-5B

*ST-3A

*ST-3B

*ST-3C

**ST-4A

*ST-4B

*ST-5A

*ST-5B

*AC-3A

*AC-3B

*AC-3C

**AC-4A

*AC-4B

*AC-5A

*AC-5B

*DX-3A

*DX-3B

*DX-3C

**DX-4A

*DX-4B

*DX-5A

*DX-5B

SFA-4A

SFA-4B

* = plain copper, rifle bore copper

** Plain copper, rifle bore copper , 304 stainless steel

Tube Material

Fin Material

Casing Material

P = Plain Copper

Al = Aluminium

Gi = Galvanised iron

R = Rifle bore copper

Cu = Plain copper

Al = stainless steel

S = 304 Stainless steel

Ep = coated aluminium

Cu = plain copper

Page 6

Note:subjecttochangewithoutnotice

COILS
Page 2 of 2
01-10-2009

HC HEAT - EXCHANGERS
CUSTOMER COILS

Data Required for Coil Selections


DATA

Typical Print-out

CW HW ST AC DX FA

Capacity

kW

Air Flow
Air Inlet temp

m3/s
C (DB & WB)

Air Outlet temp

C (DB & WB)

Water Flow

l/s

Water Inlet Temp

Water Outlet temp

Condensing Temp

Evaporating temp

X
X
X
X
X
X
X

X
X
X
X
X
X
X

Refrigerant
Steam Pressure

kPa

Steam Temp

Altitude

Size H x L

mm x mm

X
X

X
X

X
X
X
X

X
X
X

X
X

X
X
X
X

X
X

X
X
X
X

X
X
X
X

X
X

X
X

X
X

---------- CONDENSER CALCULATOR REPORT -------03/12/2009


RAC-3A - 23 x 2250 x 4R x 12.00F x 11.43C - Ri/Al
COIL DESIGN
Tubing
Height
Length
Tube rows
Fin spacing
Circuits
BAROMETER
Atmospheric pressure
Altitude
AIR
Entering temperature
Leaving temperature
RH ON
RH OFF
Mass flow
Volume flow
Face velocity
Pressure drop
Fan

X
X

Typical Example
Condensing THR:
Air flow
Air on coil
Condensing Temp
Refrigerant
Altitude:
Size (H x L)

66kW
5 m3/s
30.0 /20.0 C
45 C
R22
Sea level
600 x 3360 mm

101.36 kPa
0.00 m
30/20.04 C
41.22/23.27 C
40 %
21.50 %
5.814 kg/s
5.023 m3/s
3.725 m/s
143.03 Pa
3.00 x
EBM S4D 500

REFRIGERANT (R22)
Condensing temperature
Desuperheating
Subcooling
Mass flow
Charge
Pressure drop
40.54 kPa
DUTY
Total duty

Notes:

For fluids other than water, ethylene glycol


or propylene glycol the following would
also be required:
Density
Heat capacity
Conductivity
Viscosity

10.1 x 0.3 mm
23.6 in.
2250 mm.
4
12 fpi
11.43

45.00 C
0.00 K
3.00 K
0.406 kg/s
4.66 kg
66.849 kW

kg/m3
kJ/kgK
kW.mKx1e6
mg/ms

40

40

40

FINNED

FIN

AIR VENT
CHILLED W ATER
OUT

150

BSPM

CENTRE PLATE
IF 1500 mm O R
LONGER

150

AIR FLOW

BSPM
CHILLED W ATER
IN
DRAIN

40
150
MAX OVER
BENDS

50

150

BSPM
CHILLED W ATER
IN

LEFT HAND
CONNECTION

RIGHT HAND
CO NNECTION

MO UNTING HOLES 10.15 AT 150 CRS

Page 7

Note:subjecttochangewithoutnotice

HCV - 500 - B
Page 1 of 4
31-10-2011

HC HEAT - EXCHANGERS
HCV RANGE OF AIR COOLED CONDENSER
WITH FLOATING COILS AND 500mm FANS

General Description
The HCV-501-B to -508-B range of Air Cooled Condensers comprises 32models covering duties from
21.9kW to 233.4kW total heat rejection at 15K ITD. The range of low profile appearance units is ideal for
roof-mounted applications. The low noise level modular fan arrangement is well suited to economical fan
cycling head pressure control. Each unit is factory wired to a terminal strip in a terminal box. The coil
incorporates our floating coil construction, eliminating tube failure at the tube plates, with resultant refrigerant
loss and thus ensures a long trouble-free service life.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fins

Coated Al fins

Galvanised steel casing


Epoxy powder coated finish

430 Stainless steel casing

EC modulating fans

RAL-7032 Kiesel grey colour

Fan cycling head pressure control

Baffled individual fan sections

Horizontal air discharge

Vertical air discharge

Multiple system operation

Single system operation

230/1/50 Hz fan motor

400/3/50 Hz fan motor

Nomenclature
H C V 501 B 4R - 2S
HC Heat-Exchangers
No. of systems
Air cooled condenser
No. of coil rows (2, 3 or 4 row)
V = Vertical air flow
H = Horizontal air flow

Vintage

Fan diameter -cm

No. of fans

Page 8

Note: subject to change without notice

HCV - 500 - B
Page 2 of 4
31-10-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 500mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

501-2R 501-3R 501-4R 502-2R 502-3R 502-4R 503-2R 503-3R 503-4R 504-2R 504-3R 504-4R

1.5

1.8

2.0

2.9

3.5

3.9

4.3

5.3

5.8

5.7

7.1

7.8

10

14.6

18.0

19.8

28.9

35.5

39.0

43.3

53.2

58.4

57.4

70.9

77.8

11

16.0

19.8

21.8

31.8

39.0

42.8

47.6

58.5

64.2

63.1

78.0

85.6

12

17.5

21.6

23.8

34.6

42.6

46.7

52.0

63.8

70.0

68.9

85.1

93.4

13

19.0

23.4

25.8

37.5

46.1

50.6

56.3

69.2

75.9

74.6

92.2

101.1

14

20.4

25.2

27.7

40.4

49.6

54.5

60.6

74.5

81.7

80.3

99.3

108.9

15

21.9

27.0

29.7

43.3

53.2

58.4

64.9

79.8

87.5

86.1

106.4

116.7

16

23.3

28.8

31.7

46.2

56.7

62.3

69.3

85.1

93.4

91.8

113.5

124.5

17

24.8

30.6

33.7

49.1

60.3

66.2

73.6

90.4

99.2

97.6

120.6

132.3

18

26.2

32.4

35.7

52.0

63.8

70.1

77.9

95.7

105.0

103.3

127.7

140.0

19

27.7

34.2

37.6

54.8

67.4

74.0

82.3

101.1

110.9

109.0

134.8

147.8

20

29.2

36.0

39.6

57.7

70.9

77.9

86.6

106.4

116.7

114.8

141.9

155.6

No. of fans

m3/s
inch

2.42

2.26

2.12

4.81

4.48

4.19

7.21

6.72

6.28

9.64

8.97

8.38

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

1 3/8"

1 3/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

2 1/8"

1 System Outlet OD

inch

5/8"

5/8"

5/8"

7/8"

7/8"

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

2 System Inlet OD

inch

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

1 3/8"

1 3/8"

2 System Outlet OD

inch

1/2"

1/2"
0.70

1/2"

5/8"

5/8"
1.35

5/8"

5/8"

7/8"
2.02

7/8"

7/8"

7/8"
2.70

7/8"

litres

4.06

6.09

8.12

9.84

14.76

19.68

11.53

17.29

23.05

15.56

22.82

30.43

R22

1.17

1.71

2.25

2.22

3.29

4.34

3.34

4.94

6.56

4.66

6.58

8.74

R404A

1.3

1.90

2.5

2.47

3.66

4.83

3.72

5.5

7.31

5.34

7.34

9.75

R134a

1.11

1.61

2.12

2.09

3.09

4.08

3.14

4.64

6.17

4.2

6.19

8.22

R22
Pump - down capacity
R404A
kg @ 80%
R134a

3.6

5.4

7.2

8.7

13.1

17.5

10.2

15.4

20.5

13.8

20.3

27.0

3.1

4.6

6.1

7.4

11.1

14.9

8.7

13.0

17.4

11.8

17.2

23.0

3.7

5.5

7.3

8.9

13.3

17.8

10.4

15.6

20.8

14.1

20.6

27.5

Air quantity
1 System Intlet OD

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

Net mass kg

m2

Al fin

92

97

102

140

149

158

185

199

213

231

249

267

Cu fin

102

112

122

158

178

197

214

242

270

269

306

343

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 120 kW
Ambient design condition: 36C
Altitude: 1800m
Condensing temperature: 50 C
Refrigerant: R404A

Capacity Correction
Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 36C = 14C
Correction Factor R404A = 1.03
Correction Factor 1800m = 0.88
Required capacity at catalogue conditions:
120 kW 1.03 0.88 = 132.4kW THR required at
14C ITD, Refrigerant R22, Altitude 0m
At 14C ITD the "HCV-505-4R" gives 136.4 kW
Select the "HCV-505-4R"

Page 9

Note: subject to change without notice

HCV - 500 - B
Page 3 of 4
31-10-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 500mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

505-2R 505-3R 505-4R 506-2R 506-3R 506-4R 507-2R 507-3R 507-4R 508-2R 508-3R 508-4R

7.2

8.9

9.7

8.6

10.7

11.7

10.0

12.4

13.6

11.5

14.1

15.6

10

71.7

88.7

97.4

86.1

106.6

116.7

100.4

124.1

136.1

114.8

140.8

155.6

11

78.9

97.5

107.1

94.7

117.3

128.4

110.5

136.5

149.7

126.3

154.9

171.2

12

86.1

106.4

116.9

103.3

127.9

140.1

120.5

149.0

163.4

137.7

168.9

186.7

13

93.3

115.3

126.6

111.9

138.6

151.8

130.6

161.4

177.0

149.2

183.0

202.3

14

100.4

124.1

136.4

120.5

149.2

163.4

140.6

173.8

190.6

160.7

197.1

217.8

15

107.6

133.0

146.1

129.1

159.9

175.1

150.7

186.2

204.2

172.2

211.2

233.4

16

114.8

141.9

155.8

137.7

170.6

186.8

160.7

198.6

217.8

183.6

225.3

249.0

17

122.0

150.7

165.6

146.3

181.2

198.4

170.7

211.0

231.4

195.1

239.3

264.5

18

129.1

159.6

175.3

155.0

191.9

210.1

180.8

223.4

245.0

206.6

253.4

280.1

19

136.3

168.5

185.1

163.6

202.5

221.8

190.8

235.9

258.7

218.1

267.5

295.6

20

143.5

177.3

194.8

172.2

213.2

233.5

200.9

248.3

272.3

229.6

281.6

311.2

No. of fans

m3/s
inch

12.05

11.21

10.47

14.46

13.45

12.57

16.87

15.69

14.66

19.28

17.98

16.76

1 5/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

1 System Outlet OD

inch

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 1/8"

1 1/8"

1 3/8"

1 1/8"

1 3/8"

1 3/8"

2 System Inlet OD

inch

1 3/8"

1 3/8"

1 3/8"

1 3/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

2 1/8"

2 System Outlet OD

inch

7/8"

7/8"
3.37

7/8"

7/8"

7/8"
4.05

1 1/8"

7/8"

1 1/8"
4.72

1 1/8"

1 1/8"

1 1/8"
5.39

1 1/8"

litres

19.33

28.35

37.80

23.09

33.88

45.17

26.86

39.41

52.54

30.62

45.93

59.91

R22

5.82

8.23

10.85

6.99

9.88

13.12

8.15

11.52

15.3

9.31

13.86

17.49

R404A

6.67

9.18

12.09

11.01

14.63

9.34

12.84

17.06

10.6

15.70

19.7

R134a

5.52

7.74

10.12

6.72

9.29

12.34

7.84

10.83

14.38

8.84

13.1

16.45

R22
Pump - down capacity
R404A
kg @ 80%
R134a

17.2

25.2

33.6

50.5

30.1

40.1

23.9

35.0

46.7

27.2

40.8

53.2

14.6

21.4

28.5

20.9

25.6

34.1

20.3

29.7

39.7

23.1

34.7

45.2
54.1

Air quantity
1 System Intlet OD

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

Net mass kg

m2

17.5

25.6

34.1

17.4

30.6

40.8

24.3

35.6

47.5

27.7

41.5

Al fin

292

314

336

334

361

388

391

422

453

437

473

509

Cu fin

340

386

432

391

446

501

458

523

588

513

587

661

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 120 kW
Ambient design condition: 36C
Altitude: 1800m
Condensing temperature: 50 C
Refrigerant: R404A

Capacity Correction
Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 36C = 14C
Correction Factor R404A = 1.03
Correction Factor 1800m = 0.88
Required capacity at catalogue conditions:
120 kW 1.03 0.88 = 132.4kW THR required at
14C ITD, Refrigerant R22, Altitude 0m
At 14C ITD the "HCV-505-4R" gives 136.4 kW
Select the "HCV-505-4R"

Page 10

Note: subject to change without notice

HCV - 500 - B
Page 4 of 4
31-10-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 500mm FANS

HCV

Note:
- Center leg on models 505 & larger
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
AC 500mm diameter
400/ 3/50 Hz.
0.72 kW 1.41 A Each.

Coil:
- 3/8" Rifle bore copper tube
- Aluminium fin
- 12 fins per inch

HCH

Fan Wiring
Motor

Diameter
mm
3 Phase DELTA
500
EC
500
1 Phase
500
L1 L2 L3

TOP TOP

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Voltage
V
400
400
230

Frequency
Hz
50
50
50

Speed
rpm
1390
1440
1300

Power Amperage
W
A
720
1.41
1050
1.90
680
3.00

Standard
Optional
Optional

NOTE: SEE APPEDIX B FOR EC FAN WIRING


L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 11

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216201

Note: subject to change without notice

HCV - 630 - B
Page 1 of 4
15-07-2011

HC HEAT - EXCHANGERS
HCV RANGE OF AIR COOLED CONDENSER
WITH FLOATING COILS AND 630mm FANS

General Description
The HCV-631-B to -636-B range of Air Cooled Condensers comprises 18 models covering duties from
48.4kW to 420.9 kW total heat rejection at 15K ITD. The range of low profile appearance units is ideal for
roof-mounted applications. The low noise level modular fan arrangement is well suited to economical fan
cycling head pressure control. Each unit is factory wired to a terminal strip in a terminal box. The coil
incorporates our floating coil construction, eliminating tube failure at the tube plates, with resultant refrigerant
loss and thus ensures a long trouble-free service life.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fins

Coated Al fins

Galvanised steel casing

430 Stainless steel casing

Epoxy powder coated finish

Fan cycling head pressure control

RAL-7032 Kiesel grey colour

Horizontal air discharge

Baffled individual fan sections

Multiple system operation

Vertical air discharge


Single system operation
400/3/50 Hz fan motor

Nomenclature
H C V 631 B 4R - 2S
HC Heat-Exchangers
No. of systems
Air cooled condenser
No. of coil rows (2, 3 or 4 row)
V = Vertical air flow
H = Horizontal air flow

Vintage

Fan diameter -cm

No. of fans

Page 12

Note: subject to change without notice

HCV - 630 - B
Page 2 of 4
15-07-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 630mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

631-2R 631-3R 631-4R 632-2R 632-3R 632-4R 633-2R 633-3R 633-4R

3.2

4.1

4.7

6.5

8.2

9.4

9.7

12.4

14.0

10

32.3

41.0

46.5

64.8

82.4

93.5

97.2

123.6

140.3

11

35.5

45.2

51.2

71.3

90.6

102.9

106.9

136.0

154.3

12

38.7

49.3

55.9

77.8

98.9

112.2

116.6

148.3

168.3

13

41.9

53.4

60.5

84.2

107.1

121.6

126.4

160.7

182.3

14

45.2

57.5

65.2

90.7

115.4

130.9

136.1

173.0

196.4

15

48.4

61.6

69.8

97.2

123.6

140.3

145.8

185.4

210.4

16

51.6

65.7

74.5

103.7

131.8

149.7

155.5

197.8

224.4

17

54.9

69.8

79.1

110.1

140.1

159.0

165.2

210.1

238.5

18

58.1

73.9

83.8

116.6

148.3

168.4

175.0

222.5

252.5

19

61.3

78.0

88.4

123.1

156.6

177.7

184.7

234.8

266.5

20

64.5

82.1

93.1

129.6

164.8

187.1

194.4

247.2

280.5

No. of fans

m3/s
inch

5.33

5.19

5.04

10.67

10.39

10.11

16.00

15.58

15.17

1 3/8"

1 3/8"

1 3/8"

1 5/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 5/8"

1 System Outlet OD

inch

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

2 System Inlet OD

inch

1 3/8"

1 3/8"

1 3/8"

2 System Outlet OD

inch

5/8"

7/8"
3.05

7/8"

Air quantity
1 System Intlet OD

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

m2

4.57

litres

9.39

14.09

18.78

18.69

28.04

37.38

27.59

41.39

R22

2.65

3.89

5.15

5.34

7.84

10.36

8.01

11.76

15.55

R404A

2.96

4.34

5.74

5.95

8.74

11.55

8.93

13.11

17.34

R134a

2.54

3.70

4.89

5.07

7.45

9.84

7.61

11.17

14.77

R22

8.3

12.5

16.7

16.6

24.9

33.2

24.5

36.8

49.0

7.1

10.6

14.2

14.3

21.4

28.5

20.8

31.2

41.7

8.5

12.7

17.0

16.9

25.3

33.8

24.9

37.4

49.8

Pump - down capacity


R404A
kg @ 80%
R134a
Net mass kg

1.51

55.18

Al fin

169

183

197

278

306

334

397

439

481

Cu fin

202

233

264

345

407

469

498

590

682

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 115 kW
Ambient design condition: 32C
Altitude: 1600m
Condensing temperature: 45 C
Refrigerant: R507

Capacity Correction Factors:


R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 32C = 13C
Correction Factor R507 = 1.03
Correction Factor 1600m = 0.9
Required capacity at catalogue conditions:
115 kW 1.03 0.9 = 124 kW THR required at
13C ITD, Refrigerant R22, Altitude 0m
At 13C ITD the "HCV-633-2R" gives 126.4 kW
Select the "HCV-633-2R"

Page 13

Note: subject to change without notice

HCV - 630 - B
Page 3 of 4
15-07-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 630mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

634-2R 634-3R 634-4R 635-2R 635-3R 635-4R 636-2R 636-3R 636-4R

13.0

16.5

18.7

16.2

20.6

23.4

19.4

24.7

28.1

10

129.6

164.8

187.1

162.0

206.1

233.8

194.4

247.3

280.6

11

142.6

181.3

205.8

178.2

226.7

257.2

213.8

272.0

308.7

12

155.5

197.8

224.5

194.4

247.3

280.6

233.3

296.7

336.7

13

168.5

214.2

243.2

210.6

267.9

303.9

252.7

321.4

364.8

14

181.4

230.7

261.9

226.8

288.5

327.3

272.2

346.2

392.8

15

194.4

247.2

280.6

243.0

309.1

350.7

291.6

370.9

420.9

16

207.4

263.7

299.3

259.2

329.7

374.1

311.0

395.6

449.0

17

220.3

280.2

318.0

275.4

350.3

397.5

330.5

420.4

477.0

18

233.3

296.6

336.7

291.6

370.9

420.8

349.9

445.1

505.1

19

246.2

313.1

355.4

307.8

391.5

444.2

369.4

469.8

533.1

20

259.2

329.6

374.1

324.0

412.1

467.6

388.8

494.5

561.2

No. of fans

Air quantity

m3/s

21.34

20.78

20.22

26.68

25.98

25.28

32.02

31.18

30.34

1 System Intlet OD

inch

2 1/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

1 3/8"

1 5/8"

1 5/8"

1 System Outlet OD

inch

1 3/8"

1 3/8"

1 3/8"

1 3/8"

1 5/8"

1 5/8"

2 System Inlet OD

inch

1 5/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 System Outlet OD

inch
m2

1 1/8"

1 1/8"
6.10

1 1/8"

1 1/8"

1 3/8"
9.14

1 3/8"

litres

36.49

54.74

72.98

45.39

68.09

90.78

54.30

81.45

108.60

R22

10.68

15.68

20.73

13.35

19.60

25.92

16.01

23.52

31.10

R404A

11.91

17.48

23.11

14.89

21.85

28.90

17.85

26.22

34.92

R134a

10.15

14.90

19.69

12.68

18.62

24.62

15.21

22.34

29.44

R22
Pump - down capacity
R404A
kg @ 80%
R134a

32.4

48.6

64.8

40.3

60.5

80.6

48.2

72.3

96.4

27.6

41.3

55.1

34.3

51.4

68.5

41.0

61.5

82.0
98.1

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

Net mass kg

7.62

33.0

49.4

65.9

41.0

61.5

82.0

49.0

73.6

Al fin

504

560

616

627

696

765

734

817

900

Cu fin

639

762

885

796

949

1102

936

1120

1304

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 115 kW
Ambient design condition: 32C
Altitude: 1600m
Condensing temperature: 45 C
Refrigerant: R507

Capacity Correction
Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 32C = 13C
Correction Factor R507 = 1.03
Correction Factor 1600m = 0.9
Required capacity at catalogue conditions:
115 kW 1.03 0.9 = 124 kW THR required at
13C ITD, Refrigerant R22, Altitude 0m
At 13C ITD the "HCV-633-2R" gives 126.4 kW
Select the "HCV-633-2R"

Page 14

Note: subject to change without notice

HCV - 630 - B
Page 4 of 4
15-07-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 630mm FANS

HCV

Note:
- Centre leg on models 633 & larger
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
- AC 630mm diameter
- 400/3/50 Hz.
- 2.63 kW 4.78 A Each.

Coil:
- 12mm Rifle bore copper tube
- Aluminium fin
- 12 fins per inch

HCH

Fan Wiring
Motor

Diameter
mm

Voltage
V

Frequency
Hz

Speed
rpm

3 Phase DELTA
3 Phase STAR
EC

630
630
630

400
400
400

50
50
50

1320
1050
1510

L1 L2 L3

TOP TOP

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Power Amperage
W
A

2630
1750
3200

4.78
2.95
5

Standard
Optional
Optional

E
L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 15

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216201

Note: subject to change without notice

HCV - 800 - B
Page 1 of 4
15-07-2011

HC HEAT - EXCHANGERS
HCV RANGE OF AIR COOLED CONDENSER
WITH FLOATING COILS AND 800mm FANS

General Description
The HCV-801-B to -806-B range of Air Cooled Condensers comprises 18 models covering duties from 62.1
kW to 513.3 kW total heat rejection at 15K ITD. The range of low profile appearance units is ideal for roofmounted applications. The low noise level modular fan arrangement is well suited to economical fan cycling
head pressure control. Each unit is factory wired to a terminal strip in a terminal box. The coil incorporates
our floating coil construction, eliminating tube failure at the tube plates, with resultant refrigerant loss and
thus ensures a long trouble-free service life.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fins

Coated Al fins

Galvanised steel casing

430 Stainless steel casing

Epoxy powder coated finish

Horizontal air discharge

RAL-7032 Kiesel grey colour

Multiple system operation

Baffled individual fan sections

400/3/50 Hz AC Fan motor

Vertical air discharge


Single system operation
EC 800mm Modulating fans

Nomenclature
H C V 801 B 4R - 2S
HC Heat-Exchangers
No. of systems
Air cooled condenser
No. of coil rows (2, 3 or 4 row)
V = Vertical air flow
H = Horizontal air flow

Vintage

Fan diameter -cm

No. of fans

Page 16

Note: subject to change without notice

HCV - 800 - B
Page 2 of 4
15-07-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

801-2R 801-3R 801-4R 802-2R 802-3R 802-4R 803-2R 803-3R 803-4R

4.1

5.2

5.8

8.1

10.2

11.4

12.2

15.3

17.1

10

41.4

51.7

57.8

81.3

101.5

114.1

122.0

152.7

171.1

11

45.5

56.9

63.6

89.5

111.7

125.5

134.2

168.0

188.2

12

49.7

62.0

69.4

97.6

121.8

136.9

146.4

183.3

205.3

13

53.8

67.2

75.2

105.7

132.0

148.3

158.6

198.6

222.4

14

58.0

72.4

81.0

113.9

142.1

159.7

170.8

213.8

239.5

15

62.1

77.5

86.8

122.0

152.3

171.1

183.0

229.1

256.6

16

66.2

82.7

92.6

130.1

162.5

182.5

195.2

244.4

273.7

17

70.4

87.9

98.3

138.3

172.6

193.9

207.4

259.6

290.8

18

74.5

93.0

104.1

146.4

182.8

205.3

219.6

274.9

307.9

19

78.6

98.2

109.9

154.5

192.9

216.7

231.8

290.2

325.0

20

82.8

103.4

115.7

162.7

203.1

228.1

244.0

305.5

342.1

No. of fans

m3/s
inch

6.47

6.24

6.02

12.86

12.40

11.96

19.29

18.59

17.94

1 3/8"

1 5/8"

1 5/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 5/8"

2 5/8"

1 System Outlet OD

inch

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

1 3/8"

2 System Inlet OD

inch

1 3/8"

1 5/8"

1 5/8"

2 System Outlet OD

inch

7/8"

7/8"
3.05

7/8"

Air quantity
1 System Intlet OD

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

m2

4.57

litres

11.83

17.74

23.65

22.54

33.80

45.07

33.33

50.00

R22

3.63

5.38

7.07

6.94

10.41

13.56

10.41

15.41

20.34

R404A

4.05

6.00

7.88

7.74

11.61

11.63

11.61

17.18

17.47

R134a

3.45

5.11

6.72

6.59

9.89

13.79

9.89

14.64

20.69

R22

10.5

15.8

21.0

20.0

30.0

40.0

29.6

44.4

59.2

9.0

13.5

18.0

17.2

25.8

34.3

25.4

38.1

50.8

10.7

16.0

21.4

20.4

30.5

40.7

30.1

45.2

60.2

Pump - down capacity


R404A
kg @ 80%
R134a
Net mass kg

1.51

66.66

Al fin

214

233

252

367

404

441

526

581

636

Cu fin

260

302

344

456

537

618

659

781

903

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 320 kW
Ambient design condition: 35C
Altitude: 1800m
Condensing temperature: 50 C
Refrigerant: R22

Capacity Correction Factors:


R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 35C = 15C
Correction Factor R22 = 1
Correction Factor 1800m = 0.88
Required capacity at catalogue conditions:
320 kW 1 0.88 = 363 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HCV-806-2R" gives 366.0 kW
Select the "HCV-806-2R"

Page 17

Note: subject to change without notice

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

HCV - 800 - B
Page 3 of 4
15-07-2011

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

804-2R 804-3R 804-4R 805-2R 805-3R 805-4R 806-2R 806-3R 806-4R

16.3

20.3

22.8

20.3

25.4

28.5

24.4

30.5

34.2

10

162.7

203.1

228.1

203.3

253.9

285.1

244.0

305.5

342.2

11

178.9

223.4

250.9

223.7

279.3

313.6

268.4

336.0

376.4

12

195.2

243.7

273.8

244.0

304.6

342.2

292.8

366.6

410.6

13

211.5

264.0

296.6

264.3

330.0

370.7

317.2

397.1

444.9

14

227.7

284.3

319.4

284.7

355.4

399.2

341.6

427.7

479.1

15

244.0

304.6

342.2

305.0

380.8

427.7

366.0

458.2

513.3

16

260.3

324.9

365.0

325.3

406.2

456.2

390.4

488.7

547.5

17

276.5

345.2

387.8

345.7

431.6

484.7

414.8

519.3

581.7

18

292.8

365.5

410.6

366.0

457.0

513.2

439.2

549.8

616.0

19

309.1

385.8

433.5

386.3

482.3

541.8

463.6

580.4

650.2

20

325.3

406.1

456.3

406.7

507.7

570.3

488.0

610.9

684.4

No. of fans

Air quantity

m3/s

25.72

24.79

23.92

32.14

30.99

29.90

38.57

37.19

35.88

1 System Intlet OD

inch

2 5/8"

2 5/8"

2 5/8"

2 5/8"

3 1/8"

3 1/8"

3 1/8"

3 1/8"

3 1/8"

1 5/8"

1 5/8"

2 1/8"

1 System Outlet OD

inch

1 3/8"

1 5/8"

1 5/8"

1 5/8"

2 1/8"

2 1/8"

2 System Inlet OD

inch

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 5/8"

2 5/8"

2 System Outlet OD

inch
m2

1 1/8"

1 1/8"
6.10

1 1/8"

1 3/8"

1 3/8"
9.14

1 3/8"

litres

44.12

66.17

88.23

54.90

82.35

109.80

65.70

98.55

131.40

R22

13.88

20.82

27.12

17.35

26.03

33.90

20.82

30.82

40.68

R404A

15.48

23.21

23.27

19.35

29.02

29.09

23.21

34.36

34.90

R134a

13.19

19.78

27.58

16.48

24.73

34.48

19.78

29.28

41.37

R22
Pump - down capacity
R404A
kg @ 80%
R134a

29.4

44.1

58.8

48.8

73.1

97.5

58.4

87.5

116.7

25.2

37.8

50.4

41.8

62.7

83.7

50.1

75.1

100.1
118.7

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

Net mass kg

7.62

29.9

44.8

59.8

49.6

74.4

99.2

59.4

89.0

Al fin

672

745

818

835

926

1017

981

1090

1199

Cu fin

850

1012

1174

1057

1259

1461

1247

1489

1731

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 320 kW
Ambient design condition: 35C
Altitude: 1800m
Condensing temperature: 50 C
Refrigerant: R22

Capacity Correction Factors:


R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 35C = 15C
Correction Factor R22 = 1
Correction Factor 1800m = 0.88
Required capacity at catalogue conditions:
320 kW 1 0.88 = 363 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HCV-806-2R" gives 366.0 kW
Select the "HCV-806-2R"

Page 18

Note: subject to change without notice

HCV - 800 - B
Page 4 of 4
15-07-2011

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

HCV

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
applications

Fan:
- EC 800mm diameter
- 2.56 kW 3.9 A Each.

Coil:
- 12mm Rifle bore copper tube
- Aluminium fin
- 12 fins per inch

HCH

Fan Wiring
Motor

Diameter
mm
EC
800
3 Phase DELTA
800

Voltage
V
400
400

Frequency
Hz
50
50

Speed
rpm
1020
880

Power Amperage
W
A
2560
3.9
1940
3.9

Standard
Optional

Note: EC Wiring diagram located in appendix C

Page 19

Note: subject to change without notice

HCV RANGE OF AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

HCV - 800 - A
Page 5 of 5
01-10-2009

Fan Wiring
Motor
EC
3 Phase DELTA

Diameter
mm
800
800

Voltage
V
400
400

Frequency
Hz
50
50

Speed
rpm
1030
896

Power
W
2200
2000

Amperage
A
3.7
4.3

Standard
Optional

Note:ECWiringdiagramlocatedinappendixC

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 20

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HVV - 500 - A
Page 1 of 4
01-10-2009

HC HEAT - EXCHANGERS
V-SHAPED AIR COOLED CONDENSER
WITH FLOATING COILS AND 500mm FANS

General Description
The HVV-502 to -5010 range of Air Cooled Condensers comprises 15 models covering duties from 43kW
to 287.8kW total heat rejection at 15K ITD. The range of compact units is ideal for minimal footprint
applications.
The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control. Each unit is factory wired to a terminal strip in a terminal box. The coil incorporates our floating
coil construction, eliminating tube failure at the tube plates, with resultant refrigerant loss and thus
ensures a long and trouble-free service life.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin coil

Aluminium fins

Coated Al fin coil

Galvanised steel casing

430 Stainless steel casing

Epoxy powder coated finish

EC modulating fans

RAL-7032 Kiesel grey colour

230/1/50 Hz fan motor

Baffled individual fan sections

Fan cycling head pressure control

Vertical air discharge

Wire mesh screen

Dual system operation


400/3/50 Hz fan motor

Nomenclature
H V V 502 A 4R - 2S
HC Heat-Exchangers

No. of systems

V Shaped condenser

No. of coil rows (2, 3 or 4 row)

V = Vertical air flow

Vintage

Fan diameter -cm

No. of fans

Page 21

Note: subject to change without notice

HVV - 500 - A
Page 2 of 4
01-10-2009

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 500mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

502-2R 502-3R 502-4R 504-2R 504-3R 504-4R 506-2R 506-3R 506-4R

2.9

3.5

3.8

5.7

7.0

7.7

8.6

10.5

11.5

10

28.7

35.2

38.4

57.2

70.3

76.8

85.8

105.5

115.1

11

31.6

38.7

42.2

62.9

77.4

84.4

94.3

116.0

126.7

12

34.4

42.2

46.1

68.6

84.4

92.1

102.9

126.6

138.2

13

37.3

45.7

49.9

74.3

91.4

99.8

111.5

137.1

149.7

14

40.2

49.2

53.7

80.1

98.4

107.5

120.1

147.7

161.2

15

43.0

52.8

57.6

85.8

105.5

115.1

128.7

158.2

172.7

16

45.9

56.3

61.4

91.5

112.5

122.8

137.2

168.8

184.2

17

48.8

59.8

65.2

97.2

119.5

130.5

145.8

179.3

195.7

18

51.6

63.3

69.1

102.9

126.6

138.2

154.4

189.9

207.3

19

54.5

66.8

72.9

108.6

133.6

145.8

163.0

200.4

218.8

20

57.4

70.3

76.8

114.4

140.6

153.5

171.5

211.0

230.3

4.81

4.49

4.18

9.62

8.97

8.36

14.43

13.46

12.54

2 System Inlet OD

m3/s
inch

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

1 3/8"

1 3/8"

2 System Outlet OD

inch

5/8"

5/8"

5/8"

3/4"

7/8"

7/8"

7/8"

7/8"

1 1/8"

No. of fans
Air quantity

Coil face area


Inter. Coil vol.

m2

1.38

2.76

4.14

litres

8.74

13.12

17.49

16.24

24.36

32.5

23.7

35.6

47.5

R22

2.34

3.48

4.62

4.76

6.98

9.24

7.14

10.46

13.86

Total refrigerant
operating charge kg

R404A

2.7

4.05

5.4

5.4

8.1

10.8

8.08

12.12

16.16

R134a

2.26

3.39

4.52

4.52

6.78

9.04

6.78

10.17

13.56

Total pump - down


capacity kg @ 80%

R22

7.77

11.65

15.54

14.43

21.64

28.85

21.08

31.63

42.2

R404A

6.6

9.9

13.20

12.26

18.39

24.51

17.91

26.87

35.8

R134a

7.9

11.85

15.8

14.67

22

29.3

21.4

32.16

42.9

Al fin

161

145

155

240

259

277

317

345

372

Cu fin

180

173

192

278

315

352

373

429

484

Alt m
Factor

0
1.00

200
0.99

400
0.97

600
0.96

800
0.95

1000
0.93

1200
0.92

Net mass kg

Altitude correction factors

1400
0.91

1600
0.90

1800
0.88

Example:
Required THR: 105 kW
Ambient design condition: 34C
Altitude: 200m
Condensing temperature: 50 C
Refrigerant: R407C

Capacity Correction Factors:


R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 34C = 16C
Correction Factor R407C = 0.87
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
105 kW 0.87 0.99 = 121.9 kW THR required at
16C ITD, Refrigerant R22, Altitude 0m
At 16C ITD the "HVV-504-4R" gives 122.8 kW
Select the "HVV-504-4R"

Page 22

Note: subject to change without notice

HVV - 500 - A
Page 3 of 4
01-10-2009

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 500mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

508-2R 508-3R 508-4R 5010-2R 5010-3R 5010-4R

11.4

14.1

15.4

14.3

17.6

19.2

10

114.4

140.7

153.5

142.9

175.8

191.9

11

125.8

154.7

168.9

157.2

193.4

211.1

12

137.2

168.8

184.2

171.5

211.0

230.3

13

148.7

182.8

199.6

185.8

228.5

249.5

14

160.1

196.9

214.9

200.1

246.1

268.7

15

171.5

211.0

230.3

214.4

263.7

287.9

16

183.0

225.0

245.6

228.7

281.3

307.0

17

194.4

239.1

261.0

243.0

298.9

326.2

18

205.8

253.2

276.3

257.3

316.5

345.4

19

217.3

267.2

291.7

271.6

334.0

364.6

20

228.7

281.3

307.1

285.9

351.6

383.8

No. of fans

10

Air quantity

m3/s

19.24

17.94

16.72

24.05

22.43

20.9

2 System Inlet OD

inch

1 3/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

1 5/8"

2 System Outlet OD

inch
m2

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

litres

31.2

46.8

62.5

38.7

58.1

R22

9.52

13.94

18.48

11.88

17.44

23.1

R404A

10.78

16.17

21.56

13.48

20.22

26.96

R134a

9.04

13.56

18.08

11.32

16.98

22.64

R22

27.7

41.6

55.5

34.4

51.6

68.8

R404A

23.6

35.4

47.1

29.2

43.8

58.5

R134a

28.2

42.3

56.4

35.0

52.5

70.0

Coil face area


Inter. Coil vol.
Total refrigerant
operating charge kg
Total pump - down
capacity kg @ 80%
Net mass kg

5.52

6.90
77.5

Al fin

412

448

484

504

548

593

Cu fin

486

560

633

597

688

780

Alt m
Factor

0
1.00

200
0.99

400
0.97

600
0.96

Altitude correction factors

800
0.95

1000
0.93

1200
0.92

1400
0.91

1600
0.90

1800
0.88

Example:
Required THR: 105 kW
Ambient design condition: 34C
Altitude: 200m
Condensing temperature: 50 C
Refrigerant: R407C

Capacity Correction
Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 34C = 16C
Correction Factor R407C = 0.87
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
105 kW 0.87 0.99 = 121.9 kW THR Required at
16C ITD, Refrigerant R22, Altitude 0m
At 16C ITD the "HVV-504-4R" gives 122.8 kW
Select the "HVV-504-4R"

Page 23

Note: subject to change without notice

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 500mm FANS

HVV - 500 - A
Page 4 of 4
01-10-2009

1190

3080
3140

1200
1500

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
AC 500mm diameter
400/3/50 Hz
0.82 kW 1.59A

HVV 502

Coil:

HVV 504

- 3/8" Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

HVV 506

740
1340
1940
2540

HVV 508

Motor

Diameter
mm
3 Phase DELTA
500
EC
500
1 Phase
500

L1 L2 L3

3140

HVV 5010

Fan Wiring

TOP TOP

Voltage
V
400
400
230

Frequency
Hz
50
50
50

Speed
rpm
1325
1450
1270

Power Amperage
W
A
820
1.59
1004
1.9
760
3.3

Standard
Optional
Optional

NOTE: EC Wiring diagram see Appendix B


L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 24

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216201

Note: subject to change without notice

HVV - 630 - B
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
V-SHAPED AIR COOLED CONDENSER
WITH FLOATING COILS AND 630mm FANS

General Description
The HVV-632 to -638 range of Air Cooled Condensers comprises 12 models covering duties from 97.2
kW to 556.5 kW total heat rejection at 15K ITD. The range of compact units is ideal for minimal footprint
applications.
The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control. Each unit is factory wired to a terminal strip in a terminal box. The coil incorporates our floating
coil construction, eliminating tube failure at the tube plates, with resultant refrigerant loss and thus
ensures a long and trouble-free service life.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin coils

Aluminium fins

Coated Al fin coils

Galvanised steel casing

430 Stainless steel casing

Epoxy powder coated finish

Fan cycling head pressure control

RAL-7032 Kiesel grey colour

Wire mesh screen

Baffled individual fan sections


Vertical air discharge
Dual system operation
400/3/50 Hz fan motor

Nomenclature
H V V 632 A 4R - 2S
HC Heat-Exchangers

No. of systems

V Shaped condenser

No. of coil rows (2, 3 or 4 row)

V = Vertical air flow

Vintage

Fan diameter -cm

No. of fans

Page 25

Note:subjecttochangewithoutnotice

HVV - 630 - B
Page 2 of 3
01-10-2009

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 630mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

632-2R 632-3R 632-4R 634-2R 634-3R 634-4R 636-2R 636-3R 636-4R 638-2R 638-3R 638-4R

6.5

8.2

9.3

13.0

16.4

18.6

19.4

24.6

27.8

25.9

32.8

37.1

10

64.8

81.9

92.7

129.7

163.8

185.5

194.5

245.7

278.3

259.3

327.7

371.0

11

71.3

90.1

102.0

142.6

180.2

204.1

213.9

270.3

306.1

285.2

360.4

408.1

12

77.8

98.3

111.3

155.6

196.6

222.6

233.4

294.9

333.9

311.1

393.2

445.2

13

84.3

106.5

120.6

168.6

212.9

241.2

252.8

319.5

361.7

337.0

426.0

482.3

14

90.7

114.7

129.8

181.5

229.3

259.7

272.3

344.0

389.6

363.0

458.7

519.4

15

97.2

122.9

139.1

194.5

245.7

278.3

291.7

368.6

417.4

388.9

491.5

556.5

16

103.7

131.1

148.4

207.5

262.1

296.9

311.1

393.2

445.2

414.8

524.3

593.6

17

110.2

139.3

157.6

220.4

278.5

315.4

330.6

417.7

473.1

440.8

557.0

630.7

18

116.7

147.5

166.9

233.4

294.8

334.0

350.0

442.3

500.9

466.7

589.8

667.8

19

123.2

155.7

176.2

246.4

311.2

352.5

369.5

466.9

528.7

492.6

622.6

704.9

20

129.6

163.9

185.5

259.3

327.6

371.1

388.9

491.5

556.5

518.5

655.3

742.0

No. of fans

10.68

10.4

10.11

21.36

20.80

20.22

32.04

31.21

30.34

42.73

41.61

40.45

2 System Inlet OD

m3/s
inch

1 3/8"

1 3/8"

1 3/8"

1 5/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 5/8"

2 1/8"

2 5/8"

2 5/8"

2 System Outlet OD

inch

7/8"

7/8"
3.05

7/8"

1 1/8"

1 1/8"
6.10

1 1/8"

1 1/8"

1 3/8"
9.14

1 3/8"

1 3/8"

1 3/8"
12.19

1 3/8"

litres

19.41

29.12

38.82

37.06

55.58

74.1

54.7

82.1

109.4

72.4

108.5

144.7

R22

5.54

8.24

10.8

11.1

16.5

21.6

16.6

24.7

32.52

22.16

32.96

43.36

R404A

6.32

9.38

12.3

12.6

18.7

24.6

16

28.14

36.95

25.28

37.52

49.28

R134a

5.32

7.84

10.2

10.6

15.6

20.4

18.9

23.52

30.66

21.28

31.36

40.88

R22

17.2

25.9

34.5

32.9

49.4

65.8

48.6

72.9

97.2

64.3

96.4

128.5

14.7

22.0

29.3

28.0

42.0

55.9

41.3

61.9

82.6

54.6

81.9

109.2

17.5

26.3

35.1

33.5

50.2

66.9

49.4

74.1

98.8

65.4

98.0

130.7

Al fin

357

388

419

610

671

732

861

952

1042

1112

1232

1352

Cu fin

435

505

575

767

907

1047

1096

1304

1513

1425

1702

1979

Air quantity

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

m2

Pump - down capacity


R404A
kg @ 80%
R134a
Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:

Capacity Correction Factors:


R134a:
R22:
R507:
R404A:
R407C:
R410A:

Required THR: 450 kW


Ambient design condition: 30C
Altitude: 1800m
Condensing temperature: 45 C
Refrigerant: R22

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15C
Correction Factor R22 = 1
Correction Factor 1800m = 0.88
Required capacity at catalogue conditions:
450 kW 1 0.88 = 511 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HVV-638-4R" gives 556.5 kW
Select the "HVV-638-4R"

Page 26

Note:subjecttochangewithoutnotice

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 630mm FANS

HVV - 630 - B
Page 3 of 3
01-10-2009

145

1650

2100

4200

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
AC 630mm diameter
400/ 3 / 50 Hz.
1.62 kW 5.2 A Each.

Coil:

1200

HVV 632

- 12mm Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

2200

HVV 634

3200

HVV 636

4200

HVV 638

Fan Wiring
Motor

Diameter
mm

Voltage
V

Frequency
Hz

Speed
rpm

3 Phase DELTA
3 Phase STAR

630
630

400
400

50
50

1340
1050

L1 L2 L3

TOP TOP

F1

Power Amperage
W
A

2530
1680

Standard
Optional

5.2
2.9

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 27

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216201

Note:subjecttochangewithoutnotice

HVV - 800 - B
Page 1 of 4
01-10-2009

HC HEAT - EXCHANGERS
V-SHAPED AIR COOLED CONDENSER
WITH FLOATING COILS AND 800mm FANS
General Description

The HVV-802 to -808 range of Air Cooled Condensers comprises 12 models covering duties from 121kW to
676 kW total heat rejection at 15K ITD. The range of compact units is ideal for minimal footprint
applications.
The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control. Each unit is factory wired to a terminal strip in a terminal box. The coil incorporates our floating coil
construction, eliminating tube failure at the tube plates, with resultant refrigerant loss and thus ensures a
long and trouble-free service life.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fins

Coated Al fins

Galvanised steel casing

430 Stainless steel casing

Epoxy powder coated finish

400/3/50 Hz Fan motor

RAL-7032 Kiesel grey colour

Wire mesh screen

Baffled individual fan sections


Vertical air discharge
Dual system operation
EC modulating fan

Nomenclature

H V V 802 A 4R - 2S
No. of systems

HC Heat-Exchangers

No. of coil rows (2, 3 or 4 row)

V Shaped condenser

Vintage

V = Vertical air flow

No. of fans

Fan diameter -cm


Page 28

Note:subjecttochangewithoutnotice

HVV - 800 - B
Page 2 of 4
01-10-2009

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

802-2R 802-3R 802-4R 804-2R 804-3R 804-4R 806-2R 806-3R 806-4R 808-2R 808-3R 808-4R

8.1

10.1

11.3

16.2

20.2

22.6

24.4

30.3

33.8

32.5

40.4

45.1

10

81.1

101.1

112.7

162.3

202.1

225.5

243.5

303.2

338.3

324.7

404.3

451.0

11

89.2

111.2

124.0

178.6

222.3

248.1

267.9

333.5

372.1

357.2

444.7

496.1

12

97.4

121.3

135.3

194.8

242.6

270.6

292.2

363.8

405.9

389.7

485.1

541.2

13

105.5

131.4

146.6

211.0

262.8

293.2

316.6

394.2

439.7

422.2

525.5

586.3

14

113.6

141.5

157.8

227.3

283.0

315.7

340.9

424.5

473.6

454.6

566.0

631.4

15

121.7

151.6

169.1

243.5

303.2

338.3

365.3

454.8

507.4

487.1

606.4

676.5

16

129.8

161.7

180.4

259.7

323.4

360.9

389.7

485.1

541.2

519.6

646.8

721.6

17

137.9

171.8

191.6

276.0

343.6

383.4

414.0

515.4

575.1

552.0

687.3

766.7

18

146.0

181.9

202.9

292.2

363.8

406.0

438.4

545.8

608.9

584.5

727.7

811.8

19

154.2

192.0

214.2

308.4

384.1

428.5

462.7

576.1

642.7

617.0

768.1

856.9

20

162.3

202.1

225.5

324.7

404.3

451.1

487.1

606.4

676.5

649.5

808.5

902.0

No. of fans

12.88

12.4

11.9

25.7

24.80

23.90

38.70

37.2

35.9

51.5

49.58

47.8

2 System Inlet OD

m3/s
inch

1 3/8"

1 5/8"

1 5/8"

2 1/8"

2 1/8"

2 1/8"

2 1/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

2 5/8"

2 System Outlet OD

inch

7/8"

7/8"
4.02

1 1/8"

1 1/8"

1 1/8"
8.04

1 1/8"

1 3/8"

1 3/8"
12.07

1 3/8"

1 3/8"

1 5/8"
16.09

1 5/8"

litres

25.41

38.1

50.80

48.70

73.1

97.4

72.0

108.0

144.0

95.3

142.9

190.6

R22

7.3

10.7

14.3

14.5

21.5

28.6

21.8

32.2

42.9

29.0

43.0

57.2

R404A

8.3

12.3

16.3

16.6

24.6

32.5

24.8

37.0

48.8

33.1

49.3

65.0

R134a

7.0

10.2

13.6

14.0

20.4

27.2

20.9

30.7

40.7

27.9

40.9

54.3

R22

22.6

33.8

45.1

43.3

64.9

86.5

64.0

95.9

127.9

84.6

126.9

169.3

Air quantity

Coil face area


Inter. Coil vol.
Refrigerant operating
charge kg

Pump - down capacity


R404A
kg @ 80%
R134a
Net mass kg

19.2

28.8

38.3

36.8

55.2

73.5

54.3

81.5

108.7

71.9

107.9

143.9

23.0

34.4

45.9

44.0

66.0

88.0

65.0

97.6

130.1

86.1

129.1

172.2

Al fin

525

565

606

897

978

1058

1269

1388

1507

1640

1799

1957

Cu fin

628

720

812

1106

1290

1474

1580

1855

2126

2054

2420

2785

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Example:
Required THR: 400 kW
Ambient design condition: 30C
Altitude: 1800m
Condensing temperature: 45 C
Refrigerant: R22

Capacity Correction Factors:


R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

ITD (Initial Temperature Difference)


ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15C
Correction Factor R22 = 1
Correction Factor 1800m = 0.88
Required capacity at catalogue conditions:
400 kW 1 0.88 = 454.5 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HVV-806-3R" gives 454.8 kW
Select the "HVV-806-3R"

Page 29

Note:subjecttochangewithoutnotice

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

HVV - 800 - B
Page 3 of 4
01-10-2009

272

2225

1953

4540

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

1240

HVV 802

Fan:
EC 800mm diameter
400/3/50 Hz
2.2kW x 3.7A Each

2340

HVV 804

3440

HVV 806

4540

HVV 808

Coil:
- 12mm Rifle bore copper tube
- Aluminium fin
- 12 fins per inch

Page 30

Note:subjecttochangewithoutnotice

HVV - 800 - B
Page 4 of 4
01-10-2009

V-SHAPED AIR COOLED CONDENSER


WITH FLOATING COILS AND 800mm FANS

Fan Wiring
Motor

Diameter

Voltage

Frequency

Speed

Power

Amperage

mm

Hz

rpm

EC

800

400

50

1030

2200

3.7

Standard

3 Phase DELTA

800

400

50

895

2000

4.3

Optional

Note:ECWiringdiagramlocatedinappendixC

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 31

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HAV-350-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HAV REMOTE AIR COOLED CONDENSER
WITH 350mm FANS

General Description
The new HAV-351 to 353 range of Remote Air Cooled Condensers comprises 9 models covering duties
from 6.5 kW to 25.2 kW total heat rejection at 15K ITD. The low noise level modular fan arrangement is
well suited to economical fan cycling head pressure control while high efficiency rifle bore tube enhances
performance. Each unit is factory wired to a terminal strip in a terminal box. The coil incorporates our
floating coil construction, eliminating tube failure at the tube plates, with resultant refrigerant loss, and
ensures a long trouble-free service life.

HAH

HAV

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated Al fins

Galvanized steel casing

430 Stainless steel casing

Floating coil construction

Legs

Vertical or Horizontal air discharge

400/3/50 Hz fan motor

CPO-5012 Hammer black color


230/1/50 Hz fan motor

Nomenclature
H A V 351 - A - 4R - 1S
HC Heat-Exchangers

No. of systems

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

V=Vertical H=Horizontal

Vintage

Fan diameter -cm

No. of fans

Page 32

Note: subject to change without notice

HAV-350-A
Page 2 of 3
01-10-2009

HAV REMOTE AIR COOLED CONDENSER


WITH 350mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

351-2R 351-3R 351-4R 352-2R 352-3R 352-4R 353-2R 353-3R 353-4R

0.4

0.5

0.6

0.9

1.0

1.1

1.3

1.6

1.7

10

4.3

5.2

5.6

8.7

10.5

11.2

13.1

15.7

16.8

11

4.8

5.7

6.2

9.6

11.5

12.3

14.4

17.2

18.5

12

5.2

6.2

6.7

10.5

12.6

13.4

15.7

18.8

20.1

13

5.6

6.8

7.3

11.3

13.6

14.5

17.0

20.3

21.8

14

6.1

7.3

7.9

12.2

14.7

15.7

18.3

21.9

23.5

15

6.5

7.8

8.4

13.1

15.7

16.8

19.6

23.5

25.2

16

6.9

8.3

9.0

14.0

16.7

17.9

20.9

25.0

26.9

17

7.4

8.8

9.5

14.8

17.8

19.0

22.2

26.6

28.5

18

7.8

9.4

10.1

15.7

18.8

20.1

23.6

28.2

30.2

19

8.2

9.9

10.7

16.6

19.9

21.3

24.9

29.7

31.9

20

8.7

10.4

11.2

17.4

20.9

22.4

26.2

31.3

33.6

0.708

0.645

0.594

1.42

1.29

1.19

2.123

1.94

1.781

1 System Inlet OD

m3/s
inch

5/8"

5/8"

5/8"

3/4"

3/4"

7/8"

7/8"

7/8"

7/8"

1 System Outlet OD

inch

1/2"

1/2"
0.23

1/2"

1/2"

5/8"

5/8"

5/8"

5/8"

5/8"

Coil face area


Inter. Coil vol.
Condenser refrigerant
operating charge kg
Total Pump - down
capacity kg @ 80%
Net mass kg

No. of fans
Air quantity

m2

0.46

0.69

liters

1.50

2.25

3.00

2.80

4.19

5.59

4.09

6.14

R22

0.40

0.59

0.76

0.78

1.15

1.55

1.18

1.75

2.32

R404A

0.44

0.67

0.88

0.90

1.33

1.76

1.35

2.00

2.64

R134a

0.39

0.55

0.72

0.75

1.11

1.45

1.13

1.67

2.17

R22

1.33

2.00

2.67

2.49

3.72

4.97

3.63

5.46

7.28

R404A

1.13

1.69

2.26

2.11

3.16

4.21

3.08

4.63

6.17

R134a

1.36

2.03

2.71

2.53

3.79

5.05

3.70

5.55

7.40

Al fin

22

23

25

41

44

51

59

64

73

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Density
Capacity Correction Factors:
multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

8.19

Factor

Refrigeration Densities @ 44C

R134a:
R22:
R507:
R404A:
R407C:
R410A:

kg/m

kg/l

R12

1238.1

1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 19 kW
Ambient design condition: 30C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
19 kW 0.98 0.99 = 19.58 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HAV-353-2R" gives 19.6 kW
Select the "HAV-353-2R"

Page 33

Note: subject to change without notice

HAV REMOTE AIR COOLED CONDENSER


WITH 350mm FANS

HAV-350-A
Page 3 of 3
01-10-2009

430
300

30

30

HAV 351

500
1000

HAV 352
HAV 353

1500
1690

130

60
30

457

517

30

Note:

Note:

- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
AC 350mm diameter
0.132 kW 0.58 A Each.

Coil:
- 3/8" Rife bore copper tube
- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC
AC

Diameter
mm
350
350

L1 N

Voltage
V
230
400

Frequency
Hz
50
50

Speed
rpm
1400
1365

Power
W
130
115

Amperage
A
0.58
0.42

Standard
Optional

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 34

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HAV-400-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HAV REMOTE AIR COOLED CONDENSER
WITH 400mm FANS
General Description

The new HAV-401 to 403 range of Remote Air Cooled Condensers comprises 9 models covering duties from
9.5 kW to 37.2 kW total heat rejection at 15K ITD. The low noise level modular fan arrangement is well suited
to economical fan cycling head pressure control while high efficiency rifle bore tube enhances performance.
Each unit is factory wired to a terminal strip in a terminal box. The coil incorporates our floating coil
construction, eliminating tube failure at the tube plates, with resultant refrigerant loss, and ensures a long
trouble-free service life.

HAH

HAV

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated Al fins

Galvanized steel casing

430 Stainless steel casing

Floating coil construction

Legs

Vertical or Horizontal air discharge

400/3/50 Hz fan motor

CPO-5012 Hammer black color


400/3/50 Hz fan motor

Nomenclature
H A V 401 - A - 4R - 1S
HC Heat-Exchangers

No. of systems

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

V=Vertical H=Horizontal

Vintage

Fan diameter -cm

No. of fans
Page 35

Note:subjecttochangewithoutnotice

HAV-400-A
Page 2 of 3
01-10-2009

HAV REMOTE AIR COOLED CONDENSER


WITH 400mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

401-2R 401-3R 401-4R 402-2R 402-3R 402-4R 403-2R 403-3R 403-4R

0.6

0.8

0.8

1.3

1.5

1.7

1.9

2.3

2.5

10

6.3

7.6

8.3

12.6

15.3

16.5

19.0

22.9

24.8

11

7.0

8.4

9.1

13.9

16.8

18.2

20.9

25.2

27.3

12

7.6

9.2

9.9

15.1

18.3

19.9

22.8

27.5

29.8

13

8.3

9.9

10.8

16.4

19.9

21.5

24.7

29.8

32.3

14

8.9

10.7

11.6

17.7

21.4

23.2

26.6

32.1

34.7

15

9.5

11.5

12.4

18.9

22.9

24.8

28.5

34.4

37.2

16

10.2

12.2

13.2

20.2

24.4

26.5

30.4

36.7

39.7

17

10.8

13.0

14.1

21.4

26.0

28.1

32.3

39.0

42.2

18

11.4

13.7

14.9

22.7

27.5

29.8

34.2

41.2

44.7

19

12.1

14.5

15.7

24.0

29.0

31.4

36.1

43.5

47.2

20

12.7

15.3

16.6

25.2

30.5

33.1

38.0

45.8

49.6

0.979

0.916

0.858

1.96

1.83

1.72

2.936

2.75

2.575

1 System Inlet OD

m3/s
inch

5/8"

5/8"

3/4"

3/4"

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 System Outlet OD

inch

1/2"

1/2"
0.37

1/2"

5/8"

5/8"

5/8"

3/4"

3/4"

3/4"

No. of fans
Air quantity

Coil face area


Inter. Coil vol.
Condenser refrigerant
operating charge kg
Total Pump - down
capacity kg @ 80%
Net mass kg

0.73

1.10

liters

2.52

3.63

4.84

4.49

6.74

8.99

6.57

9.85

13.14

R22

0.62

0.93

1.23

1.27

1.86

2.47

1.87

2.79

3.70

R404A

0.71

1.06

1.41

1.43

2.13

2.80

2.15

3.20

4.20

R134a

0.60

0.89

1.14

1.19

1.77

2.33

1.79

2.66

3.50

R22

2.24

3.23

4.30

3.99

5.99

7.99

5.84

8.75

11.67

R404A

1.90

2.73

3.65

3.38

5.08

6.77

4.95

7.42

9.90

R134a

2.28

3.28

4.37

4.06

6.09

8.12

5.94

8.90

11.87

Al fin

29

32

34

56

61

71

80

87

103

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Density
Capacity Correction Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 22 kW
Ambient design condition: 30C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
22 kW 0.98 0.99 = 22.67 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HAV-402-3R" gives 22.9 kW
Select the "HAV-402-3R"

Page 36

Note:subjecttochangewithoutnotice

HAV-400-A
Page 3 of 3
01-10-2009

HAV REMOTE AIR COOLED CONDENSER


WITH 400mm FANS

430
300

30

30

IN
HAV 401

600

HAV 402

OUT

670
1200
1800

HAV 403

1990

130

60

Note:

Note:

- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:

AC 400mm diameter
0.135 kW 0.76 A Each.

Coil:

- 3/8" Rife bore copper tube


- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC

AC

Diameter
mm
400
400

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Voltage
V
400
230

Frequency
Hz
50
50

Speed
rpm
1450
1430

Power
W
135
160

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 37

Amperage
A
0.76
0.73

Standard
Optional

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HAV-500-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
REMOTE AIR COOLED CONDENSER
WITH 500mm FANS

General Description
The new HAV-501 to 503 range of Remote Air Cooled Condensers comprises 9 models covering duties
from 20.1 kW to 79.6 kW total heat rejection at 15K ITD. The low noise level modular fan arrangement is
well suited to economical fan cycling head pressure control. Each unit is factory wired to a terminal strip in a
terminal box. The coil incorporates our floating coil construction, eliminating tube failure at the tube plates,
with resultant refrigerant loss, and ensures a long trouble-free service life.

HAH

HAV

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated Al fins

Galvanised steel casing

430 Stainless steel casing

Vertical or Horizontal air discharge

Legs

CPO-5012 Hammer black colour

230/1/50 Hz fan motor

400/3/50 Hz fan motor

Nomenclature
H A V 501 - A - 4R - 1S
HC Heat-Exchangers

No. of systems

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

V = Vertical H = Vertical

Vintage

Fan diameter -cm

No. of fans

Page 38

Note: subject to change without notice

HAV-500-A
Page 2 of 3
01-10-2009

REMOTE AIR COOLED CONDENSER


WITH 500mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

501-2R 501-3R 501-4R 502-2R 502-3R 502-4R 503-2R 503-3R 503-4R

1.3

1.6

1.8

2.7

3.3

3.5

4.0

4.9

5.3

10

13.4

16.3

17.7

26.8

32.6

35.4

40.1

48.9

53.1

11

14.8

17.9

19.5

29.4

35.9

38.9

44.1

53.8

58.4

12

16.1

19.6

21.2

32.1

39.1

42.5

48.1

58.7

63.7

13

17.5

21.2

23.0

34.8

42.4

46.0

52.2

63.6

69.0

14

18.8

22.8

24.8

37.5

45.6

49.5

56.2

68.5

74.3

15

20.1

24.4

26.5

40.1

48.9

53.1

60.2

73.3

79.6

16

21.5

26.1

28.3

42.8

52.2

56.6

64.2

78.2

84.9

17

22.8

27.7

30.1

45.5

55.4

60.1

68.2

83.1

90.2

18

24.2

29.3

31.8

48.2

58.7

63.7

72.2

88.0

95.5

19

25.5

31.0

33.6

50.8

61.9

67.2

76.2

92.9

100.8

20

26.9

32.6

35.4

53.5

65.2

70.8

80.2

97.8

106.1

2.319

2.126

2.261

4.64

4.25

3.91

6.956

6.38

5.86

1 System Intlet OD

m3/s
inch

3/4"

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

1 System Outlet OD

inch

5/8"

5/8"
0.59

5/8"

5/8"

3/4"

7/8"

7/8"

1 1/8"

1 1/8"

No. of fans
Air quantity

Coil face area


Inter. Coil vol.
Condensor refrigerant
operating charge kg
Total Pump - down
capacity kg @ 80%
Net mass kg

m2

1.19

1.78

litres

3.71

5.56

7.42

7.08

10.62

14.16

10.45

15.68

R22

1.01

1.51

2.01

2.06

3.03

4.02

3.09

4.54

6.03

R404A

0.71

1.06

1.41

1.43

2.13

2.80

2.15

3.20

4.20

R134a

0.99

1.46

1.92

1.98

2.91

3.78

2.96

4.36

5.67

R22

3.30

4.94

6.59

6.29

9.44

12.58

9.28

13.93

18.57

R404A

1.17

1.74

2.30

2.33

3.48

4.60

3.50

5.22

6.89

R134a

3.35

5.02

6.70

6.40

9.60

12.79

9.44

14.17

18.89

Al fin

47

51

55

92

100

117

133

145

170

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Density
Capacity Correction Factors:
multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

20.90

Factor

Refrigeration Densities @ 44C

R134a:
R22:
R507:
R404A:
R407C:
R410A:

kg/m

kg/L

R12

1238.1

1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 38 kW
Ambient design condition: 30C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
38 kW 0.98 0.99 = 39.16 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HAV-502-2R" gives 40.1 kW
Select the "HAV-502-2R"

Page 39

Note: subject to change without notice

HAV-500-A
Page 3 of 3
01-10-2009

REMOTE AIR COOLED CONDENSER


WITH 500mm FANS

430
300

30

30
IN

HAV 501

780

OUT

822

HAV 502

1560

HAV 503

2340

2530
130
60

Note:

Note:

- Dimensions in mm
- Dimansions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
AC 500mm diameter
0.82 kW 1.59 A Each.

Coil:
- 3/8" Rife bore copper tube
- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC

AC

Diameter
mm
500
500
L1 L2 L3

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Voltage
V
400
230
TOP TOP

Frequency
Hz
50
50

Speed
rpm
1330
1270

Power
W
830
760

Amperage
A
1.65
3.3

Standard
Optional

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 40

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HCB-200-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCB AIR COOLED CONDENSER BASE
WITH RECEIVER AND 200mm FANS
General Description

The HCB-201-2R to HCB-201-4R comprises 3 models covering duties from 0.92kW to 1.14kW total heat
rejection at 15K ITD. Features include our strengthened header connections and high efficiency rifle bore
tube.
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets
etc.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fin

Coated Al fins

Galvanized steel casing

430 Stainless steel casing

230/1/50 Hz fan motor

Nomenclature
H C B 201 - A - 4R - 12F
HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

Base

Vintage

Fan diameter -cm

No. of fans
Page 41

Note:subjecttochangewithoutnotice

HCB-200-A
Page 2 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 200mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

201-2R

201-3R

201-4R

0.06

0.07

0.08

10

0.61

0.71

0.76

11

0.67

0.79

0.84

12

0.73

0.86

0.91

13

0.79

0.93

0.99

14

0.85

1.00

1.06

15

0.92

1.07

1.14

16

0.98

1.14

1.22

17

1.04

1.21

1.29

18

1.10

1.29

1.37

19

1.16

1.36

1.45

20

1.22

1.43

1.52

0.09

0.08

0.08

1 System Inlet OD

m3/s
inch

3/8"

3/8"

3/8"

1 System Outlet OD

inch

3/8"

3/8"

3/8"

No. of fans
Air quantity

Coil face area

0.06

Inter. Coil vol.

liters

0.45

0.67

0.89

Inter. Receiver vol.

liters

0.50

0.50

0.50

R22

0.14

0.19

0.25

R404A

0.15

0.20

0.27

R134a

0.12

0.17

0.22

R22

0.84

1.04

1.23

R404A

0.72

0.88

1.05

R134a

0.86

1.06

1.26

Al fin

6.77

7.56

8.00

Condenser refrigerant
operating charge kg
Total Pump - down
capacity kg @ 80%
Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

Density
kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 0.75kW
Ambient design condition: 33C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 33C = 12 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
0.75 kW 0.98 0.99 = 0.77 kW THR required at
12C ITD, Refrigerant R22, Altitude 0 m
At 12C ITD the "HCB-201-3R" gives 0.86 kW
Select the "HCB-201-3R"

Page 42

Note:subjecttochangewithoutnotice

HCB-200-A
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 200mm FANS

[mm]

201-2R

201-3R

201-4R

85

110

130

275

235

20

380

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:

200mm diameter
0.31 kW 0.2 A Each.

Coil:

- 3/8" Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

95

330

Fan Wiring
Motor
AC

Diameter
mm
200

L1 N

Voltage
V
230

Frequency
Hz
50

Speed
rpm
1300

Power
W
31

Amperage
A
0.2

Standard

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 43

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HCB-250-B
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCB AIR COOLED CONDENSER BASE
WITH RECEIVER AND 250mm FANS
General Description

The HCB-251-B-2R to HCB-252-B-4R comprises 6 models covering duties from 1.6 kW to 4.1 kW total heat
rejection at 15K ITD. Features include our strengthened header connections and high efficiency rifle bore
tube.
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets
etc.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fin

Coated Al fins

Galvanized steel casing and base

430 Stainless steel casing

Epoxy powder coated finish


RAL 5005 Signal blue color
230/1/50 Hz fan motor

Nomenclature
H C B 251 - B - 4R - 12F
HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

Base

Vintage

Fan diameter -cm

No. of fans
Page 44

Note:subjecttochangewithoutnotice

HCB-250-B
Page 2 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 250mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

251-2R

251-3R

251-4R

252-2R

252-3R

252-4R

0.11

0.13

0.13

0.23

0.27

0.27

10

1.07

1.27

1.33

2.33

2.67

2.73

11

1.17

1.39

1.47

2.57

2.93

3.01

12

1.28

1.52

1.60

2.80

3.20

3.28

13

1.39

1.65

1.73

3.03

3.47

3.55

14

1.49

1.77

1.87

3.27

3.73

3.83

15

1.60

1.90

2.00

3.50

4.00

4.10

16

1.71

2.03

2.13

3.73

4.27

4.37

17

1.81

2.15

2.27

3.97

4.53

4.65

18

1.92

2.28

2.40

4.20

4.80

4.92

19

2.03

2.41

2.53

4.43

5.07

5.19

20

2.13

2.53

2.67

4.67

5.33

5.47

0.18

0.15

0.14

0.36

0.31

0.27

1 System Inlet OD

m3/s
inch

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

1 System Outlet OD

inch

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

Coil face area

No. of fans
Air quantity

0.16

0.08

Inter. Coil vol.

liters

0.63

0.94

1.25

1.09

1.64

2.19

Inter. Receiver vol.

liters

0.50

0.50

0.50

0.50

0.50

0.50

R22

0.15

0.23

0.31

0.29

0.43

0.55

R404A

0.19

0.26

0.33

0.33

0.49

0.63

R134a

0.15

0.21

0.28

0.28

0.38

0.51

R22

1.00

1.28

1.55

1.41

1.90

2.39

R404A

0.85

1.08

1.32

1.20

1.61

2.03

R134a

1.02

1.30

1.58

1.44

1.93

2.43

Al fin

9.28

10.09

10.50

18.56

20.18

21.00

Condensor refrigerant
operating charge kg
Total Pump - down
capacity kg @ 80%
Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

Density
kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 1.5 kW
Ambient design condition: 31C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 31C = 14 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
1.5 kW 0.98 0.99 = 1.54 kW THR required at
14C ITD, Refrigerant R22, Altitude 0 m
At 14C ITD the "HCB-251-2R" gives 1.75 kW
Select the "HCB-251-2R"

Page 45

Note:subjecttochangewithoutnotice

HCB-250-B
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 250mm FANS

595

300

130

280

20

485

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:

AC 250mm diameter
0.60 kW 0.42 A Each.

Coil:

- 3/8" Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

120

375

670

Fan Wiring
Motor
AC

Diameter
mm
250

L1 N

Voltage
V
230

Frequency
Hz
50

Speed
rpm
1300

Power
W
60

Amperage
A
0.42

Standard

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 46

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HC

HC HEAT-EXCHANGERS

HCBC-300-A
Page 1 of 3
01.10.2009

HCBC COMPACT AIR COOLED CONDENSER


BASE WITH RECEIVER AND 300mm FAN

General Description
The HCBC-300 comprises 8 models covering duties from kW to kW total heat rejection at 15K ITD. The unit
is designed to be lighter and more compact than the standard HCB-300. Features include our floating coil
construction strengthened header connections and high efficiency rifle bore tubes
construction,
tubes.
The base allows for easy handling and ready fitment of compressors, HP/LP brackets etc. The low noise level
modular fan arrangement is well suited to economical fan cycling head pressure control.

Standard Features

Optional Features

Aluminium fin

Copper fin

Rifle bore copper tube

Coated aluminium fin

12 FPI floating coil construction

Stainless steel casing

Galvanised steel casing and base


RAL 5005 Signal Blue colour
Note: Subject to change without notice

230/1/50 fan motor

Nomenclature

H C BC 30 1 4R x 12F

HC Heat-Exchangers
Heat Exchangers
Air cooled condenser

Fins per inch (12F)

Base - Compact

No. of coil rows (2R, 3R or 4R)

Fan diameter - cm
Page 47

No. of fans 1 to 2

HCBC COMPACT AIR COOLED CONDENSER BASE


WITH RECEIVER AND 300mm FANS

HCBC-300-A
Page 2 of 3
01-10-2009

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

301-2R 301-3R 301-4R 302-2R 302-3R 302-4R

0.21

0.25

0.26

0.50

0.56

0.58

10

2.10

2.53

2.56

5.01

5.59

5.77

11

2.31

2.78

2.82

5.51

6.14

6.35

12

2.52

3.03

3.08

6.01

6.70

6.92

13

2.73

3.29

3.33

6.51

7.26

7.50

14

2.94

3.54

3.59

7.01

7.82

8.08

15

3.16

3.79

3.85

7.51

8.38

8.65

16

3.37

4.05

4.10

8.01

8.94

9.23

17

3.58

4.30

4.36

8.51

9.50

9.81

18

3.79

4.55

4.61

9.01

10.05

10.38

19

4.00

4.80

4.87

9.51

10.61

10.96

20

4.21

5.06

5.13

10.01

11.17

11.54

0.39

0.33

0.27

0.83

0.69

0.61

1 System Intlet OD

m3/s
inch

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

1 System Outlet OD

inch

3/8"

3/8"
0.11

3/8"

3/8"

3/8"
0.24

3/8"

2.65

No. of fans
Air quantity

Coil face area

Inter. Coil vol.

litres

0.61

0.91

1.22

1.33

1.99

Inter. Receiver vol.

litres

R22

0.61

0.74

0.86

0.83

1.07

1.31

R404A

0.62

0.75

0.89

0.86

1.10

1.35

R134a

0.57

0.70

0.83

0.8

1.06

1.3

R22

3.21

3.47

3.75

3.85

4.43

5.02

R404A

2.72

2.95

3.18

3.26

3.76

4.26

R134a

3.26

3.53

3.81

3.91

4.51

5.11

Al fin

11.36

12.26

13.16

20.50

22.30

24.20

Condensor refrigerant
operating charge kg
Total Pump - down
capacity kg @ 80%
Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

Density
kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 3.0 kW
Ambient design condition: 37C
Altitude: 800m
Condensing temperature: 50C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 37C = 13 C
Correction Factor R134a= 0.98
Correction Factor 800m = 0.95
Required capacity at catalogue conditions:
3.0 kW 0.98 0.95 = 3.22 kW THR required at
13C ITD, Refrigerant R22, Altitude 0 m
At 13C ITD the "HCBC-301-3R" gives 3.29 kW
Select the "HCB-301-3R"

Page 48

Note:subjecttochangewithoutnotice

HCBC-300-A
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 300mm FANS

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:

AC 300mm diameter
0.11 kW 0.75 A Each.

Coil:

- 3/8" Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC

Diameter
mm
300

L1 N

Voltage
V
230

Frequency
Hz
50

Speed
rpm
1300

Power
W
110

Amperage
A
0.75

Standard

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 49

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HCB-300-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCB AIR COOLED CONDENSER BASE
WITH RECEIVER AND 300mm FANS
General Description

The HCB-301 to HCB-302 comprises 6 models covering duties from 4.33 kW to 10.6 kW total heat rejection at
15K ITD. Features include our floating coil construction, strengthened header connections and high efficiency
rifle bore tube.
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets etc.
The low noise level modular fan arrangement is well suited to economical fan cycling head pressure control on
multi fan units Each unit is factory wired to a terminal strip in a terminal box.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fin

Coated Al fins

Galvanized steel casing and base

430 Stainless steel casing

Epoxy powder coated finish


RAL 5005 Signal blue color
230/1/50 Hz fan motor

Nomenclature
H C B 301 - A - 4R - 12F
HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

Base

Vintage

Fan diameter -cm

No. of fans
Page 50

Note:subjecttochangewithoutnotice

HCB-300-A
Page 2 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 300mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

301-2R 301-3R 301-4R 302-2R 302-3R 302-4R

0.33

0.39

0.40

0.68

0.77

0.80

10

3.32

3.87

4.01

6.84

7.73

7.99

11

3.65

4.26

4.41

7.53

8.51

8.79

12

3.98

4.64

4.81

8.21

9.28

9.59

13

4.31

5.03

5.21

8.90

10.05

10.39

14

4.65

5.42

5.61

9.58

10.83

11.19

15

4.98

5.80

6.01

10.26

11.60

11.99

16

5.31

6.19

6.41

10.95

12.37

12.79

17

5.64

6.58

6.82

11.63

13.15

13.59

18

5.97

6.96

7.22

12.32

13.92

14.39

19

6.30

7.35

7.62

13.00

14.69

15.18

20

6.64

7.74

8.02

13.69

15.47

15.98

0.54

0.46

0.41

1.09

0.93

0.82

1 System Inlet OD

m3/s
inch

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

1 System Outlet OD

inch

3/8"

3/8"
0.18

3/8"

1/2"

1/2"
0.37

1/2"

4.44

No. of fans
Air quantity

Coil face area

Inter. Coil vol.

liters

1.20

1.80

2.40

2.2

3.33

Inter. Receiver vol.

liters

R22

0.32

0.46

0.60

0.62

0.92

1.23

Condenser refrigerant
operating charge kg

R404A

0.37

0.52

0.70

0.71

1.07

1.4

R134a

0.30

0.45

0.58

0.6

11.16

11.673

Total Pump - down


capacity kg @ 80%

R22

3.73

4.26

4.80

6.40

7.40

8.39

R404A

3.16

3.62

4.07

5.42

6.27

7.11

R134a

3.80

4.34

4.88

6.51

7.53

8.53

Al fin

28.90

30.60

32.30

45.00

48.10

51.30

Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

Density
kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 8 kW
Ambient design condition: 37C
Altitude: 800m
Condensing temperature: 50C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 50C - 37C = 13 C
Correction Factor R134a= 0.98
Correction Factor 800m = 0.95
Required capacity at catalogue conditions:
8 kW 0.98 0.95 = 8.59 kW THR required at
13C ITD, Refrigerant R22, Altitude 0 m
At 13C ITD the "HCB-302-2R" gives 8.9 kW
Select the "HCB-302-2R"

Page 51

Note:subjecttochangewithoutnotice

HCB-300-A
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 300mm FANS

Model

301-2R 301-3R 301-4R 301-6R 302-2R 302-3R 302-4R 302-6R

[mm]

490

490

490

490

940

940

940

940

[mm]

596

596

596

596

1050

1050

1050

1050

[mm]

680

680

680

680

1125

1125

1125

1125

[mm]

160

160

160

160

160

160

160

160

A
A

61

203

485

75

40

40

410

440
750

30 x 10
SLOT

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

546

Fan:

AC 300mm diameter
0.11 kW 0.75 A Each.

Coil:
100

- 3/8" Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

D
C

Fan Wiring
Motor
AC

Diameter
mm
300

L1 N

Voltage
V
230

Frequency
Hz
50

Speed
rpm
1300

Power
W
110

Amperage
A
0.75

Standard

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 52

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HCB-350-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCB AIR COOLED CONDENSER BASE
WITH RECEIVER AND 350mm FANS
General Description

The HCB-351 to HCB-353 comprises 9 models covering duties from 6.9kW to 27 kW total heat rejection at
15K ITD. Features include our floating coil construction, strengthened header connections and high
efficiency rifle bore tubes. Model 352 and above include our unique receiver inlet which limits the filling of a
receiver to 80% by volume (covered by patents).
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets
etc. The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control on multi fan units. Each unit is factory wired to a terminal strip in a terminal box.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fins

Coated Al fins

Galvanized steel casing

430 Stainless steel casing

Receiver inlet volume limiter


_(model 352 & 353)

400/3/50 Hz Fan motor

RAL-5005 Signal blue color


230/1/50 Hz fan motor

Nomenclature
H C B 351 - A - 4R - 12F
HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

Base

Vintage

Fan diameter -cm

No. of fans
Page 53

Note:subjecttochangewithoutnotice

HCB-350-A
Page 2 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 350mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

351-2R 351-3R 351-4R 352-2R 352-3R 352-4R 353-2R 353-3R 353-4R

0.5

0.6

0.6

0.9

1.1

1.2

1.4

1.7

1.8

10

4.6

5.6

6.0

9.3

11.1

12.0

13.9

16.7

18.0

11

5.1

6.2

6.6

10.2

12.2

13.2

15.3

18.4

19.8

12

5.6

6.7

7.2

11.1

13.3

14.4

16.7

20.1

21.6

13

6.0

7.3

7.8

12.0

14.5

15.6

18.0

21.8

23.4

14

6.5

7.8

8.4

13.0

15.6

16.8

19.4

23.4

25.2

15

6.9

8.4

9.0

13.9

16.7

18.0

20.8

25.1

27.0

16

7.4

8.9

9.6

14.8

17.8

19.2

22.2

26.8

28.8

17

7.9

9.5

10.2

15.7

18.9

20.4

23.6

28.4

30.6

18

8.3

10.1

10.8

16.7

20.0

21.6

25.0

30.1

32.4

19

8.8

10.6

11.4

17.6

21.1

22.8

26.4

31.8

34.2

20

9.3

11.2

12.0

18.5

22.2

24.0

27.8

33.5

36.0

0.74

0.68

0.63

1.47

1.36

2.50

2.20

2.03

1.89

1 System Inlet OD

m3/s
inch

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

1/2"

1/2"

5/8"

1 System Outlet OD

inch

3/8"

3/8"
0.25

3/8"

1/2"

1/2"
0.50

1/2"

1/2"

1/2"
0.75

1/2"

No. of fans
Air quantity

Coil face area

Inter. Coil vol.

liters

1.60

2.40

3.20

3.00

4.51

6.01

4.41

6.61

8.81

Inter. Receiver vol.

liters

5.00

5.00

5.00

10.62

10.62

10.62

15.93

15.93

15.93

Condenser refrigerant
operating charge kg

R22

0.43

0.63

0.84

0.86

1.29

1.68

1.29

1.91

2.53

R404A

0.50

0.73

0.97

0.99

1.46

1.94

1.49

2.19

2.90

R134a

0.42

0.61

0.81

0.84

1.22

1.58

1.24

1.82

2.38

Total Pump - down


capacity kg @ 80%

R22

5.86

6.57

7.29

12.10

13.44

14.78

2.90

20.03

21.98

R404A

4.97

5.57

6.18

10.26

11.40

12.53

15.32

16.98

18.64

R134a

5.96

6.69

7.41

12.31

13.67

15.03

18.38

20.37

22.36

Al fin

36.5

38.8

41

60.3

64.5

68.7

97.2

103.3

109.4

Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:

Density

R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 8 kW
Ambient design condition: 30C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
8 kW 0.98 0.99 = 8.25 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HCB-351-3R" gives 8.4 kW
Select the "HCB-351-3R"

Page 54

Note:subjecttochangewithoutnotice

HCB-350-A
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 350mm FANS

Model

351-2R 351-3R 351-4R 352-2R 352-3R 352-4R 353-2R 353-3R 353-4R

590

590

590

1142

1142

1142

1690

1690

1690

840

840

840

1250

1250

1250

1800

1800

1800

780

780

780

1330

1330

1330

1880

1880

1880

160

160

160

820

820

820

1220

1220

1220

750

750

750

950

950

950

950

950

950

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:

AC 350mm diameter
0.115 kW 0.33 A Each.

Coil:

- 3/8" Rifle bore copper tube


- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC
AC

Diameter
mm
350
350

L1 N

Voltage
V
230
400

Frequency
Hz
50
50

Speed
rpm
1420
1420

Power
W
115
135

Amperage
A
0.33
0.58

Standard
Optional

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 55

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HCB-400-A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCB AIR COOLED CONDENSER BASE
WITH RECEIVER AND 400mm FANS
General Description

The HCB-401 to HCB-403 comprises 9 models covering duties from 9kW to 34.9kW total heat rejection at
15K ITD. Features include our floating coil construction, strengthened header connections and high
efficiency rifle bore tube. The HCB 400 range includes our unique receiver inlet which limits the filling of a
receiver to 80% by volume (covered by patents).
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets
etc. The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control on multi fan units. Each unit is factory wired to a terminal strip in a terminal box.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fin

Coated Al fins

Galvanized steel casing

430 Stainless steel casing

Receiver inlet volume limiter

230/1/50 Hz fan motor

RAL-5005 Signal blue color


400/3/50 Hz fan motor

Nomenclature
H C B 401 - A - 4R - 12F
HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

Base

Vintage

Fan diameter -cm

No. of fans
Page 56

Note:subjecttochangewithoutnotice

HCB - 400 -A
Page 2 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 400mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

401-2R 401-3R 401-4R 402-2R 402-3R 402-4R 403-2R 403-3R 403-4R

0.6

0.7

0.8

1.2

1.4

1.6

1.8

2.2

2.3

10

6.0

7.2

7.8

11.9

14.4

15.5

17.9

21.6

23.3

11

6.6

7.9

8.5

13.1

15.8

17.1

19.7

23.7

25.6

12

7.2

8.6

9.3

14.3

17.3

18.6

21.5

25.9

27.9

13

7.8

9.3

10.1

15.5

18.7

20.2

23.3

28.0

30.3

14

8.4

10.1

10.9

16.7

20.1

21.7

25.1

30.2

32.6

15

9.0

10.8

11.6

17.9

21.6

23.3

26.9

32.3

34.9

16

9.6

11.5

12.4

19.1

23.0

24.8

28.7

34.5

37.3

17

10.2

12.2

13.2

20.3

24.4

26.4

30.5

36.7

39.6

18

10.8

12.9

14.0

21.5

25.9

27.9

32.3

38.8

41.9

19

11.4

13.6

14.8

22.7

27.3

29.5

34.1

41.0

44.2

20

12.0

14.4

15.5

23.9

28.8

31.0

35.9

43.1

46.6

0.948

0.876

0.815

1.90

1.75

1.63

2.848

2.63

1 System Inlet OD

m3/s
inch

3/8"

1/2"

1/2"

1/2"

5/8"

5/8"

5/8"

5/8"

3/4"

1 System Outlet OD

inch

3/8"

1/2"

1/2"

1/2"

5/8"
0.99

5/8"

m2

1/2"
0.66

1/2"

Coil face area

3/8"
0.33

No. of fans
Air quantity

3
2.446

Inter. Coil vol.

liters

2.10

3.15

4.20

3.97

5.96

7.94

5.84

8.77

11.69

Inter. Receiver vol.

liters

7.03

7.03

7.03

12.27

12.27

12.27

17.26

17.26

17.26

Condenser refrigerant
operating charge kg

R22

0.57

0.84

1.11

1.13

1.68

2.22

1.70

2.52

3.33

R404A

0.55

0.79

1.04

1.08

1.59

2.09

1.62

2.38

3.14

R134a

0.55

0.79

1.04

1.08

1.59

2.09

1.62

2.38

3.14

Total Pump - down


capacity kg @ 80%

R22

8.11

9.04

9.98

14.43

16.20

17.96

20.52

23.13

25.72

R404A

6.88

7.67

8.46

12.23

13.73

15.22

17.40

19.61

21.81

R134a

8.25

9.20

10.15

14.67

16.47

18.26

20.87

23.52

26.16

Al fin

46.27

49.13

51.99

89.7

95.08

100.46

123.71

131.6

139.6

Net mass kg

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:

Density

R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

kg/m
R12

1238.1

kg/l
1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 22 kW
Ambient design condition: 30C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
22 kW 0.98 0.99 = 22.68 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HCB-402-4R" gives 23.3 kW
Select the "HCB-402-4R"

Page 57

Note:subjecttochangewithoutnotice

HCB-400-A
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 400mm FANS

401-2R 401-3R 401-4R 401-6R 402-2R 402-3R 402-4R 402-6R 403-2R 403-3R 403-4R 403-6R
A

690

690

690

690

1340

1340

1340

1340

1990

1990

1990

1990

796

796

796

796

1466

1466

1466

1466

2116

2116

2116

2116

874

874

874

874

1544

1544

1544

1544

2194

2194

2194

2194

570

570

570

570

1020

1020

1020

1020

1320

1320

1320

1320

950

950

950

950

950

950

950

950

950

950

950

950

Note:
- Dimensions in mm
- Dimensions
Di
i
2 mm
- Refer to manufacturer for R410A
_applications

Fan:

AC 400mm diameter
0.135 kW 0.44 A Each.

Coil:

- 3/8" Rife bore copper tube


- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC

AC

Diameter
mm
400
400
L1 L2 L3

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Voltage
V
400
230
TOP TOP

Frequency
Hz
50
50

Speed
rpm
1450
1430

Power
W
135
160

Amperage
A
0.76
0.73

Standard
Optional

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 58

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HCB-500-B
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCB AIR COOLED CONDENSER BASE
WITH RECEIVER AND 500mm FANS

General Description
The HCB-501 to HCB-503 comprises 12 models covering duties from 14.44kW to 72.12kW total heat
rejection at 15K ITD. Features include our floating coil construction, strengthened header connections and
high efficiency rifle bore tube. The HCB 500 range includes our unique receiver inlet which limits the filling of
a receiver to 80% by volume (covered by patents).
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets
etc. The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control on multi fan units. Each unit is factory wired to a terminal strip in a terminal box.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fins

Aluminium fin

Coated Al fins

Galvanized steel casing

430 Stainless steel casing

Receiver inlet volume limiter


RAL-5005 Signal blue color
400/3/50 Hz fan motor

Nomenclature
H C B 501 - A - 4R - 12F
HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3 or 4 row)

Base

Vintage

Fan diameter -cm

No. of fans

Page 59

Note: subject to change without notice

HCB-500-B
Page 2 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 500mm FANS

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

501-2R 501-3R 501-4R H501-4R 502-2R 502-3R 502-4R H502-4R 503-2R 503-3R 503-4R H503-4R

1.2

1.4

1.5

1.7

2.3

2.8

3.0

3.5

3.5

4.2

4.5

5.2

10

11.6

13.9

14.9

17.2

23.2

27.7

29.7

34.5

34.7

41.6

44.6

51.7

11

12.7

15.2

16.3

19.0

25.5

30.5

32.7

38.0

38.2

45.7

49.0

56.9

12

13.9

16.6

17.8

20.7

27.8

33.3

35.7

41.4

41.7

49.9

53.5

62.1

13

15.0

18.0

19.3

22.4

30.1

36.0

38.6

44.9

45.2

54.0

57.9

67.3

14

16.2

19.4

20.8

24.1

32.4

38.8

41.6

48.3

48.6

58.2

62.4

72.4

15

17.3

20.8

22.3

25.9

34.7

41.6

44.6

51.8

52.1

62.3

66.8

77.6

16

18.5

22.2

23.8

27.6

37.1

44.3

47.5

55.2

55.6

66.5

71.3

82.8

17

19.6

23.5

25.3

29.3

39.4

47.1

50.5

58.7

59.1

70.7

75.8

88.0

18

20.8

24.9

26.7

31.0

41.7

49.9

53.5

62.1

62.5

74.8

80.2

93.1

19

21.9

26.3

28.2

32.8

44.0

52.7

56.5

65.6

66.0

79.0

84.7

98.3

20

23.1

27.7

29.7

34.5

46.3

55.4

59.4

69.0

69.5

83.1

89.1

103.5

2.12

2.16

1.67

1.91

4.24

3.74

3.35

3.83

6.36

5.61

5.02

5.74

1 System Inlet OD

m3/s
inch

5/8"

5/8"

3/4"

3/4"

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 System Outlet OD

inch

5/8"

5/8"
0.46

5/8"

5/8"

7/8"

7/8"
0.91

7/8"

7/8"

7/8"

7/8"
1.37

7/8"

1 1/8"

No. of fans
Air quantity

Coil face area

m2

0.56

1.12

1.69

Inter. Coil vol.

liters

2.76

4.13

5.51

6.89

5.31

7.96

10.62

13.27

7.86

11.79

15.72

19.65

Inter. Receiver vol.

liters

9.00

9.00

9.00

9.00

16.00

16.00

16.00

16.00

16.00

16.00

16.00

21.00

R22

0.79

1.17

1.55

1.94

1.58

2.35

3.14

3.87

2.36

3.52

4.66

5.81

0.90

1.33

1.77

2.21

1.81

2.69

3.54

4.42

2.71

4.03

5.31

6.63

0.76

1.12

1.46

1.84

1.52

2.23

2.96

3.68

2.28

3.35

4.43

5.53

10.45

36.12

Condenser
refrigerant operating R404A
charge kg
R134a
R22
Total Pump - down
R404A
capacity kg @ 80%
R134a

11.67

12.89

14.12

18.93

21.29

23.65

26.01

21.20

24.69

28.18

8.86

9.89

10.93

11.97

16.05

18.05

20.05

22.05

17.97

20.93

23.89

30.62

10.63

11.86

13.11

14.36

19.26

21.65

24.05

26.45

21.56

25.11

28.66

36.73

Net mass kg

46.27

49.13

51.99

64.9

89.7

95.08

100.46

120

123.71

131.6

139.6

167

Al fin

Altitude correction factors

Alt m

200

400

600

800

1000

1200

1400

1600

1800

Factor

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

Refrigeration Densities @ 44C


Capacity Correction Factors:
R134a:
R22:
R507:
R404A:
R407C:
R410A:

multiply kW by 0.98
multiply kW by 1.00
multiply kW by 1.03
multiply kW by 1.03
multiply kW by 0.87
multiply kW by 1.09

Density
kg/m3

kg/L

R12

1238.1

1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Example:
Required THR: 21 kW
Ambient design condition: 30C
Altitude: 200m
Condensing temperature: 45C
Refrigerant: R134a
ITD (Initial Temperature Difference)
ITD = Condensing Temperature - Ambient Temperature
ITD = 45C - 30C = 15 C
Correction Factor R134a= 0.98
Correction Factor 200m = 0.99
Required capacity at catalogue conditions:
21 kW 0.98 0.99 = 21.65 kW THR required at
15C ITD, Refrigerant R22, Altitude 0m
At 15C ITD the "HCB-501-4R" gives 22.3 kW
Select the "HCB-501-4R"

Page 60

Note: subject to change without notice

HCB-500-B
Page 3 of 3
01-10-2009

HCB AIR COOLED CONDENSER BASE


WITH RECEIVER AND 500mm FANS

Model

501-2R 501-3R 501-4R H501-4R 502-2R 502-3R 502-4R H502-4R 503-2R 503-3R 503-4R H503-4R

790

790

790

790

1540

1540

1540

1540

2290

2290

2290

2290

916

916

916

916

1666

1666

1666

1666

2416

2416

2416

2416

994

994

994

994

1744

1744

1744

1744

2494

2494

2494

2494

720

720

720

720

1620

1620

1620

1620

2320

2320

2320

2320

1125

1125

1125

1125

1125

1125

1125

1125

1125

1125

1125

1125

Note:
- Dimensions in mm
- Dimensions 2 mm
- Refer to manufacturer for R410A
_applications

Fan:
AC 500mm diameter
0.82 kW 1.59 A Each.

Coil:
- 3/8" Rife bore copper tube
- Aluminium fin
- 12 fins per inch

Fan Wiring
Motor
AC

AC

Diameter
mm
500
500
L1 L2 L3

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Voltage
V
400
230
TOP TOP

Frequency
Hz
50
50

Speed
rpm
1325
1270

Power
W
820
760

Amperage
A
1.59
3.3

Standard
Optional

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 61

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HC HEAT-EXCHANGERS

HCB-630-D
Page 1 of 3
01.10.2009

HC

HCB AIR COOLED CONDENSER BASE WITH


RECEIVER AND 630mm FAN
General Description
The HCB-631-D to HCB-633-D comprises 12 models covering duties from 45.49 kW to 209.88 kW total heat
rejection at 15K ITD. Features include our floating coil construction, strengthened header connections, high
efficiency rifle bore tube and unique receiver inlet which limits the filling of a receiver to 80% by volume
(covered by patents).
The rugged design of the base allows for easy handling and ready fitment of compressors, HP/LP brackets
etc.The low noise level modular fan arrangement is well suited to economical fan cycling head pressure
control. Each unit is factory wired to a terminal strip in a terminal box.

Standard Features

Optional Features

Aluminium fin

Copper fin

Rifle bore copper tube

Coated aluminium fin

12 FPI Floating coil construction

Stainless steel casing

Receiver inlet volume limiter


Galvanised steel casing and base
RAL 5005 Signal blue colour
Note: Subject to change without notice

400/3/50 fan motor

Nomenclature

H C B 63 1 B 4R x 12F

Nomenclature

HC Heat-Exchangers

Fins per inch (12F)

Air cooled condenser

No. of coil rows (2, 3, 4 or 6 row)

Base

Vintage

Fan diameter - cm

No. of fans 1 to 3

Page 62

HCB-630-D
Page 2 of 3
01.10.2009

HCB AIR COOLED CONDENSER WITH BASE


630mm FAN

HC

Technical & Physical Data


Total Heat Rejection - kW
Model

ITD K

631-2R

631-3R

631-4R

631-6R

632-2R

632-3R

632-4R

632-6R

633-2R

633-3R

633-4R

3.03

3.81

4.30

4.66

6.07

7.62

8.61

9.33

9.10

11.44

12.91

13.99

10

30.33

38.12

43.03

46.64

60.66

76.23

86.07

93.29

90.99

114.35

129.09

139.92

11

33.36

41.93

47.34

51.30

66.73

83.86

94.67

102.62

100.09

125.79

142.00

153.91

12

36.39

45.74

51.64

55.97

72.79

91.48

103.28

111.94

109.19

137.22

154.91

167.90

13

39.42

49.56

55.94

60.63

78.86

99.10

111.89

121.27

118.29

148.66

167.82

181.90

14

42.46

53.37

60.25

65.30

84.92

106.73

120.49

130.60

127.39

160.09

180.73

195.89

15

45.49

57.18

64.55

69.96

90.99

114.35

129.10

139.93

136.49

171.53

193.64

209.88

16

48.52

60.99

68.85

74.62

97.06

121.97

137.71

149.26

145.59

182.97

206.55

223.87

17

51.56

64.80

73.16

79.29

103.12

129.60

146.31

158.59

154.69

194.40

219.46

237.86

18

54.59

68.62

77.46

83.95

109.19

137.22

154.92

167.92

163.79

205.84

232.37

251.86

19

57.62

72.43

81.76

88.62

115.25

144.84

163.53

177.24

172.89

217.27

245.28

265.85

20

60.65

76.24

86.07

93.28

121.32

152.47

172.13

186.57

181.99

228.71

258.19

279.84

m3/s

5.20

4.99

4.79

4.40

10.39

9.97

9.58

8.80

15.59

14.96

14.37

13.21

1 System Outlet

ins

7/8"

7/8"

7/8"

7/8"

1-1/8"

1-1/8"

1-1/8"

1-1/8"

1-3/8"

1-3/8"

1-3/8"

1-3/8"

1 System Inlet

ins

7/8"

1-1/8"

1-1/8"

1-1/8"

1-3/8"

1-3/8"

1-5/8"

1-5/8"

1-5/8"

2-1/8"

2-1/8"

2-1/8"

Coil face area

m2

1.36

1.36

1.36

1.36

2.72

2.72

2.72

2.72

4.08

4.08

4.08

4.08

Coil surface area

m2

50.90

76.35

101.80

152.70

101.80

152.70

203.60

305.40

152.70

229.05

305.40

458.10

Inter. coil vol. Litres

8.10

12.15

16.20

24.29

15.84

23.76

31.68

47.51

23.58

35.37

47.16

70.73

Receiver vol. Litres


System pump-down capacity
l @ 80%

16.00

16.00

16.00

16.00

21.00

21.00

21.00

21.00

30.00

30.00

30.00

30.00

19.28

22.52

25.76

32.23

29.47

35.81

42.14

54.81

42.86

52.30

61.73

80.58

6.36

7.59

8.83

11.29

12.26

14.67

17.08

21.91

18.45

22.04

25.63

32.82
33.71

No. of fans
Air quantity

R22
Refrigerant
R134a
operating charge
R404A
(l)
R507
Mass (dry)

kg

633-6R

6.51

7.78

9.05

11.60

12.54

15.03

17.52

22.51

18.87

22.58

26.29

5.88

7.18

8.47

11.05

11.35

13.88

16.41

21.46

17.07

20.84

24.60

32.12

5.88

7.17

8.46

11.05

11.35

13.87

16.40

21.45

17.06

20.82

24.59

32.11

186.00

196.00

206.00

225.00

341.0

360.0

378.0

416.0

494.0

522.0

550.0

606.0

Note: subject to change without notice

Page 63

HCB-630-D
Page 3 of 3
01.10.2009

HCB AIR COOLED CONDENSER WITH BASE


630mm FAN

HC

Selection Example
Given:
Duty 100kW total heat rejection R134a
Ambient temperature 30C
Condensing temperature 45C
Altitude 200m

Note:
- Dimensions in mm
- Dimensions 2mm
Fan:
- 630 mm diameter
- 400/1/50
-2.53 W x 4.95 A each.

Solution:
ITD = Initial temperature difference
= cond. temp. - ambient temp.
= 45-30C
= 15K

Coil:
- Copper tube
- Aluminium fin
- 12FPI

Correction factors (see below)


for R134a = 0.95
for 200m = 0.99
Consider model HCB-632-C-3R
Std duty at 15K ITD = 114.35
Corrected duty
= 114.35 x 0,95 x 0,99
=107.5 kW
Therefore select model HCB-632-C-3R

Considering Receiver pump down capacity

Refrigeration Densities @ 44C

Density

Given:
Operating charge for system 45.00kg
Refrigerant R134a

R12

R134a density:
= 1.1295 kg/l
Volume occupied is:
45.00 kg /

1.2381

R22

1110.6

1.1106

R134a

1129.5

1.1295

R404A

941.6

0.9416

R507

940.5

0.9405

Capacity Correction Factors

Condenser base pump down capacity for HCB-632-C-3R

For R134a multiply kW by 0.95

= 43.53l
Therefore condenser base is adequate

Factor

kg/l

1238.1

1.1295kg/l

= 39.84l

Altitude m

kg/m3

For R22

multiply kW by 1.00

For R507

multiply kW by 1.05

For R404A multiply kW by 1.06

200

400

600

800

1000

1200

1400

1600

1800

2000

1.00

0.99

0.97

0.96

0.95

0.93

0.92

0.91

0.90

0.88

0.87

Fan Wiring
Diameter

Voltage

Frequency

mm

Hz

630

400

50

RPM
1340

Power

Amperage

2530

5.2

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (011) 674-1237
Fax: (011) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (031) 202-7829
Fax: (031) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021) 551-7873
Fax: (021) 551-1751

Page 64

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

HC

HC HEAT-EXCHANGERS

HLR
Page 1 of 3
31.01.2009

HLR RANGE OF LIQUID


Q
RECEIVERS

General Description
HC Heat-Exchangers now offers liquid receivers which are engineered and manufactured to ASME 2004
standards. Features include; adequately sized pick up tubes to prevent vortices and the introduction of gas
into the liquid line and our patented receiver inlet volume limiter
limiter. This unique feature ensures that the receiver
cannot be filled beyond the 80% point (by volume) ensuring safe operation.

Standard Features

Optional Features

Mounting feet

Mounting plates for compressors


punched to suit

Inlet and outlet valve


Blue epoxy, powder coat finish
Patented inlet volume limiter
Fusible plug

Note: Subject to change without notice

Nomenclature

H L R 5 220 V

HC Heat-Exchangers
Heat Exchangers
Liquid

Vertical / Horizontal

Receiver

Length of tank

Pipe diameter - inchs


Page 65

HC

HLR
Page 2 of 3
31.01.2009

HLR RANGE LIQUID RECEIVERS

General Data
Model

HLR-5-220-V HLR-5-380-V

Capacity @ 80%

litre

2.12

3.82

Liquid valve

inch

3/8"

3/8"

Condensate inlet

inch

3/8"

1/2"

Dimensions(mm) HLR-5-220-V

220

M8

140

100

176

HLR-5-380-V

380

M8

140

100

304

Physical Data

Note: subject to change without notice

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (011) 674-1237
Fax: (011) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (031) 202-7829
Fax: (031) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021) 551-7873
Fax: (021) 551-1751

Page 66

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

HC

HLR
Page 3 of 3
31.01.2009

HLR RANGE LIQUID RECEIVERS


General Data

Model

HLR-5-570-H

HLR-5-720-H

HLR-5-820-H

HLR-5-1020-H

HLR-5-1220-H

HLR-5-1320-H

HLR-5-1620-H

HLR-5-2320-H

Capacity

litre

7.30

9.30

10.60

13.30

16.00

17.30

21.20

30.50

Liquid valve

inch

3/8"

1/2"

1/2"

1/2"

1/2"

5/8"

5/8"

3/4"

Condensate

inch

1/2"

5/8"

5/8"

5/8"

5/8"

3/4"

3/4"

7/8"

Physical Data
Dimensions
(mm)

HLR-5-570-H

570

480

140

30

65

HLR-5-720-H

720

630

140

30

65

HLR-5-820-H

820

730

140

30

65

HLR-5-1020-H

1020

930

140

30

65

HLR-5-1220-H

1220

1130

140

30

65

HLR-5-1320-H

1320

1230

140

30

65

HLR-5-1620-H

1620

1530

140

30

65

HLR-5-2320-H

2320

2230

140

30

65

Note: subject to change without notice

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (011) 674-1237
674 1237
Fax: (011) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (031) 202
202-7829
7829
Fax: (031) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021) 551
551-7873
7873
Fax: (021) 551-1751

Page 67

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261
261-647
647
Fax: (0926461) 216-201

RONDO - B
Page 1 of 4
01-10-2009

HC HEAT - EXCHANGERS
RONDO RANGE OF UNIT COOLERS
WITH 250 AND 300mm FANS
General Description

The Rondo range of unit coolers comprises 10 models for medium temperature applications only, utilising 250
mm and 300 mm diameter fans. The unique design results in a 180 air discharge.
The range is available in a 6 fins per inch spacing and is compatible with Refrigerants R134a, R22, R404A
and R507 etc. Other fin spacings are available on request.
The cooler has an injection moulded plastic driptray and top plate, suitable for temperatures down to -10C.
The driptray is hinged and held in place by easily removable knurled screws.

Standard Features

Optional Features

Plain copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel casing

RAL-9003 White epoxy coating


230/1/ 50 Hz fan motor
Injection moulded plastic driptray
Hinged driptray
Injection moulded plastic top panel
180 air discharge

Page 68

Note:subjecttochangewithoutnotice

RONDO - B
Page 2 of 4
01-10-2009

RONDO RANGE OF UNIT COOLERS


WITH 250mm AND 300mm FANS
Technical Data
Model

RONDO

140-A

240-A

340-A

440-A

400-A

500-A

Fin Spacing 6F
Nominal Capacity R22

0.63

0.80

0.95

1.08

1.19

700-A

900-A

1100-A

1300-A

3.38

4.04

4.64
17.03

(4,2mm)

1.66

2.06

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2

1.98

2.97

3.71

4.45

4.15

6.23

8.3

10.22

12.77

Air flow - frost free

m3 / s
m/s

0.21

0.19

0.21

0.22

0.29

0.37

0.43

0.92

1.05

0.94

2.22

1.96

1.76

1.57

2.25

1.92

1.65

2.88

2.64

2.36

Mass

kg

4.00

4.50

5.00

5.50

7.20

8.30

9.40

14.00

15.40

17.40

Tube internal volume

litre

0.56

0.84

1.05

1.26

1.15

1.72

2.3

2.80

3.5

4.66

1x250

1x250

1x250

1x250

2x250

2x250

2x250

2x300

2x300

2x300

Face velocity

General Data
Fans
Liquid connection

inch

3/8"

3/8"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

3/8"

3/8"

1/2"

1/2"

1/2"

1/2"

5/8"

5/8"

3/4"

3/4"

RPM

Power
W
16/60
25/90

Fan Wiring
Square shaded-pole motor (standard)
Diameter
Voltage
Frequency
mm
Hz
V
250
230
50
300
230
50

L1 N

F1

1300
1300

Amperage
A
0.42
0.52

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

Page 69

Note:subjecttochangewithoutnotice

RONDO - B
Page 3 of 4
01-10-2009

RONDO RANGE OF UNIT COOLERS


WITH 250 AND 300mm FANS
Mounting hole positions:
760

Page 70

Note:subjecttochangewithoutnotice

RONDO - B
Page 4 of 4
01-10-2009

RONDO RANGE OF UNIT COOLERS


WITH 250 AND 300mm FANS
Physical Data: Rondo 140 - 440
Dimensions

140-A

240-A

340-A

440-A

120

120

145

170

NOTE:
Drain: 1/2"BSPM
connection.

AIR

455

Physical Data: Rondo 400 - 1300


Dimensions

400-A

500-A

700-A

135

175

230

900-A 1100-A 1300-A


230

265

265

760

760

760

1060

1060

1060

430

430

430

530

530

530

NOTE:
Drain: 1/2"BSPM
connection.
NOTE:
Rondo: 140A;240Aare
Internallyequalized
AIR

NOTE:
Rondo:340A,440A;500
A;700A;900A;1100A;1300A
areexternallyequalized

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 71

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HC

HWM-300-A
Page 1 of 3
29.09.2009

HC HEAT-EXCHANGERS

HWM RANGE OF WALL MOUNTED COOLERS


WITH 300mm FAN

General Description
The HWM-300 range of wall mounted coolers comprises 8 models for medium temperature applications
utilising 300 mm diameter fans.
The range is available in 6 fins/inch and is compatible with refrigerants R134a
R134a, R22
R22, R404A
R404A, R507A
R507A, etc
etc.
Other fin spacings are available on request.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional
p
Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel tubes

RAL 9003 white epoxy


p y coating
g

Stainless steel casing


g

230/1/50 fan motor

Nomenclature

Note: Subject to change without notice

H WM 30 2 A 4R x 6F

HC Heat-Exchangers

Fins per inch

Wall Mount

No. of coil rows (2, 3, 4 or 5)

Fan diameter - cm
No. of fans
Vintage
Page 72

HC

HWM RANGE OF WALL MOUNTED


COOLERS WITH 300mm FANS

Technical Data
Model

HWM

301-A-2R

301-A-3R

301-A-4R

Fin Spacing 6F

301-A-5R

(4,2mm)

0.71
1.03
1.21
1.30
For other conditions refer to table under appendix A

Nominal Capacity R22


kW @ ITD = 6K and Te = - 5C
Coil surface area

m2

1.51

2.27

3.02

3.78

Air flow - frost free

m3 / s

0.37

0.31

0.26

0.23

Face velocity - frost free

m/s

4.90

4.10

3.44

2.96

Mass

kg

16.00

17.00

17.00

18.00

Tube internal volume

litre

General Data
Air throw

0.79
11

1.18
10

1.57
9

1.97
8

No. x Dia

1x300

1x300

1x300

1x300

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

1/2"

1/2"

1/2"

1/2"

int

int

int

int

302-A-3R

302-A-4R

302-A-5R

Fans

Expansion Valve Internally / externally equalized:

Technical Data
Model

302-A-2R

HWM

Fin Spacing 6F

(4,2mm)

1.79
2.45
2.6
2.70
For other conditions refer to table under appendix A

Nominal Capacity R22


kW @ ITD = 6K and Te = - 5C
Coil surface area

m2

3.02

4.53

6.04

7.55

Air flow - frost free

m3 / s

0.75

0.63

0.52

0.45

Face velocity - frost free

m/s

4.90

4.10

3.44

2.96

Mass

kg

30.00

31.00

32.00

33.00

Tube internal volume

litre

General Data
Air throw
Fans

1.47
13

2.20
12

2.93
11

3.66
10

No. x Dia

2x300

2x300

2x300

2x300

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

1/2"

5/8"

5/8"

5/8"

ext

ext

ext

ext

Frequency
Hz
50

RPM

Power
W
25/90

Amperage
A
0.52

Expansion Valve Internally / externally equalized:

Fan Wiring
Square shaded-pole motor (standard)
Diameter
Voltage
mm
V
300
230

1300

L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

Page 73

HWM-300-A
Page 2 of 3
29.09.2009

HWM RANGE OF WALL MOUNTED


COOLERS WITH 300mm FANS

HC

HWM-300-A
Page 3 of 3
29.09.2009

Physical Data: HWM-301-A

600

725

605

155

Note: subject to change without notice

Physical Data: HWM-302-A

1120

155

605
725

Note: subject to change without notice

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (011) 674-1237
Fax: (011) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (031) 202-7829
Fax: (031) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021) 551-7873
Fax: (021) 551-1751

Page 74

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

HDD - 200 - A
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HDD RANGE OF DUAL DISCHARGE
COOLERS WITH 200mm FAN
General Description

The HDD-200 range of dual discharge coolers comprises 3 models for both medium and low temperature
applications to -10C utilising 200 mm diameter fans.
The range is available in a 4,2mm fin spacing, i.e. 6 fpi, with or without electric defrost and is compatible with
Refrigerants R134a, R22, R404A and R507 etc. Other fin spacings are available on request.
The dual discharge cooler has an injection moulded plastic driptray, suitable for temperatures down to 10C, easily removable with 4 knurled driptray screws.
The entire unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin coil

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel casing

RAL-9003 White epoxy coating


230/1/ 50 Hz fan motor
Injection moulded plastic driptray
Thermo-protector (low temp.)
Electric defrost heating (low temp.)

Nomenclature
H DD 20 1 4R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)


No. of coil rows (2,3 or 4 row)
No. of fans

Fan diameter - cm
Page 75

Note:subjecttochangewithoutnotice

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 200mm FAN

HDD - 200 - A
Page 2 of 3
01-10-2009

Technical Data
Model

HDD

201-A-2R

201-A-3R

201-A-4R

Fin Spacing 6F
Nominal Capacity R22

0.38

(4,2mm)

0.48

0.53

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = -5C


m2

1.17

1.76

2.34

m3 / s
m/s

0.10

0.09

0.08

1.63

1.49

1.38

Mass

kg

4.30

4.70

5.00

Tube internal volume

litre

0.35

0.53

0.7

1.8

1.7

Liquid connection

inch

3/8"

3/8"

3/8"

Suction connection

inch

3/8"

3/8"

3/8"

Elect. defrost 230V

kW

0.30

0.30

0.30

Coil external surface area


Air flow - frost free
Face velocity

General Data
Air throw

Physical Data
NOTE:
Models:
201 2R and above are suitable for internally
equalized expansion valves

NOTE:
Drain: 1/2" BSPM connection
Fan:
-200mm diameter
230 / 1/ 50Hz
36 W x 0.25 A each

Page 76

Note:subjecttochangewithoutnotice

HDD - 200 - A
Page 3 of 3
01-10-2009

HDD RANGE OF UNIT COOLERS


WITH 200mm FANS
Defrost Wiring
Model
Phase
201-A

L1

Heater no.

Watts

Volt

Amp

Klixon

300

230

1.3

37T31(5A)

1+2

Defrost heater placement.


L1

AIR

AIR
1

2R

L1
N

AIR

HDD 201

AIR
1

3R
KLIXON
CLOSE -5C
OPEN +25C

AIR

AIR
1

HEATER

Motor

Voltage
V

Frequency
Hz

Speed
rpm

Power
W

Amperage
A

200

230

50

1300

10/36

0.25

L1 N

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

4R

Diameter
mm

ShadedPole

F1

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 77

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HDD - 250 - B
Page 1 of 4
01-10-2009

HC HEAT - EXCHANGERS
HDD RANGE OF DUAL DISCHARGE
COOLERS WITH 250mm FAN
General Description

The HDD-250 range of dual discharge coolers comprises 6 models for both medium and low temperature
applications to -10C utilising 250 mm diameter fans.
The range is available in a 4,2mm fin spacing, i.e. 6 fpi, with or without electric defrost and is compatible with
Refrigerants R134a, R22, R404A and R507 etc. Other fin spacings are available on request.
The dual discharge cooler has an injection moulded plastic driptray, suitable for temperatures down to 10C, easily removable with 4 knurled driptray screws.
The entire unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin coil

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel casing

RAL-9003 White epoxy coating


230/1/ 50 Hz fan motor
Injection moulded plastic driptray on
single fan model
Thermo-protector (low temp.)
Electric defrost heating (low temp.)

Nomenclature
H DD 25 1 4R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)


No. of coil rows (2,3 or 4 row)
No. of fans

Fan diameter - cm
Page 78

Note:subjecttochangewithoutnotice

HDD - 250 - B
Page 2 of 4
01-10-2009

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 250mm FAN

Model

Technical Data
251-A-2R 251-A-3R

HDD

251-A-4R

252-A-2R

Fin Spacing 6F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C
Coil surface area
m2
Air flow (dry)
m3 / s
Face velocity
m/s
Mass
kg

Tube internal volume


Air throw
Fans
Liquid connection
Suction connection
Elect. Defrost

litre
m
No. x Dia
inch
inch
kW

0.78
1.76
0.19
2.22
5.70

252-A-3R

252-A-4R

(4,2mm)

1.67
2.03
0.95
1.03
For other conditions refer to table under appendix A
3.51
5.27
2.63
3.52
0.39
0.33
0.16
0.15
2.22
1.89
1.89
1.69
9.50
10.50
6.20
6.80

General Data
0.53
0.79
2.7
2.3
1x250
1x250
3/8"
3/8"
3/8"
3/8"
0.45
0.45

1.05
2.1
1x250
1/2"
1/2"
0.45

1.06
2.7
2x250
1/2"
1/2"
0.90

1.58
2.3
2x250
1/2"
5/8"
0.90

2.18
7.02
0.29
1.69
11.50

2.1
2.1
2x250
1/2"
5/8"
0.90

NOTE:
Drain: 1/2"BSPMconnection
NOTE:
Models:
251 2R/ 3Rare suitable for internally equalized expansion valves
While 251 4R above are suitable for externally
equalized expansion valves
Page 79

Fan:
250mmdiameter
230/1/50Hz
60Wx0.42Aeach

Note:subjecttochangewithoutnotice

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 250mm FAN

HDD - 250 - B
Page 3 of 4
01-10-2009

NOTE:
Drain: 1/2"BSPMconnection
Fan:
250mmdiameter
230/1/50Hz
60Wx0.42Aeach

Page 80

Note:subjecttochangewithoutnotice

HDD - 250 - B
Page 4 of 4
01-10-2009

HDD RANGE OF UNIT COOLERS


WITH 250mm FANS
Defrost Wiring
Model
Phase
251-A
251-A

L1
L1

Heater no.

Watts

Volt

Amp

Klixon

450
900

230
230

2.0
4.0

37T31(5A)
37T31(5A)

1+2
1+2

Defrost heater placement.


L1

AIR

AIR

1
HDD 250

L1
N

2R

AIR

AIR
1

3R
KLIXON
CLOSE -5C
OPEN +25C

AIR

HEATER

AIR
1

4R
Motor

ShadedPole

L1 N

Diameter
mm

Voltage
V

Frequency
Hz

Speed
rpm

Power
W

Amperage
A

250

230

50

1300

16/60

0.42

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 81

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HDD-300-A
Page 1 of 5
01-10-2009

HC HEAT - EXCHANGERS
HDD RANGE OF DUAL DISCHARGE
COOLERS WITH 300mm FAN
General Description

The HDD-300-A range of dual discharge coolers comprises 24 models for both medium and low temperature
applications utilising 300 mm diameter fans and high efficiency rifle bore copper tube. The range is available
in either 4 fins/inch or 6 fins/inch, with or without electric defrost and is compatible with Refrigerants R134a,
R22, R404A, R507A, etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel casing

RAL-9003 White epoxy coating

Stainless steel tubes

230/1/ 50 Hz fan motor


Aluminium drain fitting
Thermo-protector (low temp.)
Electric defrost heating (low temp.)

Nomenclature
H DD 30 1 - A - 4R - 6F - E
HC Heat-Exchangers

Electric defrost (if required)

Model

Fins per inch (4 or 6)

Fan diameter -cm

No. of coil rows (2,3 or 4 row)

No. of fans

Vintage
Page 82

Note:subjecttochangewithoutnotice

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 300mm FAN

HDD-300-A
Page 2 of 5
01-10-2009

Technical Data
Model

HDD

301-2R

301-3R

301-4R

302-2R

Fin Spacing 6F
Nominal Capacity R22

1.97

2.49

kW @ ITD = 6K and Te = - 5C

2.81

302-3R

302-4R

(4,2mm)

3.96

5.01

5.66

For other conditions refer to table under appendix A

Coil surface area

m2

5.97

8.95

11.94

11.94

17.9

23.87

Air flow - frost free

m3 / s
m/s

0.66

0.57

0.51

1.31

1.14

1.03

3.44

2.99

2.70

3.44

2.99

2.70

kg

16

16

17

24

25.4

27

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

1.54

2.01

2.41

(6,35mm)
3.10

4.11

4.84

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2

4.06

6.09

8.12

8.12

12.19

16.25

Air flow - frost free

m3 / s
m/s

0.72

0.65

0.58

1.44

1.29

1.17

3.78

3.40

3.06

3.78

3.37

3.06

Mass

kg

15

16

17

24

25.22

27

Tube internal volume

litre

1.24

2.49

2.25

3.37

4.49

Face velocity

General Data
Air throw

1.86

2.6

2.4

2.6

2.4

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

1/2"

1/2"

1/2"

5/8"

5/8"

7/8"

Elect. Defrost / 230V

kW

1.08

1.08

1.08

2.16

2.16

2.16

Model

HDD

303-2R

303-3R

303-4R

304-2R

304-3R

304-4R

5.96

7.53

Fin Spacing 6F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C

8.49

(4,2mm)

7.97

10.04

11.34

For other conditions refer to table under appendix A

Coil surface area

m2

17.90

26.85

35.81

23.87

35.81

47.74

Air flow - frost free

m3 / s
m/s

1.97

1.71

1.54

2.62

2.28

2.05

3.44

2.99

2.70

3.44

2.99

2.70

kg

31

34

36

39

41.93

45

4.66

6.18

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C

7.27

(6,35mm)
6.22

8.24

9.71

For other conditions refer to table under appendix A

Coil surface area

m2

12.19

18.28

24.37

16.25

24.37

32.50

Air flow - frost free

m3 / s
m/s

2.16

1.93

1.75

2.88

2.57

2.34

3.78

3.37

3.06

3.78

3.37

3.06

kg

31

33

35

39

41.57

44

Face velocity
Mass

General Data
Tube internal volume

litre

3.25

4.87

6.50

4.25

6.38

8.50

2.6

2.4

2.6

2.4

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

Elect. Defrost / 230V

kW

3.24

3.24

3.24

4.32

4.32

4.32

Air throw

Page 83

Note:subjecttochangewithoutnotice

HDD-300-A
Page 3 of 5
01-10-2009

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 300mm FAN

Model

HDD

301-A

302-A

303-A

500

500

500

500

540

500

500

540

500

540

AIR

304-A

AIR

NOTE:
Models:
3012R4Fissuitableforinternallyequalizedexpansionvalves
whiletheremainingmodelsrequireexternally
equalizedexpansionvalves
Drain: 3/4"BSPM
1/2"Rifleborecoppertube
Fan:300mmdiameter
230/1/50Hz
110Wx0.75Aeach

Page 84

Note:subjecttochangewithoutnotice

HDD-300-A
Page 4 of 5
01-10-2009

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 300mm FAN

Defrost Wiring
Model
Phase
301-A-2R
301-A-3R
301-A-4R
302-A-2R
302-A-3R
302-A-4R
303-A-2R
303-A-3R
303-A-4R

L1
L1
L1
L1
L1
L1
L1
L1
L1
L2
L1
L1
L1
L2

303A4R

304-A-2R
304-A-3R
304-A-4R
304-A-4R

Heater no.

Watts

Volt

Amp

Klixon

1+2+3+4
1+2+3+4+5+6
1+2+3+4+5+6+7+8
1+2+3+4
1+2+3+4+5+6
1+2+3+4+5+6+7+8
1+2+3+4
1+2+3+4+5+6
1+2+3+4
5+6+7+8
1+2+3+4
1+2+3+4+5+6
1+2+3+4
5+6+7+8

1200
1800
2400
2200
3300
4400
3200
4800
3200
3200
4200
4200
4200
4200

230
230
230
230
230
230
230
230
230
230
230
230
230
230

5.2
7.8
10.4
9.6
14.3
19.1
13.9
20.9
13.9
13.9
18.3
18.3
18.3
18.3

14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

L1

Defrost heater placement.


T

AIR

AIR

HDD 301/302/303/304 -2R

2R

L1

AIR

AIR

HDD 301/302/303/304 -3R

3R

L1

3
T

AIR
1

AIR

4R

HDD 301/302/-4R
L1

L2

HDD 303/304/-4R

Page 85

Note:subjecttochangewithoutnotice

HDD-300-A
Page 5 of 5
01-10-2009

HDD RANGE OF DUAL DISCHARGE


COOLERS WITH 300mm FAN

Motor

Diameter

ShadedPole
ExternalRotor

L1 N

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Voltage

Frequency

Speed

Power

Amperage

mm

Hz

rpm

300
300

230
230

50
50

1300
1400

34/110
0.68

0.75
0.3

Standard
Standard

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 86

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HC

HDD-350-A
Page 1 of 6
15.09.2009

HC HEAT-EXCHANGERS

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 350mm FAN

General Description
The HDD-350-A range of dual discharge coolers comprises 32 models for both medium and low temperature
applications utilising 350 mm diameter fans. The range is available in either 4 fins/inch or 6 fins/inch, with or
without electric defrost and is compatible with Refrigerants R134a
R134a, R22
R22, R404A
R404A, R507A
R507A, etc
etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel tubes

RAL 9003 white epoxy coating

Stainless steel casing

230/1/50 fan motor

400/3/50 fan motor

Aluminium drain fitting


Thermo-protector (low temp.)

Note: Subject to change without notice

Electric
El t i d
defrost
f th
heaters
t
(low
(l
temp.)
t
)

Nomenclature

H DD 35 2 A 4R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Fan diameter - cm

No. of coil rows (3, 4, 5 or 6)

No. of fans
Vintage
Page 87

HC

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 350mm FANS

HDD-350-A
Page 2 of 6
15.09.2009

Technical Data
Model

HDD

351-A-3R

351-A-4R

351-A-5R

Fin Spacing 6F
4.07

351-A-6R

(4,2mm)

Nominal Capacity R22

3.50

kW @ ITD = 6K and Te = - 5C

For other conditions refer to table under index 24

4.45

4.67

Coil surface area

m2

13.00

17.33

21.67

26.00

Air flow - frost free

m3 / s

0.78

0.75

0.73

0.70

Face velocity - frost free

m/s

2.70

2.61

2.52

2.43

Mass

kg

24

26

28

30

Fin Spacing 4F
3.35

(6,35mm)

Nominal Capacity R22

2.77

3.81

kW @ ITD = 6K and Te = - 5C

For other conditions refer to table under index 24

4.16

Coil surface area

m2

8.96

11.95

14.93

17.92

Air flow - frost free

m3 / s

0.80

0.78

0.76

0.74

Face velocity - frost free

m/s

2.77

2.70

2.63

2.56

Mass

kg

24

26

28

30

Tube internal volume

litre

2.57

3.42

4.28

5.13

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

7/8"

7/8"

7/8"

7/8"

Electric defrost/230V

kW

1.50

2.50

2.50

3.00

352-A-4R

352-A-5R

352-A-6R

General Data
Air throw

Technical Data
Model

HDD

352-A-3R

Fin Spacing 6F
8.16

(4,2mm)

Nominal Capacity R22

7.04

kW @ ITD = 6K and Te = - 5C

For other conditions refer to table under index 24

8.93

9.37

Coil surface area

m2

26.00

34.67

43.33

52.00

Air flow - frost free

m3 / s

1.56

1.50

1.46

1.40

Face velocity - frost free

m/s

2.70

2.61

2.52

2.43

Mass

kg

38

42

46

50

Fin Spacing 4F
6.72

(6,35mm)

Nominal Capacity R22

5.55

kW @ ITD = 6K and Te = - 5C

For other conditions refer to table under index 24

7.65

8.33

Coil surface area

m2

17.92

23.89

29.87

35.84

Air flow - frost free

m3 / s

1.60

1.56

1.52

1.48

Face velocity - frost free

m/s

2.77

2.70

2.63

2.56

Mass

kg

39

43

47

51

Tube internal volume

litre

5.13

6.84

8.55

10.26

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

1-1/8"

1-1/8"

1-1/8"

1-1/8"

Electric defrost/230V

kW

3.00

5.00

5.00

6.00

General Data
Air throw

Note: subject to change without notice

Page 88

HC

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 350mm FANS

HDD-350-A
Page 3 of 6
15.09.2009

Technical Data
Model

HDD

353-A-3R

353-A-4R

353-A-5R

Fin Spacing 6F
Nominal Capacity R22

10.58

kW @ ITD = 6K and Te = - 5C

12.28

353-A-6R

(4,2mm)
13.39

14.08

For other conditions refer to table under index 24

Coil surface area

m2

39.00

52.00

65.00

78.00

Air flow - frost free

m3 / s

2.34

2.25

2.19

2.10

Face velocity - frost free

m/s

2.70

2.61

2.52

2.43

Mass

kg

53

58

64

69

Fin Spacing 4F
10.10

(6,35mm)

Nominal Capacity R22

8.34

kW @ ITD = 6K and Te = - 5C

For other conditions refer to table under index 24

11.48

12.53

Coil surface area

m2

26.89

35.85

44.82

53.78

Air flow - frost free

m3 / s

2.40

2.34

2.28

2.22

Face velocity - frost free

m/s

2.77

2.70

2.63

2.56

Mass

kg

54

60

66

72

Tube internal volume

litre

7.70

10.26

12.83

15.39

Liquid connection

inch

5/8"

5/8"

5/8"

5/8"

Suction connection

inch

1-1/8"

1-1/8"

1-3/8"

1-3/8"

Electric defrost/230V

kW

4.50

7.50

7.50

9.00

354-A-3R

354-A-4R

354-A-5R

354-A-6R

General Data
Air throw

Model

HDD

Fin Spacing 6F
Nominal Capacity R22

14.14

kW @ ITD = 6K and Te = - 5C

16.40

(4,2mm)
17.9

18.77

For other conditions refer to table under index 24

Coil surface area

m2

52.00

69.33

86.67

104.00

Air flow - frost free

m3 / s

3.12

3.00

2.92

2.80

Face velocity - frost free

m/s

2.70

2.61

2.52

2.43

Mass

kg

67

74

82

89

Fin Spacing 4F
Nominal Capacity R22

11.14

13.49

(6,35mm)
15.32

16.72

For other conditions refer to table under index 24

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2

35.85

47.80

59.75

71.70

Air flow - frost free

m3 / s

3.20

3.12

3.04

2.96

Face velocity - frost free

m/s

2.77

2.70

2.63

2.56

Mass

kg

69

77

84

92

Tube internal volume

litre

10.26

13.68

17.10

20.52

Liquid connection

inch

5/8"

5/8"

5/8"

5/8"

Suction connection

inch

1-3/8"

1-3/8"

1-3/8"

1-3/8"

Electric defrost/230V

kW

6.00

10.00

10.00

12.00

General Data
Air throw

Note: subject to change without notice

Page 89

HC

HDD-350-A
Page 4 of 6
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 350mm FANS
Physical Data
Model

HDD

351-A

352-A

353-A

354-A

600

540

540

540

600

540

540

600

540

600

AIR

AIR

NOTE:
All models are suitable for externally
equalized expansion valves

Note: subject to change without notice

Page 90

HDD-350-A
Page 5 of 6
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 350mm FANS

HC

Defrost Wiring
Range

Model

Phase Heater no.

HDD

351-A-3R
351-A-4R
351-A-5R
351-A-6R
352-A-3R
352-A-4R
352-A-5R
352-A-6R
353-A-3R
353-A-4R

L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2

353-A-5R
353-A-6R
354-A-3R
354-A-4R
354-A-5R
354-A-6R

Watts Volt Amp Klixon

1+2+3+4+5+6
1+2+3+4+5+6+7+8
1+2+3+4+5+6+7+8
1+2+3+4+5+6+7+8+9+10
1+2+3+4+5+6
1+2+3+4+5+6+7+8
1+2+3+4+5+6+7+8
1+2+3+4+5+6+7+8+9+10
1+2+3+4+5+6
1+2+3+4
5+6+7+8
1+2+3+4
5+6+7+8
1+2+3+4+5
6+7+8+9+10
1+2+3
4+5+6
1+2+3+4
5+6+7+8
1+2+3+4
5+6+7+8
1+2+3+4+5
6+7+8+9+10

1500
2000
2000
2500
3000
4000
4000
5000
4500
3000
3000
3000
3000
3750
3750
3000
3000
4000
4000
4000
4000
5000
5000

230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

6.5
8.7
8.7
10.9
13.0
17.4
17.4
21.7
19.6
13.0
13.0
13.0
13.0
16.3
16.3
13.0
13.0
17.4
17.4
17.4
17.4
21.7
21.7

14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

Heater
L1

Klixon:

Close -5C
Open +25C

HDD-351-A to 353-A-3R

L1

L2

Page 91

10

HDD-353-A-4R to HDD-354-A-6R

HC

HDD-350
Page 6 of 6
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 350mm FANS

Defrost Heater Placement

3 Row

5 Row
3

1
8

4 Row

6 Row

10

Fan Wiring

Standard
Option

Diameter
mm
350
350

Voltage
V
230
400

Frequency
Hz
50
50

Standard

L1 N

Amperage
A
0.58
0.33

Option

L1 L2 L3 E

F1

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

Speed Power
rpm
W
1400
130
1420
115

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 92

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

HC

HC HEAT-EXCHANGERS

HDD-500-A
Page 1 of 8
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FAN

General Description
The HDD-500 range of dual discharge coolers comprises 24 models for both medium and low temperature
applications utilising 500 mm diameter fans. The range is available in either 4 fins/inch or 6 fins/inch, with or
without electric defrost and is compatible with refrigerants R134a
R134a, R22
R22, R404A
R404A, R507A
R507A, etc
etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated GI casing

Stainless steel tubes

RAL 9003 white epoxy coating

Stainless steel casing

400/3/50 fan motor


Stainless steel driptray
Brass drain fitting

Note: Subject to change without notice

Thermo-protector
Th
t t (low
(l
temp.)
t
)
Electric defrost heating (low temp.)

Nomenclature

H DD 50 2 A 4R x 6F E DELTA

HC Heat-Exchangers

Star or Delta wired

Dual Discharge

Electric Defrost (if required)

Fan diameter - cm

Fins per inch (4 or 6)

No. of fans

No. of coil rows (3, 4, 5 or 6)

Vintage

Page 93

HC

HDD-500-A
Page 2 of 8
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS
Technical Data
Delta option

Model

HDD

501-A-3R

501-A-4R

501-A-5R

501-A-6R

Fin Spacing 6F
Nominal Capacity R22

11.18

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2
m3 / s

Air flow - frost free

13.15

14.55

502-A-3R

502-A-4R

(4,2mm)

15.51

22.43

26.38

For other conditions refer to table under appendix A


38.81

51.75

64.68

77.62

77.62

2.57

2.52

2.47

2.42

5.14

103.49
5.04

Face velocity - frost free

m/s

2.99

2.93

2.88

2.81

2.99

2.93

Mass

kg

72

77

84

90

124

136

17.29

21.15

Fin Spacing 4F
Nominal Capacity R22

8.62

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2
m3 / s

Air flow - frost free

10.56

12.10

(6,35mm)

13.34

For other conditions refer to table under appendix A


26.75

35.67

44.58

53.50

53.50

2.61

2.57

2.53

2.49

5.22

71.34
5.14

Face velocity - frost free

m/s

3.04

2.99

2.95

2.90

3.04

2.99

Mass

kg

72

76

82

88

122

133

501-A-5R

501-A-6R

502-A-3R

502-A-4R

Star option
Model

HDD

501-A-3R

501-A-4R

9.99

11.58

Fin Spacing 6F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C
Coil surface area

m2
m3 / s

Air flow - frost free

12.64

(4,2mm)

13.30

20.03

23.20

For other conditions refer to table under appendix A


38.81

51.75

64.68

77.62

77.62

2.14

2.08

2.03

1.98

4.28

103.49
4.16

Face velocity - frost free

m/s

2.49

2.43

2.36

2.30

2.49

2.43

Mass

kg

72

77

84

90

124

136

7.77

9.40

15.56

18.85

Fin Spacing 4F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C
Coil surface area
Air flow - frost free

m2
m3 / s

10.67

(6,35mm)

11.66

For other conditions refer to table under appendix A


26.75

35.67

44.58

53.50

53.50

2.19

2.14

2.10

2.06

4.38

71.34
4.28

Face velocity - frost free

m/s

2.54

2.49

2.44

2.39

2.54

2.49

Mass

kg

72

76

82

88

122

133

20.41

General Data
Tube internal volume

litre

7.65

10.21

12.76

15.31

15.31

Liquid connection

inch

5/8"

5/8"

5/8"

5/8"

7/8"

7/8"

Suction connection

inch

1-3/8"

1-3/8"

1-3/8"

1-3/8"

1-5/8"

1-5/8"

Electric defrost/230V

kW

3.15

6.30

6.30

8.10

7.20

12.60

Air throw (delta option)

Fan motor

400/ 3/50Hz Delta

830W 1.65 Amps each. 1330 Rpm

Fan motor

400/ 3/50Hz Star

560W 0.98 Amps each. 1020 Rpm

Note: subject to change without notice


Page 94

HC

HDD-500-A
Page 3 of 8
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS
Technical Data
Delta option

Model

HDD

502-A-5R

502-A-6R

503-A-3R

503-A-4R

Fin Spacing 6F
Nominal Capacity R22

29.16

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2
m3 / s

Air flow - frost free

31.06

32.63

503-A-5R

503-A-6R

(4,2mm)

38.42

42.51

45.20

For other conditions refer to table under appendix A


129.37

155.24

109.40

145.87

182.33

4.94

4.84

7.67

7.51

7.32

218.80
7.16

Face velocity - frost free

m/s

2.88

2.81

3.17

3.10

3.02

2.95

Mass

kg

148

160

173

195

211

228

35.33

38.99

Fin Spacing 4F
Nominal Capacity R22

24.24

kW @ ITD = 6K and Te = - 5C
Coil surface area

m2
m3 / s

Air flow - frost free

26.73

25.17

(6,35mm)

30.82

For other conditions refer to table under appendix A


89.16

107.00

75.40

100.50

125.67

5.06

4.98

7.79

7.67

7.54

150.80
7.40

Face velocity - frost free

m/s

2.95

2.90

3.22

3.17

3.11

3.05

Mass

kg

144

155

170

190

206

221

503-A-3R

503-A-4R

503-A-5R

503-A-6R

Star option
Model

HDD

502-A-5R

502-A-6R

25.32

26.64

Fin Spacing 6F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C
Coil surface area

m2
m3 / s

Air flow - frost free

29.16

(4,2mm)

33.80

36.86

38.78

For other conditions refer to table under appendix A


129.37

155.24

109.40

145.87

182.33

4.06

3.96

6.37

6.18

6.01

218.80
5.84

Face velocity - frost free

m/s

2.36

2.30

2.63

2.55

2.48

2.41

Mass

kg

148

160

173

195

211

228

21.38

23.35

31.17

34.02

Fin Spacing 4F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C
Coil surface area
Air flow - frost free

m2
m3 / s

22.66

(6,35mm)

27.42

For other conditions refer to table under appendix A


89.16

107.00

75.40

100.50

125.67

4.20

4.12

6.50

6.35

6.22

150.80
6.09

Face velocity - frost free

m/s

2.54

2.49

2.68

2.62

2.57

2.52

Mass

kg

144

155

170

190

206

221

43.16

General Data
Tube internal volume

litre

25.51

30.62

21.58

28.77

35.96

Liquid connection

inch

7/8"

7/8"

7/8"

7/8"

1-1/8"

1-1/8"

Suction connection

inch

1-5/8"

1-5/8"

2-1/8"

2-1/8"

2-1/8"

2-1/8"

Electric defrost/230V

kW

12.60

16.20

10.80

18.90

18.90

24.30

Air throw (delta option)

Fan motor

400/ 3/50Hz Delta

830W 1.65 Amps each. 1330 Rpm

Fan motor

400/ 3/50Hz Star

560W 0.98 Amps each. 1020 Rpm

Note: subject to change without notice


Page 95

HC

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS

HDD-500-A
Page 4 of 8
15.09.2009

Physical Data
Model

HDD

501-A

502-A

A
B

1000

940

503-A
883

1000

883

943

NOTE:
All models are suitable for externally
equalized expansion valves

Note: subject to change without notice

Page 96

HC

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS

HDD-500-A
Page 5 of 8
15.09.2009

Defrost Wiring
Model

Phase Heater no.

501-A-3R

L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
L3
L4
L1
L2
L3
L4
L1
L2
L3
L4
L1
L2
L1
L2
L3
L4
L1
L2
L3
L4
L1
L2
L3
L4
L5
L6

501-A-4R
501-A-5R
501-A-6R
502-A-3R
502-A-4R

502-A-5R

502-A-6R

503-A-3R
503-A-4R

503-A-5R

503-A-6R

Watts Volt Amp Klixon

1+2+3+4
5+6+7+8
1+2+3+4+5+6+7
8+9+10+11+12+13+14
1+2+3+4+5+6+7
8+9+10+11+12+13+14
1+2+3+4+5+6+7+8+9
10+11+12+13+14+15+16+17+18
1+2+3+4
5+6+7+8
1+2+3+4
5+6+7
8+9+10+11
12+13+14
1+2+3+4
5+6+7
8+9+10+11
12+13+14
1+2+3+4+5
6+7+8+9
10+11+12+13+14
15+16+17+18
1+2+3+4
5+6+7+8
1+2+3+4
5+6+7
8+9+10+11
12+13+14
1+2+3+4
5+6+7
8+9+10+11
12+13+14
1+2+3
4+5+6
7+8+9
10+11+12
13+14+15
16+17+18

Page 97

1800
1800
3150
3150
3150
3150
4050
4050
3600
3600
3600
2700
3600
2700
3600
2700
3600
2700
4500
3600
4500
3600
5400
5400
5400
4050
5400
4050
5400
4050
5400
4050
4050
4050
4050
4050
4050
4050

230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

7.8 14T31(25A)
7.8 14T31(25A)
13.7 14T31(25A)
13.7 14T31(25A)
13.7 14T31(25A)
13.7 14T31(25A)
17.6 14T31(25A)
17.6 14T31(25A)
15.7 14T31(25A)
15.7 14T31(25A)
15.7
14T31(25A)
11.7
15.7
14T31(25A)
11.7
15.7
14T31(25A)
11.7
15.7
14T31(25A)
11.7
19.6
14T31(25A)
15.7
19.6
14T31(25A)
15.7
23.5 14T31(25A)
23.5 14T31(25A)
23.5
14T31(25A)
17.6
23.5
14T31(25A)
17.6
23.5
14T31(25A)
17.6
23.5
14T31(25A)
17.6
17.6
17.6 14T31(25A)
17.6
17.6
17.6 14T31(25A)
17.6

HC

HDD-500-A
Page 6 of 8
15.09.2009

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS

Defrost Wiring
L1

L2

HDD-501-A, HDD-502-A-3R, HDD-503-A-3R

L1

L2

L2

L3

10

12

11

13

14

HDD-502-A-4R, HDD-502-A-5R, HDD-502-A-6R, HDD-503-A-4R, HDD-503-A-5R

L2

L2

L1

L1

L2

L2

10

11

12

13

14

15

16

17

HDD-503-A-6R

Page 98

18

HC

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS

Defrost Heater Placement

Page 99

HDD-500-A
Page 7 of 8
15.09.2009

HC

HDD RANGE OF DUAL DISCHARGE COOLERS


WITH 500mm FANS

HDD-500-A
Page 8 of 8
15.09.2009

Fan Wiring
Diameter
mm
500

Voltage
V
400

L1 L2 L3

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel:
(011) 674
674-12
1237
37
Tel: (011)
Fax: (011) 674-1268

Frequency
Hz
50

TOP TOP

RPM
1330

Power
W
830

Amperage
A
1.65

E
L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
202-7
Tel:
(031) 202
7829
829
Tel: (031)
Fax: (031) 202-7849

Page 100

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021)
Tel:
(021) 551
551-7
7873
873
Fax: (021) 551-1751

NAMIBIA
P.O Box 1301
Windhoek
T
261-647
Tel:
el: (0926461)
(0926461) 261
647
Fax: (0926461) 216-201

HCT - 250 - B
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HCT RANGE OF UNIT COOLERS
WITH 250mm FANS
General Description

The HCT-250 range of unit coolers comprises 12 models for both medium and low temperature applications
utilising 250 mm diameter fans.
The range is available in 6 fins per inch spacings, with or without electric defrost and is compatible with
Refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

AIR

Standard Features

Optional Features

Rifle bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated aluminium


_casing

Stainless steel tubes


Stainless steel casing

RAL 9003 white epoxy coating


230/1/50 Hz fan motor
Hinged drip tray
Aluminium drain fitting
Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H CT 25 2 3R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model
CT - Ceiling type

Fins per inch (6)

Fan diameter - cm

No. of fans 1 to 4

No. of coil rows (2,3 or 4 row)

Page 101

Note:subjecttochangewithoutnotice

HCT - 250 - B
Page 2 of 3
01-10-2009

HCT RANGE OF UNIT COOLERS


WITH 250mm FANS
Technical Data
Model

HCT

251-2R 251-3R 251-4R 252-2R 252-3R 252-4R 253-2R 253-3R 253-4R 254-2R 254-3R 254-4R

Fin Spacing 6F
Nominal Capacity R22

0.41

0.55

0.63

kW @ ITD = 6K and Te = -5C

0.97

1.21

1.33

(4,2mm)

1.49

1.82

2.00

1.99

2.43

2.67

For other conditions refer to table under appendix A

Coil surface area

m2

1.0

1.5

2.0

2.0

3.0

4.0

3.0

4.5

6.0

4.0

6.0

8.0

Air flow - frost free

m3 / s
m/s

0.14

0.12

0.11

0.28

0.24

0.22

0.43

0.36

0.32

0.57

0.49

0.43

2.91

2.49

2.22

2.91

2.49

2.22

2.91

2.49

2.22

2.91

2.49

2.22

kg

5.2

5.5

5.7

7.8

8.4

8.9

10.9

11.7

12.4

14.0

15.0

16.0

Face velocity
Mass

General Data
Tube internal volume

litre

0.35

0.53

0.71

0.62

0.94

1.25

0.89

1.34

1.79

1.75

2.33

10

10

10

10

Liquid connection

inch

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Elect. defrost 230V

kW

0.18

0.18

0.18

0.36

0.36

0.36

0.54

0.54

0.54

0.72

0.72

0.72

Air throw

1.16

Physical Data

NOTE:
Models:
HCT2512R/3R/4Raresuitablefor
Internallyequalizedexpansionvalves
Models:
2522Randabovearesuitableforexternally
equalizedexpansionvalves

NOTE:
Drain3/4"BSPMFitting
Fan:
250mmdiameter
230/1/50Hz
620Wx0.42Aeach

1400
HCT 254
1075
HCT 253
750
HCT 252

450

425
HCT 251
177
450

18

AIR

Page 102

Note:subjecttochangewithoutnotice

HCT - 250 - B
Page 3 of 3
01-10-2009

HCT RANGE OF UNIT COOLERS


WITH 250mm FANS
Defrost Wiring
Model
Phase

Heater no.

Watts

Volt

Amp

Klixon

251-2R

L1

180

230

0.8

37T31 (5A)

251-3R

L1

180

230

0.8

37T31 (5A)

251-4R

L1

180

230

0.8

37T31 (5A)

252-2R

L1

360

230

1.6

37T31 (5A)

252-3R

L1

360

230

1.6

37T31 (5A)

252-4R

L1

360

230

1.6

37T31 (5A)

253-2R

L1

540

230

2.3

37T31 (5A)

253-3R

L1

540

230

2.3

37T31 (5A)

253-4R

L1

540

230

2.3

37T31 (5A)

254-2R

L1

720

230

3.1

37T31 (5A)

254-3R

L1

720

230

3.1

37T31 (5A)

254-4R

L1

720

230

3.1

37T31 (5A)

KLIXON
CLOSE -5C
OPEN +25C

Defrost heater placement.

HEATER
Fin Block

Heater 1

L1

L1

HCT 251

Motor
Shaded Pole

L1 N

HCT 252

Heater 4

L1

Heater 3

L1

Heater 2

Voltage
V
230

L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

HCT 253

Diameter
mm
250

Frequency Speed
Hz
rpm
50
1300

Power
W
16/60

Amperage
A
0.42

HCT 254

Standard

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 103

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HCR - 300
Page 1 of 3
15-07-2011

HC HEAT - EXCHANGERS
HCR RANGE OF UNIT COOLERS
WITH 300mm FANS

General Description
The HCR-300 range of unit coolers comprises 16 models for both medium and low temperature applications
utilising 300 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is
compatible with Refrigerants R134a, R22, R404A and R507 etc.
The unit cooler has a unique angular design for flush mounting to the wall without hindering the airflow.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel tubes

RAL 9003 white epoxy coating

Stainless steel casing

230 /1/ 50 Hz fan motor

230 /1/50 Hz Energy saving fan

Aluminium drain fitting


Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H C R 30 2 5R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (3 or 5 row)

Fan diameter - cm

No. of fans 1 to 4

Page 104

Note: subject to change without notice

HCR - 300
Page 2 of 3
15.07.2011

HCR RANGE OF UNIT COOLERS


WITH 300mm FANS

Technical Data
Model

HCR

Nominal Capacity R22

301-3R

1.20

301-5R

1.54

302-5R

303-3R

Fin Spacing 6F

(4,2mm)

302-3R

2.42

3.10

3.66

303-5R

304-3R

304-5R

4.67

4.88

6.25
35.81

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

5.37

8.95

10.74

17.90

16.11

26.85

21.48

Air flow - frost free

m3 / s
m/s

0.37

0.30

0.74

0.60

1.11

0.90

1.47

1.20

3.22

2.63

3.22

2.63

3.22

2.63

3.22

2.63

kg

12

14

21

24

30

36

39

45

0.94

1.30

3.96

3.83

5.29
24.37

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C

1.90

2.63

(6,35mm)
2.86

For other conditions refer to table under appendix A

Coil surface area

m2

6.09

7.31

12.19

10.97

18.28

14.62

Air flow - frost free

m3 / s
m/s

0.42

0.35

0.84

0.70

1.26

1.04

1.68

1.39

3.68

3.04

3.68

3.04

3.68

3.04

3.68

3.04

Mass

kg

12

14

20

24

29

34

37

42

Tube internal volume

litre

0.96

1.60

1.86

3.10

2.77

4.61

3.67

6.11

11

10

14

13

15

14

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

5/8"

5/8"

7/8"

7/8"

7/8"

7/8"

7/8"

1 1/8"

Elect. Defrost / 230V

kW

0.90

1.35

1.50

2.25

2.20

3.30

2.80

4.20

Face velocity

General Data
Air throw

Physical Data

NOTE:
Drain: 3/4" BSPM Fitting

Fan:
-300mm diameter
230 / 1 /50 Hz
90 W x 0.52 A each

NOTE:
Models:
HCR 301 3R/5R are suitable for
Internally equalized expansion valves
Models :
302 3R and above are suitable for externally
equalized expansion valves

Page 105

Note: subject to change without notice

HCR - 300
Page 3 of 3
15-07-2011

HCR RANGE OF UNIT COOLERS


WITH 300mm FANS

Defrost Wiring
Model
Phase Heater no. Watts
L1
L1
L1
L1
L1
L1
L1
L1

301-3R
301-5R
302-3R
302-5R
303-3R
303-5R
304-3R
304-5R

1+2
1+2+3
1+2
1+2+3
1+2
1+2+3
1+2
1+2+3

Volt Amp

900
1350
1500
2250
2200
3300
2800
4200

230
230
230
230
230
230
230
230

Klixon
3.9
5.9
6.5
9.8
9.6
14.3
12.2
18.3

37T31(5A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

L1

Defrost heater placement.

HCR 301 / 302 / 303 / 304

AIR

AIR

1
2

2
3

3R

5R

KLIXON
CLOSE -5C
OPEN +25C

HEATER

Motor

Diameter
mm
Square shaded pole
300

L1 N

Voltage
V
230

Frequency Speed
Hz
rpm
50
1300

Power
W
25/90

Amperage
A
0.52

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 106

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HDR - 300
Page 1 of 3
15-07-2011

HC HEAT - EXCHANGERS
HDR RANGE OF UNIT COOLERS
WITH 300mm FANS

General Description
The HDR-300 range of unit coolers comprises 16 models for both medium and low temperature applications
utilising 300 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is
compatible with Refrigerants R134a, R22, R404A and R507 etc.
The unit cooler has a unique angular design for flush mounting to the wall without hindering the airflow.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel tubes

RAL 9003 white epoxy coating

Stainless steel casing

230/1/ 50 Hz fan motor

230/1/ 50 Hz Energy saving fan

Aluminium drain fitting


Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H D R 30 2 5R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (3 or 5 row)

Fan diameter - cm

No. of fans 1 to 4

Page 107

Note: subject to change without notice

HDR - 300
Page 2 of 3
15.07.2011

HDR RANGE OF UNIT COOLERS


WITH 300mm FANS

Technical Data
Model

HDR

Nominal Capacity R22

301-3R

1.76

301-5R

2.22

302-5R

303-3R

Fin Spacing 6F

(4,2mm)

302-3R

3.54

4.46

5.35

303-5R

304-3R

304-5R

6.72

7.14

8.98
57.29

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

8.59

14.32

17.19

28.64

25.78

42.97

34.37

Air flow - frost free

m3 / s
m/s

0.48

0.40

0.95

0.81

1.43

1.21

1.90

1.62

2.60

2.21

2.60

2.21

2.60

2.21

2.60

2.21

kg

15

18

25

30

35

43

48

58

1.41

1.91

5.80

5.72

7.75
39.00

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

2.85

kW @ ITD = 6K and Te = - 5C

3.86

(6,35mm)
4.28

For other conditions refer to table under appendix A

Coil surface area

m2

5.85

9.75

11.70

19.50

17.55

29.25

23.4

Air flow - frost free

m3 / s
m/s

0.52

0.46

1.04

0.91

1.56

1.37

2.08

1.82

2.85

2.49

2.85

2.49

2.85

2.49

2.85

2.49

Mass

kg

15

17

25

30

35

42

45

54

Tube internal volume

litre

1.54

2.56

2.98

4.97

4.42

7.37

5.87

9.78

11

10

14

13

15

14

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

5/8"

Suction connection

inch

5/8"

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

Elect. Defrost / 230V

kW

1.80

2.25

3.00

3.75

4.40

5.50

5.60

7.00

Face velocity

General Data
Air throw

Physical Data

340

NOTE:
Drain: 3/4" BSPM Fitting

Fan:
-300mm diameter
230 / 1/50 Hz
90W x 0.52 A each

NOTE:
Models:
HDR 301 3R is suitable for
Internally equalized expansion valves
Models :
301 5R and above are suitable for externally
equalized expansion valves

Page 108

Note: subject to change without notice

HDR - 300
Page 3 of 3
15-07-2011

HDR RANGE OF UNIT COOLERS


WITH 300mm FANS

Defrost Wiring
Model
Phase Heater no. Watts
L1
L1
L1
L1
L1
L1
L1
L1
L2

301-3R
301-5R
302-3R
302-5R
303-3R
303-5R
304-3R
304-5R

1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+5
3+4

Volt Amp

1800
2250
3000
3750
4400
5500
5600
4200
2800

230
230
230
230
230
230
230
230
230

Klixon
7.8
9.8
13.0
16.3
19.1
23.9
24.3
18.3
12.2

14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

Defrost heater placement.

L1

3
2

AIR

AIR

HDR 301 / 302 / 303 / 304 - 3R

5R

3R
L1

L2

Motor

L1 N

HEATER

HDR 304 - 5R

Diameter
mm
Square shaded pole
300

Voltage
V
230

KLIXON
CLOSE -5C
OPEN +25C

Frequency Speed
Hz
rpm
50
1300

Power
W
25/90

1
Amperage
A
0.52

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 109

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HSR - 300
Page 1 of 4
01-10-2009

HC HEAT - EXCHANGERS
HSR RANGE OF UNIT COOLERS
WITH 300mm FANS
General Description

The HSR-300 range of unit coolers comprises 30 models for both medium and low temperature applications
utilising 300 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is compatible
with Refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fins

Aluminium fins

Coated aluminium fins

Epoxy powder coated Al casing

Stainless steel tubes

RAL 9003 white epoxy coating

Stainless steel casing

230/1/50 Hz fan motor

External rotor fan motor

Intermediate drip tray


Aluminium drain fitting
Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H S R 30 2 3R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (3,4 or 5 row)

Fan diameter - cm

No. of fans 1 to 5
Page 110

Note:subjecttochangewithoutnotice

HSR - 300
Page 2 of 4
01-10-2009

HSR RANGE OF UNIT COOLERS


WITH 300mm FANS
Technical Data
Model

HSR

301-3R

301-4R

301-5R

302-3R

302-4R

Fin Spacing 6F
Nominal Capacity R22

1.81

2.09

kW @ ITD = 6K and Te = -5C

2.29

3.65

4.22

302-5R

303-3R

303-4R

303-5R

5.49

6.34

6.91

(4,2mm)
4.60

For other conditions refer to table under appendix A

Coil surface area

m2

12

15

18

24

30

27

36

45

Air flow - frost free

m3 / s
m/s

0.48

0.44

0.41

0.96

0.88

0.82

1.44

1.32

1.23

2.51

2.31

2.15

2.51

2.31

2.15

2.51

2.31

2.15

kg

17

18

19

26

29

31

35

39

42

4.44

5.32

5.98

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

1.46

1.75

kW @ ITD = 6K and Te = -5C

1.97

2.95

3.54

(6,35mm)
3.98

For other conditions refer to table under appendix A

Coil surface area

m2

10

12

16

20

18

24

30

Air flow - frost free

m3 / s
m/s

0.51

0.48

0.45

1.02

0.96

0.90

1.53

1.44

1.35

2.66

2.50

2.34

2.66

2.50

2.34

2.66

2.50

2.34

Mass

kg

16

17

18

24

27

29

32

36

39

Tube internal volume

litre

1.86

2.49

4.49

5.61

4.87

6.50

8.12

Face velocity

General Data
Ai throw
th
Air

3.11

3.37

11

10

11

10

11

10

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction connection

inch

5/8"

7/8"

7/8"

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

Elect. defrost 230V

kW

1.20

1.20

1.50

2.20

2.20

2.75

3.20

3.20

4.00

DIMENSIONS (mm)

350

350

375

375

400

400

400

Physical Data
350

375

NOTE:
Drain: 3/4"BSPMFitting
Fan:
300mmdiameter
230/1/50Hz
110Wx0.75Aeach

NOTE:
Models:
301 3R and above are suitable for externally
equalized expansion valves
Page 111

Note:subjecttochangewithoutnotice

HSR - 300
Page 3 of 4
01-10-2009

HSR RANGE OF UNIT COOLERS


WITH 300mm FANS
Technical Data
Model

HSR

304-3R

304-4R

304-5R

305-3R

Fin Spacing 6F
Nominal Capacity R22

7.35

8.50

kW @ ITD = 6K and Te = -5C

9.25

305-4R

305-5R

10.62

11.58

(4,2mm)

9.22

For other conditions reffer to table under appendix A

Coil surface area

m2

36

48

60

45

60

75

Air flow - frost free

m3 / s
m/s

1.92

1.76

1.64

2.40

2.20

2.05

2.51

2.31

2.15

2.51

2.31

2.15

kg

44

49

53

53

59

64

8.90

9.99

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

5.93

7.11

kW @ ITD = 6K and Te = -5C

7.99

(6,35mm)

7.43

For other conditions reffer to table under appendix A

Coil surface area

m2

24

33

41

30

41

51

Air flow - frost free

m3 / s
m/s

2.04

1.92

1.80

2.55

2.40

2.25

2.66

2.50

2.34

2.66

2.50

2.34

Mass

kg

41

45

50

49

55

60

Tube internal volume

litre

6.38

10.63

7.88

10.51

13.14

Face velocity

General Data
Ai throw
th
Air

8.50

11

10

11

10

Liquid connection

inch

1/2"

5/8"

5/8"

5/8"

5/8"

5/8"

Suction connection

inch

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

Elect. defrost / 230V

kW

4.20

4.20

5.25

5.20

5.20

6.50

500

500

600

600

600

Physical Data
DIMENSIONS (mm)

500

NOTE:
Drain: 3/4" BSPM Fitting
Fan:
-300mm diameter
230/1/50 Hz
110 W x 0.75 A each
NOTE:
Models:
301 3R and above are suitable for externally
equalized expansion valves

Page 112

Note:subjecttochangewithoutnotice

HSR - 300
Page 4 of 4
01-10-2009

HSR RANGE OF UNIT COOLERS


WITH 300mm FANS
Defrost Wiring
Model
3013R
3014R
3015R
3023R
3024R
3025R
3033R
3034R
3035R
3043R
3044R
3045R
3053R
3054R
3055R
3055R

Phase
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L2

Heater no.
1+2+3+4
1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+3+4
1+2+3+4+5
1+2+3+4
1+2+3+4
1+2+3
4+5

Watts
1200
1200
1500
2200
2200
2750
3200
3200
4000
4200
4200
5250
5200
5200
3900
2600

Volt
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

L1

Amp
5.2
5.2
6.5
9.6
9.6
12.0
13.9
13.9
17.4
18.3
18.3
22.8
22.6
22.6
17.0
11.3

Klixon
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

Defrost heater placement.

AIR

AIR

AIR

HSR 301 / 302 / 303 / 304 / 305 - 3R / 305 - 4R

1
L2

L1

3R

4R
T

Diameter
mm

Voltage
V

ShadedPole
ExternalRotor

300
300

230
230

L1 N

HEATER

HSR 305- 5R

Motor

5R

KLIXON
CLOSE -5C
OPEN +25C

1
5

Frequency Speed
Hz
rpm

50
50

1300
1400

Power
W

Amperage
A

34/110
68

0.75
0.3

Standard
Optional

L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 113

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HSR - 350
Page 1 of 3
01-10-2009

HC HEAT - EXCHANGERS
HSR RANGE OF UNIT COOLERS
WITH 350mm FANS
General Description

The HSR-350 range of unit coolers comprises 16 models for both medium and low temperature applications
utilising 350 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is compatible
with refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Al casing

Stainless steel tubes

RAL 9003 white epoxy coating

Stainless steel casing

230/1/50 Hz fan motor

400/3/50 Hz fan motor

Intermediate drip tray


Aluminium drain fitting
Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H S R 35 2 4R x 6F E

HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (4 or 6 row)

Fan diameter - cm

No. of fans 1 to 4
Page 114

Note:subjecttochangewithoutnotice

HSR - 350
Page 2 of 3
01-10-2009

HSR RANGE OF UNIT COOLERS


WITH 350mm FANS
Technical Data
Model

HSR

351-4R

351-6R

352-4R

352-6R

Fin Spacing 6F
Nominal Capacity R22

3.24

3.82

kW @ ITD = 6K and Te = - 5C

6.54

7.70

353-4R

353-6R

354-4R

354-6R

11.58

13.14

15.44

(4,2mm)
9.83

For other conditions refer to table under appendix A

Coil surface area

m2

16

24

32

48

48

72

64

97

Air flow - frost free

m3 / s
m/s

0.71

0.65

1.42

1.30

2.13

1.95

2.84

2.60

2.67

2.44

2.67

2.44

2.67

2.44

2.67

2.44

kg

23

27

38

44

51

61

65

78

10.07

10.73

13.45

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

2.66

3.33

kW @ ITD = 6K and Te = - 5C

5.33

6.70

(6,35mm)
8.04

For other conditions refer to table under appendix A

Coil surface area

m2

11

17

22

33

33

50

44

67

Air flow - frost free

m3 / s
m/s

0.75

0.70

1.50

1.40

2.25

2.10

3.00

2.80

2.79

2.61

2.79

2.61

2.79

2.61

2.79

2.61

Mass

kg

23

26

37

43

49

58

63

75

Tube internal volume

litre

3.44

5.16

9.38

9.07

13.61

11.59

17.83

Face velocity

General Data
Ai throw
th
Air

6.26

14

14

15

15

16

16

17

17

Liquid connection

inch

1/2"

1/2"

1/2"

1/2"

5/8"

5/8"

5/8"

5/8"

Suction connection

inch

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

1 3/8"

1 3/8"

1 3/8"

Elect. Defrost / 230V

kW

2.0

2.5

4.0

5.0

6.0

7.5

8.0

10.0

DIMENSIONS (mm)

350

350

375

400

400

500

500

Physical Data

NOTE:
Drain: 3/4" BSPM Fitting

375

NOTE:

Fan:
-350mm diameter
230 /1/50 Hz
130 W x 0.58 A each

Models:
351 4R and above are suitable for externally
equalized expansion valves
Page 115

Note:subjecttochangewithoutnotice

HSR - 350
Page 3 of 3
01-10-2009

HSR RANGE OF UNIT COOLERS


WITH 350mm FANS
Defrost Wiring
Model Phase Heater no.
3514R
3516R
3524R
3526R
3534R

L1
L1
L1
L1
L1
L2
L1
L2
L1
L2
L1
L2

3536R
3544R
3546R

Watts

1+2+3+4+5+6+7+8
1+2+3+4+5+6+7+8+9+10
1+2+3+4+5+6+7+8
1+2+3+4+5+6+7+8+9+10
1+2+3+4
5+6+7+8
1+2+3+4+5
6+7+8+9+10
1+2+3+4
5+6+7+8
1+2+3+4+5
6+7+8+9+10

L1

2000
2500
4000
5000
3000
3000
3750
3750
4000
4000
5000
5000

Volt Amp
230
230
230
230
230
230
230
230
230
230
230
230

HSR 351 / 352

8.7
10.9
17.4
21.7
13.0
13.0
16.3
16.3
17.4
17.4
21.7
21.7

Klixon
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

Defrost heater placement.

10

3
N
L1

HSR 353 / 354

L2

AIR

AIR

6
1

10

4R

KLIXON
CLOSE -5C
OPEN +25C

7
10

6R

HEATER

Motor
1 Phase
3 Phase

L1 N

Diameter
mm
350
350

Voltage
V
230
400

Frequency Speed
Hz
rpm
50
1400
50
1420

Power
W
130
115

Amperage
1
A
0.58
0.33

Standard
Optional

E
L - BLUE
N - BROWN
E - GREEN / YELLOW
F1 - FAN MOTOR

F1
GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

Page 116

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note:subjecttochangewithoutnotice

HSR - 500
Page 1 of 4
15.07.2011

HC HEAT - EXCHANGERS
HSR RANGE OF UNIT COOLERS
WITH 500mm FANS

General Description
The HSR-500 range of unit coolers comprises 12 models for both medium and low temperature applications
utilising 500 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is
compatible with Refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated Galv casing

Guide vane

RAL 9003 white epoxy coating

Stainless steel tubes

400/3/50 Hz fan motor

Stainless steel casing

Intermediate drip tray


Brass drain fitting
Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H S R 50 2 4R x 6F E DELTA
Star or Delta
HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (4 or 6 row)

Fan diameter - cm

No. of fans 1 to 3

Page 117

Note: subject to change without notice

HSR - 500
Page 2 of 4
15.07.2011

HSR RANGE OF UNIT COOLERS


WITH 500mm FANS

Technical Data
Delta option
Model

HSR

501-4R

501-6R

8.27

10.08

502-4R

502-6R

Fin Spacing 6F
Nominal Capacity R22

16.65

503-4R

503-6R

23.81

29.02

(4,2mm)

20.29

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

36

54

72

108

101

152

Air flow - frost free

m3 / s
m/s

2.21

1.99

4.42

3.98

6.50

5.77

3.86

3.47

3.86

3.47

4.02

3.57

kg

79

86

132

146

181

200

6.49

8.44

18.58

24.11

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

13.00

(6,35mm)

16.88

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

24

37

49

73

69

103

Air flow - frost free

m3 / s
m/s

2.37

2.19

4.73

4.38

6.99

6.41

4.13

3.83

4.13

3.83

4.33

3.97

kg

78

84

130

143

178

196

502-4R

502-6R

503-4R

503-6R

21.73

25.59

Face velocity
Mass

Star option
Model

HSR

501-4R

501-6R

7.54

8.92

Fin Spacing 6F
Nominal Capacity R22

Air flow - frost free


Face velocity
Mass

(4,2mm)

17.93

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

15.20

m2

36

54

72

108

101

152

m /s
m/s

1.80

1.60

3.59

3.20

5.26

4.64

3.13

2.79

3.13

2.79

3.26

2.87

kg

79

86

132

146

181

200

6.06

7.64

17.38

21.92

Fin Spacing 4F
Nominal Capacity R22

12.17

(6,35mm)

15.39

kW @ ITD = 6K and Te =For


- 5
other
C conditions refer to table under appendix A

Coil surface area

m2

24

37

49

73

69

103

Air flow - frost free

m3 / s
m/s

1.94

1.78

3.87

3.55

5.69

5.19

3.38

3.1

3.38

3.1

3.52

3.21

Mass

kg

78

84

130

143

178

196

Tube internal volume

litre

6.28

9.42

12.31

18.47

17.25

25.88

20

20

24

24

27

27

Face velocity

General Data
Air throw
Liquid connection

inch

5/8"

5/8"

5/8"

7/8"

7/8"

7/8"

Suction connection

inch

1 1/8"

1 1/8"

1 3/8"

1 5/8"

1 5/8"

2 1/8"

E.L. defrost/230V

kW

4.05

5.4

8.1

10.8

12.15

16.2

Page 118

Note: subject to change without notice

HSR - 500
Page 3 of 4
15.07.2011

HSR RANGE OF UNIT COOLERS


WITH 500mm FANS

Model

HSR

DIMENSIONS (mm)

501-4R

501-6R

502-4R

502-6R

503-4R

503-6R

400

400

500

500

600

600

AIR

NOTE:
Drain: 1 1/4" BSPM Fitting
Fan:
-500mm diameter
400/3/ 50Hz
720 W x 1.41 A each
NOTE:
Models:
501 4R and above are suitable for externally
equalized expansion valves

Page 119

Note: subject to change without notice

HSR - 500
Page 4 of 4
15-07-2011

HSR RANGE OF UNIT COOLERS


WITH 500mm FANS

Defrost Wiring
Model

Phase

501-4R
501-6R

Heater no.

L1
L1
L2
L1
L2
L1
L2
L1
L2
L3
L1
L2
L3

502-4R
502-6R
503-4R
503-6R

1+2+3+4+5+6+7+8+9
1+2+3+4+5+6
7+8+9+10+11+12
1+2+3+4
5+6+7+8+9
1+2+3+4+5+6
7+8+9+10+11+12
1+2+3
4+5+6
7+8+9
1+2+3+4
5+6+7+8
9+10+11+12

L1

T
T

Volt Amp

4050
2700
2700
3600
4500
5400
5400
4050
4050
4050
5400
5400
5400

230
230
230
230
230
230
230
230
230
230
230
230
230

Klixon

17.6
11.7
11.7
15.7
19.6
23.5
23.5
17.6
17.6
17.6
23.5
23.5
23.5

KLIXON
CLOSE -5C
OPEN +25C

HSR 501 - 4R

Watts

14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)

Defrost heater placement.

HEATER

5
N

AIR
T

AIR

10

11

2
2

10

L2

L1

12

7
N

HSR 501 - 6R / 502

L2

L1

L3

Voltage
V

3 Phase DELTA
3 Phase STAR

500
500

400
400

L1 L2 L3

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

12

6R

HSR 503

Diameter
mm

F1

11

Motor

TOP TOP

4R

Frequency Speed
Hz
RPM

50
50

1390
1180

Power
W

Amperage
A

720
550

1.41
0.95

Standard
Optional

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 120

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HRR - 500
Page 1 of 5
15-07-2011

HC HEAT - EXCHANGERS
HRR RANGE OF UNIT COOLERS
WITH 500mm FANS

General Description
The HRR-500 range of unit coolers comprises 12 models for both medium and low temperature applications
utilising 500 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is
compatible with Refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated galv casing

Guide vane

RAL 9003 white epoxy coating

Stainless steel tubes

400/3/50 Hz fan motor

Stainless steel casing

Intermediate drip tray


Stainless steel drip tray

Brass drain fitting


Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H R R 50 2 4R x 6F E DELTA
Star or Delta
HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (4 or 6 row)

Fan diameter - cm

No. of fans 1 to 3

Page 121

Note: subject to change without notice

HRR - 500
Page 2 of 5
15-07-2011

HRR RANGE OF UNIT COOLERS


WITH 500mm FANS

Technical Data
Delta option
Model

HRR

501-4R

501-6R

9.82

12.00

502-4R

502-6R

Fin Spacing 6F
Nominal Capacity R22

19.75

503-4R

503-6R

28.36

34.64

(4,2mm)

24.11

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

45

67

90

135

126

190

Air flow - frost free

m3 / s
m/s

2.37

2.19

4.73

4.38

6.99

6.41

3.30

3.06

3.30

3.06

3.46

3.17

kg

88

97

149

166

202

225

7.78

10.08

22.36

28.99

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22

15.63

(6,35mm)

20.26

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

31

46

61

92

86

129

Air flow - frost free

m3 / s
m/s

2.48

2.35

4.95

4.70

7.35

6.93

3.46

3.28

3.46

3.28

3.64

3.43

kg

87

95

147

163

198

221

502-4R

502-6R

503-4R

503-6R

25.78

30.53

Face velocity
Mass

Star option
Model

HRR

501-4R

501-6R

8.92

10.60

Fin Spacing 6F
Nominal Capacity R22

Air flow - frost free


Face velocity
Mass

(4,2mm)

21.25

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

17.95

m2

45

67

90

135

126

190

m /s
m/s

1.94

1.77

3.87

3.54

5.69

5.19

2.7

2.47

2.7

2.47

2.82

2.57

kg

88

97

149

166

202

225

7.24

9.15

20.88

26.34

Fin Spacing 4F
Nominal Capacity R22

14.58

(6,35mm)

18.36

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

31

46

61

92

86

129

Air flow - frost free

m3 / s
m/s

2.04

1.92

4.07

3.83

6.04

5.63

2.84

2.67

2.84

2.67

2.99

2.79

Mass

kg

87

95

147

163

198

221

Tube internal volume

litre

7.85

11.77

15.39

23.08

21.57

32.35

19

19

23

23

25

25

Face velocity

General Data
Air throw
Liquid connection

inch

5/8"

5/8"

7/8"

7/8"

7/8"

7/8"

Suction connection

inch

1 1/8"

1 3/8"

1 5/8"

1 5/8"

1 5/8"

2 1/8"

E.L. defrost/230V

kW

4.95

6.30

9.90

12.60

14.85

18.9

Page 122

Note: subject to change without notice

HRR - 500
Page 3 of 5
15-07-2011

HRR RANGE OF UNIT COOLERS


WITH 500mm FANS

Model

HRR

DIMENSIONS (mm)

501-4R

501-6R

502-4R

502-6R

503-4R

503-6R

400

400

500

500

600

600

AIR

NOTE:
Drain: 1 1/4" BSPM Fitting
Fan:
-500mm diameter
400/3/ 50Hz
720 W x 1.41 A each

NOTE:
Models:
501 4R and above are suitable for externally
equalized expansion valves

Page 123

Note: subject to change without notice

HRR - 500
Page 4 of 5
15-07-2011

HRR RANGE OF UNIT COOLERS


WITH 500mm FANS

Defrost Wiring
Model Phase Heater no.
501-4R
501-6R

L1
L1
L2
L1
L2
L1
L2
L3
L1
L2
L3
L1
L2
L3

502-4R
502-6R
503-4R
503-6R

Watts Volt Amp Klixon

1+2+3+4+5+6+7+8+9+10+11
1+2+3+4+5+6+7
8+9+10+11+12+13+14
1+2+3+4+5+6
7+8+9+10+11
1+2+3+4+5
6+7+8+9+12
10+11+13+14
1+2+3+4
5+6+7+8
9+10+11
1+2+3+4+5
6+7+8+9
10+11+12+13+14

4950
3150
3150
5400
4500
4500
4500
3600
5400
5400
4050
6750
5400
6750

230
230
230
230
230
230
230
230
230
230
230
230
230
230

21.5
13.7
13.7
23.5
19.6
19.6
19.6
15.7
23.5
23.5
17.6
29.3
23.5
29.3

14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
1(
T3
14

A)
25

Defrost heater placement.

L1

10

11

6
HRR 501 - 4 R

4
L1

L2

AIR
3

8
2

10

11

12

13

14

2
N

HRR 501- 6R / 502 - 4R

9
L1

L2

1
10 11

L3

4R
1

10

11

HRR 502- 6R / 503 - 4R

5
L1

L2

L3

7
1

10

11

12

13

14

HRR 503- 6R

AIR

12

3
8

11

KLIXON
CLOSE -5C
OPEN +25C

1
13

10
14

6R

HEATER

Page 124

Note: subject to change without notice

HRR - 500
Page 5 of 5
15-07-2011

HRR RANGE OF UNIT COOLERS


WITH 500mm FANS

Fan Wiring
Motor

Diameter
mm

Voltage
V

Frequency
Hz

Speed
RPM

3 Phase DELTA
3 Phase STAR

500
500

400
400

50
50

1390
1180

L1 L2 L3

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

TOP TOP

Power Amperage
W
A

720
550

1.41
0.95

Standard
Optional

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 125

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HPR - 500
Page 1 of 5
15-07-2011

HC HEAT - EXCHANGERS
HPR RANGE OF UNIT COOLERS
WITH 500mm FANS

General Description
The HPR-500 range of unit coolers comprises 12 models for both medium and low temperature applications
utilising 500 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is
compatible with Refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated galv casing

Guide vane

RAL 9003 white epoxy coating

Stainless steel tubes

400/3/50 Hz fan motor

Stainless steel casing

Intermediate drip tray


Stainless steel drip tray

Brass drain fitting


Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H P R 50 2 4R x 6F E DELTA
Star or Delta
HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (4 or 6 row)

Fan diameter - cm

No. of fans 1 to 3

Page 126

Note: subject to change without notice

HPR - 500
Page 2 of 5
15-07-2011

HPR RANGE OF UNIT COOLERS


WITH 500mm FANS

Technical Data
Delta option
Model

HPR

501-4R

501-6R

11.16

13.61

502-4R

502-6R

Fin Spacing 6F
Nominal Capacity R22

22.45

503-4R

503-6R

32.30

39.43

(4,2mm)

27.35

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

54

81

108

162

152

228

Air flow - frost free

m3 / s
m/s

2.46

2.32

4.91

4.65

7.29

6.84

2.86

2.7

2.86

2.7

3.01

2.82

kg

100

111

166

186

224

252

Face velocity
Mass

Nominal Capacity R22


kW @ ITD = 6K and Te = - 5C

8.94

Fin Spacing 4F (6,35mm)


11.54
17.98
23.20
25.79
For other conditions refer to table under appendix A

33.35

Coil surface area

m2

37

55

73

110

103

155

Air flow - frost free

m3 / s
m/s

2.54

2.45

5.09

4.89

7.57

7.25

2.96

2.85

2.96

2.85

3.12

2.91

kg

99

109

163

182

220

247

502-4R

502-6R

503-4R

503-6R

Face velocity
Mass

Star option
Model

HPR

501-4R

Nominal Capacity R22


kW @ ITD = 6K and Te = - 5C
Coil surface area
Air flow - frost free
Face velocity
Mass

10.11
m2
3

501-6R

Fin Spacing 6F (4,2mm)


11.99
20.28
24.08
29.29
For other conditions refer to table under appendix A

34.74

54

81

108

162

152

228

2.02

1.89

4.04

3.78

5.98

5.56

m /s
m/s

2.35

2.2

2.35

2.2

2.47

2.3

kg

100

111

166

186

224

252

Nominal Capacity R22


kW @ ITD = 6K and Te = - 5C

8.30

Fin Spacing 4F (6,35mm)


10.45
16.69
21.01
23.97
For other conditions refer to table under appendix A

30.20

Coil surface area

m2

37

55

73

110

103

155

Air flow - frost free

m3 / s
m/s

2.11

2.01

4.22

4.02

6.25

5.94

2.45

2.34

2.45

2.34

2.58

2.45

Mass

kg

99

109

163

182

220

247

Tube internal volume

litre

9.42

14.13

18.47

27.70

25.88

38.82

18

18

22

22

24

24

Face velocity

General Data
Air throw
Liquid connection

inch

5/8"

5/8"

7/8"

7/8"

7/8"

1 1/8"

Suction connection

inch

1 3/8"

1 3/8"

1 5/8"

1 5/8"

2 1/8"

2 1/8"

E.L. defrost/230V

kW

5.85

7.2

11.7

14.4

17.55

21.6

Page 127

Note: subject to change without notice

HPR - 500
Page 3 of 5
15.07.2011

HPR RANGE OF UNIT COOLERS


WITH 500mm FANS

Model

HPR
A

DIMENSIONS (mm)

501-4R

501-6R

502-4R

502-6R

503-4R

503-6R

400

400

500

500

600

600

AIR

NOTE:
Drain: 1 1/2" BSPM Fitting
Fan:
-500mm diameter
400/3/ 50Hz
720 W x 1.41 A each
NOTE:
Models:
501 4R and above are suitable for externally
equalized expansion valves

Page 128

Note: subject to change without notice

HPR - 500
Page 4 of 5
15-07-2011

HPR RANGE OF UNIT COOLERS


WITH 500mm FANS

Defrost Wiring
Model Phase Heater no.
501-4R

L1
L2
L1
L2
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3

501-6R
502-4R
502-6R
503-4R
503-6R

Watts Volt

1+2+3+4+5+6+7
8+9+10+11+12+13
1+2+3+4+5+6+7+8
9+10+11+12+13+14+15+16
1+2+3+4
5+6+7+8+9
10+11+12+13
1+2+3+4+5+6
7+8+9+10+11
12+13+14+15+16
1+2+3+4
5+6+7+8+9
10+11+12+13
1+2+3+4+5+6
7+8+9+10+11
12+13+14+15+16

L1

3150
2700
3600
3600
3600
4500
3600
5400
4500
4500
5400
6750
5400
8100
6750
6750

13.7
11.7
15.7
15.7
15.7
19.6
15.7
23.5
19.6
19.6
23.5
29.3
23.5
35.2
29.3
29.3

Klixon
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
A)
(25
1
T3
14
)
5A
1(2
3
T
14

Defrost heater placement

L2

230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

Amp

6
7

11

10

12

14

13

15

16

HPR 501

8
4

L1

L2

L3

AIR
T

3
10

10

11

12

13

2
N

HPR 502

11
1

L1

L2

12

L3

13

4R
T

10

11

12

13

7
L

HPR 503

5
8
4
T

KLIXON
CLOSE -5C
OPEN +25C

AIR

14

3
10

HEATER

13

2
11

12
1
15 16

6R

Page 129

Note: subject to change without notice

HPR - 500
Page 5 of 5
15-07-2011

HPR RANGE OF UNIT COOLERS


WITH 500mm FANS

Fan Wiring
Motor

Diameter
mm

Voltage
V

Frequency
Hz

Speed
RPM

3 Phase DELTA
3 Phase STAR

500
500

400
400

50
50

1390
1180

L1 L2 L3

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

TOP TOP

Power Amperage
W
A

720
550

1.41
0.95

Standard
Optional

E
L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 130

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HMR - 630
Page 1 of 5
15.07.2011

HC HEAT - EXCHANGERS
HMR RANGE OF UNIT COOLERS
WITH 630mm FANS

General Description
The HMR-630 range of unit coolers comprises 12 models for both medium and low temperature
applications utilising 630 mm diameter fans.
The range is available in either 6 or 4 fins per inch spacings, with or without electric defrost and is
compatible with Refrigerants R134a, R22, R404A and R507 etc.
The unit is epoxy powder coated in an attractive white finish.

Standard Features

Optional Features

Plain bore copper tubes

Copper fin

Aluminium fin

Coated aluminium fin

Epoxy powder coated galv casing

Guide vane

RAL 9003 white epoxy coating

Stainless steel tubes

400/3/50 Hz fan motor

Stainless steel casing

Intermediate drip tray


Stainless steel drip tray
Brass drain fitting
Thermo-protector (low temp.)
Electric defrost heaters (low temp.)

Nomenclature
H M R 63 2 4R x 6F E DELTA
Star or Delta
HC Heat-Exchangers

Electric Defrost (if required)

Model

Fins per inch (4 or 6)

Refrigerant

No. of coil rows (4 or 6 row)

Fan diameter - cm

No. of fans 1 to 3

Page 131

Note: subject to change without notice

HMR - 630
Page 2 of 5
15.07.2011

HMR RANGE OF UNIT COOLERS


WITH 630mm FANS

Technical Data
Delta option
Model

HMR

631-4R

631-6R

22.25

28.04

632-4R

632-6R

Fin Spacing 6F
Nominal Capacity R22

41.21

633-4R

633-6R

67.56

84.95

(4,2mm)

51.99

For other conditions refer to table under appendix A

kW @ ITD = 6K and Te = - 5C

Coil surface area

m2

100

150

177

266

303

454

Air flow - frost free

m3 / s
m/s

5.22

5.02

10.26

9.79

15.67

15.07

3.26

3.14

3.63

3.46

3.24

3.12

kg

174

193

280

313

427

484

17.52

23.18

53.21

70.23

Face velocity
Mass

Fin Spacing 4F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C

32.05

(6,35mm)

42.60

For other conditions refer to table under appendix A

Coil surface area

m2

68

102

121

181

206

309

Air flow - frost free

m3 / s
m/s

5.34

5.20

10.55

10.21

16.62

15.61

3.34

3.25

3.73

3.61

3.32

3.23

kg

171

189

275

306

420

472

632-4R

632-6R

633-4R

633-6R

61.02

73.97

Face velocity
Mass

Star option
Model

HMR

631-4R

631-6R

20.10

24.43

Fin Spacing 6F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C
Coil surface area
Air flow - frost free
Face velocity
Mass

37.18

(4,2mm)

45.24

For other conditions refer to table under appendix A


m2
3

100

150

177

266

303

454

4.22

4.00

8.25

7.72

12.76

12.03

m /s
m/s

2.64

2.5

2.92

2.73

2.62

2.49

kg

174

193

280

313

427

484

16.25

20.88

49.36

63.25

Fin Spacing 4F
Nominal Capacity R22
kW @ ITD = 6K and Te = - 5C

29.80

(6,35mm)

38.39

For other conditions refer to table under appendix A

Coil surface area

m2

68

102

121

181

206

309

Air flow - frost free

m3 / s
m/s

4.35

4.20

8.57

8.20

13.09

12.61

2.72

2.63

3.03

2.9

2.71

2.61

Mass

kg

171

189

275

306

420

472

Tube internal volume

litre

17.28

25.91

30.19

45.29

51.31

76.96

24

24

24

24

24

24

Face velocity

General Data
Air throw
Liquid connection

inch

7/8"

7/8"

7/8"

1 1/8"

1 1/8"

1 1/8"

Suction connection

inch

1 5/8"

2 1/8"

2 1/8"

2 5/8"

2 5/8"

2 5/8"

E.L. defrost/230V

kW

11.20

16.00

18.90

27.00

32.20

46.00

Page 132

Note: subject to change without notice

HMR - 630
Page 3 of 5
15.07.2011

HMR RANGE OF UNIT COOLERS


WITH 630mm FANS

Model

HMR

DIMENSIONS (mm)

631-4R

631-6R

632-4R

632-6R

633-4R

633-6R

400

400

500

500

600

600

AIR

NOTE:
Drain: 1 1/4" BSPM Fitting
Fan:
- 630mm diameter
- 400 /3/ 50 Hz
- 2630 W x 4.78 A each
NOTE:
Models:
501 4R and above are suitable for externally
equalized expansion valves

Page 133

Note: subject to change without notice

HMR - 630
Page 4 of 5
15.07.2011

HMR RANGE OF UNIT COOLERS


WITH 630mm FANS

Defrost Wiring
Model Phase Heater no.
631-4R

L1
L2
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3

631-6R
632-4R
632-6R
633-4R
633-6R

Watts

Volt

5600
5600
5600
5600
4800
6750
6750
5400
9450
9450
8100
11500
11500
9200
16100
16100
13800

230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

1+2+3+4+5+6+7
8+9+10+11+12+13+14
1+2+3+4+5+6+7
8+9+10+11+12+17+18
13+14+15+16+19+20
1+2+3+4+5
6+7+8+9+10
11+12+13+14
1+2+3+4+5+6+7
8+9+10+11+12+17+18
13+14+15+16+19+20
1+2+3+4+5
6+7+8+9+10
11+12+13+14
1+2+3+4+5+6+7
8+9+10+11+12+17+18
13+14+15+16+19+20

L1

L2

L3

10

11

12

17

18

13

L1

14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
14T31(25A)
A)
(25
1
T3
14
)
5A
1(2
3
T
14
A)
(25
1
T3
14
)
5A
1(2
3
T
14

HMR 631-6R

14

15

16

19

20

L2

24.3
24.3
24.3
24.3
20.9
29.3
29.3
23.5
41.1
41.1
35.2
50.0
50.0
40.0
70.0
70.0
60.0

Amp Klixon

HMR 631 - 4R

10

11

12

13

Defrost heater placement

14

18
L1

HMR 632 / 633

L2

L3

6
T

6
8

8
17

10

11

12

13

14

5
L

5
9

AIR

AIR

16

4
10

KLIXON
CLOSE -5C
OPEN +25C

10
15
3

3
11

11
14

HEATER

2
12

12

13
1

1
13

14

4R

Page 134

20

19

6R

Note: subject to change without notice

HMR - 630
Page 5 of 5
15.07.2011

HMR RANGE OF UNIT COOLERS


WITH 630mm FANS

Fan Wiring
Motor

Diameter
mm

Voltage
V

Frequency
Hz

Speed
rpm

3 Phase DELTA
3 Phase STAR

630
630

400
400

50
50

1320
1050

L1 L2 L3

F1

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (+27 11) 674-1237
Fax: (+27 11) 674-1268

TOP TOP

Power Amperage
W
A

2630
1750

4.78
2.95

Standard
Optional

E
L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

NATAL
P.O Box 30620
Mayville, 4058
Tel: (+27 31) 202-7829
Fax: (+27 31) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (+27 21) 551-7873
Fax: (+27 21) 551-1751

Page 135

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

Note: subject to change without notice

HC

HC HEAT-EXCHANGERS

HDC - 500
Page 1 of 3
31.01.2009

AIR COOLED DRY-COOLER


General Description
The HDC-501 to -508 range of Air Cooled Dry-Coolers comprises 8 models suitable for cooling liquids
compatible with copper (std) or 304 stainless steel (opt) tubes. Limits are 16 bar pressure and 100C
temperature for copper tube applications. Each unit is factory wired to a terminal strip in a terminal box.
As the coil tubes are in a horizontal position, it cannot be guaranteed that tubes get completely emptied when
draining. Where a danger of freezing may occur it is recommended that the coil is blown out with compressed
air and / or an antifreeze is used. eg glycol in water.
Coil selections are computer generated due to the many variables encountered.

Standard Features

Optional Features

Aluminium fin coil

Copper fin coil

Galvanised steel casing

Coated Al fin coil

Epoxy powder coated finish

Stainless steel casing

RAL 5005 Signal


Si
l Bl
Blue colour
l

304 Stainless steel tubes

Baffled individual fan sections

Fan cycling head pressure control

Vertical air discharge

Horizontal air discharge

Low profile

2 to 4 Row coil

Legs

Multiple system operation

4 Row coil
Single system operation

Note: Subject to change without notice

400/3/50Hz fan motor

Nomenclature

H DC 50 1 4R 1S

HC Heat-Exchangers

No. of systems

Dry-cooler

No. of coil rows

Fan diameter - cm

No. of fans
Page 136

HDC - 500

HC

AIR COOLED DRY-COOLER


Typical example

Typical print-out

Cooling capacity

24 kW

Liquid to be cooled

Note:
- Centre leg on models 505 & larger
- Dimensions in mm
- Dimensions 2mm

Liquid flow rate

30%
1,45 kg/s

Liquid on coil temp.

Fan:
- 500mm diameter
400/3/50Hz
0.83 kW x 1.65 A each.

Page 2 of 3
31.01.2009

45 C

Liquid off coil temp.

40 C

Ambient air temp.

30 C

Altitude

0m

For fluid other than water, ethylene


glycol or propylene glycol the
following would also be required :-

Coil:
- 12mm Copper tube
- Aluminium fin
- 12 FPI

Density

kg/m3

Heat capacity

kJ/kgK

Conductivity

kW.mKx1e6

Viscosity

mg/ms

Technical & Physical Data


Model

502

503

504

505

506

507

508

mm

1205

1240

1830

2420

3010

3600

4190

4780

mm

670

1205

1205

1205

1205

1205

1205

1205

2.24

4.42

6.64

8.85

11.06

13.27

15.49

17.70

No. of fans

501

Air quantity

m3/s

Coil face area

m2

0.70

1.35

2.02

2.70

3.37

4.05

4.72

5.39

Int.coil vol.

litres

8.86

17.09

24.96

32.84

40.72

48.59

56.47

64.35

Net mass - Al fin

kg

102

166

226

279

354

408

459

521

Net mass - Cu fin kg

119

199

275

347

437

510

578

656

Note: subject to change without notice

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (011) 674-1237
Fax: (011) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (031) 202-7829
Fax: (031) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021) 551-7873
Fax: (021) 551-1751

Page 137

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

HDC - 500

HC

AIR COOLED DRY-COOLER

Page 3 of 3
31.01.2009

Fan Wiring
Diameter
mm
500

Voltage
V
400

Frequency
Hz
50

RPM
1330

Power
W
830

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

Page 138

Amperage
A
1.65

HC

HC HEAT-EXCHANGERS

HDC - 630
Page 1 of 3
31.01.2009

AIR COOLED DRY-COOLER


General Description
The HDC-631 to -638 range of Air Cooled Dry-Coolers comprises 8 models suitable for cooling liquids
compatible with copper (std) or 304 stainless steel (opt) tubes. Limits are 16 bar pressure and 100C
temperature for copper tube applications. Each unit is factory wired to a terminal strip in a terminal box.
As the coil tubes are in a horizontal position, it cannot be guaranteed that tubes get completely emptied when
draining. Where a danger of freezing may occur it is recommended that the coil is blown out with compressed
air and / or an antifreeze is used. eg glycol in water.
Coil selections are computer generated due to the many variables encountered.

Standard Features

Optional Features

Aluminium fin coil

Copper fin coil

Galvanised steel casing

Coated Al fin coil

Epoxy powder coated finish

Stainless steel casing

RAL 5005 Signal


Si
l Bl
Blue colour
l

304 Stainless steel tubes

Baffled individual fan sections

Fan cycling head pressure control

Vertical air discharge

Horizontal air discharge

Low profile

2 to 4 Row coil

Legs

Multiple system operation

4 Row coil
Single system operation

Note: Subject to change without notice

400/3/50Hz fan motor

Nomenclature

H DC 63 3 4R 1S

HC Heat-Exchangers

No. of systems

Dry-cooler

No. of coil rows

Fan diameter - cm

No. of fans
Page 139

HDC - 630

HC

Page 2 of 3
31.01.2009

AIR COOLED DRY-COOLER


Typical example

Typical print-out

Cooling capacity
Note:
- Centre leg on models 635 & larger
- Dimensions in mm
- Dimensions 2mm

290 kW

Liquid to be cooled

WATER

Liquid flow rate

1,45 kg/s

Liquid on coil temp.

Fan:
- 630mm diameter
400/3/50Hz
2.53 kW x 5.2 A each.

50 C

Liquid off coil temp.

40 C

Ambient air temp.

30 C

Altitude

0m

For fluid other than water, ethylene


glycol or propylene glycol the
following would also be required :-

Coil:
- 12mm Copper tube
- Aluminium fin
- 12 FPI

Density

kg/m3

Heat capacity

kJ/kgK

Conductivity

kW.mKx1e6

Viscosity

mg/ms

Technical & Physical Data


Model

632

633

634

635

636

637

638

mm

1585

2060

3060

4060

5060

6060

7060

8060

mm

1050

1585

1585

1585

1585

1585

1585

1585

5.05

10.11

15.20

20.23

25.30

30.34

35.39

40.45

No. of fans

631

Air quantity

m3/s

Coil face area

m2

1.50

3.05

4.57

6.10

7.62

9.14

10.66

12.19

Int.coil vol.

litres

18.78

37.38

55.18

72.98

90.78

108.6

126.4

144.2

Net mass - Al fin

kg

185

326

457

583

726

852

982

1108

Net mass - Cu fin kg

262

480

687

891

1110

1314

1521

1724

Note: subject to change without notice

GAUTENG
P.O Box 147
Maraisburg, 1700
Tel: (011) 674-1237
Fax: (011) 674-1268

NATAL
P.O Box 30620
Mayville, 4058
Tel: (031) 202-7829
Fax: (031) 202-7849

CAPE
P.O Box 36640
Chempet, 7442
Tel: (021) 551-7873
Fax: (021) 551-1751

Page 140

NAMIBIA
P.O Box 1301
Windhoek
Tel: (0926461) 261-647
Fax: (0926461) 216-201

HDC - 630

HC

AIR COOLED DRY-COOLER

Page 3 of 3
31.01.2009

Fan Wiring
Diameter
mm
630

Voltage
V
400

Frequency
Hz
50

RPM
1340

Power
W
2530

L1 - BLACK
L2 - BLUE
L3 - BROWN
TOP - PURPLE
TOP - PINK
E - GREEN / YELLOW
F1 - FAN MOTOR

Page 141

Amperage
A
5.2

APPENDIX A
Page 1 of 4
01-10-2009

HC HEAT - EXCHANGERS
APPENDIX A
CORRECTION FACTORS
AIR RELATIVE HUMIDITY

The temperature difference is related to the enclosure humidity. Consult the figure below to determine
what TD to employ as a function of the required RH.

100
95

Room RH (%)

90
85
80
75
70
65
60
3

TDI (K)

CORRECTION FACTORS
Performance figures at various conditions may be found by multiplying the published figures by the
factors below. TDI refers to the difference between the air inlet and evaporating/dew temperature.
R22 (Low & Medium Temperature)

TDI(K)
5
6
7
8
9
10

35
0.66
0.83
1.01
1.19
1.36
1.55

FormodelsHDD,HCTandHWMreferto
manufactureronhightempapplications

30
0.67
0.84
1.02
1.20
1.38
1.56

Evaporatingtemperature(Celsius)
25
20
15
0.69
0.74
0.76
0.86
0.92
0.94
1.03
1.10
1.12
1.21
1.28
1.31
1.39
1.48
1.50
1.58
1.67
1.68

Page 142

10
0.79
0.97
1.15
1.33
1.51
1.71

5
0.84
1.00
1.15

Note:subjecttochangewithoutnotice

APPENDIX A
Page 2 of 4
01-10-2009

APPENDIX A
CORRECTION FACTORS

R 22 (High Temp)
Evaporating temperature (Celsius)

TDI(K)
5
5
6
7
8
9
10

1.21
1.41
1.60

50%70%RH
0
5
0.66
0.66
0.84
0.85
1.03
1.03
1.22
1.23
1.41
1.42
1.60
1.61

80%RH
10
0.66
0.85
1.04
1.23
1.42
1.61

5
-

1.36
1.60
1.87

5
0.66
0.84
1.10
1.36
1.64
1.91

10
0.66
0.85
1.10
1.39
1.70
2.00

0.67
0.85
1.11
1.43
1.75
2.09

R134 (Low & Medium Temperature)

TDI(K)
5
6
7
8
9
10

35
0.60
0.76
0.93
1.09
1.26
1.43

30
0.63
0.79
0.96
1.12
1.29
1.46

Evaporatingtemperature(Celsius)
25
20
15
0.65
0.70
0.73
0.82
0.88
0.90
0.98
1.05
1.07
1.15
1.22
1.24
1.32
1.41
1.42
1.50
1.59
1.60

10
0.75
0.92
1.09
1.26
1.44
1.63

5
0.80
0.95
1.10

R134a (High Temp)


Evaporating temperature (Celsius)

TDI(K)
5
5
6
7
8
9
10

1.19
1.37
1.57

50%70%RH
0
5
0.64
0.65
0.82
0.83
1.01
1.01
1.20
1.20
1.38
1.39
1.57
1.58

80%RH
10
0.65
0.83
1.02
1.21
1.40
1.59

5
-

1.30
1.56
1.81

0
0.64
0.82
1.06
1.32
1.59
1.86

5
0.65
0.83
1.06
1.35
1.64
1.95

10
1.01
1.19
1.37
1.55
1.74
1.93

5
1.07
1.23
1.39

10
0.65
0.83
1.08
1.39
1.72
2.04

R404A (Low & Medium Temperature)

TDI(K)
5
6
7
8
9
10

35
0.82
0.99
1.17
1.34
1.52
1.69

30
0.83
1.00
1.18
1.36
1.54
1.71

Dewtemperature(Celsius)
25
20
15
0.86
0.92
0.96
1.03
1.11
1.15
1.20
1.29
1.33
1.38
1.48
1.51
1.55
1.67
1.70
1.74
1.86
1.89
R404A (High Temp)
Dew temperature (Celsius)

TDI(K)
5
5
6
7
8
9
10

1.44
1.64
1.84

50%70%RH
0
5
0.86
0.86
1.05
1.05
1.25
1.25
1.45
1.45
1.65
1.65
1.85
1.85

FormodelsHDD,HCTandHWMreferto
manufactureronhightempapplications

80%RH
10
0.86
1.05
1.25
1.45
1.64
1.84
Page 143

5
-

1.60
1.86
2.14

0
0.86
1.09
1.35
1.63
1.91
2.21

5
0.87
1.12
1.39
1.69
1.99
2.33

10
0.86
1.13
1.43
1.75
2.09
2.44

Note:subjecttochangewithoutnotice

APPENDIX A
Page 3 of 4
01-10-2009

APPENDIX A
CORRECTION FACTORS

R410A (Low & Medium Temperature)

TDI(K)
5
6
7
8
9
10

35
0.84
1.02
1.21
1.39
1.57
1.76

30
0.86
1.04
1.22
1.41
1.59
1.78

Dewtemperature(Celsius)
25
20
15
0.88
0.94
1.00
1.06
1.16
1.19
1.24
1.34
1.38
1.42
1.53
1.57
1.61
1.74
1.77
1.81
1.93
1.97

10
1.04
1.23
1.43
1.61
1.81
2.01

5
1.11
1.29
1.45

R410A (High Temp)


Dew temperature (Celsius)

TDI(K)
5
5
6
7
8
9
10

1.49
1.69
1.89

50%70%RH
0
5
0.88
0.88
1.08
1.08
1.28
1.28
1.48
1.48
1.69
1.69
1.89
1.89

80%RH
10
0.88
1.08
1.29
1.49
1.69
1.89

5
-

5
0.88
1.13
1.42
1.70
2.00
2.31

1.67
1.95
2.23

10
0.89
1.17
1.45
1.77
2.09
2.44

0.89
1.17
1.51
1.84
2.21
2.58

R407C (Low & Medium Temperature)

TDI(K)
5
6
7
8
9
10

35
1.22
1.40
1.58
1.76
1.94
2.12

30
1.24
1.43
1.61
1.79
1.97
2.15

Dewtemperature(Celsius)
25
20
15
1.28
1.34
1.44
1.46
1.54
1.64
1.64
1.73
1.83
1.82
1.93
2.02
2.00
2.12
2.21
2.19
2.31
2.40

10
1.51
1.70
1.89
2.07
2.27
2.47

5
1.59
1.76
1.93

R407C (High Temp)


Dew temperature (Celsius)

R407C
5
5
6
7
8
9
10

1.95
2.14
2.35

50%70%RH
0
5
1.31
1.32
1.53
1.53
1.73
1.74
1.94
1.93
2.15
2.15
2.35
2.35

FormodelsHDD,HCTandHWMreferto
manufactureronhightempapplications

80%RH
10
1.32
1.52
1.73
1.93
2.14
2.35

Page 144

5
-

2.18
2.46
2.74

5
1.44
1.70
1.98
2.26
2.55
2.86

10
1.46
1.74
2.03
2.35
2.67
3.00

1.48
1.79
2.11
2.46
2.80
3.17

Note:subjecttochangewithoutnotice

APPENDIX A
Page 4 of 4
01-10-2009

APPENDIX A
CORRECTION FACTORS

R507A (Low & Medium Temperature)

TDI(K)
5
6
7
8
9
10

35
0.65
0.82
1.00
1.17
1.35
1.52

30
0.67
0.84
1.01
1.19
1.37
1.54

Evaporatingtemperature(Celsius)
25
20
15
0.69
0.74
0.77
0.86
0.93
0.95
1.03
1.10
1.13
1.20
1.29
1.31
1.38
1.48
1.50
1.57
1.66
1.69

10
0.81
0.98
1.17
1.34
1.53
1.72

5
0.86
1.02
1.18

R507A (High Temp)


Evaporating temperature (Celsius)

TDI(K)
5
5
6
7
8
9
10

1.28
1.47
1.68

50%70%RH
0
5
0.70
0.70
0.89
0.89
1.08
1.09
1.28
1.28
1.48
1.48
1.68
1.68

FormodelsHDD,HCTandHWMreferto
manufactureronhightempapplications

80%RH
10
0.70
0.89
1.09
1.28
1.48
1.68

Page 145

5
-

1.40
1.66
1.93

5
0.70
0.89
1.15
1.42
1.70
1.99

10
0.70
0.89
1.16
1.46
1.77
2.09

0.70
0.89
1.18
1.50
1.85
2.19

Note:subjecttochangewithoutnotice

APPENDIX B
EC FAN WIRING
500mm

Page 146

APPENDIX B
Page 1 of 3
01-10-2009

Note:subjecttochangewithoutnotice

Control of Single or Multiple EC Fans from


an External Controller or Potentiometer

EC WD 1

External Controller Connection Sequence


0-10V/PWM External Controller Output Signal
CONTROLS
Laptop with
RS232 to RS485
Interface for
Programming

External
Controller
4-20mA
Output

External
Controller
0-10V/PWM
Output

3 PHASE

10k ohm
Potentiometer

Alarm-out
dry contact
L1 3
L2
L3 Power
Supply
PE
KL2

PE

KL1

PE

PE

1st Fan
L3

L2

L1

COM

NO

OUT

GND

+10V
0-10V
PWM

+20V

4-20mA

GND

0-10V
PWM

RS B

10

RS A

RS B

RS A

11

NC

KL3

12

Delete when
4-20mA
Controller
is used.

L1
L2 3
L3 Power
Supply
PE
KL2

PE

KL1

PE

PE

2nd Fan
L3

L2

L1

COM

NO

OUT

GND

+10V
0-10V
PWM

+20V

4-20mA

GND

0-10V
PWM

RS B

10

RS A

RS B

RS A

11

NC

KL3

12

(Group 1, Fan 2)

(Group 1, Fan 3)

L1
L2 3
L3 Power
Supply
PE
PE

L1

L2

L3

Subsequent
Fans

PE

PE

NC

KL1

COM

NO

OUT

GND

RS B

+10V
0-10V
PWM

RS A

+20V

RS B

KL2

4-20mA

GND

10

0-10V
PWM

11

RS A

KL3

12

(Group 1, Fan _)

L1
L2
L3
PE
KL2

PE

KL1

Wiring for the 4-20mA Controller


The following KL3 terminals are paralleled: 3+7, 2+8, 9+11, 10+12.
Alarm Circuit
Diagram depicts a normally closed circuit which opens on failure of any fan.
NB. Contacts are held in position only when power is connected to motor.
Page 147

PE

Last Fan
PE

L3

L2

L1

COM

NO

OUT

+10V

0-10V
PWM
GND

+20V

GND
0-10V
PWM
4-20mA

RS B

10

RS A

RS B

RS A

11

NC

KL3

12

(Group 1, Fan _)

Control of Single or Multiple EC Fans from


an External Controller or Potentiometer
WARNING
Electricity is dangerous. Suitable electrical qualifications may be
required to carry out the wiring.
Fans may start unexpectedly during this process. Ensure suitable
safety precautions are in place before commencing.

General overview
Object is to control the speed of all fans in response to a signal
supplied from an external source.
(External Controller or Potentiometer)

EC WD 1

5. Switch on mains supply to the fans. (The LISA ebmBus cannot talk
to the fans without power)
6. Select Open Loop PWM Control via LISA and laptop.
7. Change fans address to Group 1, Fan 2 via LISA and laptop
(It is strongly recommended that no fan is addressed Group 1
Fan 1). This is to ensure that any future replacement fans,
which are supplied factory set as Group 1, Fan 1, can be easily
commissioned. It is not possible to talk, via the LISA program,
if any fans that have the same address.
8. Connect RS485 ebmBUS and program the 2nd fan:
8.1 Connect ebmBUS wiring from 1st to 2nd fan, (Terminals 11 &
12) check A and B polarity (This is critical).

The speed change is approximately linear from approximately


1 volt (10% PWM) to maximum speed 10 volts (100% PWM).
Below approximately 1 Volt the fan is stationary.

8.2 Set operation mode to Open Loop PWM control via LISA
and laptop.
8.3 Change fans address to Group1, Fan 3 via LISA and laptop.

All fans are to operate in unison.


The external controller is to supply the fans with a 0-10 Volt
control voltage or PWM signal (Connected to terminals 2 & 3 or
7 & 8). The control signal is paralleled to all fans so that all fans
receive the same control signal (Via terminals 2 & 3 or 7 & 8).
Alternatively a 4 to 20mA signal can be connected to terminal 6
and 8. Terminals 1 and 2 are fed to terminals 2 and 3 of
subsequent fan. [Parallel to all fans so that all fans receive the
same control signal (Via terminals 2 & 3 or 7 & 8).]

9. Connect RS485 ebmBUS and program 3rd fan:


9.1 Connect ebmBUS wiring to the 3rd fan.
9.2 Set operation mode to Open Loop PWM control via LISA
and laptop.
9.3 Change fans address to Group 1, Fan 4 via LISA and laptop.
10. Connect RS485 ebmBUS and program 4th fan:
10.1 Connect RS485 ebmBUS to the 4th fan.

All fans operate at the same speed.

10.2 Set operation mode to Open Loop PWM control via LISA
and laptop.

All fans are programmed for Open loop rpm (PWM) control.
(Via the LISA ebm bus)

10.3 Change fans address to Group 1, Fan 5 via LISA and laptop.

Programming and monitoring is via the RS485 ebmBUS.

11. Connect subsequent fans in the same vane, always ensuring a


Fan No. is not duplicated.

Connection of RS485 is via daisy chained twisted pair wires.

12. Connect external controller or potentiometer to the 1st fan.


13. Test run the unit.

Set mode of operation


Mode of operation is set via ebmBUS with PC/Laptop and RS232
to RS485 Interface-converter and LISA software.

Procedure
1. Switch off mains power supply.
2. Isolate the 1st fan from the control feed from the external
controller or potentiometer.

Commissioning of these fans requires previous training


in the application and use of the ebm-papst LISA
software program. Do not attempt to commission
the fans without previous training.
A laptop computer suitably programmed to operate LISA
via the RS232/RS485 ebmBus interface is required.

3. Connect ebmBUS-wiring to the 1st fan, check A and B polarity


(This is critical). Only the 1st fan must be wired to ebmBUS at this
time. Later the ebmBUS will be connected step by step to all fans.
4. Check mains supply, especially the earth.
2 Silverton Close,
Laverton North VIC 3026
Phone (03) 8325 6400
Fax (03) 8325 6464

www.ebmpapst.com.au
Page 148

APPENDIX C
EC FAN WIRING
800 mm Fans

Page 149

APPENDIX C
Page 1 of 4
01-10-2009

Note:subjecttochangewithoutnotice

APPENDIX C
EC FAN WIRING
800 mm Fans

Page 150

APPENDIX C
Page 2 of 4
01-10-2009

Note:subjecttochangewithoutnotice

APPENDIX C
EC FAN WIRING
800 mm Fans

Page 151

APPENDIX C
Page 3 of 4
01-10-2009

Note:subjecttochangewithoutnotice

APPENDIX C
EC FAN WIRING
800 mm Fans

Page 152

APPENDIX C
Page 4 of 4
01-10-2009

Note:subjecttochangewithoutnotice

APPENDIX D
Page 1 of 5
01-10-2009

HC HEAT - EXCHANGERS
APPENDIX D
HCV/ HVV Summary
HCModel
HCV-A
5012R
5013R
5014R
5022R
6312R
5023R
5024R
6313R
5032R
6314R
5033R
5042R
5034R
6322R
5043R
5052R
5044R
6323R
5062R
5053R
6324R
6332R
5054R
5072R
5063R
5082R
5064R
6333R
5073R
5092R
6342R
5074R
6334R
5083R
50102R
5084R
5093R
6352R
6343R
5094R
50103R
6344R
50104R
6362R
6353R
6354R
6363R
6364R

#Fans
1
1
1
2
1
2
2
1
3
1
3
4
3
2
4
5
4
2
6
5
2
3
5
7
6
8
6
3
7
9
4
7
3
8
10
8
9
5
4
9
10
4
10
6
5
5
6
6

TD
15K
21.9
27.0
29.7
43.3
48.4
53.2
58.4
61.6
64.9
69.8
79.8
86.1
87.5
97.2
106.4
107.6
116.7
123.6
129.1
133.0
140.3
145.8
146.1
150.7
159.9
172.2
175.1
185.4
186.2
193.7
194.4
204.2
210.4
211.2
215.2
233.4
237.6
243.0
247.2
260.8
264.0
280.6
289.4
291.6
309.1
350.7
370.9
420.9

kW/C
1.460
1.800
1.980
2.887
3.227
3.547
3.893
4.107
4.327
4.653
5.320
5.740
5.833
6.480
7.093
7.173
7.780
8.240
8.607
8.867
9.353
9.720
9.740
10.047
10.660
11.480
11.673
12.360
12.413
12.913
12.960
13.613
14.027
14.080
14.348
15.560
15.838
16.200
16.480
17.384
17.598
18.707
19.291
19.440
20.607
23.380
24.727
28.060

HCModel
HVV-A
5022R
5023R
5024R
5042R
6322R
5043R
5044R
6323R
5062R
6324R
5063R
5082R
5064R
6342R
5083R
50102R
5084R
6343R
50122R
50103R
6344R
50104R
6362R
50123R
50124R
6363R
6382R
6364R
6383R
6384R

Page 153

#Fans
2
2
2
4
2
4
4
2
6
2
6
8
6
4
8
10
8
4
12
10
4
10
6
12
12
6
8
6
8
8

TD
15K
43.0
52.8
57.6
85.8
97.2
105.5
115.1
122.9
128.7
139.1
158.2
171.5
172.7
194.5
211.0
214.4
230.3
245.7
257.3
263.7
278.3
287.9
291.7
316.5
345.4
368.6
389.0
417.4
491.5
556.5

kW/C
2.867
3.520
3.840
5.720
6.482
7.033
7.673
8.193
8.580
9.273
10.547
11.433
11.513
12.967
14.067
14.293
15.353
16.380
17.153
17.580
18.553
19.193
19.447
21.097
23.028
24.573
25.933
27.827
32.767
37.100

Note:subjecttochangewithoutnotice

APPENDIX D
Page 2 of 5
01-10-2009

HC HEAT - EXCHANGERS
APPENDIX D
HAV Summary

MultipleFans

OneFan

SortedByNumberofFans
HCModel
HAV
351A2R
351A3R
351A4R
401A2R
401A3R
401A4R
501A2R
501A3R
501A4R
352A2R
352A3R
352A4R
402A2R
353A2R
402A3R
353A3R
402A4R
353A4R
403A2R
403A3R
403A4R
502A2R
502A3R
502A4R
503A2R
503A3R
503A4R

#Fans
1
1
1
1
1
1
1
1
1
2
2
2
2
3
2
3
2
3
3
3
3
2
2
2
2
3
3

TD
15K
6.5
7.8
8.4
9.5
11.5
12.4
20.1
24.4
26.5
13.1
15.7
16.8
18.9
19.6
22.9
23.5
24.8
25.2
28.5
34.4
37.2
40.1
48.9
53.1
60.2
73.3
79.6

SortedByCapacity
HCModel
HAV
351A2R
351A3R
351A4R
401A2R
401A3R
401A4R
352A2R
352A3R
352A4R
402A2R
353A2R
501A2R
402A3R
353A3R
501A3R
402A4R
353A4R
501A4R
403A2R
403A3R
403A4R
502A2R
502A3R
502A4R
503A2R
503A3R
503A4R

kW/C
0.433
0.520
0.560
0.633
0.767
0.827
1.340
1.627
1.767
0.873
1.047
1.120
1.260
1.307
1.527
1.567
1.653
1.680
1.900
2.293
2.480
2.673
3.260
3.540
4.013
4.887
5.307

Page 154

#Fans
1
1
1
1
1
1
2
2
2
2
3
1
2
3
1
2
3
1
3
3
3
2
2
2
2
3
3

TD
15K
6.5
7.8
8.4
9.5
11.5
12.4
13.1
15.7
16.8
18.9
19.6
20.1
22.9
23.5
24.4
24.8
25.2
26.5
28.5
34.4
37.2
40.1
48.9
53.1
60.2
73.3
79.6

kW/C
0.433
0.520
0.560
0.633
0.767
0.827
0.873
1.047
1.120
1.260
1.307
1.340
1.527
1.567
1.627
1.653
1.680
1.767
1.900
2.293
2.480
2.673
3.260
3.540
4.013
4.887
5.307

Note:subjecttochangewithoutnotice

APPENDIX D
Page 3 of 5
01-10-2009

HC HEAT - EXCHANGERS
APPENDIX D
HCB Summary

OneFan

SortedByNumberofFans
HCModel #Fans
HCB
Fans
201A2R
1
201A3R
1
201A4R
1
251B2R
1
251B3R
1
251B4R
1
C301A2R
1
301A2R
1
C301A3R
1
C301A4R
1
301A3R
1
351A2R
1
301A4R
1
401A2R
1
1
351A3R
351A4R
1
401A3R
1
401A4R
1
501A2R
1
501A3R
1
501A4R
1
H501A4R
1
1
631C2R
631C3R
1
631C4R
1
631C6R
1

TD
15K
0.9
1.1
1.1
1.6
1.9
2.0
3.2
5.0
3.8
3.9
5.8
6.9
6.0
9.0
8.4
9.0
10.8
11.6
17.3
20.8
22.3
25.9
45.5
57.2
64.6
70.0

kW/C
0.061
0.071
0.076
0.107
0.127
0.133
0.211
0.332
0.253
0.257
0.387
0.460
0.401
0.600
0.560
0.600
0.720
0.773
1.153
1.387
1.487
1.727
3.033
3.812
4.303
4.664

SortedByCapacity
HCModel #Fans
HCB
Fans
201A2R
1
201A3R
1
201A4R
1
251B2R
1
251B3R
1
251B4R
1
C301A2R
1
252B2R
2
C301A3R
1
1
C301A4R
252B3R
2
252B4R
2
301A2R
1
301A3R
1
301A4R
1
351A2R
1
C302A2R
2
C302A3R
2
351A3R
1
C302A4R
2
351A4R
1
401A2R
1
302A2R
2
401A3R
1
302A3R
2
401A4R
1

Page 155

TD
15K
0.9
1.1
1.1
1.6
1.9
2.0
3.2
3.5
3.8
3.9
4.0
4.1
5.0
5.8
6.0
6.9
7.5
8.4
8.4
8.7
9.0
9.0
10.3
10.8
11.6
11.6

kW/C
0.061
0.071
0.076
0.107
0.127
0.133
0.211
0.233
0.253
0.257
0.267
0.273
0.332
0.387
0.401
0.460
0.501
0.559
0.560
0.577
0.600
0.600
0.684
0.720
0.773
0.773

Note:subjecttochangewithoutnotice

APPENDIX D
Page 4 of 5
01-10-2009

HC HEAT - EXCHANGERS
APPENDIX D
HCB Summary

MultipleFans

SortedByNumberofFans
HCModel #Fans
TD
HAV
15K
252B2R
2
3.5
252B3R
2
4.0
252B4R
2
4.1
C302A2R
2
7.5
C302A3R
2
8.4
C302A4R
2
8.7
302A2R
2
10.3
302A3R
2
11.6
302A4R
2
12.0
352A2R
2
13.9
2
16.7
352A3R
402A2R
2
17.9
352A4R
2
18.0
353A2R
3
20.8
2
21.6
402A3R
402A4R
2
23.3
353A3R
3
25.1
403A2R
3
26.9
353A4R
3
27.0
502A2R
2
34.7
403A3R
3
32.3
403A4R
3
34.9
2
41.6
502A3R
502A4R
2
44.6
H502A4R
2
51.8
503A2R
2
52.1
503A3R
3
62.3
503A4R
3
66.8
H503A4R
3
77.6
632C2R
2
91.0
2
114.4
632C3R
632C4R
2
129.1
633C2R
3
136.5
632C6R
2
139.9
633C3R
3
171.5
633C4R
3
193.6
633C6R
3
209.9

kW/C
0.233
0.267
0.273
0.501
0.559
0.577
0.684
0.773
0.799
0.927
1.113
1.193
1.200
1.387
1.440
1.553
1.673
1.793
1.800
2.313
2.153
2.327
2.773
2.973
3.450
3.473
4.153
4.453
5.175
6.066
7.623
8.607
9.099
9.329
11.435
12.909
13.992

SortedByCapacity
HCModel #Fans
TD
HAV
15K
302A4R
2
12.0
352A2R
2
13.9
352A3R
2
16.7
501A2R
1
17.3
402A2R
2
17.9
352A4R
2
18.0
353A2R
3
20.8
501A3R
1
20.8
402A3R
2
21.6
501A4R
1
22.3
402A4R
2
23.3
353A3R
3
25.1
H501A4R
1
25.9
403A2R
3
26.9
353A4R
3
27.0
403A3R
3
32.3
502A2R
2
34.7
403A4R
3
34.9
502A3R
2
41.6
502A4R
2
44.6
631C2R
1
45.5
H502A4R
2
51.8
503A2R
2
52.1
631C3R
1
57.2
503A3R
3
62.3
631C4R
1
64.6
503A4R
3
66.8
631C6R
1
70.0
H503A4R
3
77.6
632C2R
2
91.0
632C3R
2
114.4
632C4R
2
129.1
633C2R
3
136.5
632C6R
2
139.9
633C3R
3
171.5
633C4R
3
193.6
633C6R
3
209.9

Page 156

kW/C
0.799
0.927
1.113
1.153
1.193
1.200
1.387
1.387
1.440
1.487
1.553
1.673
1.727
1.793
1.800
2.153
2.313
2.327
2.773
2.973
3.033
3.450
3.473
3.812
4.153
4.303
4.453
4.664
5.175
6.066
7.623
8.607
9.099
9.329
11.435
12.909
13.992

Note:subjecttochangewithoutnotice

HC HEAT - EXCHANGERS

APPENDIX D
Page 5 of 5
01-10-2009

APPENDIX D
Evaporators Summary
HCModel
HSR/HRR/HPR/HMR

#Fans
500/630

HSR5014Rx6F
HSR5022Rx6F
HRR5014Rx6F
HSR5016Rx6F
HPR5014Rx6F
HRR5016Rx6F
HSR5023Rx6F
HPR5016Rx6F
HSR5024Rx6F
HRR5024Rx6F
HSR5026Rx6F
HMR6314Rx6F
HPR5024Rx6F
HSR5034Rx6F
HRR5026Rx6F
HPR5026Rx6F
HMR6316Rx6F
HRR5034Rx6F
HSR5036Rx6F
HPR5034Rx6F
HRR5036Rx6F
HPR5036Rx6F
HMR6324Rx6F
HMR6326Rx6F
HMR6334Rx6F
HMR6336Rx6F

1
2
1
1
1
1
2
1
2
2
2
1
2
3
2
2
1
3
3
3
3
3
2
2
3
3

Page 157

RatingCondition
5CEvap/6KTD
6F
4F
8.3
6.490
9.1
7.410
9.8
7.780
10.1
8.440
11.2
8.940
12.0
10.080
12.7
10.500
13.6
11.540
16.7
13.000
19.8
15.630
20.3
16.880
22.3
17.520
22.5
17.980
23.8
18.580
24.1
20.260
27.4
23.200
28.0
23.180
28.4
22.360
29.0
24.110
32.3
25.790
34.6
28.990
39.4
33.350
41.2
32.050
52.0
42.600
67.6
53.210
85.0
70.230

Note:subjecttochangewithoutnotice