Академический Документы
Профессиональный Документы
Культура Документы
Power Transformers
Bob C. Degeneff
Department of Computer, Electrical,
and Systems Engineering,
Rensselaer Polytechnic Institute,
Troy, New York, USA
3.1
3.2
3.3
Introduction .......................................................................................
Transformers: Description and Use .........................................................
Transformers: Theory and Principle ........................................................
715
715
715
3.4
717
3.5
3.6
3.7
717
718
719
3.8
3.1 Introduction
This chapter presents a very brief overview of the characteristics of a transformer. The basic theory and principles of application are introduced. A simple lumped-parameter equivalent
circuit is presented. Magnetizing current and leakage reactance
a r e introduced, and cooling methods are presented and compared. In addition, transformer applications are presented and
discussed. The basic core and winding arrangements are also
presented. Finally, transformer sound, overcurrent, and losses/
efficiency are presented, and acceptance tests are outlined.
720
720
Bob C Degeneff
716
hN1 = hN2.
IH=I1
E2
N~ N2'
where E1 and E2 are the primary and secondary voltages and
where N1 and N2 are the primary and secondary turns. If a
load is applied to the secondary of the transformer and the
exciting current is small with respect to the load current, the
currents in the primary and secondary are related by:
~
Im ~
jll
~ ILR2 "JILXr2
I1
R 1+JXf2
XPl
3 Power Transformers
3.3.4 M a g n e t i z i n g I n r u s h
When a transformer is energized, the amount of current that
flows will depend on the amount of residual flux that resides in
the core. This residual is typically between 50 and 90% of the
peak operating flux. In extreme cases, the peak flux in the core
upon energization will be greater than twice the peak design
limit, and, as such, the inrush current can be 3 to 40 times the
load current (Grigsby, 2001). The actual inrush experienced
depends on the point on the voltage wave during energization,
the residual flux, air core inductance of the winding, and losses
of the transformer and system.
717
circuits. These units can be of the step-down or step-up
configuration. A step-down is designed to decrease the incoming voltage to a lower level more suitable for distribution.
Power transformers of this type are frequently located in substations or at large industrial consumer locations. Transformers that perform this reduction in voltage from a primary
feeder to the utilization level are referred to as distribution
transformers. A step-up transformer takes the input voltage
and raises it to a higher lever suitable for transmission. American National Standards Institute (ANSI) standards require the
nameplate to indicate the transformer is suitable for this type
of operation. A generator step-up transformer is an example of
this type of power transformer. The majority of these type
power transformers are three-phase units.
It is often more economical to transfer energy between two
circuits of similar voltage using an autotransformer rather than
a conventional two-winding transformer. Figure 3.3 provides
an illustration of this arrangement. Most autotransformers are
Y-connected with a delta tertiary (used to provide a path for
third harmonic currents required for excitation). The autotransformer does not afford electrical separation between the
two circuits but is a more economical transformer on a $/kVA
basis. In addition, the autotransformer is not inherently selfprotecting and typically will be subjected to higher short
circuit currents and forces than a corresponding two-winding
transformer. The autotransformer can also be used to increase
or decrease voltage in a system. By using suitable on-load tapchanging equipment, it is possible to regulate the voltage of a
system within desired limits. An autotransformer used in this
manner is referred to as a voltage-regulating transformer. Typically, the range of the regulation is 4-10% of the system voltage
in 5/8% steps.
It may be desirable to create an electrical connection
between systems that have different phase angles. These
systems may also be at different voltages. The function of
the phase-angle regulator is to provide this interconnection
between systems possessing different phase angles and voltages. Figure 3.4 illustrates one method to accomplish this
transformation.
In power system applications, there are two types of instrument transformers: current transformers and voltage trans-
/H=/1
+ T
+I
-L
-o
-O
Bob C. Degeneff
718
60
\.
A/
HI
H2
,, Primary
current
x2
Characteristics of the core-form transformer are a long magnetic path and a shorter mean length of turn. Commonly used
core-form magnetic circuits are single-phase transformers
with a two-legged magnetic path with turns wound around
each leg, a three-legged magnetic path with the center leg
wound with conductor, or a four-legged magnetic path with
the two interior legs wound with conductors (Bean et aL, 1959;
Massachusetts Institute of Technology, 1943). Three-phase
core-form designs are generally three-legged magnetic cores
with all three legs possessing windings or a five-legged core
arrangement with the three center legs possessing windings.
The simplest winding arrangement has the low-voltage
winding nearest the core and the high-voltage winding on
top of the low. Normally, in the core form construction, the
winding system is constructed from helical, layer, or disk-type
windings (Massachusetts Institute of Technology, 1943; Franklin, 1998). The disk-type winding itself can be constructed on
several different winding configurations (i.e., continuous,
interleaved, and internally shielded), all of which affect the
transient voltage response and this insulation design. Often
the design requirements, such as impedance or shipping size
limitations, call for a core and winding arrangement that is a
more complex arrangement (e.g., interleaving high- and lowvoltage windings, interwound taps, and entry and exit points
other than the top or bottom of the coil). All of these variations have an effect on the transformer's transient voltage
Xl
Primary
voltage
Secondary
current
t42
(A) Current Transformer
x2
Power Transformers
719
Windings
3.7.2 S o u n d
3.7.30vercurrent
A transformer may at some point be subjected to current in
excess of its rated load current. Current up to approximately
2% of the rated load current can be anticipated from overload
conditions on the system. These currents may last only a few
minutes or several hours. Faults on the system will subject the
transformer to peak overcurrents that may be up to 40 times
the rated load current. These currents may produce either
mechanical or thermal damage to the transformer. Mechanical
forces are proportional to the square of the current and manifest themselves in a number of different failure mechanisms.
These failure mechanisms include loosening of coils, conductor tipping, radial and axial conductor buckling, winding
deformation, core deformation, and telescoping of windings.
Bob C Degeneff
720
The variety of transient voltages a transformer may experience in its normal useful lifetime are virtually unlimited. It is
impractical to test each transformer for every conceivable
combination of transient voltage. However, the electrical industry has found that it is possible, in most instances, to assess
the integrity of the transformer's insulation systems to withstand transient voltages with the application of a few specific
aperiodic voltage waveforms (Massachusetts Institute of Technology, 1943), illustrating the full, chopped, and switching
surge waveforms. Each of these tests is designed to test the
insulation structure for a different transient condition. The
purpose of applying this variety of tests is to substantiate
adequate performance of the total insulation system for all
the various transient voltages a transformer may see in service.
References
Bean, R.L., Crackan, N., Moore, H.R., and Wentz, E. (1959). Transformers for the electricpower industry. New York: McGraw-Hill.
Blume, L.F., Boyajian, A., Camilli, G., Lennox, T.C., Minneci, S., and
Montsinger, V.M. (1951). Transformer Engineering. (2d ed.). New
York: John Wiley & Sons.
Fink, D.G., and Beat),, H.W. (1987). Standard handbook for electrical
engineers. (12th ed.). New York: McGraw-Hill.
Grigsby, L.L. (2001). The Electric Power Engineering Handbook. CRC
Press.
Heathcote, M., Franklin, A., Franklin, D. (1998). J&P Transformer
Book. London: Butterworth-Heinemann.
IEEE guide and standards for distribution, power, and regulating transformers. New York: IEEE Press, 1998.
Massachusetts Institute of Technology, Department of Electrical
Engineering (1943). Magnetic circuits and transformers. New York:
John Wiley & Sons.